101 BASICS SERIES LEARNING MODULE 6: MEDIUM VOLTAGE POWER CIRCUIT BREAKERS. Cutler-Hammer

Size: px
Start display at page:

Download "101 BASICS SERIES LEARNING MODULE 6: MEDIUM VOLTAGE POWER CIRCUIT BREAKERS. Cutler-Hammer"

Transcription

1 101 BASICS SERIES LEARNING MODULE 6: MEDIUM VOLTAGE POWER CIRCUIT BREAKERS Cutler-Hammer

2 WELCOME Welcome to Module 6, which is about medium voltage power circuit breakers. By medium voltage, we mean a voltage range of 1000 volts to 38 kv. (Some consider 72.5 kv as the upper end of medium voltage, but we will work with 38 kv for the purpose of this training module.) FIGURE 1. FAMILY OF MEDIUM VOLTAGE VACUUM CIRCUIT BREAKERS (ANSI AND IEC TYPES) Like the other modules in this series, this one presents small, manageable sections of new material followed by a series of questions about that material. Study the material carefully, then answer the questions without referring back to what you ve just read. You are the best judge of how well you grasp the material. Review the material as often as you think necessary. The most important thing is establishing a solid foundation to build on as you move from topic to topic and module to module. A Note on Font Styles Viewing the Glossary Key points are in bold. Glossary terms are underlined and italicized the first time they appear. You may view definitions of glossary items by clicking on terms and words that are underlined and italicized in the text. You may also browse the Glossary by clicking on the Glossary bookmark in the left-hand margin. 1

3 WHAT YOU WILL LEARN We ll step through each of these topics in detail: Section TitlePage Number Introduction 3 Components 4 Frame 4 Operating Mechanism 4 Trip Unit 5 Trip Intelligence 5 Arc Extinguisher 6 Arc Extinguishing Technologies 7 Vacuum Interrupter Technology 7 Spiral Contacts 9 SF 6 Gas Technology 10 Puffer-Type SF 6 Gas Technology 11 Rotary Arc-Type SF 6 Gas Technology 12 Review 1 13 Ratings 14 Ratings and Standards Vary 14 Maximum Voltage 15 Continuous Current 15 Short Circuit Current 15 Enclosure and Mounting 16 Enclosure 16 Mounting 17 Fixed Mount 17 Drawout Mount 18 Standards 20 Helping the Customer 21 Circuit Breaker Details 21 Configuration and Accessory Details 21 Review 2 22 Glossary 23 Review Answers 26 2

4 INTRO- DUCTION To understand where the medium voltage power circuit breaker (MVPCB) fits into the scheme of things, you need to understand the basics of power distribution in an industrial environment. An industrial distribution system consists of: metering devices to measure power consumption main and branch disconnects protective devices switching devices to start and stop power flow conductors transformers Power may be distributed through various switchgear and switchboards, transformers and panelboards. The medium voltage power circuit breaker is found in switchgear assembly. A switchgear assembly controls electric power circuits. PADMOUNT TRANSFORMER SWITCHGEAR DISTRIBUTION PANELBOARD DRY TYPE TRANSFORMER SWITCHBOARD LIGHTING PANELBOARDS SAFETY SWITCHES ENCLOSED CONTROL FIGURE 2. TYPICAL INDUSTRIAL POWER DISTRIBUTION The circuit breaker is the main device the heart of the switchgear. It provides centralized control and protection of medium voltage power equipment and circuits. Its operation covers load switching, control and fault protection for generators, motors, transformers, capacitors and all types of feeder circuits. This type of power equipment is normally found in industrial, commercial and electric utility installations. Typical applications include electric utility systems, industrial distribution systems, commercial buildings, municipal pumping stations, and transportation systems. 3

5 COMPO- NENTS There are four main parts to a medium voltage power circuit breaker. These are: Frame Operating Mechanism Trip Unit Arc Extinguisher FIGURE 3. TYPICAL MEDIUM VOLTAGE VACUUM CIRCUIT BREAKER WITH FRONT COVER REMOVED, EXPOSING OPERATING MECHANISM Frame Operating Mechanism A medium voltage power circuit breaker is essentially an assembly of parts on a rugged metal frame. Depending upon factors such as ratings and interrupting method, they come in a variety of shapes, sizes and configurations. The medium voltage power circuit breaker uses a stored-energy operating mechanism to open the circuit breaker. It has a motor-charged, spring-type, storedenergy closing mechanism. Closing the breaker charges the accelerating springs. Protective relays on the control switch energize a shunt trip coil to release the accelerating springs and open the breaker. This is a trip-free design truly mechanically and electrically trip free. Breaker contacts will not touch or close onto a fault, even when a mechanical or electrical close command is issued. The manual controls are usually accessed from the front of the circuit breaker. Although medium voltage power circuit breakers are electrically operated, the closing springs can be charged manually. For more on operating mechanisms, see Module 5, Fundamentals of Circuit Breakers. 4

6 Trip Unit A trip unit is typically integral to a circuit breaker. But, the medium voltage power circuit breaker uses externally mounted trip units to provide the operational intelligence. These devices are called protective relays. The protective relays are normally wired to the circuit breaker and current transformers. They are mounted on a panel or door of the switchgear assembly. They function to detect a defective line or apparatus, as well as dangerous or undesirable system conditions. The relay energizes the trip coil of the circuit breaker to clear a fault. FIGURE 4. TYPICAL MEDIUM VOLTAGE SWITCHGEAR ASSEMBLY WITH PROTECTIVE RELAYS AND OTHER DEVICES SHOWN MOUNTED ON COMPARTMENT DOORS Trip Intelligence The protective relay intelligence devices fall into two broad categories. These are: Electromagnetic The electromagnetic protective relay has been used widely in the industry for many years, with a high degree of success. It functions to tell the circuit breaker when to operate, based on the specific relay type selected. Many different types of electromagnetic protective relays are available, and each type performs rather specific functions. Common relay types include: instantaneous overcurrent, time overcurrent and overvoltage. Because these devices are limited in scope, a number of different relays (each with different protective capabilities) must be used to provide a comprehensive protective package. 5

7 Trip Intelligence (continued) Microprocessor-Based The microprocessor-based protective relay is a multi-function device. It can provide all the features of several electromagnetic relays in one box. It is also easier to mount and wire. Overall, it is a smaller investment than an electromagnetic protective relay solution. FIGURE 5. TYPICAL MEDIUM VOLTAGE SWITCHGEAR ASSEMBLY WITH MICROPROCESSOR-BASED DEVICES SHOWN MOUNTED In most cases, only one device is required for each three-phase circuit, not one device for each phase. One of the more sophisticated microprocessorbased protective relays is capable of replacing the normal complement of three or four electromagnetic relays, as well as a number of associated meters and switches (Figure 6). FIGURE 6. TYPICAL SOPHISTICATED MICROPROCESSOR-BASED PROTECTIVE RELAY Since these are individual devices, apart from the medium voltage circuit breaker itself, there will be no further discussion of the tripping intelligence in this module. Arc Extinguisher The arc extinguisher extinguishes the arc produced when the contacts are pulled apart to interrupt current flow. The higher the voltage, the harder it is to interrupt the flow of current. There are a number of arc extinguishing technologies in use today. We will look at the most prominent types in the next section. 6

8 ARC EXTIN- GUISHING TECHNO- LOGIES Vacuum Interrupter Technology In a low voltage circuit breaker, using air or arc chutes is sufficient to extinguish an arc. In the medium voltage range, a different technology needs to be used. The main technology used today is the vacuum interrupter. The vacuum interrupter (VI) was briefly discussed in Module 5, Fundamentals of Circuit Breakers. FIGURE 7. SCHEMATIC FOR A TYPICAL VACUUM INTERRUPTER Basically, the vacuum interrupter is a pair of separable contacts (called primary contacts ) enclosed in a vacuum-tight envelope. The envelope itself is a ceramic material, with a metal end plate brazed to each end. The metal plates seal the ends and provide support for the parts inside. Of the two contacts (also called electrodes ) inside, one is fixed. The other is movable, through a bellows-type connection. Various shields inside the envelope provide different types of protection to interrupter parts. Figure 8 depicts the important arcing and interruption phenomena within a vacuum. FIGURE 8. INTERRUPTION IN A VACUUM When the circuit breaker is closed, the contacts within the interrupter touch, allowing current to flow. 7

9 Vacuum Interrupter Technology (continued) When a fault occurs and interruption is required, the contacts are quickly separated and an arc forms. An arc is formed because the voltage tries to keep the current moving. FIGURE 9. ENCLOSING CONTACTS IN A VACUUM The arc burns in the metal vapor evaporated from hot spots on the contact surfaces. This metal vapor continuously leaves the contact region and recondenses on the contact surfaces and surrounding metal shield, which protects the ceramic envelope. At current zero, the arc extinguishes, contact vapor production stops, and the original vacuum condition is restored. Current zero is a point in the AC current sine wave where the value is zero. + CURRENT ZERO POINTS 0 - FIGURE 10. CURRENT ZERO POINTS IN AN AC CYCLE 8

10 Vacuum Interrupter Technology (continued) The vacuum in the envelope is considered a dielectric The dielectric strength is the maximum voltage the dielectric can withstand without breaking down. The transient recovery voltage (TRV) is the most severe waveform the interrupter will have to withstand. This is why the speed of the dielectric recovery and the strength of the dielectric inside the interrupter are critical issues for successful circuit interruption. If the dielectric does not reach sufficient strength fast enough, the arc will re-ignite. Vacuum interrupters for circuit breaker duty must be capable of interrupting currents of 12 to 50 ka (and up), at voltages up to 38 kv (Figure 11). Spiral Contacts FIGURE 11. REAR VIEW OF CIRCUIT BREAKER WITH VACUUM INTERRUPTERS INSTALLED (ONE PER PHASE) A newer technology is now being used in the vacuum interrupter. It involves using spiral-shaped copper-chrome contacts inside the vacuum tube. They provide a self-induced magnetic effect that moves the arc root around the contact periphery. This very efficient arc control method prevents hot spots, minimizing contact erosion. FIGURE 12. SPIRAL CONTACTS 9

11 SF 6 Gas Technology Another arc extinguishing technology is SF 6 (sulfur hexafluoride) technology. It is popular outside the United States. It is specifically associated with European manufacturers of medium and higher voltage circuit breakers. SF 6 technology was briefly discussed in Module 5, Fundamentals of Circuit Breakers. The main contacts are enclosed in a chamber of SF 6 gas, which happens to be a very good dielectric (Figure 13). FIGURE 13. ENCLOSING CONTACTS IN SF 6 GAS In short, this arc interruption technology results the in arc energy being used and absorbed, while the arc is simultaneously cooled. There are several SF 6 interrupter designs, but only two types will be covered here: Puffer Rotary Arc 10

12 Puffer-Type SF 6 Gas Technology The puffer-type of SF 6 interrupter is the older of the two SF 6 technologies. It is more capable but more complicated than the rotary arc-type. The interrupter is shown below in the closed position, and in the opening sequence. FIGURE 14. TYPICAL SF 6 PUFFER INTERRUPTER IN CLOSED POSITION (ON LEFT) FIGURE 15. TYPICAL SF 6 PUFFER INTERRUPTER DURING OPENING SEQUENCE: HIGH CURRENT ARC (IN CENTER), AND NEAR CURRENT ZERO (ON RIGHT) During current interruption, a piston compresses the SF 6 gas in a cylinder, all of which is enclosed in an epoxy-type enclosure. After the main current-carrying contacts part, the current transfers to the arcing contacts. Once the arcing contacts part, the SF 6 gas in the compression chamber blasts the arc through the nozzle. The heat created by the arc breaks the SF 6 molecules into fluorine and sulfur. Arc energy is absorbed and the arc is cooled. As current zero is approached, the heat energy subsides as more SF 6 gas enters the system. At current zero, the high-pressure SF 6 gas flows through the nozzle and extinguishes the arc. Compressing the SF 6 gas requires significant mechanical energy. A circuit breaker equipped with this type of technology requires a higher-energy operating mechanism than is required by an equivalent vacuum circuit breaker. In addition, this interrupter type has a large number of parts. 11

13 Rotary Arc-Type SF 6 Gas Technology Rotary arc SF 6 technology is less complicated in design than the puffer type. It has fewer parts and does not require such a high-energy operating mechanism. However, it is not effective over as wide a range of short circuit currents and voltages as the SF 6 puffer or vacuum. Suitable applications are somewhat limited. Figure 16 shows a typical SF 6 rotary arc interrupter. FIGURE 16. CROSS-SECTIONAL VIEW OF TYPICAL SF 6 ROTARY ARC INTERRUPTER As the contacts part, the arc transfers from the main contacts to an annular contact. This causes the current to switch into the coil behind it. The coil s magnetic field, produced by the load current itself, causes the arc to rotate rapidly. The arc is cooled by moving through the SF 6 gas. The SF 6 gas is normally at rest inside this interrupter. The arc s movement acts like a mixer, mixing hotter and cooler gas. This helps cool the arc. Contact erosion is also reduced due to this rapid arc movement. As current zero is approached, the dwindling arc must sustain enough speed to be lost in the SF 6 environment, in order to withstand the transient recovery voltage. (This is mentioned because the magnetic field produced by the load current causes the all important arc rotation. As the current decreases, the magnetic field decreases, and the arc rotation slows.) At current zero, the arc is cooled and extinguished. 12

14 REVIEW 1 Answer the following questions without referring to the material just presented. Begin the next section when you are confident that you understand what you ve already read. 1. The is the heart of the switchgear. 2. There are four main parts to a medium voltage power circuit breaker. These are: 3. A microprocessor-based trip intelligence is superior to an electromagnetic-based trip intelligence. In your own words, explain why. 4. Vacuum interrupters for circuit breaker duty must be capable of interrupting currents of to ka (and up), at voltages up to kv. 5. SF 6 arc extinguishing technology is popular outside the United States. The two mostly commonly used types are and. 13

15 RATINGS Ratings and Standards Vary Medium voltage power circuit breaker ratings vary in different parts of the world. As a matter of fact, medium voltage is not uniformly defined around the world. While the standard we are using in this training module defines medium voltage as 1000 volts to 72.5 kv (a commonly accepted medium voltage range in the United States, as well as other parts of the world), one foreign country considers 1000 volts and above to be high voltage. Medium voltage power circuit breaker ratings charts specify many different types of ratings. Usually, a chart indicates the ratings required by the governing standards where the circuit breaker is applied. ANSI or IEC is normally the governing standard for medium voltage power circuit breakers. ANSI is associated with U.S. standards, and IEC is associated with international standards. However, neither the standards nor the ratings charts are identical. Charts also vary from manufacturer to manufacturer (Figures 17 and 18). To give an idea of the differences, consider the following example. Breaker Type Maximum Voltage (kv rms) Continuous Current (Amps) Short Circuit Current (ka rms) 270VCP-W VCP-W VCP-W FIGURE 17. PARTIAL SAMPLE OF A MEDIUM VOLTAGE ANSI RATINGS CHART Breaker Type Voltage Class (kv rms) Normal Current (Amps) Short Circuit Current (ka rms) 240VCP-W VCP-W VCP-W FIGURE 18. PARTIAL SAMPLE OF A MEDIUM VOLTAGE IEC RATINGS CHART All of the indicated ratings are important. A number of them are merely calculations. For the sake of this discussion, we will cover only three of them. 14

16 Ratings and Standards Vary (continued) These are: Maximum Voltage Continuous Current Short Circuit Current These three ratings are common to both ANSI- and IEC-rated circuit breakers. In most instances, a grasp of these three ratings will allow you to assist a customer with a medium voltage power circuit breaker selection. Maximum Voltage This is the maximum voltage at which the breaker can operate. It is termed maximum voltage on ANSI charts and voltage class on IEC charts. The operating voltage where the circuit breaker is applied should not exceed the circuit breaker s rated maximum voltage. Typical maximum voltage ratings encountered with ANSI applications are: 4.76, 8.25, 15, 27 and 38 kv. Typical voltage classes encountered with IEC applications are: 3.6, 7.2, 12, 17.5 and 24 kv. Continuous Current This is the amount of current the breaker can carry continuously at 60 cycles without exceeding the temperature rise limit. It is termed continuous current on ANSI charts and normal current on IEC charts. This maximum rating should always be in excess of the utilization equipment rating to provide for a short-time overload capability. Typical continuous current currents encountered with ANSI applications are: 600, 1200, 2000 and 3000 amps. Typical normal currents encountered with IEC applications are: 630, 1250 and 2000 amps. Short Circuit Current This is the level of three-phase short circuit current that the circuit breaker can safely interrupt. The short circuit current is a rating at the circuit breaker s maximum voltage (ANSI) or voltage class (IEC). Typical short circuit currents encountered with ANSI applications are: 16, 29, 33, 37 and 63 ka. Typical short circuit currents encountered with IEC applications are: 16, 25, 31.5, and 40 ka. 15

17 ENCLOSURE AND MOUNTING The medium voltage power circuit breaker is always placed in a switchgear assembly. The switchgear assembly is usually referred to as a metal-clad assembly. The phrase metal-clad means that compartments within the switchgear assembly are separated by metal barriers (Figure 19). Enclosure FIGURE 19. TYPICAL MEDIUM VOLTAGE METAL-CLAD ASSEMBLY STRUCTURE WITH TWO VACUUM CIRCUIT BREAKERS (SIDE VIEW) This is different from a metal enclosed assembly, where the equipment is enclosed, but not necessarily separated by barriers. The metal enclosed assembly is typically associated with low voltage equipment. FIGURE 20. TYPICAL VACUUM SWITCHGEAR ASSEMBLY WITH ONE CIRCUIT BREAKER IN UPPER COMPARTMENT AND ONE BELOW WITH DOOR CLOSED 16

18 Mounting There are two methods for mounting a circuit breaker in the switchgear. These are: Fixed Mount Drawout Mount Fixed Mount Fixed mount circuit breakers are usually found in outdoor applications. When installed outdoors, a special type of housing must be provided to protect the equipment from the elements. This outdoor protection is provided in a number of ways. Fixed medium voltage power circuit breaker designs exist for a limited range of applications and voltages. This outdoor substation utilizes fixed medium voltage power circuit breakers to perform a series of capacitor switching functions. Each breaker must be housed in a weatherproof enclosure to protect it from the elements. IN THE WORKPLACE FIXED MEDIUM VOLTAGE POWER CIRCUIT BREAKER INSTALLED IN OUTDOOR ENCLOSURE 17

19 Drawout Mount The drawout mount (or removable) type is by far the most common medium voltage power circuit breaker in use. It is used almost exclusively through 38 kv. Prior to the introduction of vacuum designs, medium voltage power circuit breakers were much larger (Figure 21). For example, one vertical structure could accommodate one magnetic air type circuit breaker. The circuit breaker was removable; typically rolled out of the structure on wheels. FIGURE 21. TYPICAL MEDIUM VOLTAGE MAGNETIC AIR CIRCUIT BREAKER (FRONT BARRIER REMOVED) Today, medium voltage power circuit breakers are frequently small enough to be stacked two units high in one vertical compartment. The circuit breaker has three positions: DISCONNECT, TEST and CONNECT. Normally, the circuit breaker is manually pushed to the TEST position, then mechanically levered between the TEST and CONNECT positions (Figure 22). The secondary and primary electrical connections are automatically connected or disconnected as the circuit breaker is levered from one position to another. FIGURE 22. MEDIUM VOLTAGE VACUUM CIRCUIT BREAKER BEING MECHANICALLY LEVERED INTO ITS STRUCTURE 18

20 Drawout Mount (continued) Most drawout medium voltage power circuit breakers can be completely removed from their compartments onto integral extension rails (Figure 23). This feature makes the task of inspecting the circuit breaker and the compartment much simpler. FIGURE 23. MEDIUM VOLTAGE VACUUM CIRCUIT BREAKER SHOWN REMOVED FROM COMPARTMENT ON EXTENSION RAILS If the circuit breaker must be lifted from the extension rails onto the floor, integral wheels permit it to be rolled around outside of its structure. 19

21 STANDARDS The testing required and the standards that must be met by a medium voltage power circuit breaker depend on the area of the world where the circuit breaker is applied. A medium voltage power circuit breaker must meet the requirements of ANSI, IEC, IEEE and NEMA to be considered world-class (Figure 24). FIGURE 24. DOMINANT WORLDWIDE STANDARDS In addition, UL is an important consideration in certain local areas. Standards and testing to prove compliance are rather stringent. This is because of the voltage and current levels associated with medium voltage equipment under abnormal (and even normal) operating conditions. The testing goes beyond just testing the circuit breaker itself. Since a medium voltage power circuit breaker must function properly with a compatible housing, it is tested separately and in combination with the structural assembly. For this reason, most circuit breaker manufacturers are also switchgear assembly manufacturers. 20

22 HELPING THE CUSTOMER Now you should be ready to assist a customer in matching a product to an application. When you meet with the customer, conduct a short interview to obtain information in these two areas: Circuit Breaker Details Configuration and Accessory Details Circuit Breaker Details Before you can select a specific circuit breaker, get the following information from the customer: Which set of standards (ANSI or IEC) apply to the circuit breaker? What maximum voltage (ANSI) or voltage class (IEC) is required? What continuous current (ANSI) or normal current (IEC) is required? What short circuit current is required? This information alone should be enough to allow you to select an appropriate circuit breaker. However, the more information you have, the better. Configuration and Accessory Details It is also important to know how the circuit breaker is to be configured. Ask the customer these two questions: Will the circuit breaker be drawout or fix mounted? Will the circuit breaker be used indoors or outdoors? Will circuit breakers be stacked two to a vertical structure, or mounted one per structure? Medium voltage circuit breakers do not normally have a large number of accessory items. However, you should make yourself aware of anything additional the customer expects. 21

23 REVIEW 2 Answer the following questions without referring to the material just presented. 1. For each rating type, identify it as being ANSI, IEC, or both. Normal Current Short Circuit Current Maximum Voltage 2. In your own words, explain the difference between a metal-clad assembly and a metal enclosed assembly. 3. There are two methods for mounting a circuit breaker in the switchgear. These are: 4. A medium voltage power circuit breaker must meet the requirements of,, and in order to be considered world-class. 5. There are seven main questions to ask a customer when attempting to match a product to an application. Name three of them. 22

24 GLOSSARY ANSI Arc Arc Chute American National Standards Institute. It was organized to simplify and standardize production and construction. The effect generated when current is forced to be interrupted between two contacts. A component of the arc extinguisher in a low voltage circuit breaker. It elongates and cools an arc. Arc Extinguisher Circuit Breaker Continuous Current Current Transformer Current Zero Dielectric Dielectric Strength Drawout Mount Envelope Fixed Mount A component of a circuit breaker. It actually interrupts the flow of current. A reusable overcurrent protection device. After tripping to break the circuit, it can be reset to protect the circuit again. The amount of current the breaker can carry continuously at 60 cycles without exceeding the temperature rise limit, according to ANSI charts. A step-down transformer that steps down supplied current to a current usable by control components such as relays and meters. Also Zero Point. A point in the AC current sine wave where the value is zero. The insulating medium between two contacts. Typical dielectrics are air, gas, ceramic or gas and ceramic. A vacuum is the only perfect dielectric. The maximum voltage a dielectric can withstand without breaking down. A mounting type for medium voltage power circuit breakers in which the breaker can be completely removed from its compartment onto integral extension rails. Main component of a vacuum interrupter. A sealed, evacuated ceramic enclosure, with a metal end plate brazed to each end. A mounting type for medium voltage power circuit breakers in which the breakers are fixed in place. Usually found in outdoor applications. 23

25 Frame IEC IEEE Magnetic Air Type Circuit Breaker Maximum Voltage Medium Voltage Power Circuit Breaker Metal-Clad Assembly Metal-Enclosed Assembly NEMA Normal Current Operating Mechanism Panelboard A component of a medium voltage power circuit breaker. Its primary function is to provide a rigid, mechanically strong, insulated housing in which the other components are mounted. Abbreviation for International Electro-technical Commission. This organization is associated with equipment used internationally. Institute of Electrical and Electronic Engineers. A professional organization of scientists and engineers whose purpose is the advancement of engineering. A type of medium voltage power circuit breaker no longer in common use. The highest voltage at which the breaker can operate, according to ANSI charts. The operating voltage where the circuit breaker is applied should not exceed the circuit breaker s rated maximum voltage. A specific type of circuit breaker, used in a switchgear assembly, with a voltage range of 1000 volts to 38 kv. Equipment in the assembly is enclosed, and separated by metal barriers into individual compartments. Typically associated with medium voltage equipment. Equipment in the assembly is enclosed, but not necessarily separated by barriers. Typically associated with low voltage equipment. Abbreviation for National Electrical Manufacturers Association. An organization of manufacturers of electrical products. The amount of current the breaker can carry continuously at 60 cycles without exceeding the temperature rise limit, according to IEC charts. Opens and closes the contacts of a circuit breaker. A wall-mounted electrical power distribution device for use in commercial and industrial applications. It provides circuit control and overcurrent protection for light, heat or power circuits. 24

26 Protective Relay SF 6 Short Circuit Current Switchboard Switchgear Transient Recovery Voltage Trip Unit UL Vacuum Interrupter Voltage Class The specific trip unit used with a medium voltage power circuit breaker. Functions to detect a defective line or apparatus, as well as dangerous or undesirable system conditions. An arc extinguishing technology involving the use of sulfur hexafluoride gas. A rating of the level of three-phase short circuit current that the circuit breaker can safely interrupt. The short circuit current is a rating at the circuit breaker s maximum voltage (ANSI) or voltage class (IEC). A floor-standing electrical power distribution device for use in commercial and industrial applications. It divides large blocks of electrical current into smaller blocks of current used by electrical equipment. An assembly of switching and interrupting devices, along with control, metering, protective and regulating equipment. The most severe waveform the vacuum interrupter will have to withstand. The brain of a circuit breaker. Underwriters Laboratory. An independent laboratory that tests equipment to determine whether it meets certain safety standards when properly used. An arc extinguishing technology. Features a pair of separable contacts enclosed in a vacuum-tight envelope. Since the environment inside the interrupter envelope is a vacuum, an arc cannot be sustained easily. The highest voltage at which the breaker can operate, according to IEC charts. The operating voltage where the circuit breaker is applied should not exceed the circuit breaker s rated voltage class. 25

27 REVIEW 1 ANSWERS 1. Circuit breaker 2. Frame Operating Mechanism Trip Unit Arc Extinguisher 3. Answer should basically say: The microprocessor-based protective relay is a multi-function device. It can provide all the features of several electromagnetic relays in one box. It is also easier to mount and wire. Overall, it is a smaller investment than an electromagnetic protective relay solution , 50, Puffer, Rotary Arc REVIEW 2 ANSWERS 1. IEC Both ANSI 2. Answer should basically say: A metal-clad assembly has internal compartments which are separated by metal barriers. A metal enclosed assembly does not necessarily have internal separation barriers 3. Fixed mount, Drawout mount 4. ANSI, IEC, IEEE and NEMA 5. Any four of the following: Which set of standards (ANSI or IEC) apply to the circuit breaker? What maximum voltage (ANSI) or voltage class (IEC) is required? What continuous current (ANSI) or normal current (IEC) is required? What short circuit current is required? Will the circuit breaker be drawout or fix mounted? Will the circuit breaker be used indoors or outdoors? Will circuit breakers be stacked two to a vertical structure, or mounted one per structure? 26

28 Cutler-Hammer Milwaukee, Wisconsin U.S.A. Publication No. TR T.E February 1999 Printed in U.S.A. (GSP) 101 Basics Series and 201 Advanced Series are trademarks of Cutler-Hammer University, Cutler-Hammer and Eaton Corp. 1999, Eaton Corp.

101 BASICS SERIES LEARNING MODULE 3: FUNDAMENTALS OF ELECTRICAL DISTRIBUTION. Cutler-Hammer

101 BASICS SERIES LEARNING MODULE 3: FUNDAMENTALS OF ELECTRICAL DISTRIBUTION. Cutler-Hammer 101 BASICS SERIES LEARNING MODULE 3: FUNDAMENTALS OF ELECTRICAL DISTRIBUTION Cutler-Hammer WELCOME Welcome to Module 3, Fundamentals of Electrical Distribution. If you have successfully completed Module

More information

Primary and Secondary Electrical Distribution Systems

Primary and Secondary Electrical Distribution Systems Primary and Secondary Electrical Distribution Systems Critical Facilities Round Table 12th Quarterly Membership Meeting June 2, 2006 David D. Roybal. P.E. Eaton Electrical Cutler-Hammer Products Utility

More information

Secondary Unit Substations

Secondary Unit Substations 14 SWITCHGEAR Secondary Unit Substations Overview Siemens offers a wide variety of unit substation designs to meet customer requirements. A unit substation consists of one or more transformers mechanically

More information

2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1. 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.

2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1. 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. 2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. Relays) Part 1 General 1.1 CONDITIONS AND REQUIREMENTS: A. Refer to

More information

Submit shop drawings for equipment provided under this section Shop drawings shall indicate:

Submit shop drawings for equipment provided under this section Shop drawings shall indicate: Section 16435 - SWITCHBOARDS Introduction Part 1 - General Reference The work under this section is subject to requirements of the Contract Documents including the General Conditions, Supplementary Conditions,

More information

Circuit Breakers and Switchgear. Thomas Greer Director of Engineering TLG Services

Circuit Breakers and Switchgear. Thomas Greer Director of Engineering TLG Services Circuit Breakers and Switchgear Thomas Greer Director of Engineering TLG Services Presentation Outline Switchgear Definition Overcurrent Protection Devices Circuit Breaker Trip Curves and Coordination

More information

Fusible Disconnect Switch

Fusible Disconnect Switch Circuit Breakers Circuit breakers are used in panelboards and switchboards to provide circuit protection and provide a means of energizing and de-energizing a circuit. Siemens Sentron molded case circuit

More information

Section 9: Power Distribution Equipment Bill Brown, P.E., Square D Engineering Services

Section 9: Power Distribution Equipment Bill Brown, P.E., Square D Engineering Services Section 9: Power Distribution Equipment Bill Brown, P.E., Square D Engineering Services Introduction Power Distribution Equipment is a term generally used to describe any apparatus used for the generation,

More information

DATA CENTER UNIQUE CHARACTERISTICS AND THE ROLE OF MEDIUM VOLTAGE VACUUM CIRCUIT BREAKERS

DATA CENTER UNIQUE CHARACTERISTICS AND THE ROLE OF MEDIUM VOLTAGE VACUUM CIRCUIT BREAKERS DATA CENTER UNIQUE CHARACTERISTICS AND THE ROLE OF MEDIUM VOLTAGE VACUUM CIRCUIT BREAKERS ABSTRACT Data Centers are a critical part of the world economic systems. Billions of electronic transactions happen

More information

Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components

Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components Course No: E02-010 Credit: 2 PDH Boris Shvartsberg, Ph.D., P.E., P.M.P. Continuing Education

More information

101 BASICS SERIES LEARNING MODULE 19: STARTERS AND CONTACTORS. Cutler-Hammer

101 BASICS SERIES LEARNING MODULE 19: STARTERS AND CONTACTORS. Cutler-Hammer 101 BASICS SERIES LEARNING MODULE 19: STARTERS AND CONTACTORS Cutler-Hammer WELCOME Welcome to Module 19, which is about starters, devices that control the use of electrical power to equipment, usually

More information

Learning Module 13: Panelboards and Switchboards. 101 Basic Series

Learning Module 13: Panelboards and Switchboards. 101 Basic Series Learning Module 13: Panelboards and Switchboards 101 Basic Series What You Will Learn We ll step through each of these topics in detail: Introduction 4 Definitions 4 Similarities Between Panelboards and

More information

Sentron Series Circuit Breakers

Sentron Series Circuit Breakers Sentron Series Circuit Breakers Siemens Sentron Series circuit breakers are available in nine frame sizes: ED, FD, JD, LD, LMD, MD, ND, PD, and RD. Sentron Series circuit breakers have a wide range of

More information

101 BASICS SERIES LEARNING MODULE 2: FUNDAMENTALS OF ELECTRICITY. Cutler-Hammer

101 BASICS SERIES LEARNING MODULE 2: FUNDAMENTALS OF ELECTRICITY. Cutler-Hammer 101 BASICS SERIES LEARNING MODULE 2: FUNDAMENTALS OF ELECTRICITY Cutler-Hammer WELCOME Welcome to Module 2, Fundamentals of Electricity. This module will cover the fundamentals of electricity in a practical

More information

The Intelligent AX1 Switchgear for Medium Voltage

The Intelligent AX1 Switchgear for Medium Voltage The Intelligent AX1 Switchgear for Medium Voltage Leif Lundin, Manager of Research and Development, Division Medium Voltage and Compact Substations, ABB Distribution, Sweden Abstract The newly launched

More information

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation Basis of Design This section applies to the design relating to low voltage switchboards. Design Criteria UW Class N1 facilities main switchboards shall be rear accessible. The main, tie and feeder breakers

More information

Contents. Description. Product Selection Guide

Contents. Description. Product Selection Guide .1 Medium Voltage Switchgear Introduction Indoor Type VCP-W Metal-Clad Switchgear Assembly (5/15 kv shown) Product Selection Guide Product Offering Chart Metal-Enclosed Contents Description Notes Additional

More information

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4 CE - BF - C - en - REV.00 2012.4 APPLICATION CE-BF Switchbords up to 40.5 kv are designed for use in public and industrial distribution system up to 40,5KV for the operation and protection of lines, transformers,

More information

Eaton Electrical Inc. 1000 Cherrington Parkway Moon Township, PA 15108 United States tel: 1-800-525-2000 www.eatonelectrical.com.

Eaton Electrical Inc. 1000 Cherrington Parkway Moon Township, PA 15108 United States tel: 1-800-525-2000 www.eatonelectrical.com. Page 1 Abstract Adequate space is a concern for electrical installations for several reasons including: Worker safety; Working room; and Adequate clearances for personnel working on energized equipment

More information

FFI. Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars. Presented By: Greg Pelster & Robert Schmid

FFI. Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars. Presented By: Greg Pelster & Robert Schmid Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars Presented By: Greg Pelster & Robert Schmid FFI Ferrie, Franzmann Industries LOW VOLTAGE SWITCHGEAR & LOW VOLTAGE

More information

HVL 5 38 kv Load Interrupter Switchgear. The Standard for Performance, Protection and Dependability

HVL 5 38 kv Load Interrupter Switchgear. The Standard for Performance, Protection and Dependability HVL 5 38 kv Load Interrupter Switchgear The Standard for Performance, Protection and Dependability For a generation of engineers, Square D High Voltage Load (HVL ) Interrupter Switchgear by Schneider Electric

More information

CIRCUIT BREAKER INTERRUPTING CAPACITY AND SHORT-TIME CURRENT RATINGS

CIRCUIT BREAKER INTERRUPTING CAPACITY AND SHORT-TIME CURRENT RATINGS CIRCUIT BREAKER INTERRUPTING CAPACITY AND SHORT-TIME CURRENT RATINGS David D. Roybal, P.E. Senior Member, IEEE Eaton Electrical 3697 Mount Diablo Boulevard Lafayette, CA 94549 Abstract Low-voltage circuit

More information

Sample - No Commercial Use

Sample - No Commercial Use COMPLETE REVISION October 2010 Electrical PIP ELSSG01 Design and Fabrication of Low-Voltage Metal-Enclosed AC Power Circuit Breaker Switchgear PURPOSE AND USE OF PROCESS INDUSTRY PRACTICES In an effort

More information

Spending too much to maintain aging switchgear? Circuit breaker solutions from Square D Services.

Spending too much to maintain aging switchgear? Circuit breaker solutions from Square D Services. Spending too much to maintain aging switchgear? Circuit breaker solutions from Square D Services. Spending too much time and money on equipment maintenance? Square D Services: Your source for circuit breaker

More information

New Arc Resistant, Compact Metal Clad Switchgear: Meeting ANSI / UL Design Challenges By Ashok Kulkarni and Predrag Milovac

New Arc Resistant, Compact Metal Clad Switchgear: Meeting ANSI / UL Design Challenges By Ashok Kulkarni and Predrag Milovac New Arc Resistant, Compact Metal Clad Switchgear: Meeting ANSI / UL Design Challenges By Ashok Kulkarni and Predrag Milovac New Arc Resistant, Compact Metal Clad Switchgear: Meeting ANSI / UL Design Challenges

More information

Specification Guide. for RVAC. Direct Replacement. AC Medium Voltage. Circuit Breakers

Specification Guide. for RVAC. Direct Replacement. AC Medium Voltage. Circuit Breakers Specification Guide for RVAC Direct Replacement AC Medium Voltage Circuit Breakers Table of Contents 1.0 General Work Scope...3 2.0 Standards...3 3.0 Supplier Qualifications...4 4.0 Circuit Breaker Element

More information

Siemens AG Power Transmission and Distribution Medium Voltage Division Mozartstr. 31c 91052 Erlangen Germany. www.siemens.

Siemens AG Power Transmission and Distribution Medium Voltage Division Mozartstr. 31c 91052 Erlangen Germany. www.siemens. Siemens AG Power Transmission and Distribution Medium Voltage Division Mozartstr. 31c 91052 Erlangen Germany www.siemens.com/energy For questions on power transmission and distribution, please contact

More information

Siemens STEP 2000 Course Basics of Electrical Products

Siemens STEP 2000 Course Basics of Electrical Products Siemens STEP 2000 Course Basics of Electrical Products It's easy to get in STEP! Download any course. Hint: Make sure you download all parts for each course and the test answer form. Complete each chapter

More information

PRODUCT GUIDE. SL Medium Voltage IEC Vacuum Contactors

PRODUCT GUIDE. SL Medium Voltage IEC Vacuum Contactors PRODUCT GUIDE SL Medium Voltage IEC Vacuum Contactors Table of Contents 1 Overview Introduction....................................................2 Features........................................................2

More information

Arc Flash Hazards. Electrical Hazards. Dan Neeser Field Application Engineer DanRNeeser@Eaton.com. Electrical Hazards 2/18/2015. Shock.

Arc Flash Hazards. Electrical Hazards. Dan Neeser Field Application Engineer DanRNeeser@Eaton.com. Electrical Hazards 2/18/2015. Shock. Arc Flash Hazards Dan Neeser Field Application Engineer DanRNeeser@Eaton.com Electrical Hazards Electrical Hazards Shock Arc Flash Arc Blast 2 1 Arcing Fault Basics 35,000 F Radiant Heat & UV Speed of

More information

Masterclad Medium Voltage Passive Arc-Resistant Switchgear

Masterclad Medium Voltage Passive Arc-Resistant Switchgear Masterclad Medium Voltage Passive Arc-Resistant Switchgear Square D Masterclad medium voltage passive arc-resistant (AR) switchgear is designed with utilities and industrial customers in mind who demand

More information

STANDARDS AND RATINGS FOR THE APPLICATION OF MOLDED CASE, INSULATED CASE, AND POWER CIRCUIT BREAKERS

STANDARDS AND RATINGS FOR THE APPLICATION OF MOLDED CASE, INSULATED CASE, AND POWER CIRCUIT BREAKERS STANDARDS AND RATINGS FOR THE APPLICATION OF MOLDED CASE, INSULATED CASE, AND POWER CIRCUIT BREAKERS David D. Roybal, P.E. Senior Member, IEEE Cutler-Hammer, Inc. 3697 Mount Diablo Boulevard Lafayette,

More information

Advantages of Fixed Circuit Breaker Switchgear

Advantages of Fixed Circuit Breaker Switchgear Advantages of Fixed Circuit Breaker Switchgear by Lionel Mackay, EDF Energy, and Mike Adams, Schneider Electric Ltd Introduction The purpose of this paper is to review the advantages of fixed circuit breaker

More information

Primary-Side Transformer Protection

Primary-Side Transformer Protection Primary-Side Transformer Protection Peter J. Meyer, S&C Electric Company, Chicago, Illinois Presented at the Doble Life of a Transformer Seminar; Laguna Beach, California February 21 25, 2005 INTRODUCTION

More information

NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems. Safe energy distribution that meets the highest industrial requirements

NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems. Safe energy distribution that meets the highest industrial requirements NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems Safe energy distribution that meets the highest industrial requirements NATUS switchgear systems your advantages minimal use of insulant

More information

Unified requirements for systems with voltages above 1 kv up to 15 kv

Unified requirements for systems with voltages above 1 kv up to 15 kv (1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements apply to

More information

Defining the Needs of Modern Data Center Power Systems, Low Voltage Circuit Breaker Application

Defining the Needs of Modern Data Center Power Systems, Low Voltage Circuit Breaker Application Defining the Needs of Modern Data Center Power Systems, Low Voltage Circuit Breaker Application by Reza Tajali, P.E. Square D Company ABSTRACT In modern data centers, Uninterruptible Power Supplies (UPS)

More information

ALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU

ALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU ALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU George CURCANU, Constantin ILINCA, Ilie SBORA ICMET Craiova, Romania, Calea Bucuresti 144, phone:

More information

A Comparison of Contemporary Electrical Distribution Equipment Standards. San Francisco IEEE Industry Applications Society May 26, 2009

A Comparison of Contemporary Electrical Distribution Equipment Standards. San Francisco IEEE Industry Applications Society May 26, 2009 A Comparison of Contemporary Electrical Distribution Equipment Standards San Francisco IEEE Industry Applications Society May 26, 2009 What are Standards? Clearly defined performance characteristics Based

More information

New SACE Emax 2 for UL 1066 From Circuit Breaker to Power Manager

New SACE Emax 2 for UL 1066 From Circuit Breaker to Power Manager New SACE Emax 2 for UL 1066 From Circuit Breaker to Power Manager 2 1SDC200039B0201 New SACE Emax 2 for UL 1066 Circuit breakers switch power SACE Emax 2 manages it. SACE Emax 2 is the new benchmark of

More information

High-Voltage Circuit-Breakers 3AP1/2 72.5 kv up to 550 kv. Power Transmission and Distribution

High-Voltage Circuit-Breakers 3AP1/2 72.5 kv up to 550 kv. Power Transmission and Distribution High-Voltage Circuit-Breakers AP/ 7.5 kv up to 550 kv Power Transmission and Distribution The AP/ High-Voltage Circuit-Breakers Now Applicable for 550 kv Decades of our experience in high-voltage switching

More information

Instructions for Installation, Operation and Maintenance of 24kV Type W-VAC Vacuum Circuit Breaker

Instructions for Installation, Operation and Maintenance of 24kV Type W-VAC Vacuum Circuit Breaker Instructions for Installation, Operation and Maintenance of 24kV Type W-VAC Vacuum Circuit Breaker Effective 2/98 ! WARNING! WARNING IMPROPERLY INSTALLING OR MAINTAINING THESE PRODUCTS CAN RESULT IN DEATH,

More information

Trade of Electrician. Three-phase Distribution Boards And Socket Circuits

Trade of Electrician. Three-phase Distribution Boards And Socket Circuits Trade of Electrician Standards Based Apprenticeship Three-phase Distribution Boards And Socket Circuits Phase 2 Module No. 2.3 Unit No. 2.3.2 COURSE NOTES Created by Charlie Walsh - Athlone TC Revision

More information

The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies

The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies DATE: November 17, 1999 REVISION: AUTHOR: John Merrell Introduction In some short circuit studies, the X/R ratio is ignored when comparing

More information

METAL-CLAD AND METAL-ENCLOSED SWITCHGEAR 3.6KV~40.5KV. tgood.com. Energy. Fast.

METAL-CLAD AND METAL-ENCLOSED SWITCHGEAR 3.6KV~40.5KV. tgood.com. Energy. Fast. METAL-CLAD AND METAL-ENCLOSED SWITCHGEAR 3.6KV~40.5KV tgood.com Energy. Fast. TGOOD produces over 5000 switchgear units annually for projects around the globe PRODUCT OVERVIEW Integral substation component

More information

SF 6 Gas Insulated Switchgear Type SDF for 170 kv

SF 6 Gas Insulated Switchgear Type SDF for 170 kv Three Phase Encapsulated Type SF 6 Gas Insulated Switchgear Type SDF for 170 kv 06B1-E-0001 With Trustworthy Technology, Structure Fuji Electric as a manufacturer of comprehensive substation equipment

More information

Arc Fault Circuit Interrupters Frequently Asked Questions

Arc Fault Circuit Interrupters Frequently Asked Questions Contents My AFCI is tripping! What do I do? What is the difference between branch feeder and combination type Arc Fault Circuit Interrupters? What is new with the 2008 NEC versus the 2005 NEC with respect

More information

Vacuum Circuit Breaker Type VAD-3

Vacuum Circuit Breaker Type VAD-3 Instruction Bulletin Bulletin 6055-11 Vacuum Circuit Breaker Type VAD-3 4.76 kv, 29 ka (250 MVA) 4.76 kv, 41 ka (350 MVA) 8.25 kv, 33 ka (500 MVA) 15.0 kv, 18 ka (500 MVA) 15.0 kv, 28 ka (750 MVA) 15,0

More information

2004 TRANSMISSION SYSTEMS SEMINAR MEDIUM VOLTAGE, METAL-CLAD ARC RESISTANT SWITCHGEAR: ENHANCING WORKPLACE SAFETY

2004 TRANSMISSION SYSTEMS SEMINAR MEDIUM VOLTAGE, METAL-CLAD ARC RESISTANT SWITCHGEAR: ENHANCING WORKPLACE SAFETY 2004 TRANSMISSION SYSTEMS SEMINAR MEDIUM VOLTAGE, METAL-CLAD ARC RESISTANT SWITCHGEAR: ENHANCING WORKPLACE SAFETY Thomas P. McNamara, P.E. Manager, Development Engineering ABB Inc. Power Technologies Medium

More information

UniGear ZS1. Medium voltage, arc proof, air insulated switchgear for primary distribution

UniGear ZS1. Medium voltage, arc proof, air insulated switchgear for primary distribution UniGear ZS1 Medium voltage, arc proof, air insulated switchgear for primary distribution UniGear ZS1: an innovative solution for all installation requirements ABB UniGear is medium voltage metal-clad,

More information

Arc Terminator Active Arc-Resistant Switchgear

Arc Terminator Active Arc-Resistant Switchgear Arc Terminator Active Arc-Resistant Switchgear Increasing safety and productivity by extinguishing internal arcing faults within the switchgear. The Square D Arc Terminator from Schneider Electric offers

More information

Fuseology. Medium Voltage Fuses. Continuous Current-Carrying Capacity. General. Interrupting Rating. Additional Rules.

Fuseology. Medium Voltage Fuses. Continuous Current-Carrying Capacity. General. Interrupting Rating. Additional Rules. Fuseology Medium Voltage Fuses General Fuses above are classified under one of three classifications as defined in ANSI/IEEE C37.40. 1. General Purpose Current-Limiting Fuse: A fuse capable of interrupting

More information

Digital Energy ITI. Instrument Transformer Basic Technical Information and Application

Digital Energy ITI. Instrument Transformer Basic Technical Information and Application g Digital Energy ITI Instrument Transformer Basic Technical Information and Application Table of Contents DEFINITIONS AND FUNCTIONS CONSTRUCTION FEATURES MAGNETIC CIRCUITS RATING AND RATIO CURRENT TRANSFORMER

More information

SECTION 16346A METAL-CLAD MEDIUM VOLTAGE ARC RESISTANT SWITCHGEAR

SECTION 16346A METAL-CLAD MEDIUM VOLTAGE ARC RESISTANT SWITCHGEAR METAL-CLAD MEDIUM VOLTAGE ARC RESISTANT SWITCHGEAR PART 1 GENERAL 1.01 SCOPE A. The Contractor shall furnish and install the equipment as specified herein and as shown on the contract drawings. 1.02 RELATED

More information

Atlanta Chapter IEEE Industry Applications Society

Atlanta Chapter IEEE Industry Applications Society Atlanta Chapter IEEE Industry Applications Society Electrical Equipment Room Design Considerations presented at the Sheraton Buckhead Hotel Atlanta, Georgia November 20, 2006 Outline 1. Definitions 2.

More information

Engineers Edge, LLC PDH & Professional Training

Engineers Edge, LLC PDH & Professional Training 510 N. Crosslane Rd. Monroe, Georgia 30656 (770) 266-6915 fax (678) 643-1758 Engineers Edge, LLC PDH & Professional Training Copyright, All Rights Reserved Engineers Edge, LLC An Introduction to Interior

More information

National Craft Assessment and Certification Program S P E C I F I C A T I O N S

National Craft Assessment and Certification Program S P E C I F I C A T I O N S National Craft Assessment and Certification Program S P E C I F I C A T I O N S INDUSTRIAL ELECTRICIAN V4 ELEC26_O4 Released September 2013 Focus Statement An Industrial Electrician must be able to interpret

More information

High-Voltage Compact Switchgear 3AP1 DTC for 145 kv and 245 kv

High-Voltage Compact Switchgear 3AP1 DTC for 145 kv and 245 kv High-Voltage Compact Switchgear AP1 DTC for 1 kv and kv Answers for energy. The AP1 DTC Complying with our Customers demands Experience you can rely on - at anytime, anywhere Decades of experience in high-voltage

More information

Integrating SPDs in Switchgear & Switchboards Causes More Problems than it Solves

Integrating SPDs in Switchgear & Switchboards Causes More Problems than it Solves Integrating SPDs in Switchgear & Switchboards Causes More Problems than it Solves White Paper July 2010 Integrating surge protective devices (SPD) into distribution equipment (i.e. switchgear, switchboards,

More information

Medium voltage indoor circuit breakers ANSI/IEC solutions

Medium voltage indoor circuit breakers ANSI/IEC solutions Medium voltage indoor circuit breakers ANSI/ solutions Table of contents Introduction... 3 Vmax/A... 4 ADVAC... 6 AMVAC... 8 Vmax... 10 VD4... 12 VM1... 16 HD4... 19 V-Contact VSC... 22 2 Medium voltage

More information

The following components are common to most cubicles; this example is an ABB HK cubicle.

The following components are common to most cubicles; this example is an ABB HK cubicle. 4.0 CIRCUIT BREAKER CUBICLE Learning Objectives The circuit breaker cubicle is the component of the switchgear that holds the circuit breaker, and the controls and cabling for the distribution system.

More information

Bypass transfer switch mechanisms

Bypass transfer switch mechanisms Power topic #6013 Technical information from Cummins Power Generation transfer switch mechanisms > White paper By Gary Olson, Director, Power Systems Development This paper describes the configuration

More information

Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000

Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000 Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000 Description Firetrol FTA1000 Full Voltage Fire Pump Controllers are intended for use with electric motor driven fi re pumps

More information

Why and How we Use Capacity Control

Why and How we Use Capacity Control Why and How we Use Capacity Control On refrigeration and air conditioning applications where the load may vary over a wide range, due to lighting, occupancy, product loading, ambient weather variations,

More information

MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING

MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING Training Title MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING Training Duration 5 days Training Date MV, HV and EHV Switchgear Testing & Commissioning 5 20 24 Apr $3,750 Dubai, UAE In any of the 5 star

More information

NFPA 70E 2012 Rolls Out New Electrical Safety Requirements Affecting Data Centers

NFPA 70E 2012 Rolls Out New Electrical Safety Requirements Affecting Data Centers NFPA 70E 2012 Rolls Out New Electrical Safety Requirements Affecting Data Centers A market position paper from the experts in Business-Critical Continuity TM Executive Summary Electrocutions are the fourth

More information

Power-Zone 4 Arc Resistant Low Voltage Switchgear

Power-Zone 4 Arc Resistant Low Voltage Switchgear Power-Zone 4 Arc Resistant Low Voltage Switchgear with ArcBlok Technology Make the most of your energy SM Workplace safety 2 I Power-Zone 4 Arc Resistant Low Voltage Switchgear Five to ten arc flash explosions

More information

Harmonics in your electrical system

Harmonics in your electrical system Harmonics in your electrical system What they are, how they can be harmful, and what to do about them Abstract Harmonic currents, generated by non-linear electronic loads, increase power system heat losses

More information

Switchgear and Metal-Enclosed Bus

Switchgear and Metal-Enclosed Bus Section 18 Switchgear and Metal-Enclosed Bus 180. SWITCHGEAR ASSEMBLIES 180A. General Requirements for All Switchgear. This rule covers general requirements for all switchgear. Examples of switchgear found

More information

Power transformers. Generator step-up and system intertie power transformers Securing high-quality AC transmission

Power transformers. Generator step-up and system intertie power transformers Securing high-quality AC transmission Power transformers Generator step-up and system intertie power transformers Securing high-quality AC transmission Generator step-up transformers Built to withstand continuous full load Generator step-up

More information

TWENTIES WORKSHOP, EWEA 2012 Unveiling the future energy system: full scale demonstrations to reach 2020 targets. 17th April 2012

TWENTIES WORKSHOP, EWEA 2012 Unveiling the future energy system: full scale demonstrations to reach 2020 targets. 17th April 2012 TWENTIES WORKSHOP, EWEA 2012 Unveiling the future energy system: full scale demonstrations to reach 2020 targets 17th April 2012 Session 2 Technological challenges to cope with in TWENTIES field tests

More information

Protect your home and family with Advanced Technology from Cutler-Hammer

Protect your home and family with Advanced Technology from Cutler-Hammer Protect your home and family with Advanced Technology from Cutler-Hammer Residential Home Fire Statistics Annually - over 415,000 Residential Fires Annually - over 40,000 electrical fires over 350 deaths

More information

Alternate Methods to Short Circuit Breaker Coordination

Alternate Methods to Short Circuit Breaker Coordination Alternate Methods to Short Circuit Breaker Coordination Nguyen Perez, PE Senior Electrical Engineer 2600 Douglas Road, Suite 301 Coral Gables, Florida 305.529.1515 (p) www.brplusa.com Importance in Healthcare

More information

Guide to the electrical parameter classifications of IEC 60950 and IEC 62368 safety standards

Guide to the electrical parameter classifications of IEC 60950 and IEC 62368 safety standards Guide to the electrical parameter classifications of IEC 60950 and IEC 62368 safety standards Abstract This Guide is an informative listing of selected terms and definitions found in IEC Glossary entry

More information

SWITCHGEAR SOLUTIONS FOR MISSION CRITICAL APPLICATIONS. Presented by SAI Advanced Power Solutions

SWITCHGEAR SOLUTIONS FOR MISSION CRITICAL APPLICATIONS. Presented by SAI Advanced Power Solutions SWITCHGEAR SOLUTIONS FOR MISSION CRITICAL APPLICATIONS POWER DISTRIBUTION RACKS IN A MISSION CRITICAL SYSTEM MODULES IN A MISSION CRITICAL SYSTEM UPS Convertor Main Inverter Load Battery BPC UPS & BATTERY

More information

ELECTRICAL - WIRING DESIGN AND PROTECTION SELF INSPECTION CHECKLIST

ELECTRICAL - WIRING DESIGN AND PROTECTION SELF INSPECTION CHECKLIST Name of School: OPTIONAL INFORMATION Date of Inspection: Vocational Program/Course/Room: Signature of Inspector: ELECTRICAL - WIRING DESIGN AND PROTECTION SELF INSPECTION CHECKLIST Guidelines: This checklist

More information

MCC Ratings. Voltage Rating

MCC Ratings. Voltage Rating MCC Ratings In addition to the various ratings of individual components used in motor control centers, the overall ratings of the motor control center must also be considered. Voltage Rating Motor control

More information

Dead Tank Circuit Breaker 72PM40-C Proven reliability through common platforms

Dead Tank Circuit Breaker 72PM40-C Proven reliability through common platforms Dead Tank Circuit Breaker 72PM40-C Proven reliability through common platforms ABB innovations for changing demands ABB (www.abb.com) is a leader in power and automation technologies that enables utility

More information

Best Practice Catalog Generator Switchgear

Best Practice Catalog Generator Switchgear Best Practice Catalog Generator Switchgear Revision 2.0, 8/23/2012 Prepared by MESA ASSOCIATES, INC. Chattanooga, TN 37402 and OAK RIDGE NATIONAL LABORATORY Oak Ridge, Tennessee 37831-6283 managed by UT-BATTELLE,

More information

Medium Voltage Motor Control Assemblies

Medium Voltage Motor Control Assemblies Medium Voltage Motor Control Assemblies Arc Resistant AMPGARD.1 Product............................................. 2 Application........................................... 2 Features, Benefits and Functions...................................

More information

Choosing the Best Solution for Reducing Arc Energy

Choosing the Best Solution for Reducing Arc Energy CONVENTION SESSION HANDOUT Choosing the Best Solution for Reducing Arc Energy Terry L. Schiazza, Business Development Manager Square D / Schneider Electric SESSION #11 Independent Electrical Contractors

More information

Product Description Primary Resistance Starting Electric Fire Pump Controllers FTA1500

Product Description Primary Resistance Starting Electric Fire Pump Controllers FTA1500 Product Description Primary Resistance Starting Electric Fire Pump Controllers FTA1500 Description Firetrol FTA1500 Primary Resistance Fire Pump Controllers use resistors in the line to reduce line voltage

More information

QUESTIONS and ANSWERS RFB 745-15-9894, Metal Clad Switchgear and Power Control Room

QUESTIONS and ANSWERS RFB 745-15-9894, Metal Clad Switchgear and Power Control Room QUESTIONS and ANSWERS RFB 745-15-9894, Metal Clad Switchgear and Power Control Room 1) When you click on the UTHSCSA Drawing the site takes you to the E-1 drawing no other. Will there be other drawings

More information

Reliability requires consulting engineers and end users to grasp design, maintenance basics. By Reza Tajali, P.E. Square D Power Systems Engineering

Reliability requires consulting engineers and end users to grasp design, maintenance basics. By Reza Tajali, P.E. Square D Power Systems Engineering LOW VOLTAGE CIRCUIT BREAKER GUIDELINES FOR DATA CENTERS Reliability requires consulting engineers and end users to grasp design, maintenance basics By Reza Tajali, P.E. Square D Power Systems Engineering

More information

SWITCHGEAR Section 16. SECTION INCLUDES This Section includes service and distribution switchboards rated 600 V and less.

SWITCHGEAR Section 16. SECTION INCLUDES This Section includes service and distribution switchboards rated 600 V and less. PART 1 - GENERAL SECTION INCLUDES This Section includes service and distribution switchboards rated 600 V and less. RELATED SECTIONS Division 16 Section "Basic Electrical Materials and Methods" for general

More information

Installation Manual Version 7.3 IMPORTANT:

Installation Manual Version 7.3 IMPORTANT: Installation Manual Version 7.3 IMPORTANT: READ ENTIRE MANUAL CAREFULLY, THIS PHASE CONVERTER MUST BE INSTALLED BY A INDUSTRIAL LICENSED ELECTRICIAN 230 VOLTS MODEL ONLY READ FIRST!!!!!! DANGER: HIGH VOLTAGE

More information

What are the basic electrical safety issues and remedies in solar photovoltaic installations?

What are the basic electrical safety issues and remedies in solar photovoltaic installations? What are the basic electrical safety issues and remedies in solar photovoltaic installations? Presented by: Behzad Eghtesady City of Los Angeles Department of Building and Safety Topics Covered Photovoltaic

More information

MTE SERIES RLW. World REACTORS USER MANUAL PART NO. INSTR 030 REL. 090930. 2009 MTE Corporation

MTE SERIES RLW. World REACTORS USER MANUAL PART NO. INSTR 030 REL. 090930. 2009 MTE Corporation MTE SERIES RLW World REACTORS USER MANUAL PART NO. INSTR 030 REL. 090930 2009 MTE Corporation IMPORTANT USER INFORMATION NOTICE MTE Series RLW reactors are components designed to improve the reliability

More information

Exploring the Necessity of the Hot Hipot Test

Exploring the Necessity of the Hot Hipot Test Exploring the Necessity of the Hot Hipot Test Introduction In an industry comprised of workers with varying electronics knowledge, a Hipot test can seem a daunting task for some. Indeed, many test operators

More information

MEDIUM VOLTAGE METAL CLAD SWITCHGEAR

MEDIUM VOLTAGE METAL CLAD SWITCHGEAR MEDIUM VOLTAGE METAL CLAD SWITCHGEAR PART 1 - GENERAL 1.1 DESCRIPTION This section specifies the furnishing, installation, connection and testing of the medium voltage switchgear. 1.2 SWITCHGEAR FEATURES

More information

Grounding of Electrical Systems NEW CODE: Grounding and Bonding

Grounding of Electrical Systems NEW CODE: Grounding and Bonding Grounding of Electrical Systems NEW CODE: Grounding and Bonding Presented By Scott Peele PE Grounding of Electrical Systems Outline Defining the Terms Why should I Ground? Types of Grounding Systems Separately

More information

All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.

All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations. DIVISION 16 ELECTRICAL SECTION 16100 - ELECTRICAL PART 1 - GENERAL SCOPE All electrical work as shown on the drawings and as necessary to provide a complete electrical system. Include primary service,

More information

Introduction. Upon completion of Basics of Electrical Products, you should be able to:

Introduction. Upon completion of Basics of Electrical Products, you should be able to: Table of Contents Introduction... 2 Siemens Industry, Inc... 4 Electric Power... 5 Residential Applications... 10 Commercial Applications... 20 Industrial Applications... 37 Manufacturing Applications...

More information

Evaluating Water-Damaged Electrical Equipment

Evaluating Water-Damaged Electrical Equipment Evaluating Water-Damaged Electrical Equipment 1 USE OF THIS PUBLICATION This publication provides information on how to evaluate electrical equipment that has been exposed to water through flooding, fire

More information

Engineering Series Ratings: Is It Practical?

Engineering Series Ratings: Is It Practical? Engineering Series Ratings: Is It Practical? By the National Electrical Manufacturers Association The 2005 National Electrical Code (NEC) introduces a change regarding series ratings for circuit breakers

More information

Grounding of AC generators and switching the neutral in emergency and standby power systems

Grounding of AC generators and switching the neutral in emergency and standby power systems Power topic #6006 Part 2 of 2 Technical information from Cummins Power eneration rounding of AC generators and switching the neutral in emergency and standby power systems > White paper By Lawrence A.

More information

Modan 3000 ADVANCED TECHNOLOGY, INDUSTRIAL GRADE MOTOR CONTROL CENTER. Systems Products and Services. Motor Control Centers Modan 3000

Modan 3000 ADVANCED TECHNOLOGY, INDUSTRIAL GRADE MOTOR CONTROL CENTER. Systems Products and Services. Motor Control Centers Modan 3000 Systems Products Motor Control Centers Modan 3 Modan 3 UL / CSA ADVANCED TECHNOLOGY, INDUSTRIAL GRADE MOTOR CONTROL CENTER MODAN 3 Motor Control Centers Offer: Over 1 years of Motor Control experience

More information

Proper Application of 415V Systems in North American Data Centers. A White Paper from the Experts in Business-Critical Continuity

Proper Application of 415V Systems in North American Data Centers. A White Paper from the Experts in Business-Critical Continuity Proper Application of 415V Systems in North American Data Centers A White Paper from the Experts in Business-Critical Continuity Introduction Increasing pressure to reduce operating expenses and be more

More information

COMPARISON OF ANSI/IEEE AND IEC REQUIREMENTS FOR LOW- VOLTAGE SWITCHGEAR

COMPARISON OF ANSI/IEEE AND IEC REQUIREMENTS FOR LOW- VOLTAGE SWITCHGEAR COMPARISON OF ANSI/IEEE AND IEC REQUIREMENTS FOR LOW- VOLTAGE SWITCHGEAR Copyright Material IEEE Paper No. PCIC 2003-13 Eddie Wilkie Eaton Cutler-Hammer 3990 Old Tasso Road NE Cleveland, TN 37312 USA Abstract

More information

Circuit Breakers. NRC Series. NRC Series. 900 www.idec.com

Circuit Breakers. NRC Series. NRC Series. 900 www.idec.com Switches & Pilot Lights Display Lights NRC series circuit breakers offer circuit protection which is far superior to using fuses in applications containing relay circuits, motor circuits, heater circuits,

More information