ISSUE DATE JANUARY 1ST, 2008 SECTION 3 GENERAL DETAILS
|
|
- Florence Reynolds
- 7 years ago
- Views:
Transcription
1 ISSUE DATE JANUARY 1ST, 2008 SECTION 3 GENERAL DETAILS
2 NOMINAL PIPE DIAMETER (INCHES) TABLE 1 HORIZONTAL BENDS AND ELBOWS LENGTH OF RESTRAINED JOINT PIPE (FEET) 90 BENDS 45 BENDS 22 1/2 BENDS 11 1/4 BENDS TABLE 2 TEES AND WYES NOMINAL PIPE DIAMETER OF BRANCH PIPE (IN INCHES) RESTRAINED LENGTH ALONG BRANCH PIPE (IN FEET) TABLE 3 REDUCERS NOMINAL PIPE DIAMETER LARGE END SMALL END RESTRAINED LENGTH ALONG PIPE (IN FEET) TABLE 4 DEAD ENDS & IN-LINE VALVES NOMINAL PIPE DIAMETER RESTRAINED LENGTH ALONG PIPE (IN FEET) Fittings shall be restrained joint unless otherwise noted. 2. All pipe is to be restrained in accordance with these tables or as per design criteria, whichever is greater. 3. Where two (2) or more fittings are together, restrain joints in accordance with fitting which yields greatest length of restrained pipe. 4. Provide thrust blocks in addition to specified restraints when soils exhibit plasticity or elastic properties or as directed by the Engineer and/or Charlotte County Utilities. 5. No restraints or thrust blocks will be required for bends of 7 1/2 or less. 6. Restraint tables only applicable to test pressures of 150 psi or less. 7. For pipe encased in polyethylene, increase the given values by a factor of All pipe is to be restrained in accordance with these tables or as per design criteria, whichever is greater. 9. Length of restrained pipe indicated in Tables 1 & 4 shall be the length of restrained pipe on each side of fitting/valve or as per design criteria, whichever is greater Length of restrained pipe indicated in Table 2 shall be the length of pipe restrained along branch of pipe only or as per design criteria, whichever is greater. Pipe on both sides of branch shall have a minimum laying length of 10 feet. 11. ALL TEES SHALL BE THRUST BLOCKED AND RESTRAINED: (SEE TAPPING SLEEVE, TYPICAL THRUST BLOCK ETC. DETAILS) 12. Length of restrained pipe indicated in Table 3 shall be the length of pipe restrained on large end only or as per design criteria, whichever is greater. DATE: 1/1/2008 APPROVED BY: TGD RESTRAINT TABLE PAGE No. 13 NUMBER: G-01-RT
3 LOCATOR BALL LOCATOR BALL FORCE/WATER MAINS TAPPING SLEEVE POWER POLE SERVICE LINE LOCATOR BALL POWER POLE LOCATOR BALL LOCATOR BALL 150' 150' FORCE MAIN AND WATER MAIN GRAVITY MAIN FINISHED GRADE LOCATOR BALL METALLIC LOCATION TAPE TO BE INSTALLED ON ALL MAINS 18" 22" MH R/W LINE LOCATOR BALL GRAVITY SERVICE LINE MH PROFILE VIEW PLAN VIEW 1. METALLIC LOCATION TAPE SHALL BE PLACED DIRECTLY ABOVE THE WATER/FORCE MAIN APPROXIMITELY 22" BELOW FINISHED GRADE. 2. MARKER BALLS SHALL BE 4" IN DIAMETER AS MANUFACTURED BY 3M, MODEL 1423-XR/ID FOR WATER (BLUE) AND 1424-XR/ID FOR WASTEWATER (GREEN) 1428-XR/ID FOR REUSE WATER (PURPLE). 3. BALLS ARE TO BE INSTALLED BY CONTRACTOR AT 18 INCHES BELOW FINISH GRADE ON TOP OF THE METALLIC LOCATION TAPE AND DIRECTLY ABOVE MAIN. 4. MARKERS ARE TO BE INSTALLED AT ALL CHANGE OF DIRECTIONS AND FITTINGS ABSENT OF ANY VALVE. ON STRAIGHT RUNS, MARKERS ARE TO BE INSTALLED AT EVERY POWER POLE. IF POWER POLES ARE MORE THAN 160 FEET APART OR NOT AVAILABLE, THEN PLACE MARKER BALLS EVERY 150 FEET FROM THE NEAREST CHANGE OF DIRECTION. 5. CONTRACTOR SHALL PROGRAM MARKER BALLS USING CCU TEMPLATE AND SUPPLY DATA IN AN ELECTRONIC FORMAT ie; MICROSOFT EXCEL OR ACCESS FILE, DATA CONSISTING OF THE PROGRAMED DATA IN EACH MARKER BALL, TO CHARLOTTE COUNTY UTILITIES. DATE: 1/1/2008 APPROVED BY:TD MARKER BALL AND METALLIC LOCATION TAPE INSTALLATION PAGE No. 14 NUMBER: G-02-MBL
4 DATE: 1/1/2008 APPROVED BY: TGD BUTTERFLY VALVE INSTALLATION DETAIL PAGE No. 15 NUMBER: G-03-A-BFV
5 DATE: 1/1/2008 APPROVED BY: TGD PLUG VALVE INSTALLATION PAGE No. 16 NUMBER: G-03.B-PV
6 15" VALVE BOX WITH COVER (TO BE MARKED "WATER","SEWER" OR "RECLAIMED") AND PAINTED ACCORDINGLY. FIN. GRADE 18" MAX. 6" TWO #4 BAR EACH WAY SIDE BY SIDE 36"MIN. 48''MAX. 30" SQUARE x 6" THICK CONC. SLAB TO BE CAST AROUND TOP OF BOX PSI (MIN) EXTENSION BAR WITH GUIDE (REQUIRED FOR VALVES WITH TOPS BELOW 36" BURY DEPTH) ADJUSTABLE CAST IRON VALVE BOX TOP OF PIPE WRAP VALVE WITH VISQUEEN BEFORE INSTALLING SUPPORT OR THRUST BLOCK. THRUST BLOCK (3 CU. FT. CONC.) DATE: 1/1/2008 DRAWN BY:DEC APPROVED BY: TD 1. WEDGE TO BE FULLY ENCAPSULATED IN EPDM RUBBER. 2. ALL VALVES SHALL BE INSTALLED OUTSIDE OF PAVEMENT. GATE VALVE INSTALLATION PAGE No. 17 NUMBER: G-03-C-GV
7 OTHER PIPE HORIZONTAL SEPARATION CROSSINGS JOINT CROSSINGS (FULL JOINT CENTERED) WATER MAIN STORM SEWER STORMWATER FORCE MAIN RECLAIMED WATER WATER MAIN 3 FT. MINIMUM 12 INCHES PREFERRED 6 INCHES MINIMUM - STORM SEWER ONLY ALTERNATE 3 FT. MINIMUM WATER MAIN WATER MAIN GRAVITY OR LOW PRESSURE SANITARY SEWER (1) SANITARY SEWER FORCE MAIN SEPTIC TANKS (2) WATER MAIN 10 FEET PREFERRED 6 FEET MINIMUM 12 INCHES IS THE MINIMUM, EXCEPT FOR GRAVITY SEWER, THEN 6 INCHES IS THE MINIMUM AND 12 INCHES IS PREFERRED. ALTERNATE 6 FT. MINIMUM WATER MAIN (1). 3 FEET FOR GRAVITY TYPE SANITARY SEWERS WHERE THE BOTTOM OF THE WATER MAIN IS LAID AT LEAST 6 INCHES ABOVE THE TOP OF THE GRAVITY TYPE SANITARY SEWER. (2). THE SEPARATION BETWEEN OSTDS (SEPTIC TANKS) MUST BE 10 FEET. (3). WATER MAIN SHOULD CROSS ABOVE OTHER PIPE. WHEN WATER MAIN MUST BE BELOW OTHER PIPE THE MINIMUM SEPARATION IS 18 INCHES. n.t.s. IN ACCORDANCE WITH F.A.C. RULE DATE: 1/1/2008 APPROVED BY: TD MAIN SEPARATION PAGE No. 18 NUMBER: G-04-MS
8 5' MIN FIRE HYDRANT'S SHALL NOT BE MORE THAN ONE FOOT OUTSIDE OF ROW LINE AND AT LEAST EIGHT FEET FROM CLOSEST ROAD IMPROVEMENT (PAVEMENT, GUTTER, CURB, ETC..) P.C. : 5' MIN P.C. 8' MIN P.C. WM WM WM P.C. WM WM WM WM FM FM FM FM FM FM FM CLOSEST ROAD IMPROVEMENT 5' MIN 1. (P/L) = PROPERTY LINE, EASEMENT LINE OR RIGHT OF WAY LINE 2. ALL VALVES SHALL BE PLACED AT THE FITTING UNLESS OTHERWISE APPROVED BY CCU. 3. ALL MAINS SHALL BE LOCATED A MINIMUM OF 5'-0" FROM EDGE OF ROADWAY IMPROVEMENTS (PAVEMENT, GUTTERS, CURBS ETC..) UNLESS OTHERWISE APPROVED BY CCU. 4. ALL WATER LINES SHALL BE LOCATED ON THE NORTH SIDE OF EAST-WEST STREETS AND ON THE WEST SIDE OF NORTH-SOUTH STREETS UNLESS OTHERWISE APPROVED BY CCU. 5. ALL SEWER FORCE MAINS SHALL BE LOCATED ON THE SOUTH SIDE OF EAST-WEST STREETS AND ON THE EAST SIDE OF NORTH-SOUTH STREETS UNLESS OTHERWISE APPROVED BY CCU. 6. NO VALVES SHALL BE IN PAVEMENT UNLESS OTHERWISE APPROVED BY CCU. DATE: 1/1/2008 APPROVED BY: TGD ALIGNMENT OF MAINS, VALVES, AND HYDRANTS PAGE No. 19 NUMBER: G-05-MA
9 DATE: 1/1/2008 APPROVED BY: TD TAPPING SLEEVE PAGE No. 20 NUMBER: G-06-TS
10 UNDISTURBED EARTH UNDISTURBED EARTH FORMED CONCRETE FORMED CONCRETE FORMED CONCRETE X X X X MAIN BEND PLAN BEND 6" MIN. BLANKED TEE & WYE TYPICAL TEE & WYE 6" MIN. THRUST BLOCK BEARING AREA TABLE SIZE OF PIPE TEES & PLUGS 90 BENDS 45 BENDS 22 1/2 BENDS (SQ. FT.) 11 1/4 BENDS 4" " " " " " " NOTE: 1. WRAP ALL FITTINGS WITH VISQUEEN BEFORE POURING THRUST BLOCKS. ALL THRUST BLOCKS MUST BE LEFT OPEN FOR INSPECTION BY THE ENGINEER & OWNER. 2. ALL BEARING SURFACE TO BE CARRIED TO UNDISTURBED SOIL. 3. THESE TABLES SHOW MINIMUM SIZE THRUST BLOCKS FOR GOOD SOIL WITH A 2,000 P.S.F. SOIL BEARING (A-1 THRU A-3 CLEAN SAND AND GRAVELS). 4. POOR SOIL (A-1 THRU A-8, SILTY SOILS, CLAYS, MUCK & PEAT) WILL REQUIRE LARGER THRUST BLOCKS. 5. THRUST BLOCK SIZES BASED ON 150 P.S.I. HYDROSTATIC TEST PRESSURE. 6. ALL THRUST BLOCKING TO BE 2500 PSI-28 DAY CONCRETE. 7. CONCRETE SHALL BE READY-MIXED TO ASTM C94, ALTERNATE2, NO HAND MIXING. 8. VERTICAL BENDS ONLY - 1/2" TIE RODS TO BE ANCHORED TO REACTION BLOCK AND COATED WITH 2 COATS OF BITUMINOUS EPOXY (16 MILS DRY THICKNESS). 9. VERTICAL BENDS ONLY - FORMED CONCRETE TO BE SIZED BY ENGINEER. 10. THRUST BLOCKS ARE TO BE USED IN CONJUNCTION WITH THE RESTRAINED JOINT TABLE WHEN DIRECTED BY THE ENGINEER AND/OR. 11. THRUST BLOCKS APPLY TO ALL PIPING (MECHANICAL, GLUED, ETC...) DATE: 1/1/2008 APPROVED BY: TD BEND SECTION 45 24" MIN.-12"& LARGER PIPE 18" MIN.-10"& SMALLER PIPE FORMED CONCRETE TYPICAL THRUST BLOCK DETAILS SECTION X-X ANCHOR THRUST BLOCK (VERTICAL BENDS ONLY) (SEE NOTE 8 & 9) 1/2" TIE ROD UNDISTURBED EARTH PAGE No. 21 NUMBER: G-07-THB
11 DATE: 1/1/2008 APPROVED BY: TD TYPICAL CUT-IN VALVE PAGE No. 22 NUMBER: G-07.5-CIV
12 EXISTING STORM CULVERT (IF APPLICABLE) C L PAVEMENT EXISTING STORM CULVERT (IF APPLICABLE) 3' MIN. 3' MIN. 18" MIN. 5' MIN. 5' MIN. 18" MIN. HDPE CONNECTION TO PVC/DIP SHALL BE IN ACCORDANCE WITH CHARLOTTE COUNTY UTILITIES CURRENT STANDARDS. DIRECTIONAL BORE POLYETHELENE PRESSURE PIPE, SDR 11 PE-3408 OR FUSIBLE PVC. HDPE CONNECTION TO PVC/DIP SHALL BE IN ACCORDANCE WITH CHARLOTTE COUNTY UTILITIES CURRENT STANDARDS. C L DRIVEWAY 3" MIN. 3" MIN. 3" MIN. HDPE CONNECTION TO PVC/DIP SHALL BE IN ACCORDANCE WITH CHARLOTTE COUNTY UTILITIES CURRENT STANDARDS. DIRECTIONAL BORE POLYETHELENE PRESSURE PIPE, SDR 11 PE-3408 OR FUSIBLE PVC. HDPE CONNECTION TO PVC/DIP SHALL BE IN ACCORDANCE WITH CHARLOTTE COUNTY UTILITIES CURRENT STANDARDS. 1. HDPE PIPE TO HAVE AN OUTSIDE DIAMETER EQUAL TO DUCTILE IRON PIPE. 2. BENDING FOR HDPE PIPE SHALL NOT HAVE A RADIUS LESS THAN 35'. 3. UPON APPROVAL OF THE PILOT HOLE LOCATION BY THE COUNTY, THE HOLE OPENING OR ENLARGING PHASE OF THE INSTALLATION SHALL BEGIN. THE BOREHOLE DIAMETER SHALL BE INCREASED TO ACCOMMODATE THE PULLBACK OPERATION OF THE VARIOUS DIAMETER PIPE. THE TYPE OF HOLE OPENER OR BACK REAMER TO BE UTILIZED IN THIS PHASE SHALL BE DETERMINED BY THE TYPES OF SUBSURFACE SOIL CONDITIONS. THAT HAVE BEEN ENCOUNTERED DURING THE PILOT HOLE DRILLING OPERATION. THE REAMER TYPE AND SIZE SHALL BE AT THE CONTRACTOR'S DISCRETION. A MINIMUM OF 1 PREREAMING IS REQUIRED ON PIPES OF 8" OR LARGER. 4. STATE HIGHWAY CROSSING SHALL ADHERE TO FLORIDA D.O.T. REQUIREMENTS, GENERALLY A MINIMUM OF 8 FEET BELOW ROAD SURFACE, OR A 1 FOOT DEPTH FOR EACH ONE INCH PIPE DIAMETER. 5. DIRESCTIONAL BORED FUSIBLE PVC SHALL HAVE LETTERING FACING UP IN OPEN TRENCH. DATE: 1/1/2008 APPROVED BY: TD TYPICAL DIRECTIONAL BORE PAGE No. 23 NUMBER: G-08-DB
13 R/W LINE 4' MIN. OR AS REQ'D BY DEPT. OF TRANSPORTATION OR RAILROAD FIN. GRADE OF HIGHWAY OR RAILROAD BED R/W LINE 36"MIN. C L 30" MIN. FOR RESIDENTIAL ROADS 42" MIN. FOR HIGHWAY & 66" MIN. FOR RAILROAD STEEL CASING PIPE WELD EYE-BOLT TO CASING 5/8" S.S. ALL THREAD BELL RESTRAINER (PLACE HORIZONTALLY) (TYPICAL) CARRIER PIPE CASING & CARRIER PIPE DETAIL. (SEE SECTION A-A) PLICO CASING END SEALS n.t.s. A 12" PRESSURE PIPE = 6' (TYP.) GRAVITY SEWER = 4' (TYP.) CASING & CARRIER PIPE DETAIL STEEL CASING PIPE SCHEDULE A CARRIER PIPE NOMINAL DIAMETER STEEL CASING PIPE NOMINAL DIAMETER MINIMUM WALL THICKNESS 4" 12" " 14" " 16" " 18" " 24" " 24" " 24" " 30" " 30" " 36" " 38" " 40" " & GREATER CARRIER PIPE DIA. + 8" STEEL PIPE CASING, SEE SPEC'S CARRIER PIPE CASING SPACER 1. PLACE SPACERS EQUALLY ON CENTER AND A MIN. OF 4 PER JOINT OF PIPE. 2. CARRIER PIPE WILL BE DUCTILE IRON PIPE WITH ASKETS, OR AS SPECIFIED ON THE DRAWINGS. 3. CASING PIPE SHALL BE (NEW) ASTM.A139. GRADE "A" PIPE OF A DIAMETER & THICKNESS EQUAL TO OR GREATER THAN THAT CONFORMING TO THE F.D.O.T. UTILITY ACCOMMODATION GUIDE. DATE: 1/1/2008 APPROVED BY: TD TYPICAL PIPE AND CASING PAGE No. 24 NUMBER: G-09-JBC
14 2' MIN. PIPE IS TO BE WRAPPED IN VISQUEEN TYPE PLASTIC SHEETING CONTINUOSLY 5/8" S.S. ALL THREAD CENTERED ON PIPE FIRST JOINT CLOSEST TO VALVE IS TO BE UNIFLANGE RETRAINT TIED BACK TO DEAD MAN MAIN 36" MIN. 12"MIN. UNDISTURBED EARTH 1' 4'-0" MIN. MJ VALVE (SEE DETAIL) (AS REQUIRED) 5/8" S.S. ALL THREAD MAIN 5/8" S.S. ALL THREAD DUCT-LUGS (4 REQ'D FOR 12"-16" DIA. PIPE TO BE AT 45 OFFSET) 36" MIN PSI CONCRETE 3'-0" MIN. 3'-0" MIN. : 1. DEAD MEN ARE TO BE SET PRIOR TO THE FIRST JOINT FROM A VALVE. UNLESS END-OF-LINE, THEN THERE WILL BE A TIE-BACK ASSEMBLY ON EACH SIDE OF VALVE. 2. ALL JOINTS BETWEEN CONCRETE AND VALVE SHALL BE RESTRAINED. DATE: 1/1/2008 APPROVED BY: TD TIE-BACK ASSEMBLY PAGE No. 25 NUMBER: G-11-TB
15 DATE: 1/1/2008 APPROVED BY: TGD STANDARD PRESSURE PIPE TRENCH PAGE No. 26 NUMBER: G-12-TEBFPP
16 DATE: 1/1/2008 APPROVED BY: TGD STANDARD GRAVITY SEWER PIPE TRENCH PAGE No. 27 NUMBER: G-13-TEBFGS
17 DATE: 1/1/2008 APPROVED BY: TD MANUAL AIR RELEASE PAGE No. 28 NUMBER: G-14-MAR
18 DATE: 1/1/2008 APPROVED BY: TD CRAWL GUARD ASSEMBLY PAGE No. 29 NUMBER: G-15-CGA
19 10" CAUTION BURIED XXXXX MAIN 14" 18 GA. ALUMINUM SIGN CHARLOTTE COUNTY UTILITIES CALL BEFORE DIGGING (941) ' GALV. STEEL "U-CHANNEL" 36" MIN. 18" UNDISTURBED EARTH 6" MIN. CONC. BASE SUPPORT 6" MIN. 1. ALL WATER MAIN TEXT IS TO BE BLUE IN COLOR AND ON WHITE BACKGROUND. 2. ALL SEWER MAIN TEXT IS TO BE GREEN IN COLOR AND ON WHITE BACKGROUND. 3. ALL RECLAIMED MAIN TEXT IS TO BE PURPLE IN COLOR AND ON WHITE BACKGROUND. 4. SIGN IS TO BE MOUNTED SO IT WILL NOT TURN. DATE: 1/1/2008 APPROVED BY: TD BURIED MAIN SIGN PAGE No. 30 NUMBER: G-17-BMS
20 DATE: 1/1/2008 APPROVED BY: TGD CCU PROJECT SIGN PAGE No. 31 NUMBER: G-18-PS-
21 DATE: 1/1/2008 APPROVED BY: TGD PIPE PROFILE IN SWALE PAGE No. 32 NUMBER: G-20-PPS
22 DATE: 1/1/2008 APPROVED BY: TGD CONFLICT BOX PAGE No. 33 NUMBER: G-25-CB-
23 DATE: 1/1/2008 APPROVED BY: TGD TALLY BLOCK FORMAT PAGE No. 34 NUMBER: G-45-TBT
24 DATE: 1/1/2008 APPROVED BY: TGD SEWER AIR RELEASE VALVE ASSEMBLY WITH ODOR CONTROL SYSTEM (VERTICAL PIPE LAYOUT) PAGE No. 35 NUMBER: G-46-ARV-ODOR
25 MJ FITTING PVC OR DIP MAIN MJ RESTRAINT MJ RESTRAINT HDPE MAIN n.t.s. MJ SOLID SLEEVE PVC OR DIP MAIN HDPE MAIN MJ RESTRAINT n.t.s. HDPE MAIN PVC OR DIP MAIN MJ RESTRAINT n.t.s. 1. STAINLESS STEEL STIFFENER REQUIRED WITH HDPE PIPE. DATE: 1/1/2008 APPROVED BY:TD HDPE CONNECTION TO PVC/DIP PAGE No. 36 NUMBER: G-55-HDPE-CON
26 POLYMER CONCRETE METER BOX WITH TRAFFIC BEARING LID FINAL GRADE 6" 2" BRASS NIPPLE 2" BRASS BALL VALVE WITH STAINLESS STEEL HANDLE & RUBBER COVER EPOXY OR NYLON COATED STAINLESS STEEL DOUBLE STRAP SERVICE SADDLE MAIN DATE: 1/1/2008 APPROVED BY: TGD SUBAQEOUS CROSSING TESTING POINT PAGE No. 37 NUMBER: G-19-SWTP
08003-1 WATER SERVICE 2
08003_Mar08_2011.pdf Page 1 of 7 INDEX Page 08003-1 WATER SERVICE 2 1.1 Pipe 2 1.1.1 Copper 2 1.1.2 Polyethylene 2 1.2 Valves and Fittings 2 1.2.1 Main Stops 3 1.2.2 Curb Stops 3 1.2.3 Curb Box 3 1.2.4
More informationEXHIBIT "A. Technical Specifications for Water and Sewer Service Lines
EXHIBIT "A Technical Specifications for Water and Sewer Service Lines Water and Sewer Line Bedding and Backfill: Drawings show cross-section of trench, pipe laid on top of 6" min. bedding material, bedding
More informationSANITARY SEWER SPECIFICATIONS
SANITARY SEWER SPECIFICATIONS OCTOBER 2003 HARVEST-MONROVIA WATER, SEWER, AND FIRE PROTECTION AUTHORITY SECTION 1.00 1.10 Purpose The purpose of this document is to assemble the sewer specifications, policies,
More informationSECTION 33 11 00.11 POLYVINYL CHLORIDE (PVC) PIPE
SECTION 33 11 00.11 POLYVINYL CHLORIDE (PVC) PIPE PART 1: GENERAL 1.01 SECTION INCLUDES PVC pressure pipe and fabricated fittings in nominal sizes 4-inches through 12-inches with cast iron pipe equivalent
More informationARTICLE II (2) ARTICLE II - REQUIRED USE OF PUBLIC SEWERS. PARAGRAPH 020001 Purpose and Application.
ARTICLE II - REQUIRED USE OF PUBLIC SEWERS. PARAGRAPH 020001 Purpose and Application. Article II provides rules governing the allowable connection to the City POTW and the construction and inspection of
More informationSTANDARD SPECIFICATIONS FOR PRIVATE BUILDING SEWER LINES IN PUBLIC RIGHT-OF-WAY
STANDARD SPECIFICATIONS FOR PRIVATE BUILDING SEWER LINES IN PUBLIC RIGHT-OF-WAY Approved and adopted as Official Document Number 800576 this 10th day of December, 1980 Donald R. Boyd, P.E., Director Water
More information3. Contractor shall ensure that all permits are obtained prior to any construction. Contractor shall be responsible for all utility fees.
The following shall serve as the minimum requirements for contractors performing work in relation to the Authority s potable water and sanitary sewer system(s), appurtenances and service connections. General:
More informationDIVISION 2 - SEWERAGE AND DRAINAGE SECTION 02720 - STORM DRAIN SYSTEMS PART 1 - GENERAL
DIVISION 2 - SEWERAGE AND DRAINAGE SECTION 02720 - STORM DRAIN SYSTEMS PART 1 - GENERAL 1.01 DESCRIPTION A. Furnish and install all storm drains, including manholes, inlets, service lines and other appurtenant
More informationSection 3510: Reclaimed water Pipes, Valves, and Appurtenances February 11, 2011
STANDARDS AND CONSTRUCTION MANUAL : Reclaimed water Pipes, Valves, and Appurtenances February 11, 2011 PART 1 - GENERAL 1.01 SCOPE OF WORK A. These specifications cover the pipes, fittings, and appurtenances
More informationSECTION 02720 SANITARY SEWER AND STORM DRAIN SYSTEMS
SECTION 02720 SANITARY SEWER AND STORM DRAIN SYSTEMS PART 1 GENERAL 1.01 SECTION INCLUDES A. The requirements for pipe material and installation in sewer and drainage collection systems. All materials
More informationThe checklist utilized by the Authority will be similar to that which is shown below. Project Name: Location: Consulting Engineering Firm:
Page 1 of 6 Section 1. PURPOSE This policy is an Engineering checklist of the Local Review Program for sanitary sewer improvement projects by the Bedford Regional Water Authority ( Authority ). Section
More informationSUBDRAINS AND FOOTING DRAIN COLLECTORS. A. Construct subdrains, subdrain cleanouts and outlets, and footing drain collectors.
SUBDRAINS AND FOOTING DRAIN COLLECTORS PART 1 - GENERAL 1.01 SECTION INCLUDES A. Subdrains B. Subdrain Cleanouts and Outlets C. Footing Drain Collectors D. Storm Sewer Service and Connections 1.02 DESCRIPTION
More informationSECTION 6 SANITARY SEWER MAIN 6.01 SCOPE
6.01 SCOPE The work covered by this section of the specifications consists of the furnishing of all plant, labor, materials, equipment and supervision and performing all operations involved in the construction
More informationBeacon Hill Sewer District Standard Specifications
Beacon Hill Sewer District Standard Specifications Residential Gravity Side Sewer Including Design Criteria and Standard Construction Drawings Residential Gravity Side Sewer Design Criteria 1. Provisions
More informationStandard Specifications for Installation and Repairs of Water and Sewer Service Lines
Standard Specifications for Installation and Repairs of Water and Sewer Service Lines Effective December 1, 2013 Approved /S/ Kyle Mathis Kyle Mathis City Engineer /S/ Robert Glenn Robert Glenn Water/Wastewater
More informationSECTION 603 SANITARY SEWER FORCE MAINS
SECTION 603 SANITARY SEWER FORCE MAINS 1. GENERAL Pipelines for sanitary sewer force main systems shall conform to the following specifications and shall be installed at the locations indicated on the
More informationSan Antonio Water System Standard Specifications for Construction ITEM NO. 854 SANITARY SEWER LATERALS
San Antonio Water System Standard Specifications for Construction ITEM NO. 854 SANITARY SEWER LATERALS 854.1 DESCRIPTION: This item shall govern sanitary sewer laterals installed in accordance with these
More informationSECTION 08000 STORM DRAINAGE TABLE OF CONTENTS
SECTION 08000 STORM DRAINAGE 08010 DESIGN A. Location B. Sizing TABLE OF CONTENTS 08020 MATERIALS A. Pipe Materials B. Structure Materials C. Installation D. Inlets and Outlets 08030 INSPECTIONS AND TESTING
More informationSECTION 2 POTABLE WATER SYSTEMS 2.1 GENERAL 2.2 SYSTEM DESIGN
SECTION 2 POTABLE WATER SYSTEMS 2.1 GENERAL This section sets forth the general requirements for design, installation and testing of water distribution systems for potable service and fire protection.
More informationSUMMARY OF PUBLIC WORK STANDARD SPECIFICATION REVISIONS 2016
SUMMARY OF PUBLIC WORK STANDARD SPECIFICATION REVISIONS 2016 102.5 Bid Deposits The City of Madison bid deposit form is required for all bids unless a Biennial Bid Bond is on file or check deposit is used.
More informationTown House 11265 Center Highway North Huntingdon, PA 15642
APPENDIX C SPECIFICATIONS FOR THE CONSTRUCTION OF BUILDING LATERAL SANITARY SEWERS DECEMBER 2004, INCLUDING AMENDMENTS ADOPTED ON FEBRUARY 6, 2008 AND APRIL 2, 2008; EFFECTIVE ON MAY 1, 2008 Town House
More informationDIVISION 4300 STORM DRAINAGE
DIVISION 4300 STORM DRAINAGE SECTION 4305 STORM SEWER PART 1 - GENERAL 1.01 SCOPE This section covers the construction of storm sewers for the collection and transport of stormwater runoff. 1.02 REFERENCES
More informationState of Illinois Department Of Transportation CONSTRUCTION INSPECTOR S CHECKLIST FOR STORM SEWERS
State of Illinois Department Of Transportation CONSTRUCTION INSPECTOR S CHECKLIST FOR STORM SEWERS While its use is not required, this checklist has been prepared to provide the field inspector a summary
More informationSection 2100-Trenching and Tunneling
SECTION 5200 - STORM SEWER PART 1 - GENERAL 1.01 SCOPE: This Section covers installation of storm sewer mains and culverts. Topics include permits and fees, trench widths, pipe laying, bedding, initial
More informationDESIGN AND CONSTRUCTION GUIDELINES AND STANDARDS DIVISION 33 UTILITIES 33 00 00 SITE UTILITIES
SECTION INCLUDES Domestic Water Fire Water Service Water Well Sanitary Sewer Storm Drains Foundation Drainage RELATED SECTIONS 03 30 00 Concrete 21 00 00 Fire Suppression - Sprinklers 22 00 00 Plumbing
More informationElectric Engineering Division FIBER CONDUIT RULES AND REGULATIONS
Electric Engineering Division FIBER CONDUIT RULES AND REGULATIONS TABLE OF CONTENTS I. RULES AND REGULATIONS A. TABLE OF CONTENTS... 2 B. TERMS AND DEFINITIONS... 3 C. DEVELOPER S/CONTRACTOR S RESPONSIBILITIES...
More informationEFFECTIVE FEBRUARY 2014. note: drainage permit required to call for a dampproof inspection
EFFECTIVE FEBRUARY 2014 note: drainage permit required to call for a dampproof inspection 1. ROOF DRAINS/DECK DRAINS (INTERIOR ) All roof and deck drains within the perimeter of the building shall be APPROVED
More information32-02.05 Precast Manhole Sections and Castings. These items shall conform to Section 31, "Storm Drain Installation," of these Standard Provisions.
SECTION 32: SANITARY SEWER INSTALLATION 32-01 SCOPE. The Work shall consist of furnishing and installing sewer mains, manholes, laterals, cleanout fittings and appurtenances; and testing, flushing and
More informationSECTION 02401 - SANITARY SEWER PIPE
PART 1 - GENERAL 1.1 DESCRIPTION A. The WORK under this Section includes providing all labor, materials, tools and equipment necessary for furnishing and installing sanitary sewer pipe, in accordance with
More informationSECTION 02110 - ASBESTOS CEMENT PIPE REPAIRS, DEMOLITION, AND DISPOSAL
SECTION 02110 - ASBESTOS CEMENT PIPE REPAIRS, DEMOLITION, AND DISPOSAL PART 1 - GENERAL 1.1 WORK INCLUDED IN THIS SECTION A. The WORK of this Section includes the repair, demolition, and disposal of asbestos
More informationFY08 SEWER POINT REPAIRS BID TABULATION
6-07-831 Page 1 of 12 1 FOR CLEANING AND TELEVISING EXISTING SEWERS, AS SPECIFIED, ANY REQUIRED CLEANING, ANY LOCATION, ANY LENGTH OF SEWER, COMPLETE IN PLACE, FOR VARIOUS PIPE DIAMETERS. A. EXISTING "
More informationAll work shall comply with applicable codes and ordinances. Work shall comply with the BOCA National Plumbing Code, latest edition.
DIVISION 15 MECHANICAL SECTION 15100 - PLUMBING PART 1 - GENERAL SCOPE Plumbing work includes all domestic water, gas, and sanitary sewer systems as shown on plans. Also all fixtures and equipment which
More informationFY11 Sanitary Sewer Main Rehab and Point Repair Bid Tabulation
644-10-569 Page 1 of 9 1 FOR CLEANING AND TELEVISING EXISTING SEWERS, AS SPECIFIED, ANY REQUIRED CLEANING, ANY LOCATION, ANY LENGTH OF SEWER, COMPLETE IN PLACE, FOR VARIOUS PIPE DIAMETERS. A. EXISTING
More informationSewage Compliance Form Instructions
CITY OF JOHNSTOWN DEPARTMENT OF COMMUNITY & ECONOMIC DEVELOPMENT 401 MAIN STREET ROOM 200 JOHNSTOWN, PA 15901 814-533-2017 FAX 814-539-5816 RENEE K. DALY DIRECTOR Sewage Compliance Form Instructions 1)
More informationSpecifications for Residential Property Owners Connection to New Public Sewer
Specifications for Residential Property Owners Connection to New Public Sewer Spalding Tract property owners are required to connect to the community sewer system when construction is complete and the
More informationWATER MAIN CONSTRUCTION TECHNIQUES DEPARTMENT OF PUBLIC WORKS WATER & WASTEWATER DIVISION
WATER MAIN CONSTRUCTION TECHNIQUES Overview Water Main - Materials Specifications Installation Future? Water Main Materials Material Types There are various material types used for water mains, these include:
More informationSECTION LS 2530 SANITARY SEWERS. A. General: Submit the following in accordance with The General Conditions.
SECTION LS 2530 SANITARY SEWERS PART 1 GENERAL 1.1 SUBMITTALS A. General: Submit the following in accordance with The General Conditions. 1. Product data for drainage piping specialties. 2. Shop drawings
More informationASTM C76, Class III, Wall B, except as modified herein. Clean natural sand, ASTM C33. Artificial or manufactured sand will not be permitted.
SECTION 3000 - SANITARY SEWERS 3001 SCOPE. This section applies to sanitary sewer construction and shall consist of furnishing all labor, materials, and equipment for the complete installation of sewers
More informationLS 2540 SEWER LATERALS AND INSPECTION TEES
LS 2540 SEWER LATERALS AND INSPECTION TEES A. Summary B. Submittals C. Site Information D. Sewer Pipe and Fittings E. Lateral Locations F. Lateral Installation G. Inspection Tee Installation H. Removal
More information2.0 DESIGN CRITERIA FOR WATER DISTRIBUTION SYSTEMS
2.0 DESIGN CRITERIA FOR WATER DISTRIBUTION SYSTEMS Water system improvements proposed for inclusion into Western s service area shall be designed in accordance with all appropriate AWWA standards, include
More informationINDEX. Sec. No. Items Page Nos.
INDEX Sec. No. Items Page Nos. 1. Types of Pipe............... MSSP- 2 2. Concrete Pipe............... MSSP- 2 thru MSSP-3 3. ABS and PVC Truss Pipe............... MSSP- 3 4. ABS and PVC Solid Wall Pipe...............
More informationSECTION 33 11 00.15 DUCTILE IRON PIPE AND FITTINGS
SECTION 33 11 00.15 DUCTILE IRON PIPE AND FITTINGS PART 1: GENERAL 1.01 COORDINATION OF WORK Connection to existing pipelines may require shutdown of AW facilities. Closely coordinate construction work
More informationSECTION 5 DRAFTING STANDARDS
SECTION 5 DRAFTING STANDARDS 1 SECTION FIVE TABLE OF CONTENTS Description Page TABLE OF CONTENTS... 5-2 GENERAL... 5-3 DRAFTING STANDARDS... 5-5 DRAFTING MINIMUM REQUIREMENTS HANDOUT... 5-8 2 GENERAL 1.
More informationSECTION 02400 - STORM DRAIN SYSTEM
SECTION 02400 - STORM DRAIN SYSTEM CONTENTS: Part 1 - General... 1 1.01 Work Included... 1 1.02 Related Requirements... 1 1.03 Reference Standards... 1 1.04 Quality Assurance... 1 1.05 Measurement And
More informationUtility Marking Trace Wire Guide
Manufacture product options: Utility Marking Trace Wire Guide The information provided by Copperhead Industries gives you product options to help you choose the correct wire termination points connectors
More informationSECTION 15 AIR RELEASE VALVE ASSEMBLIES. 15-1 General
SECTION 15 AIR RELEASE VALVE ASSEMBLIES 15-1.01 Scope 15-1 General This section describes the requirements for furnishing and installing Air Release Valve Assemblies of the size and type shown on the plans,
More informationLet Us Give Utilities the Respect that they Deserve.
Water & Sewer Utilities Miscellaneous Design and Plan Preparation Guidelines Issued by: Ray Mowla, P.E. Jefferson Parish Department of Engineering, Utilities Section The purpose of issuing these miscellaneous
More informationCITY OF ANN ARBOR PUBLIC SERVICES PLAN REVIEW CHECKLIST
CITY OF ANN ARBOR PUBLIC SERVICES PLAN REVIEW CHECKLIST NOTE: The following list shall only be used as a guide and shall not be used in lieu of the specifications found in the CITY OF ANN ARBOR PUBLIC
More informationSEPTIC SYSTEM CONSTRUCTION REQUIREMENTS ST. MARY S COUNTY HEALTH DEPARTMENT
SEPTIC SYSTEM CONSTRUCTION REQUIREMENTS ST. MARY S COUNTY HEALTH DEPARTMENT The following are minimum requirements for installation of conventional trench sewage disposal systems in St. Mary s County,
More informationREFER TO SPECIFICATIONS AND STANDARD PLANS FOR DETAILED WATER METER, METER VAULT, AND SERVICE LINE REQUIREMENTS
GENERAL REQUIREMENTS METER, METER VAULT, AND SERVICE LINE REFER TO SPECIFICATIONS AND STANDARD PLANS FOR DETAILED METER, METER VAULT, AND SERVICE LINE REQUIREMENTS METER & METER VAULT: 1. METER AND RADIOREAD
More information60.12. Depend-O-Lok FxE Expansion Coupling. System No. Submitted By Spec Sect Para Location Date Approved Date. DEPEND-O-LOK FxE EXPANSION COUPLING
60.1 D-O-L FxE expansion couplings are a bolted, split-sleeve design that provides for expansion and contraction at the coupled joint. These couplings are furnished with restraint rings that, when affixed
More information505.3.6 For a building with a crawl space, see Figure 10. 505-1
505 WATER SERVICE INSTALLATION 505.1 DEFINITION A service line is comprised of the piping and related appurtenances including the connection installed from the Des Moines Water Works water main to the
More informationSECTION 02630 STORM DRAINAGE SYSTEM
SECTION 02630 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes specifications for storm drainage systems including modifications and connections to existing storm drainage systems. 1.02 REFERENCE
More informationThe Manitoba Water Services Board SECTION 027030 Standard Construction Specifications September 2013 Page 1 of 21
September 2013 Page 1 of 21 Part 1 General 1.1 DESCRIPTION OF WORK.1 The work described herein shall consist of the construction of sewers including: the supply and installation of pipe, saddles, tees,
More informationA. Contractor shall furnish, to the Engineer, all materials certifications available from the manufacturer for all required materials.
PART 1 GENERAL 1.1 SCOPE A. This item shall include the work necessary for the installation of storm sewer line construction. B. Reference Section 3800 Trenching and Backfill and the General Conditions,
More informationCCU Engineering Specifications. Section 003300 PRECAST CONCRETE PRODUCTS
CCU Engineering Specifications Section 003300 Effective Date: Nov. 1st, 2011 Page 1 of 5 PRECAST CONCRETE PRODUCTS PART 1 - GENERAL The following specification is intended for use for the design, selection
More informationSECTION 02150 REMOVAL OR ABANDONMENT OF EXISTING UTILITIES AND UNDERGROUND STRUCTURES. 1. Trench excavation, backfill, and compaction; Section 02250.
02150-1 of 6 SECTION 02150 REMOVAL OR ABANDONMENT OF EXISTING 02150.01 GENERAL A. Description Removal or abandonment of existing utilities and underground structures shall include, but not necessarily
More informationCOMMERCIAL CONDUIT RULES AND REGULATION
Electric Engineering Division COMMERCIAL CONDUIT RULES AND REGULATION S:\COO_ACM_US_Electric_Telecommunications\COO_ET_Engineering\Conduit Policies\Residential 1805 NE 30th Ave., Bldg. 400 Ocala, FL 34470-4875
More informationTECHNICAL SPECIFICATION
THOMAS - G-FLEX GFLEX TECH SPEC CONNECTING INNOVATION JOHANNESBURG TEL: +27 11 794 7594 CAPE TOWN TEL: +27 21 556 5258 POLOKWANE TEL: 015 298 9142 DESIGNER, MANUFACTURER AND DISTRIBUTOR OF PIPE CONNECTION,
More informationMANUAL FOR THE DESIGN OF WATER AND SEWER LINES
SECTION I: GENERAL PROVISIONS 1.01 This manual is intended to aid and assist engineers in the layout and design of sanitary sewers and water lines to definite standards and to obtain uniformity in the
More informationSpecial Specification 7021 Water Main and Sewer Line Replacements
Special Specification 7021 Water Main and Sewer Line Replacements 1. DESCRIPTION Furnish, install, or replace water pipe, water valves, water meters and boxes, water service connections, fire hydrant assemblies,
More information2013 Edition. Flanged fittings 30"-64" NSF. industrial Applications, water & Wastewater. Certified to ANSI/NSF 61
30"-64" Ductile Iron industrial Applications, water & Wastewater 2 Table of Contents Flanged Fittings for Water 3 Flange Details 5 Flanged Fittings 6 90º and 45º Bend 6 22-1/2º and 11-1/4º Bends 7 Tees
More informationSECTION 5: SANITARY SEWER SYSTEM DESIGN
SECTION 5: SANITARY SEWER SYSTEM DESIGN 5.01 GENERAL Sanitary sewer improvements shall be designed to serve the ultimate level of City development as defined in the General Plan and the Wastewater Facilities
More informationWastewater Capital Projects Management Standard Construction Specification
CITY AND COUNTY OF DENVER ENGINEERING DIVISION Wastewater Capital Projects Management Standard Construction Specification 10.1 Precast Concrete Pipe 10.1.1 General This section covers material requirements,
More informationSECTION 15076 CEMENT-MORTAR LINED AND COATED STEEL PIPE
SECTION 15076 CEMENT-MORTAR LINED AND COATED (CML&C) STEEL PIPE PART 1 GENERAL 1.01 DESCRIPTION This section designates the requirements for steel pipe fabrication, test in shop, installation of steel
More informationSECTION 55 PIPE FOR STORM DRAINS AND CULVERTS (FAA D-701)
SECTION 55 PIPE FOR STORM DRAINS AND CULVERTS (FAA D-701) 55-1 GENERAL The Contractor shall perform all work required by the plans for construction of pipe for storm drains, precast polymer trench drains
More informationSECTION 06000 WATER DISTRIBUTION SYSTEMS TABLE OF CONTENTS
SECTION 06000 WATER DISTRIBUTION SYSTEMS TABLE OF CONTENTS 06010 WATER DISTRIBUTION PIPE A. Design B. Materials C. Installation 06020 FIRE PROTECTION A. Fire Hydrants B. Automatic Fire Sprinkler Systems
More informationSECTION 15105 DUCTILE IRON PIPE AND FITTINGS
SECTION 15105 DUCTILE IRON PIPE AND FITTINGS PART 1 GENERAL.01 COORDINATION OF WORK Connection to existing pipelines may require shutdown of Owner facilities. Closely coordinate construction work and connections
More information3A-1---------------------------------General Information A. Concepts... 1 B. Conditions... 1
Statewide Urban Design and Specifications Table of Contents Design Manual Chapter 3 Sanitary Sewers Table of Contents TOC Chapter 3 Sanitary Sewers 3A General Information 3A-1---------------------------------General
More informationGas Meter Clearances and Service Installation Requirements
March 2016 Gas Meter Clearances and Service Installation Requirements Builder/Owner/Developer Requirements Call PSE's Customer Construction Services 1 888 321 7779 or visit PSE.com/CustomerConstruction
More informationSECTION 15125 HIGH DENSITY POLYETHYLENE (HDPE) PIPE AND FITTINGS FOR WATER DISTRIBUTION AND TRANSMISSION
SECTION 15125 HIGH DENSITY POLYETHYLENE (HDPE) PIPE AND FITTINGS FOR WATER DISTRIBUTION AND TRANSMISSION PART 1 GENERAL.01 SECTION INCLUDES Furnishing and installing 4 inch through 16 inch high density
More informationSECTION 3 SANITARY SEWER DESIGN
SECTION 3 SANITARY SEWER DESIGN 3.1 GENERAL DESIGN CRITERIA 3.1.1 Requirement for Sanitary Sewer 3.1.2 Design Approval 3.1.3 IEPA Permit Required 3.1.4 Differentiation Between Public and Private Sanitary
More informationLouisiana Administrative Code Title 51 Part XIII. Sewage Disposal
Louisiana Administrative Code Title 51 Part XIII. Sewage Disposal Regulations Regarding Septic Tank Installations with Field Beds/Absorption Trenches For Individual Residential Installations Chapter 3.
More informationSECTION 02732 BUILDING SEWERS. B. Connection of building sanitary drainage system to municipal sewers.
SECTION 02732 BUILDING SEWERS PART 1 GENERAL 1.01 SECTION INCLUDES A. Lateral piping, fittings, and accessories. B. Connection of building sanitary drainage system to municipal sewers. 1.02 REGULATORY
More informationWastewater Collection System Supplemental Design Standards for Capital Improvement Program Projects
Wastewater Collection System Supplemental Design Standards for Capital Improvement Program Projects March 2013 i Metropolitan Sewer District of Greater Cincinnati Wastewater Collection System Supplemental
More informationBethel Township Municipal Authority (BTMA) RESIDENTIAL SEWER CONNECTION MANUAL
155 E. Front Street (rear) Lititz, PA 17543 Phone (717) 625-1930 Fax (717) 625-1931 Bethel Township Municipal Authority (BTMA) RESIDENTIAL SEWER CONNECTION MANUAL CONSTRUCTION SPECIFICATIONS AND DETAILS
More informationCHAPTER 6 PIPELINE MATERIALS, VALVES AND APPURTENANCES
VALVES AND APPURTENANCES 6.1 PIPELINE MATERIALS All pipe, fittings, packing, jointing material, valves, and fire hydrants shall be new and conform to Section C of AWWA Standards. All pipe material, solder
More informationSTANDARD SPECIFICATIONS SECTION 02701 INSTALLATION OF GRAVITY SEWER PIPELINES. 1. Trenching, Backfilling and Compacting: 02223
STANDARD SPECIFICATIONS SECTION 02701 INSTALLATION OF GRAVITY SEWER PIPELINES PART 1 - GENERAL A. Description This section describes the installation of gravity sewer pipelines fabricated of vitrified
More informationCD i -STREETS- Detail #
-STREETS- Detail # 3000 Vertical Curb, Gutter and Sidewalk 3010 Low-Profile Curb, Gutter and Sidewalk 3020 Rolled Curb, Gutter and Sidewalk 3030 Separated Sidewalk, Curb & Gutter 3040 Sidewalk Staged Construction
More informationTABLE OF CONTENTS SECTION 500 SANITARY SEWER AND FORCE MAIN
TABLE OF CONTENTS SECTION 500 SANITARY SEWER AND FORCE MAIN Starts on Page 500 GENERAL... 2 501 MATERIALS... 2 502 CONSTRUCTION PROCEDURES... 7 503 ABANDONMENT OF EXISTING SANITARY SEWER FACILITIES...
More informationAIR RELEASE, CLEANOUT, AND SEWER MANHOLES
AIR RELEASE, CLEANOUT, AND SEWER MANHOLES **From Hartford IM BLDG(10) DESCRIPTION. This work shall consist of the construction of air release, cleanout, and sanitary sewer manholes; and the furnishing
More informationSTANDARD OPEN PATIO COVER
STANDARD OPEN PATIO COVER BUILDING & SAFETY DIVISION 201 E. LA HABRA BLVD. LA HABRA, CA 90631 62-90-9710 Call Before You Dig 1-800-227-2600 PLEASE NOTE: This information Bulletin is made available to assist
More informationAPPLICATION PROCEDURES FOR PLACEMENT OF UNDERGROUND WATER AND SEWER PIPELINES IN THE VICINITY OF TRANSPORTATION FACILITIES UNDER THE
APPLICATION PROCEDURES FOR PLACEMENT OF UNDERGROUND WATER AND SEWER PIPELINES IN THE VICINITY OF TRANSPORTATION FACILITIES UNDER THE JURISDICTION OF ALBERTA TRANSPORTATION 1.0 Application Procedures 2.0
More informationCHAPTER 11 STORM DRAINAGE
CHAPTER STORM DRAINAGE SECTION PC 0 GENERAL 0. Scope. The provisions of this chapter shall govern the materials, design, construction and installation of storm drainage. Storm water discharge shall be
More informationSECTION 33 12 19 FIRE HYDRANTS
SECTION 33 12 19 FIRE HYDRANTS PART 1: GENERAL 1.01 SCOPE A. Fire hydrants. B. Adjustment of fire hydrants and gate valves. 1.02 SUBMITTALS A. Conform to requirements of Section 01 33 00 - Submittals.
More informationNote: All dimensions are nominal. All weights are for shipping purposes only. Availability is subject to change.
CHANNEL DrAiNS Durable Designed for maximum durability and drainage, NDS Channel Drains are a proven alternative to traditional concrete drains. UV inhibitors in the grates, channel and component parts
More informationSERVICE LINE EXTENSION AND SERVICE LINE CONNECTION CONDENSED SANITARY SEWER SYSTEM INSTALLATION SPECIFICATIONS
1001 SOUTH LEECHBURG HILL LEECHBURG, PA 15656 Phone: 724-845-9355 Fax: 724-845-1186 SERVICE LINE EXTENSION AND SERVICE LINE CONNECTION CONDENSED SANITARY SEWER SYSTEM INSTALLATION SPECIFICATIONS 1. General
More informationCONTENTS. Yale University Design Standards. Underground Electrical Duct Bank. A. Summary. B. System Design and Performance Requirements
16600 Underground Electrical Duct Bank This document provides design standards only, and is not intended for use, in whole or in part, as a specification. Do not copy this information verbatim in specifications
More informationTelescoping Post Indicator Wall Post KENNEDY VALVE ISO 9000 ISO 14001
Telescoping Post Indicator Wall Post KENNEDY VALVE ISO 9000 ISO 14001 Telescoping Post Indicator 2945 A 1" SQUARE STEM 9" MAX. = 10" MIN. = 7" FIELD ADJUSTMENT INSTRUCTIONS 1. Remove the top section from
More informationWATER & SEWER CORROSIVE RESISTANT PRODUCTS
WATER & SEWER CORROSIVE RESISTANT PRODUCTS The Standard of Excellence in the Industry CASING SPACERS COUPLINGS & FLANGE COUPLING ADAPTERS REPAIR CLAMPS DUCTILE IRON SADDLES STAINLESS STEEL SADDLES TAPPING
More informationStandard Specifications For Private Sewer Laterals
BUILDING SERVICES DEPARTMENT 250 Frank H. Ogawa Plaza, 2nd Floor, Oakland, CA 94612 Inspection Services: 510.238.3443 FAX: 510.238.2263 Standard Specifications For Private Sewer Laterals APPROVED MATERIALS
More informationINDICATOR POST STYLE 2945 A TELESCOPING BARREL ASSEMBLY UL AND FM APPROVED
INDICATOR POST STYLE 2945 A TELESCOPING BARREL ASSEMBLY UL AND FM APPROVED Available in Sizes B C D E See Page 6 for Dimensions Kennedy Valve/Indicator Posts 17-1 INDICATOR POST STYLE 2945 A TELESCOPING
More informationMS-3/2009 HDPE (High Density Polyethylene) Pipe and Fittings Specification for Buried Potable Water
MS-3/2009 HDPE (High Density Polyethylene) Pipe and Fittings Specification for Buried Potable Water 105 Decker Court, Suite 825, Irving, TX 75062 P: 469-499-1044 F: 469-499-1063 www.plasticpipe.org HDPE
More informationSECTION 8 WATER SUPPLY SYSTEMS
SECTION 8 WATER SUPPLY SYSTEMS Contents Page 8-1 INTRODUCTION... 1 8-2 INTENT OF WATER SYSTEM IMPROVEMENT STANDARDS... 1 8-3 DEFINITIONS... 1 8-4 APPLICABLE STANDARDS... 1 8-5 IMPROVEMENT AND LANDSCAPE
More informationSECTION 221413 FACILITY STORM DRAINAGE PIPING
SECTION 221413 FACILITY STORM DRAINAGE PIPING PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01
More informationSECTION 33 41 13 PUBLIC STORM UTILITY DRAINAGE PIPING
SECTION 33 41 13 PUBLIC STORM PART 1 - GENERAL 1.01 SECTION INCLUDES A. Storm drainage piping, fittings, and accessories at proposed station areas and locations other than under and immediately adjacent
More informationSECTION 15410 GROUND WATER STORAGE TANKS
SECTION 15410 GROUND WATER STORAGE TANKS PART 1 GENERAL.01 SCOPE A. Section Includes Requirements for designing, fabricating, and erecting a welded steel ground storage tank..02 SYSTEM DESCRIPTION A. Design
More informationPUBLIC WORKS DESIGN, SPECIFICATIONS & PROCEDURES MANUAL LINEAR INFRASTRUCTURE
REGION OF PEEL PUBLIC WORKS DESIGN, SPECIFICATIONS & PROCEDURES MANUAL LINEAR INFRASTRUCTURE Storm Sewer Design Criteria REVISED July 2009 PUBLIC WORKS STORM SEWER DESIGN CRITERIA TABLE OF CONTENTS 1.0
More informationSECTION 16402 UNDERGROUND ELECTRIC SERVICE
SECTION 16402 UNDERGROUND ELECTRIC SERVICE PART 1 GENERAL 1.1 SUMMARY A. Description of System 1. Furnish all labor, materials, and equipment for below grade work external to buildings as required, and
More informationMobile Home Pre-Inspection Checklist
Mobile Home Pre-Inspection Checklist TWO (2) STEP INSPECTION PROCESS STEP ONE: CALL FOR THE FIRST INSPECTION WHEN THESE ITEMS ARE COMPLETE. 1. Septic tank installed and plumbing complete. (SEE PLUMBING
More information