SHIMADEN DIGITAL CONTROLLER
|
|
- Logan Lesley Stevenson
- 7 years ago
- Views:
Transcription
1 Shimaden, Temperature and Humidity Control Specialists C %RH Series SR7 SHIMADEN DIGITAL CONTROLLER & NRTL /C approved ASIC FEATURES Multi-input and multi-range performance Includes a new processing system, Expert PID, remarkably improved PID control efficiency; overshoot and undershoot are controlled effectively. The keylock function can avoid erroneous operation resulting from set values or parameter settings. The PV bias function can correct errors caused by sensor input. A wide selection of additional functions (optional) is available to suit various needs.
2 SPECIFICATIONS Display Digital display: 7 segments / Measured value (PV) Green LED 4 digits, Set value (SV) Orange LED 4 digits Parameter display: y 7 segment LEDs for PV and SV Action display / colors: -type LED lamp indication Control output (OUT) / Green Auto tuning (AT) / Green Alarm ( and AL / H) / Red Display accuracy: ± (.5% FS+1 digit) excluding cold junction temperature compensation accuracy in the case of the thermocouple input. ±5% FS for temperatures below 4 C (75 F) of thermocouple. Display accuracy range: ±5 C Display resolution: Depends on measuring range (.1, 1) Measured value display range: -1~11% of measuring range (-1~68 C for -~6 C of R.T.D. input) Sampling cycle:.5 sec. Setting Setting: Setting range: y 4 front key switches Same as the measuring range. Refer to Table of Measuring Range Codes. Input Type of input / measuring range: Thermocouple, R.T.D. and voltage (mv) input types: Multi-input, Multi-range Refer to Table of Measuring Range Codes. Voltage (V) and current (4~mA) input types: by code selection Thermocouple:, R, S, K, E, J, T, N {U, L (DIN 471)} External resistance: 1Ω max. Input impedance: 5kΩ min. urnout: Standard feature (up scale) Cold junction temperature compensation accuracy: ± C (5~45 C) R.T.D.: JIS Pt1 / JPt1 -wire type Amperage: Approx..5mA Lead wire tolerable resistance: 5Ω max. / wire (The lead wires should have same resistance.) Voltage: ~1, 1~5, ~1mV DC or ~1, 1~5, ~1V DC Input impedance: 5kΩ min. Current: 4~mA DC Receiving impedance: 5Ω Sampling cycle:.5 sec. PV bias: ±. unit in case the decimal point is included in the measuring range. If not, ± unit. PV filter: ~1 sec. ( = without filter) Isolation: Insulated between input and output (not insulated between input and system, SV bias and CT input)
3 Series SR7 Control Control mode: Auto-tuning PID control / On-Off control Proportional band ( P ): Off,.1~.% FS (Off setting: On-Off action) Integral time ( I ): 1~6 sec. Derivative time ( D ): ~6 sec. ( sec. setting: PI action) On - Off hysteresis: 1~ unit Proportional cycle: Fixed to sec. during contact output Fixed to sec. during SSR drive voltage output Control output characteristics: RA / DA selectable (set RA when shipped) Set value function ( SF ): Off (Off =.) and.1~1. Control output type / rating Contact output ( Y1 ): Current output ( I1 ): SSR drive voltage output ( P1 ): Voltage output ( V1 ): Isolation: SR71: 4V AC A / resistive load: 1.A / dielectric load SR7, SR7 and SR74: 4V AC.5A / resistive load: 1.5A / dielectric load 4~mA DC / load resistance: 6Ω max. ±V DC (with load resistance at 1.5kΩ) / load current: ma maximum ~1V DC / load current: ma maximum Isolated between control output and system and input ADDITIONAL FUNCTIONS (OPTIONAL) Alarm output Number of alarm points: Alarm Type: ( and AL / H) (for both normal open and common) Selectable from combinations of the following types. Not assigned Higher limit deviation value + 1. lower limit deviation value without inhibit action Higher limit absolute value +. lower limit absolute value without inhibit action Higher limit deviation value +. lower limit deviation value with inhibit action Higher limit absolute value + 4. lower limit absolute value with inhibit action Higher limit deviation 5. value without inhibit action + heater break Higher limit absolute 6. value without inhibit action + heater break Higher limit deviation 7. value with inhibit action + heater break Higher limit absolute 8. value with inhibit action + heater break Alarm setting range: Alarm action: Alarm action hysteresis: Alarm output / rating: Higher limit and lower limit absolute value alarms: Within measuring range Deviation value: Higher limit: ~ unit* Lower limit: -1~ unit* In case SV is out of the } measuring range, higher and lower limit values of the measuring range become the On - Off action action points. Fixed to.% of the measuring range Contact 1a (common) / 4V AC 1.5A (resistive load)
4 Series SR7 Heater break alarm (for single phase) (Note: This function can be added if the instrument has an alarm option and the control output is the contact type or the SSR drive voltage type. In SR71, addition is possible unless it has an SV bias option.) Alarm action: Heater amperage detected by externally attached CT (CT provided). Alarm output On upon detection of heater break while control output is On. Current setting range: Off,.1~5.A (Alarm action stops when Off is set.) Setting resolution:.1a Amperage display:.~55.a Display accuracy: 5% FS (when sine wave is 5 Hz) Minimum time for action confirmation: On time: 5 msec. Alarm holding: Selectable between Lock (holding) and Real (no holding) Sampling cycle: sec. Isolation: Insulated between CT input and control output (not isolated between CT input and system and other inputs) Set value bias (Note: In case of SR71, this function can be added unless it has a Heater reak Alarm option.) Setting range: -1~ unit Setting resolution: Same as display resolution Action input: Non-voltage contact (bias in action when S terminal is closed) Isolation: Insulated between the SV bias input and the control output (not isolated between the SV bias and the system and other inputs) Others Data storage: y non-volatile memory (EEPROM) Operating ambient temperature / humidity range: -1~5 C / % RH max. (no dew condensation) Data storage temperature: -~+65 C Supply voltage: 1~4V AC±1% (5 / 6 Hz) Power consumption: Approx. 11VA Input noise eliminating ratio: Normal mode: 6d min. (5 / 6Hz) Common mode: 1d min. (5 / 6Hz) Applicable standard: Safety: IEC11-1 and EN611-1 EMC: EN616 Insulation resistance: Dielectric strength: Protective structure: Material: External dimensions: Mounting: Panel thickness: Panel cutout: Weight: etween the input / output terminal and the power supply terminal: 5V DC MΩ minimum etween the input / output terminal and the ground terminal: 5V DC MΩ minimum 1 min. at V AC between the input / output terminal and the power supply terminals 1 min. at V AC between the power supply terminal and the ground terminal Only front panel has simple dust-proof and drip-proof structure PPO resin molding (equivalent to UL4V-1) SR71: H48 W48 D11 (panel depth: 1) mm SR7: H7 W7 D11 (panel depth: 1) mm SR7: H6 W6 D11 (panel depth: 1) mm SR74: H6 W48 D11 (panel depth: 1) mm Push-in panel (one-touch mount) 1.~.5 mm SR71: H45 W45mm, SR7: H68 W68mm SR7: H Wmm, SR74: H W45mm SR71: Approx. 18g, SR7: Approx. 6g SR7: Approx. g, SR74: Approx. 5g
5 APPLICATION EXAMPLE (SV IAS) Series SR7 Temperature sensor Set value for target temperature (SV) SR7 controller Timer T Plant culture tank C SV bias (S) -5 C 18 C ias operation signal ON OFF Day Night Day Night Heater ALARM OUTPUT (OPTIONAL) Alarm Method Alarm Setting Range Action Higher limit deviation value alarm ~ unit OFF ON Lower limit deviation value alarm -1~ unit ON OFF Higher limit absolute value alarm within measuring range OFF ON Lower limit absolute value alarm within measuring range ON OFF Main setting Alarm setting WIRING EXAMPLE Contact output (Y1) SR7, SR74 SV bias no-voltage contact (closed for input) S CT +A L N GR COM NO NC COM Fuse 5VAC.5A MC Instrurment power supply 1-4V AC 5/6Hz MC : Electro-magnetic switch 1 1 AL Higher limit alarm Lower limit alarm or healer break alarm Thermocouple Power supply Heater CT V AC 5/6Hz Note: 1. The heater break alarm function (optional) can be added when the control output is of the contact (Y1) or the SSR drive voltage (P1) type.. Fuse: Since the instrument dose not have a built-in fuse, do not forget to install a fuse in the power circuit to be connected to the power terminal. The fuse should be positioned between the switch or the breaker and the instrument and be attached to the L side of the power terminal. Fuse Rating: 5V AC.5A / medium lagged or lagged type Use a fuse which meets the requirements of IEC 17. Current output (I1) SSR drive voltage (P1) Control output portion only Control output portion only Operating power supply SR7, SR74 SR7, SR mA DC 6Ω Max. PAC series (thyristor) V DC ma Max. 16 PAC series (SSR) Heater Operating power supply Heater
6 SR71 Series SR7 External Dimensions Panel Cutout Terminal Arrangement OUT AT / H SR71 48 PV SV ENT SHIMADEN min. 1-4V AC~ L 5/6Hz11VA N GR A - 6 min. Unit : mm DC OUTPUT 4-mA DC -1V DC mavdc A4V AC COM 1.5A 4V AC AL/H 1.5A 4V AC CT/S SR7 External Dimensions Panel Cutout Terminal Arrangement OUT AT / H PV SV min. 1 min. S + + A DC CT 16 COM A 4V AC 18 AL/H 1.5A 4V AC 1 8 L 1-4V AC~ 1 5/6Hz11VA N GR + COM 11 OUTPUT 4 - ma DC - - 1V DC NO 1 mav DC NC 1.5A 4V AC ENT SR7 SHIMADEN Unit : mm SR7 AND SR74 SR7 External Dimensions Panel Cutout Terminal Arrangement (Common) PV SV OUT SR7 6 AT / H ENT SHIMADEN min min. Unit : mm S CT L 1-4V AC~ 1 5/6Hz1VA N 1 GR + COM 14 OUTPUT 4-mA DC - -1V DC NO mav DC NC 16.5A 4V AC + + A 7 17 DC COM 1 1.5A 4V AC AL/H 1 1.5A 4V AC SR (48xN ) PV +.8 SV OUT AT / H 6 1 min. When instruments are installed in colse contact with each other sideways. N=the number of instruments. ENT SR74 SHIMADEN Unit : mm
7 ORDERING INFORMATION Series SR7 ITEMS CODE SPECIFICATIONS SR71- H48 W48 D11 DIN size digital controller for auto tuning PID control SR7- H7 W7 D11 DIN size digital controller for auto tuning PID control SERIES SR7- H6 W6 D11 DIN size digital controller for auto tuning PID control SR74- H6 W48 D11 DIN size digital controller for auto tuning PID control Thermocouple, R, S, K, E, J, T, N Value set at {U, L (DIN471)} 8 Multi input K ~1 C R.T.D. Pt1 / JPt1 INPUT when shipped Voltage (mv) ~1, 1~5, ~1mV DC 4 Current (ma) 4~mA DC Value set at 4~mA / ~1. when shipped 6 Voltage (V) ~1, 1~5, ~1V DC Value set at ~1V / ~1. when shipped Contact (1c) Contact capacity: 4V AC.5A / resistive load Y1- Proportional cycle fixed to sec. RA (heating CONTROL I 1- Current 4~mA DC Load resistance: 6Ω max. characteristics) OUTPUT SSR drive voltage Output rating: V±V DC ma max. set when shipped P1- Proportional cycle fixed to sec. V1- Voltage ~1V DC load current: ma max. None Alarm points (higher and lower limits) alarm (1a) Alarm: Higher & lower (for both normal open and common) limit deviation 1 OPTIONAL FUNCTION (Deviation / absolute value and inhibit action are value (without Alarm selectable) inhibit action) Heater break alarm Alarm + heater break alarm (can be assigned to AL / H) Heater break alarm (for single phase) Setting range:.~.a mode: Lock mode, (Selectable only for Y1 Alarm + heater break alarm (can be assigned to AL / H) set when shipped or P1 control output) Setting range:.~5.a SV bias 4 SV bias Setting range: -1~ unit 5 Alarm + SV bias 6 Alarm + heater break alarm (.A) + SV bias (Note: Unselectable for SR71) 7 Alarm + heater break alarm (5.A) + SV bias (Note: Unselectable for SR71) C Without (for CE Marking) REMARKS With (for remarks other than CE Marking) SR71: Control output Contact (1a) Contact capacity: 4V AC A / resistive load ACCESSORIES REQUIRED FOR HEATER REAK ALARM FUNCTION (COMMON) CT wiring A (CTL-6-S) 5A (CTL-1-S6-8).8.6 To CT Input terminal Heater (load) wiring M (Unit: mm)
8 MEASURING RANGE CODES Series SR7 Multi-input Input Type Code Measuring Range ( C) Code Measuring Range ( F) 1 1 ~ 18 1 ~ R ~ 17 1 ~ 1 S ~ ~ 1 K1 4-1 ~ 4 - ~ 75 K 5 ~ 1 16 ~ Thermocouple E 6 ~ 7 17 ~ 1 R.T.D. J 7 ~ 6 18 ~ 11 T 8-1. ~. 1 - ~ 4 N ~ 1 ~ U 1-1. ~. 1 - ~ 4 L 11 ~ 6 ~ 11 Pt1 1 - ~ 6 - ~ ~ ~. -5. ~ ~ ~. 4 ~ ~ ~ ~ ~. JPt ~ ~ ~. 46 ~ 4. ~ 1 71 lnitial value :.~1. Note) 1 Thermocouple : fixed at Voltage (mv) 1 ~ 5 7 Conditions of scaling Accuracy not guaranteed Scaling. setting ~ range: 1. for temperatures below ~ 1 7 1~, 4 C (75 F) ~ 1 81 Span: 1~5 counts Thermocouple U, L: DIN471 fixed at Voltage (V) 1 ~ 5 8 Position of decimal point: R.T.D.Pt1: Present JIS / IEC JPt1: Former JIS No decimal. point, ~ the 1. ~ 1 8 Thermocouple T: first, second and third Accuracy not guaranteed decimal places fixed at Current (ma) 4 ~ 5 for temperatures below. ~ 1. - C, ± (.7%FS + 1 digit) TERMINAL COVER (AVAILALE SEPARATELY) Model SR71 SR511-6 SR7 SR51-6 SR7 SR51- SR74 SR541-7 Material / Appearance: PVC / transparent Thickness: 1 mm Mounting: + tight pan-head screws M. 6mm Warning The SR7 series is designed for the control of temperature, humidity and other physical values of general industrial equipment. (It is not to be used for any purpose which regulates the prevention of serious effects on human life or safety.) Caution If the possibility of loss or damage to your system or property as a result of failure of any part of the process exists, proper safety measures must be made before the instrument is put into use so as to prevent the occurrence of trouble. ISO 1 (The contents of this brochure are subject to change without notice.) Temperature and Humidity Control Specialists Head Office: --1 Kitamachi, Nerima-Ku, Tokyo Japan Phone: Fax: exp-dept@shimaden.co.jp URL: FSR7
SR1, SR3 Series Digital Controller Instruction Manual
SR, SR Series Digital Controller Instruction Manual Please do not begin operating this product until you have read this instruction manual thoroughly and you understand its contents. Safety Rules For matters
More informationTLK 48 MICROPROCESSOR-BASED DIGITAL ELECTRONIC REGULATOR
TLK 48 MICROPROCESSOR-BASED DIGITAL ELECTRONIC REGULATOR TECHNICAL DATA CARATTERISTICHE MECCANICHE Housing Self-extinguishing plastic, UL 94 V0 Dimensions 48x48 mm DIN depth 98 mm Weight 225 g approx.
More informationTemperature Controller CD401/CD901/CD701/CD501/CD100/CD101 Instruction Manual
Ⅰ. Warn Warning of connection Temperature Controller CD401/CD901/CD701/CD501/CD100/CD101 Instruction Manual If the controller fails to operate or error occurs, the system will bring fault for it, please
More informationAuto-tune PID. Temperature Controller BRAINCHILD FEATURES
Auto-tune PID Temperature Controller FEATURES Easy-to-use Fuzzy modified PID heat & cool control Fast A-D sampling rate (5 times/s) Universal input (PT100, thermocouple) with high accuracy 18-bit A-D Analog
More informationInput signal Maximum Range Accuracy. Thermocouple E -50 to 700 C (-58 to 1832 F) ±1 C
F4 Process Controller Installation and Operation Guide SAFETY ALERTS The symbols below are used on the equipment and throughout this document to draw the user s attention to important operational and safety
More information#1381-3, Juan-dong, Nam-gu, Incheon, Korea TEL:(82-32) 876-4697 FAX:(82-32) 876-4696 http://www.hynux.com E-mail: sdt@hyelec.co.kr
#1381-3, Juan-dong, Nam-gu, Incheon, Korea TEL:(8-3) 876-4697 FAX:(8-3) 876-4696 http://www.hynux.com E-mail: sdt@hyelec.co.kr MA01E50110 Recorder & Temperature Controller RT9 INSTRUCTION MANUAL Thank
More informationJ TB/TW Temperature limiter, temperature monitor
JUMO GmbH & Co. KG Delivery address:mackenrodtstraße 14, 36039 Fulda, Germany Postal address: 36035 Fulda, Germany Phone: +49 661 6003-0 Fax: +49 661 6003-607 e-mail: mail@jumo.net Internet: www.jumo.net
More informationUser Manual Auto Tuning PID Temperature Controller
User Manual Auto Tuning PID Temperature Controller TUPC-T series (Applicable for accurate controls of Temperature) TEMPSEN DEVICES Plot No : 2&3, Balaji Nagar, 4 th Street, Mettukuppam, Thoraipakkam, Chennai-600097
More information+ A + + - B V B - - + + + NO NC V COM - - - PV PV
+ - A + B B - V + - NO NC COM + - + - V + - PV PV Ramp Soak 100 70 50 30 3 5 3 8 5 3 Minute Steam Heating Sensor Cooling Water PID Hotplate Specifications Input power supply AC 100 to 240V, 50/60Hz, DC
More informationHONEYWELL DC 1010 / 1020 1030 / 1040 DIGITAL CONTROLLER PRODUCT MANUAL 51-52-25-113 06/02
HONEYWELL DC 1010 / 1020 1030 / 1040 DIGITAL CONTROLLER PRODUCT MANUAL 51-52-25-113 06/02 Before using this manual, please check to ensure the Model number, input type Range and output match your requirements.
More informationCurrent valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw
4 937 DESIO Current valve for AC 24 V pulse/pause control of electrical loads up to 30 kw SEA45.1 Use The current valve is used for the control of electric heating elements in heating, ventilation and
More informationMeter Relays. 077 Series Analogue Meter Relays. Features. Applications
077 Series Analogue Features Monitors and controls any variable which can be converted to an A.C. or D.C. signal. Rugged, shock and vibration resistant design Indicator, relays and power unit in one housing
More informationPanel Meters and Controllers Modular Panel Meter Type EDM 35
Panel Meters and Controllers Modular Panel Meter Type EDM 35 Modular digital panel meter, 3 1/2-digit Indicating or controlling current, voltage, resistance, temperature, tacho or frequency. Easy programming
More informationDifferential Pressure Sensors for air and non-corrosive gases, with calibration certificate
1 919 1919P01 1919P03 QBM65/C, QBM75-1U/C Differential Pressure Sensors for air and non-corrosive gases, with calibration certificate QBM751-1/C QBM65/C QBM75/C Highly accurate measurements with calibration
More informationAdjustment functions for both span and shift have been incorporated
SENSORS FOR SERIES LED Type Wafer Alignment Sensor FX-0-F FT-F9 FD-F7 EX-F70/F60 M SH-7 FD-L4 M-DW The use of a safe LED light beam now allows for high precision detection with a resolution of 0!m (.8
More informationCONTROLS DATA MANAGEMENT PROCESS AUTOMATION EUROCUBE. General purpose single phase thyristors and solid state relays Product data.
425 CONTROLS DATA MANAGEMENT PROCESS AUTOMATION EUROCUBE General purpose single phase thyristors and solid state relays Product data abc 425 EUROCUBE A complete range of low cost solid state relays and
More informationRISH CON - Hz. Salient Features : Application : Product Features: FREQUENCY TRANSDUCER
Application : The RISH CON - Hz transducer is used for frequency measurement. The output signal is proportional to measured frequency and is either load independent DC Current or load independent DC Voltage.
More informationACS-30-EU-EMDR-10-MOD
Multi-application heat tracing Control and Monitoring in commercial and residential buildings Roof & Gutter de-icing sensor module Technical Information Approvals Module IP rating Ambient operating temperature
More informationAutomation System TROVIS 6400 TROVIS 6493 Compact Controller
Automation System TROVIS 6400 TROVIS 6493 Compact Controller For panel mounting (front frame 48 x 96 mm/1.89 x 3.78 inch) Application Digital controller to automate industrial and process plants for general
More informationQuick Connect. quick - simple - efficient. www.g-mw.de
Quick Connect quick - simple - efficient www.g-mw.de Phone: +49 9103 7129-0 Fax: +49 9103 7129-207 Innovative connection technology to plug three single-phase current transformers to multifunctional power
More informationTelefon (+45) 43 43 82 00 Telefax (+45) 43 43 74 75 mail@uni-valve.com www.uni-valve.com. Installation and operating manual
Uni-Valve A /S VENTILER & INSTRUMENTER Telefon (+45) 43 43 82 00 Telefax (+45) 43 43 74 75 mail@uni-valve.com www.uni-valve.com UNI-EL Electric actuator Installation and operating manual Remote position
More informationINITIAL SETTING MANUAL
REX - C100 REX - C400 REX - C410 REX - C700 REX - C900 INITIAL SETTING MANUAL RKC RKC INSTRUMENT INC. F.M FRANKLIN PTY LTD PH. (07) 3391 4865 This is a manual for the initial setting of the REX-C100, -C400,
More informationRISH EM 3490 DS Dual Source Energy Meter RISH EM 3490 DS. Application : Product Features:
Application : RISH Master 3490 DS measures important electrical parameters of Utility (in normal mode) & Generators (in Power back up) in three phase and single phase Network & replaces the multiple analog
More informationThyristor-controlled power supplies and battery chargers
Thyristor-controlled power supplies and battery chargers Input voltage: 115 / 230 VAC, single phase, 50 / 60 Hz or 208 / 400 / 480 VAC, three phases, 50 / 60 Hz Output voltage: 12 / 24 / 48 / 60 / 72 /
More informationProcess controller Setpoint programmer 1/16 DIN - 48 x 48 mm gammadue series M5 line
BT. 2.9 M/E Process controller programmer /6 DIN - 48 x 48 mm gammadue series M line Advanced features, customizable and process adaptable High speed data aquisition and signal management. Efficent information
More informationPID Microprocessor temperature controllers CTD43 - CTD46 - CTH46
PID Microprocessor temperature controllers CTD43 - CTD46 - CTH46 Display 1. Red measurement display (or the set point for CTD 43 by pressing, indicated by a flashing decimal point). 2. Green display of
More informationType: EASY719 DC RC Article No.: 274119. Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC. Description
Type: EASY719 DC RC Article.: 274119 Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC Description 12 digital inputs (4 inputs available as analog inputs) 6 relay outputs LCD display
More informationABB i-bus KNX Switch Actuator, x-fold, 16/20 A, MDRC SA/S x.16.6.1, 2CDG 110 1xx R0011
, 2CDG 110 1xx R0011 SA/S 8.16.6.1 2CDC 071 006 S0010 The 16/20 A Switch actuators are modular installation devices in Pro M Design for installation in the distribution board. The devices are especially
More informationFLOW CALCULATOR INSTRUCTION MANUAL MESURES BAMOPHOX 759 26-06-2007 759 M1 02 E MES FLOW CALCULATOR 759-02/1
BAMOPHOX 759 E - M FLOW CALCULATOR INSTRUCTION MANUAL MESURES 22, Rue de la Voie des Bans - Z.I. de la Gare - 95100 ARGENTEUIL Tél : (33) 01 30 25 83 20 - Web : www.bamo.fr Fax : (33) 01 34 10 16 05 -
More informationUser s Manual Before using the inverter, you need to read and save the safety instructions.
User s Manual Before using the inverter, you need to read and save the safety instructions. STI SERIES (STI200, STI300, STI500, STI700, STI1000) Power Frequency Pure Sine Wave Inverter The information
More informationDigital Pressure Measuring Instrument MDR480
Description The digital panel instrument MDR480 is designed to measure, display, and monitor pressures in industrial applications. The instrument is panel mounted with a front frame dimension of 96 mm
More informationDigital input modules
8 172 TX-I/O Digital input modules TXM1.8D TXM1.16D Two fully compatible versions: TXM1.8D: 8 inputs, each with a three-color LED (green, yellow or red) TXM1.16D: As TXM1.8X, but 16 inputs, each with a
More informationHow To Control A Power Supply With A Mini Transmitter And Switch (Power Supply)
transmitter (2 wire) / switch for continuous or On/Off Control Indication, monitoring, transmitting and continuous or On/Off control in one device Output signal 4...20 ma, 2-wire for continuous control
More informationElectronic timer CT-VBS.17+18 OFF-delayed without auxiliary voltage, for DC contactors Data sheet
Characteristics Single-function OFF-delay timer for DC contactors, without auxiliary voltage Width.5 mm CDC 5 6 F3 Approvals A culus E CCC CT-VBS a Circuit diagram b Marker label Marks a CE b C-Tick Order
More informationSeries AMEPR30-AZ up to 2.5A AC-DC / DC-DC LED Driver / Converter
FEATURES: Click on Series name for product info on aimtec.com Models Single output Model Max Output Power (W) 1 AC-DC Constant Current or Constant Over temperature protection Voltage LED Driver Over current
More informationMLC 9000+ TM Maximum Productivity and Versatility for Control without Compromise!
Data Sheet Maximum Productivity and Versatility for Control without Compromise! Basic Bus Communication Module DESCRIPTION The Basic Bus Communication Module (BCM) is part of the MLC 9000+ DIN rail mount
More informationH/L = Power supply. FN = Nominal Frequency. RN = Rated value of output burden. UN = Nominal input voltage. IN = Nominal input current.
Application : The transducer RISH CON - CA/CV (Fig.1) converts a sinusoidal AC Current or AC Voltage into a load independent DC Current or a load independent DC Voltage proportional to the measured value.
More informationSYL-2372 PID TEMPERATURE CONTROLLER INSTRUCTION MANUAL Version 1.4 (May 2016)
AUBER INSTRUMENTS Instruction Manual SYL-7 PID TEMPERATURE CONTROLLER INSTRUCTION MANUAL Version 1.4 (May 16) Caution This controller is intended to control equipment under normal operating conditions.
More informationTMS TANK MANAGEMENT SYSTEM
TMS TANK MANAGEMENT SYSTEM Page 1 of 9 Operating Instructions GENERAL The Tank Management System is a bespoke design to control, monitor and accommodate efficient storage and dispensing of TMS. FUNCTIONS
More informationAnalogue Input, 4-fold, MDRC AE/S 4.1, GH Q605 0054 R0001
Analogue Input, -fold, MDRC, GH Q605 005 R0001 The analogue input is a DIN rail mounted device for insertion in the distribution board. It is connected to the EIB via the bus connecting terminal supplied.
More informationCQM1-SF200/CS1W-SF200
Safety Relay Unit ( I/O Unit Type) CQM1-SF200/CS1W-SF200 CSM_CQM1-SF200_CS1W-SF200_DS_E_2_1 A Safety Relay Unit That Functions as a I/O Unit. Less Installation Space and Wiring Required. Safety Relay Unit
More informationDC1000 Series General Purpose UNIVERSAL DIGITAL CONTROLLERS
DC1000 Series General Purpose UNIVESA DIGITA CONTOES PODUCT SPECIFICATION SHEET OVEVIEW The DC1000 family of microprocessor based controllers combine a high degree of functionality, reliability at a very
More informationABB i-bus KNX Fan Coil Actuator, MDRC FCA/S 1.1M, 2CDG 110 084 R0011
, 2CDG 110 084 R0011 2CDC 071 112 F0008 The Fan Coil Actuator is a modular installation device (MDRC) in pro M design. It is intended for installation in the distribution board on 35 mm mounting rails.
More informationProcess modules Digital input PMI for 24 V DC inputs for 120 V AC inputs
E031026 000823 Process modules Digital input PMI for inputs for 120 V AC inputs PMI Input E4, E5, GND L- PMI 120 V AC Input E4, E5, Common C E6, E7, GND L- E6, E7, Common C LEDs for the inputs operation
More informationHERZ-Thermal Actuators
HERZ-Thermal Actuators Data Sheet 7708-7990, Issue 1011 Dimensions in mm 1 7710 00 1 7710 01 1 7711 18 1 7710 80 1 7710 81 1 7711 80 1 7711 81 1 7990 00 1 7980 00 1 7708 11 1 7708 10 1 7708 23 1 7709 01
More informationMILLENIUM INSTALLATION MANUAL NTR 735 A. Simple Automation Control Module (MAS)
MILLENIUM Table of contents 1. INTRODUCTION 1 2. HARDWARE DESCRIPTION 2 3. INSTALLATION 5 4. CONNECTION 6 5. USER SAFETY AND PROTECTION OF EQUIPMENT 8 1. Introduction The MILLENIUM series has been designed
More informationFeatures. Display. Measurements. Intelligent. Accuracy. Models. Installation DEIF A/S. Multi-instrument 4921210109D
7000/7000C/7020 Multi-instrument 4921210109D Features Measurements All 3-phase AC measurements True RMS Replaces analogue meters Demand on each phase current Accuracy U, I and F class 0.5 Other values
More informationEnergy Management Energy Meter Type EM23 DIN
Energy Management Energy Meter Type EM23 DIN Class 1 (kwh) according to EN62053-21 Class B (kwh) according to EN50470-3 Class 2 (kvarh) according to EN62053-23 Accuracy ±0.5 RDG (current/voltage) Energy
More informationThe E5CN provides communications or event input functionality when mounted with one of the following Option Boards.
Digital Temperature Controller Compact and Intelligent Temperature Controller Auto-tuning and self-tuning available. Can auto-tune even during execution of self-tuning Heating or heating/cooling control
More informationCPCI-3U-AC-300W-R. Rugged 300W AC Input 3U CompactPCI Power Supply. Electrical Specification for: Telkoor Part Number: 900-4602-0000
Electrical Specification for: CPCI-3U-AC-300W-R Rugged 300W AC Input 3U CompactPCI Power Supply Telkoor Part Number: 900-4602-0000 GENERAL SCALE RELEASE DATE 12/9/06 SHEET 1 OF 6 REVISION HISTORY Rev Level
More informationRM17TE 183...528 V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC
Characteristics multifunction control relay RM17-TE - range 183..528 V AC Complementary Reset time Maximum switching voltage Minimum switching current Maximum switching current [Us] rated supply voltage
More informationADM1TE 5/30A DIN rail single phase two wire energy meter
ADMTE 5/30A DIN rail single phase two wire energy meter. Safety instruction.2 Foreword.3 Performance criteria.4 Specifications.5 Basic errors.6 Description.7 Dimensions.8 Installation.9 Operating.0 Troubleshooting.
More informationPower Meter Series 700
PowerLogic power-monitoring units Power Meter Series 700 Technical data sheet 2007 Functions and characteristics E90463 The PowerLogic Power Meter Series 700 offers all the measurement capabilities required
More informationDigital inductive conductivity transmitter
Digital inductive conductivity transmitter Optimal solution for conductivity measurements in difficult fluids (polluted, dirty,...) PEEK/PPA version for CIP applications Large range of process connections
More informationABB i-bus KNX Switch Actuator, x-fold, 16 A, MDRC SA/S x.16.2.1, 2CDG1101xxR0011
Technical Data 2CDC505051D0205 ABB i-bus KNX Product description Switch Actuators SA/S x.16.2.1, 16 A are modular installation devices in ProM design for installation in the distribution board. They are
More informationHEAT MONITORING AND CONTROL INSTRUMENTS FOR TRANSFORMERS MB 103 TEMPERATURE CONTROL UNIT PT 100 TEMPERATURE SENSOR
HEAT MONITORING AND CONTROL INSTRUMENTS FOR TRANSFORMERS MB 103 TEMPERATURE CONTROL UNIT PT 100 TEMPERATURE SENSOR 2 MB 103 TRANSFORMER TEMPERATURE CONTROL UNIT WITH CONTROL SIGNAL Recent approval of new
More informationCircuit Breakers. NRC Series. NRC Series. 900 www.idec.com
Switches & Pilot Lights Display Lights NRC series circuit breakers offer circuit protection which is far superior to using fuses in applications containing relay circuits, motor circuits, heater circuits,
More informationSolid-State Timer H3G
ASH & ALAIN INDIA PVT LTD S-100, F.I.E.E., Okhla Industrial Area, Phase-ii, New Delhi-11000(India) Tel : 011-43797575 Fax : 011-43797574 E-mail : sales@ashalain.com Solid-State Timer Low-Cost, Plug-In
More informationVAQ. Built-in V-series Miniature Basic Switch for Compatibility with Business and Consumer Equipment. Pushbutton Switch (Cylindrical 10.5-dia.
Pushbutton Switch (Cylindrical 10.5-dia.) CSM DS_E_4_4 Built-in V-series Miniature Basic Switch for Compatibility with Business and Consumer Equipment Momentary operation and lock. available in six colors.
More information3. ELECTRICAL PERFORMANCE PROPERTY TEST CONDITION PERFORMANCE 3. 1 Contact Resistance 1) Center Push 100mΩ Max
1. GENERAL 1. 1 Application : This specification is applied to MULTI WAY SWITCH for electronic equipment. 1. 2 Operating Temperature Range :-25 ~ 70 1. 3 Storage Temperature Range :-0 ~ 85. However, 96
More informationVOLTAGE/CURRENT CALIBRATOR ISO-TECH ILC-421
VOLTAGE/CURRENT CALIBRATOR ISO-TECH ILC-421 TABLE OF CONTENTS 1. FEATURES... 1 2. SPECIFICATIONS... 1 2-1 General Specifications...1 2-2 Electrical Specifications... 2 3. FRONT PANEL DESCRIPTION... 4 3-1
More informationLong sensing range. Most suitable for conveyor lines and parking lot applications. 10 m 32.808 ft (Red LED)
NX SERIES Compact Multi-voltage Photoelectric Power Supply Built-in Multi-voltage photoelectric sensor usable worldwide Conforming to ow Voltage and EMC Directive Multi-voltage The NX series can operate
More informationHSP GmbH Zum Handwerkerhof 2 90530 Wendelstein Tel. 09129 / 2852-0 Fax: 09129 / 2852-11 Web: www.hsshsp.de EMAIL: HSP@hsshsp.de NTG-3000.
NTG-3000 Transducer Data Sheet Document Version 2.8 Page 1 of 10 Versions / Revisions: Document Creation Author Description version date 2.0 2012-07-25 P. Compensis First official version 2.1 2012-08-24
More informationPSU-U-24V/AC-6A/10/FTA-TR-MC PSAC 0624
PSU-U-24V/AC-6A/10/FTA-TR-MC PSAC 0624 v.1.0 AC/AC power supply unit Edition: 1 from 24 th October 2008 Supercedes edition: ---------- 10062009 CONTENTS: 1. Technical description. 1.1. General description
More informationWD-AMX Water Detection Controllers
Page 1 of 5 WD-AMX Water Detection Controllers Features: Benefit: LED Status of leak status VFC output Audible alarm Auto or manual reset alarm output Uses an isolated AC signal which prevents oxidation
More informationDuct Humidity Transmitter
SDC-H Duct Humidity Transmitter Features Replaceable sensor element Humidity measurement for air ducts Minimum and maximum value memory 0 0V, 0 0mA or 0V, 4 0mA measuring signals selectable with jumpers
More informationABB 1. Three-phase monitoring relay CM-PFS. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories. Application.
1SR 430 824 F9300 Features Monitoring of three-phase mains for phase sequence and failure Powered by the measuring circuit 2 c/o (SPDT) contacts 1 LED for status indication Approvals R: yellow LED - relay
More informationCOMPALARM AP GENERAL MAIN FEATURES
GENERAL The COMPALARM AP is a point alarm system, with as many normally closed input contacts. It givesthe possibility of selecting the alarm sequence according with 0 x 0 mm cells, fitted with ultra bright
More informationCross-beam scanning system to detect slim objects. 100 mm 3.937 in
891 Object Area Sensor General terms and conditions... F-17 Related Information Glossary of terms... P.1359~ Sensor selection guide...p.831~ General precautions... P.1405 PHOTO PHOTO Conforming to EMC
More informationHow To Read A Pipe From A Sensor
Liquid Level Sensor Installation on pipes. Sensing by means electrostatic capacity and is not influenced by the color of the pipe or liquid. Available in 8 to mm dia. and to mm dia. models to enable sensing
More informationPower Supply and Indicator Unit Type 5024-1. Fig. 1 Type 5024-1. Mounting and Operating Instructions EB 9539 EN
Power Supply and Indicator Unit Type 5024-1 Fig. 1 Type 5024-1 Mounting and Operating Instructions EB 9539 EN Edition October 2003 Application 1 Application The Type 5024-1 Power Supply and Indicator Unit
More informationMagnetic and Hydraulic-Magnetic Circuit Breaker 8340-G2...
Magnetic and Hydraulic-Magnetic Circuit Breaker 840-G2... Description Single, two and three pole magnetic circuit breakers with trip-free mechanism and push/pull on/off manual actuation. A choice of fast
More informationMultifunction devices
devices devices devices, electronic Type Page LED multifunction displays pulse, frequency, time (DC) Codix 524 240 pulse, frequency, time (AC+DC) Codix 544 243 LCD multifunction preset counters 1 or 2
More informationR4D0-FB-IA* FieldBarrier. Features. Assembly. Function. Connection IN + - S OUT ... ... Spur 2. Spur 1. Zone 1. Zone 0
FieldBarrier Features Assembly 8... 12 outputs Ex ia IIC, FISCO and Entity Advanced fault isolation and diagnostics at the spur FieldBarrier in Zone 1/Div. 2 Instruments in Zone 0...1/Div. 1 For FOUNDATION
More informationElectrical data Nominal voltage AC/DC 24 V Nominal voltage frequency
echnical data sheet NV24A--RE Communicative globe valve actuator for 2-way and 3-way globe valves Actuating force 1000 N Nominal voltage AC/DC 24 V Control Modulating DC (0)2...10 V Variable Nominal stroke
More informationCPA PC-Programmable Current/Voltage and RTD/Thermocouple Limit Alarm Trips
January 2014 Description The universal CPA PC-Programmable Alarms provide on/off control, warn of unwanted process conditions, and provide emergency shutdown. Very economical, they accept a direct signal
More informationABB i-bus EIB / KNX Analogue Input AE/S 4.2
Product Manual ABB i-bus EIB / KNX Analogue Input AE/S 4.2 Intelligent Installation Systems This manual describes the functionality of Analogue Input AE/S 4.2. Subject to changes and errors excepted. Exclusion
More informationGSM HOME SECURITY SYSTEM
Cell /Mobile phone home security system GSM HOME SECURITY SYSTEM Model : GSM-120 TABLE OF CONTENTS 1. FEATURES... 1 2. APPLICATION... 2 3. SPECIFICATIONS... 3 4. FRONT PANEL & LAYOUT DESCRIPTION...6 5.
More informationCONSTANT CURRENT REGULATOR INDUPERM TYPE CCR 951. Standarddescription of CONSTANT CURRENT REGULATOR TYPE CCR 951.
Standarddescription of TYPE CCR 951 List of contents: A. General Description B. General Data's and Functions C. CCR Working Principle D. Specifications Page 1 of 9 pages A. General Description. Induperm
More informationDALI RC BASIC SO. Control unit Operating instructions
DALI RC BASIC SO Control unit Operating instructions Contents Safety... 4 General instructions 4 Safety instructions 4 Description... 5 Purpose and application 5 Function 5 Light control 5 Brightness
More informationRadiant Temperature Sensor TY7321
AB-5361-U Specifications/Instructions Radiant Temperature TY7321 General TY7321 Radiant Temperature s are designed to measure infrared radiation from perimeter windows and walls and provide a proportional
More information650W Single Output Power Supply
AK-650 series Features : Universal AC input with active PFC Programmable output Voltage ( 0% ~ 05% ) Programmable output Current ( % ~ 05% ) High efficiency up to 9% + / 0.5A auxiliary output Intelligent
More informationEnergy Management Power Analyzer Type WM14-96 Basic Version
Energy Management Power Analyzer Type WM-96 Basic Version Optional dual pulse output Alarms (visual only) V, An Optional galvanically insulated measuring inputs Product Description 3-phase power analyzer
More informationShort information Parameters are programmed via front-side membrane keypad
Digital remote display for Flow Meter DM /DE Universal meter UZ Indication of the quantity consumed in m³ Features LED-Display 14.2mm red Indicating range -99999... 999999 0... 3 Decimal points programmable
More informationThermal-Magnetic Circuit Breaker 3120-...-M1-..
Thermal-Magnetic Circuit Breaker -...-M-.. Description Single or two pole rocker switch/thermal-magnetic circuit breaker with trip-free mechanism (S-type TM CBE to EN 34). The addition of a magnetic tripping
More informationManual Ranging MultiMeter
Owner s Manual Manual Ranging MultiMeter Model 82345 CAUTION: Read, understand and follow Safety Rules and Operating Instructions in this manual before using this product.! Safety! Operation! Maintenance!
More informationRM35UA13MW. range 15..600 V. Main. Product or component type. Relay monitored parameters
Characteristics multifunction voltage control relay RM35-U - range 15..600 V Complementary Reset time Maximum switching voltage [Us] rated supply voltage Supply voltage limits Power consumption in W Main
More informationDRM75A 230V 20/100A DIN rail single phase two wire energy meter
DRM75A 230V 20/100A DIN rail single phase two wire energy meter 1.1 Safety instruction 1.2 Foreword 1.3 Performance criteria 1.4 Specifications 1.5 Basic errors 1.6 Description 1.7 Dimensions 1.8 Installation
More informationClimasys Thermal Management System. Schneider Electric Universal Enclosures 2009
Climasys Thermal Management System Schneider Electric Universal Enclosures 2009 Schneider Electric Universal Enclosures The specialist in sealed equipment What is the mission of Schneider Electric Universal
More informationABB i-bus KNX SA/S Switch Actuators Product Manual
ABB i-bus KNX SA/S Switch Actuators Product Manual Contents Contents Page 1 General... 5 1.1 Using the product manual...5 1.1.1 Structure of the product manual...6 1.1.2 Notes...6 1.2 Product and functional
More informationSEZ220. Signal Converter. Synco 200. With preprogrammed standard applications Freely programmable Menu-driven operation. Use
s 5 146 Synco 200 Signal Converter SEZ220 With preprogrammed standard applications Freely programmable enu-driven operation Use The signal converter is for use in HVAC plant to provide minimum / maximum
More informationDCS Input/Output Relay Card Series
Input/Output Relay Card Series I/O RELAY CARD (with loopback test function) 8N The 8N series I/O Relay Cards easily and quickly standardize and facilitate installation of the relay board. Loopback test
More informationTT 49 MICROPROCESSOR-BASED DIGITAL ELECTRONIC TIMER. OPERATING INSTRUCTIONS Vr. 01 (ENG) - cod.: ISTR 06050. TECNOLOGIC S.p.A.
TT 49 MICROPROCESSOR-BASED DIGITAL ELECTRONIC TIMER INDEX..2 2 2. 2.2 2.3 3 3. 3.2 3.3 3.4 4 4. 4.2 4.3 4.4 4.5 5 5. 5.2 6 6. 6.2 7 7. 7.2 7.3 7.4 7.5 INSTRUMENT DESCRIPTION GENERAL DESCRIPTION FRONT PANEL
More informationKnow-how makes the difference. Electrical Actuators
Know-how makes the difference Electrical Actuators With Dansk Ventil Center as your business partner, you are always guaranteed a wide and well sorted product range and a unique technical know-how Product
More informationPreset Counter signo 721
Most simple handling Impressive, clearly readable display in 48x48 mm Input frequency up to 60 khz Easy installation due to pluggable terminals TECHNICAL DATA GENERAL Display Height of digits Supply voltage
More informationDS 1.102 DRTE. AIR ROOM TEMPERATURE SENSOR with fan speed control switches
DS 1.102 02/99 AIR ROOM TEMPERATURE SENSOR with fan speed control switches Specification No. 528-X-XXX* The Active Room Temperature sensor incorporating fan speed control switches is designed to give a
More informationModel: DC-A2IO Advanced HVAC Controller
Model: DC-A2IO Advanced HVAC Controller Job Name: Schedule Reference: Date: DC-A2IO Advanced HVAC Controller Package PAC-IF01 M-Net Adapter AL2-14MR-D α2 Simple Application Controller Accessories AL2-2DA
More informationPower source. Input. Contact / Open collector Voltage input (SELECTABLE) AC100-240V DC12-24V AC100-240V. Output indicator
SERIES Electronic Preset Counter Instruction Manual Please note that misuse of this device may lead to injury to the user or damage to the device. Please observe all safety precautions and warnings in
More information2. Terminal arrangement. Default (PV display) (SV display) Communication protocol selection Selects the Communication protocol. Modbus ASCII mode:
COMMUNICATION INSTRUCTION MANUAL TEMPERATURE CONTROLLER KT4, KT8 and KT9 No.KTC1E6 2009.05 To prevent accidents arising from the misuse of this controller, please ensure the operator receives this manual.
More informationDurant PGM. For Sales and Support, Contact Walker EMD Toll-free: (800) 876-4444 Tel: (203) 426-7700 Fax: (203) 426-7800 www.walkeremd.
Eclipse Series Digital Panel Meters Installation and Operation Manual Number 57700-900-05 Models: 5770X-40X - DC Volts 5770X-4X - AC Volts 5770X-42X - DC Amps 5770X-43X - AC Amps 5770X-44X - 5A AC 5770X-45X
More information