Erie VT/VS PopTop Series Two Position Spring Return Valves
|
|
|
- Percival Barker
- 9 years ago
- Views:
Transcription
1 Invensys uilding Systems, Inc. 135 Clifford venue P. O. ox 290 Loves Park, IL Erie VT/VS PopTop Series Two Position Spring Return Valves General & High Close-Off PopTop Zone Valves General Instructions pplication PopTop Series valve bodies and actuators provide easy installation for a variety of heating and cooling applications. Valve s actuator can be installed after valve body has been installed onto fan coil, baseboard or air handler. VS Series valves are available for low pressure steam applications. Features Direct replacement for all existing PopTop applications. Hysteresis synchronous motor for long life Spring return operation provides a fail-safe Valve body rated for 300 psi static pressure vailable in a variety of voltages ctuator mounts directly onto valve body without need for linkages or calibration Manual override lever (normally closed only) ctuator can be replaced without any tools, or removal of valve from system VS Series available for low pressure steam VT/VS Series with General Close-Off ctuator pplicable Literature EN-205 Water and Steam System Guidelines, F VT/VS Series with High Close-Off ctuator Litho in U.S F-2696-
2 SPECIFICTIONS Valve ctuator Service Hot and chilled water models, up to 50% glycol. Steam models up to 15 psi (both valve body and valve actuator must be rated for high temperature). System Static Pressure Limits 300 psi (2068. kpa). Close-off Refer to Table-2. Fluid/mbient Temperature Limits Refer to Table-1. Seat Leakage NSI class IV (0.01%) with pressure at inlet (-port/-port, if 3-way). ody Forged brass. Stem Nickel-plated. Seat rass. Paddle (VT series) una N. Paddle (VS series) Highly saturated nitrile. Voltage 2 50/60 Hz. 110/120 50/60 Hz Hz /60 Hz /60 Hz. Power Requirements 6.5 watts, 7.5 Va. 5, 20 Vac for actuators rated 20V or less; or 5, 277 Vac for actuators rated 277V. Control Signal On/off, 2 position, spring return. Timing, Full Open to Full Close 25 Sec max for 60 Hz; 30 Sec max for 50 Hz; and 9 Sec max spring return. Materials Stainless steel base plate, aluminum cover. mbient Temperature Limits: Shipping & Storage, -0 to 160 F (-0 to 71 C). Operating, Refer to Table-1. Humidity 5 to 95% relative humidity, non-condensing. gency Listings UL873: Underwriters laboratories (File #E929 Catagory Temperature Indicating and Regulating Equipment) CUL: UL Listed for use in Canada by Underwriters Laboratory. Canadian Standards C22.2 No. 2. European Community: EMC Directive (89/336/EEC). Low Voltage Directive (72/23/EEC). ustralia: This product meets requirements to bear the C-Tick Mark according to the terms specified by the Communications uthority under the Radio Communications ct of Shipping Weight (ctuator/valve ssembly) 2.25 lbs (1020 g). Table-1 Valve ody and ctuators Model Chart Model VTXXXX VSXXXX XX3XXX XXXXX Temperature Range 32 to 200 F 10 F (mbient) (0 to 93 0 C) 32 to 250 F 169 F (mbient) (0 to C), and/or 15 PSI (103 kpa) Steam a 32 to 200 F 10 F (mbient) (0 to 93 0 C) 32 to 250 F 169 F (mbient) (0 to C), and/or 15 PSI (103 kpa) Steam a a: For steam applications both valve body and valve actuator must be rated for high temperature. Example: VS2213G1020 = ssembly. VS2213 = Valve body. G1020 = ctuator. ccessories for Inverted Flare Connection Valves 3/" inverted flare bodies accept the following adapters to copper pipe: Union nut & elbow assembly, female for 1/2" (5/8" O.D.) copper, 15/16" long Union nut & coupling assembly, female for 1/2" (5/8" O.D.) copper, 1-1/16" long Union nut & coupling assembly, female for 3/" (7/8" O.D.) copper, 1-27/32" long Union nut & nipple assembly, male for 1/2" (5/8" O.D.) copper, 3" long Union nut & elbow assembly, male for 1/2" (5/8" O.D.) copper, 1-15/16" long Union nut & coupling assembly, female for 1" (1-1/8" O.D.) copper, 1-3/8" long 2
3 Table-2 Flow Coefficients & Maximum Close-Off Pressure Differential Valve Size Connection Type 2-way Cv (kv) 3-way Cv (kv) (G)* Close-Off P PSI (kpa) (H) PSI Close-Off P (kpa) 1/2" NPT, SW, Rp, SE 3/" IFL 1/2" NPT, SW, Rp, SE 3/" NPT, SW, IFL, Rp 1.0 (0.9) 1.5 (30) 60 (1) 75 (517) 2.5 (2.2) 3.0 (2.6) 0 (276) 50 (3) 1/2" NPT, SW, SE, Rp 3/" NPT, SW, IFL, Rp 3.5 (3.0).0 (3.) 25 (172) 30 (208) 1" SW 3/" NPT, SW, Rp 1" SW 5.0 (.3) 5.0 (.3) 20 (137) 25 (172) 3/" NPT, SW, Rp 7.5 (6.5) 7.5 (6.5) 17 (117) 20 (137) 1" NPT, SW, Rp 1-1/" SW 8.0 (6.9) 8.0 (6.9) 17 (117) 20 (137) Valve ody Legend NPT Threaded (female) SW Sweat IFL Inverted Flare SE Society utomotive Engineers Flare (male) Rp "Metric" Threaded (female) * G = General close off actuator H = High close off actuator Table-3 Water Valve Sizing Table* P 1.0 Cv 1.5 Cv 2.5 Cv 3.0 Cv 3.5 Cv.0 Cv 5.0 Cv 7.5 Cv 8.0 Cv 1 PSI Differential Pressure, P 2 PSI PSI PSI PSI * Water capacity in gallons per minute (GPM). 3
4 ody Type & Temperature T = On/Off (General) S = On/Off (Steam) High temperature actuator must be used. Part Numbering System Two Position Zone Valves, Spring Return ctuators 1 V X X X X X X X X X XX X 2 Options 0 = No Options = 5 6 Configuration 2 = 2-Way 3 = 3-Way 2 = 1/2" 3 = 3/" = 1" 5= 1-1/" Valve Size Electrical Leads 00 = 6" Wires 01 = Terminal lock with (General Temp., 2 VC only) 02 = 18" (Standard) Wire Leads Voltage = 2 VC, 50/60 HZ = 110/120 VC, 50/60 HZ D = 208 VC, 50/60 HZ T = 277 VC, 50/60 HZ U = 230 VC, 50 HZ 5 Connection Type vailability 3 1 = Sweat 1/2", 3/", 1", 1-1/" 2 = Threaded NPT 1/2", 3/", 1" 3 = Threaded Rp (metric) 1/2", 3/", 1" = Inverted Flare (Retrofit) 3/" 5 = SE Flare 1/2" Temperature Ratings 3 = General Temperature = High Temperature Spring Return vailability 1 = Normally Closed 2-way and 3-way 2 = Normally Open 2-way only CV Size ctuator Type G = On/Off (General Close-Off) H = On/Off (High Close-off) No. 2-way 3-way Size Connection Type 1 = /2" 1, 2, 3, 5 3/" 2 = /2" 1, 2, 3, 5 3/" 1, 2, 3, 1/2" 1, 2, 3, 5 3 = /" 1, 2, 3, 1" 1 5 = /" 1, 2, 3 1" 1 7 = /" 1, 2, " 1, 2, 3 1-1/" 1 ody & ctuator Combination Requirements Temperature Configurations ody Configuration V T X X X X T = General S = Steam If body configuration is T, actuator temp rating can be 3 or. If body configuration is S, actuator temp rating must be When ordering valve body only: use the first six positions to configure the valve. When ordering actuator only use the last seven positions to configure the actuator. Prefix with the letter "". Invensys inverted flare fittings must be ordered separately. See actuator accessories for fitting part numbers. End switch is only available if actuator temperature rating is general (3). 5 ctuators with Terminal blocks require endswitch and the endswitch is 2 V/5. 6 End switch is 20V/5 max for actuators rated 20V or less. End switch is 277V/5 max for actuators rated 277V. ctuator Spring Return Mode X X 3 X X X X 3 = General Temperature = High Temperature If actuator temp rating is 3, body style must be T. If actuator temp rating is, body style can be S or T. Example: ssembly: VT2213G Components: VT2213 = ody. G13020= ctuator. The actuator part number is prefixed with the letter "".
5 TYPICL PPLICTION (wiring diagram) Honeywell - Wire Leads Honeywell - Terminal lock ES TR ES TR Invensys - Erie Wire Leads Invensys - Erie Terminal lock TR TR ES ES Figure-1 Typical Wiring of a PopTop to Replace a Honeywell Valve 2 V 5 max Invensys - Erie Wire Leads White - Rodgers (1311 or 1321) (Hot) (Hot) 6 5 Invensys - Erie Terminal lock 6 5 TR TR ES ES Figure-2 Typical Wiring of a PopTop to Replace a Flair or White-Rodgers 3-Wire Valve 2 V 5 max 5
6 Flair - Terminal lock Taco - Terminal lock Invensys - Erie Wire Leads Invensys - Erie Wire Leads Invensys - Erie Terminal lock TR ES ES TR 2 V 5 max Figure-3 Typical Wiring of a PopTop to Replace a Flair or Taco 3-Wire Valve Thermostat T1 Valve #1 TR ES /TR ES T T URNER CONTROL Valve #2 T2 TR ES /TR ES Figure- Typical Multiple Valve Wiring 6
7 INSTLLTION Inspection Requirements Precautions Inspect the package for damage. If package is damaged, notify the appropriate carrier immediately. If undamaged, open the package and inspect the device for obvious damage. Return damaged products. Tools (not provided) Wrench 1 to 1-5/8" (if threaded valve) Soldering equipment (if sweat fit) or flare Training: Installer must be a qualified, experienced technician Other accessories as appropriate General W R N I N G Electrical shock hazard! Disconnect power before installation to prevent electrical shock or equipment damage. Make all connections in accordance with the electrical wiring diagram and in accordance with national and local electrical codes. Use copper conductors only. ll conductors shall be provided with insulation rated for the highest voltage motor and end switch circuits. C U T I O N void locations where excessive moisture, corrosive fumes, explosive vapors, or vibration are present. void electrical noise interference. Do not install near large conductors, electrical machinery, or welding equipment. When making lead connections within the actuator, use caution not to put leads or connectors below the motor. Federal Communications Commission (FCC) N O T E This equipment has been tested and found to comply with the limits for a Class digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in residential installations. This equipment generates, uses, and can radiate radio frequency energy and may cause harmful interference if not installed and used in accordance with the instructions. Even when instructions are followed, there is no guarantee that interference will not occur in a particular installation. If this equipment causes harmful interference to radio and television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the following measures: Reorient or relocate the receiving antenna. Increase the separation between the equipment and receiver. Connect the equipment to an outlet on a circuit different from that to which the receiver is connected. Consult the dealer or an experienced radio/television technician for help. Canadian Department of Communications (DOC) N O T E This class digital apparatus meets all requirements of the Canadian Interference-Causing Equipment Regulations. European Standard EN W R N I N G This is a class (European Classification) product. In a domestic environment this product may cause radio interference in which case the user may be required to take adequate measures. 7
8 Mounting The valves can be mounted in horizontal or vertical piping. When installed in horizontal piping, the actuator must be above the valve body. Refer to Figure-5. When installed in horizontal piping the actuator can be tilted left or right but it must not be tilted below 85 from vertical Figure-5 Mounting Position N O T E Make certain there is no overhead water source that may drip onto valve actuator. In normal service, some condensation may occur on or around the valve. drip pan may be necessary or the valve body may be insulated. Piping These valves must be piped so the paddle closes against the direction of flow. Flow is from to. Refer to Figure-6a to Figure-6f. When installing the actuator to a normally closed valve, the actuator must be placed in the manually open position by using the manual operating lever. The first time the valve is operated electrically, the manual operating lever of the actuator will transfer to the automatic position. The manual operating lever can be used to allow flushing of the system after installation. The valves are designed for application in closed hydronic heating and cooling systems. High levels of dissolved oxygen and chlorine found in open systems may attack the valve materials and result in premature failure. Install over a drip pan if condensation in chilled water applications occurs. C U T I O N Use in systems which have substantial make-up water (open systems) is not recommended. Follow proper water treatment practices and system procedures. Refer to document F for Water and Steam EN205 Guidelines. N O T E Three-way valves always require a normally closed actuator. Three-way valves are always closed at the port when no power is applied to the motor. On power-up the valve closes to port on three-way valves. Orient the three-way valve body as needed for normally open or normally closed flow through coil. 8
9 POWER OFF POWER OFF Coil Coil Figure-6a 2-Way Valve With Normally Closed ctuator Figure-6b 2-Way Valve With Normally Open ctuator POWER OFF POWER OFF Coil Coil Figure-6c 3-Way Valve in Mixing Configuration Normally Closed to the Coil Figure-6d 3-Way Valve in Mixing Configuration Normally Open to the Coil POWER OFF POWER OFF Coil Coil Figure-6e 3-Way Valve in Diverting Configuration Normally Closed to the Coil Figure-6f 3-Way Valve in Diverting Configuration Normally Open to the Coil N O T E Three-way N.O. applications can be achieved when using a N.C. actuator, by piping the valve in reverse. The thee-way examples show normally closed actuators. Sweat Connections C U T I O N Do not solder with actuator in place, or with paddle against seat, as the heat can damage the unit. efore soldering, move the manual open lever into Open position then remove the actuator from the body. Orient paddle so it is not against a seat. Use lead or tin based solder with melting point below 600 F. Do not overheat. Direct flame tip away from valve. Cool valve quickly with a wet cloth. ody assembly can be submerged for leak testing prior to attaching the actuator. 9
10 Threaded Connection pply Teflon tape to all but the last two threads of male pipe thread. Hand screw the pipe into the valve, turning it as far as it will go. Use a wrench to fully tighten the valve to the pipe. Do not over tighten or strip the threads. Inverted Flare Union Connection Solder fittings onto pipe. Use solder with melting point below 600 F. Mount valve to union nuts. Release utton Manual Operating Lever Release utton Manual Operating Lever Mating Hole General Close-Off (G) Stem High Close-Off (H) Mating Hole Figure-7 PopTop Installation Installing ctuator on Valve ody Slowly latch the manual operating lever in the open, engaged position (G1 or H1 only). Depress the release button (see Figure-7). lign the body with the actuator to ensure the stem is inserted into the large mating hole on the bottom side of the actuator. Engage the actuator on the body and release the button. C U T I O N Do not use the valve body to manually open the actuator as damage to the valve actuator will result. CHECKOUT 1. Make sure the valve stem rotates freely before and after installing the actuator. 2. If the stem does not operate freely it may indicate that the stem was damaged and may require that the valve be repaired or replaced. 3. fter the piping is under pressure, check the valve body and the connections for leaks.. fter the valve and actuator are installed, power the actuator and check the operation. EORY OF OPERTION PopTop Series are two position spring return valves. When powered, the actuator moves to the desired position, tensing the spring return system. When power is removed the actuator returns to the normal position. PopTop Series two position spring return valves can be purchased with an optional built-in auxiliary SPDT end switch for interfacing or signaling; for example, zone pump burner control. MINTENNCE FIELD REPIR PopTop Series two position spring return valves are maintenance free. Replace defective modules. ctuator may be replaced without removing the valve. Regular maintenance of the total system is recomended to assure sustained, optimum performance. Replace any damaged or failed components with complete replacement unit. 10
11 DIMENSIONL DT /16" /" /8" 12 7/16" /8" /8" /16" /16" -PORT -PORT 2-WY C 3-WY D Figure-8 VT/VS Series General Close-Off /16" /" /" /8" 1 9/16" /16" /16" /16" -PORT -PORT 2-WY C 3-WY D Figure-9 VT/VS Series High Close-Off Table- Dimensions - inches (mm) Valve ody Size C D (General Close-Off) D (High Close-Off) 1/2" Sweat 1-5/16 (33) 15/16 (23) 1-5/16 (33) 3-5/16 (8) 3-5/8 (92) 3/" Sweat 1-3/8 (35) 15/16 (23) 1-11/16 (3) 3-3/8 (86) 3-3/ (95) 1" Sweat 1-11/16 (3) 15/16 (23) 1-11/16 (3) 3-5/8 (92) (102) 1-1/" Sweat 1-7/8 (7) 1 (25) 1-13/16 (6) 3-11/16 (9) -1/8 (105) 1/2" NPT, Rp 1-3/8 (35) 15/16 (23) 1-5/16 (33) 3-3/8 (86) 3-5/8 (92) 3/" NPT, Rp 1-11/16 (3) 15/16 (23) 1-7/16 (37) 3-5/8 (92) (102) 1" NPT, Rp 1-7/8 (7) 1 (25) 1-11/16 (3) 3-11/16 (9) -1/8 (105) Inverted Flare See Figure-11-3/16 (106) -7/16 (113) SE Flare See Figure-10 11
12 -PORT -PORT 26 1" /" /16" /16" 112 7/16" Figure-10 SE - High Close-Off Style ctuator Shown -PORT -PORT /16" 2-WY /" 3-WY /16" /16" 109 5/16" Figure-11 Inverted Flare - General Close-Off Style ctuator Shown F ll specifications are nominal and may change as design improvements are introduced. Invensys uilding Systems shall not be liable for damages resulting from misapplication or misuse of its products. The following trademarks are the property of Invensys: Invensys Erie PopTop Printed in U.S..
TAC Erie VT/VS PopTop Series Two Position Spring Return Valves
TC 1354 Clifford venue P. O. ox 2940 Loves Park, IL 61132-2940 www.tac.com TC Erie VT/VS PopTop Series Two Position Spring Return Valves General & High Close-Off PopTop Zone Valves General Instructions
VC Series Zone Valves BALANCED 2-WAY AND 3-WAY HYDRONIC VALVES
VC Series Zone Valves BALANCED 2-WAY AND 3-WAY HYDRONIC VALVES PRODUCT DATA Design VC Series zone valves consist of: 2-way or 3-way valve housing available with various connection ends Spindle and cartridge
XE70 SERIES VC SERIES BALANCED HYDRONIC VALVES 2-WAY AND 3-WAY
XE70 SERIES VC SERIES BALANCED HYDRONIC VALVES 2-WAY AND 3-WAY PRODUCT SPECIFICATION SHEET switched off. This results in energy savings during mild weather. Normal control will resume when T3 fails to
! WARNING. Before using product, read and understand instructions.
McDonnell & Miller Installation & Maintenance Instructions MM-600G) Series FS8-W General Purpose Liquid Flow Switch OPERATION This control is an independently mounted water flow sensing device that makes
VG2000 Series Cast Iron Flanged Globe Valves
VG2000 Series ast Iron Flanged Globe Valves Installation Instructions Part No. 14-1161-106, Rev. Issued November 15, 2013 Supersedes June 15, 2007 pplications VG2000 Series ast Iron Flanged Globe Valves
VU53S; VU54S; VU443A; VU444A; VU843A; VU844A Fan Coil Valves and Actuators
VU53S; VU54S; VU443A; VU444A; VU843A; VU844A Fan Coil Valves and Actuators APPLICATION VU Fan Coil Actuator and Valves The VU443, VU444, VU843 and VU844 Fan Coil Valve Actuators are used in conjunction
INSTALLATION AND OPERATION INSTRUCTIONS - (LOW FLOW MODELS) (Before installation, compare electrical needed for the model of heater selected)
CHRONOMITE INSTANT-FLOW WATER HEATER INSTALLATION AND OPERATION INSTRUCTIONS - (LOW FLOW MODELS) (Before installation, compare electrical needed for the model of heater selected) TABLE 1 Model No. Wattage
TABLE 1. Rugged cast aluminum alloy casing,celcon waterways with nichrome parts White (unless stainless steel housing)
CHRONOMITE INSTANT-FLOW MICRO WATER HEATER INSTALLATION AND OPERATION INSTRUCTIONS - (LOW FLOW MODELS) (Before installation, compare electrical needed for the model of heater selected) TABLE 1 Model No.
BUILT-IN DISHWASHER INSTALLATION INSTRUCTIONS
BUILT-IN DISHWASHER INSTALLATION INSTRUCTIONS PLEASE READ COMPLETE INSTRUCTIONS BEFORE YOU BEGIN LEAVE INSTALLATION INSTRUCTIONS AND USER'S GUIDE WITH OWNER ALL ELECTRIC WIRING AND PLUMBING MUST BE DONE
STC 3S012-020-A Series Solenoid Valves
STC 3S012-020-A Series Solenoid Valves 3S012-020-A Series Solenoid Valve Specifications Valve Model 3S012-1/8-A 3S012-1/4-A 3S020-1/8-A 3S020-1/4-A Port Size (NPT) 1/8 1/4 1/8 1/4 Valve Type Action 3 Way,
Indirect-Fired Storage Water Heater Models WH-30 through WH-80 INSTALLATION AND OPERATING INSTRUCTIONS
Indirect-Fired Storage Water Heater Models WH-30 through WH-80 INSTALLATION AND OPERATING INSTRUCTIONS Contents Page Ratings and Specifications..................... 2 Installation Requirements......................
CEILING CASSETTE FAN COIL UNIT
CEILING CASSETTE FAN COIL UNIT Operation and Installation Manual MHCFC4W-04, 08, 12, 16 Four way ceiling cassette fan coil unit Please read this manual before using the fan coil unit. Installation and
36G22, 36G23, 36G24 & 36G52 36J22, 36J23, 36J24 & 36J52 DSI and HSI Single Stage Combination Gas Valve
Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE. DESCRIPTION
StructureScan HD Module. Installation Guide ENGLISH. www.bandg.com www.simrad-yachting.com www.lowrance.com
StructureScan HD Module Installation Guide ENGLISH www.bandg.com www.simrad-yachting.com www.lowrance.com Disclaimer As Navico is continuously improving this product, we retain the right to make changes
USB Dual Handset Adapter for Nortel 1100-Series IP Phones
1021 USB Dual Handset Adapter for Nortel 1100-Series IP Phones User Guide Document#: 90-00039 [email protected] [email protected] www.algosolutions.com Table of Contents Algo 1021 USB Dual
OWNER S MANUAL FORCE 10 MARINE COMPANY 23080 HAMILTON ROAD RICHMOND, BC CANADA V6V 1C9 TEL: (604) 522-0233 FAX: (604) 522-9608
Electric Water Heater OWNER S MANUAL FORCE 10 MARINE COMPANY 23080 HAMILTON ROAD RICHMOND, BC CANADA V6V 1C9 TEL: (604) 522-0233 FAX: (604) 522-9608 If your water Heater is Damaged or you have questions
Stainless Steel Single and Dual Circulation Kits
Instruction Sheet P/N 160780 01 Stainless Steel Single and Dual Circulation Kits Introduction The single and dual high-pressure circulation kits allow you to vary and control the circulation rate of coating
Install Guide CT101. Caution. Caution
Install Guide CT101 PG 1 Caution top cover Your thermostat is a precise instrument, handle it with care. Turn off electricity to the system before installing or servicing thermostat or any part of the
Select Radiators Installation Guide
Select Radiators Installation Guide Table of Contents Informational Symbols...3 Before You Begin...4 Select Rough-In... 5 Connection Installation...6 Optional Piping Arrangements...7 Conventional Wall
Manual. Simrad StructureScan LSS-1 Sonar Module. English
Manual Simrad StructureScan LSS-1 Sonar Module English www.simrad-yachting.com A brand by Navico - Leader in Marine Electronics Disclaimer As Navico is continuously improving this product, we retain the
Wiser Panel Meter, Model Number WISERCTPM200 Installer s Guide
Instruction Bulletin EAV85226 08/2014 Wiser Panel Meter, Model Number WISERCTPM200 Installer s Guide Retain for future use. Product Description Kit Contents The Wiser Panel Meter is for use in energy management
Oil and Coolant Circulating Heating System. Model - OCSM
Oil and Coolant Circulating Heating System Model - OCSM Installation & Operation Manual 216280-000 REV 2 Identifying Your System The HOTSTART heating system is designed to heat fluids for use in marine
On/Off Relay Switch and 3-Way Switch Kit
45637/45638 Wireless Lighting Control On/Off Relay Switch and 3-Way Switch Kit marthome Control the On/Off status of permanently installed lighting, fans and more! www.lowes.com/iris 2012 JASCO Made in
INSTALLATION INSTRUCTIONS & HOME OWNERS MANUAL EEMAX ELECTRIC TANKLESS WATER HEATERS IMPORTANT SAFETY INFORMATION
INSTALLATION INSTRUCTIONS & HOME OWNERS MANUAL EEMAX ELECTRIC TANKLESS WATER HEATERS IMPORTANT SAFETY INFORMATION When installing or using any high voltage electrical appliance, basic safety precautions
MCR1900 Media Converter 19-Slot Chassis
MCR1900 Media Converter 19-Slot Chassis Installation Guide Part #5500304-11 Copyright Statement This document must not be reproduced in any way whatsoever, either printed or electronically, without the
VC series BALANCED HYDRONIC VALVES 2 -WAY AND 3 -WAY
VC series BALANCED HYDRONIC VALVES 2 -WAY AND 3 -WAY APPLICATION PRODUCT HANDBOOK The VC series balanced hydronic valves allow greater control of hot and/or cold water flow. The VC series balanced hydronic
Rotary actuator for 2 and 3-way (control) ball valves Torque 5 Nm Nominal voltage AC 100... 240 V Control: Open/close or 3-point Auxiliary switch
echnical data sheet Rotary actuator LR-S Rotary actuator for and -way (control) ball valves orque 5 Nm Nominal voltage C... 4 V Control: Open/close or -point uxiliary switch echnical data Electrical data
I nstallation. M100Q Series Proportional Actuator with R81Q Controller Board for Thermistor Sensor Applications. Tools Needed.
FANs 268.1, 1628.3 Installation Bulletin M100Q Issue Date 1099 M100Q Series Proportional Actuator with R81Q Controller Board for Thermistor Sensor Applications I nstallation Parts Included M110QGA-1 and
Powers Controls TH 192 S Single Temperature Room Thermostat
Technical Instructions Document No. 155-065P25 TH 192-1 Powers Controls TH 192 S Single Temperature Room Thermostat 50 60 70 80 TH0355R1 70 80 POWERS Description The TH 192 S thermostats are proportional
ENCL-MZ800-WAL ENCL-MX800-PAN MNL-800-101. TAC I/A Series MicroNet MN 800 Series Controller Installation Instructions. Application.
ENCL-MZ800-WAL ENCL-MX800-PAN MNL-800-101 TAC I/A Series MicroNet MN 800 Series Controller Installation Instructions Application The TAC I/A Series MicroNet 800 Series Controllers are programmable, interoperable,
V46 Pressure-Actuated Water-Regulating Valve
V46 Pressure-Actuated Water-Regulating Valve Product Bulletin Code No. LIT-125687 Issued August 9, 2010 Supersedes October 1, 1995 The V46 pressure-actuated modulating valves come in two types of control
Seaward Products OWNER S MANUAL WATER HEATERS. Serial Number:
Seaward Products WATER HEATERS OWNER S MANUAL Serial Number: IMPORTANT SAFETY INSTRUCTIONS WARNING When using electrical appliances, basic safety precautions to reduce the risk of fire, electrical shock,
INSTANT HOT WATER RECIRCULATING SYSTEM
INSTANT HOT WATER RECIRCULATING SYSTEM INSTALLATION AND OPERATING INSTRUCTIONS Save manual for future reference MODEL 500800 Warning Please read carefully before proceeding with installation. Your failure
JOB or CUSTOMER: ENGINEER: CONTRACTOR: SUBMITTED BY: SPECIFICATION REF: QUANTITY TAG NO. MODEL NO. GPM FEET LEAD LENGTH COMMENTS.
Redi-Flo2, 2 Environmental Submersible Pumps MP1 Submittal Data QUANTITY TAG NO. MODEL NO. GPM FEET LEAD LENGTH COMMENTS Technical Data Motor Type: Water-Filled, variable speed submersible Maximum Fluid
4.3-inch Back-Up Camera
TM 4.-inch Back-Up Camera Model No.: PKC0BU4 Owner s Manual and Warranty Information Read these instructions completely before using this product. Retain this Owner s Manual for future reference. INTRODUCTION
Advantium 2 Plus Alarm
ADI 9510-B Advantium 2 Plus Alarm INSTALLATION AND OPERATING INSTRUCTIONS Carefully Read These Instructions Before Operating Carefully Read These Controls Corporation of America 1501 Harpers Road Virginia
4 Posiflow Proportional Solenoid Valves
4 Posiflow Solenoid Brass or Stainless Steel Bodies 1/4" to 1/2" NPT 2/2 Features Flow rates adjustable between 0% and 100% of rating Flow rate can also be regulated by a range of electrical inputs (sensors,
Introduction. Angle/Flared/Sequence/Changeover Service Valves. Valves D-193. www.usa.siemens.com/hvac
Introduction Angle/Flared/Sequence/Changeover Service D-193 In this section, you will find flared, angled, sequence and changeover valves for use in service applications. D-194 Need additional assistance?
ADSL Modem Installation Guide. Model # 36R515 Part # 030-300108 Rev. D Revision Date 12/2000. ADSL Modem Installation Guide
ADSL Modem Installation Guide Model # 36R515 Part # 030-300108 Rev. D Revision Date 12/2000 ADSL Modem Installation Guide Installation Instructions Westell ADSL Modem 1. Package Inspection and Contents...2
ScreenLogic Wireless Connection Kit. Installation Guide. pool/spa control system
pool/spa control system ScreenLogic Wireless Connection Kit Installation Guide P/N 520663 - Rev B 8 Technical Support Contact Technical Support at: Sanford, North Carolina (8 A.M. to 5 P.M.) Phone: (800)
MPX-Series Diesel Engine Shut Down Valves (Manual Reset / Air Pressure and Manual Closure Options)
MPX-Series Diesel Engine Shut Down Valves (Manual Reset / ir Pressure and Manual Closure Options) Selection, pplication and Maintenance Valve Numbers MPX-300 MPX-301 MPX-302 MPX-303 MPX-310 MPX-500 MPX-501
Square D Clipsal DIN-Rail Four-Channel Auxiliary Input Unit
Square D Clipsal DIN-Rail Four-Channel Auxiliary Input Unit SLCLE5504AUX for Use with Wired C-Bus Networks Instruction Bulletin Retain for future use. Square D Clipsal DIN-Rail Four-Channel Auxiliary Input
USE &CARE GUIDE. Remote Faucet Pump System. See Important Safeguards on page 2
Remote Faucet Pump System USE &CARE GUIDE See Important Safeguards on page 2 An exclamation point within an equilateral triangle is intended to alert user to the presence of important operating and maintenance
! WARNING. McDonnell & Miller Installation & Maintenance Instructions MM-217(I) Series 150S and 157S (Snap Switch, All Models except 157S-RB-P)
Series 150S and 157S (Snap Switch, All Models except 157S-RB-P) Low Water Cut-Off/Pump Controllers For Steam Boilers and Other Level Control Applications McDonnell & Miller Installation & Maintenance Instructions
2 WAY (2/2) AND 3 WAY (3/2) BRASS AND STAINLESS STEEL SOLENOID VALVES
2 WAY (2/2) AND 3 WAY (3/2) BRASS AND STAINLESS STEEL SOLENOID VALVES DIRECT ACTING Brochure N-289 SPECIFICATIONS Port Size: 1/8 and1/4 Solenoid Valve for air, oil, water and other fluids Flow Direction:
NFC Communication Tray Model: HHX-IT3-Z
INSTRUCTION MANUAL NFC Communication Tray Model: HHX-IT3-Z ENGLISH CONTENTS Introduction...3 Important safety information...4 Know your unit...6 Transferring data to the PC...7 Care and maintenance...8
VALVES FOR REFRIGERATING SYSTEMS
VALVES FOR REFRIGERATING SYSTEMS FROM QUALITY OUR NATURAL DEVELOPMENT Achieved the goal of fi fty years working in the industry of Refrigeration and Air Conditioning, Castel Quality Range of Products is
Model 70A00-1. GSM Cellular Communications Center
Home Automation, Inc. Model 70A00-1 GSM Cellular Communications Center Operation Manual Document Number 70I00-1 Rev A August, 2009 Contents Description... 1 Use with security systems...1 Everyday use...2
ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL
RANCO INSTALLATION INSTRUCTIONS ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL Relay Electrical Ratings PRODUCT DESCRIPTION The Ranco ETC is a microprocessor-based family of electronic temperature controls,
CoolTop. A unique water cooled air-conditioning unit for server room cooling from the top AC-TOPx-CW-240/60
CoolTop A unique water cooled air-conditioning unit for server room cooling from the top AC-TOPx-CW-240/60 Application CoolTop is a new, unique air conditioning unit especially designed for datacenters.
Operator: Save these instructions for future use!
WHITE-RODGERS 36C01 Combination Gas Valves (24 Volt and 120 Volt Models) INSTALLATI INSTRUCTIS FAILURE TO READ AND FOLLOW ALL INSTRUCTIS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CTROL COULD CAUSE
Ceiling Mount Air Handler Manual
www.surna.com 303.993.5271 Ceiling Mount Air Handler Manual Models: CMAH12, CMAH18, CMAH24, CMAH30, CMAH36, CMAH48, CMAH60 Revised: September 2014 Table of Contents Warranty Information 4 Limited Warranty
2012 Valve & Valve Actuator Catalog. For new construction or retrofits, simplify projects with our complete selection. www.usa.siemens.
2012 Valve & Valve Actuator Catalog For new construction or retrofits, simplify projects with our complete selection. www.usa.siemens.com/hvac Our dynamic duos provide comprehensive control. Fast installation
3. SEISCO PARTS & SERVICE REMOVAL AND REPAIR GUIDE
4 3. SEISCO PARTS & SERVICE REMOVAL AND REPAIR GUIDE A. Changing the Control Board B. Replacing a Heating Element C. Thermistor Replacement D. High Limit Switch Replacement E. Level Detector Replacement
INSTALLATION INSTRUCTIONS Fan Coil Replacement Coil Kit EBX & EBXX
Fan Coil Replacement Coil Kit EBX & EBXX These instructions must be read and understood completely before attempting installation. These instructions covers the installation of replacement coil kit into
PRESSURE AND TEMPERATURE SENSORS for use with the BURNERLOGIX Burner Management System and PPC4000 Series Fuel/Air Ratio Controller
BLZPTS-1 NOVEMBER 19, 2013 TS350 TS752 BLPS PRESSURE AND TEMPERATURE SENSORS for use with the BURNERLOGIX Burner Management System and PPC4000 Series Fuel/Air Ratio Controller DESCRIPTION The BLPS, TS350
Model 1210C Battery Powered Pump Shown. Description
12 Volt DC Rotary Vane Pump Series 1200C Model 1210C Battery Powered Pump Shown Description of Included Models Model Number FR1205C FR1210C FR1211C FR2410C FR2411C Description Basic 12 volt DC pump with
Installation Manual. Rental Services. Air Handling Units CHS-SVN01A-EN. July 2008
Installation Manual Rental Services Air Handling Units July 2008 CHS-SVN01A-EN Copyright 2008 Trane All rights reserved This document and the information in it are the property of Trane and may not be
3 WAY (3/2) POPPET VALVES FOR AIR AND VACUUM SERVICE SOLENOID OR AIR ACTUATED BROCHURE N-223
3 WAY (3/2) POPPET VALVES FOR AIR AND VACUUM SERVICE SOLENOID OR AIR ACTUATED BROCHURE N-223 HERION S HIGH PERFORMANCE POPPET VALVES For those applications requiring high Cv, fast response times, large
Installer Guide smart connect
Installer Guide smart connect TM 7330 Wireless Remote Humidity Sensor Please read all instructions before proceeding. The wireless remote humidity sensor monitors the humidity passing through the return
Your safety and the safety of others are very important.
NATURAL GAS TO PROPANE CONVERSION KIT 090 INSTALLATION INSTRUCTIONS FOR ALTITUDES 0 -,00 FT. ONLY PROPANE CONVERSION KIT SAFETY... INSTALLATION REQUIREMENTS... Tools and Parts... LP Gas Requirements...
Drayton Digistat +2RF/+3RF
/+3RF Programmable Room Thermostat Wireless Model: RF700/22090 Model: RF701/22092 Power Supply: Battery - Thermostat Mains - Digistat SCR Invensys Controls Europe Customer Service Tel: 0845 130 5522 Customer
LED Security Spotlight User Manual
MOT ION-TR ACKING LED Security Spotlight User Manual www.jascoproducts.com 1-800-654-8483 2 TABLE OF CONTENTS Parts List 3 Questions? Missing Parts? 4 Installation (Wall mount) 6-9 Installation (Eave mount)
BPM Series. Metered Rack Mount PDUs. Quick Start Guide. Models Covered:
WTI Part No.: 13963 Rev.: PM Series Metered Rack Mount PDUs Models Covered: PM-8HS20-1 PM-16VS30-1 PM-24VS30-1 PM-24VS30-D PM-8HS20-2 PM-16VS30-2 PM-24VS30-2 PM-24VS30-Y PM-16VS20-1 PM-24VS20-1 PM-24VS20-D
SunMaxx Solar Filling Station Operating Instructions
SunMaxx Solar Filling Operating Instructions Content 1. Declaration of conformity... 2 2. Introduction... 2 3. Transportation and unpacking... 4 4. Mounting and commissioning... 5 5. End of operation...
Cisco TelePresence MCU 4500 Series safety and compliance information
Cisco TelePresence MCU 4500 Series safety and compliance information On this page: Safety information symbols Operating guidelines Safety warnings Technical specifications Compliance information WEEE information
Electric Water Heater
Electric Water Heater Operation and Installation Manual (LIMITED WARRANTY AND TANK REPLACEMENT POLICY) The following information should be noted at time of installation and retained for future reference.
7 High-Resolution Digital Photo Frame
TM 16-1003 User s Guide 7 High-Resolution Digital Photo Frame One demo photo included, as illustrated Please read this user s guide before using your new photo frame. Package contents Photo Frame AC Adapter
BERMAD Fire Protection
400E-2M/700E-2M IOM Bermad Electrically Controlled Deluge Valve with EasyLock Manual Reset Model: 400E-2M/700E-2M INSTALLATION OPERATION MAINTENANCE Application Engineering BERMAD 400E-2M/700E-2M Bermad
POWERS Controls No. 4 Pneumatic Damper Actuator
POWERS Controls No. 4 Pneumatic Damper Actuator Technical Instructions Document No. 155-032P25 AP 331-2 Actuator Assembly 331-2929 Typical Actuator Assembly 331-2904 Typical Actuator Assembly 331-3000
Power supply unit Model: PAC-SC50KUA
Building Air Conditioning Control System Power supply unit Model: PAC-SC50KUA Installation Manual Contents 1. Safety precautions... 1 2. Product feature... 2 1. Specification... 2 2. Appearance... 2 3.
A99B Series Temperature Sensors
FANs 125, 121, 930, 930.5 Product/Technical Bulletin A99 Issue Date 0615 A99B Series Temperature s The A99B Series Temperature s are passive PTC (Positive Temperature Coefficient) sensors. The A99B sensors
MP8000 Series Pneumatic Valve Actuators
14-1161- 9, Rev. A Technical Bulletin MP8000 Issue Date March 2016 MP8000 Series Pneumatic Valve Actuators Pre-Assembly Details Page 3 MP8000 Actuator Components 3 Tools Required to Assemble an MP8000
T7560A,B,C Digital Wall Module
T7560A,B,C Digital Wall Module HONEYWELL EXCEL 5000 OPEN SYSTEM BEFORE INSTALLATION All wiring must comply with local electrical codes and ordinances or as specified on installation wiring diagrams. Digital
DN [mm] [m 3 /h] Characterizing disk Dimensions / Weights see «Dimensions and weights», page 3 Motorizing
Technical data sheet R5.. Characterized control valves, 3-way, with external thread for open and closed cold and warm water systems for modulating control on the water side of air-handling and heating
M SERIES REFRIGERANT COIL MODULE REFRIGERANT COILS for R-22, R-407C, R-410A
Bulletin 20-20.2 / July 2012 M SERIES REFRIGERANT COIL MODULE REFRIGERANT COILS for R-22, R-407C, R-410A ➀ ➁ ➂ Model Number Key M 2430 C L 1 - A - ➀ Unit Type M=Modular Nominal Capacity 2430=24000 to 30000
Installation and Operating Instruction Manual
Electric Mini Tank Water Heaters CMT-1.3 CMT-2.5 CMT-4.0 CMT-ST70 Tempering valve Optionally available Installation and Operating Instruction Manual Table of Contents Important Safety Instructions 3 General
REGULATORS 175/153 Series
175/153 Series 175 HEATING 153 COOLING Watson McDaniel reserves the right to change the designs and/or materials of its products without notice. 2002 Watson McDaniel Company Revised 7/2002 175 / 153 Screwed
P70, P72, and P170 Series Controls for Dual Pressure Applications
P70, P72, and P170 Series Controls for Dual Pressure Applications Product Bulletin Code No. LIT-125455 Issued August 30, 2012 Supersedes September 1, 2000 The P70, P72, and P170 controls for dual pressure
Float and Thermostatic Traps Series H, C and X
Hoffman Specialty Installation & Maintenance Instructions HS-(E) and Thermostatic Traps Series H, C and X Series C & NPT Series C NPT Series X NPT Series C NPT Series H Ratings Maximum Max. Operating NPT
Failure to comply with the following cautions and warnings could cause equipment damage and personal injury.
1.0 IMPORTANT RECEIVING INSTRUCTIONS Visually inspect all components for shipping damage. Shipping Damage is not covered by warranty. If shipping damage is found, notify carrier at once. The carrier is
ES-CAM2A IP Camera. www.etiger.com
ES-CAM2A IP Camera www.etiger.com EN Box content - ES-CAM2A x1 - Mounting bracket x1 - AC Adaptor x1 - User Manual x1 and apps Before using the ES-CAM2A, download the app isecurity+ on the App Store or
Installation and maintenance instructions. Danfoss Vent
Installation and maintenance instructions Danfoss Vent 1 Unit design... 2 2 Project planning and installation instructions... 3 2.1 Ventilation...3 2.2 Piping installation....3 2.3 Condensation line...4
How To Use A Flowmeter
INLINE flowmeter for continuous flow measurement Economic integration in pipe systems without any additional piping 3-wire frequency pulse version to directly interface with PLC s (both PNP and NPN) Connection
VG7000 Series Bronze Control Valves
VG7000 Series Bronze Control Valves Product Bulletin VG7000 Series Code No. LIT-977140 Issued November 15, 2013 Supersedes March 29, 2013 VG7000 Series Bronze Control Valves are designed primarily to regulate
Broadband Telecommunications Drop Amplifier
INSTALL SHEET BDA Broadband Telecommunications Drop Amplifier Introduction The Broadband Telecommunications Drop Amplifier (BDA) is a two-way, 1 GHz amplifier designed for customer-premise amplification
Submersion/Insertion Toroidal Sensor
Instruction Sheet PN 51A-228/rev.P December 2010 Model 228 Submersion/Insertion Toroidal Sensor For additional information, please visit our website at www.emersonprocess.com/raihome/liquid/. CAUTION SENSOR/PROCESS
User Manual. RK-2d / RK-2t. dedicated KVM switch and rackmount screen technology. Designed and manufactured by Austin Hughes
dedicated KVM switch and rackmount screen technology User Manual RK-2d / RK-2t 1U Short Depth Keyboard Drawer Designed and manufactured by Austin Hughes 751 Legal Information First English printing, October
Powers Controls Free Energy Band TH 193 HC Heating/Cooling Room Thermostat
Document No. 155-068P25 TH 193-4 Powers Controls Free Energy Band TH 193 HC Heating/Cooling Room Thermostat 50 60 70 80 70 TH0356R1 60 80 POWERS Description The TH 193 HC thermostats are proportional dual
Powers Controls TH 192 HC Heating/Cooling Room Thermostat
Powers Controls TH 192 HC Heating/Cooling Room Thermostat Technical Instructions Document No. 155-066P25 TH 192-2 50 60 70 80 70 TH0356R1 60 80 POWERS Description The TH 192 HC thermostats are proportional
P66 Series Electronic Fan Speed Controls
P66 Series Electronic Fan Speed Controls Product Bulletin Code No. LIT-125465 Issued September 30, 2009 Supersedes March 23, 2006 The P66 Series Electronic Fan Speed Controls are refrigerant pressure actuated,
T7079A,B Solid State Remote Temperature Controllers
T7079A,B Solid State Remote Temperature Controllers FEATURES PRODUCT DATA Switch selection of heat or cool mode. Temperature sensing up to 400 feet. Does not require field calibration. 0K NTC temperature
MVX-Series Diesel Engine Shut Down Valves (Cable Operated Closure/Integral Reset Lever Types)
MVX-Series Diesel Engine Shut Down Valves (Cable Operated Closure/Integral Reset Lever Types) Selection, pplication and Maintenance Valve Numbers MVX-301 MVX-302 MVX-303 MVX-501 MVX-502 MVX-503 MVX-801
Replacement parts. WM97+ gas-fired water boiler Boiler Manual. OBTAIN PARTS ONLY THROUGH WEIL-McLAIN THE BOILER CONTAINS CERAMIC FIBER MATERIALS
Replacement parts DO NOT SERVICE THE BOILER WITHOUT A WM97+ MAINTENANCE KIT AVAILABLE Failure to adhere to these guidelines can result in severe personal injury, death or substantial property damage. The
Daily use. Never use alcohol or other solvents to clean any part of the loudspeakers!
BeoLab 6002 Guide WARNING: To reduce the risk of fire or electric shock, do not expose this appliance to rain or moisture. Do not expose this equip ment to dripping or splashing and ensure that no objects
Valve series MN-06 acc. to NAMUR, 3/2-way G1/4 750 Nl/min (0.762 Cv)
Valve series MN-06 acc. to NAMUR, 3/2-way G1/4 750 Nl/min (0.762 Cv) Order code Series and function 1) Plug socket see page 5.042. MN-06-310-HN-442 Standard coil 1) 441 = 12 V DC, 4.2 W 442 = 24 V DC,
4-Port Pocket. USB KVM Switch with USB 2.0 Hub
4-Port Pocket USB KVM Switch with USB 2.0 Hub Manual - 1 - Index 1. INTRODUCTION... 3 1.1 FEATURES... 3 1.2 PHYSICAL DIAGRAM... 4 1.3 PACKAGE CONTENTS... 4 2. SPECIFICATIONS... 5 2.1 ERAL... 5 2.2 LED
with MERCURY FREE 1 HP Relays ! WARNING Before using this product read and understand instructions.
B Installation & Maintenance Instructions MM-414 Series 150E and 157E Low Water Cut-Off/Pump Controllers For Steam Boilers and Other Level Control Applications A Typical Applications: Primary or secondary
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules.
Power Max Level 2 Charging Station en Installation and Operating Instructions This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the