High-Efficiency Plumbing Fixture Direct Install Water Savings Analysis
|
|
|
- Maurice Richardson
- 10 years ago
- Views:
Transcription
1 High-Efficiency Plumbing Fixture Direct Install Water Savings Analysis for Santa Clara Valley Water District 5750 Almaden Expressway San Jose, California and California Urban Water Conservation Council 716 Tenth Street, Suite 200 Sacramento, California October 2012 By John Koeller Koeller and Company Yorba Linda, California
2 TABLE OF CONTENTS INTRODUCTION Page 2 PROGRAM BACKGROUND 3 Fixture Replacements 3 Participating Properties 4 Data Collection 4 STUDY RESULTS 6 Methodology 6 Findings 6 -Overall water savings 6 -Multi-family water savings 6 -Non-residential water savings 7 -Water savings by toilet replaced 7 SUMMARY AND CONCLUSIONS 9 TABLES AND FIGURES Table 1 Toilet fixture replacements by community 3 Table 2 Non-residential toilet fixture replacements 4 Table 3 Properties participating in the program 4 Table 4 Savings from all toilet fixture replacements 6 Table 5 Residential properties, toilet replacement, and water savings 6 Table 6 Water savings by non-residential category 7 Table 7 Water savings by replaced toilet 7 Table 8 Water savings summary 9 Figure 1 HET installation months 5 Koeller & Company 1 September 2012
3 INTRODUCTION The purpose of this study was to evaluate and estimate water savings that accrued from the replacement of slightly less than 5,000 aging high-volume toilets 1 in 80 multi-family residential and commercial properties within the service area of the Santa Clara Valley Water District (SCVWD). The replacement toilets chosen for the project were all High-Efficiency Toilets 2 (HETs). The SCVWD engaged the services of an experienced retrofit contractor to perform the replacements; licensed plumbers were used to install all toilet fixtures. The replacements that are the subject of this study all took place during a period of approximately four years from July 2007 to May Except for a few instances noted later, all replacement installations involved only the toilet. SCVWD reports that other plumbing or appliance items within the subject properties were not replaced during the period of savings analysis. The program was implemented in Santa Clara County. Water use data for the study was provided by the Cities of Morgan Hill, Mountain View, Palo Alto and Sunnyvale. A very special thank you goes to Ms. Karen Koppett of the SCVWD. Ms. Koppett was instrumental in furnishing information and setting the direction of the study. Many thanks also go to the Cities of Morgan Hill, Mountain View, Palo Alto and Sunnyvale, where persons associated with the water billing departments spent a large number of hours retrieving billing data for the 80 properties covered by the study. This was a significant task and their work yielded results that were essential to the study conclusions. 1 Replaced toilets consisted entirely of fixtures rated at 3.5 and 5.0 gallons per flush-gpf (13 and 19 liters per flush- Lpf) 2 High-efficiency toilet (HET) fixtures are defined as those with an effective flush volume 20 percent less than the Federal maximum of 1.6 gallons (6.0 liters) per flush. As such, all HETs flush (on average) at 1.28 gallons (4.8 liters) or less. Koeller & Company 2 September 2012
4 PROGRAM BACKGROUND Fixture Replacements This analysis focused on the replacement of 4,954 aging toilet fixtures 3 with High-Efficiency Toilet (HET) 4 models, divided as follows: Table 1. Toilet fixture replacements by community The program replaced aging 3.5- and 5.0-gallons per flush (gpf) fixtures with HETs 5, most of which were gravity-fed tank-type fixtures. The gravity-fed fixture used was the Caroma Sydney Smart 305 dual-flush with elongated bowl, flushing at 1.3 gpf on the full flush and 0.9 gpf on the reduced flush 6. This fixture model is certified to the WaterSense specification and carries the WaterSense label 7. The few flushometer valve-bowl combinations replaced used the Zurn EcoVantage 1.28 gpf elongated bowl 8. Replacement of 1.6-gpf fixtures was not a part of the SCVWD s replacement program. Table 2 displays the distribution of the 1,711 non-residential replacements by sector. 3 The difference between the total number of fixtures replaced and the 4,954 is due largely to the exclusion from the analysis of: (a) those toilet replacements that were accompanied by concurrent high-efficiency urinal retrofits, (b) replacement installations with incomplete water consumption data either before or after the physical replacement took place, and (c) those generating anomalous water use data. 4 The first HET fixtures were introduced to the North American marketplace in Since that date, over 1,300 different HET models from dozens of manufacturers exist in the U.S. marketplace. The U.S. EPA s WaterSense program endorses HETs and labels those models that perform to a high set of standards. The gravity-fed HET model installed in most locations is WaterSense labeled (see footnote 6 below). 5 A total of gpf toilet fixtures were replaced in multi-family buildings and included within this evaluation, all of which were located in Sunnyvale. The remaining 4,123 fixtures, all but 5 of which flushed at 3.5-gpf, were scattered throughout the four communities. 6 Caroma model numbers bowl and tank; MaP score of 800 grams Zurn model Z5615 bowl; MaP score of 800 grams when matched with a 1.28 gpf flushometer valve Koeller & Company 3 September 2012
5 Table 2. Non-residential toilet fixture replacements Schedule of Replacements *-Hospitality includes lodging establishments and eating places Replacement of the 4,954 fixtures was spread over a period of four (4) years, beginning in July 2007 and concluding in May of Figure 1 shows the spread of installations by category over that period of time. Participating Properties A total of 80 properties from the four communities participated in the replacement program and are benefitting from it. These are divided as follows: Table 3. Properties participating in the program Data Collection For the purpose of assessing water use reductions achieved through the program, the SCVWD collaborated with the four retail water service providers to secure water meter readings for no less than one year following fixture installation. These meter readings were then compared to meter reads from periods prior to installation of from 12 to 36 months. In addition to metered water consumption and property location, each data set for an individual participant (property) contained information on type of property, the number of fixtures replaced within the property, the flush volume of the replaced toilets, and the date of replacement. Information on population within the residential properties, occupancy rate of the hotels, and employment in the non-residential buildings in which toilets were replaced was not obtained and was not a consideration in the data collection or analyses. Koeller & Company 4 September 2012
6 !"#$%&'(%)*+,## -.)/$%&'(%)*+,## OPPS OPPR OPPQ OP;P OP;;! " # $ % &! ' ( " (!! " # $ % &! ' ( " (!! " # $ % &! ' ( " (!! " # $ % &! ' ( " (! =+26/-34/-B #1.++4 C7-3/4)D)27:E/172 $F17)D)G7H/134 IBG*=734-.)J49K*#63 (L8MN3: $-.7: )*)(+,-.)/,)0./1.)/,2-3442)-++5)64317 '/89:7);<)=>?)@,2-3443A+,)(+,-.2
7 Methodology STUDY RESULTS Metered water consumption data furnished by the retail water utilities (through SCVWD) were used to assess demand reductions, if any, resulting from toilet fixture replacements. Submetering or other fixture-specific monitoring of uses within homes and businesses was not performed. All results relied entirely upon data from utility meters and reports from the program contractor. To reduce the effect of seasonal variations in climate (and, hence, water demand variances) from year to year, water demand during the four high-use summer months was excluded. Some of the participating water utilities are programmed for bimonthly billing of their customers, others bill monthly. As a result, in some cases, two billing periods were excluded while, in other cases, four billing periods were excluded. Except for one property, all of the toilet replacements were made without other water efficiency improvements being made at the same time. That one property, with 468 replacement toilets, was therefore excluded from all analyses, since it was not possible to disaggregate water savings for the toilets alone. Findings Water savings achieved through toilet fixture replacement were assessed for several different categories of end-user as well as for the flush volume of the old and new toilets Overall water savings The replacement of toilet fixtures resulted in the following: Table 4. Savings from all toilet fixture replacements 9 Multi-family residential water savings For residential, the distribution of toilet replacements and water savings were as follows: Table 5. Residential properties, toilet replacement, and water savings 9 Represents a mixture of aging toilets replaced: 3.5-gpf and 5.0-gpf. Replacement toilets all qualified as HETs. Koeller & Company 6 September 2012
8 Non-residential water savings Non-residential installations fell into seven general categories, most participating properties being in the hospitality and office/medical classifications as noted in Table 6. Table 6. Water savings by non-residential category Water savings by toilet replaced (3.5 gallons per flush vs. 5.0 gallons per flush) The program contractor recorded the flush volume of the aging toilets replaced at each participating property, indicating whether the replaced fixtures had been functioning at 3.5-gpf or 5.0-gpf. Assuming that the contractor correctly assessed the flush volumes, Table 7 shows the savings associated with each category of replacement. Table 7. Water savings by replaced toilet For multi-family residential installations, the data in Table 7 shows savings from replacing 3.5- gpf toilets slightly higher than those resulting from the replacement of 5.0-gpf fixtures. Specific data on the age or condition of the properties and the replaced fixtures is not available, nor was the resident population of the 44 residential properties. That is, the resident density of these properties may be significantly different between those replacing 3.5-gpf toilets and those very few properties with 5.0-gpf toilets. Because of these factors, we cannot estimate and compare the daily resident usage of the 5.0-gpf fixtures with the 3.5-gpf fixtures. Koeller & Company 7 September 2012
9 Another causal factor is the leakage of aging toilet fixtures, which usually played a large role in water savings figures for toilet fixtures. It is common in the older fixtures that leakage can be significant 10, particularly in multi-family housing where the tenant is not responsible for maintaining the toilet fixture. When these leaking fixtures are replaced with new models, leakage is eliminated and water is saved (at least for a period of time). This factor, when combined with reduced flush volumes, can yield extraordinary water savings. The magnitude of those savings is largely influenced by the condition of those older fixtures, which, in turn, may be determined by the level of maintenance on the fixtures performed over their lifetime. In cases with attentive management and fixture maintenance, leakage is usually not significant. On the other hand, a lack of proper maintenance can result in ongoing leakage that is eliminated when the aging fixture is replaced with a new HET. In this case, we have no data on the physical condition of either the 3.5-gpf or the 5.0-gpf toilets removed and replaced. Given the large number of water consumption variables existing in aging toilets installed in multi-family residential (physical condition of the aging toilet and occupancy of the dwellings), it is not wise to focus only on the rated flush volume changes when estimating water use reductions 11. Rather, an overall number for all aging toilet replacements is more appropriate. Therefore, the combined daily water savings rate of 38.0 gallons per toilet (Table 5) is recommended as a planning number for the replacement of multi-family residential fixtures dating from the 1980s and previous. 10 Leakage at gravity-fed toilets usually occurs for one or both of the following reasons: (a) degraded or incorrect flush valve seals (flappers) and (b) faulty fill valves (ballcock float arm type) that release water into the overflow tube as a result of system water pressure changes. In the latter case, this type of leakage can be eliminated by re-setting the water line in the tank. 11 In this specific case, the 1.5 gpf difference between a 3.5 gpf and a 5.0 gpf toilet (which are very unlikely to be flushing at those rates) may not be reflective of savings potential. In addition, to estimate a savings based solely upon the delta between a 5.0 gpf toilet and a 1.28 gpf HET, for example, does not necessarily result in a reliable real world number. Koeller & Company 8 September 2012
10 SUMMARY AND CONCLUSIONS In the properties covered in this analysis, the SCVWD s program targeted only toilet fixture replacements. The primary goal of the analysis was to derive daily water savings per toilet fixture based upon a total of 4,954 such replacements 12. While this represents an adequate sample from which to draw some general water savings metrics to be applied elsewhere, the parsing of this number into smaller and smaller increments for more sector-specific metrics leads to unreliable data. However, the resulting water savings metrics for these sectors is still generally useful for rough projections of likely water use reductions when conservation programs are being developed or evaluated. Key water savings findings from the study were as follows: Table 8. Water savings summary 12 As noted in the report, however, other installations were removed from the analysis due to missing or inconsistent data. Koeller & Company 9 September 2012
Toilet Flapper Study: Final Report
Toilet Flapper Study: Final Report Prepared for The California Urban Water Conservation Council 455 Capitol Mall, Suite 703 Sacramento, California 95814 (916) 552-5885 December 15, 2004 By Koeller and
Water/Sewer Billing, Metering, and Water Efficiency. May 3, 2011
Water/Sewer Billing, Metering, and Water Efficiency May 3, 2011 Two Types of Water/Sewer Billing Flat Rate ( Frontage ) A series of set fees based on the size of a building and the number of water-using
Introduction. Kitchens
Chapter 10 Water Fixtures and Conservation Introduction Responsible use of fresh water means WATER AT-A-GLANCE ensuring that all water-consuming fixtures Introduction in public areas are operating properly,
THE PEOPLE OF THE CITY OF LOS ANGELES DO ORDAIN AS FOLLOWS: Section 1. Article V of Chapter XII of the Los Angeles Municipal Code is added to read:
ORDINANCE NO. 1,;...8_U_8_2_2_ An ordinance adding Article V to Chapter XII, and amending Section 94.103.1.2.9, of the Los Angeles Municipal Code establishing water efficiency requirements for new development
Plumbing Fixture Replacement (SB 407) for Existing Single-Family Residential, Multifamily Residential and Commercial Buildings
Community Development Department Building Division 39550 Liberty Street, PO Box 5006, CA 94537-5006 510-494-4460 ph www.fremont.gov Plumbing Fixture Replacement (SB 407) for Existing Single-Family Residential,
7.1 Conservation Programs for Industrial, Commercial, and Institutional Accounts
Industrial, Commercial, and Institutional Accounts Applicability This BMP is intended for all Municipal Water User Groups ( utility ) which serve industrial, commercial, and institutional ( ICI ) customers.
AB 715 COVERS: Toilets and Urinals CHAPTERED AS: Health and Safety Code 17921.3
Interactions Among AB 715 (Laird 2007), SB 407 (Padilla 2009), and CALGreen Building Standards Assessing for Provisions of Water Use Efficiency Regulations Existing law provides for the following: requires
The Impacts of High Efficiency Toilets on Plumbing Drainlines and Sewers
The Impacts of High Efficiency Toilets on Plumbing Drainlines and Sewers July 1, 2011 This article addresses key questions and concerns as well as misperceptions about the impacts of reduced water use
Section 5.900 - Emergency Water Shortage Regulations and Staged Water Use Reduction Plan Section 5.905 - Scope and Purpose
Section 5.900 - Emergency Water Shortage Regulations and Staged Water Use Reduction Plan Section 5.900 of Chapter 5 of the District Code shall be known and cited as the Heritage Ranch Community Services
Leak Detector Guide. Your Guide to Home Water Conservation
E v e r y D r o p C o u n t s! Leak Detector Guide Your Guide to Home Water Conservation M i a m i - D a d e W a t e r a n d S e w e r D e p a r t m e n t A High Bill Usually Means a Leak Did you know
San Francisco Public Utilities Commission
San Francisco Public Utilities Commission Wholesale Customer Water Conservation Potential Technical Report Prepared by: URS Corporation Oakland, California Maddaus Water Management Alamo, California Jordan
Georgia State Amendments to the International Plumbing Code
Georgia State Amendments to the International Plumbing Code (2006 Edition) Georgia Department of Community Affairs Local Government Assistance Division 60 Executive Park South, N.E. Atlanta, Georgia 30329-2231
WaterSense or Energy Star. Tank type toilets: WaterSense = 1.28 gpf (4.8L) with at least 350 gram waste. 1.5 gpm maximum & 0.8 gpm minimum at 20 psi
National Efficiency Standards and s for and Water Using Toilets Lavatory (Bathroom) Faucets 2.2 gpm at 60 psi 2 Kitchen Faucets Showerheads Clothes Washers, Energy Independence and Security Act of 2007
Green Plumbing and Mechanical Code Supplement
Green Plumbing and Mechanical Code Supplement Doug Kirk IAPMO Director of Green Plumbing Curriculum [email protected] 1 IAPMO Green Uniform Codes - developed with critical eye on sustainability 2007-
Calculation of Potential Water Savings in
1 Appendix D Single-Family Homes Calculation of Potential Water Savings in Current Single-Family Residential Water Use In 2004, the Southern Nevada Water Authority (SNWA) delivered more than 198 thousand
A Do-It-Yourself Home Water Audit
A Do-It-Yourself Home Water Audit This page is left blank intentionally. Please use the double-sided printer setting when printing. Your new Home Water Savings Kit can help you conduct a do-it-yourself
Guideline for Implementation of California Civil Code Sections 1101.1 1101.8 Water-Conserving Plumbing Fixtures
Guideline for Implementation of California Civil Code Sections 1101.1 1101.8 Water-Conserving Plumbing Fixtures Information Bulletin No. IB-021 Effective: January 1, 2014 By: Chief Building Official For
North San Jose Neighborhoods Planning Taskforce
North San Jose Neighborhoods Planning Taskforce Key Topics Water Supply Flooding Related Topics Storm Water Storm Sewer Sanitary Sewer Water Conservation Treatment Plant Water Background Responsible Agencies
Codes and Standards Research Report. California s Residential Indoor Water Use. 2 nd Edition (Revised May 8, 2015)
Codes and Standards Research Report California s Residential Indoor Water Use 2 nd Edition (Revised May 8, 2015) Codes and Standards Research Report California s Residential Indoor Water Use 2 nd Edition
How to Locate and Stop Costly Water Leaks
Chesterfield County, Virginia How to Locate and Stop Costly Water Leaks Water leaks are a waste of a valuable resource: pure, clean drinking water. An undetected leak may result in a costly utility bill.
Codes and Standards Research Report. California s Residential Indoor Water Use
Codes and Standards Research Report California s Residential Indoor Water Use Codes and Standards Research Report California s Residential Indoor Water Use FUNDED THROUGH A GRANT FROM: 1215 K Street, Ste.
Did you know a utility provider s sewer rates are typically 3-5 times higher than their water rates?
Why am I being billed? Utility costs are rapidly increasing. The owner of your community has chosen to have the residents pay for their utilities separately, which in the past were built into rent. Billing
BUILDING CODE MANUAL COUNTY OF LOS ANGELES DEPARTMENT OF PUBLIC WORKS BUILDING AND SAFETY DIVISION Based on the 2014 LACBC
BUILDING CODE MANUAL COUNTY OF LOS ANGELES DEPARTMENT OF PUBLIC WORKS BUILDING AND SAFETY DIVISION Based on the 2014 LACBC #145 106.4 Article 3 04-01-14 Page 1 of 7 PLUMBING FIXTURE REPLACEMENT ISSUE:
Estimated Water Savings
Easy Plumbing Fixes Estimated Water Savings A family of 4 could save: 200 gpd by fixing toilet leaks 20 gpd by fixing faucet leaks 100 gpd by installing low-flow showerheads 40 gpd using faucet aerators
INSTALLATION OF WATER-CONSERVING PLUMBING FIXTURES SB 407 California Civil Code Section 1101.1 2013 Green Building Standards Code
INSTALLATION OF WATER-CONSERVING PLUMBING FIXTURES SB 407 California Civil Code Section 1101.1 2013 Green Building Standards Code In 2009, the California State Legislature passed Senate Bill SB 407 which
Effective Date: October 2015 Void After: October 2016. Product: Water Closets with Dual Flush Feature File No. 5319
IAPMO Research and Testing, Inc. is a product certification body which tests and inspects samples taken from the supplier's stock or from the market or a combination of both to verify compliance to the
City of Modesto WATER-USE HOME SURVEY
City of Modesto WATER-USE HOME SURVEY Water is a precious natural resource important to our health, community and the quality of life. Because water is precious, it is essential to conserve and use water
Broward Water Partnership High-Efficiency Toilet (HET) Rebate Program
Broward Water Partnership High-Efficiency Toilet (HET) Rebate Program Rebate applications will only be accepted from qualifying residents, property managers and commercial businesses within the Broward
WATER & SEWER SERVICES
WATER/SEWER ENGINEERING SECTION PHONE (703) 228-3677 WATER & SEWER SERVICES INFORMATION & APPLICATION PACKAGE REVISED MAY 2014 1 MAY 2014 Dear Customer: Thank you for taking the time to read this information
Water Conservation and the State s New Green Building Code for Residential Construction
Water Conservation and the State s New Green Building Code for Residential Construction Silver Sponsors Media Sponsors Certified Sponsors Solano County Water Agency Zone 7 Water Agency Founding Partners
Effective Date: March 2015 -Rev. 5/29/2015- Void After: March 2016. Product: Ceramic Plumbing Fixtures File No. 3360
IAPMO Research and Testing, Inc. is a product certification body which tests and inspects samples taken from the supplier's stock or from the market or a combination of both to verify compliance to the
A High Bill Usually Means a Leak
A High Bill Usually Means a Leak Did you know that approximately 50 percent of all households have some kind of plumbing leak? Most of these leaks are due to worn out washers, flappers or faulty tank valves,
Metering of Individual Units
Metering of Irrigation Use and Individual Dwelling Units at Apartments, Condominiums, Townhouses, Mobile-home Parks, and Commercial Facilities From a water management perspective it makes sense to meter
Monitoring Water Use
GIIRS Emerging Market Assessment Resource Guide: What s in this Guide? I. Definition: Water Use II. Why Monitor and Record Water Use? III. How to Monitor and Record Water Use? IV. Water Conservation V.
LEAK DETECTION GUIDE
LEAK DETECTION GUIDE Your Guide to Home Water Conservation CITY OF BELLEVUE UTILITIES WATER & SEWER DEPARTMENTS LEAK DETECTION GUIDE PAGE: 1 WHERE TO START If you receive a high water bill, or think there
RESIDENTIAL WATER LEAK DETECTION GUIDE
RESIDENTIAL WATER LEAK DETECTION GUIDE WATER - USE IT DON T WASTE IT PROTECT YOUR HOME FROM DAMAGING LEAKS CONTENTS Understanding Your Water Bill 4 Understanding Your Water Meter 6 10 Common Indoor Water
Water Meter Basics leak detection and water consumption calculations
Water Meter Basics leak detection and water consumption calculations Calculating Water Use Have you ever received your water bill and thought to yourself, How could I have used that much water in two months?
AMOUNT New Account Deposit $50.00 Service Delinquent $10.00 Delinquency Notification $15.00 NSF Check processing $20.00
RIVERGROVE WATER DISTRICT FREQUENTLY ASKED QUESTIONS 1. WHERE DOES THE WATER COME FROM? Rivergrove Water District s water source is groundwater and comes from wells that we have drilled into the Columbia
SEATTLE HOME WATER CONSERVATION STUDY
SEATTLE HOME WATER CONSERVATION STUDY THE IMPACTS OF HIGH EFFICIENCY PLUMBING FIXTURE RETROFITS IN SINGLE-FAMILY HOMES December 2000 Submitted to: Seattle Public Utilities and The United States Environmental
LOS ANGELES DEPARTMENT OF WATER AND POWER. Requirements for Ultra-Low-Flush Toilets. Supplementary Purchase Specification to ASME A112.19.
LOS ANGELES DEPARTMENT OF WATER AND POWER Requirements for Ultra-Low-Flush Toilets Supplementary Purchase Specification to ASME A112.19.2-2003 Effective: July 1, 2000 Revised: October 1, 2004 The following
RESIDENTIAL WATER SURVEY
RESIDENTIAL WATER SURVEY Thomas Guide 2009 Page Number: Meter #/Location: Appointment Date Time Acct Number Customer Name Last First Address City Zip Code Daytime Phone Evening Phone Age of Home Years
LIVING VICTORIA WATER REBATE PROGRAM 1 JULY 2012 TO 30 JUNE 2015 FOR UP TO 50 EMPLOYEES. Small Business
FOR UP TO 50 EMPLOYEES LIVING VICTORIA WATER REBATE PROGRAM 1 JULY 2012 TO 30 JUNE 2015 Small Business Claim up to $2000 to improve the water efficiency of your business. Save water and money. The Living
C.3 Workshop Track 2: Sizing Calculations and Design Considerations for LID Treatment Measures
C.3 Workshop Track 2: Sizing Calculations and Design Considerations for LID Treatment Measures Jill Bicknell, P.E., EOA, Inc. Santa Clara Valley Urban Runoff Pollution Prevention Program Presentation Overview
SECTION 1 PURPOSE AND POLICIES
SECTION 1 PURPOSE AND POLICIES These Rules and Regulations have been enacted to serve the public in securing the health, safety, and general welfare of the inhabitants of the Southwest Suburban Denver
Subject: YLWD Comments on the Mandatory Conservation Proposed Regulatory Framework
April 13, 2015 Felicia Marcus Chairperson, State Water Resources Control Board Attn: Jessica Bean 1001 I Street, 24 th Floor Sacramento CA 95814 Subject: YLWD Comments on the Mandatory Conservation Proposed
detection kit the water leak water leaks: What you should know A helpful guide for locating indoor and outdoor water leaks Getting Ready
water leaks: What you should know the water leak detection kit Imagine that the dot inside these brackets [ ] is the only hole in your home s water system. By its size alone, that hole may not seem worth
1993 Food Industry Environmental Conference SURVEY OF WATER USE IN THE CALIFORNIA FOOD PROCESSING INDUSTRY
SURVEY OF WATER USE IN THE CALIFORNIA FOOD PROCESSING INDUSTRY Jatal D. Mannapperuma Project Engineer California Institute of Food and Agricultural Research Department of Food Science and Technology University
Industrial Green Building Retrofit 101 Opportunities and Challenges. Light Industrial Green Building Retrofits. Why Green Retrofit?
Industrial Green Building 101 Opportunities and Challenges Joanne Sawatzky Senior Project Manager, Light House Sustainability at Work Re-visioning a Sustainable False Creek Flats Light Industrial Green
Water Distress in Growing Cities Issues & Challenges. Presented by: Neeta Sharma Managing Director IAPMO India
Water Distress in Growing Cities Issues & Challenges Presented by: Neeta Sharma Managing Director IAPMO India Source: UNESCO Green Approach- A MUST today- for Sustainability (better life cycle costs and
Common Causes of High Water Bills
Common Causes of High Water Bills An unusually high water bill is most often caused by a leak or change in water use. Some common causes of high water bills include: A leaking toilet, or a toilet that
Santa Clara Valley Water District
Santa Clara Valley Water District Commercial Institutional Industrial (CII) WATER USE & CONSERVATION BASELINE STUDY FINAL REPORT February 2008 Santa Clara Valley Water District 5750 Almaden Expressway,
EconoVue Snapshot Santa Clara County
EconoVue Snapshot Santa Clara County EconoVue, www.econovue.com A service of San Jose/Silicon Valley Workforce Investment Board (work2future) and The Urban Explorer, Inc Santa Clara County Snapshot: Introduction
City of Cornwall Social Housing Division Top 10 Energy & Water Saving Tips. in Multi-Unit Residential Buildings
City of Cornwall Social Housing Division Top 10 Energy & Water Saving Tips in Multi-Unit Residential Buildings Duncan Hill Canada Mortgage and Housing Corporation Andrew Pride Minto Developments Inc. Energy
Water Efficiency Self-Assessment Guide from
Water Efficiency Self-Assessment Guide from 1 Water Efficiency Self-Assessment Guide from Anglian Water Introduction More than 97% of the water in the world is too salty to drink, 2% is locked in glaciers
RESIDENTIAL END USES OF WATER
RESIDENTIAL END USES OF WATER Prepared by: Peter W. Mayer and William B. DeOreo Aquacraft, Inc. Water Engineering and Management 2709 Pine St. Eva M. Opitz, Jack C. Kiefer, William Y. Davis, and Benedykt
CHAPTER 2: The Plumbing System
CHAPTER 2: The Plumbing System SECTION I: SIZING REQUIREMENTS Establish building dimensions Building height can be determined either by architectural drawings or # of floors times height/floor. (ex: 1
SUBCHAPTER H: UTILITY SUBMETERING AND ALLOCATION 291.121-291.127 Effective January 6, 2011
Texas Commission on Environmental Quality Page 1 SUBCHAPTER H: UTILITY SUBMETERING AND ALLOCATION 291.121-291.127 Effective January 6, 2011 291.121. General Rules and Definitions. (a) Purpose and scope.
APPENDIX A RECOMMENDED RULES FOR SIZING THE WATER SUPPLY SYSTEM
APPENDIX A RECOMMENDED RULES FOR SIZING THE WATER SUPPLY SYSTEM Because of the variable conditions encountered, it is impractical to lay down definite detailed rules of procedure for determining the sizes
The Potential for Energy Retrofits within the City of Sacramento s Rental Housing Inspection Program
PNNL-20343 Prepared for the U.S. Department of Energy under Contract DE-AC05-76RL01830 The Potential for Energy Retrofits within the City of Sacramento s Rental Housing Inspection Program MM Iverson S
REPLACE A TOILET FILL VALVE
PROJECT 15 REPLACE A TOILET FILL VALVE 110 PLUMBING OKAY, SO YOU ARE AT PLAN B. Honestly, replacing a fill valve is no biggie. Of course, you can make a big deal and brag to your friends how you saved
Storm Drain System Operation and Maintenance
Santa Clara Valley Urban Runoff Pollution Prevention Program PUBLIC AGENCY ACTIVITIES Performance Standard and Supporting Documents for Storm Drain System Operation and Maintenance December 19, 1996 March
Santa Clara: Reinvented and on the rise.
MARKETPLACE Santa Clara: Reinvented and on the rise. Located in the center of Silicon Valley, the city of Santa Clara is perfectly positioned to be the next big Bay Area city. Between the CalTrain, Amtrak,
PLEASE NOTE. For more information concerning the history of these regulations, please see the Table of Regulations.
PLEASE NOTE This document, prepared by the Legislative Counsel Office, is an office consolidation of this regulation, current to June 1, 2014. It is intended for information and reference purposes only.
Water Saving Incentive Program Totals for FY2015
1 Lee Belle Lago Homeowners' Belle Lago HOA - Controller Upgrade Association Project $115,348.00 $50,000 32.00 32.00 Broward County Enivronmental Planning and 2 Broward Community Resilience High Efficiency
Economic and Fiscal Impacts Generated by Apple in Cupertino Current Facilities and Apple Campus 2. Prepared for: Apple Inc.
Economic and Fiscal Impacts Generated by Apple in Current and Apple Campus 2 Prepared for: May 2013 TABLE OF CONTENTS Page I. Introduction 1 A. Apple s Current in and the Apple Campus 2 Building Program
Maximum Performance (MaP) of WaterSense High-Efficiency Toilet Fixtures Sorted by Manufacturer
Maximum Performance (MaP) of WaterSense Toilet Fixtures Sorted by Manufacturer KEY: Cadet 3 FloWise EL 2832.128: 3014.128, 4021.128 tank 1,000 2 3 E HET F Cadet 3 FloWise EL ADA 2835.128: 3016.128, 4021.128
ENERGY EFFICIENCY COMPARISON
California Energy Commission STAFF REPORT ENERGY EFFICIENCY COMPARISON California s Building Energy Efficiency Standards and the International Energy Conservation Code and American Society of Heating,