Chilled Water System Presentation

Size: px
Start display at page:

Download "Chilled Water System Presentation"

Transcription

1 Chilled Water System Presentation

2 Constant Volume Distribution Constant Volume Distribution

3 Air-conditioning System Components

4 Constant Volume System Components

5 Typical 3-way Valve Zone

6 Full Load Condition

7 Fully Loaded Coil Supply water temperature 45 F Design return water temp. 55 F Coil design flow 100 GPM Coil design pressure drop 20 FT Load (flow x 10 F x 500) 500,000 Btuh Coil design flow 20 FT Bypass flow 0 GPM Bypass P 3-way valve closed 3-way valve pressure drop 10 FT Pump flow and head FT Actual return water temp 55 F

8 Unloaded Condition

9 Unloaded Coil Supply water temperature 45 F Design return water temp. 55 F Coil design flow 0 GPM Coil design pressure drop 3-way valve closed Load (flow x 10 F x 500) 0.0 Btuh Coil design flow 0 FT Bypass flow 100 GPM Bypass P 20 FT 3-way valve pressure drop 10 FT Pump flow and head FT Actual return water temp 45 F

10 So What? When the load on the coil is zero, the valve is returning unused chilled water at essentially supply temperature. Cold return water unloads the chillers, causing them to operate inefficiently.

11 Part Load Condition

12 Partially Loaded Coil Supply water temperature 45 F Design return water temp. 55 F Coil design flow 50 GPM Coil design pressure drop 20 FT Load (flow x 10 F x 500) 250,000 Btuh Coil design flow 5 FT Bypass flow??? GPM Bypass P 3-way partially closed 3-way valve pressure drop 10 FT Pump flow and head??? 30 FT Actual return water temp?? F

13 3-way Valve Characteristic 125 1/2 Through Coil 1/2 Through Bypass 100 % Flow Full Flow Through Coil Full Flow Through Bypass % Valve Stroke

14 What s Really Happening?

15 Coil with 3-way Valve at Mid-position Supply water temperature 45 F Design return water temp. 55 F Load (flow x 10 F x 500) 250,000 Btuh Coil design pressure drop 20 FT Coil flow 62.5 GPM Coil 62.5% flow 7.8 FT Coil leaving water temp 53 F Bypass flow 62.5 GPM Bypass P 7.8 FT 3-way valve pressure drop 10 FT Pump flow and head FT Actual return water temp 49 F ( F F)

16 Head 2 = Head 1 (Flow 2 / Flow 1 ) 2 Head 2 = 20(.625/1) 2 Head 2 = 20(.3906 ) Head 2 = 7.8

17 T = Load/ Flow X 500 T = 250,000/62.5 X 500 T = 8 Therefore, LWT coil = = 53

18 RWT = (Flow 1 X EWT + Flow 2 X LWT)/ Flow RWT = (62.5 X X 53)/125 RWT = 49

19 3-way Valve in Mid Position

20 3-way Valve System Deficiencies 1. Low return water temperatures. 2. Robs chilled water from other coils at part load conditions. 3. Increases flow in primary piping. 4. Adds additional chillers on line. 5. Chiller performance is reduced.

21 Chiller Performance Curve KW per Ton Percent Load

22 Pump Sizing Select for full chiller flow Head must be adequate for: Chiller evaporator Longest circuit Coil Three way valve Air separator

23 System Configuration Constant Volume

24 Any Questions?

25 Variable Volume Constant Speed

26 Variable Volume Constant Speed Primary Secondary System Primary Circuit Includes Chillers & Primary Pump. Constant water flow through the chiller is maintained and chilled water is produced Secondary Chilled water is circulated to the Circuit demand area (load) by using Secondary pumps.

27 PRIMARY - SECONDARY

28 Other Famous Names of Primary- Secondary Primary Production Loop Secondary Distribution Loop

29 Fundamental Idea

30 No Secondary Flow

31 Primary = Secondary

32 Primary > Secondary

33 Primary < Secondary

34 Control Valve in Secondary

35 Common Pipe Design Criteria Use the flow of the largest chiller Chiller staging at half of this flow is common Head loss in common <1 1/2 ft Distribution pipe size is often used where reductions would be inconvenient Three pipe diameters between tees Excessive length increases total head loss Low velocities in system piping

36 Control Valve in Secondary Variable flow through coil Constant flow through system Three Way Valve Variable flow through coil Variable flow through system Two Way Valve

37 Variable Volume Constant Speed PRIMARY SECONDARY CIRCUIT

38 Control Valves Change the Secondary System Curve H1 H2 H3 Head Flow F1 F2 F3

39 Head Absorbed by 2-way Valves 150 TDH of pump Pump curve HD Varying differential pressure absorbed by control valve System resistance % Flow

40 Pump Horsepower Comparison Constant Flow Primary Pumps, only HP Secondary Pumps + Primary Pumps = V/V % Design Flow

41 Constant vs Variable Volume Constant Flow, C/S Pump (3 Way Valve) Pump Over-haded by 150% C/S Pump (2 Way Valve) Base Design HP % % Full Load (Design) HP Constant Flow, C/S Pump (3 Way Valve) C/S Pump (2 Way Valve) Pump HD Matched to Design Flow % Flow

42 Any Questions?

43 Step Function of Chillers

44 Production = Distribution

45 Distribution > Production

46 Production > Distribution

47 Loading a Chiller A chiller is a heat transfer device. Like most equipment, it is most efficient at full load. To load a chiller means: Supply it with its rated flow of water Insure that water is warm enough to permit removal of rated Btu without freezing the water

48 Chiller Performance Curve 1.1 KW per Ton Percent Load

49 Check Valve in Common?

50 What can we do?

51 What else can we do? Reset Supply Temperature Lower chiller set point when mixing occurs to maintain a constant temperature to the system. Expect increases in cost of chiller operation at lower set point: 1-3% per degree of reset. Delays start of the next chiller.

52 What else can we do? Coils that are selected at higher supply temperatures will not be impaired by small changes. Loads that require fixed temperatures may use a small chiller to reverse the effects of mixing.

53 Multiple Chillers

54 60/40 Chiller Split to Help Minimize Low Part Load Operation

55 Typical Load Profile % Time % Load

56 Three Unequally Sized Chillers

57 Approaching Flow = Load % Load Time

58 Any Questions?Alternate Pumping Methods Comparison

59 Two Pipe Direct Return

60 Two Pipe Reverse Return

61 Primary-Secondary Pumping. Simplest to install. Simplest to operate. Flexible in design for present and future. Efficient to operate. May over-pressurize near zones.

62 Primary-Secondary-Tertiary

63 Primary-Secondary-Tertiary Pumping. Best piping flexibility. Best expansion flexibility. Provides hydraulic decoupling. Efficient to operate. May require added horsepower. Requires additional pumps and piping. Increased controls complexity.

64 Primary-Secondary-Tertiary Hybrid

65 Primary-Secondary-Tertiary Hybrid Pumping. Low present horsepower. Low future horsepower. Good piping flexibility. Good expansion flexibility. Provides hydraulic decoupling. May require added horsepower Requires additional pumps and piping. Increased controls complexity.

66 Primary-Secondary Zone Pumping

67 Primary-Secondary Zone Pumping. Low built out horsepower. Low system head. Increased control complexity. Present horsepower total higher due to future needs. Present pumps sized for future requirements. Difficult to apply in retrofits projects.

68 Any Questions?

69 Variable Volume Variable Speed

70 Why Do We Need Variable Speed Secondary Pumps??? For Energy Saving. For better & optimise operation.

71 How Do We Achieve This Reduction In Power Consumption?? By Using Variable Frequency Drive and Logic controller with the Secondary Pumps.

72 Power Comparison at Reduced Speed

73 Basic Law which helps in achieving this Affinity law 1. Flow 2 = Flow 1 (Speed 2 / Speed 1 ) 2. Head 2 = Head 1 (Speed 2 / Speed 1 ) 2 3. BKW 2 = BKW 1 (Speed 2 / Speed 1 ) 3 If Diameter of Impeller is to be trimmed then instead of speed the same can be used in above formulas.

74 Operating Cost Annual Operating Cost $ $0.10/kWh Motor Horsepower

75 Variable flow system Pump Curve System Curve as two way valves close Head System Curve Flow

76 Energy savings offset Pump Curve Increased head loss System Curve at part load System Curve at design flow H Q

77 Pumps in parallel Head Single Pump System Curve Pumps in Parallel Flow

78 Parallel pumping power savings Horsepower % Single Parallel Pump Single Large Pump Two Parallel Pumps Flow %

79 Theoretical Savings

80 Establishing Efficiency Curves 50 % 60 % 70 % 80 % % Efficiency 85 % 85 % 80 % 100 % 90 % Head, Feet 30 % 40 % 50% 60 % 70 % % Speed Curves 80 % Constant Efficiency Curve GPM

81 Variable Speed Efficiencies FT, 85.9 % 600 A B 1770 E D 600 C

82 No Valve System Curve Head Overall system curve 25 FT Differential Head Maintained Across Load (Set Point) Set Point Flow Distribution piping head loss curve Pump TDH

83 110 Effect of Constant Set Point 100 Head Overall system curve Control curve Distribution piping head loss curve Set point, 25 FT Pump TDH Flow

84 Control curve P1 P2 100% 75% Control Curve Head 50% P Variable Head Loss Flow

85 Large systems, long pipe runs Annual Operating Cost $0.10/kwh) Single C/S Pump, 200% Overheaded Single C/S Pump, No Overheading Variable Speed Pump Total Equivalent Pipe Length (feet)

86 Variable Head Loss Ratio Base C/S, Constant Flow System Pump Head Matched to System at Design Flow Percent Design BHP C/S, Variable Flow V/S, 0% Variable Hd Loss, 100% Constant Hd V/S, 25% Variable Hd Loss, 75% Constant Hd V/S, 50% Variable Hd Loss, 50% Constant Hd V/S, 75% Variable Hd Loss, 25% Constant Hd V/S, 100% Variable Hd Loss, 0% Constant Hd % Flow

87 Variable Head Ratio w/ Overheading Constant Flow, C/S Pump 150 Pump O Headed by 150% (3 Way Valve) C/S Pump (2 Way Valve) Base Design HP % % Full Load (Design) HP Constant Flow, C/S Pump (3 Way Valve) C/S Pump (2 Way Valve) V/S, 100% Constant HD V/S, 25/75* V/S, 50/50 V/S, 75/25 V/S, 100% Variable HD Pump HD Matched to Design Flow * 25/75 Means: 25 % Variable HD Loss 75 % Constant HD Loss

88 Locations of Sensor Where to install the Sensor? What type of Sensor?

89 Single Point Pressure Sensor Load Balancing Valve 2 Way Valve Chillers Single Point Pressure Sensing Panel with PLC & VFD`s Primary Pumps Common Secondary Pumps Air - Separator

90 Single Point Pressure Sensor Is Single Point Pressure Sensor Correct? Wrong!! Why? -Pump is a differential pressure device. -A single point is only influence by pressure. This is good for booster only. -In a closed loop system, system pressure rises due to thermal expansion, pumps will slow down. -When static pressure decrease, pumps will speed up. -This is self-defeating since now the pump speed is not influence by the system load changes, but rather by system water pressure. -Therefore, single pressure sensor are a misapplication in a closed loop HVAC system.

91 Single Point Differential Pressure Sensor Primary - Secondary Circuit With Variable Speed Secondary Pumps Load Balancing Valve DPT 2 Way Valve Chillers Panel with PLC & VFD`s Primary Pumps Common Secondary Pumps Air - Separator

92 Opening/Closing of 2- Way Valve -Signal from the sensor, installed at load regulates the valve opening & closing. -This way differential across 2-way valve also changes & accordingly output signal is given to PLC. 2 Way Valve Control Temperature Sensor Load ` ` Output to PFU from DPT `

93 Question: Can we put the DPT across coil alone?

94 Question: Across the pumps?

95 Single Point Differential Pressure Sensor Primary - Secondary Circuit With Variable Speed Secondary Pumps To Maximize energy system, we must maximize the variable head loss in the system. This is done by locating the sensor at the most remote zone ( hydraulically) in the system.

96 System Control Curve Ft Hd Control curve Overall system curve Distribution piping head loss curve Set point, 25 FT Pump TDH Flow, gpm

97 Variable vs Constant Head Loss

98 The Active Zone Zone set points do not have to be the same. Pump controller scans all zones often, comparing process variable to set point in each case. Pumps are controlled to satisfy the worst case. What happens to the rest of the zones?

99 Basic Concept PMU Set Value 4 20 ma From Field Sensor (DPT) PFU Output To VFD/Pump PFU Pump Functional Unit PMU Pump Management Unit

100 Multi Point Differential Pressure Sensor Different Sensor Signal To Common PFU Panel DPT DPT Balancing Valve Panel with PLC & VFD`s Load Chillers Secondary Pumps Common

101 Multi Point Differential Pressure Sensor POSSIBILITY OF MULTIPLE PROCESS SIGNALS FROM DIFFERENT ZONES PMU Set Value VFD Module PFU VFD Multiple Process Signals From Field Sensors All zones can have different set values

102 Multi Point Differential Pressure Sensor POSSIBILITY OF MULTIPLE PROCESS SIGNALS FROM DIFFERENT ZONES Multiple Process Signals From Field Sensors PMU Set Value VFD 4 20 ma Sig Signal Comparator PFU VFD Signal Comparator All zones can have different set values

103 HVAC Control System DPT Signal Comparator

104 HVAC Control System DPT Signal Comparator - High and Low Signal Selections - Signal Averaging - High/Low Limit Control The module has the addition following features : 1) LED status indications 2) Accepts voltage or milliamp input signal 3) DIP switch-selectable operating modes 4) Accepts 24 VAC/DC power

105 HVAC Control System DPT Signal Comparator Benefits 1) We are able to supply VFD systems with multiple inputs signals ranges to compete with our competitors. 2) We are able to use Grundfos PFU 2000 as the main processor to control the full system operations. 3) We will be minimising outsourcing or external controller in order to serve the HVAC market. 4) The MM allows us to integrate into the system multiple sensor control at a more cost effective price.

106 HVAC System Other Types of Systems

107 Separate System for Each Zone Balancing Valve DPT DPT Load 2 Way Valve Panel with PLC & VFD`s Chillers Secondary Pumps Primary Pumps Common Air - Separator Expansion Tank

108 Separate System for Each Zone Systems In Multi - Zones Two options: 1. Separate Systems can be used for different zones. So each zone will have its own sensor. 2. Signal from different zone sensors is given to the common PFU and most deviated signal, from the set point, is given as output.

109 Tertiary Pumping System VFD pumps For Each Zone Balancing Valve DPT DPT Load 2 Way Valve E-pumps E-pumps Chillers Primary Pumps Common Air - Separator Secondary Pump Expansion Tank

110 Reverse Return Pumping Load Balancing Valve DPT Chillers Panel with PLC & VFD`s Primary Pumps Common Secondary Pumps Air - Separator

111 Reverse Return Pumping Benefits : 1) Equalize the pressure drops of each zone. 2) Selections of the sensor becomes easier. 3) If load are similar or symmetrical, 1 centrally located sensor is adequate. 4) As in direct return system, multiple sensor can still provide a benefit to the end user.

112 Type of VFD Systems

113 Possible Options of Variable Speed panels Type ME - Multiple Pumps & Multiple VFDs. Type MF - Common VFD for Multiple Pumps.

114 System with Multi Pumps & Multi VFDs Signal from Field Sensor(s) (DPT) Panel with PFU & PMU VFD - 1 VFD - 2 Secondary Pumps

115 System with Common VFD for All Pumps Signal from Field Sensor(s) (DPT) Panel with PFU & PMU VFD Secondary Pumps

116 APPROVAL FROM INTERNATIONAL AGENCIES Approval from CE, U/L Conforms to - Electromagnetic compatibility (89/336/EEC) to standard EN and EN and Electrical equipment design 73/23/EEC standard to EN

117 Single PMU For Control of 8 Zones/Pumps PMU PFU PFU

118 Single PMU For Control of 8 Zones/Pumps PMU PFU PFU PFU PFU

119 The End

Centrifugal Fans and Pumps are sized to meet the maximum

Centrifugal Fans and Pumps are sized to meet the maximum Fans and Pumps are sized to meet the maximum flow rate required by the system. System conditions frequently require reducing the flow rate. Throttling and bypass devices dampers and valves are installed

More information

Applying Pressure Independent Control Valves in H.V.A.C. Systems. A Presentation to: Orange Empire ASHRAE Santa Ana Nov. 17, 2009

Applying Pressure Independent Control Valves in H.V.A.C. Systems. A Presentation to: Orange Empire ASHRAE Santa Ana Nov. 17, 2009 Applying Pressure Independent Control Valves in H.V.A.C. Systems A Presentation to: Orange Empire ASHRAE Santa Ana Nov. 17, 2009 1 Introduction I know, as building design consultants, so much of your effort

More information

HIGH PERFORMANCE CHILLED WATER SYSTEMS. EarthWise HVAC. EarthWise HVAC High Performance CHW Plants

HIGH PERFORMANCE CHILLED WATER SYSTEMS. EarthWise HVAC. EarthWise HVAC High Performance CHW Plants HIGH PERFORMANCE CHILLED WATER SYSTEMS EarthWise HVAC Simon Ho e: Simon.Ho@irco.com 2012 EarthWise HVAC High Performance CHW Plants Low Flow Low Temperature Systems Variable Flow Systems Variable CHW Variable

More information

Chilled Water System Commissioning: Variable Primary Flow. John D. Villani, P.E. Associate Grumman/Butkus Associates

Chilled Water System Commissioning: Variable Primary Flow. John D. Villani, P.E. Associate Grumman/Butkus Associates Chilled Water System Commissioning: Variable Primary Flow John D. Villani, P.E. Associate Grumman/Butkus Associates AIA Quality Assurance Learning Objectives 1. History of chilled water system configurations

More information

Commissioning - Construction Documents (Page 1 of 6)

Commissioning - Construction Documents (Page 1 of 6) Commissioning - Construction Documents (Page 1 of 6) A. General Information Climate Zone: Building Type: Conditioned Area (sf): Reviewer's Name: Reviewer's Agency: Note: Design Review for each system/subsystem

More information

VARIABLE VOLUME / VARIABLE SPEED SYSTEMS APPLICATIONS

VARIABLE VOLUME / VARIABLE SPEED SYSTEMS APPLICATIONS Bulletin D-120B Pages D120-115 to D120-118 VARIABLE SPEED PRIMARY CHILLED WATER PUMP CONTROL WITH TWO WAY VALVE DIRECT RETURN SYSTEM DESCRIPTION: The volume of water supplied to the system is varied in

More information

R22. K Control. Indoor Unit. Nomenclature. Compatibility PL H 3 G K H B. Unit style Heat Pump Horse Power

R22. K Control. Indoor Unit. Nomenclature. Compatibility PL H 3 G K H B. Unit style Heat Pump Horse Power R22. K Control. Indoor Unit. Nomenclature. PL H 3 G K H B Compatibility Unit style Heat Pump Horse Power Control Boost Heaters R22. K Control. Outdoor Unit. Nomenclature. PU H 3 Y K A Compatibility Outdoor

More information

Frequently Asked Questions

Frequently Asked Questions Frequently Asked Questions System and Valve Basics: 1. Q: What is good cooling coil performance? A: The temperature range is controlled within +/- 0.5 F (0.28 C) off the cooling coil at set point or below.

More information

Building Performance With District Cooling

Building Performance With District Cooling Reprinting this proof for distribution or posting on web sites is not permitted. Authors may request permission to reprint or post on their web site once the fi nal version has been published. A reprint

More information

Life Cycle Costing Analysis of Water-cooled Chillers. Chillventa Nuremburg, Germany

Life Cycle Costing Analysis of Water-cooled Chillers. Chillventa Nuremburg, Germany Life Cycle Costing Analysis of Water-cooled Chillers Chillventa Nuremburg, Germany Spring 2012 Description Life Cycle Cost Analysis is a method of determining and comparing the total costs of investment

More information

CHILLED WATER PLANT PUMPING SCHEMES. James J. Nonnenmann, PE Stanley Consultants, Inc. Muscatine, Iowa

CHILLED WATER PLANT PUMPING SCHEMES. James J. Nonnenmann, PE Stanley Consultants, Inc. Muscatine, Iowa CHILLED WATER PLANT PUMPING SCHEMES James J. Nonnenmann, PE Stanley Consultants, Inc. Muscatine, Iowa ABSTRACT From the advent of central chilled water plants, the system for delivering chilled water to

More information

ENERGY RETROFIT PROGRAM

ENERGY RETROFIT PROGRAM ENERGY RETROFIT PROGRAM An innovative but simple retrofit for existing hot water and chilled water piping systems that will help you save money. REDUCE FLOW BY 50% REDUCE PUMP HEAD BY 75% REDUCE PUMP POWER

More information

HVAC Processes. Lecture 7

HVAC Processes. Lecture 7 HVAC Processes Lecture 7 Targets of Lecture General understanding about HVAC systems: Typical HVAC processes Air handling units, fan coil units, exhaust fans Typical plumbing systems Transfer pumps, sump

More information

Principals of Condensing Boiler System Design

Principals of Condensing Boiler System Design Principals of Condensing Boiler System Design Dennis Jones, P.E. Member ASHRAE ABSTRACT Condensing boilers can provide significant energy savings due to operating efficiencies as high as 98% as compared

More information

presents Hydraulic Separation Beyond Primary / Secondary Piping

presents Hydraulic Separation Beyond Primary / Secondary Piping presents Hydraulic Separation Beyond Primary / Secondary Piping This Webinar is exclusively sponsored and the property of Caleffi Hydronic Solutions. All rights reserved. October 2007 Modern compact boilers

More information

Water cooled chiller plant (cp/vs)

Water cooled chiller plant (cp/vs) Data Center Water cooled chiller plant (cp/vs) Design Envelope File No: 9.573 Date: december 16, 2014 Supersedes: 9.573 Date: november 14, 2014 design envelope s performance improvements are among the

More information

OPTIMIZING CONDENSER WATER FLOW RATES. W. A. Liegois, P.E. Stanley Consultants, Inc. Muscatine, Iowa

OPTIMIZING CONDENSER WATER FLOW RATES. W. A. Liegois, P.E. Stanley Consultants, Inc. Muscatine, Iowa OPTIMIZING CONDENSER WATER FLOW RATES W. A. Liegois, P.E. Stanley Consultants, Inc. Muscatine, Iowa T.A. Brown, P.E. Thermal Energy Corporation Houston, Texas ABSTRACT Most chillers are designed for a

More information

Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks

Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks Presentation Outline Common Terms / Concepts HVAC Building Blocks Plant Level Building Blocks Description / Application Data Green opportunities Selection Criteria Air Distribution Building Blocks same

More information

MAC-120HE-01 Air-Cooled Chiller

MAC-120HE-01 Air-Cooled Chiller MAC-120HE-01 Air-Cooled Chiller 10 Ton / 120,000 BTUH Air-Cooled Chiller 208/230-1-50/60 1 HVAC Guide Specifications Air-Cooled Liquid Chiller Nominal Size: 10 Tons Multiaqua Model Number: MAC-120HE-01

More information

Product Data Bulletin

Product Data Bulletin Product Data Bulletin Adjustable Frequency Drives and HVAC Systems An Application Guide September, 1994 Raleigh, NC, U.S.A. INTRODUCTION All buildings pose the same problem: how to heat or cool the air

More information

IDEA Presentation SMALL CAMPUS CHILLED WATER PLANT OPTIMIZATION.

IDEA Presentation SMALL CAMPUS CHILLED WATER PLANT OPTIMIZATION. IDEA Presentation SMALL CAMPUS CHILLED WATER PLANT OPTIMIZATION. Pre-Project Details Hawaiian Community College Campus consisting of 16 individual buildings totaling 308,000 sq.ft of conditioned space.

More information

- White Paper - Data Centre Cooling. Best Practice

- White Paper - Data Centre Cooling. Best Practice - White Paper - Data Centre Cooling Best Practice Release 2, April 2008 Contents INTRODUCTION... 3 1. AIR FLOW LEAKAGE... 3 2. PERFORATED TILES: NUMBER AND OPENING FACTOR... 4 3. PERFORATED TILES: WITH

More information

By Steven C. Severini, P.E., Member ASHRAE

By Steven C. Severini, P.E., Member ASHRAE The following article was published in ASHRAE Journal, July 2004. Copyright 2004 American Society of Heating, Refrigerating and Air- Conditioning Engineers, Inc. It is presented for educational purposes

More information

KU DESIGN GUIDELINES APPENDIX XVI RECOMMENDED BAS I/O CONTROL POINTS BY EQUIPMENT / SYSTEM

KU DESIGN GUIDELINES APPENDIX XVI RECOMMENDED BAS I/O CONTROL POINTS BY EQUIPMENT / SYSTEM KU DESIGN GUIDELINES APPENDIX XVI RECOMMENDED BAS I/O CONTROL POINTS BY EQUIPMENT / SYSTEM AIR HANDLING UNITS... 1 CHILLERS... 2 COOLING TOWERS... 2 CLOSED LOOP COOLERS... 2 MISCELLANEOUS SUPPLY FANS...

More information

COMMERCIAL HVAC CHILLER EQUIPMENT. Air-Cooled Chillers

COMMERCIAL HVAC CHILLER EQUIPMENT. Air-Cooled Chillers COMMERCIAL HVAC CHILLER EQUIPMENT Air-Cooled Chillers Technical Development Programs (TDP) are modules of technical training on HVAC theory, system design, equipment selection and application topics. They

More information

CHILLER PLANT CONTROL MULTIPLE CHILLER CONTROLS

CHILLER PLANT CONTROL MULTIPLE CHILLER CONTROLS CHILLER PLANT CONTROL MULTIPLE CHILLER CONTROLS By: Michael J. Bitondo, Mark J. Tozzi Carrier Corporation Syracuse, New York August 1999 INTRODUCTION In December of 1998, the American Refrigeration Institute

More information

NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES

NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES 8.1 INTRODUCTION Testing, adjusting, and balancing of HVAC systems can best be accomplished by following a series of systematic procedures. The NEBB TAB

More information

POLK STATE COLLEGE CHILLER PLANT EVALUATION WINTER HAVEN, FLORIDA APRIL 2, 2014. C arastro & A ssociates, C&A# 5747

POLK STATE COLLEGE CHILLER PLANT EVALUATION WINTER HAVEN, FLORIDA APRIL 2, 2014. C arastro & A ssociates, C&A# 5747 POLK STATE COLLEGE WINTER HAVEN, FLORIDA CHILLER PLANT EVALUATION APRIL 2, 2014 C&A# 5747 C arastro & A ssociates, c o n s u l t i n g e n g i n e e r s inc. 2609 W. De Leon Street, Tampa, Florida 33609

More information

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-23 09 93 (November 2015) ----------------------------- Preparing Activity: USACE Superseding UFGS-23 09 23 (May 2011) UNIFIED FACILITIES GUIDE SPECIFICATIONS References

More information

Heating & Cooling Efficiency

Heating & Cooling Efficiency Heating & Cooling Efficiency Advantages of Geothermal HVAC Efficiency Keith Swilley Gulf Power Company Why Gulf Power Promotes Energy Efficiency? Customer Satisfaction Education Help Customers Make Smart

More information

HVAC Applications. VFD considerations for HVAC systems...

HVAC Applications. VFD considerations for HVAC systems... HVAC Applications VFD considerations for HVAC systems... 1 COMMON TERMINOLOGY VFD (VARIABLE FREQUENCY DRIVES) AFC (ADJUSTABLE FREQ. CONTOLLER) ASD (ADJUSTABLE SPEED DRIVES) VSD (VARIABLE SPEED DRIVES)

More information

HVAC Systems: Overview

HVAC Systems: Overview HVAC Systems: Overview Michael J. Brandemuehl, Ph.D, P.E. University of Colorado Boulder, CO, USA Overview System Description Secondary HVAC Systems Air distribution Room diffusers and air terminals Duct

More information

Denver International Airport Total Facility Optimization. Josh Foerschler Aurom Mahobian

Denver International Airport Total Facility Optimization. Josh Foerschler Aurom Mahobian Denver International Airport Total Facility Optimization Josh Foerschler Aurom Mahobian AGENDA DIA Intro BMcD-DIA History Optimization Projects Results Conclusion Denver International Airport Opened February

More information

State of the Art Energy Efficient Data Centre Air Conditioning

State of the Art Energy Efficient Data Centre Air Conditioning - White Paper - State of the Art Energy Efficient Data Centre Air Conditioning - Dynamic Free Cooling - Release 2, April 2008 Contents ABSTRACT... 3 1. WHY DO I NEED AN ENERGY EFFICIENT COOLING SYSTEM...

More information

The main steam enters the building in the basement mechanical room; this is where the condensate line also leaves the building.

The main steam enters the building in the basement mechanical room; this is where the condensate line also leaves the building. MSV: Square Footage: 24,844 No. of Floors: 1 Year Built: 1963 Type of Use: Lounge and dining area open all night for snacks Steam Water-cooled condenser, 50-Ton York unit with a 6 cylinder-reciprocating

More information

ICE THERMAL STORAGE IN AIR CONDITIONING APPLICATION FUNDAMENTALS

ICE THERMAL STORAGE IN AIR CONDITIONING APPLICATION FUNDAMENTALS ICE THERMAL STORAGE IN AIR CONDITIONING APPLICATION FUNDAMENTALS By: T. S. Wan Date: April 19, 1994 (1st draft 3/7/86) Copyright 1994 by T. S. Wan (All rights reserved) ABSTRACT: The technology of energy

More information

Creating Efficient HVAC Systems

Creating Efficient HVAC Systems Creating Efficient HVAC Systems Heating and Cooling Fundamentals for Commercial Buildings Heating, ventilating, and air conditioning (HVAC) systems account for nearly half of the energy used in a typical

More information

Impact of Control System Technologies on Industrial Energy Savings

Impact of Control System Technologies on Industrial Energy Savings Impact of Control System Technologies on Industrial Energy Savings Priyam Parikh Industrial Assessment Center Texas A&M University Bryan P. Rasmussen Industrial Assessment Center Texas A&M University http://farolconsulting.com/?page_id=110

More information

DATA COLLECTION AND PUMP ENERGY SAVING OPPORTUNITIES. Presented By: Rick Rumsey, P.E.

DATA COLLECTION AND PUMP ENERGY SAVING OPPORTUNITIES. Presented By: Rick Rumsey, P.E. DATA COLLECTION AND PUMP ENERGY SAVING OPPORTUNITIES Presented By: Rick Rumsey, P.E. Data Collection Customer Information Pump Motor Information Pump Information Irrigation System Information Historic

More information

Glossary of Heating, Ventilation and Air Conditioning Terms

Glossary of Heating, Ventilation and Air Conditioning Terms Glossary of Heating, Ventilation and Air Conditioning Terms Air Change: Unlike re-circulated air, this is the total air required to completely replace the air in a room or building. Air Conditioner: Equipment

More information

Water Fired Chiller/Chiller-Heater. WFC-S Series: 10, 20 and 30 RT Cooling

Water Fired Chiller/Chiller-Heater. WFC-S Series: 10, 20 and 30 RT Cooling Water Fired Chiller/Chiller-Heater WFC-S Series: 1, 2 and 3 RT Cooling W E A R E F R I E N D L Y T O T H E E A R T H Water Fired SINGLE-EFFECT Chiller or Chiller-Heater Absorption Principle Cooling Cycle

More information

CGC s Hybrid System Loop Control

CGC s Hybrid System Loop Control verview The CGC Group Hybrid Heat Pump System does NT operate with the same fluid loop temperatures as a conventional reversing Water Source Heat Pump system. The CGC system differs from a WSHP system

More information

GREEN DATA CENTER DESIGN

GREEN DATA CENTER DESIGN Jeffrey Menig Global Facilities Facility Engineering The application of multiple available technologies resulting in improved energy optimization without significantly increasing capital investment. A

More information

AIR COOLED CHILLER CHILLED WATER PUMP CONTROL: The chilled water pump with the lowest runtime will automatically start when the outside air temperature rises above the system enable setpoint. When the

More information

Heating, Ventilation & Air Conditioning Equipment

Heating, Ventilation & Air Conditioning Equipment FinAnswer Express Wyoming Incentive Catalog Effective as of October 1, 2011 Heating, Ventilation & Air Conditioning Equipment Rocky Mountain Power provides incentives for many types of energy efficient

More information

Laddomat 21-60 Charging unit

Laddomat 21-60 Charging unit Laddomat 21-60 Charging unit User and installation instructions NOTE! Diagrams in this brochure only describe connection principles. Each installation must be measured and carried out according to the

More information

Secondary Loop Chilled Water In Super High-Rise

Secondary Loop Chilled Water In Super High-Rise The following article was published in ASHRAE Journal, May 2008. Copyright 2008 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. It is presented for educational purposes

More information

Technical Support Bulletin Nr. 20 Special AC Functions

Technical Support Bulletin Nr. 20 Special AC Functions Technical Support Bulletin Nr. 20 Special AC Functions Summary! Introduction! Hot Start Control! Adaptive Control! Defrost Start Temperature Compensation Control! Anti-Sticking Control! Water Free Cooling

More information

for Plans Examiners and Building Inspectors

for Plans Examiners and Building Inspectors Building Technologies Program HVAC Controls Guide for Plans Examiners and Building Inspectors September 2011 Authors: Eric Makela, PNNL James Russell, PECI Sarah Fujita, PECI Cindy Strecker, PECI Prepared

More information

Example Retrocommissioning Measure: Opening Throttled Discharge Valves

Example Retrocommissioning Measure: Opening Throttled Discharge Valves Opening Throttled Discharge Valves This 21-story building, constructed in 1997, is located in Oregon and contains 589,000 gross square feet of mostly office occupancy. The HVAC system includes six large

More information

Conversion From Constant Flow System To Variable Flow

Conversion From Constant Flow System To Variable Flow White Paper Conversion From Constant Flow System To Variable Flow By: Tony Egan 94.21-4/29/2010 www.armstrongintegrated.com S.A. Armstrong Limited 2010 S.A. Armstrong Limited 23 Bertrand Avenue Toronto,

More information

Cat Electronic Technician 2015C v1.0 Product Status Report 2/20/2016 4:34 PM

Cat Electronic Technician 2015C v1.0 Product Status Report 2/20/2016 4:34 PM Cat Electronic Technician 2015C v1.0 Product Status Report 2/20/2016 4:34 PM Product Status Report Parameter Product ID Equipment ID Comments Value JGB00714 NOT PROGRAMMED Machine Control 345D (JGB00714)

More information

Irrigation Pump Variable Frequency Drive (VFD) Energy Savings Calculation Methodology. Public Utility District No. 1 of Chelan County

Irrigation Pump Variable Frequency Drive (VFD) Energy Savings Calculation Methodology. Public Utility District No. 1 of Chelan County Irrigation Pump Variable Frequency Drive (VFD) Energy Savings Calculation Methodology Public Utility District No. 1 of Chelan County This paper describes how to calculate energy saved by installing a variable

More information

Failure code manual. content

Failure code manual. content Failure code manual content 一 wall split AC series 2 二 floor standing AC series. 4 三 portable AC series.. 5 四 dehumidifer 6 五 DC inverter single split series...7 六 DC inverter multi-split series 10 1 一

More information

Centauri. Condensing Fire Tube Water Boiler 399 to 1000 MBH

Centauri. Condensing Fire Tube Water Boiler 399 to 1000 MBH Centauri Condensing Fire Tube Water Boiler 399 to 1000 MBH Pre-mix surface burner with up to a 7-to-1 turndown NOx levels as low a 5 ppm at full rate Operates on 4" gas pressure shown with optional gauges

More information

ASPE Seminar Water Heater Piping Strategies. Presented by Joe Kalarickal, EIT Regional Sales Manager AERCO International

ASPE Seminar Water Heater Piping Strategies. Presented by Joe Kalarickal, EIT Regional Sales Manager AERCO International ASPE Seminar Water Heater Piping Strategies Presented by Joe Kalarickal, EIT Regional Sales Manager AERCO International Presentation Overview Water Heater Piping Strategies How to size a water heater?

More information

ULTRA-EFFICIENT HVAC DESIGN AND CONTROL

ULTRA-EFFICIENT HVAC DESIGN AND CONTROL CASE STUDY ULTRA-EFFICIENT HVAC DESIGN AND CONTROL MAJOR HEATING, VENTILATING AND AIR- CONDITIONING REPLACEMENT AT THE COUNTY OF SAN DIEGO CRIME LAB December 30, 2005 8520 Tech Way, Suite 110 San Diego,

More information

Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia

Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia Prepared for the U.S. Department of Energy s Federal Energy Management Program

More information

Heating, Ventilation & Air Conditioning Equipment

Heating, Ventilation & Air Conditioning Equipment FinAnswer Express Utah Incentive Catalog Effective as of May 19, 2012 Heating, Ventilation & Air Conditioning Equipment Rocky Mountain Power provides incentives for many types of energy-efficient technologies.

More information

Commercial & Municipal Retrofit 2015 VFD Rebate

Commercial & Municipal Retrofit 2015 VFD Rebate 2015 VFD Rebate Section A: MEMBER INFORMATION Member Name Electric Account Number Rate Number Facility Address City State Zip Code Service Location Identification Email Mailing Address (if different from

More information

HVAC Efficiency Definitions

HVAC Efficiency Definitions HVAC Efficiency Definitions Term page EER - 2 SEER - 3 COP - 4 HSPF - 5 IPLV - 6 John Mix May 2006 Carrier Corporation 1 Energy Efficiency Ratio (EER) The energy efficiency ratio is used to evaluate the

More information

Heating, air-conditioning, cooling

Heating, air-conditioning, cooling Series description Design High efficiency, single stage, low pressure, inline centrifugal pump Supplied with EC motor and electronic duty adaptation Available in glanded construction, mechanical shaft

More information

Chapter 3.4: HVAC & Refrigeration System

Chapter 3.4: HVAC & Refrigeration System Chapter 3.4: HVAC & Refrigeration System Part I: Objective type questions and answers 1. One ton of refrigeration (TR) is equal to. a) Kcal/h b) 3.51 kw c) 120oo BTU/h d) all 2. The driving force for refrigeration

More information

Characterised control valve (CCV) with adjustable flow rate and sensoroperated flow control, and power and energy-monitoring function

Characterised control valve (CCV) with adjustable flow rate and sensoroperated flow control, and power and energy-monitoring function Belimo Energy Valve TM web server manual P6..W..EV-BAC Characterised control valve (CCV) with adjustable flow rate and sensoroperated flow control, and power and energy-monitoring function Contents General

More information

BULLETIN NO. TEH-908. Bell & Gossett R T. Hydronic System Design with the Bell & Gossett System Syzer / ON GPM FLOW

BULLETIN NO. TEH-908. Bell & Gossett R T. Hydronic System Design with the Bell & Gossett System Syzer / ON GPM FLOW 2000 BULLETIN NO. TEH-8 Bell & Gossett Hydronic System Design with the Bell & Gossett System Syzer 2 T 3 4 AT R T DIF URE TEMPERA 5 6 2M 7 8 9 10 3M 1 1M 800 600 0 400 GPM/T / ON GPM FLOW P PIPING FRICTION

More information

Defining Quality. Building Comfort. Precision. Air Conditioning

Defining Quality. Building Comfort. Precision. Air Conditioning Defining Quality. Building Comfort. Precision Air Conditioning Today s technology rooms require precise, stable environments in order for sensitive electronics to operate optimally. Standard comfort air

More information

HVAC Basic Science - System Capacity

HVAC Basic Science - System Capacity HVAC Basic Science - System Capacity Btu/hour, btu/h, b/h, btuh. btu?? 1 MBH = 1000 btu/hour 1 KBH = 1000 btu/hour 1 ton of cooling= 12,000 btu/hour 1 watt = 3.414 btu/hour 1 kilowatt = 1000 watts = 3,414

More information

How To Save Energy With High Pressure Control

How To Save Energy With High Pressure Control Energy savings in commercial refrigeration equipment : High Pressure Control July 2011/White paper by Christophe Borlein AFF and IIF-IIR member Make the most of your energy Summary Executive summary I

More information

Analog Servo Drive 25A8

Analog Servo Drive 25A8 Description Power Range NOTE: This product has been replaced by the AxCent family of servo drives. Please visit our website at www.a-m-c.com or contact us for replacement model information and retrofit

More information

Liquid Cooling Solutions for DATA CENTERS - R.M.IYENGAR BLUESTAR LIMITED.

Liquid Cooling Solutions for DATA CENTERS - R.M.IYENGAR BLUESTAR LIMITED. Liquid Cooling Solutions for DATA CENTERS - R.M.IYENGAR BLUESTAR LIMITED. Presentation Goals & Outline Power Density Where we have been- where we are now - where we are going Limitations of Air Cooling

More information

Application Engineering

Application Engineering Application Engineering February 2012 Digital Capacity Control for Copeland Scroll Refrigeration Compressors INDEX Page 1. Introduction... 1 2. Theory of Operation... 1 3. Nomenclature... 1 4. Digital

More information

Indoor coil is too warm in cooling mode or too cold in heating mode. Reversing valve or coil thermistor is faulty

Indoor coil is too warm in cooling mode or too cold in heating mode. Reversing valve or coil thermistor is faulty Codes Room Air Conditioner range: Indoor unit alarm s If timer lamp flashes for 1 second on, 1 second off, this indicates pre heating on the coil during heating mode and is not an error. If timer lamp

More information

REAL OPERATING COST SAVINGS FROM RETRO- COMMISSIONING OPPORTUNITIES FOR SAVINGS IN ACADEMIC MEDICAL CENTERS

REAL OPERATING COST SAVINGS FROM RETRO- COMMISSIONING OPPORTUNITIES FOR SAVINGS IN ACADEMIC MEDICAL CENTERS REAL OPERATING COST SAVINGS FROM RETRO- COMMISSIONING OPPORTUNITIES FOR SAVINGS IN ACADEMIC MEDICAL CENTERS Ken L. Hansen P.E. University of Nebraska Medical Center hansenkl@unmc.edu 402-559- 5301 402-630-

More information

THERMO KING TRUCK & TRAILER UNIT ALARM CODES THIS DOCUMENT SHOWS ALL CURRENT ALARM CODES FOR THERMO KING TRUCK AND TRAILER UNITS.

THERMO KING TRUCK & TRAILER UNIT ALARM CODES THIS DOCUMENT SHOWS ALL CURRENT ALARM CODES FOR THERMO KING TRUCK AND TRAILER UNITS. THERMO KING TRUCK & TRAILER UNIT ALARM CODES THIS DOCUMENT SHOWS ALL CURRENT ALARM CODES FOR THERMO KING TRUCK AND TRAILER UNITS. NOT ALL CODES ARE POSSIBLE ON ANY INDIVIDUAL UNIT. IF THE ALARM APPLIES

More information

Mixing Valves. ARGUS Application Note: Mixing Valves

Mixing Valves. ARGUS Application Note: Mixing Valves Mixing Valves Most radiant hot water heating systems in greenhouses use mixing valves to control the temperature of heating pipes. Both 3-way and 4- way valves are commonly used. Mixing valves provide

More information

Calculating System Flow Requirements

Calculating System Flow Requirements Calculating System Flow Requirements To select a pump, we need to know the flow rate (the amount of fluid to be pumped) and the system resistance or head. In the U.S., flow rates are given in gallons per

More information

See any red flags? Let s take a look at the problems that occurred on the job and how to avoid making the same mistakes.

See any red flags? Let s take a look at the problems that occurred on the job and how to avoid making the same mistakes. providing insights for today s hvac system designer Engineers Newsletter volume 43 2 Chilled-Water Systems Design Issues Learning from past mistakes As with anything in life, you can learn HVAC design

More information

Typical Cooling Load Profile

Typical Cooling Load Profile Ice Storage Systems and Impact on Electric Demand Georges Hoeterickx Specialists in Heat Transfer Products and Services 1 2 Cooling Load Typical Cooling Load Profile 0 2 4 6 8 10 12 14 16 18 20 22 Time

More information

INNOVATIVE SOLUTION OF DOMESTIC HEATING SPLIT TYPE SPLIT DHW INTEGRATED TYPE MONOBLOC TYPE

INNOVATIVE SOLUTION OF DOMESTIC HEATING SPLIT TYPE SPLIT DHW INTEGRATED TYPE MONOBLOC TYPE INNOVATIVE SOLUTION OF DOMESTIC HEATING SPLIT TYPE SPLIT DHW INTEGRATED TYPE MONOBLOC TYPE Fujitsu General realizes considerable energy saving operations by the Heat pump heating system using the ambient

More information

ALFEA HYBRID DUO GAZ. New Model 2011

ALFEA HYBRID DUO GAZ. New Model 2011 ALFEA HYBRID DUO GAZ New Model 2011 1 Context Market: The renovation market for heat pumps stagnates since 2 years whereas the gas condensing market remains dynamic Interest of Alfea Hybrid Duo Gas: Regarding

More information

Description of functions

Description of functions Description of functions Laddomat 21 is designed to......allow the boiler to reach a high working temperature soon after firing....to preheat the cold tank water in the bottom of the boiler so that the

More information

CURBING THE COST OF DATA CENTER COOLING. Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers

CURBING THE COST OF DATA CENTER COOLING. Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers CURBING THE COST OF DATA CENTER COOLING Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers OVERVIEW Compare Cooling Strategies in Free- Standing and In-Building

More information

Printing and Publishing Energy Savings Guide

Printing and Publishing Energy Savings Guide Printing and Publishing Energy Savings Guide Oregon printing and publishing plants face challenges of rising operating costs, environmental and other regulations, outdated equipment and customer demand

More information

STULZ Water-Side Economizer Solutions

STULZ Water-Side Economizer Solutions STULZ Water-Side Economizer Solutions with STULZ Dynamic Economizer Cooling Optimized Cap-Ex and Minimized Op-Ex STULZ Data Center Design Guide Authors: Jason Derrick PE, David Joy Date: June 11, 2014

More information

Geothermal Case Studies and Considerations

Geothermal Case Studies and Considerations Geothermal Case Studies and Considerations Geothermal Air Conditioning: Eliminate your cooling tower! By Jay Egg Pumps and Exchangers Pinellas County Safety Complex: 1300 tons Geothermal Open Loop Application

More information

Energy savings in commercial refrigeration. Low pressure control

Energy savings in commercial refrigeration. Low pressure control Energy savings in commercial refrigeration equipment : Low pressure control August 2011/White paper by Christophe Borlein AFF and l IIF-IIR member Make the most of your energy Summary Executive summary

More information

National Grid Your Partner in Energy Solutions

National Grid Your Partner in Energy Solutions National Grid Your Partner in Energy Solutions National Grid Webinar: Enhancing Reliability, Capacity and Capital Expenditure through Data Center Efficiency April 8, 2014 Presented by: Fran Boucher National

More information

The Chilled Water and Hot Water Building Deferential Pressure Setpoint Calculation Chilled Water and Hot Water Pump Speed Control

The Chilled Water and Hot Water Building Deferential Pressure Setpoint Calculation Chilled Water and Hot Water Pump Speed Control The Chilled Water and Hot Water Building Deferential Pressure Setpoint Calculation Chilled Water and Hot Water Pump Speed Control Chenggang Liu Research Associate Homer L. Bruner, Jr., CEM Mechanical Systems

More information

Condensing Boiler Efficiency

Condensing Boiler Efficiency Condensing Boiler Efficiency Date: July 17, 2012 PRES E NT ED BY DO N L E O NA RDI LE O N A RD I I NC. HV AC T RAI N I N G & C ON SU LT IN G Concepts 1 The current state of evolution in boiler design 2

More information

Tom Brooke, PE, MBA, CEM tabrooke@embarqmail.com

Tom Brooke, PE, MBA, CEM tabrooke@embarqmail.com Tom Brooke, PE, MBA, CEM tabrooke@embarqmail.com Framework, perspective or example in a particular discipline at a given time These four new models are: New and additional, or Updated Today's Paradigm

More information

CENTRIFUGAL PUMP OVERVIEW Presented by Matt Prosoli Of Pumps Plus Inc.

CENTRIFUGAL PUMP OVERVIEW Presented by Matt Prosoli Of Pumps Plus Inc. CENTRIFUGAL PUMP OVERVIEW Presented by Matt Prosoli Of Pumps Plus Inc. 1 Centrifugal Pump- Definition Centrifugal Pump can be defined as a mechanical device used to transfer liquid of various types. As

More information

Why and How we Use Capacity Control

Why and How we Use Capacity Control Why and How we Use Capacity Control On refrigeration and air conditioning applications where the load may vary over a wide range, due to lighting, occupancy, product loading, ambient weather variations,

More information

Digital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect

Digital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect Digital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect of Record: SPARCH Project Overview The project is

More information

LEV Integrated with Mechanical Covers to Achieve Energy Savings

LEV Integrated with Mechanical Covers to Achieve Energy Savings LEV Integrated with Mechanical Covers to Achieve Energy Savings Exhaust Systems for Open Surface Tanks Jim Hankinson - KCH Engineered Systems KCH Engineered Systems Pollution Control Exhaust Systems 144

More information

ECOCIAT. Domestic hot water heat recovery unit

ECOCIAT. Domestic hot water heat recovery unit Heat recovery unit Domestic hot water High energy efficiency with R410A Compact and quiet Scroll compressors Brazed-plate heat exchangers Heating Heat recovery ENVIRONMENTALLY HFC R410A PROTECTION DE FRIENDLY

More information

Basic Nameplate Information

Basic Nameplate Information Basic Nameplate Information General Information: Most equipment nameplates will have some common items of information. Many of these are self explanatory, and include: Manufacturer Manufacturerʼs address

More information

AE21-1319 R6 December 2013. Digital Capacity Control for Copeland Scroll Refrigeration Compressors AE21-1319 R6

AE21-1319 R6 December 2013. Digital Capacity Control for Copeland Scroll Refrigeration Compressors AE21-1319 R6 AE21-1319 R6 December 2013 Digital Capacity Control for Copeland Scroll Refrigeration Compressors TABLE OF CONTENTS Section Page Section Page Safety Safety Instructions...2 Safety Icon Explanation...2

More information

1. What percent of a commercial business s energy usage comes from their HVAC system? A. 13% B. 23% C. 33% D. 43% E. 53%

1. What percent of a commercial business s energy usage comes from their HVAC system? A. 13% B. 23% C. 33% D. 43% E. 53% 1 1. What percent of a commercial business s energy usage comes from their HVAC system? A. 13% B. 23% C. 33% D. 43% E. 53% 2. How much money do commercial facilities spend per square foot on energy costs

More information

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America 7 Best Practices for Increasing Efficiency, Availability and Capacity XXXX XXXXXXXX Liebert North America Emerson Network Power: The global leader in enabling Business-Critical Continuity Automatic Transfer

More information

Ground Source Heat Pumps The Fundamentals. Southington, Connecticut 860 628 4622 John F. Sima III P.E.

Ground Source Heat Pumps The Fundamentals. Southington, Connecticut 860 628 4622 John F. Sima III P.E. Ground Source Heat Pumps The Fundamentals Southington, Connecticut 860 628 4622 John F. Sima III P.E. Winter/Spring 2010 Ground Source Heat Pumps The Fundamentals TOPICS: Heat Pump Terminology Basic Physics

More information