Calibration of Building Simulation Model by Using Building Automation System a Case Study

Size: px
Start display at page:

Download "Calibration of Building Simulation Model by Using Building Automation System a Case Study"

Transcription

1 Calibration of Building Simulation Model by Using Building Automation System a Case Study Hannu Keränen, Tuomas Suur-Uski, Mika Vuolle HVAC-Laboratory, Helsinki University of Technology, P.O. Box 4400, Hut 02015, Finland Corresponding hannu.keranen@tkk.fi SUMMARY A thermal simulation program called IDA-ICE was used in the evaluation of the energy efficiency and indoor climate of a pilot-building in Jyväskylä, Finland. The simulation model was calibrated concerning the heating and cooling energy, because the performance of the building was evaluated using results of the calibrated simulation model as reference to the measured performance. The calibrated simulation model was built for continues commissioning. This paper explains the calibration process and its results. The measured and calculated energy use of the building corresponded to each other as the result of the calibration. INTRODUCTION The purpose of the study was to evaluate, how calibrated simulation model can be used in assessment of the building energy performance. The heat use and electricity use of the HVACsystem were evaluated as well as the indoor temperatures. In the year 2003 the first version of the simulation model was established and the pilotbuilding was constructed. The measured and simulated results differed from each other about 30 % concerning the heat use and 15 % concerning the electricity use in the first year. The results are presented more exactly in sources [1] and [2]. The simulation model was calibrated utilizing building automation system (BAS) and building energy management system (BEMS). The building automation system was used in determining the ventilation air flow rates, the set point temperatures of the room devices and of the supply air. The air flow rates, which were underestimated in the original model, were corrected to the calibrated model. The measured air flow rates and temperature of the supply air and the electricity use of the lighting and the office devices were used as time dependent input parameters in the simulation model. The building energy management system was utilized in determination of the electricity use and the heat use of the building. The input files needed in the simulations were generated from BAS and BEMS. The indoor temperatures were evaluated using duration curves concerning utilization time of the building. The duration curves were also compared to the simulated temperatures. Basic Information of the Building The case building is situated in Jyväskylä, 350 km from the Finnish capital, Helsinki. The building gives accommodation for the Department of Information Technology of Jyväskylä

2 Polytechnic. The construction works was finished by May 2003 and the building was taken into actual use in August The five-storey building consists mainly of classrooms. The building has also an assembly hall, a library, an auditorium, a lunchroom, a kitchen and a bomb shelter, which are situated in the ground floor. The working rooms of teachers are situated in the fifth floor. The floor area of the Pilot building is approximately m 2 and its exterior volume is m 3. Over students are studying and more than 40 teachers and other personnel are working in the building. The Principle of the HVAC System The classrooms and the working rooms of the case building have heating and cooling panels detached from the ceiling. Floor heating is used all over the ground floor. The conventional radiators are not used for heating. The building is heated by district heating and it is cooled by electricity using two refrigeration compressors and one storage tank and in addition free cooling by outdoor air is used. The ventilation system has combined heating-cooling-free cooling coils and a rotating heat recovery unit. HVAC-system has also a mechanism, which recovers the indoor overheat from the cooling panel s liquids to the supply air. The innovative patented system is advance low temperature heating system. The principle of the HVAC-system is explained in reference [3]. The building is conditioned using an integrated heating, ventilation and cooling system. The heating and cooling liquids are transferred through a 3-pipe system with common return liquid. The HVAC-system is presented in figure 1. The building has variable air volume (VAV) ventilation system [4], which is controlled with the both indoor air temperature and carbon dioxide level [5]. EMS and BEMS The case building has separate energy building management system (EMS) and building automation system (BAS). BES measures hourly heat, electricity and cold water uses. Measured values are reported monthly, daily and hourly using tables and figures. Heat use, which is weather corrected by degree day method, is also available. Besides the control of the HVAC-system, building automation system measures temperatures in 20 of the total 50 rooms, temperatures of liquids, position of valves, rotation speeds of the motors of fans and pumps as well as chamber pressures in air-handling-units. Also timetables of the AHUs and set points and set point curves can be viewed on the BAS. BAS can be used over internet, using a password protected user interface. A part of the measured data is saved to the BAS server of the case building, and it can be transferred trough the Internet using three file formats, HTML, CSV and XML. CSV-protocol was used in the evaluation of the performance of the building.

3 Air-handling unit Incoming air Water to air heat exchanger Water to air heat exchanger Supply air Rotating heat recovery system Exhaust air Return air Cooling tank Water to water heat exchanger Water to water heat exchanger ROOM Cooling of rooms Heating of supply air Cooling panels Heating panels District heating Heating and cooling liquids are merged Figure 1 The HVAC-system of case building METHODS Simulation Program IDA-Indoor Climate and Energy is a program designed for studying the indoor climate of zones of a building and for simulating energy consumption of a building [6]. IDA-ICE is an extension to an IDA simulation environment and an advanced user can simulate any system with the aid of the general functionality of the IDA simulation environment.

4 In normal circumstances, the building to be simulated consists of one or more zones and a primary (heat producing) system and one or more air handling units. The weather data is supplied by weather data files or it can be synthetically generated. The shading of the surrounding buildings is also evaluated. Predefined building components and other parameter objects can be loaded from a database. This can also be used to store personally defined building components. The mathematical models of IDA-ICE are described in terms of equations using a formal language named NMF, which can be used to make new modules or to replace existing program modules. The actual function of the components and relationship between the components models are modeled using NMF-files. Calibration of the Simulation Model The calibration of the simulation model of the case building included the following steps: 1. Developing a model which determines the volume flows of VAV-system using the rotation speed and pressure rice over the fans in calculation 2. The internal heat gains from the electric devices were determined using hourly electricity measurements from the BEMS 3. The leaking of the building was evaluated using information from the literature 4. The set temperatures of the supply air as well as the room temperatures were determined using the BAS 5. The set temperatures of the entering heating and the cooling liquids were also determined using the measurements of the BAS 6. The simulated output values, for instance for the indoor air temperature, the temperature of return liquids, and the energy consumptions, were compared to measured ones to evaluate the validity of the input parameters The first version of the simulation model of case building was made by a Finnish HVAC engineer company Olof A. Granlund. They modeled the building with a simulation program RIUSKA [7], which is based on DOE 2.1 E. Case building was modeled again by the researchers IDA-ICE and the model was calibrated using the measurements of building automation system. The principle of the calibration process is presented more precisely in the reference [8] concerning the commissioning and in the reference [9] concerning simulation model itself. The volume flows to each of the rooms were calculated based on the calculated indoor temperature and the calculated carbon dioxide emission from the people. However, the calculated total volume flows differed much from the measured ones, because the exact patent protected control strategy and the real occupancy level were not known. Due to that the measured and calculated heat uses differed quite much from each other. At the next phase the volume flows of each of the VAV-flow AHUs were taken directly from BAS-measurements based calculation model to the simulation program. The volume flows were divided in the rooms in the proportion of the floor areas, because the exact volume flows of the rooms were not saved to database of the BAS. At the same time the electricity use of the rooms were determined from the hourly electricity measurements and divided in the rooms with the same principles as the division of the volume flows. The electricity use of the HVAC was reduced from the total electricity use.

5 RESULTS Use of Energy for Heating Figure 2 presents the measured and calculated heat use of the case building in the first and second year of the building in use. The measured heat use was 30 % more than the simulated one during the first year. The difference was mainly due to the difficulty to determine the actual volume flows of VAV-system. The heat use of the second year was calculated after several corrections to the model. The calibration process included procedure explained in the previous chapter. The most important measure was to determine the variable air volume flows using a model. It was found out comparing the first estimation of the volume flows afterwards, that volume flows were underestimated with 30 % in the first year. 180 The heat use of IT-Dynamo in 1. and 2. year Heat use / floor area [kwh/m 2 /a] MEASURED IDA-ICE RIUSKA EN Heat use 1. year Heat use 2. year Figure 2 The heat use of the case building during the first and second year in use The heat use of the second year was calculated using three different calculation programs, two simulation program IDA-ICE and RIUSKA and a standard calculation method (EN 13790) [10]. The results of RIUSKA were not calibrated, and that is why the results of calibrated model of IDA-ICE correspond best to the measured heat use in the second year. The result of standard calculation overestimated the heat use with several percents. The Electricity use of HVAC-system Evaluation of the electricity use HCAC-system including fans, pumps, cooling devices etc. was difficult due to the same problems as in the determination of the heat use. The electricity use of the fans was dominant concerning the electricity use of HVAC. That is why the determination of the volume flows [4] was important also to find out the exact electricity use of fans and therefore the whole HVAC-system.

6 In the first year the measured electricity use of HVAC was 47 kwh/floor-m 2 /a as while the calculated one was 35 kwh/floor-m 2 /a. The measured and calculated electricity use of HVAC -system was according to both the measurement and the simulation 40 kwh/floor-m 2 /a in the second year. The difference between the measured and calculated values disappeared because of the calibration. Besides the determination of the volume flows, the electricity of the cooling devices was able to be determined more exactly in the second year than in the first year. That was done developing a mathematical model based on measurements. The electricity use of the cooling system was according to electricity measurements 12 kwh/floor-m 2 /a. The energy production of the free cooling system was according to the measurement based model 36 kwh/floor-m 2 and according to simulations 33 kwh/floor-m 2 /a. The whole panel cooling energy use of was according to the measurements and the simulations 48 kwh/floor-m 2 /a at the same time, and therefore 75 % of the cooling power was produced using the free cooling. The measured and the calculated total cooling energy need are presented in figure 3. The total and free energy needs were underestimated a little in the simulations compared to the measurements in spring Cooling energy per conditioned area Energy, kwh/floor-m /04 10/04 11/04 12/04 1/05 2/05 3/05 4/05 Tot al measured Free measured Total calculated Free calculated Figure 3 The measured and calculated energy use for cooling in the case building between Approximately 23 kwh/m 2 /a of the total electricity use of the HVAC-system 40 kwh/m 2 /a was consumed by the fans in the ventilation system. The electricity use for the cooling was 12 kwh/m 2 /a. The rest of the electricity 5 kwh/m 2 /a was consumed by the pumps and the control devices. The electricity use of the lighting, PC:s and other office devices was 83 kwh/m 2 /a in the second year, which was two times higher compared to the consumption of a similar buildings in Finland.

7 Free Energy Savings An estimation of the energy production of the free cooling system was measured to be 286 MWh and simulated to be 259 MWh between 09/ /2005. The total COP of the cooling system is estimated to be 1.2, which is typical COP-value of the whole cooling system. The total COP includes all the power losses in the production of the cooling energy. It is not the same as COP of a refrigerator, which is normally between 2 and 3. The savings of heat use were 162 or 107 MWh according to measurements and calculations respectively. In the calculations the lowering in efficiency of the heat recovery unit was taken into account. The total energy savings was about 14 % in heat use, 25 % in electricity use and 20 % in the average according to the measurements. The same values were a little lower according to the simulation results, but the differences are because the deficiencies in the model. Savings are calculated also in euros in a year and current value of the savings in ten years calculated with an interest rate of 5 %. The investment costs of the system are not remarkable more than in a regular system according to manufacturer of the system. The results are presented in Table 1. Table 1 Comparison of calculated and measured savings in the case building Measured Simulated Electricity Heat Total Electricity Heat Total Total energy use in MWh Energy saving in MWh Saving in % Saving in euro Current value in euros / 10 years Figure 4 Duration curves of the indoor temperatures in the case building

8 Evaluation of the Indoor Climate The indoor temperatures of the class rooms and the working rooms were estimated using duration curves. The duration curves presented in figure 4 were calculated concerning the time, when the building has been in actual use. The temperature has remained between 21 C and 26 C in the class rooms and between 20 C and 23 C in the working room. The calculated and measured temperatures correspond quite well to each other in a little working room 530, but differed about 1 C from each other in large classrooms 207 and 426 between and DISCUSSION The energy performance and the indoor climate of an educational building were evaluated using measurements results and simulation model. The calibration of the simulation model was done based on measurements of the building automation system and energy management system. The calibration process took two years, but after that the measurement and simulation results to correspond to each other. The main reason for differences between measurement and calculation results were the difficulties in determining the exact volume flows, the control strategy and the actual the utilization factor of the building. The lack of the information of the exact control strategy was found out to be the main reason for difficulties to calculate the exact volume flows, the indoor temperatures and the energy use for cooling. When the volume flows and indoor set temperature was taken from measurement results of BAS, the calculated heat use and electricity use of HVAC-system correspond to each other quite well. The simulation model should be kept as simple as possible when assessing a real system. The complicated models are difficult to calibrate, when the calculation parameters are more difficult to find out. The duration of the calibration process should also be much shorter, one month or two at the most, to make the calibration cost-effective. LITERATURE 1. Evaluation of the energy efficiency of a complex educational building, IBRI 2005, Hannu Keränen, Timo Kalema, Tampere University of Technology, Finland, 2005, 9 p. 2. Experiences of using models and information of building automation system in commissioning, Hannu Keränen, ICEBO 2004, Timo Kalema, Anssi Pesonen, Tampere University of Technology, Suomi, 2004, 17 p Modelling the ductwork of VAV-system, Annex 40, Hannu Keränen, Timo Kalema, Tampere University of Technology, unpublished, Finland 2004, 15 p aspx, IDA Indoor Climate and Energy, EQUA Simulation AB, Sweden, 2002, 243 p. 7. RIUSKA- Energy Simulation Tool - for the entire Building Life Cycle, Olof Granlund Oy, 2 p. 8. Using whole-building simulation models in commissioning, ANNEX 40, David E, Claridge, TAMU, USA, 2002, 14 p. 9. ASHRAE GUIDELINE 14, Measurement of Energy and Demand Savings, ASHRAE, USA, 2002, 165 p. 10. Thermal performance of buildings calculation of energy use for space heating, EN ISO 13790, CEN, 2003, 60 p.

Energy Efficient HVAC-system and Building Design

Energy Efficient HVAC-system and Building Design Energy Efficient HVAC-system and Building Design Maija Virta 1, Harri Itkonen 1, Panu Mustakallio 1, Risto Kosonen 1 1 Halton Oy, Finland Corresponding email: maija.virta@halton.com SUMMARY This paper

More information

HVAC Processes. Lecture 7

HVAC Processes. Lecture 7 HVAC Processes Lecture 7 Targets of Lecture General understanding about HVAC systems: Typical HVAC processes Air handling units, fan coil units, exhaust fans Typical plumbing systems Transfer pumps, sump

More information

The Chilled Water and Hot Water Building Deferential Pressure Setpoint Calculation Chilled Water and Hot Water Pump Speed Control

The Chilled Water and Hot Water Building Deferential Pressure Setpoint Calculation Chilled Water and Hot Water Pump Speed Control The Chilled Water and Hot Water Building Deferential Pressure Setpoint Calculation Chilled Water and Hot Water Pump Speed Control Chenggang Liu Research Associate Homer L. Bruner, Jr., CEM Mechanical Systems

More information

HVAC Systems: Overview

HVAC Systems: Overview HVAC Systems: Overview Michael J. Brandemuehl, Ph.D, P.E. University of Colorado Boulder, CO, USA Overview System Description Secondary HVAC Systems Air distribution Room diffusers and air terminals Duct

More information

SPECIAL ISSUE: NATIONAL SCIENCE FOUNDATION WORKSHOP

SPECIAL ISSUE: NATIONAL SCIENCE FOUNDATION WORKSHOP research journal 2013 / VOL 05.01 www.perkinswill.com SPECIAL ISSUE: NATIONAL SCIENCE FOUNDATION WORKSHOP ARCHITECTURE AND ENGINEERING OF SUSTAINABLE BUILDINGS Current Trends in Low-Energy HVAC Design

More information

COMPARISON OF DIFFERENT HVAC SYSTEMS IN MULTI- STOREY APARTMENT BUILDINGS IN HELSINKI

COMPARISON OF DIFFERENT HVAC SYSTEMS IN MULTI- STOREY APARTMENT BUILDINGS IN HELSINKI Proceedings of Healthy Buildings 2000, Vol. 2 675 COMPARISON OF DIFFERENT HVAC SYSTEMS IN MULTI- STOREY APARTMENT BUILDINGS IN HELSINKI Mikko Saari 1, Juhani Laine 1, Sami Karjalainen 1 and Klaus Hamström

More information

Advanced Energy Design Guide LEED Strategies for Schools. and High Performance Buildings

Advanced Energy Design Guide LEED Strategies for Schools. and High Performance Buildings Advanced Energy Design Guide LEED Strategies for Schools and High Performance Buildings Today s Presenters Stephen Koontz, LEED AP Energy Services Leader Tampa Bay Trane Allen Irvine General Sales Manager

More information

Fläkt Woods Building Future

Fläkt Woods Building Future Energy, Expertise and Environment with Fläkt Woods Fläkt Woods Building Future Saving energy in building ventilation You must save 20% on energy before 2020. Following the Kyoto protocol the European Union

More information

ENHANCED LABORATORY HVAC SYSTEM

ENHANCED LABORATORY HVAC SYSTEM ENHANCED LABORATORY HVAC SYSTEM INTRODUCTION Since the early 1980's the attention to more energy efficient laboratory designs has been on the rise due to the increase in energy cost and the emergence of

More information

Design Guide. Retrofitting Options For HVAC Systems In Live Performance Venues

Design Guide. Retrofitting Options For HVAC Systems In Live Performance Venues Design Guide Retrofitting Options For HVAC Systems In Live Performance Venues Heating, ventilation and air conditioning (HVAC) systems are major energy consumers in live performance venues. For this reason,

More information

Air Conditioning. The opportunity for energy efficiency. Low cost actions to reduce energy usage now

Air Conditioning. The opportunity for energy efficiency. Low cost actions to reduce energy usage now Fact Sheet #6 Air Conditioning In this fact sheet you will discover: The opportunity for energy efficiency How air conditioning works Low cost actions to reduce energy usage now Investments to reduce costs

More information

Creating Efficient HVAC Systems

Creating Efficient HVAC Systems Creating Efficient HVAC Systems Heating and Cooling Fundamentals for Commercial Buildings Heating, ventilating, and air conditioning (HVAC) systems account for nearly half of the energy used in a typical

More information

APPLICATION GUIDE. Comparison of Latent Cooling Performance of Various HVAC systems in a Classroom Application

APPLICATION GUIDE. Comparison of Latent Cooling Performance of Various HVAC systems in a Classroom Application APPLICATION GUIDE Comparison of Latent Cooling Performance of Various HVAC systems in a Classroom Application Section Comparison of Latent Cooling Performance of Introduction Most commercial HVAC systems

More information

ALBUQUERQUE PUBLIC SCHOOLS Facility Design & Construction / Maintenance & Operations

ALBUQUERQUE PUBLIC SCHOOLS Facility Design & Construction / Maintenance & Operations ALBUQUERQUE PUBLIC SCHOOLS Facility Design & Construction / Maintenance & Operations MECHANICAL SYSTEMS DESIGN STANDARDS Appendix A RECOMMENDED HVAC SYSTEMS BY TYPE OF SPACE Matt Higgins Valentin Lucero

More information

EFA PSBP. Natural Ventilation Strategy. Introduction. 1.1 Relevant legislation. 1.1.1 The Building Regulations 2010

EFA PSBP. Natural Ventilation Strategy. Introduction. 1.1 Relevant legislation. 1.1.1 The Building Regulations 2010 EFA PSBP Natural Ventilation Strategy Introduction The Baseline Designs Project will provide scheme design details for a number of Primary and Secondary School Exemplars. For the purposes of setting a

More information

Leveraging the Power of Intelligent Motor Control to Maximize HVAC System Efficiency

Leveraging the Power of Intelligent Motor Control to Maximize HVAC System Efficiency Leveraging the Power of Intelligent Motor Control to Maximize HVAC System Efficiency Because HVAC systems comprise a large amount of a building s operating costs, it makes sense to ensure these systems

More information

Life Cycle Costing Analysis of Water-cooled Chillers. Chillventa Nuremburg, Germany

Life Cycle Costing Analysis of Water-cooled Chillers. Chillventa Nuremburg, Germany Life Cycle Costing Analysis of Water-cooled Chillers Chillventa Nuremburg, Germany Spring 2012 Description Life Cycle Cost Analysis is a method of determining and comparing the total costs of investment

More information

HVAC For Schools How to purchase an HVAC system that meets your school s unique requirements and stays within your budget

HVAC For Schools How to purchase an HVAC system that meets your school s unique requirements and stays within your budget A PRIMER Educational HVAC For Schools How to purchase an HVAC system that meets your school s unique requirements and stays within your budget Contents: Introduction: The best HVAC system is durable, reliable

More information

MECHANICAL PROJECT PROPOSAL

MECHANICAL PROJECT PROPOSAL PSUAE MECHANICAL PROJECT PROPOSAL REDESIGN PROJECT Nicholas B Scheib 2010 M e c h a n i c a l O p t i o n - IP Table of Contents Executive Summary... 2 Project Summary... 3 Existing Mechanical System Summary...

More information

Carnegie Mellon University School of Architecture, Department of Mechanical Engineering Center for Building Performance and Diagnostics

Carnegie Mellon University School of Architecture, Department of Mechanical Engineering Center for Building Performance and Diagnostics Carnegie Mellon University School of Architecture, Department of Mechanical Engineering Center for Building Performance and Diagnostics A Presentation of Work in Progress 4 October 2006 in the Intelligent

More information

CHAPTER 3. BUILDING THERMAL LOAD ESTIMATION

CHAPTER 3. BUILDING THERMAL LOAD ESTIMATION CHAPTER 3. BUILDING THERMAL LOAD ESTIMATION 3.1 Purpose of Thermal Load Estimation 3.2 Heating Load versus Cooling Load 3.3 Critical Conditions for Design 3.4 Manual versus Computer Calculations 3.5 Heating

More information

International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS

International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS International Telecommunication Union ITU-T TELECOMMUNICATION STANDARDIZATION SECTOR OF ITU Technical Paper (13 December 2013) SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES

More information

EnergyPro Building Energy Analysis. Assisted Living Building

EnergyPro Building Energy Analysis. Assisted Living Building EnergyPro Building Energy Analysis Assisted Living Building EnergyPro Building Energy Analysis for an assisted living building Project Scope The purpose of the EnergyPro energy model was to evaluate the

More information

Mechanical Systems Proposal revised

Mechanical Systems Proposal revised Mechanical Systems Proposal revised Prepared for: Dr. William Bahnfleth, Professor The Pennsylvania State University, Department of Architectural Engineering Prepared by: Chris Nicolais Mechanical Option

More information

ENERGY SAVING STUDY IN A HOTEL HVAC SYSTEM

ENERGY SAVING STUDY IN A HOTEL HVAC SYSTEM ENERGY SAVING STUDY IN A HOTEL HVAC SYSTEM J.S. Hu, Philip C.W. Kwong, and Christopher Y.H. Chao Department of Mechanical Engineering, The Hong Kong University of Science and Technology Clear Water Bay,

More information

Modeling and Simulation of HVAC Faulty Operations and Performance Degradation due to Maintenance Issues

Modeling and Simulation of HVAC Faulty Operations and Performance Degradation due to Maintenance Issues LBNL-6129E ERNEST ORLANDO LAWRENCE BERKELEY NATIONAL LABORATORY Modeling and Simulation of HVAC Faulty Operations and Performance Degradation due to Maintenance Issues Liping Wang, Tianzhen Hong Environmental

More information

2 STEPS TO CONDUCTING YOUR HVAC ASSESSMENT

2 STEPS TO CONDUCTING YOUR HVAC ASSESSMENT Presentation Synopsis Heating, Ventilating and Air Conditioning Building Condition Assessment Vancouver, B.C. Prepared for: EPIC Prepared by: Douglas Spratt, P.Eng Douglas Spratt & Associates Ltd. www.dspratt-associates.com

More information

Venice Library Humidity Study. for Williams Building Diagnostics, LLC 305 15 th Street West Bradenton, FL 34205. Report April 13, 2015

Venice Library Humidity Study. for Williams Building Diagnostics, LLC 305 15 th Street West Bradenton, FL 34205. Report April 13, 2015 for Williams Building Diagnostics, LLC 305 15 th Street West Bradenton, FL 34205 Report April 13, 2015 Moses & Associates, Inc. 2209 NW 40 th Terrace, Suite A Gainesville, FL 32605 FL License EB-0003097

More information

Development of Air-to-Water Heat Pump for Home Air conditioning/hot Water Supply Combination System with Chilled/Hot Water in European Markets

Development of Air-to-Water Heat Pump for Home Air conditioning/hot Water Supply Combination System with Chilled/Hot Water in European Markets 2 Development of Air-to-Water Heat Pump for Home Air conditioning/hot Water Supply Combination System with Chilled/Hot Water in European Markets - Extending Use of New Heat Pump System in Cold Regions

More information

Lesson 36 Selection Of Air Conditioning Systems

Lesson 36 Selection Of Air Conditioning Systems Lesson 36 Selection Of Air Conditioning Systems Version 1 ME, IIT Kharagpur 1 The specific objectives of this chapter are to: 1. Introduction to thermal distribution systems and their functions (Section

More information

Comparison of two calculation methods used to estimate cooling energy demand and indoor summer temperatures

Comparison of two calculation methods used to estimate cooling energy demand and indoor summer temperatures Comparison of two calculation methods used to estimate cooling energy demand and indoor summer temperatures Kai Sirén and Ala Hasan Helsinki University of Technology, Finland Corresponding email: kai.siren@tkk.fi

More information

ICT PLATFORM FOR HOLISTIC ENERGY EFFICIENCY SIMULATION AND LIFECYCLE MANAGEMENT OF PUBLIC USE FACILITIES

ICT PLATFORM FOR HOLISTIC ENERGY EFFICIENCY SIMULATION AND LIFECYCLE MANAGEMENT OF PUBLIC USE FACILITIES SEVENTH FRAMEWORK PROGRAMME OF THE EUROPEAN COMMUNITY (EC GRANT AGREEMENT N 26088) ICT PLATFORM FOR HOLISTIC ENERGY EFFICIENCY SIMULATION AND LIFECYCLE MANAGEMENT OF PUBLIC USE FACILITIES Deliverable D6.2:

More information

AIR CONDITIONING EFFICIENCY F8 Energy eco-efficiency opportunities in Queensland Foundries

AIR CONDITIONING EFFICIENCY F8 Energy eco-efficiency opportunities in Queensland Foundries AIR CONDITIONING EFFICIENCY F8 Energy eco-efficiency opportunities in Queensland Foundries Hot tips and cool ideas to save energy and money! Air conditioning units or systems are often used by foundries

More information

HVACPowDen.xls An Easy-to-Use Tool for Recognizing Energy Efficient Buildings and HVAC Systems

HVACPowDen.xls An Easy-to-Use Tool for Recognizing Energy Efficient Buildings and HVAC Systems HVACPowDen.xls An Easy-to-Use Tool for Recognizing Energy Efficient Buildings and HVAC Systems Fundamental Principles of Environmentally Responsible, Energy Efficient Buildings 1. Energy efficiency is

More information

HVAC Efficiency Definitions

HVAC Efficiency Definitions HVAC Efficiency Definitions Term page EER - 2 SEER - 3 COP - 4 HSPF - 5 IPLV - 6 John Mix May 2006 Carrier Corporation 1 Energy Efficiency Ratio (EER) The energy efficiency ratio is used to evaluate the

More information

The District Energy Manager and Classroom Heating

The District Energy Manager and Classroom Heating Mt. Carmel Area School District Energy Conservation Policy Adopted 6/19/06 These guidelines supersede all previous instructions. It is crucial that these energy guidelines be observed in the operation

More information

Energy Efficiency in Industrial HVAC Systems

Energy Efficiency in Industrial HVAC Systems Energy Efficiency in Industrial HVAC Systems Heating, ventilation and air conditioning (HVAC) constitutes up to 35 percent of energy used in manufacturing facilities. This fact sheet is geared towards

More information

HEATING, VENTILATION & AIR CONDITIONING

HEATING, VENTILATION & AIR CONDITIONING HEATING, VENTILATION & AIR CONDITIONING as part of the Energy Efficiency Information Grants Program Heating and cooling can account for approximately 23 % of energy use in pubs and hotels 1. Reducing heating

More information

Element D Services Heating, Ventilating, and Air Conditioning

Element D Services Heating, Ventilating, and Air Conditioning PART 1 - GENERAL 1.01 OVERVIEW A. This section supplements Design Guideline Element D3041 on air handling distribution with specific criteria for projects involving design of a Data Center spaces B. Refer

More information

Energy consumption and heat recovery of refrigeration system in modern Arena

Energy consumption and heat recovery of refrigeration system in modern Arena Energy consumption and heat recovery of refrigeration system in modern Arena By Alexander Cohr Pachai Johnson Controls Building Efficiency Christian X s Vej 201 8270 Hoejbjerg Denmark alexander.c.pachai@jci.com

More information

Life cycle cost comparison of TAB vs. other HVAC (UK) TECHNICAL BROCHURE

Life cycle cost comparison of TAB vs. other HVAC (UK) TECHNICAL BROCHURE Life cycle cost comparison of TAB vs. other HVAC (UK) TECHNICAL BROCHURE 3 213 2 2 UPONOR LIFE CYCLE COST COMPARISON OF TAB VS. OTHER HVAC Contents Introduction... 4 Base building... 5 System and tested

More information

How To Design A Building In New Delhi

How To Design A Building In New Delhi ENERGY EFFICIENT HVAC DESIGN FOR COMPOSITE CLIMATE Overview of Design Conditions: Air conditioning system consumes most of the energy that a building needs in its operation. In order to reduce energy consumption

More information

ENERGY EFFICIENT HVAC DESIGN FOR WARM-HUMID CLIMATE CLIMATE

ENERGY EFFICIENT HVAC DESIGN FOR WARM-HUMID CLIMATE CLIMATE ENERGY EFFICIENT HVAC DESIGN FOR WARM-HUMID CLIMATE CLIMATE Overview of Design Conditions: Air conditioning system consumes most of the energy that a building needs in its operation. In order to reduce

More information

UNIVERSITY OF MISSOURI 23 0000 - Heating Ventilating and Air-Conditioning (HVAC) March 2015.01

UNIVERSITY OF MISSOURI 23 0000 - Heating Ventilating and Air-Conditioning (HVAC) March 2015.01 GENERAL: This section provides general standards for overall sizing and design of Heating, Ventilating, and Air Conditioning (HVAC) systems. Other sections contain specific standards for each system per

More information

Condensing Boiler Efficiency

Condensing Boiler Efficiency Condensing Boiler Efficiency Date: July 17, 2012 PRES E NT ED BY DO N L E O NA RDI LE O N A RD I I NC. HV AC T RAI N I N G & C ON SU LT IN G Concepts 1 The current state of evolution in boiler design 2

More information

DataCenter 2020: first results for energy-optimization at existing data centers

DataCenter 2020: first results for energy-optimization at existing data centers DataCenter : first results for energy-optimization at existing data centers July Powered by WHITE PAPER: DataCenter DataCenter : first results for energy-optimization at existing data centers Introduction

More information

Heating, ventilation and air conditioning (HVAC) equipment. A guide to equipment eligible for Enhanced Capital Allowances

Heating, ventilation and air conditioning (HVAC) equipment. A guide to equipment eligible for Enhanced Capital Allowances Heating, ventilation and air conditioning (HVAC) equipment A guide to equipment eligible for Enhanced Capital Allowances 2 Contents Boost Introduction your cash flow 03 1. Background Check it s on the

More information

HEAT PUMPING AND REVERSIBLE AIR CONDITIONING: HOW TO MAKE THE BEST USE OF HVAC EQUIPMENT?

HEAT PUMPING AND REVERSIBLE AIR CONDITIONING: HOW TO MAKE THE BEST USE OF HVAC EQUIPMENT? - 1 - HEAT PUMPING AND REVERSIBLE AIR CONDITIONING: HOW TO MAKE THE BEST USE OF HVAC EQUIPMENT? S. Bertagnolio, Research Assistant, Laboratoire de Thermodynamique Université de Liège, Liège, Belgium. J.

More information

ASTACEA4 Inspect complex/central air conditioning systems

ASTACEA4 Inspect complex/central air conditioning systems Overview This Unit covers the competences required to inspect complex/central air conditioning systems as defined by the CIBSE TM 44 Figure 1.1: Summary of system types and their component parts. The air

More information

Glossary of HVAC Terms

Glossary of HVAC Terms Glossary of HVAC Terms Heating, Ventilation and Air Conditioning (HVAC) is a major sub- discipline of mechanical engineering. The goal of HVAC design is to balance indoor environmental comfort with other

More information

Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks

Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks Presentation Outline Common Terms / Concepts HVAC Building Blocks Plant Level Building Blocks Description / Application Data Green opportunities Selection Criteria Air Distribution Building Blocks same

More information

Residential HVAC Load Sizing Training October 14, 2015. David Kaiser Green Code Plan Reviewer

Residential HVAC Load Sizing Training October 14, 2015. David Kaiser Green Code Plan Reviewer Residential HVAC Load Sizing Training October 14, 2015 David Kaiser Green Code Plan Reviewer DCRA - Green Building Division Regulations of green codes including: Green Building Act Green Construction Code

More information

Heating, ventilation and air conditioning equipment. A guide to equipment eligible for Enhanced Capital Allowances

Heating, ventilation and air conditioning equipment. A guide to equipment eligible for Enhanced Capital Allowances Heating, ventilation and air conditioning equipment A guide to equipment eligible for Enhanced Capital Allowances 2 Contents Introduction 03 Background 03 Setting the scene 03 Benefits of purchasing ETL

More information

Energy audit in Finland

Energy audit in Finland Energy audit in Finland NorTech Oulu Lauri Mikkonen Energy Audit in Finland An energy audit tells about the energy efficiency and total energy consumption in a building, including all consumed heating,

More information

International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS

International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS International Telecommunication Union ITU-T TELECOMMUNICATION STANDARDIZATION SECTOR OF ITU Technical Paper (13 December 2013) SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES

More information

ENERGY AUDIT IN THE KACST BUILDING

ENERGY AUDIT IN THE KACST BUILDING ENERGY AUDIT IN THE KACST BUILDING S. M. Hasnain, S. H. Alawaji, A. M. Al-Ibrahim and S. M. Smiai Energy Research Institute (ERI) King Abdulaziz City for Science and Technology (KACST) P.O. Box 6086, Riyadh

More information

A global list. The Fortification Depot A CO 2 -reduction project

A global list. The Fortification Depot A CO 2 -reduction project The Fortification Depot A CO 2 -reduction project A global list Passive measures: Windows, glazing, solar shading Insulation of walls, roofs, floors Improving air tightness 1 A global list Technical measures:

More information

Hybrid system. Energy-efficient and environmentally friendly

Hybrid system. Energy-efficient and environmentally friendly Hybrid system Energy-efficient and environmentally friendly Hybrid solutions Hybrid heating systems utilise several different energy sources for heating and hot water supply during the different seasons

More information

Crawl space heat and moisture behaviour

Crawl space heat and moisture behaviour Crawl space heat and moisture behaviour Miimu Airaksinen, Dr., Technical Research Centre of Finland, VTT miimu.airaksinen@vtt.fi, www.vtt.fi KEYWORDS: crawl space, moisture, evaporation from ground, ground

More information

IES <Virtual Environment> training. Trainee notes. ASHRAE 90.1 Appendix G - PRM Navigator. Version 6.4.0.7

IES <Virtual Environment> training. Trainee notes. ASHRAE 90.1 Appendix G - PRM Navigator. Version 6.4.0.7 IES training Trainee notes ASHRAE 90.1 Appendix G - PRM Navigator Version 6.4.0.7 Introduction These training notes are to be used in conjunction with your ASHRAE 90.1 Appendix G

More information

Research on the Air Conditioning Water Heater System

Research on the Air Conditioning Water Heater System Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 28 Research on the Air Conditioning Water Heater System Fei Liu Gree Electric

More information

Horizontal ventilation units

Horizontal ventilation units THE ART OF AIR INNOVATION SINCE 1983 FOR HOMES AND BUSINESSES Horizontal ventilation units Healthy indoor air increases your well-being Today people spend much of their life indoors. It is therefore important

More information

Components HVAC General Standards HVAC Guidelines HVAC System Selection Life Cycle Cost Analysis

Components HVAC General Standards HVAC Guidelines HVAC System Selection Life Cycle Cost Analysis Components HVAC General System Selection Life Cycle Cost Analysis Outdoor Air Design Values Indoor Air Design Values Outdoor Air Ventilation Welding Ventilation Temperature Control Systems Ductwork HVAC

More information

Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia

Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia Prepared for the U.S. Department of Energy s Federal Energy Management Program

More information

HOW TO CONDUCT ENERGY SAVINGS ANALYSIS IN A FACILITY VALUE ENGINEERING STUDY

HOW TO CONDUCT ENERGY SAVINGS ANALYSIS IN A FACILITY VALUE ENGINEERING STUDY HOW TO CONDUCT ENERGY SAVINGS ANALYSIS IN A FACILITY VALUE ENGINEERING STUDY Benson Kwong, CVS, PE, CEM, LEED AP, CCE envergie consulting, LLC Biography Benson Kwong is an independent consultant providing

More information

SAM HOUSTON STATE UNIVERSITY

SAM HOUSTON STATE UNIVERSITY PART 1: GENERAL 1.01 General Requirements A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the

More information

Energy Efficiency HOSPITALITY. www.energia.ie

Energy Efficiency HOSPITALITY. www.energia.ie Energy Efficiency HOSPITALITY www.energia.ie Your chance to reduce your business energy usage by as much as 20%! 20% is a significant figure and reducing your energy bill by this amount could make a real

More information

Building Energy Systems. - HVAC: Heating, Distribution -

Building Energy Systems. - HVAC: Heating, Distribution - * Some of the images used in these slides are taken from the internet for instructional purposes only Building Energy Systems - HVAC: Heating, Distribution - Bryan Eisenhower Associate Director Center

More information

Green House, Hungary

Green House, Hungary Further information Skanska AB www.skanska.com Contact Noel Morrin, SVP Sustainability & Green Support noel.morrin@skanska.se Green House, Hungary Case Study 109 Aspects of Sustainability This project

More information

06150 PORVOO, FINLAND Pelican eco ED(D), Pelican eco EDE(D), Pelican eco EDW(D), Pelican eco EDX(D)

06150 PORVOO, FINLAND Pelican eco ED(D), Pelican eco EDE(D), Pelican eco EDW(D), Pelican eco EDX(D) Certificate Certified Passive House Component For cool, temperate climates, valid until 31 December 2013 Passive House Institute Dr. Wolfgang Feist 64283 Darmstadt GERMANY Category: Manufacturer: Heat

More information

Study on Performance Evaluation of a Split Air Conditioning System Under the Actual Conditions

Study on Performance Evaluation of a Split Air Conditioning System Under the Actual Conditions Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2006 Study on Performance Evaluation of a Split Air Conditioning System Under

More information

BEC 2012 Vs BEC 2015 - Summary of Major Amendments

BEC 2012 Vs BEC 2015 - Summary of Major Amendments - Summary of Major Amendments Note: 1. The following summary table includes the major amendments, with requirements tightened in general for enhanced energy efficiency. Please refer to BEC 2015 for the

More information

Eurovent Certification for Air Handling Units : Five Energy Efficiency classes to make the right choice

Eurovent Certification for Air Handling Units : Five Energy Efficiency classes to make the right choice Eurovent Certification for Air Handling Units : Five Energy Efficiency classes to make the right choice A truly international certification The Eurovent Certification Programmes are managed by an autonomous

More information

Air Conditioning in Green Office Buildings?

Air Conditioning in Green Office Buildings? Air Conditioning in Green Office Buildings? How to implement Demand Controlled Ventilation Stuttgart Rechte allein bei ICEBO 08 10.10.2008 CI / DrRo 1 Air Conditioning in Green Office Buildings ventilation

More information

Energy Efficiency in Buildings

Energy Efficiency in Buildings Energy Efficiency in Buildings Supplemental Guide to SANS 10400-XA & SANS 204 V. 3.0 Registered to: The Drawing Studio Image: digitalart / FreeDigitalPhotos.net Report Date: 26 August 2014 Practice Name:

More information

Infrastructure & Cities Sector

Infrastructure & Cities Sector Technical Article Infrastructure & Cities Sector Building Technologies Division Zug (Switzerland), October 18, 2011 Saving Energy in a Data Center A Leap of Faith? New guidelines from ASHRAE (American

More information

SECTION 23 05 93 TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION

SECTION 23 05 93 TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION SECTION 23 05 93 TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION The purpose of this guide specification is to assist the specifier in correctly specifying Mechanical System Testing

More information

Why Measure Carbon Dioxide Inside Buildings? By Rich Prill, Washington State University Extension Energy Program

Why Measure Carbon Dioxide Inside Buildings? By Rich Prill, Washington State University Extension Energy Program Why Measure Carbon Dioxide Inside Buildings? By Rich Prill, Indoor air quality Workers and students spend about half their waking hours at work or school. Therefore, maintaining adequate indoor air quality

More information

The natural ombination

The natural ombination The natural ombination DAikin Altherma Hybrid heat pump system The future is now The new hybrid system Heat pump solution for gas boiler replacement market Daikin Altherma hybrid combines heat pump technology

More information

SBi 2013:14. Study of a Two-Pipe Chilled Beam System for both Cooling and Heating of Office Buildings

SBi 2013:14. Study of a Two-Pipe Chilled Beam System for both Cooling and Heating of Office Buildings SBi 2013:14 Study of a Two-Pipe Chilled Beam System for both Cooling and Heating of Office Buildings Study of a Two-Pipe Chilled Beam System for both Cooling and Heating of Office Buildings Rouzbeh Norouzi,

More information

3/29/2012 INTRODUCTION HVAC BASICS

3/29/2012 INTRODUCTION HVAC BASICS INTRODUCTION HVAC BASICS AND HVAC SYSTEM EFFICIENCY IMPROVEMENT SECTION O HVAC systems or Heating, Ventilating and Air-Conditioning systems control the environment for people and equipment in our facilities.

More information

Tim Sisson - Trane HVAC OVERVIEW

Tim Sisson - Trane HVAC OVERVIEW Tim Sisson - Trane HVAC OVERVIEW HVAC Systems System Types Acoustics Controls Modernization more than one Down to the Studs Opportunity for new System Type Renovation Possible opportunity for new System

More information

Draft UCL Heating, Cooling and Ventilation Policy

Draft UCL Heating, Cooling and Ventilation Policy Draft UCL Heating, Cooling and Ventilation Policy Page 1 of 7 UCL Estates UCL Heating, Cooling & UCL Heating, Cooling and Document Owner UCL Estates Leadership Team is the Owner of this document. Distribution

More information

HVAC Technologies for Building Energy Efficiency Improvements 2013 National Symposium on Market Transformation. Richard Lord Carrier Fellow

HVAC Technologies for Building Energy Efficiency Improvements 2013 National Symposium on Market Transformation. Richard Lord Carrier Fellow HVAC Technologies for Building Energy Efficiency Improvements 2013 National Symposium on Market Transformation Richard Lord Carrier Fellow HVAC Industry Challenges and Issues Ozone Deletion Global Warming

More information

RFI Response RFP: HSCG88-16-R-PQQ015 Replace HVAC Bldg A & C San Diego, CA.

RFI Response RFP: HSCG88-16-R-PQQ015 Replace HVAC Bldg A & C San Diego, CA. 1. There is verbiage in the hazardous material report referring to a state licensed abatement contractor. Within the recommendations part of the report (page 64 of 111 of the specification pdf) is the

More information

HEAT PUMPING AND REVERSIBLE AIR CONDITIONING; RETROFIT OPPORTUNITIES IN A LABORATORY BUILDING. Campus du Sart Tilman, B49, B-4000 Liège, Belgium

HEAT PUMPING AND REVERSIBLE AIR CONDITIONING; RETROFIT OPPORTUNITIES IN A LABORATORY BUILDING. Campus du Sart Tilman, B49, B-4000 Liège, Belgium HEAT PUMPING AND REVERSIBLE AIR CONDITIONING; RETROFIT OPPORTUNITIES IN A LABORATORY BUILDING Cleide Aparecida Silva 1, cj.hannay@ulg.ac.be Stéphane Bertagnolio 1, stephane.bertagnolio@student.ulg.ac.be

More information

ENERGY PILE AND HEAT PUMP MODELING IN WHOLE BUILDING SIMULATION MODEL

ENERGY PILE AND HEAT PUMP MODELING IN WHOLE BUILDING SIMULATION MODEL ENERGY PILE AND HEAT PUMP MODELING IN WHOLE BUILDING SIMULATION MODEL Jevgeni Fadejev, Jarek Kurnitski Faculty of Civil Engineering, Tallinn University of Technology, Tallinn, Estonia Jevgeni.Fadejev@ttu.ee;

More information

Facilities Management System That Reduces Environmental Burden of Buildings

Facilities Management System That Reduces Environmental Burden of Buildings Facilities Management System That Reduces Environmental Burden of Buildings V Masahiro Maeeda (Manuscript received February 1, 2005) In recent years, the problem of global warming has become serious, and

More information

Investigations of a Long-Distance 1000 MW Heat Transport System with APROS Simulation Software

Investigations of a Long-Distance 1000 MW Heat Transport System with APROS Simulation Software th International Conference on Structural Mechanics in Reactor Technology (SMiRT ) Espoo, Finland, August 9-4, 9 SMiRT -Division 3, Paper 56 Investigations of a Long-Distance MW Heat Transport System with

More information

Bring the fresh in. Dedicated Outside Air Systems

Bring the fresh in. Dedicated Outside Air Systems Bring the fresh in. Dedicated Outside Air Systems The inside story on outside air. On average, we breathe in 3,400 gallons of air each day. Ambient indoor air pollution is a major problem, affecting health

More information

Federation of European Heating, Ventilation and Air-conditioning Associations

Federation of European Heating, Ventilation and Air-conditioning Associations Federation of European Heating, Ventilation and Air-conditioning Associations Address: Rue Washington 40 1050 Brussels Belgium www.rehva.eu info@rehva.eu Tel: +32 2 514 11 71 Fax: +32 2 512 90 62 REHVA

More information

Comparing Energy Savings of Different VAV Systems

Comparing Energy Savings of Different VAV Systems Comparing Energy Savings of Different VAV Systems Prepared By: Martyn Dodd mart@energysoft.com EnergySoft LLC 1025 5th Street, Suite A Novato, CA 94945 415-897-6400 www.energysoft.com Last Modified: March

More information

3-D Modeller Rendered Visualisations

3-D Modeller Rendered Visualisations Recognised energy Dynamic Simulation Modelling (DSM) software DesignBuilder is a user interface to the EnergyPlus DSM. EnergyPlus builds on the most popular features and capabilities of BLAST and DOE-2

More information

LG Electronics AE Company, Commercial Air Conditioning

LG Electronics AE Company, Commercial Air Conditioning www.lgeaircon.com New concept Ecofriendly Highefficiency Heating solution Total heating & Hot water Solution for MULTI V LG Electronics AE Company, Commercial Air Conditioning 2 Yeouidodong, Yeongdeungpogu,

More information

Halton - Achieving Energy Efficiency in School Design

Halton - Achieving Energy Efficiency in School Design Halton - Achieving Energy Efficiency in School Design Enabling Wellbeing Halton Design Tools Drive Energy Efficient Kitchen Ventilation and Comfort Today, nutritional guidelines for school foodservice

More information

Impact of energy management software on the improvement of energy performance in public buildings

Impact of energy management software on the improvement of energy performance in public buildings Impact of energy management software on the improvement of energy performance in public buildings Prof. Dr Velimir Čongradac Faculty of technical sciences, Novi Sad, Serbia Introduction Why to use energy

More information

All Electrical School

All Electrical School All Electrical School with GS in Quebec Preliminary Results Vasile MINEA Workshop on Canadian Heat Pumps & Refrigeration Activities Montreal, May 10, 2004 Hydro-Quebec Contribution Sector: Commercial,

More information

Lawrence Berkeley National Laboratory Lawrence Berkeley National Laboratory

Lawrence Berkeley National Laboratory Lawrence Berkeley National Laboratory Lawrence Berkeley National Laboratory Lawrence Berkeley National Laboratory Title: Comparison of energy efficiency between variable refrigerant flow systems and ground source heat pump systems Author:

More information

Fundamentals of HVAC Control Systems

Fundamentals of HVAC Control Systems ASHRAE Hong Kong Chapter Technical Workshop Fundamentals of HVAC Control Systems 18, 19, 25, 26 April 2007 2007 ASHRAE Hong Kong Chapter Slide 1 Chapter 5 Control Diagrams and Sequences 2007 ASHRAE Hong

More information

Forty-one miles of submerged coils that heat and cool a high school of 2,400 students.

Forty-one miles of submerged coils that heat and cool a high school of 2,400 students. ACKNOWLEDGEMENTS Architects: Bray Associates Architects, Inc., Sheboygan, Wisconsin Energy consultant: CDH Energy Corporation, Evansville, Wisconsin Energy management system: J&H Controls, Inc., Fond du

More information