Deploying High Power at the Rack
|
|
- Jemimah Knight
- 7 years ago
- Views:
Transcription
1 Deploying High Power at the Rack Presented by: David Wood, Director Power Business PIS 14 April 30, 2013
2 Agenda Industry trends & challenges Introduction to 400V Other considerations, e.g. 480V Summary and benefits
3 Industry trends & challenges High power demands from high density Big Data, Cloud infrastructure Blade servers, storage, and high density networking fabrics New generations of traditional servers, e.g. HP Gen 8 New generation of Low Energy Servers Containers and modular Increasing need for changes due to variety of demand Need to consider both medium density (5-10 kw/rack) and high density (15-30 kw/rack) equipment Power requirements for a variety of equipment and deployments, e.g. single/three phase, rack power (kw), and physical receptacles
4 Power Density Trends: Extreme Low Energy Servers
5 Lack of power capacity = downtime Hitting capacity thresholds introduces RISK Average cost of data center downtime = $5,600/minute. Average reported incident length: 90 minutes Average cost of a single downtime event: $505,500. UPS failure proved to be most costly root cause Studies by Ponemon Institute Published article in Data Center Knowledge
6 Higher power at the rack Higher current, 30A to 60A 3 phase 24x208x1.73 = 8.6kW 40x208x1.73 = 14.4kW 48x208x1.73 = 17.3kW Higher voltage, trend towards 400V 3 phase to the rack 24x400x1.73 = 16.6kW 48x400x1.73 = 33.2kW We re seeing more requests for 40+KW ipdu 63*400*1.73 = 43.6kW Design zones in the data center 5kW racks + 17+kW racks Calculations assume pf = 1
7 400V topology vs. Traditional Improved transmission efficiency By eliminating unnecessary voltage transformations, 400V power reduces energy costs by approximately 2-3% vs. 208V distribution; and approximately 4-5% vs. 120V distribution Source: greengrid.org
8 North America: 208V vs. 400V Intelligent PDUs Power density review 30A 30A 30A 60A Phase Single phase Three phase Delta Three phase Wye Input Voltage 208V 208V 400V 208V Output Voltage Apparent power 1U servers supported* 2u servers supported* Blade chassis supported* 208V 208V 230V 208V Three phase Delta 5.0 kw 8.6 kw 16.6 kw 17.3kW *HP Proliant GL 360G6 1U server, 206 watts at 80% load on SPECpower_ssj2008 HP Proliant GL 380G6 2U server, 208 watts at 80% load on SPECpower_ssj2008 HP Proliant C7000, ProLiant BL2x220c G6, 4860 watts at 80% load on SPECpower_ssj2008
9 EU and AP: 230V vs. 400V Intelligent PDUs Power density review 32A 16A 32A 63A Phase Single phase Three phase Wye Three phase Wye Input Voltage 230V 400V 400V 400V Output Voltage Apparent power 1U servers supported* 2u servers supported* Blade chassis supported* 230V 230V 230V 230V Three phase Wye 7.4 kw 11.1 kw 22.1 kw 43.6 kw *HP Proliant GL 360G6 1U server, 206 watts at 80% load on SPECpower_ssj2008 *HP Proliant GL 380G6 2U server, 208 watts at 80% load on SPECpower_ssj2008 *HP Proliant C7000, ProLiant BL2x220c G6, 4860 watts at 80% load on SPECpower_ssj2008
10 Compare 208V vs.400v input cord 400V for similar power: Less copper Less weight Less space Less cost 400V 30A WYE 208V 60A Delta Source: General Cable SOOW cable specification
11 208V vs. 400V plug assessment 30A 400V 3 phase Wye: HUBBELL HBL2821 AC Plug NEMA L22-30 Male 16.6kW Plug Price $32.00 Receptacle Price $ A 208V 3 phase Delta: Mennekes ME460P9W IEC P9W Pin & Sleeve 17.3kW Plug Price $ Receptacle Price $ $73.00 $ Price source:
12 Single-pole vs. double-pole breakers Some vendors may use double pole breakers, others single pole Situation: North America 30A 400V 3 phase WYE. Some use 3 double pole breakers, we use 6 single pole One is cheaper, one is more expensive One is more limiting, one is less limiting One is less reliable, one is more reliable L1 24A Pole 1 Pole 2 20A 12A L1 24A 24A Pole 1 Pole 1 20A 20A L2 Pole 1 L2 24A Pole 1 20A Pole 2 24A Pole 1 20A L3 Pole 1 L3 24A Pole 1 20A Pole 2 24A Pole 1 20A 12
13 Why and when 3 pole? Blade applications can require 36kVA E.g. up to 5 x HP C7000 blade chassis in a single rack Note: HP C7000 has 6 power supplies per chassis, 3 per side A-side PDU and blade power supplies (same applies to B-side not shown) Isolate any faults to a single blade chassis Eliminate potential for cascading failure
14 Multi-inlets scenario 2 PDUs each with 2 input cords to deliver twice as much power Easier to install than 4 PDUs Less expensive because each PDU has one controller
15 Other considerations - What about 480V/277V? 15 Issue: Majority of servers don t have power supplies that support 277V. Max typically 250V Issue: Industry C13 and C19 s don t support 277V Facebook / OpenCompute pushing it to improve efficiency Additional savings BUT everything is basically CUSTOM Custom triplet racks Custom servers and power supply Custom battery/ups Rack pdu 480/277 Custom s, Tyco 3-pin Mate-N-Loc
16 Example 480V/277V components Facebook / OpenCompute receptacle and power supply HUBBELL HBL4760 AC Receptacle NEMA L7-15 Female Black 277 Volt 15 Amp 16 Net-Net: technically feasible, but requires scale & additional expense to improve efficiency by 1-2% more than V 3 phase systems.
17 Benefits of 400V 3 phase Intelligent Rack PDUs Achieve higher power densities at the rack and increased capacities More efficient power distribution resulting from reduced electrical transmission losses Improved sustainability through lower copper utilization Save costs from lower amperage plugs whips with less copper, lower weight fewer cable runs in the plenum reduced pole positions at the panels resulting less equipment expense, e.g. floor PDUs/RPPs less power distribution losses
18 The Commercial Raritan s easy-to-use integrated solution: PX high-power PDUs with plug-and-play sensors temperature, humidity, airflow, air pressure used with Power IQ can 1) deliver high power and 2) monitor before and after cooling. Just have basic PDUs? Raritan s EMX (and PX) supports sensors and Wi-Fi networking so you don t even need expensive Ethernet drops. Raritan has a broad portfolio of high-power intelligent PDUs,, sensors and energy management software. Come see us at booth # 835
19 Resources Raritan white paper Deploying High Power to IT Equipment Racks Raritan Blog How to Calculate Current on a 3-Phase, 208V Rack PDU (Power Strip) phase-208v-rack-pdu-power-strip/
20 QUESTIONS David Wood Director, Power Business Raritan, Inc Ext Raritan, Inc. - Proprietary and Confidential
Server Technology Intl.
Server Technology, Inc. 3-Phase Power in the Data Center White Paper STI-100-005 North America/ASIA EMEA Server Technology, Inc. Server Technology Intl. 1040 Sandhill Drive Sienna Court Reno, NV 89521
More informationServer Technology, Inc.
Server Technology, Inc. Power Efficiency Gains by Deploying 415 VAC Power Distribution in North American Data Centers White Paper STI-100-008 2009-April-07 Headquarters Server Technology, Inc. 1040 Sandhill
More informationThree-Phase Electric Power Distribution for Computer Data Centers
Three-hase Electric ower Distribution for Computer Data Centers WHITE AER E901 Geist January 008 Summary This paper will describe the characteristics of three-phase power and outline the advantages of
More informationServer Technology Inc.
Server Technology Inc. Efficiency Gains with 480V/277V Power at the Cabinet Level White Paper STI-100-012 2011-May-2 Headquarters Server Technology, Inc. 1040 Sandhill Drive Reno, NV 89521 United States
More informationIncreasing Data Center Efficiency by Using Improved High Density Power Distribution
Increasing Data Center Efficiency by Using Improved High Density Power Distribution By Neil Rasmussen White Paper #128 Executive Summary A new approach to power distribution for high density server installations
More informationPX Intelligent Rack PDUs
PX Intelligent Rack PDUs Rack Power Distribution Units for Your Data Center Raritan s PX intelligent rack PDU series offers more than just power distribution -- it s a launch pad for real-time remote power
More informationPX Intelligent Rack PDUs
PX Intelligent Rack PDUs Rack Power Distribution Units for Your Data Center Raritan s PX intelligent rack PDU series offers more than just power distribution -- it s a launch pad for real-time remote power
More informationPower Distribution in Data Centers: STARLINE Track Busway, PX ipdus and Power IQ
Power Distribution in Data Centers: STARLINE Track Busway, PX ipdus and Power IQ 2011 Raritan Inc. Overview Data center managers are faced with increasingly challenging demands: supplying additional computing
More informationQuickSpecs. HP 480/277 Volt Solutions. Overview
Overview As the quest for efficiency continues it becomes apparent that what worked in the past needs improvement. More and more data center managers are looking at alternate power plans to distribute
More informationPower Distribution Considerations for Data Center Racks
Power Distribution Considerations for Data Center Racks Power Distribution Considerations for Data Center Racks Table of Contents 3 Overview 4 At what voltage do you run all the IT equipment? 4 What electrical
More informationRELIABLE AND FLEXIBLE POWER FOR YOUR DATA CENTRE
RELIABLE AND FLEXIBLE POWER FOR YOUR DATA CENTRE Highly efficient solutions for power distribution, management and monitoring POWER DISTRIBUTION WIRE-FREE MONITORING LEAK DETECTION Daxten provides comprehensive
More informationQuickSpecs. Overview. HP Power Distribution Rack. HP Power Distribution Rack. DA - 12859 North America Version 5 August 22, 2008 Page 1
Overview It's getting harder to manage a data center efficiently, with rising utility bills and ever-increasing demands due to processor power and server density increases. Growing user requests mean heavier
More informationIntelligent Power Distribution in the Data Center
Rack Power Intelligent Power Distribution in the Data Center Agenda Data Centre Power UPS Power Distribution Rack Mount PDU s UPS Power problems Configuration Capacity Power Distribution Types of Distribution
More informationQuickSpecs. HP Remote Monitored Power Distribution Units (mpdu) Overview
Overview HP Remote Monitored Power Distribution Units (PDU) provide rack level power monitoring over the network. With billing grade accuracy these PDUs are excellent choices for data centers wanting to
More informationHigh-Efficiency AC Power Distribution for Data Centers
High-Efficiency AC Power Distribution for Data Centers White Paper 128 Revision 2 by Neil Rasmussen > Executive summary The use of 240 volt power distribution for data centers saves floor space, simplifies
More informationAPC 3Phase Power Distribution
APC 3Phase Power Distribution North American 3 Phase Business Development Team All content in this presentation is protected 2008 American Power Conversion Corporation Objectives Understand the entire
More informationPanduit Infrastructure Management Software for Data Centers and Enterprises
Panduit Infrastructure Management Software for Data Centers and Enterprises SmartZone Rack Energy Kits Energy and Environmental Monitoring for Small Data Centers SmartZone Rack Energy Kits Features: Simple
More informationdctrack Data Center Infrastructure Management Visualize, Manage and Track IT and Facilities Systems dctrack
dctrack Data Center Infrastructure Management Visualize, Manage and Track IT and Facilities Systems dctrack An all-in-one solution for efficient data center management, spanning facilities, networking
More information8 Intelligent PDUs. Intelligent Power Distribution Units for Data Centers
BRC_PDU_US_B_BRC_IcePack 4/30/13 11:31 AM Page 2 8 Intelligent PDUs Intelligent Power Distribution Units for Data Centers Intelligent Power Distribution Units Siemon s line of intelligent PDUs provide
More informationQuickSpecs. HP Managed Power Distribution Units (mapdu) Overview
Overview Looking for a power distribution unit that meets the demands of high temperature operating environments and provides monitoring and switching capabilities? The HP Managed Power Distribution Unit
More informationWhat is a Datacenter?
What is a Datacenter? Telecom Room Primarily Cross Connect Equipment and switches. Computer room A room whose primary function is to house computer equipment. (Servers, Storage) 5 or less cabinets Small
More informationEfficiency and Other Benefits of 208 Volt Over 120 Volt Input for IT Equipment
Efficiency and Other Benefits of 208 Volt Over 120 Volt Input for IT Equipment By Neil Rasmussen White Paper #27 Revision 2 Executive Summary Decisions made regarding the distribution of 208V or 120V power
More informationFundamentals of Power
Fundamentals of Power Fundamentals of Power 2008 American Power Conversion Corporation. All rights reserved. All trademarks provided are the property of their respective owners. Learning Objectives At
More informationDistributing Power to Blade Servers
Distributing Power to Blade Servers Ten steps to selecting the optimal power distribution design With the growth in blade servers with dual or triple power supplies, a single rack of equipment can easily
More informationIncrease the efficiency of power distribution in your high-density data center
Increase the efficiency of power distribution in your high-density data center Abstract As power density in modern data centers increases, more focus has been placed on improving efficiency in the power
More informationEmerson Network Power Rack PDU Solutions Rack Power Distribution For Critical IT Equipment. AC Power For Business-Critical Continuity
Emerson Network Power Rack PDU Solutions Rack Power Distribution For Critical IT Equipment AC Power For Business-Critical Continuity Enhanced Performance And Management Of Dynamic IT Spaces IT space is
More informationA Scalable, Reconfigurable, and Efficient Data Center Power Distribution Architecture
A Scalable, Reconfigurable, and Efficient Data Center Power Distribution Architecture By Neil Rasmussen White Paper #129 Executive Summary Significant improvements in efficiency, power density, power monitoring,
More informationQuickSpecs. HP Modular Power Distribution Units (Zero-U/1U Modular PDUs) Overview
Overview HP Modular PDUs have a unique modular architecture designed specifically for data center customers who want to maximize power distribution and space efficiencies in the rack. Modular PDUs consist
More informationServer Technology Inc.
Server Technology Inc. Alternating Phase Power Distribution at the Data Center Rack PDU White Paper STI-100-012 2013-April-18 By Steve Hammond, Product Manager, Server Technology Headquarters Server Technology,
More informationMeasuring Power in your Data Center: The Roadmap to your PUE and Carbon Footprint
Measuring Power in your Data Center: The Roadmap to your PUE and Carbon Footprint Energy usage in the data center Electricity Transformer/ UPS Air 10% Movement 12% Cooling 25% Lighting, etc. 3% IT Equipment
More information415V DISTRIBUTION FOR GREEN DATA CENTERS
White Paper: HMRP-WP001-A1 October 1, 2010 415V DISTRIBUTION FOR GREEN DATA CENTERS Prepared by: Anthony (Tony) Hoevenaars, P. Eng President and CEO Mirus International Inc. Copyright 2005 Mirus International
More information5 Great Reasons to Use Colored Rack PDUs
5 Great Reasons to Use Colored Rack PDUs TABLE OF CONTENTS Why Color Rack PDUs? 5 Great Reasons to Use Colored Rack PDUs REASON 1. Easily Identify Redundant Power Feeds to IT Equipment REASON 2. Make it
More informationHow to enhance hyperconvergence with infrastructure management
White Paper Markets Served Data Centers By Tony Harvey, senior product manager engineering, Cisco Elizabeth Bagnas, business value marketing manager, Eaton How to enhance hyperconvergence with infrastructure
More informationPower Distribution Systems for the Dell PowerEdge M1000e Modular Server Enclosure - Selection and Installation
One Dell Way Round Rock, Texas 78682 www.dell.com Dell Enterprise White Paper Power Distribution Systems for the Dell PowerEdge M1000e Modular Server Enclosure - Selection and Installation January, 2008
More informationQualitative Analysis of Power Distribution Configurations for Data Centers
Qualitative Analysis of Power Distribution Configurations for Data Centers White Paper #4 2007 The Green Grid. All rights reserved. No part of this publication may be used, reproduced, photocopied, transmitted,
More informationEducation Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009
Education Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009 Agenda Overview - Network Critical Physical Infrastructure Cooling issues in the Server Room
More informationPrecisely distribute, monitor, analyze and manage power distribution in your facility to maximize processing capacity and promote power efficiency.
SECTION FOUR Table of Contents Page 69-78 Enclosure Power Distribution Units (PDUs) 70 71 Single-Phase Basic/Smart PDUs 72 3-Phase Basic/Smart PDUs 73 Single- and 3-Phase Switched PDUs 74 PDU Accessories
More informationNext Generation Power Distribution for the High-Density Datacenter
Next Generation Power Distribution for the High-Density Datacenter George Wasielewski Eaton/Powerware Power Quality Products and Services Dallas Enhance (IT) July 10, 2008 2007 Eaton Corporation. All rights
More informationA Scalable, Reconfigurable, and Efficient Data Center Power Distribution Architecture
A Scalable, Reconfigurable, and Efficient Data Center Power Distribution Architecture White Paper 129 Revision 1 by Neil Rasmussen > Executive summary Significant improvements in efficiency, power density,
More informationData Center Power Distribution and Capacity Planning:
Data Center Power Distribution and Capacity Planning: Understanding what you know and don t know about power usage in your data center 2009, Raritan Inc. About This Series Raritan, a leading provider of
More informationManagement and Wireless in the Data Center
SOLUTIONS BRIEF Management and Wireless in the Data Center High Performance Wireless Networks Management and Wireless in the Data Center Worldwide demand for new and more powerful IT-based applications,
More informationThe Different Types of AC Power Connectors in North America
The Different Types of AC Power Connectors in North America White Paper #20 Executive Summary A confusing array of AC power plugs and receptacles exist to deliver power to various electronic loads. This
More informationSelecting Rack-Mount Power Distribution Units For High-Efficiency Data Centers
C P I P O W E R M A N A G E M E N T WHITE PAPER Selecting Rack-Mount Power Distribution Units For High-Efficiency Data Centers By Anderson Hungria Sr. Product Manager of Power, Electronics & Software Published
More information415V DISTRIBUTION FOR GREEN DATA CENTERS
White Paper: HMRP-WP001-A5 June 5, 2012 415V DISTRIBUTION FOR GREEN DATA CENTERS Prepared by: Anthony (Tony) Hoevenaars, P. Eng President and CEO Mirus International Inc. Copyright 2012 Mirus International
More informationQuickSpecs. HP Fixed Cord PDUs & Extension Bars (Zero-U/1U Modular PDUs) Overview
Overview Fixed Cord PDUs and Extension Bars have a unique architecture designed specifically for 1U fixed rail servers (HP ProLiant DL360, HP ProLiant DL320, HP ProLiant DL140). This new design consists
More informationCisco Nexus 7000 Series Power Supply Modules
Cisco Nexus 7000 Series Power Supply Modules Product Overview The Cisco Nexus 7000 Series Power Supply Modules (Figures 1 and 2) deliver fault tolerance, high efficiency, load sharing, and hot-swappable
More informationZONIT POWER DISTRIBUTION SYSTEM ORDER CATALOG
ZONIT POWER DISTRIBUTION SYSTEM ORDER CATALOG Introduction The Zonit Data Center Power Distribution System (zpds ) offers an ultrareliable, turnkey power distribution system for modern high-availability
More informationRack Power Distribution Unit For Critical IT Equipment
AC Power for Business-Critical Continuity Rack Power Distribution Unit For Critical IT Equipment One Move Ahead With Emerson Network Power Emerson Network Power, a division of Emerson, is a global company
More informationRack Power Distribution
The Rack PDU Selector is located at: www.apc.com/tools/selector/pdu Test drive a metered or switched Rack Power Distribution Rack PDU at testdrive.apc.com 132 Fairgrounds Road West Kingston, RI 02892 Phone:
More informationPower to the adaptable data center
Business Unit Manager, Data Center Solutions, Eaton s electrical group IT managers have more options than ever to tailor the power infrastructure to their unique data center and business requirements.
More informationHow To Power A Bladecenter H Servers
Solutions Guide for IBM Data Center Architecture: IBM BladeCenter H Servers In today s high-demand enterprise environment, organizations need a reliable infrastructure to run compute-intensive applications
More informationAdvantages of Wire- Free Power Monitoring in the Data Center
Advantages of Wire- Free Power Monitoring in the Data Center Using PIPS (Per Inlet Power Sensing) and POPS (Per Outlet Power Sensing) CDU Technology with RF Code s Wire- Free Solutions February 3, 2011
More informationHow Eight California Data Centers Reduced Energy by 20%
How Eight California Data Centers Reduced Energy by 20% Sponsored by the California Energy Commission Public Interest Energy Research David Weightman, Energy Commission Specialist California Energy Commission
More informationPower Management Strategies for High-Density IT Facilities and Systems. A White Paper from the Experts in Business-Critical Continuity TM
Power Management Strategies for High-Density IT Facilities and Systems A White Paper from the Experts in Business-Critical Continuity TM Executive Summary Increases in data center density and diversity
More informationModel #: SMART2200VS. 2200VA / 2.2kVA line interactive tower UPS. Maintains 120V nominal output over an input range of 79 to 147V
SmartPro VS Tower UPS System Intelligent, line-interactive power management system Model #: SMART2200VS 2200VA / 2.2kVA line interactive tower UPS Maintains 120V nominal output over an input range of 79
More informationPacket Power. Data Center Solutions. Packet Power for Data Centers. Benefits. Features. The Packet Power Solution. Data Center Monitoring Made Easy
Data Center Solutions Packet Power for Data Centers Packet Power provides the easiest, most cost-effective way to capture detailed power and temperature information for both single-site and large multi-facility
More informationEO 13514 and Smart Federal Government Data Center Management
1 Overview In fiscal year 2009, the U.S. government used an astounding 1,095.7 trillion BTUs of energy. This total included everything from keeping the lights on at the Lincoln Memorial to maintaining
More informationDatacenter Design Issues
Datacenter Design Issues Topics Power Cooling Floor loading Wiring Density Power Higher voltage = better efficiency Fewer conversions = better efficiency Power factor correction 3 phase power (polyphase(
More information(Examples of various colocation sites)
Overview The largest factor involved in maintaining business servers today are the fixed costs associated with data centers. The Colocation Environment is an outsourcing model whereby a colocation company
More informationBenefits of. Air Flow Management. Data Center
Benefits of Passive Air Flow Management in the Data Center Learning Objectives At the end of this program, participants will be able to: Readily identify if opportunities i where networking equipment
More informationAlternating Phase Power Distribution at the Data Center Rack PDU
Alternating Phase Power Distribution at the Data Center Rack PDU White Paper STI-100-012 November 2013 - Updated August 2014 By Steve Hammond, Product Manager, Server Technology Marc Cram, Director of
More informationHP power and cooling technologies for the data center
HP power and cooling technologies for the data center Technology brief, 2 nd edition Introduction... 2 ProLiant server efficiency... 2 High-efficiency features... 2 Power monitoring and reporting tools...
More informationElectrical Systems. <Presenter>
Review Root Causes of Energy Inefficiency Roadmap to Maximize Energy Efficiency Best Practices Alternative Energy Sources Controls Take Aways Seek Professional Help. ENERGY INEFFICIENCY OF
More informationSpecialty Environment Design Mission Critical Facilities
Brian M. Medina PE Associate Brett M. Griffin PE, LEED AP Vice President Environmental Systems Design, Inc. Mission Critical Facilities Specialty Environment Design Mission Critical Facilities March 25,
More informationRack Systems Solutions
Rack Systems Solutions Designed to simplify cable management and improve power distribution Engineered by APC by Schneider Electric for Dell, NetShelter S is the next-generation rack enclosure solution
More informationProper Application of 415V Systems in North American Data Centers. A White Paper from the Experts in Business-Critical Continuity
Proper Application of 415V Systems in North American Data Centers A White Paper from the Experts in Business-Critical Continuity Introduction Increasing pressure to reduce operating expenses and be more
More informationIs your data center ready for virtualization?
Is your data center ready for virtualization? Important power considerations for virtualized IT environments By Chris Loeffler, Global Applications Manager, Distributed Power Solutions Eaton Corporation
More informationRe Engineering to a "Green" Data Center, with Measurable ROI
Re Engineering to a "Green" Data Center, with Measurable ROI Alan Mamane CEO and Founder Agenda Data Center Energy Trends Benchmarking Efficiency Systematic Approach to Improve Energy Efficiency Best Practices
More informationJanuary 16-17, 2013 Santa Clara
January 16-17, 2013 Santa Clara Open Rack Workshop Day 1 Matt Corddry, Facebook Pierluigi Sarti, Facebook Steve Mills, Facebook Richard Chan, Delta Products Patrick MacDonald, Sanmina Corp Eric Wilcox,
More informationOptimum Climate Control For Datacenter - Case Study. T. Prabu March 17 th 2009
Optimum Climate Control For Datacenter - Case Study T. Prabu March 17 th 2009 Agenda 2 About EDEC (Emerson) Facility Data Center Details Design Considerations & Challenges Layout Design CFD Analysis Of
More informationSMARTPLAY7. Increase your Deal Size and Profitability with SmartPlays
SMARTPLAY7 Increase your Deal Size and Profitability with SmartPlays - Comstor and Panduit have joined forces to promote the power and flexibility of UCS combined with market leading energy efficient enclosures.
More informationSolutions to Make Your Data Center Energy Effi cient
Common $en e: Solutions to Make Your Data Center Energy Effi cient Energy effi ciency is a life style. It s also common sense. In a data center, the name of the game is effi ciency and how many compute
More informationIssues Affecting the Design and Choice of Cabling Infrastructures within Data Centres
Issues Affecting the Design and Choice of Cabling Infrastructures within Data Centres White Paper Nexans Cabling Solutions September 2006 Executive Summary Planning for the unknown is always a difficult
More informationEaton epdu Data Center Product Catalog
Power distribution solutions Eaton epdu Data Center Product Catalog Switch N to Eaton. 2 eaton corporation Enclosure Power Distribution Units Table of contents Product Line Overview... 4 Choosing epdu
More informationHP Power Advisor utility: a tool for estimating power requirements for HP ProLiant server systems
HP Power Advisor utility: a tool for estimating power requirements for HP ProLiant server systems technology brief Abstract... 2 Introduction... 2 Key power parameters... 2 Input line voltage... 2 Device
More informationENERGY STAR Program Requirements Product Specification for Computer Servers. Test Method Rev. Apr-2013
ENERGY STAR Program Requirements Product Specification for Computer Servers Test Method Rev. Apr-2013 1 OVERVIEW The following test method shall be used for determining compliance with requirements in
More informationPower Commander Power Distribution Units from Wiremold/Legrand offer
Power Commander Power Distribution Units Rack Power Distribution Solutions for IT/Network Environments Power Commander Power Distribution Units from Wiremold/Legrand offer comprehensive power distribution
More informationIn Row Cooling Options for High Density IT Applications
In Row Cooling Options for High Density IT Applications By Ramzi Y. Namek, PE, LEED AP, BD+C; Director of Engineering 1 Users wishing to deploy high density IT racks have several In Row Cooling solutions
More informationServer Technology, Inc.
Server Technology, Inc. Cabinet Power Monitoring, Management & Control Within the Data Center White Paper STI-100-011 2010-Sept-27 by Calvin Nicholson, Senior Director Software and Strategic Alliances,
More informationOpen Rack Hardware v1.0
Open Rack Hardware v1.0 Authors: Pierluigi Sarti, System Designer Steve Mills, Mechanical Engineer 1 Scope This document describes the technical specifications for the custom rack that houses Open Compute
More informationED1259R5 Updated April 2011 For latest specs visit www.legrand.us/wiremold
Rack Power Distribution Solutions for IT/Network Environments Wiremold Power Commander Power Distribution Units offer comprehensive power distribution solutions for IT environments from networking solutions
More informationPacket Power. Data Center Solutions. Packet Power. Packet Power for Data Centers. Benefits. Features. The Packet Power Solution
Data Center Solutions for Data Centers provides the easiest, most cost-effective way to capture detailed power and temperature information for both single-site and large multi-facility operations. Gain
More informationFour secrets to avoiding data center downtime
Four secrets to avoiding data center downtime Four secrets to avoiding data center downtime 2 INTRODUCTION 3 POWER GENERATION & DELIVERY SYSTEMS 4 BREAKER TRIP ON FAILOVER 5 BREAKER TRIP DURING RESTART
More informationHow To Upgrade An Hp Power Distribution Rack To A Power Distribution Unit
Overview Power protection in the data center is critical to maintain up time, and the increased densities in data centers is driving the need for uninterruptible power with increased power density, power
More informationConsiderations for a Highly Available Intelligent Rack Power Distribution Unit. A White Paper on Availability
Considerations for a Highly Available Intelligent Rack Power Distribution Unit A White Paper on Availability Introduction Data centers are currently undergoing a period of great change. Data center managers
More informationPower Management. Raritan Description. http://www.raritan.com/products/power-management/
Raritan Description Raritan is a proven innovator of power management, infrastructure management, KVM and serial solutions for data centers of all sizes. In more than 50,000 locations worldwide, our hardware
More informationThe following are general terms that we have found being used by tenants, landlords, IT Staff and consultants when discussing facility space.
The following are general terms that we have found being used by tenants, landlords, IT Staff and consultants when discussing facility space. Terminology: Telco: Dmarc: NOC: SAN: GENSET: Switch: Blade
More informationPE8216/PE8324. Energy Intelligence Solutions
PE8216/PE8324 As part of its NRGence line, ATEN has developed a new generation of green energy power distribution units (eco PDUs) to effectively increase the efficiency of data center power usage. The
More informationEmerson Network Power Rack PDU Systems
AC Power For Business-Critical Continuity Emerson Network Power Rack PDU Systems Product Selection Guide - North American Models TABLE OF CONTENTS 1.0 EMERSON NETWORK POWER RACK PDU SYSTEMS..............................1
More informationLEVEL 3 DATA CENTER ASSESSMENT
Nationwide Services Corporate Headquarters 410 Forest Street Marlborough, MA 01752 USA Tel: 800-342-5332 Fax: 508-303-0579 www.eecnet.com LEVEL 3 DATA CENTER ASSESSMENT Submitted by: Electronic Environments
More informationEaton epdu. Intelligent and flexible power distribution
Eaton epdu Intelligent and flexible power distribution Introduction and overview With today s changing technology, increasing power demands and the need for reliability, data centre professionals require
More informationNavigating the Pros and Cons of Structured Cabling vs. Top of Rack in the Data Center
May 2013 Navigating the Pros and Cons of Structured Cabling vs. Top of Rack in the Data Center Executive Summary There is no single end-all cabling configuration for every data center, and CIOs, data center
More informationAPC APPLICATION NOTE #112
#112 Best Practices for Deploying the InfraStruXure InRow SC By David Roden Abstract The InfraStruXure InRow SC (ACSC100 and ACSC101) is a self-contained air conditioner for server rooms and wiring closets.
More informationCooling Small Server Rooms Can Be. - Jim Magallanes Computer Room Uptime: www.cruptime.com Uptime Racks: www.uptimeracks.com
Cooling Small Server Rooms Can Be Inexpensive, Efficient and Easy - Jim Magallanes Computer Room Uptime: www.cruptime.com Uptime Racks: www.uptimeracks.com Server Rooms Description & Heat Problem Trends
More informationPower and Cooling Guidelines for Deploying IT in Colocation Data Centers
Power and Cooling Guidelines for Deploying IT in Colocation Data Centers White Paper 173 Revision 0 by Paul Lin and Victor Avelar Executive summary Some prospective colocation data center tenants view
More informationOptimizing Power Distribution for High-Density Computing
Optimizing Power Distribution for High-Density Computing Choosing the right power distribution units for today and preparing for the future By Michael Camesano Product Manager Eaton Corporation Executive
More informationEnergy Management Solutions
Energy Management Solutions Introducing the world s most innovative intelligent Power Distribution Units (ipdus) designed to simplify rack energy and environmental management of your data center. Enlogic
More informationRack Power Distribution. Worldwide
Rack Distribution Worldwide Introduction APC TM by Schneider Electric TM offers a wide array of standardized Rack Distribution Units (PDUs) designed to increase manageability and efficiency in your data
More information