1 Section 27 Line Insulation 270. APPLICATION OF RULE Line insulation in Sec. 27 applies to insulators for open conductor supply lines only, not communication lines or secondary duplex, triplex, or quadruplex (230C3) cables. Note 1 references Rule 243C6 (this should be Rule 243C5). Rule 243C5 states that the strength requirements in Sec. 27 apply to all grades of construction. There are not separate Grade B and Grade C strength factors for insulators. Note 2 references Rule 242E for insulation requirements of neutral conductors. Rule 242E states that supply neutrals, which are effectively grounded and not located above supply conductors of more than 750 V to ground, do not need to meet any insulation requirements. Even though effectively grounded neutrals do not need to meet any insulation requirements, it is common to see neutral conductors attached to insulators for support and termination purposes. Section 27 does not apply to secondary duplex, triplex, and quadruplex (230C3) cables, however, it is common to see the messengers of these cables attached to insulators for support and termination purposes. The Code rules related to the application of line insulation are outlined in Fig MATERIAL AND MARKING Supply circuit insulators are required to be wet-process porcelain or other materials. Examples of insulators made of porcelain and other materials are shown in Fig
2 320 OVERHEAD LINES Rule 272 Fig Application of line insulation (Rule 270). The manufacturers must mark insulators for use at or above 2.3 kv with the manufacturer name or trademark and an identification (e.g., a catalog number) that will permit determination of the electrical and mechanical properties. The Code rules for marking insulators are outlined in Fig RATIO OF FLASHOVER TO PUNCTURE VOLTAGE Rule 272 requires insulators to meet standards for a flashover to puncture voltage ratio. A list of applicable standards is provided. When a standard does not exist for the flashover to puncture voltage ratio, Rule 272 specifies a not-to-exceed value of 75 percent with an exception that permits not more than 80 percent in areas of high atmospheric contamination. The flashover to puncture voltage ratio is used by manufacturers but it is not always published in insulator catalog data. Insulator catalog data typically does include the low-frequency dry-flashover value.
3 Rule 273 LINE INSULATION 321 Fig Examples of insulators made of porcelain or other materials (Rule 271) INSULATION LEVEL Rule 273 specifies insulator dry flashover voltages in NESC Table The dry flashover tests must be done in accordance with ANSI Standard C29.1. Using dry flashover voltage ratings lower than the values in NESC Table requires a qualified engineering study. Values higher than shown in NESC Table must be used for areas with severe lightning, high atmospheric contamination (e.g., salt water fog, industrial plant pollution, etc.) or other unfavorable circumstances. The low-frequency dry flashover rating is the most common value referenced when comparing insulator specifications. Additional ratings are commonly published in insulator catalog sheets and in insulator specifications. Typical insulator ratings are listed in Fig In addition to electrical ratings, the NESC specifies mechanical ratings for insulators in Rule 277.
4 322 OVERHEAD LINES Rule 274 Fig Marking of insulators (Rule 271). Fig Insulation level requirements (Rule 273) FACTORY TESTS Insulator factory tests per ANSI Standards are required for insulators at or above 2.3 kv SPECIAL INSULATOR APPLICATIONS Special consideration must be given to constant-current circuits (e.g., series street lighting). The voltage rating of the insulator must be based on the full load rated voltage of the supply transformer, not just the operating voltage of the circuit.
5 Rule 277 LINE INSULATION 323 Single-phase lines fed from three-phase lines are required to use insulators based on the three-phase line phase-to-phase voltages. See Fig NUMBER 276 NOT USED IN THIS EDITION 277. MECHANICAL STRENGTH OF INSULATORS Rule 277 specifies the mechanical strength requirements for insulators. This is done in the form of strength factors that are applied to the insulators. Overload factors for wire tension, wire vertical (weight) loads, and wire transverse (wind) loads are not applicable. Rule 277 requires insulators to withstand the loads in Rules 250, 251, and 252. The overload factors in Rule 253 are not required and the extreme wind loads of Rule 250C are not required. Said another way, the overload factor for the loads on insulators is 1.0. The strength factor percentages provided in Rule 277 do not distinguish between Grade B and Grade C construction. After Rule 277 states that the extreme wind loads in Rule 250C are not applicable, the rule continues on requiring proper allowance for Rule 250C loads. Rule 250C only applies to structures and supported facilities more than 60 ft high. Fig Insulators of singe-phase circuits connected to three-phase circuits (Rule 275).
6 324 OVERHEAD LINES Rule 278 The strength factor percentages listed in Rule 277 are of the insulator s rated ultimate strength. The method in which rated ultimate strength is calculated for various types of insulators and various insulator materials is discussed in Note 1 and Note 2. Notes 1 and 2 reference ANSI and IEEE Standards for the test method used to determine rated ultimate strength. The rated ultimate strength of an insulator may not be very clear on an insulator catalog sheet. Catalog sheets may use terms like routine test load, maximum design load, average failing load, average breaking load, or maximum working load. The insulator manufacturer should be consulted or the ANSI and IEEE Standards should be reviewed to verify that the percentages provided in Rule 277 are being applied to the insulator s rated ultimate strength as specified in Notes 1 and 2 of Rule 277. Examples of cantilever, compression, and tension loads on insulators are shown in Fig AERIAL CABLE SYSTEMS Aerial cable systems primarily consist of tree wire conductors described in Rule 230D. The insulators supporting aerial cables must meet Rule 273. The covered conductors of aerial cable systems are considered bare conductors for electrical insulation requirements. The insulators and spacers of an aerial cable system must meet Rule 277. Rule 278B2 requires that the insulating spaces used in aerial cable systems withstand the loads specified in Sec. 25. Section 25 includes Rule 253, which contains overload factors. Rule 277 does not require overload factors as Rule 277 specifies the loads in Rules 250, 251, and 252, not Rule GUY AND SPAN INSULATORS 279A. Insulators. The Code rules for the material properties of guy insulators and the electrical and mechanical strength of guy insulators are outlined in Fig The requirements for mechanical strength of a guy insulator hinge on the word required strength of the guy. Guy insulators do not require the application of strength factors like line insulators in Rule 277. Guy insulators indirectly have overload factors applied to them via the overload factors that are applied to wire tension and wind loading. See Fig Guys may be ungrounded and insulated per Rule 279A2a or grounded per Rule 215C2. The grounding methods for guys are provided in Rule 092C2. See Fig When guy insulators are installed, they must meet the physical location criteria provided in Rule 279A2b. Complex structures with multiple guyed circuits require careful application of Rule 279A2b. The Code rules related to installation of guy insulators are outlined in Fig If a guy insulator is used exclusively for the elimination of corrosion of an anchor attached to a grounded guy on an effectively grounded system, then it is
7 Rule 279A LINE INSULATION 325 Fig Examples of cantilever, compression, and tension loads on insulators (Rule 277).
8 326 OVERHEAD LINES Rule 279A Fig Properties of guy insulators (Rule 279A1). not classified as a guy insulator. Therefore, the electrical requirements (i.e., the dry flashover and wet flashover ratings) do not apply. The guy in this case is assumed to be grounded per Rule 215C2 using the grounding methods in Rule 092C2. The corrosion protection insulator must not reduce the mechanical strength of the guy. The Code is not specific in this case whether this is the required strength of the guy as stated in Rule 279A1c or the strength of the guy wire. An example of a guy insulator used exclusively for corrosion protection is shown in Fig
9 Rule 279B LINE INSULATION 327 Fig Example of the required strength of a guy insulator (Rule 279A1). Fig Use of guy insulators (Rule 279A2a). The clearance requirements between a guy insulator and energized conductors are provided in NESC Table See Rule 235E for a discussion. 279B. Span-Wire Insulators. The requirements of span-wire insulators are similar to guy insulators. Rule 274 is referenced for insulator testing. The rated ultimate strength of a span wire insulator is based on the required strength of the span wire in which it is located.
10 Fig Installation of guy insulators (Rule 279A2b). Fig Example of a guy insulator for corrosion protection (Rule 279A3). SECTION NUMBER 28 NOT USED IN THIS EDITION SECTION NUMBER 29 NOT USED IN THIS EDITION
Pole Guying More Complicated Than Meets the Eye. NRECA TechAdvantage 2014 Presented by Jason Settle, P.E. jason.settle@gdsassociates.
Pole Guying More Complicated Than Meets the Eye NRECA TechAdvantage 2014 Presented by Jason Settle, P.E. jason.settle@gdsassociates.com Pole Guying Strength of components NESC vs. RUS Guy Factor Grounding
More informationHendrix Spacer Cable
Hendrix Spacer Cable What is Spacer Cable? Covered Conductor Withstands temporary branch contact Eliminates temporary faults Protects wildlife Less clearance issues Compact Configuration Multiple Circuits
More informationDiscussion on Class I & II Terminology. IEEE PES Transformers Committee Fall Meeting 2011 Boston, MA
Discussion on Class I & II Terminology IEEE PES Transformers Committee Fall Meeting 2011 Boston, MA What is Class I & II? C57.12.00 2010 is the only document we have that defined these terms. 5.10 Insulation
More informationTransmission Silicone Insulators Line Post 69 kv to 161 kv
K-LINE INSULATORS LIMITED Catalogue T-LP Transmission Silicone Insulators Line Post 69 kv to 161 kv ISO9001 SAI GLOBAL FILE No. 000117 Transmission Silicone Insulators Line Post Today transmission lines
More informationproduces and delivers products worldwide can provide the optimal are dedicated to supplying you with superior advice and global support.
www.ppcinsulators.com The very Best. The very Best. That s what we deliver. ong od Insulators Only a company that develops, produces and delivers products worldwide can provide the optimal solution for
More informationCONSTRUCTION STANDARD ELECTRIC OPERATIONS ORGANIZATION
Page 1 of 11 ****This Standard Supercedes BECo CS2.13-2.3 & ComElectric OH Construction Manual, System Grounding Section, drawings CGND, GRDSUM, and C2**** 1.0 Bill of Materials GROUNDING AND BONDING POLE-MOUNTED
More informationPower Voltage Transformers for Air Insulated Substations. THE PROVEN POWER.
Power Voltage Transformers for Air Insulated Substations THE PROVEN POWER. Introduction Trench Power Voltage Transformers (Power VTs) combine the attributes of an inductive voltage transformer with the
More informationRequirements for the Attachment of Communication Cable Facilities on PPL Poles
Page 99 of 137 Requirements for the Attachment of Communication Cable Facilities on Replaces: URS-3002 URS-3004 URS-101C-304 A-157649 Page 100 of 137 Reference Notes for Drawings: General 1. The term communication
More informationWIRE AND CABLE ENGINEERING GUIDE
DC Hi Pot Testing Excerpt from PRYSMIAN S WIRE AND CABLE ENGINEERING GUIDE (FOR INFORMATIONAL PURPOSES ONLY) Page 1 of 6 DC HIGH POTENTIAL TESTING DC Hi-Pot testing can be applied as a withstand test (a
More informationPlease check with your local inspection authority for any additional requirements before installation.
Specifications for Residential Overhead Electric Service Installation This brochure addresses most typical residential overhead service installations. Variances for the following specifications must be
More informationDigital Energy ITI. Instrument Transformer Basic Technical Information and Application
g Digital Energy ITI Instrument Transformer Basic Technical Information and Application Table of Contents DEFINITIONS AND FUNCTIONS CONSTRUCTION FEATURES MAGNETIC CIRCUITS RATING AND RATIO CURRENT TRANSFORMER
More informationV.A PJM Design and Application of Overhead Transmission Lines 69kV and Above
V.A PJM Design and Application of Overhead Transmission Lines 69kV and Above These design criteria have been established to assure acceptable reliability of the bulk transmission system facilities. These
More informationTECHNICAL MEMORANDUM
TECHNICAL MEMORANDUM OCS Requirements TM 3.2.1 Prepared by: Signed document on file 09 July 09_ Xavier de Vimal Checked by: Signed document on file 10 July 09_ Richard Schmedes Approved by: Signed document
More information25-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp and 1250 Amp
Page 1 2015 Grounded Metal Equipment Plate Equipment Connection Bus Bar or Other Component 15 kv or 25 kv Separable Insulated Connector (elbow) Equipment Connection Power Cable Power Cable Grounded Metal
More information3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance
SPECIFICATION FOR LOW VOLTAGE SWITCHBOARD SEN I N D E X Description 10 STANDARD TECHNICAL REQUIREMENTS 11 Standards 12 General Operating Conditions 13 General Description Of Switchboard 131 Structure 132
More informationGUIDELINES FOR UTILITY INSTALLATIONS Part 1 - Wire Lines and Communications Cables
Engineering Department SEPTEMBER, 2007 GUIDELINES FOR UTILITY INSTALLATIONS Part 1 - Wire Lines and Communications Cables General Requirements This section applies to all public and private utilities,
More informationINTERNATIONAL STANDARD
INTERNATIONAL STANDARD IEC 60071-2 Third edition 1996-12 Insulation co-ordination Part 2: Application guide This English-language version is derived from the original bilingual publication by leaving out
More informationELECTRICAL ENGINEERING DESIGN CRITERIA APPENDIX F
ELECTRICAL ENGINEERING DESIGN CRITERIA APPENDIX F TABLE OF CONTENTS Appendix F - Electrical Engineering Design Criteria F.1 Introduction...F-1 F.2 Codes and Standards...F-1 F.3 Switchyard and Transformers...F-1
More informationInsulation Resistance Testing of Low Voltage Cables in the Field
Insulation Resistance Testing of Low Voltage Cables in the Field Table of Contents 1. Background...3 1.1. Before Making Measurements...3 1.2. How to Apply the Temperature Correction Factor...4 1.2.1. Calculation...4
More informationSAMPLE OF THE STUDY MATERIAL PART OF CHAPTER 3. Symmetrical Components & Faults Calculations
SAMPLE OF THE STUDY MATERIAL PART OF CHAPTER 3 3.0 Introduction Fortescue's work proves that an unbalanced system of 'n' related phasors can be resolved into 'n' systems of balanced phasors called the
More information1ZSE 2750-105 en, Rev. 8. Transformer bushings, type GOE and GOE(2) Technical guide
1ZSE 2750-105 en, Rev. 8 Transformer bushings, type GOE and GOE(2) Technical guide Original instruction The information provided in this document is intended to be general and does not cover all possible
More informationEarth Fault Detection Basics in Theory
Earth Fault Detection Basics in Theory Author: Dipl.-Ing. Ingo Kühnen Woodward Power Solutions Krefelder Weg 47 47906 Kempen, Germany Kempen, 16.04.2010 Earth_Fault_Detection_20100416.doc page 1 1. Star
More informationTHE IMPORTANCE OF HIPOT ISOLATION ON INDUSTRIAL ETHERNET SWITCHES
THE IMPORTANCE OF HIPOT ISOLATION ON INDUSTRIAL ETHERNET SWITCHES THE IMPORTANCE OF HIPOT ISOLATION ON INDUSTRIAL ETHERNET SWITCHES What is Hipot? HIPOT is the short term for high potential (high voltage).
More informationCalculating Creepage and Clearance Early Avoids Design Problems Later Homi Ahmadi
Calculating Creepage and Clearance Early Avoids Design Problems Later Homi Ahmadi One of the most common errors uncovered by product safety engineers stems from manufacturers and designers failing to fully
More informationDISTRIBUTION SYSTEMS INDEX NOV 06 SECTION 2. Detroit...2-1-5 Ann Arbor...2-1-6 Mt. Clemens...2-1-7 Port Huron...2-1-8
DISTRIBUTION SYSTEMS INDEX NOV 06 SECTION 2 Kinds and Uses of Service... 2-1-1 and 2-1-2 Wye Network Area Maps Detroit...2-1-5 Ann Arbor...2-1-6 Mt. Clemens...2-1-7 Port Huron...2-1-8 Transformer Connections
More informationHV glass suspension insulator U70BS and U70BL type Ball and socket type Standard profile
U70BS and U70BL type IEC 60305 U70BS U70BL GOST 27661 ПС70Е ПС70Е Minimum mechanical failing load kn 70 70 Minimum mechanical residual strength kn 56 56 Diameter of the insulating part, D mm 255 255 Nominal
More informationSUPPLEMENT TO SPECIFICATIONS FOR ELECTRICAL INSTALLATIONS
SUPPLEMENT TO SPECIFICATIONS FOR ELECTRICAL INSTALLATIONS PRIMARY METER POLE ELECTRIC SYSTEM BULLETIN No. 753 JUNE 1993, 2 ND PRINTING APRIL 2002 (Supersedes issue dated March 1983 and incorporates Nov.
More informationAnalysis of Pollution Impact on Potential Distribution of Suspension Type Discs Insulators in Overhead Lines
Australian Journal of Basic and Applied Sciences, 5(8): 734-742, 2011 ISSN 1991-8178 Analysis of Pollution Impact on Potential Distribution of Suspension Type Discs Insulators in Oerhead Lines R. Ebrahimi,
More informationPPS-PPQ-BT-PIAS RESIN INSULATORS FOR OIL INSULATED ELECTRICAL MACHINES
PPS-PPQ-BT-PIAS RESIN INSULATORS FOR OIL INSULATED ELECTRICAL MACHINES BUSHING WITH PLUG CONNECTION WITH OUTER CONE PPS CHARACTERISTICS The PPS bushing can be used as a fixed section for the entry of medium
More informationAerial Fibre Optics. Complete One Stop Solution for Aerial Fibre Optics. OPGW Cable and Fittings for OPGW
Complete One Stop Solution for OPGW Cable and Fittings for OPGW 53, Justice Chandra Madhav Road, Kolkata - 700020. India. Phone: 91-33-24748575 / 7565 Fax: 91-33-2476-1955 Email: sales@supremeco.com Website:
More informationGrounding of Electrical Systems NEW CODE: Grounding and Bonding
Grounding of Electrical Systems NEW CODE: Grounding and Bonding Presented By Scott Peele PE Grounding of Electrical Systems Outline Defining the Terms Why should I Ground? Types of Grounding Systems Separately
More informationUnified requirements for systems with voltages above 1 kv up to 15 kv
(1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements apply to
More informationAMP CO Plus Insert for Cat. 6 A Applications
Product Specification 108-93039 10/Mar/2011 Rev F AMP CO Plus Insert for Cat. 6 A Applications 1. SCOPE 1.1 Content This specification covers performance, tests and quality requirements for AMP* CO Plus
More informationPower transformers. Special transformers Railway
Power transformers Special transformers Railway A leader in railway systems Our compact and low-weight transformers fully comply with the customer s specifications. The products are developed together
More information100% Stator Ground Fault Detection Implementation at Hibbard Renewable Energy Center. 598 N. Buth Rd 3215 Arrowhead Rd
100% Stator Ground Fault Detection Implementation at Hibbard Renewable Energy Center Introduction Roger Hedding Steven Schoenherr, P.E. ABB Inc. Minnesota Power 598 N. Buth Rd 3215 Arrowhead Rd Dousman,
More informationMANUFACTURER S CERTIFICATE OF COMPLIANCE
s Type AC (Armored Clad) aluminum and steel interlocked metal clad 600-volt cable is produced 100% in the United States of America using accepted practices and quality assurance procedures to comply with
More informationAutoLink Three-Phase Sectionalizer Specifications. Scope. General. Applicable Standards. Operating principle
Scope This specification stipulates the minimum requirements for mechanically linked three-phase electronic sectionalizers, for use on outdoor medium voltage overhead lines of 15, 27, and 38 kv. Electronic
More informationJanuary 23, 2015. Minimum Design Standards Task Force
Minimum Transmission Design Standards for Competitive January 23, 2015 Minimum Design Standards Task Force Revision History Date or Version Number 12/17/2014 Revision IR 1/23/2015 Revision 1 Author Change
More informationDesign Test Report Veri*Lite Suspension Insulators Catalog Numbers: 405003, 405004, 405005, 405006
Design Test Report Veri*Lite Suspension s Catalog Numbers: 0003, 000, 000, 000 This design test report records the results of laboratory tests made on the Ohio Brass Veri*Lite Suspension s. Test performed
More informationDead Tank Circuit Breaker 72PM40-C Proven reliability through common platforms
Dead Tank Circuit Breaker 72PM40-C Proven reliability through common platforms ABB innovations for changing demands ABB (www.abb.com) is a leader in power and automation technologies that enables utility
More informationHyperlinks are Inactive
Prepared by: NIB/EOB PLANNING GUIDE FOR SINGLE CUSTOMER SUBSTATIONS SERVED FROM TRANSMISSION LINES 05503 Department: Electric T&D Section: T&D Engineering and Technical Support Approved by: G.O. Duru (GOD)
More informationMedium voltage insulator
Medium voltage insulator Line post insulators type R-ET Commercial designation LPI 24 N ET 1) LPI 24 L ET/5 1)2) LPI 24 L ET/6 1)2) LPI 38 L ET 1) esignation acc. to IEC 720 R 12,5 ET 125 N R 12,5 ET 125
More informationHarmonics in your electrical system
Harmonics in your electrical system What they are, how they can be harmful, and what to do about them Abstract Harmonic currents, generated by non-linear electronic loads, increase power system heat losses
More informationProduct Safety Considerations for Insulation Coordination of Low- Voltage Equipment. Scott Aldous, Compliance Engineer
Product Safety Considerations for Insulation Coordination of Low- Voltage Equipment Scott Aldous, Compliance Engineer What is Insulation Coordination? From IEC 60664-1, Edition 1.2: So what does that mean
More informationThe following table shows approximate percentage wise the
SHORT-CIRCUIT CALCULATION INTRODUCTION Designing an electrical system is easy and simple, if only the normal operation of the network is taken into consideration. However, abnormal conditions which are
More informationMiCAFIL. 1 RIP Technology. Bushings. Z. Zic 09/2003
MiCAFIL 1 RIP Technology Z. Zic 09/2003 )XQFWLRQRI+LJK9ROWDJH%XVKLQJ Uncontrolled (natural) electrical field Capacity-controlled electrical field %XVKLQJV0DLQ,QVXODWLRQ6\VWHPV 7\SH 0DLQ,QVXODWLRQ +RXVLQJFRYHU
More informationPROPER SELECTION OF CONTROL CIRCUIT TRANSFORMERS WHITE PAPER BULLETIN 1497, 1497A, AND 1497B
WHITE PAPER PROPER SELECTION OF CONTROL CIRCUIT TRANSFORMERS BULLETIN 1497, 1497A, AND 1497B CONTROL CIRCUIT TRANSFORMERS The proper selection of the control circuit transformers is important for suitable
More informationLow Voltage Products. Switches Automatic Transfer Switches
Low Voltage Products Switches Automatic Transfer Switches Growing importance of a secure power supply Standby power is an integral part of many industrial and domestic electrical systems. High energy prices,
More informationHIGH VOLTAGE SHORE CONNECTION
Guide for High Voltage Shore Connection GUIDE FOR HIGH VOLTAGE SHORE CONNECTION NOVEMBER 2011 American Bureau of Shipping Incorporated by Act of Legislature of the State of New York 1862 Copyright 2011
More informationThe electrical energy produced at the gen
300 300 Principles of Power System CHAPTER CHAPTER 12 Distribution Systems General 12.1 Distribution System 12.2 Classification of Distribution Systems 12.3 A.C. Distribution 12.4 D.C. Distribution 12.5
More informationWIRE AND CABLE ENGINEERING GUIDE
Excerpt From Prysmian s WIRE AND CABLE ENGINEERING GUIDE Page 1 of 8 CABLE TESTING Testing represents an integral part in the life of a cable. A cable will be subjected to multiple tests in its lifetime
More informationPRESTRESSED CONCRETE POLES The Solid Alternative to Wood
Prestressed Concrete Utility Poles U-1 PRESTRESSED CONCRETE S The Solid Alternative to Wood Lonestar Prestress concrete poles were developed to meet the expanding need of a supporting structure for; street,
More informationCurrent Transformers
Tyco Electronics Corporation Crompton Instruments 1610 Cobb International Parkway, Unit #4 Kennesaw, GA 30152 Tel. 770-425-8903 Fax. 770-423-7194 Current Transformers Current transformers (CT's) provide
More informationTrimming Trees Near Electric Lines. Understanding Niagara Mohawk s Role and Responsibilities
Trimming Trees Near Electric Lines Understanding Niagara Mohawk s Role and Responsibilities Staying Connected If you ve called Niagara Mohawk with a tree-trimming request, you know we ask a lot of questions.
More informationLitigation Services & Information
Litigation Services & Information Laurence "Lo" Lehman, P.E. Lehman Engineering Company Lehman Engineering has been providing engineering, design, and consulting services for electrical power systems to
More informationQUESTIONS and ANSWERS RFB 745-15-9894, Metal Clad Switchgear and Power Control Room
QUESTIONS and ANSWERS RFB 745-15-9894, Metal Clad Switchgear and Power Control Room 1) When you click on the UTHSCSA Drawing the site takes you to the E-1 drawing no other. Will there be other drawings
More informationCode of Practice Electricity transmission and distribution asset management. February 2009
Code of Practice Electricity transmission and distribution asset management February 2009 CONTENTS 1 PREFACE...4 2 APPLICATION AND OBJECTIVES...5 3 SCOPE...6 4 DEFINITIONS...7 5 DESIGN AND CONSTRUCTION...11
More informationServices. Three Phase Service
Services Primary Service vs Secondary Service Overhead vs Underground Common Service Types Three Phase Wye Closed Open Delta Corner Grounded Center Tapped Open Single Phase Three Phase Service Wye Delta
More informationNational Craft Assessment and Certification Program S P E C I F I C A T I O N S
National Craft Assessment and Certification Program S P E C I F I C A T I O N S INDUSTRIAL ELECTRICIAN V4 ELEC26_O4 Released September 2013 Focus Statement An Industrial Electrician must be able to interpret
More informationOverhead lines in Ireland
Overhead lines in Ireland The value in Cigré Jarlath Doyle Abstract The main theme of my presentation is to give a brief overview of the valuable information and influence Cigré has and is having on the
More informationNESC Update. James R. Tomaseski International Brotherhood of Electrical Workers
NESC Update James R. Tomaseski International Brotherhood of Electrical Workers NATIONAL ELECTRICAL SAFETY CODE 2017 Change Proposal Activity PART 4 Work Rules for the Operation of Electric Supply and Communications
More informationGUIDE TO THE MAINTENANCE, INSPECTION AND TESTING OF PORTABLE EQUIPMENT (ELECTRICAL APPLIANCES AND TOOLS) IN THE WORKPLACE
GUIDE TO THE MAINTENANCE, INSPECTION AND TESTING OF PORTABLE EQUIPMENT (ELECTRICAL APPLIANCES AND TOOLS) IN THE WORKPLACE ET 215:2008 ELECTRO-TECHNICAL COUNCIL OF IRELAND 2008 Page 1 of 6 Published by
More informationApplication Bulletin 103 - NEC Reference Guide for SolarBridge-Enabled AC Module Installers
9229 Waterford Centre Dr. Bldg C, Suite 110 Austin, Tx 78758 Application Bulletin 103 - NEC Reference Guide for SolarBridge-Enabled AC Module Installers Current Version: 13 AC Modules are a new product
More informationBASIC NEC CODE RULES AND DESIGN PRACTICE
BASIC NEC CODE RULES AND DESIGN PRACTICE Wire Ampacity and Size Circuit Breaker Size 1. Maximum loading for any branch circuit is 80% of rating of circuit for ampacity of wire for any load. NEC 220-2,
More informationTape Wound, Split Core and Ebony Current Transformers
Tape Wound, Split Core and Ebony Current Transformers Current Transformers Contents Page Tape Wound Measuring and Protection Current Transformers 2 6 Split Core Current Transformers 7 9 3-in-1 Current
More informationIRRIGATION PUMPING Table of Contents - Section 900
IRRIGATION PUMPING Table of Contents - Section 900 PARAGRAPH 900.1 GENERAL 1 900.2 METERING REQUIREMENTS 1 900.3 CUSTOMER S CONTROL EQUIPMENT 2 900.4 SERVICE CONDUCTOR REQUIREMENTS 2 900.5 RECOMMENDATIONS
More informationwww.klmtechgroup.com TABLE OF CONTENT
Page : 1 of 13 Project Engineering Standard www.klmtechgroup.com KLM Technology #03-12 Block Aronia, Jalan Sri Perkasa 2 Taman Tampoi Utama 81200 Johor Bahru Malaysia ELECTIRAL GROUNDING TABLE OF CONTENT
More informationRadial Distribution Test Feeders
Radial Distribution Test Feeders Distribution System Analysis Subcommittee Report Abstract: Many computer programs are available for the analysis of radial distribution feeders. In 1992 a paper was published
More informationINTERNATIONAL STANDARD
INTERNATIONAL STANDARD IEC 60076-11 First edition 2004-05 Power transformers Part 11: Dry-type transformers This English-language version is derived from the original bilingual publication by leaving out
More informationEvaluating Water-Damaged Electrical Equipment
Evaluating Water-Damaged Electrical Equipment 1 USE OF THIS PUBLICATION This publication provides information on how to evaluate electrical equipment that has been exposed to water through flooding, fire
More informationMeasurement devices Accessories for analogue and digital instruments
Accessories for analogue and digital instruments 1 2CSC96F0001 Current transformers Used to transform primary currents (max. 6000 A) into.../5 A and.../1 A low secondary currents indirectly supplying power
More informationWhen power interruptions happen.
When power interruptions happen. We know it s never a good time to have your power go out, so we work all year pruning trees and investing in our system to cut down on problems before they start. Outage
More informationCSA Z32 TESTING GUIDELINE AND PROCEDURES
PO Box 20020 Red Deer, AB T4N 6X5 Phone: 403.986.2939 Web: www.908eng.com July 9, 2012 CSA Z32 TESTING GUIDELINE AND PROCEDURES This document is intended to outline the various tests, procedures and preparations
More information..OR How To Protect your 3-Phase Equipment Investment with 3-Phase Monitors from Time Mark...
..OR How To Protect your 3-Phase Equipment Investment with 3-Phase Monitors from Time Mark... TIME MARK CORPORATION 11440 EAST PINE STREET TULSA, OK 74116 USA tel 918 438-1220 fax 918 437-7584 www.time-mark.com
More informationLEAD FREE FIREX. Interlock Armored Cables TECK90 and MC Industrial Cables. w w w. n e x a n s e n e r g y. c o m
FIREX Interlock Armored Cables TECK90 and MC Industrial Cables LEAD FREE O V E R 1 8 0 Y E A R S O F E X P E R I E N C E 866-663-9267 w w w. n e x a n s e n e r g y. c o m Interlock Armored Cables Introduction....2
More informationLOW VOLTAGE RING TYPE MEASURING CURRENT TRANSFORMERS
Specification for LOW VOLTAGE RING TYPE MEASURING CURRENT TRANSFORMERS CEYLON ELECTRICITY BOARD SRI LANKA Specification for LOW VOLTAGE RING TYPE MEASURING CURRENT TRANSFORMERS CEB Standard 027: 1998 CEYLON
More informationExploring the Necessity of the Hot Hipot Test
Exploring the Necessity of the Hot Hipot Test Introduction In an industry comprised of workers with varying electronics knowledge, a Hipot test can seem a daunting task for some. Indeed, many test operators
More informationTransformers. Special transformers Reactors products
Transformers Special transformers Reactors products Reactors Custom designed, custom built ABB Oy Transformers has extensive experience and numerous references from different reactor applications, having
More informationPG&E Transmission Interconnection Handbook. Section L3: SUBSTATION DESIGN FOR LOAD-ONLY ENTITIES AND TRANSMISSION-ONLY ENTITIES
Section L3: SUBSTATION DESIGN FOR LOAD-ONLY ENTITIES AND TRANSMISSION-ONLY ENTITIES PURPOSE This section provides substation design information for Load Entities interconnected at transmission voltage
More informationFAQs-Main switchboard design criteria
FAQs-Main switchboard design criteria Q: What is the Australian standard for main switchboards? Current Australian standard is AS/NZS 3439.1: 2002 originating from IEC 60439. The new series of standard
More informationThe Contractor shall furnish and install all shielded power cable suitable for use on this project.
Section 16122 PRIMARY POWER CABLES PART 1 GENERAL: WORK INCLUDED The Contractor shall furnish and install all shielded power cable suitable for use on this project. RELATED WORK Section 16020: Tests SUBMITTALS
More informationIndustrial Control Power Transformers
Class MT Features Epoxy-encapsulated (50 5000); Completely seals the transformer coils against moisture, dust, dirt and industrial contaminants for maximum protection in hostile and industrial environments
More informationGuide for Electric Service and Meter Installations
Guide for Electric Service and Meter Installations April 28, 2009 Preface This booklet is not intended to conflict with the National Electrical Safety Code, the National Electrical Code, or such state
More informationLow Voltage Transformers Sealed, General Purpose, Dry Type
Low Voltage Transformers Sealed, General Purpose, Dry Type Catalog 7400CT9601R4/08 08 Class 7400 CONTENTS Description..............................................Page Introduction.................................................
More informationBox and Conduit Fill Calculations
Box and Conduit Fill Calculations Volume required per conductor Conduit fill - Box sizing Table 314.16(a) : Number of conductors in box 600v, nominal or less CONDUCTORS: 1. Conductors originating outside
More informationGrounding & Bonding Why it is done And How to Install Properly
Grounding & Bonding Why it is done And How to Install Properly The technical information provided herein is to assist qualifi ed persons in planning and installing electric service to farms and residences.
More informationThis section applies to the design and installation of transformers.
ELECTRICAL: TRANSFORMERS BASIS OF DESIGN This section applies to the design and installation of transformers. Design Criteria 13.8-kV equipment shall be 15-kV class. Coordinate with short-circuit studies
More informationSubmit shop drawings for equipment provided under this section Shop drawings shall indicate:
Section 16435 - SWITCHBOARDS Introduction Part 1 - General Reference The work under this section is subject to requirements of the Contract Documents including the General Conditions, Supplementary Conditions,
More informationAdaption of Cable Accessories for Onshore and Offshore Substation
Adaption of Cable Accessories for Onshore and Offshore Substation www.pfisterer.com the power connection Impressum Editor PFISTERER Holding AG Rosenstraße 44 73650 Winterbach Phone +49 7181 7005-0 Fax
More informationCT Analyzer: Coming to the Rescue. Introduction. Equivalent Circuit. Construction. Classification of a CT. Tony Porrelli, OMICRON, UK
Presentation 09.1 CT Analyzer: Coming to the Rescue Tony Porrelli, OMICRON, UK Introduction The Current Transformer (CT) may exist for many applications but for this paper we can think about them being
More informationGates, Circuits, and Boolean Algebra
Gates, Circuits, and Boolean Algebra Computers and Electricity A gate is a device that performs a basic operation on electrical signals Gates are combined into circuits to perform more complicated tasks
More informationINTRODUCTION TO BEAMS
CHAPTER Structural Steel Design LRFD Method INTRODUCTION TO BEAMS Third Edition A. J. Clark School of Engineering Department of Civil and Environmental Engineering Part II Structural Steel Design and Analysis
More informationUGVCL/SP/591/11KV HT AB CABLE
TECHNICAL SPECIFICATION FOR 11KV AERIAL BUNCHED CABLES FOR OVERHEAD LINES (CROSSED LINKED POLYTHENE DRY GAS CURED) 1. SCOPE This specification covers requirements of XLPE insulated, 11 KV Aerial Bunched
More informationELECTRICAL SERVICE REQUIREMENTS FOR MOBILE HOME DEVELOPMENTS
Prepared by: ABB1 ELECTRICAL SERVICE REQUIREMENTS FOR MOBILE HOME DEVELOPMENTS 052521 Asset Type: Electric Metering Function: Construction Issued by: Quoc Hoang (QxH1) Date: 07-01-16 Rev. #06: This document
More informationTest Before Touch Easier Said Than Done. Ken Crawford, DuPont Kent Haggerty, Dupont
Test Before Touch Easier Said Than Done Ken Crawford, DuPont Kent Haggerty, Dupont Overview Test Before Touch (TBT) Principles Key Learnings by One Company One Method for Performing a TBT Induced Voltages
More informationSECTION 16461 DRY-TYPE TRANSFORMERS
SECTION 16461 PART 1 - GENERAL 1.1 SECTION INCLUDES A. Furnishing and installation of and testing of cast resin dry type MV/LV distribution transformer in accordance with specifications and drawings. Any
More informationVrieswijk, T & Srinivasan,A Amerongen,NL, 25 januari 2012
Theory Current Transformers Vrieswijk, T & Srinivasan,A Amerongen,NL, 25 januari 2012 Theory Current Transformers 25 januari 2012 Topics - Theory of current transformers (CTs) - Equivalent Circuit for
More informationSYNCHRONOUS MACHINE TESTING WITH MOTOR CIRCUIT ANALYSIS INSTRUMENTATION
SYNCHRONOUS MACHINE TESTING WITH MOTOR CIRCUIT ANALYSIS INSTRUMENTATION Introduction Howard W. Penrose, Ph.D., CMRP Vice President, Engineering and Reliability Services Dreisilker Electric Motors, Inc.
More informationEPM3. Phase Sequence and Motor Rotation Tester. Users Manual
EPM3 Phase Sequence and Motor Rotation Tester Users Manual 1 L1 L2 L3 2 3 A B C CAT 600V 3-PHASE TESTER 5 TEST M1 M2 BATT M3 EPM3 MOTOR ROTATION TESTER EPM3 MOTOR ROTATION DETERMINED WHILE FACING MOTOR
More informationTransformer Bushings for GIS
Transformer Bushings for GIS Oil to SF6 Connections GARIP RTKG 725-55 kv SQS certified ISO 91 / ISO 141 Bushings RIP - Technology for SF6 / Oil - Bushings In modern metal enclosed switchgear SF6 -gas is
More information