SECTION III SPECIFICATIONS. Three Phase Pad Mount Transformers (Dead Front Configuration)
|
|
- Aubrey Joseph
- 7 years ago
- Views:
Transcription
1 SECTION III SPECIFICATIONS Three Phase Pad Mount Transformers (Dead Front Configuration) A. General Electrical and Mechanical Features: 1. New, not remanufactured. 2. Three-phase, 60 HZ 3. Mineral-oil filled, self-cooled, pad-mounted type distribution transformer, kva rating as shown on bid form, primary voltage kv volts DELTA, and with secondary voltage as shown on bid form. Transformer shall be suitable for connection to a kv WYE, multigrounded distribution system. 4. Secondary voltage as indicated on bid form. 5. Impedance as per below: 75kVA to 500kVA 2.5% to 3.5% 750kVA and above as per ANSI C (5.3% to 6.2%) 6. The transformer shall meet all applicable requirements of ANSI C except as otherwise specified herein. 7. The maximum temperature rise above ambient at 100% KVA load shall not exceed 65 degrees C. B. The primary connection shall be dead front and shall consist of six (6) 600A, fully rated, non-loadbreak bushings. For each incoming circuit, bushings shall be horizontally or diagonally-mounted side by side. Bushings shall be labeled as H1A, H2A, H3A (left) and H1B, H2B, H3B (right). 600A bushings shall be equipped with brass or tinned copper studs only aluminum is not acceptable. C. Three internal 600A load break switches, hot-stick operable from the front of the transformer, to be located as shown in Figure 1. The switches shall be configured as follows: 1. Line Switch A a. Open (Off) The internal 12.5kV buswork is not energized from Source A. b. Closed (On) The internal 12.5kV buswork is energized from Source A. 2. Line Switch B a. Open (Off) The internal 12.5kV buswork is not energized form Source B. b. Closed (On) The internal 12.5kV buswork is energized from Source B. 3. Transformer Switch a. Open (Off) The transformer is not energized from the internal 12.5kV buswork.
2 b. Closed (On) The transformer is energized from the internal 12.5kV buswork. The operators for the internal 600A load break switches shall be mounted in the primary compartment of the transformer. The internal 600A load break switches shall be mounted in such a way as to provide full access for hot-stick operation with a full complement of conductors on all of the available primary bushings. D. Cable accessory parking stands shall be located adjacent to the bushing wells with a minimum of 6.5 inches from the center line of the bushing to the center line of the parking stand. E. The transformer windings shall be protected by three (3) dual sensing Bay-O-Net type fuses located in the primary compartment. All Bay-O-Net fuseholders shall be provided with plastic spill pans. The transformer shall include three spare fuses of operation at 12.47kV. F. The transformer shall be equipped with an automatic pressure relief device, pressure gauge, oil level gauge and an oil temperature gauge with resettable drag needles. G. WYE connected secondaries shall have the secondary neutral brought out in the secondary compartment through a fully insulated bushing ( XO ) and equipped with a removable full ampacity ground strap. H. The four (4) low voltage bushings shall be fitted with appropriately sized spade type terminals. Secondary bushing spades shall be designed in a staggered arrangement with a minimum of 5 ½ horizontal clearance between spades and 3 ¾ clearance from any sidewall. The transformer must meet the requirements of ANSI , Fig. 3 for low voltage terminal arrangements and minimum dimensions. I. The transformer shall be equipped with a minimum of two (2) two-hole NEMA ground pads located in the lower portion of the compartments, one in the primary compartment and one in the secondary compartment. Ground pads shall be ½ inch 13NC tapped holes, 7/16 deep. Ground pads shall be capped before painting. J. The transformer shall be fitted with a one-inch upper filter press and filling plug or cap and a one-inch drain valve with built-in sampling device. Such drain valves shall be located at the bottom of the low voltage compartment. K. Transformer Termination Compartment Construction Requirements:
3 1. The transformer shall be of compartmental type construction with completely separate compartments for both the primary and the secondary. 2. The primary and secondary compartments shall be side by side, with the secondary compartment on the right side when facing the transformer front compartment. 3. The primary and secondary compartments shall be completely enclosed with removable front sills and doors. Doors are to be removable only in the fully-open position. 4. The high voltage compartment door shall be of the interlock type and shall be secured by a ½ in. stainless steel pentahead bolt held in the center frame which is accessible only after the low voltage door is opened. 5. The low voltage compartment door shall include a handle with a two (2) point locking arrangement equipped with provisions for pad-locking. The secondary compartment door handle to include a spring loaded captive stainless steel pentahead bolt which will require loosening of the bolt to permit operation of the handle. 6. An instruction nameplate shall be located on the inside of the low voltage compartment and will clearly indicate the following: a. The connection diagram. b. The location of the protective devices. c. All other pertinent information related to the unit. 7. Footprint of transformer shall not exceed the following maximum dimensions: a. 78 inches wide, including radiators. b. 70 inches deep, including radiators. 8. Stainless steel is to be used for all metal in contact with the foundation (sill, side panels, and false bottom of tank area). All exposed hardware shall be stainless steel. 9. Manufacturer must furnish certification that the transformer will meet ANSI Standard on enclosure security standards. 10. The tank wall inside the compartment shall be painted light grey. L. The transformer tank shall include a fully gasketed cover that is fully detachable for access to the interior of the tank, or approved alternate. It shall have a wraparound guard that is removable only when the compartment doors are opened and shall enclose the tank cover nuts, or approved alternate. M. The transformer shall be equipped with lifting lugs or other suitable means for safely lifting the unit. N. Each transformer shall meet, or exceed, Western Underground Committee Guide 2-13 for security and tamper-resistant operation. O. The transformer shall be provided with all required safety stickers and warning labels.
4 P. The transformer coating shall meet or exceed the latest EEI finishing guidelines for pad mounted equipment and the successful vendor must provide certified test reports insuring this requirement is met. Color shall be Munsell No: 7.0 GY 3.29/1.5 (Ameritech Telephone Green) on the outside. Inside the termination compartment, the tank wall, at minimum, shall be painted light grey. The manufacturer must furnish certification that the transformer will meet ANSI Standard C on finish. Q. The successful vendor shall provide certified test reports, which shall include core and winding losses, on the transformer supplied under this bid. R. Manufacturers are to submit certification that the transformer does not contain any measurable concentrations of PCBs. S. Transformer losses will be evaluated and combined with bid costs to determine successful bidder(s), using the City s Transformer Loss Evaluation formula (Figure 2). T. Manufacturer will stencil appropriate part # on front of transformer (min. 3 high numbers). U. Transformers shall include three 5/8 holes located in the bottom sill below the primary bushings for future installation of fault indicators. The holes shall be in a horizontal pattern and centered in the sill below the primary compartment. The holes shall be covered by a tamper-proof cover.
5 TRANSFORMER LOSS EVALUATION (20 Year) L fe = Core and related no load losses L cu = Load Losses L t = L fe + L cu = Total Losses Typical Values P d = Cost of demand/losses/kw demand only = $ 8.82/KW P e = Cost of energy losses/kwhr; incremental = $ Combined loss cost calculation: Assume load factor = 60% loss factor = 30%) P d = demand only = L fe x $ 8.82 x 12 = $ /Yr. (L fe )P e = energy cost = L fe x 8760 x $ = $ /Yr. (A.) Total, core loss cost = $ /Yr. P d = demand only = L cu x $ 8.82 x 12 = $ /Yr. (L cu )P e = energy cost = L cu x 8760 x.3 x $ = $ /Yr. (B.) Total, load loss cost = $ /Yr. Summary of cost Losses: (A.) Annual cost of No Load Losses (B.) Annual cost of Load Losses Total Annual Cost (L t = L fe + L cu ) = TOTAL ANNUAL COST $ x 20 Years $ Figure 2
S. C. Electric Cooperative s Specification for a Three-Phase, Padmounted URD Transformer (Revised 12/2014)
1.0 GENERAL S. C. Electric Cooperative s Specification for a Three-Phase, Padmounted URD Transformer (Revised 12/2014) 1.1 This specification covers the electrical and mechanical characteristics of Three-Phase,
More informationSubmit shop drawings for equipment provided under this section Shop drawings shall indicate:
Section 16435 - SWITCHBOARDS Introduction Part 1 - General Reference The work under this section is subject to requirements of the Contract Documents including the General Conditions, Supplementary Conditions,
More informationELECTRIC METERING COMMERCIAL & INDUSTRIAL
ELECTRIC METERING COMMERCIAL & 1.0 INDEX 1.0 INDEX 2.0 SCOPE 3.0 GENERAL REQUIREMENTS 4.0 METER LOCATIONS 5.0 UNDERGROUND TERMINATIONS 6.0 METERING TRANSFORMER ENCLOSURES 7.0 SINGLE CUSTOMER METER INSTALLATIONS
More informationThis section applies to the design and installation of transformers.
ELECTRICAL: TRANSFORMERS BASIS OF DESIGN This section applies to the design and installation of transformers. Design Criteria 13.8-kV equipment shall be 15-kV class. Coordinate with short-circuit studies
More informationAll work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.
DIVISION 16 ELECTRICAL SECTION 16100 - ELECTRICAL PART 1 - GENERAL SCOPE All electrical work as shown on the drawings and as necessary to provide a complete electrical system. Include primary service,
More informationInstructions for Secondary Unit Substation Transformers 150-3000 KVA, Three Phase
ABB Inc. Instruction Booklet Distribution Transformers Jefferson City, MO ISO 9001 Certified I.B. 46-060-1, Section E ILUJ000004-BLE Effective: January, 2008 Instructions for Secondary Unit Substation
More informationBERTHOLD ELECTRIC GENERATOR CONNECTION CABINET
BERTHOLD ELECTRIC GENERATOR CONNECTION CABINET Berthold Electric Company s Generator Connection Cabinet provides a quick and convenient station to connect a portable generator to a facility s main service
More informationTRANSFORMER DICTIONARY
TRANSFORMER DICTIONARY AUTOTRANSFORMER A transformer that has only one winding per phase; part of the winding is shared between the primary and secondary CONDITION New - All materials and components are
More informationMETER REQUIREMENTS GENERAL REQUIREMENTS SECTION D
12 - ELECTRIC SERVICE HANDBOOK SECTION D METER REQUIREMENTS This chapter gives you information on Central Lincoln s metering requirements. It's divided into three sections: General requirements This section
More informationCONSOLIDATED EDISON CO. OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY 10003 DISTRIBUTION ENGINEERING DEPARTMENT SUBSTATION & EQUIPMENT SECTION
CONSOLIDATED EDISON CO. OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY 10003 DISTRIBUTION ENGINEERING DEPARTMENT SUBSTATION & EQUIPMENT SECTION SPECIFICATION EO-5023 REVISION 3 MARCH 2003 REQUIREMENTS FOR
More informationMulti-tap Transformers
Multi-tap Transformers Three-Phase Multi-tap Transformer for Electrical Submersible Applications Functional Specification Guide Functional Specification for Multi-tap Transformers for Electrical Submersible
More information2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1. 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.
2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. Relays) Part 1 General 1.1 CONDITIONS AND REQUIREMENTS: A. Refer to
More informationPrimary and Secondary Electrical Distribution Systems
Primary and Secondary Electrical Distribution Systems Critical Facilities Round Table 12th Quarterly Membership Meeting June 2, 2006 David D. Roybal. P.E. Eaton Electrical Cutler-Hammer Products Utility
More informationIssued 06-01-07 E.C.S. Section WTR00 INFORMATION SECTION Page 1 of 1
Issued 06-01-07 E.C.S. Section WTR00 INFORMATION SECTION Page 1 of 1 INDEX SECTION WTR01: ELECTRICAL CONNECTIONS PRIMARY.. Page 1 SERVICE DROPS FROM THREE-PHASE TRANSFORMER BANKS.. Page 9 SECTION WTR02:
More informationIRRIGATION PUMPING Table of Contents - Section 900
IRRIGATION PUMPING Table of Contents - Section 900 PARAGRAPH 900.1 GENERAL 1 900.2 METERING REQUIREMENTS 1 900.3 CUSTOMER S CONTROL EQUIPMENT 2 900.4 SERVICE CONDUCTOR REQUIREMENTS 2 900.5 RECOMMENDATIONS
More informationSample - No Commercial Use
COMPLETE REVISION October 2010 Electrical PIP ELSSG01 Design and Fabrication of Low-Voltage Metal-Enclosed AC Power Circuit Breaker Switchgear PURPOSE AND USE OF PROCESS INDUSTRY PRACTICES In an effort
More information261000 Medium Voltage Electrical Distribution
Sections Included In This Standard: 1.1 General 1.2 Underground Cable 1.3 Medium Voltage Switches 1.4 Transformers 1.5 Electrical Manholes 1.6 Switch Vaults 1.7 Distribution Switchgear/Switchboards This
More informationTERMINATION ENCLOSURE OPTIONS
TERMINATION ENCLOSURE OPTIONS Add suffix: R - Reverse Stagger the Bus Bars (to run cable in from the top) CU - Copper NEMA Mount Bus Bars C - Plastisol Covers for Bus Bars DF - Dead Fronts T - Tin Plated
More informationLow Voltage Transformers Sealed, General Purpose, Dry Type
Low Voltage Transformers Sealed, General Purpose, Dry Type Catalog 7400CT9601R4/08 08 Class 7400 CONTENTS Description..............................................Page Introduction.................................................
More informationTechnical Specification for Oil insulated Transformers U m < 24 kv up to 1250 kva
to 1250 kva Page 1/10 Technical Specification for Oil insulated Transformers U m < 24 kv up to 1250 kva This technical specification is valid for the business unit E.ON Sweden of the market unit E.ON Nordic.
More informationMagnum Mobile Generator MMG55 Specifications
Empowering Real People Magnum Mobile Generator MMG55 Specifications ENGINE John Deere PE5030TF270 - turbocharged, diesel engine o Prime - 72 hp @ 1800 rpm o Standby - 80 hp @ 1800 rpm o 4 cylinder o 3.0
More informationELECTRICAL SERVICE REQUIREMENTS FOR MOBILE HOME DEVELOPMENTS
Prepared by: ABB1 ELECTRICAL SERVICE REQUIREMENTS FOR MOBILE HOME DEVELOPMENTS 052521 Asset Type: Electric Metering Function: Construction Issued by: Quoc Hoang (QxH1) Date: 07-01-16 Rev. #06: This document
More informationLight Duty Commercial Electric Water Heater
Features Heavy Duty Construction Hydrastone cement lining provides longer tank life Copper-silicon tappings cannot rust or corrode High impact composite jacket eliminates damage during installation and
More informationStep Voltage Regulators
Step Voltage Regulators Don Wareham Field Application Engineer Today s Agenda Introduction Voltage Regulator theory Voltage Regulator application considerations Installation and proper bypassing Wrap-up/questions
More informationSWITCHGEAR Section 16. SECTION INCLUDES This Section includes service and distribution switchboards rated 600 V and less.
PART 1 - GENERAL SECTION INCLUDES This Section includes service and distribution switchboards rated 600 V and less. RELATED SECTIONS Division 16 Section "Basic Electrical Materials and Methods" for general
More informationDoc Ref: 2015.06.01.002. 602.783.1112 baselayer.com 2015 BASELAYER TECHNOLOGY, LLC
TM 602.783.1112 baselayer.com 2015 BASELAYER TECHNOLOGY, LLC TM D400E Data Module (60Hz) The EDGE D400E is designed to meet high power density requirements for both the HPC and Web Scale environments while
More informationSpecification Guide. for RVAC. Direct Replacement. AC Medium Voltage. Circuit Breakers
Specification Guide for RVAC Direct Replacement AC Medium Voltage Circuit Breakers Table of Contents 1.0 General Work Scope...3 2.0 Standards...3 3.0 Supplier Qualifications...4 4.0 Circuit Breaker Element
More information25-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp and 1250 Amp
Page 1 2015 Grounded Metal Equipment Plate Equipment Connection Bus Bar or Other Component 15 kv or 25 kv Separable Insulated Connector (elbow) Equipment Connection Power Cable Power Cable Grounded Metal
More informationBuck - Boost Transformers
Buck - Boost Transformers Contents Buck - Boost Transformers - Terms & Definitions... 48 Buck - Boost Transformers - Sizing... 50 Quick Reference Chart - 08, 0, 40 Volts Single & Three Phase... 5 Single
More informationCurrent valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw
4 937 DESIO Current valve for AC 24 V pulse/pause control of electrical loads up to 30 kw SEA45.1 Use The current valve is used for the control of electric heating elements in heating, ventilation and
More informationGenerator DoCKInG StatIonS
Generator DOCKING STATIONS TRYSTAR Portable Power Cable Cam to cam cable extensions 2000V, 100A-400A rated to NEC table 400.5 (B) All portable power cable sold is highly flexible and UL & C-UL or CSA Listed
More informationSection 10 Electric Switchboards: 0 Through 600 Volts
Section 10 Electric Switchboards: 0 Through 600 Volts 10.1. Scope This section provides specific dimensions and details for service and meter equipment that is assembled by the manufacturer in freestanding,
More informationHyperlinks are Inactive
Prepared by: NIB/EOB PLANNING GUIDE FOR SINGLE CUSTOMER SUBSTATIONS SERVED FROM TRANSMISSION LINES 05503 Department: Electric T&D Section: T&D Engineering and Technical Support Approved by: G.O. Duru (GOD)
More informationInstallation. Smart-UPS VT MGE Galaxy 3500. Maintenance Bypass Panel. 10-40 kva 400 V
Installation Smart-UPS VT MGE Galaxy 3500 Maintenance Bypass Panel 10-40 kva 400 V Contents Safety.................................................. 1 Save these instructions...................................
More informationSecondary Unit Substations
14 SWITCHGEAR Secondary Unit Substations Overview Siemens offers a wide variety of unit substation designs to meet customer requirements. A unit substation consists of one or more transformers mechanically
More informationSPECIFICATIONS FOR TENDER NO: PSNR/SCP/VKS/E 1635 ANNEXURE I TECHNICAL SPECIFICATIONS FOR LIGHTING HIGH MAST
TECHNICAL SPECIFICATIONS FOR LIGHTING HIGH MAST ANNEXURE I Sl.No. Description for BHEL Requirement Offered Deviation Scope of supply, erection and commissioning: 1 The scope of this specification covers
More informationSECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM
SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop air conditioning unit (5 tons and smaller). 2. Roof curb. 1.2
More informationSWITCHGEAR SOLUTIONS FOR MISSION CRITICAL APPLICATIONS. Presented by SAI Advanced Power Solutions
SWITCHGEAR SOLUTIONS FOR MISSION CRITICAL APPLICATIONS POWER DISTRIBUTION RACKS IN A MISSION CRITICAL SYSTEM MODULES IN A MISSION CRITICAL SYSTEM UPS Convertor Main Inverter Load Battery BPC UPS & BATTERY
More informationRAY-MAX Integrated Solar Power Strip
RAY-MAX Integrated Solar Power Strip 600008, 600009, 600010, 600208, 600209, 600210 Owner s Manual NEXTRONEX, INC. Revision Date: 10/27/14 Contents 1. Safety Instructions... 3 2. General Equipment Warnings...
More informationHPS Universal. Single and Three Phase Potted. Buck-Boost Transformers. Buck-Boost Applications & Standard Specification... 80
Buck-Boost Transformers Single and Three Phase Potted Buck-Boost Transformers Buck-Boost Applications & Standard Specification... 80 Selecting Buck-Boost Transformers... 81 Single Phase Selection Tables...
More information-1- SPECIFICATIONS 002085 CONE SETTER PLATFORM ATTACHMENT INDEX
-1-002085 CONE SETTER PLATFORM ATTACHMENT INDEX I. GENERAL EQUIPMENT : A. Intent Statement B. Cone Setter Platform II. III. 1. Understructure Frame 2. Mounting Components 3. Paint 4. Basket 5. Labels 6.
More informationCluster Box Units. (CBU s) 3300 Series CBU Door Sizes. Fully Integrated Parcel Lockers CLUSTER BOX UNITS FRONT LOADING. continued on pages 7-11
Cluster Box Units (CBU s) continued on pages 7-11 CLUSTER BOX UNITS FRONT LOADING Made of heavy duty aluminum and stainless steel hardware, Salsbury 3300 series U.S.P.S. approved Cluster Box Units (CBU
More informationTECHNICAL SPECIFICATION FOR PROJECTION WELDING MACHINE (Qty. 2 Nos.)
TECHNICAL SPECIFICATION FOR PROJECTION WELDING MACHINE (Qty. 2 Nos.) 1. Requirement: Two (02) Nos. DC Type, 3 phase, 3 wire Projection Welding Machine is required for welding of ventilation M.S. / Stainless
More informationPS4-24 OWNERS MANUAL 24 VAC 90 WATT WALL MOUNTED CCTV POWER SUPPLY
PS4-24 OWNERS MANUAL 24 VAC 90 WATT WALL MOUNTED CCTV POWER SUPPLY 7320 Ashcroft, Suite 104 Houston, Texas 77081 p: 713-772-1404 f: 713-772-7360 e: info@juicegoose.com www.juicegoose.com 06-06 CONGRATULATIONS
More informationDistribution Voltage Regulators
Distribution Voltage Regulators Type JFR Single Phase 2.5 to 19.9 kv Type SFR Three Phase 13.2 to 34.5 kv Power Transmission & Distribution Siemens JFR & SFR Voltage Regulators Improving Quality of Service
More informationMDT5N25 & MTD5N40 SERVICE PARTS
MDTN & MTDN0 SERVICE PARTS This parts list contains the service parts and wiring diagrams for this model. Check the model number of the machine requiring the parts to be sure that this is the correct parts
More informationELECTRIC UTILITY SERVICE EQUIPMENT REQUIREMENTS COMMITTEE, EUSERC
ELECTRICAL SERVICE REQUIREMENTS ELECTRIC UTILITY SERVICE EQUIPMENT REQUIREMENTS COMMITTEE, EUSERC TABLE OF CONTENTS TITLE SECTION NO. List of Approved Electric Utility Service Equipment Requirements Committee
More informationSECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL
SECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL 1.1 SUMMARY A. This section describes the requirements for the installation of Power Monitors and associated
More informationType MOST oil switch. Technical Data 285-20. Contents. Effective October 2013 Supersedes March 2000
echnical Data 285-20 Supersedes March 2000 ype MOS oil switch Contents Description Page General...2 Ordering information....2 Features and detailed description.... 6 Fuse assemblies....7 MOS switching
More informationHL Series - Commercial Heaters Tankless Water Heating Solutions
HL Series - Commercial Heaters 5-18 kw (17,000-61,400 BTUs) Low flow activation options at.15 and.25 GPM (0.6 and 0.9 L-Min) Certified Lead-Free Design Variable Temp Heat Exchanger Pressure Drop Advantage
More informationFFI. Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars. Presented By: Greg Pelster & Robert Schmid
Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars Presented By: Greg Pelster & Robert Schmid FFI Ferrie, Franzmann Industries LOW VOLTAGE SWITCHGEAR & LOW VOLTAGE
More informationMTE SERIES RLW. World REACTORS USER MANUAL PART NO. INSTR 030 REL. 090930. 2009 MTE Corporation
MTE SERIES RLW World REACTORS USER MANUAL PART NO. INSTR 030 REL. 090930 2009 MTE Corporation IMPORTANT USER INFORMATION NOTICE MTE Series RLW reactors are components designed to improve the reliability
More informationSTB Series Enclosures
STB Series Enclosures Features/Applications: The STB series of sheet steel enclosures are designed to meet the requirement for distribution and lighting junction boxes. Available in 14 sizes with standard
More informationCABINET OPTIONS AND DESIGNATORS
CABINET OPTIONS AND DESIGNATORS Hinges: ~Stainless steel lift off Nuts and Bolts: ~ Stainless steel Hardware: ~ Handles and Corbin locks are stainless steel or zinc plated Windows: ~ Lexan Backboards:
More informationInstallation Instructions
READ BEFORE INSTALLING UNIT For Slider Casement Air Conditioners To avoid risk of personal injury, property damage, or product damage due to the weight of this device and sharp edges that may be exposed:
More informationP 602. This generator set has been designed to meet ISO 8528 regulation. This generator set is manufactured in facilities certified to ISO 9001.
This generator set has been designed to meet ISO 88 regulation. This generator set is manufactured in facilities certified to ISO 900. This generator set is available with CE certification. Enclosed product
More information16300 MEDIUM VOLTAGE DISTRIBUTION
16300 MEDIUM VOLTAGE PART 1: GENERAL 1.01 SYSTEM DESCRIPTION A. Most new loads will be served from the underground electric distribution system. This system is a primary open loop configuration served
More informationBUILT-IN DISHWASHER INSTALLATION INSTRUCTIONS
BUILT-IN DISHWASHER INSTALLATION INSTRUCTIONS PLEASE READ COMPLETE INSTRUCTIONS BEFORE YOU BEGIN LEAVE INSTALLATION INSTRUCTIONS AND USER'S GUIDE WITH OWNER ALL ELECTRIC WIRING AND PLUMBING MUST BE DONE
More informationLIEBERT VNSA Installation Sheet
LIEBERT VNSA Installation Sheet Description The Liebert vnsa network switch is designed for connecting multiple Ethernet-ready devices and comes in various models. The unit may have: A Liebert icom display
More informationSECTION 15750 PACKAGED ROOFTOP AIR CONDITIONING UNITS
SECTION 15750 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes requirements for roof mounted, self-contained units, with electric cooling, and electric or reverse refrigeration cycle (heat pump) heating
More informationMini Power-Zone Unit Substation Product Description. Product Description. Features. Typical Applications
Product Description Product Description The Mini Power-Zone Unit Substation from Schneider Electric is a miniaturized version of our Power-Zone Unit Substation. Included are: Circuit Breaker Sealed Step-Down
More informationSECTION 22 LIGHTNING PROTECTION SYSTEM
SECTION 22 LIGHTNING PROTECTION SYSTEM 22.01 SCOPE: A. These Specifications shall form a part of the Contract Documents and shall govern construction work for all buildings to be built or modified for
More informationA. Shop Drawing submittals shall include, but not be limited to, the following:
SECTION 26 05 53 IDENTIFICATION FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and Section 26 00 01, Electrical
More informationAdvantium 2 Plus Alarm
ADI 9510-B Advantium 2 Plus Alarm INSTALLATION AND OPERATING INSTRUCTIONS Carefully Read These Instructions Before Operating Carefully Read These Controls Corporation of America 1501 Harpers Road Virginia
More informationDigital Energy ITI. Instrument Transformer Basic Technical Information and Application
g Digital Energy ITI Instrument Transformer Basic Technical Information and Application Table of Contents DEFINITIONS AND FUNCTIONS CONSTRUCTION FEATURES MAGNETIC CIRCUITS RATING AND RATIO CURRENT TRANSFORMER
More informationSPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT
SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT The purpose of these specifications is to insure that there are minimum
More informationRequirements for the Attachment of Communication Cable Facilities on PPL Poles
Page 99 of 137 Requirements for the Attachment of Communication Cable Facilities on Replaces: URS-3002 URS-3004 URS-101C-304 A-157649 Page 100 of 137 Reference Notes for Drawings: General 1. The term communication
More informationPressure monitoring equipment for oil-sf 6. bushings, type GOEK
Pressure monitoring equipment for oil-sf 6 bushings, type GOEK Installation and maintenance guide 5693 827-6 en, Rev. 3, 2002-01-30 This document must not be copied without our written permission, and
More informationWE-350 Series ¼ Turn Electric Actuator
WE-350 Series ¼ Turn Electric Actuator Operation and Installation Manual Pg 1 (Rev. 020113) Table of Contents 1.0 General 1.1 Pre-Installation Inspection 1.2 Storage 1.3 Features & General Information
More informationAir Vantage 500 Kubota
Illustration of Sub Assemblies Illustration of Sub Assemblies Illustration of Sub Assemblies Illustration of Sub Assemblies P-625 P-625 RETURN TO MAIN INDEX PARTS LIST FOR Air Vantage 500 Kubota P-625-A
More informationELECTRICAL GUIDELINES FOR SINGLE-FAMILY HOME OWNERS:
ELECTRICAL GUIDELINES FOR SINGLE-FAMILY HOME OWNERS: Chapter 12 of the Burlington Code of ordinances allows owner occupants of single family homes to do their own wiring if they choose. If you choose to
More informationOPERATING AND MAINTENANCE MANUAL FOR COMMERCIAL ELECTRIC WATER HEATER ELECTRIC HEATER COMPANY BASE MODEL SE
OPERATING AND MAINTENANCE MANUAL FOR COMMERCIAL ELECTRIC WATER HEATER ELECTRIC HEATER COMPANY BASE MODEL SE HUBBELL ELECTRIC HEATER COMPANY P.O. BOX 288 STRATFORD, CT 06615 PHONE: (203) 378-2659 FAX: (203)
More informationRMM2 Heat-Tracing Remote Monitoring Module for the Raychem NGC Control System Installation Instructions
Heat-Tracing Remote Monitoring Module for the NGC Control System Installation Instructions Tools Required 3 mm slotted screwdriver 3/8 hex key (for -4X only) Approvals Nonhazardous locations Type NM LISTED
More informationInstallation Instructions
H5HK Series Installation Instructions 3 Phase Electric Heater Kits 7.5 and 0 TON Package A/C Systems Description Installation of 08/40V and 480V H5HK 3 Phase Heater Kits in 7.5 and 0 TON Packaged Air Conditioners.
More informationElectrical Service Guidelines
Electrical Service Guidelines Middle Tennessee Electric Membership Corporation Revised: May 23, 2013 MTEMC's Electrical Guidelines TABLE OF CONTENTS Right-of-Way Clearance Guide 3 MTEMC Requirements 4
More informationCustomer Substation Manual 08/05/02
Customer Substation Manual Table of Contents Section Page 2 of 85 Description 0 Preface 010.00 General 010.10 Information Required for the Review of New Customer Substations 010.20 New Customer Substation
More informationUNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation
Basis of Design This section applies to the design relating to low voltage switchboards. Design Criteria UW Class N1 facilities main switchboards shall be rear accessible. The main, tie and feeder breakers
More informationMorrison Bros. Co. General Product Specifications
Morrison Bros. Co. General Product Specifications Tank Mounted Spillbox The spill containment device is manufactured to contain spills and drips that may occur at the fill point on aboveground storage
More informationCommercial Gas Furnace Upflow
Commercial Gas Furnace Upflow Model G24-200 80% A.F.U.E. 200,000 Btuh Input Heating Cap. 7.5 or 10 Tons Nominal Add-On Cooling GUK FEATURES Certified by A.G.A./C.G.A. Laboratories. Heavy gauge painted
More informationSECTION 16322 SUBSTATION TRANSFORMERS
SUBSTATION TRANSFORMERS PART 1 GENERAL 1.01 1.02 1.03 1.04 SCOPE The Contractor shall furnish and install the primary and/or secondary substation transformers as specified herein and as shown on the contract
More informationMultiple Meter Installation - 200 Amperes Per Position -Single Phase, Self-contained
Overhead Meters TABLE OF CONTENTS D D Consumer Service Pole for Mobile Home Park Temporary Service -wire Single Phase D. Overhead Meter Installation - Single Phase D. Connection Diagram - Single Phase
More informationMODEL 2202IQ (1991-MSRP $549.00)
F O R T H E L O V E O F M U S I C F O R T H E L O V E O F M U S I C MODEL 2202IQ (1991-MSRP $549.00) OWNER'S MANUAL AND INSTALLATION GUIDE INTRODUCTION Congratulations on your decision to purchase a LINEAR
More informationAMFA-27 AMFA-29. Operator s Manual & Installation Instructions. Rev. 2.5
AMFA-27 AMFA-29 Operator s Manual & Installation Instructions Rev. 2.5 Date: 17 July, 2010 Permanently-connected, utility Interactive, single-phase, inverters Model AMFA-27 WIND TURBINE INVERTER (240 VAC
More informationInstallation. Smart-UPS VT and MGE Galaxy 3500. Maintenance Bypass Panel with Power Distribution (wall-mount) 10-30 kva 208 V
Installation Smart-UPS VT and MGE Galaxy 3500 Maintenance Bypass Panel with Power Distribution (wall-mount) 10-30 kva 208 V Contents Safety... 1 SAVE THESE INSTRUCTIONS...............................
More informationInstallation Instructions For Slider Casement Air Conditioners
Installation Instructions For Slider Casement Air Conditioners NOTE: These instructions describe installation in a typical wood framed window with a wood SLIDE-BY sash, or installation in a metal CASEMENT
More informationPRODUCT GUIDE. SL Medium Voltage IEC Vacuum Contactors
PRODUCT GUIDE SL Medium Voltage IEC Vacuum Contactors Table of Contents 1 Overview Introduction....................................................2 Features........................................................2
More informationShort Circuit Current Calculations
Introduction Several sections of the National Electrical Code relate to proper overcurrent protection. Safe and reliable application of overcurrent protective devices based on these sections mandate that
More information12VDC MAGNETIC LED DIMMABLE POWER SUPPLIES SPEC SHEET DIGEST
12VDC MAGNETIC ED DIMMABE POER SUPPIES SPEC SEET DIGEST TM-30-DIM TM-50-DIM T-60-DIM TM100-DIM TM200-DIM TM300-DIM iring Diagram for TM-50-DIM and TM-100-DIM ED 12VDC MAGNETIC DIMMABE 30 POER SUPPY Smallest
More informationSECTION 08332 COILING COUNTER DOORS. Display hidden notes to specifier. (Don't know how? Click Here)
SECTION 08332 COILING COUNTER DOORS Display hidden notes to specifier. (Don't know how? Click Here) PART 1 GENERAL 1.1 SECTION INCLUDES A. Coiling Metal Counter Doors. B. Coiling Counter Fire Doors. 1.2
More information26 3213.13 Diesel Engine Driven Generators Page 1 of 6
Last Update: December 8, 2014 A. Description of System Consultant s Handbook Page 1 of 6 1. Provide a diesel engine driven electric generating unit, factory assembled, tested and certified to operate at
More informationWARNING: FAILURE TO FOLLOW THESE RULES MAY RESULT IN SERIOUS PERSONAL INJURY CAUTION: INSTALLATION LOCATION:
Revision Level: 01 Revision Date: 07/07/2011 Please read all instructions carefully to help ensure a correct and SAFE installation of your Second Wind Ultraviolet Germicidal Air Purifier. Failure to do
More informationTECHNICAL SUPPORT MANUAL 3 Phase Air Conditioner Component R2A3**GHR
3 Phase Air Conditioner Component R2A3**GHR DANGER, WARNING, CAUTION, and NOTE The signal words DANGER, WARNING, CAU- TION, and NOTE are used to identify levels of hazard seriousness. The signal word DANGER
More informationTP-C2 Motor Operator CLEAVELAND / PRICE INC. Bulletin DB-111B12
Bulletin DB-111B12 TP-C2 Motor Operator CLEAVELAND / PRICE INC. 14000 Rt. 993, Trafford, PA 15085 (724) 864-4177 FAX (724) 864-9040 Email: sales@cleavelandprice.com Cleaveland/Price Type TP-C2 Motor Operator
More informationChromalox. Installation, Operation. Portable Industrial Unit Blower Air Heater Type DRA RENEWAL PARTS IDENTIFICATION
Chromalox Installation, Operation RENEWAL PARTS IDENTIFICATION Portable Industrial Unit Blower Air Type DRA and DIVISION SALES REFERENCE DATE SECTION (Supersedes P-) PF-) NOVEMBER, 00 DRA PF- -0-00 Specifications
More informationSECTION 16461 DRY-TYPE TRANSFORMERS
SECTION 16461 PART 1 - GENERAL 1.1 SECTION INCLUDES A. Furnishing and installation of and testing of cast resin dry type MV/LV distribution transformer in accordance with specifications and drawings. Any
More informationINSTALLATION INSTRUCTIONS
LIGHTING CONTROL PANELS 4 AND 8 RELAYS INSTALLATION INSTRUCTIONS INSTALLATION OVERVIEW The installation instructions contained in this document are provided as a guide for proper and reliable installation.
More informationRecirculating Roof Fans Models ESRMD, ESRMDF and ERD
Recirculating Roof Fans Models ESRMD, ESRMDF and ERD Four-Way Fan Exhaust Supply Mix Recirculate BUILDING VALUE IN AIR. October 2005 Recirculating Roof Fans Exhaust/Supply/Recirculation/Mix Model ESRMD
More informationLightning Arresters P30027 18 KVA P30038 10 KVA. Description & Installation
Lightning Arresters P30027 18 KVA P30038 10 KVA Description & Installation Printed in USA 09/11 TO330 Rev. B Table of Contents Page 1.0 SCOPE 2 2.0 PRODUCT OVERVIEW 2 2.1 Intended Uses 2 2.2 Lightning
More informationMCC Ratings. Voltage Rating
MCC Ratings In addition to the various ratings of individual components used in motor control centers, the overall ratings of the motor control center must also be considered. Voltage Rating Motor control
More informationSECTION 23 81 43 HEAT PUMPS
SECTION 23 81 43 HEAT PUMPS PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop heat pumps. 1.2 REFERENCES A. American Society of Heating, Refrigerating and Air-Conditioning Engineers:
More information