1 Operating Manual Trackball CHALLENGER TB GECMA COMPONENTS GMBH TEL FAX. -99 ATEX-MANUAL TB REV 1.1 EN.DOC A.J. 1
2 List of Contents List of Contents... 2 Introduction... 2 Assembly... 3 Pin Connections... 3 Technical Data... 4 Safety Instructions... 5 General Instructions... 6 Introduction The Challenger trackball (TB) is an intrinsically safe trackball for the application in zone 1. The trackball are available optional with up to 3 buttons. As a further option a variant with stainless steel trackball is available. It serves to control an ASD (Application Supporting Device) e.g. a PC terminal and it has been designed for the application in an explosion-endangered area. For the installation in Challenger components the Challenger FMO (display) must feature the option 2.PD. It is equipped with a PS/2 data interface for connection to an intrinsically safe data interface. CHALLENGER TB is a Microsoft -compatible trackball and it is also compatible with the standard Microsoft mouse driver. GECMA COMPENTS GMBH TEL FAX. -99 ATEX-MANUAL TB REV 1.1 EN.DOC A.J. 2
3 Assembly To ensure the international protection IP65 the trackball module has to be installed in a housing min. certified according to IP65 (with a cut-out of 153mm x 84mm and/or 6 x 3.3 ). The trackball module is inserted into the housing cut-out with its front side to the exterior and fastened from the inside via a minimum of four mounting clips which are evenly distributed over the external circumference of the joystick housing in such a way that the module is tight fitting. The electrical connection can be seen in the wiring diagram # and the license. Pin Connections Connection red or brown blue or white green or yellow white or green Significance Supply circuit +UB Supply / Data circuit GND Data Clock Details can be found in the wiring diagram # and the license. GECMA COMPENTS GMBH TEL FAX. -99 ATEX-MANUAL TB REV 1.1 EN.DOC A.J. 3
4 Technical Data International ignition protection: Operating temperature: (10 to 90% rel. humidity, n. c.) Zone 1 II 2G EEx ib IIC T4 Ex ib IIC T4 Ta: -20 C C (-4 F to 140 F) License: BVS 05 ATEX E 048 Housing material: Sheet steel / aluminum / PVC / stainless steel (depend of variant) Housing dimensions: see drawings International Protection Encl.:Front side IP65 with expert installation. Connection supply: Connection interface: Storage temperature: Supply voltage: connecting line connecting line -20 C C (-4 F to 140 F), 10 to 90% rel. humidity, n. cond. Via intrinsically safe supply unit with the technical data: U imax = 5,5 V, I imax = 85mA, P imax = 196mW C imax = 10uF, L i negligible Data circuit: Via intrinsically safe interface with the technical data: Ui max U imax U o U imax, I o I imax, P o P imax C imax = 10uF, L i negligible Resistivity of the trackball: Resistant to most detergents Further details can be found in the license. GECMA COMPENTS GMBH TEL FAX. -99 ATEX-MANUAL TB REV 1.1 EN.DOC A.J. 4
5 Safety Instructions General Safety Instructions The instructions stated in this chapter are to be followed accurately to ensure a safe and reliable operation. The license and the special conditions included in it are to be observed. Follow the national safety regulations and the accident prevention regulations. The installation is only to be performed by specialists. These specialists must be familiar with the characteristics of explosion-endangered facilities. Incorrect or inadmissible application as well as non-observance of the instructions of this operating manual make the guarantee void. Only use this device for the approved purpose. Conversions and modifications to the device are inadmissible. The housing is only to be opened by the company Gecma Components GmbH. Assembly The national assembly and installation regulations are to be observed. The generally accepted rules of engineering are to be observed. The entire equipment is to be connected and operated correctly and properly according to the applicable standards, guidelines and installation instructions. The housing is to be grounded via grounding equipment. Grounding must be effected with a core cross section of at least 4mm². The device is only to be connected in a de-energized condition. The intrinsically safe line system with supply and signal lines has to be effected in such a way that no error must be considered between the individual circuits, see IEC , Before putting the device into operation please ensure that the device has been installed as described and that the device and its wiring are not damaged. If the power supply of the device is not intrinsically safe, the license will become void and it must not be operated as an intrinsically safe device. Operation The device is only to be operated in an undamaged and clean condition. If the device has suffered any damages which might affect the international protection (e.g. cracks, holes or broken components) it must be taken out of service immediately. The device can only be put into operation again after the defect components have been exchanged. When the trackball is damaged, do not touch it any longer! Risk of injury! In the event of non-observance & non-compliance the stipulated explosion protection cannot be guaranteed and/or the guarantee will become void! Modifications require the written approval by the company GeCma Components GmbH. GECMA COMPENTS GMBH TEL FAX. -99 ATEX-MANUAL TB REV 1.1 EN.DOC A.J. 5
6 General Instructions Before starting the assembly read the entire operating manual! In cases of doubt (in the form of mistranslation) the German operating manual is to be applied. We do not assume liability for misprints and errors in this operating manual. Should you have any questions or suggestions please feel free to contact us any time: GeCma Components GmbH Heisenbergstraße D Kerpen Tel.: +49 (0)22 37 / Fax: +49 (0)22 37 / mailto:info@gecma.com Technical progress The manufacturer reserves the right to adjust all technical data without special announcement according to the technical progress. Repair work, hazardous material The description of the respective fault(s) is in any case to be included with the devices which are sent to GeCma Components GmbH for repair. The following measures are to be taken before sending a device in for repair: Please remove the entire adhering medium residue. Pay special attention to sealing grooves and gaps which might contain medium residue. We have to ask you to refrain from sending the device back if it is impossible for you to definitely guarantee that all health-endangering material has completely been removed. Costs which arise due to inadequate cleaning of the device for a potential disposal or for personal injury (cauterization, etc.) will be charged to the proprietor of the device. Used trademarks AT, IBM and PS/2 are registered trademarks of the International Business Machines Corporation. Microsoft, Windows and Windows NT are registered trademarks of Microsoft Corporation. All other trademarks mentioned and depicted in the text are trademarks of the respective owners and are recognized as registered. GECMA COMPENTS GMBH TEL FAX. -99 ATEX-MANUAL TB REV 1.1 EN.DOC A.J. 6
7
8
9
10
11
12
13
14
15
16
Operating Instructions
Important information: These instructions contain safety information, read and follow them carefully. Dialight will not accept any responsibility for injury, damage or loss which may occur due to incorrect
More informationExplosion proof enclosures
1 of 7 Explosion proof enclosures DE8 C 2 of 7 The Ex d enclosures are rugged and designed for harsh environment like: Oil and gas industry Chemical industry Pharmaceutical industry Agribusiness Without
More informationIsolating Barriers for our sensors A5S1 in Ex-areas Series D461
D46 Isolating Barriers for our sensors A5S1 in Ex-areas Series KEY FEATURES ATEX / IECEx certified, also approval for UL / CSA and EAC (Russia, Kazakhstan and Belarus Customs Union) Protection grade Ex
More informationFerrostat Speed Sensor Series DSF Explosion Proof Versions EEx
Ferrostat Speed Sensor Series DSF Explosion Proof Versions EEx DSF..10.**.HV Ex ATEX Operating Instructions 374E-64368 Valid from lot nr. 0103 General Function Use in potentially explosive environment
More informationATEX Installation Instructions for Micro Motion ELITE CMFS Sensors
Installation Instructions P/N MMI-20015054, Rev. AA May 2009 ATEX Installation Instructions for Micro Motion ELITE CMFS Sensors For ATEX-approved sensor installations Note: For hazardous installations
More informationOperating Instructions
Operating Instructions Cable Glands Ex d and Ex e with Compound > Contents 1 Contents 1 Contents...2 2 General Information...2 3 General Safety Information...3 4 Designated Use...4 5 Technical Data...4
More informationPLUGS & RECEPTACLES. INNOVATIVE EXPLOSION PROTECTION by R. STAHL 1-800-782-4357
Series Features: Color coding and pin configuration makes it physically impossible to mate plugs and receptacles of different voltages and current ratings (per IEC 60 309-2). Interlocked switch mechanism
More informationEX-TECH SAS CP/PB 150 EXPLOSIONPROOF MANUAL CALL POINT/ PUSH BOTTON TECHNICAL MANUAL
PRODUCT NAME: CP/PB -150- EXPLOSION-PROOF-MANUAL CALL POINT/ PUSH BOTTON DOC NO.: EX-TECH SAS-12-CP-PB150-TM REV01 EXPLOSION-PROOF MANUAL CALL POINT/ PUSH BOTTON II 2GD EPL Gb, Db Ex d IIC T6, IP66 Ex
More informationDRM75A 230V 20/100A DIN rail single phase two wire energy meter
DRM75A 230V 20/100A DIN rail single phase two wire energy meter 1.1 Safety instruction 1.2 Foreword 1.3 Performance criteria 1.4 Specifications 1.5 Basic errors 1.6 Description 1.7 Dimensions 1.8 Installation
More informationTechnical Data. Dimensions
0102 Model Number Features 15 mm quasi flush Usable up to SIL2 acc. to IEC 61508 Accessories BF 30 Mounting flange, 30 mm V1-G-N-2M-PUR Female cordset, M12, 2-pin, NAMUR, PUR cable V1-W-N-2M-PUR Female
More informationADM1TE 5/30A DIN rail single phase two wire energy meter
ADMTE 5/30A DIN rail single phase two wire energy meter. Safety instruction.2 Foreword.3 Performance criteria.4 Specifications.5 Basic errors.6 Description.7 Dimensions.8 Installation.9 Operating.0 Troubleshooting.
More informationDMP 331. Industrial Pressure Transmitter for Low Pressure. Stainless Steel Sensor
DMP Industrial Pressure Transmitter for Low Pressure Stainless Steel Sensor accuracy according to IEC 60770: standard: 0.5 % FSO option: 0.5 / 0. % FSO from 0... 00 mbar up to 0... 40 bar Output signals
More informationControl- and feedback head for integrated mounting on Robolux valves Type 2036
Control- and feedback head for integrated mounting on Robolux valves Type 203 Type 885 Type 88 can be combined with Compact stainless steel design Contactless valve position registration Coloured illuminated
More informationRedundancy Module QUINT-DIODE/40
Redundancy Module QUT DIODE provides: 00% decoupling of power supplies connected in parallel Can be installed in potentially explosive areas Load currents up to 60 A supported Easy assembly by snapping
More informationInductive sensor NI10-M18-Y1X-H1141
ATEX category II 1 G, Ex zone 0 ATEX category II 1 D, Ex zone 20 SIL2 as per IEC 61508 Threaded barrel, M18 x 1 Chrome-plated brass DC 2-wire, nom. 8.2 VDC Output acc. to DIN EN 60947-5-6 (NA- MUR) M12
More informationTechnical data sheet TDS0070
Technical data sheet TDS0070 ATEX Certified II 2 G Ex d IIC T4 Gb IECEx Certified Ex d IIC T4 Gb Ta = -20ºC to +60ºC FEATURES INCLUDE: - ATEX and IECEx Certified explosion proof Exd housing for Premier
More informationHLC A1... HLC B1... HLC F1... Data Sheet. Load cells. Special features. B2325-1.0 en
HLC B1... HLC F1... HLC A1... HLC B1... HLC F1... Load cells Special features -- Hermetically sealed (IP68) -- Max. capacities: 220 kg... 10 t -- Stainless steel -- Low overall height -- Meets EMC/ESD
More informationThreaded Resistance Thermometers Model TR10-D, Miniature Design
Electrical Temperature Measurement Threaded Resistance Thermometers Model TR10-D, Miniature Design WIKA Data Sheet TE 60.04 Applications Machine building, plant and tank construction Power transmission
More informationSYSTEM DESCRIPTION Termination Boards
PROCESS AUTOMATION SYSTEM DESCRIPTION Termination Boards Non-IS Termination Boards for Yokogawa CENTUM C3 and ProSafe RS ISO9001 With regard to the supply of products, the current issue of the following
More informationFloodlight Range Installation Guide
SPARTAN Floodlight Range Installation Guide CML13ATEX3007 IEC Ex CML14.0001 This installation guide provides instructions for installing the Infra-Red and White-Light SPARTAN SPX series of explosion protected
More information2.12. page 223 2.12. Products for Explosion hazardous Environment
2.12 page 223 2.12 Products for Explosion hazardous Environment Non-electric valves for explosion 2.12.1 page 224 hazardous environment The following manually and mechanically actuated valves are available
More informationHSP GmbH Zum Handwerkerhof 2 90530 Wendelstein Tel. 09129 / 2852-0 Fax: 09129 / 2852-11 Web: www.hsshsp.de EMAIL: HSP@hsshsp.de NTG-3000.
NTG-3000 Transducer Data Sheet Document Version 2.8 Page 1 of 10 Versions / Revisions: Document Creation Author Description version date 2.0 2012-07-25 P. Compensis First official version 2.1 2012-08-24
More informationOriginal instructions Tina 3A/Aps Adaptor unit
Original instructions Tina 3A/Aps Adaptor unit ABB Jokab Safety Varlabergsvägen 11, SE-434 39 Kungsbacka, Sweden www.abb.com/jokabsafety Read and understand this document Please read and understand this
More informationTina 2A/B Adaptor unit
Original instructions Tina 2A/B Adaptor unit ABB Jokab Safety Varlabergsvägen 11, SE-434 39 Kungsbacka, Sweden www.abb.com/jokabsafety Read and understand this document Please read and understand this
More informationSEISMIC VELOCITY TRANSDUCER T1-40
SEISMIC VELOCITY TRANSDUCER T1-40 Measurement of Omnidirectional Absolute Vibrations Certified according to ATEX 94/9/CE directive OPERATION Transducer T1-40 serves for seismic measurement of the absolute
More informationMagnetic field sensor for pneumatic cylinders BIM-INT-Y1X-H1141
ATEX category II 1 G, Ex zone 0 ATEX category II 1 D, Ex zone 20 SIL2 as per IEC 61508 Rectangular, height 6mm Plastic, PA12 Magnetic-inductive sensor DC 2-wire, nom. 8.2 VDC Output acc. to DIN EN 60947-5-6
More informationAir Sensor. SAC Ex. Manual ATEX. AQ Elteknik AB
Air Sensor SAC Ex Manual AQ Elteknik AB ATEX Air Sensor SAC Ex ATEX Certified model Manual version 2.0 Oct 2010 AQ Elteknik AB 2 Table of contents 1. Manufacturer information... 4 Manufacture Declaration
More informationR4D0-FB-IA* FieldBarrier. Features. Assembly. Function. Connection IN + - S OUT ... ... Spur 2. Spur 1. Zone 1. Zone 0
FieldBarrier Features Assembly 8... 12 outputs Ex ia IIC, FISCO and Entity Advanced fault isolation and diagnostics at the spur FieldBarrier in Zone 1/Div. 2 Instruments in Zone 0...1/Div. 1 For FOUNDATION
More informationTechnical Data. General specifications Switching element function Rated operating distance s n 15 mm
0102 Model Number Features Comfort series 15 mm flush Accessories MHW 01 Modular mounting bracket MH 04-2057B Mounting aid for VariKont and +U1+ Technical Data General specifications Switching element
More informationInstructions for Safe Use
Instructions for Safe Use (Certification N:o VTT 08 ATEX 029) Thank you for choosing Slam Trans portable transformer for your job site. Purpose of this manual is to provide you all the necessary safety
More informationMINI MCR-SL-R-UI(-SP)
Resistance/potiposition transducer INTERFACE Data Sheet 0807_en_05 Description PHOENIX CONTACT - 0/008 Features The slim MINI MCR-SL-R-UI... potiposition transducer has a width of only 6. mm and converts
More informationTechnical Data. General specifications Switching element function Rated operating distance s n 5 mm
0102 Model Number Features 5 mm flush Usable up to SIL 2 acc. to IEC 61508 Accessories EXG-18 Quick mounting bracket with dead stop BF 18 Mounting flange, 18 mm Technical Data specifications Switching
More informationMaterial: Weight: Bearing Life: Shaft Loads: Operating Temp.: Storage Temp.: Shock: Vibration: Bump: Humidity: Enclosure Rating: Cable: Cable Glands:
Oil & Gas / Heavy Industry EX-Proof Stainless Steel Shaft Encoder - Ø 68 mm Shaft - Ø 10 mm to Ø 5/8 inch Resolution up to 10,000 ppr IP 66 (IP 67 option) ATEX certified EX-Proof IECEx certified EX-Proof
More informationalpha DSL WTM EG Instructions for use ADSL-Modem alpha DSL WTM EG
alpha DSL WTM EG Instructions for use ADSL-Modem alpha DSL WTM EG Safety precautions Safety precautions The DSL modem alpha DSL WTM EG complies with the European norm EN60950 safety of information technology
More informationOperating instructions Diffuse reflection sensor. OJ50xx 701396 / 01 07 / 2004
Operating instructions Diffuse reflection sensor OJ50xx 7096 / 0 07 / 004 Contents Preliminary note. Symbols used Function and features Installation. Installation of the supplied mounting fixture 4 4 Electrical
More information3DLevelScanner II TECHNICAL DATA SHEET
TECHNICAL DATA SHEET Changing the market from level to volume APM`s 3DLevelScanner incorporates advanced technology for accurately measuring bulk solids and powder stored in silos and open bins of all
More informationLED...A70..4-..Q Series Sealed High-Intensity
LED...A70..4-..Q Series Sealed High-Intensity Area Lights High-Power Lighting for use with PresencePLUS and Other Vision Systems Features Rugged, waterproof housing, rated IEC IP68 Compact area light for
More informationVdS 2100-09en. VdS Guidelines for water extinguishing systems. Non-return valves. Requirements and test methods. VdS 2100-09en : 2011-05 (01)
VdS Guidelines for water extinguishing systems VdS 2100-09en Requirements and test methods VdS 2100-09en : 2011-05 (01) Publishing house: VdS Schadenverhütung GmbH Amsterdamer Str. 172-174 50735 Köln,
More informationUser s Manual Before using the inverter, you need to read and save the safety instructions.
User s Manual Before using the inverter, you need to read and save the safety instructions. STI SERIES (STI200, STI300, STI500, STI700, STI1000) Power Frequency Pure Sine Wave Inverter The information
More informationATL Fuel Level Sender Probes
T E C H N I C A L S P E C I F I C A T I O N The ATL EL-AD-151 (Resistance Output) and EL-AD-152 (Voltage Output) Fuel Level Senders are highly advanced sensors for continuously measuring the contents of
More informationOPTICAL HEADEND PLATFORM OTOHP-NMS NETWORK MONITORING MODULE INSTRUCTION MANUAL
OPTICAL HEADEND PLATFORM OTOHP-NMS NETWORK MONITORING MODULE INSTRUCTION MANUAL Phone: (209) 586-1022 (800) 545-1022 Fax: (209) 586-1026 OTOHP-NMS Rev. X1 E-Mail: salessupport@olsontech.com www.olsontech.com
More informationCable Plug acc. to DIN EN 175301-803, Form A
Cable Plug acc. to DIN EN 175301-803, Form A Complete program Contact form 18 mm Also available with LED indicator Optional 4-pin version for pressure switch or impulse valves respectively Versions with
More informationInstruction Manual Differential Pressure Transmitter
DE28 Instruction Manual Differential Pressure Transmitter Table of Contents 1. Safety Instructions 2. Intended Applications 3. Product Description and Functions 4. Installation 5. Commissioning 6. Maintenance
More informationGREISINGER electronic GmbH
T38.0.0X.6C-03 CO2 - Transmitter Operating Manual GT10 - CO2-1R GREISINGER electronic GmbH D - 93128 Regenstauf, Hans-Sachs-Straße 26 Tel.: +49 9402 / 9383-0, Fax: +49 9402 / 9383-33, email: info@greisinger.de
More informationInstallation instruction
1/5 ATTENTION! Mounting and dismounting of a shrink disc must be restricted to qualified personnel. Incorrect handling may cause injury to persons and damage to machines! At work, with heavy parts and
More informationDesign of intrinsically safe systems
AUTOMATION & C O N T R O L S W here intrinsically safe apparatus is interconnected by wiring, the safety of each piece of apparatus is affected by the performance of the other pieces of apparatus in the
More informationOptions for ABB drives, converters and inverters. User s manual FDPI-02 diagnostics and panel interface
Options for ABB drives, converters and inverters User s manual FDPI-02 diagnostics and panel interface Table of contents Table of contents 3 1. FDPI-02 diagnostics and panel interface Safety..............................................
More informationControl and Distribution Boxes made of Stainless Steel Series 8150
www.stahl.de > Circumferential protection channel prevents water entry > Extended temperature range due to high-quality seal s > Optionally with hinges / cam locks or screw-on cover > Hinge versions with
More informationINSTALLATION OPERATION AND MAINTENANCE INSTRUCTIONS FOR EXHEAT INDUSTRIAL IMMERSION HEATERS (INCLUDING FLAMEPROOF)
INSTALLATION OPERATION AND MAINTENANCE INSTRUCTIONS FOR EXHEAT INDUSTRIAL IMMERSION HEATERS (INCLUDING FLAMEPROOF) Please read these instructions thoroughly before installation and ensure they are passed
More informationDocumentation for. KL2602 and KL2622. Two-channel Relay Output Terminals for 230 V AC / 30 V DC. Version: 1.4 Date: 2013-03-20
Documentation for KL2602 and KL2622 Two-channel Relay Output Terminals for 230 V AC / 30 V DC Version: 1.4 Date: 2013-03-20 Table of contents Table of contents 1 Foreword 1 1.1 Notes on the documentation
More informationMounting instructions. Junction box VKK2R-8 DIGITAL. A1145-1.0 en
Mounting instructions Junction box VKK2R-8 DIGITAL VKK2R-8 DIGITAL 3 Contents Page Safety instructions... 4 1 Introduction and appropriate use... 7 2 Mechanical construction... 8 2.1 Mounting... 9 3 Electrical
More informationINSTALLATION AND OPERATING INSTRUCTIONS LEVEL SENSOR
INSTALLATION AND OPERATING INSTRUCTIONS LEVEL SENSOR 1. FUNCTIONAL DESCRIPTION: 2 2. APPLICATION: 2 3. ASSEMBLY: 2 4. HAZARD NOTICES: 2 5. ELECTRICAL CONNECTION: 3 6. OPTIONS: 3 7. CAUTION: 3 8. MAINTENANCE:
More informationPump_TM016. Local Display. 4-20mA. PLC/DCS Case 1. Relay Output Module. 4-20mA. Modbus. Optional. Case 2. Pump. Pump PT371 PT373 PCM370
Pump_TM016 Pump Local Display TM0200 TM0200 4-20mA PLC/DCS Case 1 Pump Relay Output Module 4-20mA Optional PT371 Modbus PT373 Case 2 PCM370 TM016 Velocity/ Acceleration Vibration Transmitter Introduction
More informationSeries 8146/5-V37 and Series 8150/5-V37
www.stahl.de > Clear assignment safe technology easy installation > Intelligent structure only one rotary actuator for frequency-controlled drives ) 20 ms leading auxiliary contact for safe motor disconnection
More informationKAB-ADAPT-LVDStoTTL. Document Revision 1.0
KAB-ADAPT-LVDStoTTL Document Revision 1.0 KAB-ADAPT-LVDStoTTL Contents 1. USER INFORMATION...1 1.1 About This Document...1 1.2 Copyright Notice...1 1.3 Trademarks...1 1.4 Standards...1 1.5 Warranty...2
More informationACS-30-EU-EMDR-10-MOD
Multi-application heat tracing Control and Monitoring in commercial and residential buildings Roof & Gutter de-icing sensor module Technical Information Approvals Module IP rating Ambient operating temperature
More informationBroadBand PowerShield. User Manual
BroadBand PowerShield User Manual 990-0375G 12/2006 Chapter 1 General Information The PowerShield provides a power source for broadband telephony and other DC applications. Safety This Safety Guide contains
More informationSafety instructions VEGAFLEX FX8*(*).FC/ O****A/H*****
Safety instructions VEGAFLEX FX8*(*).FC/ O****A/H***** FM 3046039 Class I Div 1, Groups A, B, C and D Class II Div 1, Groups E, F and G; Class III Class I, Zone 0, AEx ia IIC Ga, Ga/Gb, Gb Document ID:
More informationElectronic Pressure Switch EDS 300
Electronic Pressure Switch EDS 300 User manual Page 2 of 16 Content 1. Functions of the EDS 300...3 2. Mounting...3 3. Operating keys on the membrane keypad...4 4. Digital display...4 5. Output function...5
More informationINSTALLATION INSTRUCTIONS
INSTALLATION INSTRUCTIONS Electric Vacuum Pump Kit 28146 Thank you for choosing STAINLESS STEEL BRAKES CORPORATION for your braking needs. Pleases take the time to read and carefully follow these instructions
More informationRelative pressure transmitter type 520
Relative pressure transmitter type 520 Pressure range -1... 9 bar / 0... 2.5 1000 bar The compact type 520 pressure transmitter is based upon the Huba Control developed thick film technology where the
More informationPTB 07 ATEX 2048. Example/Beispiel/Exemple. Flipperventil 6144. Operating Instructions
PTB 07 ATEX 2048 Geräte mit IIC 2G EX ia Zulassung Device with IIC 2G EX ia approval Appareils avec mode de protection IIC 2G EX ia Example/Beispiel/Exemple Flipperventil 6144 Operating Instructions Bedienungsanleitung
More informationLinear Luminaire with LED Series EXLUX 6402/2
> Latest LED technology with a high luminous efficacy and a long service life > As pendant light fitting or side entry lamp > Central locking > All-pole disconnection by means of an N/C switch when the
More informationModel 201 Wiegand Touchpad Reader Installation Guide
Model 201 Wiegand Touchpad Reader Installation Guide P/N 460353001C 15AUG11 2011 UTC Fire & Security. All rights reserved. This document may not be copied in whole or in part or otherwise reproduced without
More informationFLUORESCENT UV- RING LIGHT OPERATING INSTRUCTION
FLUORESCENT UV- RING LIGHT OPERATING INSTRUCTION Caution! UV-radiation of this device is in the range of UV-A (320-400 nm). Direct exposure to eyes shall therefore be avoided. UV protection glasses shall
More informationPlug and Socket Devices SolConeX 16 A Series 8570
www.stahl.de > Switch socket / plug 16 A > Minimal force required to insert and remove > Can be optionally equipped with an auxiliary contact for control and signalling purposes > arge switching handle
More informationAmmeter / Voltmeter Series 8402, 8403, 8405, 8404
/, 8403, 8405, 8404 > Fast comparison of measured with set values > s available, 8403 and 8402 www.stahl.de, 8403, 8405, 8404 10073E00 The ammeters and voltmeters from R. STAHL are explosion protected,
More informationGEARBOX MONITOR MODEL NR. 1.1203 USER MANUAL
GEARBOX MONITOR MODEL NR. 1.1203 USER MANUAL USER SAFETY Before starting to drive with a mounted gearbox monitor you need to make sure that: the monitor does not limit field of vision of the driver; monitor
More informationEtherNet-RS232/485. London Electronics Limited. Ethernet to RS232 or RS485 data converter. Connection details and general information
London Electronics Limited Warren Court, Chicksands, Shefford, Bedfordshire SG17 5QB Tel +44(0)1462-850967 Fax +44(0)1462-850968 www.london-electronics.com help@london-electronics.com Ethernet to RS232
More informationModular I/O System Analog and Digital Interface Modules
OPERATING INSTRUCTIONS Modular I/O System Analog and Digital Interface Modules Installation Operation Maintenance Document Information Document ID Title: Operating Instructions Modular I/O System Part
More informationStructureScan HD Module. Installation Guide ENGLISH. www.bandg.com www.simrad-yachting.com www.lowrance.com
StructureScan HD Module Installation Guide ENGLISH www.bandg.com www.simrad-yachting.com www.lowrance.com Disclaimer As Navico is continuously improving this product, we retain the right to make changes
More information5SV Residual Current Protective Devices
s Siemens AG 2013 SENTRON 5SV Residual Current Protective Devices New portfolio for reliable personnel, material and fire protection Safe protection against residual currents Residual current protective
More informationINFRARED QUARTZ WALL HEATER
INFRARED QUARTZ WALL HEATER MODEL NO: IQ2000 PART NO: 6939004 MOUNTING & OPERATION INSTRUCTIONS GC0715 INTRODUCTION Thank you for purchasing this CLARKE Infrared Wall Heater. Before attempting to use this
More informationAmmeter / Voltmeter Series 8402, 8403, 8405, 8404
/, 8403, 8405, 8404 > Fast comparison of measured with set values > s available, 8403 and 8402 www.stahl.de, 8403, 8405, 8404 10073E00 The ammeters and voltmeters from R. STAHL are explosion protected,
More information3500/93 System Display
3500/93 System Display Bently Nevada* Asset Condition Monitoring Description The 3500/93 System Display is designed to meet the requirements of American Petroleum Institute (API) Standard 670 and provide
More informationPeak Atlas IT. RJ45 Network Cable Analyser Model UTP05. Designed and manufactured with pride in the UK. User Guide
GB05-6 Peak Atlas IT RJ45 Network Cable Analyser Model UTP05 Designed and manufactured with pride in the UK User Guide Peak Electronic Design Limited 2001/2012 In the interests of development, information
More informationTerminal Boxes Series 8146
Series > Enclosures in shock-resistant glass fibre reinforced polyester resin > basic enclosure sizes various heights > Fitted according to the customer's requirements > For terminals up to max. 00 mm
More informationUM-X Field display for continous level sensors
Technical Documentation Field display for continous level sensors 10/2007 Edition: 1 Item No.: 207120 FAFNIR GmbH Bahrenfelder Str. 19 D-22765 Hamburg Telephone: +49 (0)40-39 82 07-0 Fax: +49 (0)40-3 90
More informationCombi B Alarm box. Mounting instructions
Combi B Alarm box Mounting instructions EN Mounting instructions Alarm box Combi B VdS, G113064, G113065, G113066 Table of Contents 1 Description... 3 2 System overview... 3 3 Structure... 3 3.1 Power
More informationLaser diffuse reflection light scanner with background suppression. Dimensioned drawing
Specifications and description HRTL 3B Laser diffuse reflection light scanner with background suppression Dimensioned drawing We reserve the right to make changes DS_HRTL3B_en.fm en 01-2010/12 50114049
More informationType testing 07.09.2006
I G R Interessengemeinschaft Regelwerke Technik Editor: R&M Prozesstechnik GmbH MSR- und Analysentechnik, D 710 M. Dietz 069 / 305-26 63 Kompetenzcenter EMR Test report no. IGR 110615 Type testing 07.09.2006
More informationFCC COMPLIANCE STATEMENT FOR AMERICAN USERS
FCC COMPLIANCE STATEMENT FOR AMERICAN USERS This equipment has been tested and found to comply with the limits for a CLASS A digital device, pursuant to Part 15 of the FCC Rules. These limits are designed
More informationTechnical Data. General specifications Switching element function Rated operating distance s n 5 mm
0102 Model Number Features 5 mm non-flush Usable up to SIL 2 acc. to IEC 61508 Technical Data specifications Switching element function NAMUR, NC Rated operating distance s n 5 mm Installation non-flush
More information48-B-5-08-KIT 5-Wire Resistive Controller (USB) Specification Guide
48-B-5-08-KIT 5-Wire Resistive Controller (USB) Specification Guide Document Number: 6500268 Rev. 2.0 Pg. 1 The information provided in this document is intended as a guide only and is subject to change
More informationCHALLENGER. Remote PC Terminals
CHALLENGER Remote PC Terminals For modern Operation and Visualization on site in Zone 1 / 2 and Zone 22 (Class 1, Zone 1 / Class 1, Div.2) A member of the MTL Instruments group CHALLENGER 15i Remote PC-Terminal
More informationCONTOIL DFM 8EDM. Table of contents. Mounting and operating instructions
Mounting and operating instructions CONTOIL DFM 8EDM Table of contents Safety instructions 2 - Designed use - Installation, commissioning and operation - Operational safety - Return of the instruments
More informationEE-SPY801/802. Photomicrosensors for detecting wafer-carrier mounting. Wafer-carrier Mounting Photomicrosensors. Ordering Information.
Wafer-carrier Mounting Photomicrosensors EE-SPY1/ CSM_EE-SPY1 DS_E_3_ Photomicrosensors for detecting wafer-carrier mounting. The mounting position is set with a pedestal. The contact surface with the
More informationModel CS 64 Mini-DIN Cable and Adaptor
Model CS 64 Mini-DIN Cable and Adaptor Page 1 of 9 Features Hi-Pro and NOAHlink compatible cable & Mini-DIN CS 64 Clip Module / NOAHlink Adaptor #1 Integrated Clip Module - Mini-DIN Cable Integrated NOAHlink
More information550-xx05-004. 5mm LED CBI. Circuit Board Indicator Square Back Housing, Quad Block. 5 5 0 - x x 0 5-0 x 4
5mm LED CBI Circuit Board Indicator Square Back Housing, Quad Block 5.9 [.235] 3.8 [.145].35 [.250].35 [.250] 25 [.985].35 [.250] Red Cathode for Red/Green Bi-Color Cathode for /Green Bi-Color RECOMMENDED
More informationInstruction Manual. T3111 T3111L T3111P T3111Ex
www.cometsystem.cz Instruction Manual T3111 T3111L T3111P T3111Ex Programmable transmitter of temperature, relative humidity and other calculated humidity values with external probe and 4-20 ma outputs
More informationAutoLink Three-Phase Sectionalizer Specifications. Scope. General. Applicable Standards. Operating principle
Scope This specification stipulates the minimum requirements for mechanically linked three-phase electronic sectionalizers, for use on outdoor medium voltage overhead lines of 15, 27, and 38 kv. Electronic
More information1 Safety instructions. 2 Device components. Facility Pilot Server. Art. No. : FAPV-SERVER-REG Art. No. : FAPVSERVERREGGB. Operating instructions
Facility Pilot Server Art. No. : FAPV-SERVER-REG Facility Pilot Server Art. No. : FAPVSERVERREGGB Operating instructions 1 Safety instructions Electrical equipment may only be installed and fitted by electrically
More informationProgrammable set for Ethernet Modbus/TCP in IP67 TI-BL67-PG-EN-2
Type code Ident no. 1545065 Number of channels 2 Dimensions (W x L x H) 108 x 145 x 77.5 mm CoDeSys-programmable acc. to IEC 61131-3 Cable max. 50 m between interface and read/write head 10/100 Mbps Male
More informationTechnical data. General specifications. Indicators/operating means. Electrical specifications Operating voltage U B Power consumption P 0 Interface
Release date: 06-0- 09: Date of issue: 06-0- 009_eng.xml Model Number Single head system Features Parameterization interface for the application-specific adjustment of the sensor setting via the service
More informationLinear Luminaire for Fluorescent Lamps Series EXLUX 6001
> As wall, ceiling and pendant light fitting or side entry lamp > Version with 2 lamps: 18 W, 36 W and 58 W > Central locking > All-pole disconnection by means of an N/C switch when the lamp is opened
More informationRHE12. Hazardous Area Coriolis Mass Flow Transmitter. Features. Applications. Benefits
RHE12 Hazardous Area Coriolis Mass Flow Transmitter Features Field mounting Compact, pressure safe housing ATEX and CSA approvals for installation in hazardous areas 24 VDC power supply Configurable analog
More informationName Description Model Number. Parameters Min. Typ. Max. Note. Vaux Voltage 9.8 V 12 V 13.2 V Auxiliary Supply Voltage
Description Supports DALI interface driver Programming Supports 0-10V Programmable Driver Programming Supports Other Controllers (TDD-ANPNx, SDD-AAPNx) Off-line programming capability Auto programming
More informationFlameproof Audible Signal 115 db (A) Series YA90
Clifford Snell www.stahl.de > Max sound output 115 db (A) / 1 m > 2 stage alarm, independently selectable 2nd stage > IP66 rated as standard > 32 selectable tones meeting international regulations > Light
More informationOperating Manual UMB Analogue/Digital Converter ANACON Order Number: 8160.UANA
Order Number: 8160.UANA Status: V6; 1425.03.2010 G. Lufft Mess- und Regeltechnik GmbH, Fellbach, Germany 1 TABLE OF CONTENTS PLEASE READ BEFORE USE... 3 DESCRIPTION... 5 ANACON UMB ANALOGUE/DIGITAL CONVERTER...
More informationOperating Instructions. Room temperature controller
Operating Instructions 1. Area of application The room temperature controller is used to regulate the temperature in closed rooms such as flats, schools, function suites, workshops, etc. Safety instructions
More information