1 15.1 INTRODUCTION This standard is intended to provide guidelines regarding safe electrical work procedures, electrical competency requirements, access to electrical "controlled areas", grounding, and verification of grounding integrity, portable electric equipment, and electrical transmission lines. This standard applies to all electrical work above 110 volts DC or 50 volts AC DEFINITIONS COMPETENT PERSON- a person having demonstrated the knowledge and abilities that fully qualify them to perform the duty to which they are assigned and who because of training and experience is capable of identifying hazardous or dangerous conditions and of instructing other employees to identify such conditions AUTHORIZED PERSON- a person approved or assigned by plant management to perform a specific duty or to be at a specific location QUALIFIED PERSON A person who, by possession of a recognized degree, professional certificate, or who, by extensive knowledge, training, and experience in the applicable field, has successfully demonstrated the ability to solve or resolve problems and is capable of design, analysis, evaluation and specifications relating to the subject matter, the work, or the project TRAINED PERSON A person who has successfully completed an approved course related to the subject. Records of the training must be maintained to verify trained person status ELECTRICAL GROUNDING - connected to or in contact with earth, or connected to some extended conductive body that serves in place of earth, to provide a path for leakage and / or fault currents to prevent an objectionable potential above ground on non-current carrying metal parts GROUNDING SYSTEMS - typically include the following: o Equipment grounding conductors - the conductors used to connect the metal frames or enclosures of electrical equipment to the grounding electrode conductor. o Grounding electrode conductors - the conductors connecting the grounding electrode to the equipment grounding conductor. Page 1 of 20 Plant:

2 o Grounding electrodes - usually driven rods connected to each other by suitable means, buried metal, or other effective methods located at the source, to provide a low resistance earth connection REQUIREMENTS All electrical installation work shall be conducted by competent personnel in accordance with governing regulation, code, design criteria and safe work procedures There shall be demonstrated job and equipment-specific electrical competency standards and safe work procedures for all electrical work, i.e. construction, decommissioning and demolition of electrical equipment. The competency standards shall specify the frequency for re-certification, which shall be no less than every two years and address job and equipment-specific safe work procedures There shall be an arc flash protection program in place to determine incident energies and define the appropriate PPE and associated procedures to mitigate the hazard Electrical safety devices such as earth leakage and overload protection shall be installed on all final distribution circuits and the settings established by qualified personnel Electrical equipment, grounding continuity and electrical safety devices shall be inspected and / or tested on a suitable schedule and the findings recorded There must be a system for removing electrical equipment unfit or unsafe for purpose. Each plant shall establish a system for removing unfit or unsafe electrical equipment There must be a system for maintaining an up-to-date set of single line diagrams with supporting documentation showing: o System fault calculations; o Equipment details; o Electrical protection discrimination curves; and o Cable ratings. Pertinent revisions shall be properly engineered, approved and logged. (See Exhibit ) Ongoing updates to distribution panel schedules, fault calculations, equipment details, protection discrimination curves and cable ratings must also be engineered, Page 2 of 20 Plant:

3 approved and logged Equipment shall be isolated. All energized electrical work will require a safe work procedure and an Energized Electrical Work Permit with the exception of voltage testing and where no tools are used Access to an electrical cabinet or other enclosure with exposed energized terminals in excess of 1,000 volts is prohibited There shall be an assessment of overhead and underground power lines and a system in place to mitigate the hazards associated with working in close proximity, and to prevent contact by personnel or equipment. (See KUC Standard 16.4 Close Proximity Permit) Employees and contractors exposed to electrical hazards shall receive electrical hazard training at the commencement of their employment and thereafter on an annual basis. The training shall address the equipment and conditions specific to the work area of the personnel and be documented. o Welding where the open circuit voltage exceeds 110 volts DC or 50 volts AC will be considered Energized work unless an approved Voltage Reduction Device (VRD) or an electrode switching device with a trigger action is used The following policies and procedures apply to all electrical / motor control rooms containing switches, motor starters, breakers, fuses and their accessories, located near the point of entrance of supply conductors to a "building or other structure" or an otherwise defined as a controlled area, and intended to constitute the main point of control. o For purposes of this provision, a switch room / MCC room is defined as a room dedicated to electrical distribution and control equipment. If switchgear / MCC is located in a room or facility in which routine non-electrical operational and / or maintenance activities may take place, these are not considered controlled areas provided that: - The maximum voltage is less than 1,000 volts, the incident energy of any panel is no higher that Category 2, and the total amperage does not exceed 1,200 amperes. - Energized parts are inaccessible. - A system is in place to maintain arc flash and shock approach boundaries during maintenance activities. - The MCCs are protected from mobile equipment and other activities that may take place in the area. Page 3 of 20 Plant:

4 - Working space around the equipment must be maintained to provide safe access / egress at all times. - A risk assessment is in place that confirms that the MCC and potential activities are compatible without risk to personnel or equipment. - A list of such areas is maintained and approved by the site manager o Electrical panels, enclosures, control centers, substations and equipment shall be appropriately guarded, labeled, and made inaccessible (except for emergency shut off mechanisms) to unauthorized personnel. Areas containing such equipment are controlled areas. o Access to controlled areas shall be restricted to competent or authorized personnel only. Access, will be controlled by locked doors or other appropriate means. Where it is necessary for untrained personnel (e.g. visitors) to enter controlled areas there shall be a system for communicating the hazards and for escorting them with appropriately trained personnel. Contractors must have a permit to work in controlled areas. o Suitable "Danger" signs shall be posted at the entrance to all major electrical installations. Metal-enclosed switchgear, unit substations, transformers, pull boxes, connection boxes, and other similar associated equipment shall be marked with appropriate "Caution" signs. Principal power switches shall be labeled to show which units they control. The labeling shall be legible, durable and distinctive. o All electrical rooms shall be kept clean and orderly. All doors, inspection and cover plates on electrical equipment shall be kept in place at all times except during testing, installation or repairs. o All personnel doors will be equipped with panic hardware and swing outward to allow rapid egress in the event of an emergency. o Electrical rooms shall not be used as shop facilities, storage areas or lunchrooms. All electrical rooms will be posted as "NO SMOKING" areas. Combustible materials shall not be stored in any electrical room nor shall they be stored or allowed to accumulate within 25 feet of an electrical substation. Electric room engineering documentation and diagrams are acceptable but must be properly stored in racks or storage files. o Insulated platforms, insulating mats, or other electrically nonconductive material shall be kept in place at all switchboards and power-control switches where a shock hazard exists. Page 4 of 20 Plant:

5 o Working space around electrical equipment shall be provided in accordance with the National Electrical Code. Where there is access to exposed energized parts, measures such as deenergization or the use of insulated gloves or blankets shall be used in accordance with safe work procedures. o The electrical group is responsible for the upkeep, equipment integrity, maintenance and housekeeping of all electrical equipment and installations inside the electrical room GROUNDING The path from circuits, equipment, structures, and conduit or enclosures to ground shall be permanent and continuous, have ample carrying capacity to safely conduct the currents liable to be imposed on it, and have impedance sufficiently low to limit the potential rise above ground and to cause the operation of overcurrent devices to isolate the circuit. o Grounding grids and driven rod electrodes shall have a resistance to ground not to exceed 25 ohms. Where the resistance is above 25 ohms, two or more electrodes connected in parallel shall be used. o The resistance of a motor frame to grounded building steel shall not exceed one (1) ohm. o Electrical equipment shall be grounded in accordance with all applicable federal and state regulations, National Electric Code and National Electrical Safety Code requirements All structures, hardware, shield wires, and pole-mounted transformers shall be grounded All exposed metal parts of switches, structures, transformers, fences, gates, buildings, switchboards, breakers, meters, relays, lightning arresters, and communication equipment shall be grounded. o All substations shall have a ground grid to which all equipment is bonded. Resistance of grid to earth shall not exceed 25 ohms FIXED EQUIPMENT Equipment that is fastened in place or connected by permanent wiring methods. Exposed non-currentcarrying metal parts of fixed electrical equipment including motors, generators, frames, and rails of electrically operated cranes, electrically driven machinery, etc. shall be grounded. Page 5 of 20 Plant:

6 PORTABLE EQUIPMENT Equipment that is fed with portable cords or cables intended to be moved from one place to another. The non-current-carrying metal parts of portable and / or plugconnected equipment shall be grounded. o Portable electric-powered equipment such as conveyors, electric shovels, drills, etc. with associated portable substations, and switchgear shall be connected to a safety ground system. Trailing cables powering such equipment will have adequately sized ground conductors with continuously monitored ground continuity check equipment. o Portable tools and appliances protected by UL approved system of double insulation, or its equivalent, need not be grounded. Where such an approved system is used, the equipment shall be distinctively marked. o Extension cords used with portable electric tools and appliances shall be of three-wire type and shall be maintained in good condition PORTABLE and VEHICLE-MOUNTED GENERATORS - unless the owner s manual dictates otherwise, the frame of a portable generator shall not be required to be connected to a grounding electrode for a system supplied by the generator under the following conditions: o The generator supplies only equipment mounted on the generator, cord-and-plug-connected equipment through receptacles mounted on the generator, or both, and o The non-current-carrying metal parts of equipment and the equipment grounding conductor terminals of the receptacles are bonded to the generator frame. Vehicle-Mounted Generators - The frame of a vehicle shall not be required to be connected to a grounding electrode for a system supplied by a located on this vehicle under the following conditions: o The frame of the generator is bonded to the vehicle frame, and o The generator supplies only equipment located on the vehicle or cord-and-plug connected equipment through receptacles mounted on vehicle, or both equipment located on the vehicle and cord-and-plug connected equipment through receptacles mounted on the vehicle or on the generator, and o The non-current-carrying metal parts of equipment and the equipment grounding conductor terminals of the receptacles are bonded to the generator frame. Page 6 of 20 Plant:

7 Portable Welders - must be plugged into an approved receptacle and equipped with the following: o A disconnect switch or circuit breaker in the supply system. o A nameplate giving electrical data for the welder. o An approved welding lead All temporary wiring shall be effectively grounded in accordance with the National Electrical Code Operators / craftsmen shall conduct the following tests. (See attached procedure and recordkeeping forms Exhibit ) o Equipment grounding conductors - continuity and resistance must be tested immediately after installation, repair, or modification, and annually if conductors are subjected to vibration, flexing, or corrosive environments. o Grounding electrode conductors - continuity and resistance must be tested immediately after installation, repair, or modification, and annually if conductors are subjected to vibration, flexing, or corrosive environments. o Grounding electrodes - resistance must be tested immediately after installation, repair, modification, and annually thereafter Conductors in fixed installations, such as rigid conduit, armored cable, raceways, cable trays, etc. that are not subjected to vibration, flexing, or corrosive environments may be examined annually by visual observation to check for damage in lieu of the annual resistance test Grounding conductors in trailing cables, power cables, and cords that supply power to tools and portable or mobile equipment must be tested. This requirement does not apply to double insulated tools or circuits protected by ground-fault-circuit interrupters (GFCI) Testing of equipment grounding conductors and grounding electrode conductors is not required if a fail-safe ground wire monitor is used to continuously monitor the grounding circuit and which would cause the circuit protective devices to operate when the grounding conductor continuity is broken PORTABLE ELECTRICAL EQUIPMENT The exposed non-current carrying metal parts of portable and / or plug-connected tools, welders and other equipment must be Page 7 of 20 Plant:

8 grounded. o Portable tools and appliances with an approved system of double insulation need not be grounded. To avoid the grounding requirements the item being used must be clearly marked as being double insulated Hand-held power tools must be inspected before each use for damage or alteration. Unsafe conditions must be corrected before the tool is used. o Hand-held power tools such as power drills, disc sanders, grinders, circular saws, and chain saws when used in the hand held mode shall be operated with controls which require constant hand or finger pressure. o Hand-held power tools shall not be operated at voltages above 120 volts. o Disconnect tools when not in use, before servicing and cleaning, and when changing accessories such as blades, bits, and cutters. o All factory installed guarding must be in place when operating any hand tool Electrical cords must be protected from physical damage. Before use power cords must be inspected for missing ground prong and damaged insulation or damage to the plug or receptacle and be current with the grounding continuity verification requirement JUMPER PERMIT Jumpers can be used on any interlock, contact, loop, etc. that has temporarily been put out of service. This includes hardwire and software types. Jumpers can only be installed by trained electrical or control systems employee(s) or other qualified and authorized personnel designated by plant management Prior to installation of the jumper, a "Jumper Permit / Jumper Tag" (see Exhibit ) must be completed and approved by an authorized person as designated by plant management. The completed Jumper Permit will be forwarded to the electrical supervisor for inclusion in the Jumper Log The Jumper Tag must be placed on the device or inside the panel where the jumper is contained. For software jumpers (or temporary modification), the Jumper Tag must be placed in the PLC / CPU rack. When a control system technician or electrician removes a jumper, the tag must be returned to the electrical Page 8 of 20 Plant:

9 supervisor and the Jumper Permit updated that the jumper was removed A Jumper Log must be maintained by the electrical supervisor or other plant designee. The log must contain all pertinent information, including dates jumpers were installed and removed with a copy of the Jumper Permit. The record log must be kept for a minimum of two years Under no circumstances will a jumper be used to bypass an emergency safety shutdown device, e.g., pull cord switch, stop button, etc. Also, jumpers will not be used to deactivate or circumvent an activated lock out system. Whenever installing a jumper that may affect personnel safety a risk assessment must be completed Precautions must be taken on equipment when protection devices are jumpered, e.g., lube flow switches, RTDs, etc.; precautions could include more frequent interval inspections of equipment, temporary replacement devices, or constant employee watch. In any case, the risk of equipment loss must be reduced to the maximum extent possible ELECTRICAL TRANSMISSION LINES Grounding - Wood structures shall have a copper butt plate and spiral wrapped with a minimum #6 AWG soft-drawn copper wire up to ground level. Spiral wraps shall be short-circuited together by the vertical ground wire and stapled at every crossing. The wire is to be extended straight up the pole and stapled at no more than three foot intervals. All hardware and shield wires shall be connected to pole ground wires. o Steel lattice-type towers shall be grounded through the steel structure. Bolted joints shall be inspected for tightness at such intervals as experience has shown to be necessary. o Tubular steel towers shall be grounded through anchor bolts and grounding lugs provided. o Ground resistance should be monitored at strategic locations and records kept All transmission lines shall have shield or static wires in place. Shield wires shall be extra high strength galvanized steel or copper-clad steel, as determined by location and shall be securely connected to structure ground conductors. Lightning arrestors shall be installed at transformer bank primaries, fused disconnects, and in substations. Page 9 of 20 Plant:

10 Warning signs must be posted on all steel transmission line towers. Signs shall be mounted at a height of 5 to 7 feet on all four sides of the tower. These signs shall clearly indicate Danger and High Voltage Climbing steps will be installed on steel structures, if needed, and will begin at a point at least 12 feet above ground level. Steps below 12 feet high will be removed. Steps will not be installed on wood poles. Structures accessible by the public will have steps beginning at 15 feet above ground level, if steps are required Vertical and horizontal clearances between power lines and ground or other obstructions will be in accordance with published standards, taking into account line voltage, structure type, loading class, span length, type of terrain, and all other applicable constraints. o Approved clearances will be maintained between energized conductors and grounded structure parts. Energized conductors with less than minimum clearance will be shielded or insulated to protect personnel and equipment. Safety hazard signs shall also be posted. o Any powerline that could be an obstruction to air navigation will be identified by marker balls. This includes overhead lines exceeding 200 feet above ground level. In the event of a valley, ravine or gorge, the lowest point is used to determine elevation. - Markers should be spaced equally along the wire at intervals of approximately 200 feet or fraction thereof Insulation of energized conductors from structures shall be installed in accordance with operating voltage, impulse level required, and ambient conditions All transmission lines shall be visually inspected at such intervals as experience has shown to be necessary. Inspections shall be documented and corrective action shall be promptly taken to correct problems identified during the inspection. o Switches shall be exercised at such intervals as experience has shown to be necessary An infrared thermographic survey of all transmission lines shall be conducted at such intervals as experience has shown to be necessary. Any hot spots discovered in the thermographic survey shall be promptly corrected. Accurate records of location, equipment, and temperature rise shall be taken and maintained. Page 10 of 20 Plant:

11 Areas around wood poles subject to weed growth shall have an environmentally-acceptable herbicide applied in a six-foot radius around each pole at intervals as necessary to control weeds and eliminate danger of pole damage from ground fires Guy wires on wood poles shall have insulators installed at 8 feet above ground level to protect personnel. Guy wires shall be adequately marked and protected from damage Line work shall be performed only by qualified linemen. o Tools and safety equipment shall be inspected and tested at prescribed intervals. o Wherever possible, before line work is begun, the line will be isolated and grounded according to the KUC Lock and Tag Standard 16.12, Kennecott Electrical Switching Procedures, and the Kennecott Substation and Switchyards Manual. o Hot line work, if required, will be performed in strict compliance with established procedures New construction and maintenance shall conform to all applicable requirements contained in this standard and all other codes and regulations ILLUMINATION Adequate illumination shall be provided for all working spaces around electrical equipment. Whenever possible, natural lighting should be utilized in all working areas. Artificial lighting must be adequate for the type of work being performed in an area, especially where hazardous or night work situations are involved. Energy efficient lighting products must be considered whenever changing existing lighting or designing new lighting layouts. Illumination levels should be maintained to the latest ANSI Lighting Standards RECORDKEEPING A record of the most recent continuity and resistance test or visual examination conducted must be kept and made available for internal and regulatory inspections. The records shall: o Identify the equipment and location tested o Identify the person conducting the tests o Identify the date of the test o Record meter reading to the nearest 0.1 ohm Page 11 of 20 Plant:

12 o Identify action taken to address readings over one (1) ohm o Record a re-test reading upon completion of repairs Recordkeeping forms are provided as attachments to this standard. All records shall be maintained as designated in the KUC Records Retention Schedule. REFERENCES: American National Standard Practice for Industrial Lighting ANSI RP7 FAA Part 77 Airspace Obstruction Analysis FAA Obstruction Marking and Lighting KUC Safety and Health Standards 16.4 Cranes and Hoists KUC Safety and Health Standard Lockout / Tagout (Isolation) KUC Records Retention Schedule MSHA 30 CFR Part 56 & and Subpart K National Electrical Code NFPA 70 National Electrical Safety Code OSHA 29 CFR Subpart S. Rio Tinto Safety Standard C2 Electrical Safety Rio Tinto Electrical Standards Guideline Document REVISION HISTORY: MOC# Description of Change Prepared By Date Scheduled review and update including adding a procedure for continuity and resistance testing recommended by the C2 Standards Committee. Also, updated format and Document number added. KUC Safety and Health Standards Committee 6/ Scheduled review and update. Also changes incorporate requirements from combining the existing KUC H&S Standards 15.2 Lighting, 16.9 Portable Electric Equipment, Electrical Grounding, Jumper Permit and Electrical Transmission Lines (which will be eliminated) into C2 Electrical Safety Champion KUC Safety and Health Standards Committee 03/12 Page 12 of 20 Plant:

13 Exhibit Log of Engineering Revisions Plant: Page 1 of Discipline: Item Drawing/ Rev. Date Description APPROVALS No. PLC ID # (a) 1 No. (b) (c) Procedure for updating Programmable Logic Controller (PLC) software: Diskette label must show Rev. number(s), same Rev. # as shown in this log. (a) Shaded areas reserved for related PLC revision (b) Supervisor / Plant Engineer (c) Plant Engineer s supervisor (next level in organization) Page 13 of 20 Plant:

14 Exhibit Procedure for Testing Continuity and Resistance of Grounding Systems Continuity and resistance of grounding systems shall be tested immediately after installation, repair, or modification; and annually thereafter. A record of the resistance measured during the most recent test shall be made available for inspection and records shall be kept on file in accordance with the KUC records retention policy. Fixed Plant Equipment Annual Inspection (A) Equipment Needed a. Digital or analog volt-ohmmeter b. Spool of copper wire of appropriate length with alligator clamps or equivalent suitable connectors at each end (B) Zero Meter Through Wire Roll a. Attach one end of wire to meter b. Attach opposite end of wire to other meter probe c. Measure resistance of wire d. Adjust meter reading to 0 or record reading to deduct from overall resistance readings (C) Visually Inspect Grounding System and Repair as Needed a. Check for obvious signs of corrosion b. Check for broken conduit or flex c. If external grounds are present, inspect for damage (D) Record Meter Reading at Motor a. Attach one end of wire roll to grounded building steel ensuring good contact b. String out sufficient wire to reach motor and attach to meter probe c. Place other meter probe on motor housing ensuring good contact d. Record meter reading to the nearest 0.1 ohm (deduct wire roll resistance if meter not zeroed ) e. If resistance is higher than one (1) ohm, identify and correct deficiency (E) Clamp on Ground meter a. A ground resistance tester may be used in lieu of the above method to measure the resistance of the grounding system Repair or Modification (A) Measure the Resistance of the equipment grounding conductor when disconnected a. Use method A-D above but connect one probe of meter directly to the grounding conductor instead of the motor case b. After the motor is connected and before energizing measure resistance of grounding system using A E above (Annual Inspection) (B) Whenever grounding connections are visible or exposed during routine maintenance or troubleshooting, the grounding connections must be visually inspected. Page 14 of 20 Plant: effect and supersede all other revisions.

15 Portable Equipment - If not connected to a ground monitoring system (A) Equipment Needed a. Digital or analog volt-ohmmeter b. Spool of copper wire of appropriate length with alligator clamps or equivalent connector at each end (B) Zero Meter Through Wire Roll a. Attach one end of wire to meter b. Attach opposite end of wire to other meter probe c. Adjust meter reading to 0 or record reading to deduct from overall resistance readings (C) Visually Inspect Grounding System a. Check for obvious signs of corrosion b. Inspect feeder cable and connections for damage (D) Record Meter Reading at Motor a. Attach one end of wire to the MCC ground feeding the power cable, ensuring good contact b. String out sufficient wire to reach motor and attach to meter probe c. Place other meter probe on motor housing ensuring good contact d. Record meter reading to the nearest 0.1 ohm (deduct wire roll resistance if meter not zeroed ) e. If resistance is higher than one ohm, identify and correct deficiency Grounding Electrode Conductor The continuity and resistance of the equipment grounding conductors shall be measured by an inductive device or resistance reading between the frame of the motor and grounded building steel with a resistance of less than one (1) ohm Grounding Electrode The resistance of the grounding electrode or grounding electrode conductor to the earth shall be measured either by reference to an established earth-grounded electrode or inductive device (clamp on ground meter) with a resistance of less than 25 ohms Building Steel to Grounding Electrode Conductor The conductors between the building steel and the ground grid shall be visually inspected and the resistance determined by either an inductive device or a resistance meter between the building steel and the grounding electrode. Exposed steel to grid conductors should be visually examined for the condition of bonds and wiring, and of these, a representative number should be measured. Inspection or Repair When electrical equipment such as switchboards, panelboards, control panels, meter socket enclosures and motor control centers cabinet are accessed for inspection or repair, a visual inspection of the equipment grounding conductors shall be conducted. Page 15 of 20 Plant: effect and supersede all other revisions.

16 Exhibit (Designate Plant for Identification) CONTINUITY AND RESISTANCE GROUND SYSTEM LOG MODIFICATIONS AND / OR REPAIRS DATE ELECTRICIAN (S): SUPERVISOR: MODIFICATIONS LOCATION: REASON: DESCRIPTION: TEST READINGS: REPAIRS LOCATION: REASON: DESCRIPTION: TEST READINGS: NEW INSTALLATION LOCATION: REASON: DESCRIPTION: TEST READINGS: COMMENTS: Distribution: Maintenance Superintendent Plant Records Page 16 of 20 Plant: effect and supersede all other revisions.

17 Exhibit EQUIPMENT GROUNDING CONTINUITY AND RESISTANCE ANNUAL TESTING PROGRAM PLANT: EQUIPMENT NUMBER LOCATION/DESCRIPTION MOTOR FRAME TO BUILDING STEEL (OHMS TO 1 DECIMAL) PERSON PERFORMING TESTS DATE COMMENTS Distribution: Maintenance Superintendent Plant Records Page 17 of 20 Plant:

18 Exhibit ANNUAL GROUNDING SYSTEM INSPECTION RECORD USING VISUAL OR CONTINUITY / RESISTANCE READING METHODS PLANT: DESCRIPTION/ LOCATION METHOD: VISUAL OR OHM READING PERSON PERFORMING TESTS DATE COMMENTS Distribution: Maintenance Superintendent Plant Records Page 18 of 20 Plant:

19 Exhibit KENNECOTT UTAH COPPER JUMPER PERMIT (Standard15.1) Rev 6 02/12 TAG NO. EMOC # EQUIPMENT NUMBER DATE DEVICE JUMPERED TIME AM PM Work Order No. Hardwire? q Yes q No Software? q Yes q No Duration of Permit From To Reason for Jumper: Recommendations concerning safety, operating restrictions, or special instructions: APPLICABLE INFORMATION: Location & Equipment Description DWG MCC Term. Box Wire No. PLC External Force: Cabinet Block I/O Point PLC Software: PLC ID No. Rung I/O Point Requested By Print Name Signature Date Approved By Installed By JUMPER REMOVAL Removed By Print Name Signature Date Distribution Electrical Supervisor Page 19 of 20 Plant: effect and supersede all other revisions.

20 TAG NO. JUMPER TAG TRACK completed for this task (Initials): APPROVED BY EQUIPMENT NO. INSTALLED BY DATE TIME AM NOTE: RECORD ALL INFORMATION IN JUMPER LOG BOOK. PM Page 20 of 20 Plant: effect and supersede all other revisions.

Union County Public Schools. Facilities Department. Electrical. Safe Work Practices

Union County Public Schools. Facilities Department. Electrical. Safe Work Practices 1 Union County Public Schools Facilities Department Electrical Safe Work Practices 2 Purpose In accordance with OSHA Standards 1910.331-335, safety-related work practices shall be used by Union County

More information

Electrical Grounding. Appendix C

Electrical Grounding. Appendix C Appendix C Electrical Grounding Low-Voltage Equipment Grounding The most frequently cited Office of Safety and Health Administration (OSHA) electrical violation is improper occupational grounding of equipment

More information

Title: Grounding and Bonding Rev-01

Title: Grounding and Bonding Rev-01 Procedure No.: BMEHS-002-012 Page: 1 of 12 Preparer: Owner: Approver: EHS Team Member S/H Manager Site Manager Signed Copy on File Signed Copy on File Signed Copy on File Document Revision Change Table

More information

DEPARTMENT OF LICENSING AND REGULATORY AFFAIRS DIRECTOR S OFFICE CONSTRUCTION SAFETY STANDARDS

DEPARTMENT OF LICENSING AND REGULATORY AFFAIRS DIRECTOR S OFFICE CONSTRUCTION SAFETY STANDARDS MIOSHA-STD-1313 (10/15) 6 Pages For further information Ph: 517-284-7740 www.michigan.gov/mioshastandards DEPARTMENT OF LICENSING AND REGULATORY AFFAIRS DIRECTOR S OFFICE CONSTRUCTION SAFETY STANDARDS

More information

Common Electrical Hazards in the Workplace Including Arc Flash. Presented by Ken Cohen, PhD, PE & CIH (Ret.)

Common Electrical Hazards in the Workplace Including Arc Flash. Presented by Ken Cohen, PhD, PE & CIH (Ret.) Common Electrical Hazards in the Workplace Including Arc Flash Presented by Ken Cohen, PhD, PE & CIH (Ret.) 1 What s New In February 1972, OSHA incorporated the 1971 edition of the National Fire Protection

More information

IRRIGATION PUMPING Table of Contents - Section 900

IRRIGATION PUMPING Table of Contents - Section 900 IRRIGATION PUMPING Table of Contents - Section 900 PARAGRAPH 900.1 GENERAL 1 900.2 METERING REQUIREMENTS 1 900.3 CUSTOMER S CONTROL EQUIPMENT 2 900.4 SERVICE CONDUCTOR REQUIREMENTS 2 900.5 RECOMMENDATIONS

More information

Requirements for Electrical Installations

Requirements for Electrical Installations ARTICLE 110 Requirements for Electrical Installations INTRODUCTION TO ARTICLE 110 REQUIREMENTS FOR ELECTRICAL INSTALLATIONS Article 110 sets the stage for how you ll implement the rest of the NEC. This

More information

ELECTRICAL SAFETY. The standard unit for measuring electrical current.

ELECTRICAL SAFETY. The standard unit for measuring electrical current. ELECTRICAL SAFETY Introduction The following sections provide general safety guidelines and procedures for electrical safety. This chapter covers the following topics: TOPIC PAGE General Electrical Safety

More information

ELECTRICAL - WIRING DESIGN AND PROTECTION SELF INSPECTION CHECKLIST

ELECTRICAL - WIRING DESIGN AND PROTECTION SELF INSPECTION CHECKLIST Name of School: OPTIONAL INFORMATION Date of Inspection: Vocational Program/Course/Room: Signature of Inspector: ELECTRICAL - WIRING DESIGN AND PROTECTION SELF INSPECTION CHECKLIST Guidelines: This checklist

More information

Written Program ELECTRICAL SAFETY. Based on OSHA Subpart S and NFPA 70E Standards

Written Program ELECTRICAL SAFETY. Based on OSHA Subpart S and NFPA 70E Standards Written Program ELECTRICAL SAFETY Based on OSHA Subpart S and NFPA 70E Standards Revised November 2012 Disclaimer The presentations and program provided by Workplace Safety Solutions, Inc. are based on

More information

Electrical Wiring Methods, Components and Equipment for General Use. Approved for Public Release; Further Dissemination Unlimited

Electrical Wiring Methods, Components and Equipment for General Use. Approved for Public Release; Further Dissemination Unlimited Electrical Wiring Methods, Components and Equipment for General Use Approved for Public Release; Further Dissemination Unlimited At the completion of this unit you shall be able to: 1. Utilize section

More information

INDUSTRY WIDE LABOR-MANAGEMENT SAFETY COMMITTEE SAFETY BULLETIN #23

INDUSTRY WIDE LABOR-MANAGEMENT SAFETY COMMITTEE SAFETY BULLETIN #23 INDUSTRY WIDE LABOR-MANAGEMENT SAFETY COMMITTEE SAFETY BULLETIN #23 GUIDELINES FOR WORKING WITH PORTABLE POWER DISTRIBUTION SYSTEMS AND OTHER ELECTRICAL EQUIPMENT "ADDENDUM C" WORKING WITH 480 VOLT SYSTEMS

More information

What are the basic electrical safety issues and remedies in solar photovoltaic installations?

What are the basic electrical safety issues and remedies in solar photovoltaic installations? What are the basic electrical safety issues and remedies in solar photovoltaic installations? Presented by: Behzad Eghtesady City of Los Angeles Department of Building and Safety Topics Covered Photovoltaic

More information

Top Commercial / Residential Electrical Requirements *

Top Commercial / Residential Electrical Requirements * Department of Community Development Building Division 4800 West 92 nd Avenue Westminster, Colorado 80031 For Information call (303) 658-2075 Fax (303) 706-3922 www.westminsterpermits.com Top Commercial

More information

3053 Electrical Safety Training Program Course Outline

3053 Electrical Safety Training Program Course Outline 3053 Electrical Safety Training Program Course Outline The following outline summarizes the major points of information presented in the program. The outline can be used to review the program before conducting

More information

ELECTRICAL SAFETY: QUALIFIED/NON QUALIFIED

ELECTRICAL SAFETY: QUALIFIED/NON QUALIFIED Preparation: Safety Mgr Authority: Dennis Johnston Issuing Dept: Safety Page: Page 1 of 9 Purpose The purpose of the Electrical Safety program is to set forth procedures for the safe use of electrical

More information

Hyperlinks are Inactive

Hyperlinks are Inactive Prepared by: NIB/EOB PLANNING GUIDE FOR SINGLE CUSTOMER SUBSTATIONS SERVED FROM TRANSMISSION LINES 05503 Department: Electric T&D Section: T&D Engineering and Technical Support Approved by: G.O. Duru (GOD)

More information

NFPA 70E 2012 Rolls Out New Electrical Safety Requirements Affecting Data Centers

NFPA 70E 2012 Rolls Out New Electrical Safety Requirements Affecting Data Centers NFPA 70E 2012 Rolls Out New Electrical Safety Requirements Affecting Data Centers A market position paper from the experts in Business-Critical Continuity TM Executive Summary Electrocutions are the fourth

More information

Bypass transfer switch mechanisms

Bypass transfer switch mechanisms Power topic #6013 Technical information from Cummins Power Generation transfer switch mechanisms > White paper By Gary Olson, Director, Power Systems Development This paper describes the configuration

More information

ARC FLASH CALCULATIONS & LABELING REQUIREMENTS

ARC FLASH CALCULATIONS & LABELING REQUIREMENTS ARC FLASH CALCULATIONS & LABELING REQUIREMENTS Presented by: Edmund Elizalde EYP Mission Critical Facilities, Inc. Slides by: Lonnie Lindell SKM Systems Analysis, Inc. 1 Agenda NEC 110.16 NFPA 70E IEEE

More information

METER REQUIREMENTS GENERAL REQUIREMENTS SECTION D

METER REQUIREMENTS GENERAL REQUIREMENTS SECTION D 12 - ELECTRIC SERVICE HANDBOOK SECTION D METER REQUIREMENTS This chapter gives you information on Central Lincoln s metering requirements. It's divided into three sections: General requirements This section

More information

RMM 306 Lockout/Tagout (LOTO) Program for the Control of Hazardous Energy Page 2 June 2016

RMM 306 Lockout/Tagout (LOTO) Program for the Control of Hazardous Energy Page 2 June 2016 RMM 306 Lockout/Tagout (LOTO) Program for the Control of Hazardous Energy Page 2 3 Related Documents 3.1 Occupational Health and Safety Act, R.S.O. 1990 3.2 Regulations for Industrial Establishments, R.R.O.

More information

Arc Flash Hazards. Electrical Hazards. Dan Neeser Field Application Engineer DanRNeeser@Eaton.com. Electrical Hazards 2/18/2015. Shock.

Arc Flash Hazards. Electrical Hazards. Dan Neeser Field Application Engineer DanRNeeser@Eaton.com. Electrical Hazards 2/18/2015. Shock. Arc Flash Hazards Dan Neeser Field Application Engineer DanRNeeser@Eaton.com Electrical Hazards Electrical Hazards Shock Arc Flash Arc Blast 2 1 Arcing Fault Basics 35,000 F Radiant Heat & UV Speed of

More information

TABLE OF CONTENTS. 437-004-2850 Temporary Lighting and Wiring... S-2 Temporary Wiring... S-2 Temporary Lighting... S-3

TABLE OF CONTENTS. 437-004-2850 Temporary Lighting and Wiring... S-2 Temporary Wiring... S-2 Temporary Lighting... S-3 Oregon Administrative Rules and Health Division ELECTRICITY S TABLE OF CONTENTS 437-004-2810 General Requirements... S-1 437-004-2850 Temporary Lighting and Wiring... S-2 Temporary Wiring... S-2 Temporary

More information

Walking and Working Surface Checklist:

Walking and Working Surface Checklist: Walking and Working Surfaces Purpose: This information is presented to improve the level of safety in our operations, and to inform you that we will comply with the OSHA Standard 29 CFR 1910.23. Responsibility:

More information

Part 1 System Modeling & Studies for Existing Systems

Part 1 System Modeling & Studies for Existing Systems Part 1 System Modeling & Studies for Existing Systems Operation Technology, Inc. Copyright 2009 Result of rapid release of energy due to an arcing fault between two conductors. Bus voltages > 208V Temperatures

More information

ELECTRICAL INSPECTION BULLETIN (Effective 2000-03-01)

ELECTRICAL INSPECTION BULLETIN (Effective 2000-03-01) ELECTRICAL INSPECTION BULLETIN (Effective 2000-03-01) Rule 28-900 Standby Generator Installations Due to the increasing number of standby generator installations being established to maintain continuity

More information

Chapter 9. Bonding and Grounding

Chapter 9. Bonding and Grounding Chapter 9 Bonding and Grounding Objectives Describe why the cable should be bonded Describe bonding and grounding procedures Define Bonding and Grounding Explain Safety Benefits and intent of bonding and

More information

Submit shop drawings for equipment provided under this section Shop drawings shall indicate:

Submit shop drawings for equipment provided under this section Shop drawings shall indicate: Section 16435 - SWITCHBOARDS Introduction Part 1 - General Reference The work under this section is subject to requirements of the Contract Documents including the General Conditions, Supplementary Conditions,

More information

Oil and Coolant Circulating Heating System. Model - OCSM

Oil and Coolant Circulating Heating System. Model - OCSM Oil and Coolant Circulating Heating System Model - OCSM Installation & Operation Manual 216280-000 REV 2 Identifying Your System The HOTSTART heating system is designed to heat fluids for use in marine

More information

GUIDELINES FOR UTILITY INSTALLATIONS Part 1 - Wire Lines and Communications Cables

GUIDELINES FOR UTILITY INSTALLATIONS Part 1 - Wire Lines and Communications Cables Engineering Department SEPTEMBER, 2007 GUIDELINES FOR UTILITY INSTALLATIONS Part 1 - Wire Lines and Communications Cables General Requirements This section applies to all public and private utilities,

More information

Arc Flash Avoidance and its Application to Overhead Traveling Cranes

Arc Flash Avoidance and its Application to Overhead Traveling Cranes Arc Flash Avoidance and its Application to Overhead Traveling Cranes Whitepaper August 2012 Jason Wellnitz, Controls Product Manager Material Handling Numerous technical papers, bulletins, magazine articles

More information

Grounding & Bonding Why it is done And How to Install Properly

Grounding & Bonding Why it is done And How to Install Properly Grounding & Bonding Why it is done And How to Install Properly The technical information provided herein is to assist qualifi ed persons in planning and installing electric service to farms and residences.

More information

Electrical Safety Requirements

Electrical Safety Requirements Section 12 Electrical Safety Requirements This section sets forth requirements for electrical safety. It specifically addresses working in restricted areas; working near exposed energized overhead lines

More information

OPTIONAL INFORMATION ELECTRICAL SAFETY WORK PRACTICES SELF INSPECTION CHECKLIST

OPTIONAL INFORMATION ELECTRICAL SAFETY WORK PRACTICES SELF INSPECTION CHECKLIST Name of School: OPTIONAL INFORMATION Date of Inspection: Vocational Program/Course/Room: Signature of Inspector: ELECTRICAL SAFETY WORK PRACTICES SELF INSPECTION CHECKLIST Instructions: This checklist

More information

90.2(A) Covered & 90.2(B) Not Covered 6/23/2015. Learning Objectives. 90.2(A) Covered & 90.2(B) Not Covered. Change Summary

90.2(A) Covered & 90.2(B) Not Covered 6/23/2015. Learning Objectives. 90.2(A) Covered & 90.2(B) Not Covered. Change Summary Learning Objectives After reviewing this material, the student will be able to: 1. Identify the installations that fall under the scope of the 2015 edition of NFPA 70E. 2. Identify the assessments required

More information

City Of Ottawa High Voltage Substation Inspection, Maintenance Rev 00 2015 July 17 and Testing, ROPEC Page 1

City Of Ottawa High Voltage Substation Inspection, Maintenance Rev 00 2015 July 17 and Testing, ROPEC Page 1 2015 July 17 and Testing, ROPEC Page 1 PART 1 GENERAL 1.1. Scope.1 Equipment replacement and testing for a 44 kv 4.16kV/600V substation: a. Replacement of Insulators as indicated on the drawings in Appendix

More information

800 Communications Circuits

800 Communications Circuits ARTICLE 800 Communications Circuits INTRODUCTION TO ARTICLE 800 COMMUNICATIONS CIRCUITS This article has its roots in telephone technology. Consequently, it addresses telephone and related systems that

More information

misconceptions about arc-flash hazard assessments

misconceptions about arc-flash hazard assessments misconceptions about arc-flash hazard assessments There are some common misconceptions about Arc-Flash Hazard Assessments which reduce the effectiveness of the Assessments and can increase electrical hazards.

More information

IMPLEMENTING THE NEW ELECTRICAL SAFETY REQUIREMENTS

IMPLEMENTING THE NEW ELECTRICAL SAFETY REQUIREMENTS IMPLEMENTING THE NEW ELECTRICAL SAFETY REQUIREMENTS Paul A Zoubek, CSP, CIH Occupational Services, Inc. San Diego, CA 619-861 861-0612 paul@occsev.com OCCUPATIONAL SERVICES, INC. BACKGROUND Update Update

More information

Electrical Hazards. Power Tools. Extension Cords

Electrical Hazards. Power Tools. Extension Cords Electrical Hazards Electrical hazards can be found in nearly every roofing work site. Whether the hazard is posed by worn or damaged power tools or cords, improperly grounded tools or equipment, or the

More information

Homeowner Information Guide Electrical Safety. British Columbia Safety Authority

Homeowner Information Guide Electrical Safety. British Columbia Safety Authority Homeowner Information Guide Electrical Safety British Columbia Safety Authority The following information should be carefully reviewed before performing any electrical work. The information contained in

More information

INSTALLATION GUIDELINES for SOLAR PHOTOVOLTAIC SYSTEMS 1

INSTALLATION GUIDELINES for SOLAR PHOTOVOLTAIC SYSTEMS 1 City of Cotati Building Division 201 W. Sierra Ave. Cotati, CA 94931 707 665-3637 Fax 792-4604 INSTALLATION GUIDELINES for SOLAR PHOTOVOLTAIC SYSTEMS 1 Any PV system on a new structures should be included

More information

Electrical Safety Tips. Help us keep you safe

Electrical Safety Tips. Help us keep you safe Electrical Safety Tips Help us keep you safe To help you stay safe when using electricity, ActewAGL has compiled these electrical safety tips. For natural gas safety tips please see ActewAGL s natural

More information

Please check with your local inspection authority for any additional requirements before installation.

Please check with your local inspection authority for any additional requirements before installation. Specifications for Residential Overhead Electric Service Installation This brochure addresses most typical residential overhead service installations. Variances for the following specifications must be

More information

GROWTH MANAGEMENT DEPARTMENT 201 SE 3 rd ST, (Second Floor), Ocala, FL 34471 (352) 629-8421; FAX: (352) 629-8264

GROWTH MANAGEMENT DEPARTMENT 201 SE 3 rd ST, (Second Floor), Ocala, FL 34471 (352) 629-8421; FAX: (352) 629-8264 BUILDING CODE GUIDELINES FOR ELECTRICAL INSPECTIONS Building Code compliance is the obligation of design professionals and/or contractors. Plan Review and Inspection Guidelines are intended to be used

More information

LOCK-OUT/TAG-OUT PROGRAM I. Purpose

LOCK-OUT/TAG-OUT PROGRAM I. Purpose LOCK-OUT/TAG-OUT PROGRAM I. Purpose This procedure establishes requirements for the lockout of energy isolating devices. It should be used to ensure that the machine or piece of equipment is isolated from

More information

Electrical Practices for Construction Work

Electrical Practices for Construction Work 1. Purpose Electrical Practices for Construction Work The purpose of this Code is to provide practical guidance and set minimum safety requirements for electrical practices on all construction sites in

More information

Mike Holt s Illustrated Guide to. Rule 220.87, Articles 445, 700, 701, and 702. Based on the 2011 NEC

Mike Holt s Illustrated Guide to. Rule 220.87, Articles 445, 700, 701, and 702. Based on the 2011 NEC Mike Holt s Illustrated Guide to NEC Requirements for Generators and Standby Power Systems Rule 220.87, Articles 445, 700, 701, and 702 Based on the 2011 NEC Extracted from Mike Holt s Illustrated Guides

More information

City of Riverside Building & Safety Division Phone: (951) 826-5697 www.riversideca.gov

City of Riverside Building & Safety Division Phone: (951) 826-5697 www.riversideca.gov City of Riverside Building & Safety Division Phone: (951) 826-5697 www.riversideca.gov PHOTOVOLTAIC PERMITTING GUIDELINES The information provided in this document is general and is intended only as a

More information

All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.

All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations. DIVISION 16 ELECTRICAL SECTION 16100 - ELECTRICAL PART 1 - GENERAL SCOPE All electrical work as shown on the drawings and as necessary to provide a complete electrical system. Include primary service,

More information

PORTABLE GENERATORS AND OSHA CONSTRUCTION REGULATIONS

PORTABLE GENERATORS AND OSHA CONSTRUCTION REGULATIONS PORTABLE GENERATORS AND OSHA CONSTRUCTION REGULATIONS Monograph by: John Grizzy Grzywacz, Professor OSHA National Training Institute Arlington Heights, Illinois Contributing: Michael Kovacic, President

More information

Electrical Safety Program

Electrical Safety Program California State University-Fullerton 800 N. State College Blvd. Fullerton, CA 92831 Prepared by: Paul A Zoubek, CSP, CIH President/Principal Consultant Zoubek Consulting, LLC 3737 Granada Ave. San Diego,

More information

2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1. 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.

2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1. 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. 2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. Relays) Part 1 General 1.1 CONDITIONS AND REQUIREMENTS: A. Refer to

More information

270526-TC Grounding and Bonding for Telecommunications Systems

270526-TC Grounding and Bonding for Telecommunications Systems 270526-TC Grounding and Bonding for Telecommunications Systems Part 1 - General Related Documents The following related sections of the OT standards shall also be applicable to this section. OT Engineer

More information

BRANDON AND CLARK INC. // SCOTT W. CLARK, P.E. ELECTRICAL CONTINUING EDUCATION ARC FLASH - NFPA 70E

BRANDON AND CLARK INC. // SCOTT W. CLARK, P.E. ELECTRICAL CONTINUING EDUCATION ARC FLASH - NFPA 70E BRANDON AND CLARK INC. // SCOTT W. CLARK, P.E. ELECTRICAL CONTINUING EDUCATION ARC FLASH - NFPA 70E Training is not a substitute for following corporate safety guidelines. Always refer to the latest safety

More information

What s up with Arc Flash?

What s up with Arc Flash? What s up with Arc Flash? Presented by Mark Haskins, CSP Practical Safety Solutions, LLC CONN OSHA Breakfast Roundtable February 18, 2014 2014 Practical Safety Solutions, LLC What is Arc Flash? Definition

More information

How To Plan Out An Array Of Solar Panels

How To Plan Out An Array Of Solar Panels CITY OF DOWNEY COMMUNITY DEVELOPMENT, BUILDING AND SAFETY 11111 Brookshire Avenue Downey, CA 90241 562.904.7142 (www.downeyca.org) B SECTION 01/01/2011 EFFECTIVE DATE PHOTOVOLTAIC 032 FORM NUMBER 2013

More information

County of Riverside Building and Safety Department

County of Riverside Building and Safety Department County of Riverside Building and Safety Department Mike Lara Director Photovoltaic Permitting Guidelines The information provided in this document is general and is intended only as a guide. Each project

More information

12 SOLAR PHOTOVOLTAIC POWER SUPPLY SYSTEMS by John Ware. PV modules are current-limiting

12 SOLAR PHOTOVOLTAIC POWER SUPPLY SYSTEMS by John Ware. PV modules are current-limiting 12 SOLAR PHOTOVOLTAIC POWER by John Ware IT IS PLANNED for BS 7671:2008 to include a new Section 712 providing additional requirements for safety applicable to solar photovoltaic (pv) power supply systems.

More information

Test Before Touch Easier Said Than Done. Ken Crawford, DuPont Kent Haggerty, Dupont

Test Before Touch Easier Said Than Done. Ken Crawford, DuPont Kent Haggerty, Dupont Test Before Touch Easier Said Than Done Ken Crawford, DuPont Kent Haggerty, Dupont Overview Test Before Touch (TBT) Principles Key Learnings by One Company One Method for Performing a TBT Induced Voltages

More information

Notes. Material 1. Portable Ground Fault Interrupter 2. PPE (safety glasses, gloves, other) 3. Circuit Tester

Notes. Material 1. Portable Ground Fault Interrupter 2. PPE (safety glasses, gloves, other) 3. Circuit Tester OSHA's electrical standards include: 29 CFR 1910 Electrical Subpart S, 1994 revision 29 CFR 1910.147 - Control of Hazardous Energy (Lockout/ tagout) 29 CFR 1910.137 - Personal Protective Equipment Standard,

More information

2011/2008/2005 NATIONAL ELECTRICAL CODE SOLAR PV CODE COMPLIANCE REFERENCE

2011/2008/2005 NATIONAL ELECTRICAL CODE SOLAR PV CODE COMPLIANCE REFERENCE 2011/2008/2005 NATIONAL ELECTRICAL CODE SOLAR PV CODE COMPLIANCE REFERENCE PAGE 1 OF 5 This Reference provides a very comprehensive list of aspects of a solar PV installation that could be reviewed, clarifying

More information

SOLAR PV STANDARD ELECTRICAL PLAN Microinverter Systems for Single Family Dwellings

SOLAR PV STANDARD ELECTRICAL PLAN Microinverter Systems for Single Family Dwellings *** Provide this document to the inspector along with ALL system installation instructions *** Project Address: Scope: Standard plan for the installation of grounded microinverter solar PV systems, not

More information

Requirements for the Attachment of Communication Cable Facilities on PPL Poles

Requirements for the Attachment of Communication Cable Facilities on PPL Poles Page 99 of 137 Requirements for the Attachment of Communication Cable Facilities on Replaces: URS-3002 URS-3004 URS-101C-304 A-157649 Page 100 of 137 Reference Notes for Drawings: General 1. The term communication

More information

ALVERNIA UNIVERSITY OSHA REGULATION: 29 CFR 1910.147 THE CONTROL OF HAZARDOUS ENERGY (LOCKOUT / TAGOUT) SECTION: 2400

ALVERNIA UNIVERSITY OSHA REGULATION: 29 CFR 1910.147 THE CONTROL OF HAZARDOUS ENERGY (LOCKOUT / TAGOUT) SECTION: 2400 OSHA REGULATION: 29 CFR 90.7 THE CONTROL OF HAZARDOUS ENERGY (LOCKOUT / TAGOUT) DATE: 0/5/2008 DATE: /2/202 A. POLICY. This procedure follows requirements set forth in 29 CFR 90.7. 2. It is the policy

More information

2014 NEC Guide Lines for Home Owner Doing Electrical Work on their Property

2014 NEC Guide Lines for Home Owner Doing Electrical Work on their Property 2014 NEC Guide Lines for Home Owner Doing Electrical Work on their Property A brief summary of the most used code references for residential wiring State of Idaho Division of Building Safety Electrical

More information

Short Circuit Current Calculations

Short Circuit Current Calculations Introduction Several sections of the National Electrical Code relate to proper overcurrent protection. Safe and reliable application of overcurrent protective devices based on these sections mandate that

More information

ELECTRIC METERING COMMERCIAL & INDUSTRIAL

ELECTRIC METERING COMMERCIAL & INDUSTRIAL ELECTRIC METERING COMMERCIAL & 1.0 INDEX 1.0 INDEX 2.0 SCOPE 3.0 GENERAL REQUIREMENTS 4.0 METER LOCATIONS 5.0 UNDERGROUND TERMINATIONS 6.0 METERING TRANSFORMER ENCLOSURES 7.0 SINGLE CUSTOMER METER INSTALLATIONS

More information

MISCELLANEOUS ELECTRICAL JOBS REQUIRING PERMITS

MISCELLANEOUS ELECTRICAL JOBS REQUIRING PERMITS MISCELLANEOUS ELECTRICAL JOBS REQUIRING PERMITS 01. SAFETY INSPECTION of service equipment at FPL Power Source 02. Construction GFI power outlets (Temp Pole for Construction) 03. 90 day temporary power

More information

Electrical Resistance Resistance (R)

Electrical Resistance Resistance (R) Electrical Resistance Resistance (R) Any device in a circuit which converts electrical energy into some other form impedes the current. The device which converts electrical energy to heat energy is termed

More information

SAFE ELECTRICAL WORK PRACTICES & 2015 NFPA 70E

SAFE ELECTRICAL WORK PRACTICES & 2015 NFPA 70E SAFE ELECTRICAL WORK PRACTICES & 2015 NFPA 70E This easy-to-use Leader s Guide is provided to assist in conducting a successful presentation. Featured are: INTRODUCTION: A brief description of the program

More information

ARC FLASH HAZARD OVERVIEW. Presented August 13, 2015 WWOA Lake Michigan District by Mead & Hunt, Inc.

ARC FLASH HAZARD OVERVIEW. Presented August 13, 2015 WWOA Lake Michigan District by Mead & Hunt, Inc. ARC FLASH HAZARD OVERVIEW Presented August 13, 2015 WWOA Lake Michigan District by Mead & Hunt, Inc. ARC FLASH EXPERIENCE Christopher J. DeWaal, MS, MEM, PE, LEED AP, HACCP How did I get involved? A client

More information

PLANT OPERATIONS ELECTRICAL SAFETY PROGRAM

PLANT OPERATIONS ELECTRICAL SAFETY PROGRAM PLANT OPERATIONS ELECTRICAL SAFETY PROGRAM Prepared by the Department of Occupational Safety & Environmental Health PLANT ELECTRICAL SAFETY PROGRAM TABLE OF CONTENTS Page I. Purpose and Scope 1 II. Definitions

More information

Electrocution Hazards

Electrocution Hazards Electrocution Hazards 1 Electricity Accidents People who work directly or indirectly with electricity can be the victims of serious electrocution injury or death on construction sites. These accidents

More information

Model 1756 Test Lead Kit

Model 1756 Test Lead Kit Keithley Instruments 28775 Aurora Road Cleveland, Ohio 44139 1-888-KEITHLEY http://www.keithley.com Model 1756 Test Lead Kit Gerneral Purpose Test Lead Information Description These test leads allow you

More information

CHAPTER 4 UTILITY SYSTEMS ELECTRICAL. Utility Systems Electrical. Main Panel

CHAPTER 4 UTILITY SYSTEMS ELECTRICAL. Utility Systems Electrical. Main Panel CHAPTER 4 UTILITY SYSTEMS ELECTRICAL Utility Systems Electrical The electrical supply to your home begins outside, where you will see either an overhead feed and piping down the side of your home or (if

More information

How to Estimate the Cost of a Clean Room and Data Center Equipment Electrical Work. Section 2 Types of Methods of Measurements page 4

How to Estimate the Cost of a Clean Room and Data Center Equipment Electrical Work. Section 2 Types of Methods of Measurements page 4 How to Estimate the Cost of a Clean Room and Data Center Equipment Electrical Work Table of Contents Section 1 Introduction page 3 Section 2 Types of Methods of Measurements page 4 Section 3 Project Specific

More information

Best Methods for Safe Hipot Testing

Best Methods for Safe Hipot Testing Best Methods for Safe Hipot Testing When working with electrical safety test equipment, instruments that output potentially dangerous voltages and currents, it is always important to regular review and

More information

Construction Electrical Terminology. Electricians

Construction Electrical Terminology. Electricians Construction Electrical Terminology Electricians Acknowledgments Winnipeg Technical College and the Department of Labour and Immigration of Manitoba wish to express sincere appreciation to all contributors.

More information

Questions and Answers for Heating and A/C Contractors

Questions and Answers for Heating and A/C Contractors 1. How do we accomplish grounding of furnaces and / or water heaters on two wire circuits? 250.134 Equipment Fastened in Place or Connected by Permanent Wiring Methods (Fixed) Grounding. Unless grounded

More information

RAY-MAX Integrated Solar Power Strip

RAY-MAX Integrated Solar Power Strip RAY-MAX Integrated Solar Power Strip 600008, 600009, 600010, 600208, 600209, 600210 Owner s Manual NEXTRONEX, INC. Revision Date: 10/27/14 Contents 1. Safety Instructions... 3 2. General Equipment Warnings...

More information

HAZARDS, INCLUDING SHOCK, ARC FLASH AND FIRE

HAZARDS, INCLUDING SHOCK, ARC FLASH AND FIRE Appendix B-2 - Electrical Safety In Design Final Report TECHNOLOGIES THAT REDUCE LIKELIHOOD OF INJURY FROM ELECTRICAL HAZARDS, INCLUDING SHOCK, ARC FLASH AND FIRE The following are technologies that reduce

More information

ELECTRICAL ENGINEERING DESIGN CRITERIA APPENDIX F

ELECTRICAL ENGINEERING DESIGN CRITERIA APPENDIX F ELECTRICAL ENGINEERING DESIGN CRITERIA APPENDIX F TABLE OF CONTENTS Appendix F - Electrical Engineering Design Criteria F.1 Introduction...F-1 F.2 Codes and Standards...F-1 F.3 Switchyard and Transformers...F-1

More information

Cal/OSHA Guide to. Electrical Safety. Cal/OSHA Consultation Service Research and Education Division of Occupational Safety and Health

Cal/OSHA Guide to. Electrical Safety. Cal/OSHA Consultation Service Research and Education Division of Occupational Safety and Health Cal/OSHA Guide to Electrical Safety Research and Education Division of Occupational Safety and Health This guide is not meant to be either a substitute for or a legal interpretation of the occupational

More information

BUILDERS AND CONTRACTORS GUIDE FOR ELECTRIC SERVICE

BUILDERS AND CONTRACTORS GUIDE FOR ELECTRIC SERVICE BUILDERS AND CONTRACTORS GUIDE FOR ELECTRIC SERVICE Toll Free Telephone Numbers Residential Services 800.454.3853 Commercial Services 800.653.5307 Utility Locating Company N.C. 800.632.4949 S.C. 888.721.7877

More information

Circuit Breakers and Switchgear. Thomas Greer Director of Engineering TLG Services

Circuit Breakers and Switchgear. Thomas Greer Director of Engineering TLG Services Circuit Breakers and Switchgear Thomas Greer Director of Engineering TLG Services Presentation Outline Switchgear Definition Overcurrent Protection Devices Circuit Breaker Trip Curves and Coordination

More information

OSHA 29CFR1910 Subpart S

OSHA 29CFR1910 Subpart S OSHA 29CFR1910 Subpart S By Michael V. Brown New Standard Institute It's the Law. Design safety related work practices for persons who install, maintain and repair electrical circuits or equipment, as

More information

CONSTRUCTION STANDARD ELECTRIC OPERATIONS ORGANIZATION

CONSTRUCTION STANDARD ELECTRIC OPERATIONS ORGANIZATION Page 1 of 11 ****This Standard Supercedes BECo CS2.13-2.3 & ComElectric OH Construction Manual, System Grounding Section, drawings CGND, GRDSUM, and C2**** 1.0 Bill of Materials GROUNDING AND BONDING POLE-MOUNTED

More information

CONTROL OF HAZARDOUS ENERGY/ LOCKOUT/TAGOUT PROGRAM

CONTROL OF HAZARDOUS ENERGY/ LOCKOUT/TAGOUT PROGRAM CONTROL OF HAZARDOUS ENERGY/ LOCKOUT/TAGOUT PROGRAM Northern Illinois University Department of Environmental Health and Safety March 2015, Rev 0 Review and Updates Date Reviewed by Changes Made Page 2

More information

Electrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, 2016. Underground branch circuit feeding a detached garage:

Electrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, 2016. Underground branch circuit feeding a detached garage: Electrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, 2016 * Garage construction requires permits (electrical, building) * Permits must be applied for at the time. * Dial

More information

CHECKING AND TESTING ELECTRICAL INSTALLING WORK

CHECKING AND TESTING ELECTRICAL INSTALLING WORK CHECKING AND TESTING ELECTRICAL INSTALLING WORK Department of Consumer and Employment Protection Energy Safety Preface It is a requirement of the Electricity (Licensing) Regulations 1991 that all electrical

More information

BWC Division of Safety and Hygiene

BWC Division of Safety and Hygiene BWC Division of Safety and Hygiene A SAMPLE LOCKOUT/TAGOUT PROCEDURE A good Lockout/Tagout Procedure, at a minimum, should contain the following elements: 1. All maintenance personnel shall be provided

More information

SWITCHGEAR Section 16. SECTION INCLUDES This Section includes service and distribution switchboards rated 600 V and less.

SWITCHGEAR Section 16. SECTION INCLUDES This Section includes service and distribution switchboards rated 600 V and less. PART 1 - GENERAL SECTION INCLUDES This Section includes service and distribution switchboards rated 600 V and less. RELATED SECTIONS Division 16 Section "Basic Electrical Materials and Methods" for general

More information

INTRODUCTION ARC FLASH PROTECTION AND SAFETY MEASURES. September 2010

INTRODUCTION ARC FLASH PROTECTION AND SAFETY MEASURES. September 2010 ARC FLASH PROTECTION AND SAFETY MEASURES September 2010 Introduction Hazards of Electrical Energy Electrical Safety Program Safety-Related Work Practices Electrical Safety Procedures Presented By: Ken

More information

What Are the Qualifications to Conduct Arc Flash Studies? Where Do You Begin?

What Are the Qualifications to Conduct Arc Flash Studies? Where Do You Begin? What Are the Qualifications to Conduct Arc Flash Studies? Where Do You Begin? Comparing apples-to-apples bids Plant Services Special Report A shock hazard analysis should be included as part of an arc

More information

Electrical Code Regulation

Electrical Code Regulation Electrical Code Regulation St. Clair County has adopted the 2005 National Electrical Code in its entirety for the unincorporated areas of the county and all communities that have contracted with the county

More information

EARTHING AND BONDING AT SECONDARY SUBSTATIONS

EARTHING AND BONDING AT SECONDARY SUBSTATIONS DISTRIBUTION CONSTRUCTION MANUAL SECTION 4 - SUBSTATIONS ISSUE B SEPT 1996 4.4.4 EARTHING AND BONDING AT SECONDARY SUBSTATIONS 1 SCOPE This section of the Distribution Construction Manual lays down the

More information

Arc Flash Mitigation. Remote Racking and Switching for Arc Flash danger mitigation in distribution class switchgear.

Arc Flash Mitigation. Remote Racking and Switching for Arc Flash danger mitigation in distribution class switchgear. Arc Flash Mitigation Remote Racking and Switching for Arc Flash danger mitigation in distribution class switchgear. Distance is Safety We will discuss through examples of actual occurrences and possible

More information