CTG SERIES AUTOMATIC TRANSFER SWITCH
|
|
|
- Doris Mary Willis
- 9 years ago
- Views:
Transcription
1 CTG SERIES AUTOMATIC TRANSFER SWITCH The Cat CTG Series Automatic Transfer Switches (ATS) are pre-configured for applications requiring the dependability and ease of operation found in a full feature power contactor type transfer switch. CTG switches are equipped with the next generation MX150 microprocessor panel, which controls the operation and displays the status of the transfer switch s position, timers and available sources. As an embedded digital controller, the MX150 offers high reliability and ease of unattended operation across a range of applications. FEATURES Ratings 40 to 3000 amps (2, 3 or 4 poles) UL 1008 listed at 480 VAC CSA certified at 600 VAC ( amp 480V) IEC listed at 480 V Double throw, mechanically interlocked contactor mechanism Electrically operated, mechanically held Designed for emergency and standby applications Available in standard open transition (CTG) or delayed transition (CTGD) models Ringing wave immunity per IEEE 472 (ANSI C37.90A) Conducted and Radiated Emissions per EN55022 Class B (CISPR 11) (Exceeds EN55011 & MILSTD 461 Class 3) ESD immunity test per EN (Level 4) Radiated RF, electromagnetic field immunity test per EN (ENV50140) 10v/m Electrical fast transient/burst immunity test per EN Radiated RF, electromagnetic field immunity Surge immunity test per EN IEEE C62.41 (1.2 X 50 ms, 5 & 8 kv) Conducted immunity test per EN (ENV50141) Voltage dips and interruption immunity EN Seismic Compliance to IEEE and IBC-2003 DESIGN AND CONSTRUCTION FEATURES Close differential 3 phase under-voltage sensing of the normal source factory standard setting 90% pickup, 80% dropout (adjustable);under frequency sensing of the normal source factory setting 95% pickup (adjustable) Voltage and frequency sensing of the emergency source factory standard setting 90% pickup voltage, 95% pickup frequency (adjustable) Test switch (fast test/load/no load) to simulate normal source failure automatically bypassed should the emergency source fail Type 1 enclosure is standard also available in open style or Types 3R, 4, 4X, or 12. LEXX
2 STANDARD FEATURES AND OPTIONS Auxiliary Contact: Closed when the switch is in the emergency position (Additional contacts optional) Auxiliary Contact: Closed when the switch is in the normal position (Additional contacts optional) 7, 14, 28 day interval timed exerciser, pushbutton/timer operation Engine Start Contact Indicating LED Pilot Lights: -Switch in emergency position -Switch in normal position - Normal source available -Emergency source available Time Delay to Engine Start: Standard setting 3 seconds, adjustable 0-10 seconds In-Phase Monitor, self-adjusting (Not available on CTGD models) Time Delay on Retransfer to Normal: To delay retransfer to normal source (immediate retransfer on generator set failure); standard setting 30 minutes, adjustable 0-60 minutes Pushbutton Bypass of time delay and normal emergency Test Switch Momentary Event Log OD 16 Event that track date, time, reason and action taken Voltage and Frequency Indication for S1 and S2 Peak Shave/Remote Load Test: Input for peak shave or remote load test; includes automatic return to normal if emergency source fails and normal is present; 120 VAC When specified for use with a CTGD Series delayed transition switch, the control panel also includes the following: Time Delay from Neutral Switch Position to Normal on Retransfer: Standard setting 5 seconds, adjustable 0-10 minutes Time Delay from Neutral Switch Position to Emergency: Standard setting 5 seconds, adjustable 0-10 minutes Center-Off position/off Delay Timing Indicators MX150 CONTROL PANEL Time Delay for Engine Cool Down: Allows engine to run unloaded after switch retransfer to normal; standard setting 5 minutes, adjustable 0-60 minutes Time Delay on Transfer to Emergency: To delay transfer to emergency after verifying emergency source available; standard setting 1 second, adjustable 0-5 minutes Timer and voltage/frequency settings adjustable without disconnection from power sources Built-in diagnostics with LCD display for immediate troubleshooting LED/LCD indicators for ease of viewing and long life Nonvolatile memory (exerciser battery backup not required for standard operation) Processor and digital circuitry isolated from line voltage Inputs opto-isolated for high electrical immunity to transients and noise Communications header for network interface OPTIONS Plant Exerciser, clock type (load/no load): Allows the generator to start and run unloaded or to simulate a power failure, start generator and run under load ( days, user selectable) Space heater and thermostat Network communications interface card (LonWorks / ModBus) Maintained Test Switch Maintained Test Switch w/keypad Service entrance configuration Auxiliary Contact, operates on Source 1 line failure Auxiliary Contact, operates on Source 2 availability Auxiliary Contacts: Closed when the transfer switch is in Source 2 position Auxiliary Contacts: Closed when the transfer switch is in Source 1 position Disconnect Switch: Permits transfer in AUTO position and inhibits transfer in INHIBIT position. (Standard 800A and above) Elevator Pre-Signal Auxiliary Contacts: Open 0-60 seconds prior to transfer to either direction, re-closes after transfer Universal Motor Load Disconnect Circuit: Auxiliary Contact opens 0-60 seconds prior to transfer in either direction, re-closes after transfer. Can be configured by end user for Pre-transfer, Post-transfer, or both. Voltage Imbalance Monitor (Three Phase) Lockable, see-through cover for ATS controller LEXX
3 OPTIONS (continued) POWER MEASUREMENT METERS M90 EPM 2000 Digital Power Meter with Display: Amps, Volts, and Frequency M91 EPM 6000 Digital Meter with Display of Amps, Watts, Volts, Frequency, plus THD capability with Ethernet NOTE: For applications requiring additional options or other configurations, see the CTS Series fully configurable transfer switch. TESTING STANDARDS UL, CSA and IEC listed UL 1008, CSA 22.2 No. 178, IEC Ringing wave immunity IEEE 472 (ANSI C37.90A) Conducted and Radiated Emissions EN55022 Class B (CISPR 11) (Exceeds EN55011 & MILSTD 461 Class 3) ESD immunity test Class B EN (Level 4) Radiated RF, electromagnetic field immunity test EN (ENV50140) 10v/m Electrical fast, transient / burst immunity test EN Surge immunity test EN IEEE C62.41 Conducted immunity test EN (ENV50141) Voltage dips and interruption immunity EN AL/CU UL LISTED SOLDERLESS SCREW-TYPE TERMINALS FOR EXTERNAL POWER CONNECTIONS Normal, Emergency and Load Terminals Switch Size (Amps) Cables per Pole Range of Wire Sizes 40, 80 1 #8 to 3/0 AWG 100, 150, 200 & #6 AWG to 250 MCM* 260 & #4 AWG to 600 MCM* #2 AWG to 600 MCM 800, 1000, #2 AWG to 600 MCM 1600, 2000, 2600, *or 2 1/0-250 MCM may be used #2 AWG to 600 MCM LEXX
4 MX150 CONTROL SETTING RANGES Control Function Range Factory Setting Normal Line Sensing- Under-voltage Emergency Line Sensing - Under-voltage Emergency Line Sensing - Under-frequency Dropout Dropout Dropout 75-98% 75-98% 2 Hz below pickup 80% 80% Set Pickup Pickup Pickup % % % 90% 90% 95% Time Delay - Engine Start 0-10 seconds 3 seconds Time Delay - Engine Cool Down 0-60 seconds 5 minutes Time Delay - Transfer to Emergency 0-5 minutes 1 second Time Delay - Retransfer to Normal 0-60 minutes 30 minutes Time Delay - Motor Disconnect or Transfer Presignal (When applicable) 0-60 seconds 20 seconds Delayed Transition Time Delays (When applicable) 0-10 minutes 5 seconds LEXX
5 DIMENSIONAL SPECIFICATIONS CTG & CTGD TRANSFER SWITCHES NEMA 1 ENCLOSED AMP HEIGHT WIDTH DEPTH REFERENCE APPLICATION MODEL RATING POLES (A) (B) (C) FIGURE WEIGHT NOTES 40, 80, 100, 150 & 200 2,3 24 (610) 18 (457) 11 (279) A 69 (31) (610) 18 (457) 11 (279) A 69 (31) 225 2,3 46 (1168) 24 (610) 14 (356) A 69 (31) (1168) 24 (610) 14 (356) A 75 (34) 260 2,3 46 (1168) 24 (610) 14 (356) A 114 (52) (1168) 24 (610) 14 (356) A 125 (57) 400 2,3 46 (1168) 24 (610) 14 (356) A 168 (76) (1168) 24 (610) 14 (356) A 180 (82) 600 2,3 66 (1686) 24 (610) 19.5 (495) B 97 (44) 1-5 & (1686) 24 (610) 19.5 (495) B 224 (102) 800 2,3 74 (1880) 40 (1016) 19.5 (495) B 460 (209) 1-5 &7 CTG 4 74 (1880) 40 (1016) 19.5 (495) B 490 (222) ,3 74 (1880) 40 (1016) 19.5 (495) B 475 (215) 1-5 & ,3 74 (1880) 40 (1016) 19.5 (495) B 475 (215) 1-5 & ,3 90 (2286) 35.5 (902) 48 (1219) C 1030 (467) 1-5, 7& ,3 90 (2286) 35.5 (902) 48 (1219) C 1030 (467) 1-5, 7& ,3 90 (2286) 35.5 (902) 48 (1219) C 1150 (522) 1-5, 7& ,3 90 (2286) 35.5 (902) 48 (1219) C 1150 (522) 1-5, 7&8 40, 80, 100, 150, 200 & 225 2, 3 46 (1168) 24 (610) 14 (356) A 127 (58) (1168) 24 (610) 14 (356) A 133 (60) 260 & 400 2,3 46 (1168) 24 (610) 14 (356) A 176 (80) (1168) 24 (610) 14 (356) A 188 (85) 600 2,3 66 (1686) 24 (610) 19.5 (495) B 221 (100) 1-5 & (1686) 24 (610) 19.5 (495) B 230 (104) 800 2,3 74 (1880) 40 (1016) 19.5 (495) B 475 (215) 1-5 & ,3 74 (1880) 40 (1016) 19.5 (495) B 475 (215) 1-5 & 7 CTGD ,3 74 (1880) 40 (1016) 19.5 (495) B 475 (215) 1-5 & ,3 90 (2286) 35.5 (902) 48 (1219) C 1030 (467) 1-5 & ,3 90 (2286) 35.5 (902) 48 (1219) C 1030 (467) 1-5 & ,3 90 (2286) 35.5 (902) 48 (1219) C 1150 (522) 1-5 & ,3 90 (2286) 35.5 (902) 48 (1219) C 1150 (522) 1-5 & 7-8 LEXX
6 Application Notes : 1. Dimensions are listed in inches (mm) and weights in pounds (kg). 2. Includes 1.25" door projection beyond base depth. Allow a minimum of 3" additional depth for projection of handle, light, switches, pushbuttons, etc. 3. All dimensions and weights are approximate and subject to change without notice and are not for construction use. 4. Packing materials must be added to weights shown. Allow 15% additional weight for cartons, skids, crates, etc. 5. Special enclosures (NEMA 3R, 4, 4X, 12, etc.) dimensions may differ. Consult your Cat Dealer for details. 6. CTG require larger 36" H X 24" W X 14" D enclosure depending on options specified. Consult your Cat Dealer for details.7. Add 3" in height for lifting eyes. 7. Add 3" in height for lifting eyes. 8. Ventilation louvers on side/rear of 2600 and 3000A units require one side or rear of enclosure to be clear in order to afford proper airflow. Information contained in this publication may be considered confidential. Discretion is recommended when distributing. Materials and specifications are subject to change without notice. CAT, CATERPILLAR, their respective logos, Caterpillar Yellow, the Power Edge trade dress as well as corporate and product identity used herein, are trademarks of Caterpillar and may not be used without permission. LEXX LEXX (11/12) Caterpillar All rights reserved
CAT ATC POWER BREAKER & POWER CASE SWITCH AUTOMATIC TRANSFER SWITCH
CAT ATC POWER BREAKER & POWER CASE SWITCH AUTOMATIC TRANSFER SWITCH Cat transfer switches are designed for a variety of standby power applications. They provide flexibility, reliability and value in a
SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches
SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches PART 1 GENERAL 1.01 Scope Optional Standby Power Generator Systems A. Furnish and install automatic transfer switches
CTS SERIES AUTOMATIC TRANSFER SWITCH
CTS SERIES AUTOMATIC TRANSFER SWITCH The Cat CTS Series Automatic Transfer Switch (ATS) is configurable for applications requiring the dependability and ease of operation found in a full featured power
Section 14. Automatic Transfer Switches. www.geindustrial.com BuyLog Catalog 14-1
Automatic Transfer Switches...14- ATS (Residential) / ZTX Series...14-4 ATS (Commercial) / ZTG Series...14-6 ATS (Specification) / ZTS Series...14-15 ATS (Specification) / ZTE Series...14-3 ATS (Specification)
ASCO SERIES 185 Power Transfer Switches
ASCO SERIES 185 Power Transfer Switches 4-hour protection no matter when trouble strikes ASCO Series 185 Power Transfer Switches An Automatic Transfer Switch helps prevent... Your business or home from
Continuous Power... Continuous Protection
Series 165 We Keep Your Power On Continuous Power... Continuous Protection An Automatic Transfer Switch helps prevent... Your business or home from losing power during bad weather or utility power equipment
GTEC transfer switch open transition
GTEC transfer switch open transition 40-1250 Amp Description The GTEC automatic transfer switch combines reliability and flexibility in a small, economical package for transferring loads between a utility
Transfer switch BTPC open, closed or delayed transition
Transfer switch BTPC open, closed or delayed transition 150-4000 Amp Description The Cummins Power Generation BTPC series bypass isolation transfer switch combines an automatic transfer switch with a drawout
26 3213.13 Diesel Engine Driven Generators Page 1 of 6
Last Update: December 8, 2014 A. Description of System Consultant s Handbook Page 1 of 6 1. Provide a diesel engine driven electric generating unit, factory assembled, tested and certified to operate at
How To Operate A Gec Transfer Switch Open Transition 40 2000 Amp Power Supply
GTEC Transfer switch open transition 40 2000 amp Description GTEC transfer switches combine reliability and flexibility in a small, economical package for transferring loads between a utility and a generator
AUTOMATIC TRANSFER SWITCH CONTROL UNIT OPERATOR S MANUAL
ATS-220 AUTOMATIC TRANSFER SWITCH CONTROL UNIT OPERATOR S MANUAL For Use in 208 to 240 Volts Single and 3 Phase ATS Systems With 110Volt AC or DC Control Motors and selenoids 4501 NW 27 ave Miami FL 33142
SUGGESTED SPECIFICATION for Service Entrance Automatic Transfer Switches
PART 1 GENERAL 1.01 Scope SUGGESTED SPECIFICATION for Service Entrance Automatic Transfer Switches Division 16 - Electrical Standby Power Generator Systems A. Furnish and install service entrance automatic
ATC-300 Automatic Transfer Switch Controller
ATC-300 Technical Data New Information Technical Data Page 2 Effective: May 2004 ATC-300 Introduction The Cutler-Hammer ATC-300 from Eaton s Electrical business is a comprehensive, multi-function, microprocessor-based
APC Matrix-UPS 5kVA 208V/240V In 120/208/240V Out
APC Matrix-UPS 5kVA 208V/240V In 120/208/240V Out APC Matrix-UPS, 3750 Watts / 5000 VA,Input 208V / Output 120V, 208V, Interface Port DB-9 RS-232, SmartSlot, Extended runtime model Includes: CD with software,
Series TS 870 100-1200 Amp. Automatic Transfer Switches
Series TS 870 100-1200 Amp Automatic Transfer Switches A Regal Brand TS 870 AUTOMATIC TRANSFER SWITCHES THOMSON POWER SYSTEMS TS 870 AUTOMATIC TRANSFER SWITCHES OFFER THE FOLLOWING OUTSTANDING FEATURES:
Telephone- and leased line modem for industrial applications TD-36
Telephone- and leased line modem for industrial applications TD-36 Modem for industrial PSTN- and leased line applications The TD-36 is an analogue V.34 PSTN modem as well as an industrial 2-wire leased
Integrated Power Systems for Data Centers
Integrated Power Systems for Data Centers A Commitment to Data Centers Caterpillar is committed to providing optimum value to the Data Center industry by leveraging our engineering, manufacturing, distribution,
How To Test A Power Switch On A Power Supply
transfer switches Soft load Innovative, reliable, integrated solution Built with years of experience Powered with innovation Delivered with reliability A history of experience, innovation and reliability
Bulletin 150 Smart Motor Controllers SMC-3 Smart Motor Controller
Overview/Modes of Operation Bulletin 150 Smart Motor Controller The SMC-3 is a compact, simple to use, solid-state motor controller designed to operate 3-phase motors. It features a built-in overload relay
Rack mounted telephone- and leased line modem for industrial applications
Rack mounted telephone- and leased line modem for industrial applications TR-6 Rack modem for industrial PSTNand /-wire leased line applications The TR-6 is an analogue V. 9 -rack PSTN modem as well as
LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA. General Specification
08/17/12 Rev2 LTR Series General Specification 700 VA to 2.1 KVA 1.0 General LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA General Specification This specification describes the features and
SWITCHGEAR. EGP Switchgear
SWITCHEA EP Switchgear Cat generator set paralleling switchgear has been designed to integrate with Cat EMCP3 generator set controls. Now you can get greater efficiency, reliability and dependability all
Transfer Equipment Controls
Control Types Manual Transfer Switches Nonautomatic Transfer Switches Automatic Transfer Switches The type of control system for the transfer switch will vary depending on the type of switching equipment
Thyristor-controlled power supplies and battery chargers
Thyristor-controlled power supplies and battery chargers Input voltage: 115 / 230 VAC, single phase, 50 / 60 Hz or 208 / 400 / 480 VAC, three phases, 50 / 60 Hz Output voltage: 12 / 24 / 48 / 60 / 72 /
RISH EM 3490 DS Dual Source Energy Meter RISH EM 3490 DS. Application : Product Features:
Application : RISH Master 3490 DS measures important electrical parameters of Utility (in normal mode) & Generators (in Power back up) in three phase and single phase Network & replaces the multiple analog
WITH POWER TRANSFER SWITCH STANDARD SUBMITTAL PACKAGE
WITH POWER TRANSFER SWITCH STANDARD SUBMITTAL PACKAGE SBP1930-61 FTA1930 Digital Solid State Starting Electric Fire Pump Controllers Product Description Fire Pump Controllers for Business-Critical Continuity
SECTION 26 29 23 VARIABLE FREQUENCY DRIVES
SECTION 26 29 23 VARIABLE FREQUENCY DRIVES PART 1 GENERAL 1.01 SCOPE A. Furnish and install individual freestanding variable frequency AC drives (VFD) as shown on the Drawings and specified herein. 1.02
AUTOMATIC TRANSFER SWITCH. Changeover Type from 250A to 2500A
AUTOMATIC TRANSFER SWITCH Changeover Type from 250A to 2500A Table of Contents Preamble 1.1 Theoretical base 1.2 Selection the size of automatic transfer switch 1.3 Automatic transfer switch components
PRODUCT GUIDE. SL Medium Voltage IEC Vacuum Contactors
PRODUCT GUIDE SL Medium Voltage IEC Vacuum Contactors Table of Contents 1 Overview Introduction....................................................2 Features........................................................2
Medium Voltage Motor Control Assemblies
Medium Voltage Motor Control Assemblies Arc Resistant AMPGARD.1 Product............................................. 2 Application........................................... 2 Features, Benefits and Functions...................................
BT300 HVAC Drives Conventional Bypass (C-Bypass) Options
BT300 HVAC Drives Conventional Bypass (C-Bypass) Options Description The BT300 Conventional Bypass is a companion package for the family of BT300 HVAC Drives. For information on the family of BT300 HVAC
CONTROLS DATA MANAGEMENT PROCESS AUTOMATION EUROCUBE. General purpose single phase thyristors and solid state relays Product data.
425 CONTROLS DATA MANAGEMENT PROCESS AUTOMATION EUROCUBE General purpose single phase thyristors and solid state relays Product data abc 425 EUROCUBE A complete range of low cost solid state relays and
Submit shop drawings for equipment provided under this section Shop drawings shall indicate:
Section 16435 - SWITCHBOARDS Introduction Part 1 - General Reference The work under this section is subject to requirements of the Contract Documents including the General Conditions, Supplementary Conditions,
SWITCH! DESCRIPTION. ENVIRONMENTAL SPECIFICATIONS Operating Temperature: 0 C to +40 C SPECIFICATION SHEET:
SWITCH The Budderfly lighting switch is a Decora style, plug-and-play replacement for your existing building switches. Installing a Budderfly adapter transforms your building s existing wiring into the
Electronic timer CT-VBS.17+18 OFF-delayed without auxiliary voltage, for DC contactors Data sheet
Characteristics Single-function OFF-delay timer for DC contactors, without auxiliary voltage Width.5 mm CDC 5 6 F3 Approvals A culus E CCC CT-VBS a Circuit diagram b Marker label Marks a CE b C-Tick Order
Zenith Controls ISO 9001 50R-1000C 5/99
OPERATION AND MAINTENANCE MANUAL TRANSFER SWITCH CONTROL PANEL MX100 MICROPROCESSOR CONTROLLER g GE Zenith Controls ISO 9001 50R-1000C 5/99 Table of Contents Page Safety... 1 Final Equipment Inspection...
Type: EASY719 DC RC Article No.: 274119. Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC. Description
Type: EASY719 DC RC Article.: 274119 Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC Description 12 digital inputs (4 inputs available as analog inputs) 6 relay outputs LCD display
Dimensions, Inches (mm) No. of Poles Width Height Depth 2, 3 8.25 (210) 16 (407) 5.5 (140) 4 11.125 (283) 16 (407) 5.5 (140)
9-10N Supersedes Selection Data 9-10N, pages, 1-, dated dated March March 1995 1995 Mailed to: E, D, C/9-100A, 31-A, INTERRUPTING CAPACITY RATINGS IEC 947- Interrupting Capacity s➀ Interrupting Capacity
Waveguide Access Point WGA631. Product Guide
Waveguide Access Point Product Guide Waveguide Access Point Contents 1. Description............................ 3 2. Application............................ 3 3. Technical data... 4 4. Physical interfaces......................
Product Description Primary Resistance Starting Electric Fire Pump Controllers FTA1500
Product Description Primary Resistance Starting Electric Fire Pump Controllers FTA1500 Description Firetrol FTA1500 Primary Resistance Fire Pump Controllers use resistors in the line to reduce line voltage
Applications. Remote Display Mounting Kits
June 200 Sheet 105 Surge Protection Products TVSS General Description Clipper Power System Visor Series.1-5 Clipper Power System Visor Series General Description Eaton s Cutler-Hammer leading-edge surge
Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000
Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000 Description Firetrol FTA1000 Full Voltage Fire Pump Controllers are intended for use with electric motor driven fire pumps
Daker DK 1, 2, 3 kva. Manuel d installation Installation manual. Part. LE05334AC-07/13-01 GF
Daker DK 1, 2, 3 kva Manuel d installation Installation manual Part. LE05334AC-07/13-01 GF Daker DK 1, 2, 3 kva Index 1 Introduction 24 2 Conditions of use 24 3 LCD Panel 25 4 Installation 28 5 UPS communicator
3500/62 Process Variable Monitor
3500/62 Process Variable Monitor Description The 3500/62 Process Variable Monitor is a 6-channel monitor for processing machine critical parameters (pressures, flows, temperatures, levels, etc.) that merit
HI/ICMI UVR-1 Universal Voltage Regulator Control
HI Document No. 2.4.32, Revision 1 ICMI Revision August 25, 2005 Specifications HI/ICMI UVR-1 Universal Voltage Regulator Control Howard Industries Utility Products Division Howard Industries, Inc. 3225
Chrome DIN Rail Power Supply 24V 30W 1 Phase (Class II & NEC Class 2) / DRC-24V30W1AZ
Highlights & Features Protection Class II, Double Isolation (No Earth connection is required) Universal AC input voltage without power de-rating Efficiency > 87.0% @ 115Vac & 230Vac NEC Class 2 / Limited
XPress-Pro SW Series Hardened Ethernet Switches Enabling Communication for the Demanding Industrial Environment
XPress-Pro SW Series Hardened Ethernet Switches Enabling Communication for the Demanding Industrial Environment Part of the device networking family of networkenablement products, XPress-Pro SW series
RM4TG20 three-phase network control relay RM4-T - range 200..500 V
Characteristics three-phase network control relay RM4-T - range 200..500 V Complementary [Us] rated supply voltage Output contacts Setting accuracy of time delay Delay at power up Measuring cycle Marking
15 Series - Electronic step relay and dimmer. Features 15.91 15.51 15.81 SERIE
Series - Electronic step relay and dimmer SERIE Features.91.51.81 Electronic step relay and dimmer for control of lighting levels Suitable for incandescent and halogen lighting loads (with or without transformer
STRATO LED Drivers 70W, Single output
Features STRATO switch mode driver technology is designed to generate one constant current output from a wide range AC input. The size and performance of these products make them the ideal choice for LED
Single-phase (220...240 V) voltage monitoring: Undervoltage Overvoltage Window mode (overvoltage + undervoltage) Voltage fault memory selectable
Features 70.11 70.31 70.41 Electronic voltage monitoring relays for single and three-phase applications Multifunctional types, providing the flexibility of monitoring Undervoltage, Overvoltage, Window
38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 A
38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 A Common features Instant ejection of relay by plastic retaining clip Integral coil indication and protection circuit EMR Electromechanical Relays
Magnum Mobile Generator MMG55 Specifications
Empowering Real People Magnum Mobile Generator MMG55 Specifications ENGINE John Deere PE5030TF270 - turbocharged, diesel engine o Prime - 72 hp @ 1800 rpm o Standby - 80 hp @ 1800 rpm o 4 cylinder o 3.0
Single and three phase modular Automatic Transfer Switch from 40 to 160 A
NEW SINGLE PHASE Single and three phase modular Automatic Transfer Switch from 40 to 160 A SWITCH TO INNOVATION SOCOMEC: intelligent changeover systems As a worldwide leading company in changeover power
UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Metering and Monitoring. Basis of Design
Basis of Design This section applies to the design, installation and integration of metering and monitoring equipment, including: hardware installed in the electrical service and distribution equipment,
NRG. Intelligent Engine Start Battery Charger. The Smart Choice for Mission-Critical Engine Starting
NRG Intelligent Engine Start Battery Charger The Smart Choice for Mission-Critical Engine Starting Fast, accurate, mission-critical charging gives best starting reliability 4-rate, temperature-compensated
Bussmann. All-In-One Module. Bussmann Power Module Switch. How to configure Part Numbers: Step 1: Select Switch Amperage 1
How to configure Part Numbers: Step : Select Switch Amperage Power Module Switch Rating (Amps) Power Module Switch Catalog No. 30 3 60 6 00 200 2 400 4 Step 2: Select Options Needed 5 Bussmann Power Module
Smart-UPS 120 V. Advanced line interactive power protection for servers and network equipment. The world s most popular network and server UPS
Smart-UPS Advanced line interactive power protection for servers and network equipment The world s most popular network and server UPS The award-winning Smart-UPS unit from APC by Schneider Electric is
Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000
Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000 Description Firetrol FTA1000 Full Voltage Fire Pump Controllers are intended for use with electric motor driven fi re pumps
Foxboro Evo Process Automation System
Foxboro Evo Process Automation System Product Specifications PSS 31H-2Z32 FBM232 Field Device System Integrator Module, 10/100 Mbps Ethernet, Single The FBM232 Field Device System Integrator (FDSI) module
Automatic Transfer Switch Controller
Automatic Transfer Switch Controller Decision-Makerr MPAC 1500 Model KBS with Decision-Makerr MPAC 1500 Controller Applicable Models Model Description KCS Standard-Transition Any Breaker ATS ] KCP Programmed-Transition
Chrome DIN Rail Power Supply 12V 54W 1 Phase (Class II & NEC Class 2) / DRC-12V60W1AG
Highlights & Features Protection Class II, Double Isolation (No Earth connection is required) Universal AC input voltage and full power up to 55 C Power will not de-rate for the entire input voltage range
Dual Chamber Temporary External Pacemaker
5392 Dual Chamber Temporary External Pacemaker Electromagnetic Compatibility Declaration Caution: Federal law (USA) restricts this device to sale by or on the order of a physician. The following list includes
FP-4000 Feeder Protection
FP-4000 Feeder Protection Technical Data TD02602007E Effective September 2007 Supersedes TD02602003E Pages 1 8, Dated March 2006 FP-4000 FP-4000 Product Description........................... 2 Application
Power-monitoring unit PowerLogic System. Technical data sheet. Power Meter Series 800
Power-monitoring unit PowerLogic System Technical data sheet 2003 Power Meter Series 800 Function and characteristics PB100313 The PowerLogic Power Meter Series 800 offers all the high-performance measurement
DIALER SPECIFICATION VERBATIM MODULAR SERIES VSS
DIALER SPECIFICATION VERBATIM MODULAR SERIES VSS 1. Description and Phone Number Dialing: The dialer shall be a solid state component capable of dialing up to 16 telephone numbers, each up to 60 digits
Analog signal converters CC-E I/I Current / current isolators
ata sheet Analog signal converters CC-E I/I Current / current isolators The CC-E I/I is an isolator for the electrical isolation of current signals without auxiliary supply. It allows the isolation between
Owner s Manual. For Automatic Transfer Switch. 100-200 Amp, Service Entrance/Non-Service Entrance
Owner s Manual For Automatic Transfer Switch 100-200 Amp, Service Entrance/Non-Service Entrance Model Numbers RTST100A3 RTSP100A3 RTST150A3 RTST200A3 RTSP200A3 MODEL NUMBER: SERIAL NUMBER: DATE PURCHASED:
Fixed - Over/Under voltage limits, (0.75...1.2) U N respectivity Link selectable - 5 min or 10 min delay. Fixed limits
Features 71.11.8.230.0010 71.11.8.230.1010 1 - Phase 230 V Over & Under voltage monitoring relays 71.11.8.230.0010 - Fixed Over & Under voltage detection - Link selectable 5 or 10 minute lock-out delay
SWITCHGEAR SOLUTIONS FOR MISSION CRITICAL APPLICATIONS. Presented by SAI Advanced Power Solutions
SWITCHGEAR SOLUTIONS FOR MISSION CRITICAL APPLICATIONS POWER DISTRIBUTION RACKS IN A MISSION CRITICAL SYSTEM MODULES IN A MISSION CRITICAL SYSTEM UPS Convertor Main Inverter Load Battery BPC UPS & BATTERY
Bulletin 150 SMC Flex Smart Motor Controller Specifications
Specifications Specifications Standard Features Optional Features Installation Setup Communications Power Wiring Control Wiring Keypad Software Starting and Stopping Modes Protection and Diagnostics Metering
MTS Power Products MIAMI FL 33142 ATS-22AG. Automatic Transfer Switch And Control PLC Operator s Manual
MTS Power Products MIAMI FL 33142 ATS-22AG Automatic Transfer Switch And Control PLC Operator s Manual Dedicated Single Phase Transfer Switch With Touch Screen Controls Normal Power Connections Emergency
Centro-Matic Automatic Lubrication Systems System Controls
Selecting the right controls for your automated lubrication system is one of the last steps in the design process. Several different models may be chosen to control power-operated pumps, depending on the
HMIGTO4310 advanced touchscreen panel 640 x 480 pixels VGA- 7.5" - TFT - 96 MB
Product datasheet Characteristics HMIGTO4310 advanced touchscreen panel 640 x 480 pixels VGA- 7.5" - TFT - 96 MB Main Range of product Product or component type Display colour Display size Supply Magelis
QuickSpecs. Models HP T1500 UPS JPN/TWN. HP UPS T1000 G2, T1500 G2 Models Overview
Overview The Tower UPS "G2" models are the next generation HP tower UPSs with USB support. These new UPSs are designed to provide advanced power protection (or increased uptime and data corruption avoidance)
38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A
38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A 38 SERIES Common features Instant ejection of relay by plastic retaining clip Integral coil indication and protection circuit EMR Electromechanical
AIS 3000 APC AIS 3000 15kVA 208V w/2 Batt. Module Exp. To 4, Start-Up 5X8, Internal Maintenance Bypass
AIS 3000 APC AIS 3000 15kVA 208V w/2 Batt. Module Exp. To 4, Start-Up 5X8, Internal Maintenance Bypass APC AIS 3000, 12 kw / 15 kva,input 208V 3PH / Output 120V, 208V, 208V 3PH, Interface Port DB-9 RS-232,
DIESEL GENERATOR SETS
DIESEL SETS STANDBY Standby Prime Model kw (kva) kw (kva) D175-2* 175 (218.8) 157.5 (196.9) *Tier 3 EPA Approved, Emissions Certified Picture shown may not reflect actual package FEATURES SET Complete
Power Supplies 3. SDN-P DIN Rail Series
SDN-P DIN Rail Series The SDN DIN Rail power supplies provide industry leading performance. Sag Immunity, transient suppression and noise tolerant, the SDN series ensures compatibility in demanding applications.
38 SERIES. Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A. EMR Electromechanical Relays. Common features. SSR Solid State Relays. 6.
38 Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A 38 Common features Instant ejection of relay by plastic retaining clip Integral coil indication and protection circuit 6.2 mm wide EMR - DC, AC or AC/DC
SUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original
SUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original A motor starter is a combination of devices to allow an induction motor to start, run and stop according
AF09-30-22-.. / AF09Z-30-22-.. 2-stack 3-pole Contactors AC / DC Operated - with Screw Terminals
Technical Datasheet 1SBC101403D0201 24/03/11 AF09-30-22-.. / AF09Z-30-22-.. 2-stack 3-pole Contactors AC / DC Operated - with Screw Terminals AF09(Z) contactors are used for controlling power circuits
Sample - No Commercial Use
COMPLETE REVISION October 2010 Electrical PIP ELSSG01 Design and Fabrication of Low-Voltage Metal-Enclosed AC Power Circuit Breaker Switchgear PURPOSE AND USE OF PROCESS INDUSTRY PRACTICES In an effort
Power Supply Unit, Primary Switched, Narrow Design MINI-PS-12-24DC/24DC/1
Power Supply Unit, Primary Switched, Narrow Design MINI POWER provides: Extra narrow design with widths of 22.5 mm, 45 mm, and 67.5 mm (0.886, 1.772, and 2.657 in.) Global use due to a wide-range input
TM7BDM8B expansion block - TM7 - IP67-8 DI/DO - 24V DC - 0.5 A - M8 connector
Product datasheet Characteristics TM7BDM8B expansion block - TM7 - IP67-8 DI/DO - 24V DC - 0.5 A - M8 connector Main Range of product Product or component type Range compatibility Enclosure material Bus
Dead Tank Circuit Breaker 72PM40-C Proven reliability through common platforms
Dead Tank Circuit Breaker 72PM40-C Proven reliability through common platforms ABB innovations for changing demands ABB (www.abb.com) is a leader in power and automation technologies that enables utility
Chassis, Power Supply, and Element Management
Chassis, Power Supply, and Element Management C-COR CHP Max5000 Converged Headend Platform Accelerate deployment of new, revenue generating advanced services Innovative technology creating converged high-
Rated Power(W) 8W 2. EG-LED0840-01 8W 3. EG-LED1027-01 10W
14713221 001 Seite 2 von 37 Page 2 of 37 Model List: No Model Rated Voltage(V) 1. EG-LED0827-01 Rated Power(W) 8W 2. EG-LED0840-01 8W 3. EG-LED1027-01 10W 4. EG-LED1040-01 AC 100-240V, 10W 5. EG-LED1027-02
Atlas Copco Generators
Atlas Copco Generators QIX 15 - QIX 540 16 kva LTP to 549 kva LTP at 50 & 60 Hz The QIX options include Earth leakage relay Qc generating set control panels for all standby and/or paralleling applications
Control Devices Catalogue. Control Devices. Preferred and Standard Products
Control Devices Catalogue Control Devices Preferred and Standard Products KOP.J Timer Electronic 22.5 mm Characteristics Mounting KOP.J 22.5 mm mono or multifunction high immunity to interference surface
80 Series - Modular timers 16 A. Features 80.01 80.11
80 Series - Modular timers 6 A 80. Multi-function and mono-function timer range - Multi-function & multi-voltage 80. - ON delay, multi-voltage 7.5 mm wide Six time scales from 0.s to 24h 35 mm rail (EN
Rental. C18-20 XQ600 MULTI-VOLTAGE SOUND ATTENUATED POWER MODULE 60 Hz FEATURES
C18-20 XQ600 MULTI-VOLTAGE SOUND ATTENUATED POWER MODULE 60 Hz FEATURES Factory designed, certified prototype tested with torsional analysis. Production tested and delivered in a package that is ready
Product Description Digital Solid State Starting Electric Fire Pump Controllers FTA1930
Product Description Digital Solid State Starting Electric Fire Pump Controllers FTA1930 Description Firetrol FTA1930 Digital Solid State Starting Fire Pump Controllers feature soft start, soft stop and
Multifunction Digital Timer
Multifunction Digital Timer 1/16 DIN Timer with Easy-to-use Functions Nine output modes accommodate a wide variety of applications. All parameters set by scroll-through menus accessed from the front panel.
1000W Single Output Power Supply 15V 24V. Protection type: Total Power limit, Latch-style (Recovery after reset AC power ON or inhibit)
000W Single Output Power Supply AK-000 series Features: Universal AC input / Full range Programmable output Voltage (0% ~ 05%) Programmable output Current (% ~ 05%) + / 0.5A auxiliary output U profile,
SmartOnline 200-240V 5kVA 4.5kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 4U Rack/Tower, USB, DB9 Serial
SmartOnline 200-240V 5kVA 4.5kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 4U Rack/Tower, USB, DB9 Serial MODEL NUMBER: SU5000RT4UHV Description Tripp Lite SU5000RT4UHV 5000VA / 5kVA /
FTA1100-J DIESEL ENGINE FIRE PUMP CONTROLLERS STANDARD SUBMITTAL PACKAGE
FTA1100-J DIESEL ENGINE FIRE PUMP CONTROLLERS STANDARD SUBMITTAL PACKAGE SBP1100J FTA1100J Diesel Engine Fire Pump Controllers Product Description Description Firetrol combined automatic and manual Mark
80 Series - Modular timers 16 A. Features 80.01 80.11
80 Series - Modular timers 16 A Features 80.11 Multi-function and mono-function timer range - Multi-function & multi-voltage 80.11 - On-delay, multi-voltage 17.5 mm wide Six time scales from 0.1s to 24h
Industrial-Grade UPS System Heavy-duty power protection for harsh industrial environments
Industrial-Grade UPS System Heavy-duty power protection for harsh industrial environments Model #: SM2000RMX Heavy-duty, industrial-grade metal housings Shock and vibration rated to MIL-STD-810D 19 inch
Project Name: Nortrax Section 26 41 00 Project No: 13-013 SURGE PROTECTION DEVICES Page 1
Page 1 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. General: Drawings and general provisions of the Contract, including General and Supplementary Conditions and Divisions 1 Specification sections apply to