1 GASTON GT-FA &GT-F Front Terminal Valve Regulated Lead Acid (VRLA) Batteries Engineering Manual

2 Table of Contents 1. SAFETY 3 Page 2. INTRODUCTION AND FEATURES 3 3. MAIN APPLICATIONS 4 4. OPERATING PRINCIPLES OF VRLA TECHNOLOGY 4 5. CONSTRUCTION FEATURES 5 6. OPERATING FEATURES 6 7. CHARGING BATTERY SIZING APPLICABLE STANDARDS STORAGE INSTALLATION 17 Page 2

3 1. SAFETY Do not handle, unpack or install batteries without a proper understanding of the safety risks. FA Valve Regulated Lead Acid (VRLA) batteries contain sulfuric acid. Sulfuric acid can cause severe irritation and burns. Contact with sulfuric acid should be avoided. Do not handle batteries that appear to be damaged or leaking. If sulfuric acid comes in contact with the skin or eyes, flush immediately and thoroughly with water. Always have eye wash equipment available. Make sure to seek proper medical attention. Proper safety apparel should be worn to minimize exposure to sulfuric acid. Safety apparel should include rubber gloves, rubber apron, and goggles. Sulfuric acid can be neutralized with baking soda. Acid spills should only be handled by properly trained personnel. Contact GASTON BATTERY INDUSTRIAL LTD. for a copy of the MSDS sheet. Batteries generate hydrogen which is extremely explosive. GT-F VRLA batteries emit small amounts of hydrogen under normal operation, but can evolve significant amounts of hydrogen if any of the cells are charged at an excessive voltage (Operator error, charger malfunction, shorted cells in string, etc.). Never seal batteries in a room or enclosure where hydrogen can accumulate. Never smoke around batteries. Open flames and sparks should always be avoided to minimize risk of igniting the hydrogen and causing an explosion. Avoid incidental sparks by never wearing jewelry, and only using insulated tools when installing and handling batteries. Never drop or lay tools across battery terminals. Make sure all connections are properly cleaned and torqued. Electrically isolate the batteries for service and installation. Make sure to minimize voltage drops during connections to avoid sparks. Batteries are extremely heavy. Always use proper lifting techniques and equipment as specified by OSHA. Only personnel that have been properly trained on DC power safety should have access to the batteries for installation and maintenance. 2. INTRODUCTION AND FEATURES The GT-F range of Valve Regulated Lead Acid (VRLA) batteries has been designed to meet the needs of the wireless communications industry. The success of the GASTON BATTERY GT-F range is based on a product design purpose-built for the needs of a wireless communications network, and industry leading manufacturing technology for product consistency. Safety, reliability and long service life in standby applications is the result. In addition, GASTON BATTERY offers a full line of racking solutions to accommodate the GT-F range of batteries. The front-terminal GT-F batteries provide easy access to the terminals for installation and maintenance. This eliminates the need to purchase expensive sliding mechanisms for terminal access. And the GT-F range includes 8 models a revolutionary idea to further reduce space requirements and minimize the number of terminations to make it easier to install and maintain these batteries. Other features of the GT-F range include: No Water Addition Compatibility Good energy density GT-F batteries require no addition of water throughout their life which reduces maintenance costs versus vented (flooded) batteries GT-F was specially designed to meet the requirements of modern electronic equipment and is compatible with normally available recharging systems. The compact construction and excellent performance at high rates of discharge provide big savings in volume and weight as compared to conventional flooded, vented batteries. Page 3

4 Office compatibility GASTON BATTERY GT-F batteries, which are valve regulated and virtually sealed, do not give off perceptible amounts of gas under normal operating conditions so they can be installed in the same environment where people live and work. Savings Long life Installation Reliability GT-F batteries offer substantial savings in installation and maintenance costs compared to conventional vented batteries. In fact, no special rooms are required and only minimal maintenance is needed during the life of the battery. Rigorous laboratory tests and extensive field experience have enabled GASTON BATTERY to manufacture a highly reliable product with a five-year minimum design life. GT-F batteries are very easy to handle because they are designed with handles either molded into the cover or the end-walls of the container. Smaller, more compact and lighter than traditional batteries, FA batteries are supplied filled and charged so that they can be immediately installed directly into cabinets or on easily assembled racks also available from GASTON BATTERY. GT-F batteries have been tested in the field for a number of years and fully comply with established international standards. The GT-F range has been fully tested with respect to charge and discharge characteristics, cycle life, recombination efficiency, mechanical strength, vibration life and flame retardancy. 3. MAIN APPLICATIONS Wireless Communications U.P.S. GASTON BATTERY GT-F batteries have a proven track record of performance in many parts of the communications network including Central Office, Huts, CEV s and Remote Terminal cabinets. The low internal resistance Absorbent Glass Mat (AGM) FA batteries make them a good choice for U.P.S. applications, especially for Industrial U.P.S. and extended run-time applications. 4. OPERATING PRINCIPLES OF VRLA TECHNOLOGY The basic phenomenon behind VRLA technology is a process called recombination. During cycling of conventional flooded lead acid cells, water is lost from the cell due to electrolysis and results in the venting of hydrogen, oxygen and droplets of sulfuric acid entrapped in the gas stream. This results in the need for regular battery checks and periodic topping-up with water to maintain the electrolyte at the proper level. Valve regulated lead acid batteries eliminate this problem through continuous recombination of the oxygen during float charging and boost charging. The oxygen recombination process occurs if the separators are not completely filled with electrolyte. This allows some pores to be free for the oxygen diffusion from the positive plates (where it is generated) directly to the negative plates where it reacts to reform water. During float charging and boost charging the following reactions occur: 1) Oxygen is evolved at the positive plate by the reaction: H 2 O ½O 2 + 2H + + 2e - and diffuses through the unfilled pores of the separator to the surface of the negative plate. 2) At the negative plate oxygen combines with Pb and sulfuric acid: Pb + H 2 SO 4 + ½ O2 PbSO 4 + H 2 O 3) The charging process electrochemically regenerates the lead in the negative plate, completing the cycle: PbSO 4 + 2H + + 2e - Pb + H 2 SO 4 Page 4

5 As a result (see also fig. 1), the recombination process (with an efficiency higher than 98%), completes and reverses the water oxidation. At the end of the process, the recombination has replaced the water, the electrolyte and the lead in the negative plates without having modified the state of charge of the plates. H O 2H + 1 O H 2 SO 4 Pb PbO PbSO + H O 4 2 Pb + H SO 4 2 Figure 1: The Oxygen Recombination Process in VRLA Batteries Special separators with high porosity and very small pore diameter are required to facilitate the oxygen recombination cycle. In addition, a carefully controlled quantity of electrolyte must be inserted into every single cell in order to maintain sufficient electrolyte to satisfy the discharge reactions while maintaining a sufficient quantity of pores free of electrolyte to maintain the gas diffusion. These unique requirements also result in the fact that all of the electrolyte is retained in the separator and plates and there is no free electrolyte. The gas pressure within the cells during operation is normally above atmospheric pressure and consists of oxygen, hydrogen, nitrogen and carbon dioxide. It is thus necessary for each cell to have an outlet for the release of non-recombined gases to avoid excessive internal pressure. Safety valves are used for this purpose. The valves are also very important because they prevent air from entering the cell. from the surrounding environment. Oxygen in any outside air would cause the negative plates to oxidize and shorten the life of the battery. So, to allow excess internal gas to escape, while keeping external air from getting into the battery, each cell has a one-way pressure relief valve. For this reason these batteries are not always sealed batteries, so valve regulated lead acid (VRLA) batteries is used to give a more accurate description. 5. CONSTRUCTION FEATURES Plates Both positive and negative plates are of the flat pasted type. The active material is made of a paste of lead oxide, water, sulfuric acid and other materials needed to obtain the performance and stability required throughout the battery life. The grids are made of a high quality lead alloy with calcium and tin additives which assure good resistance against corrosion. The grids are sized to ensure a design life of 10 or more years at normal ambient temperature. Containers Battery cases and covers are made of a type of ABS plastic which complies with UL 94, class V-0 and with IEC 707, method FV0. It also meets the Telcordia requirement for 28% Limiting Oxygen Index (LOI). This material is shock resistant, self extinguishing and flame retardant. The containers and covers are also designed to fully withstand internal pressure variations during battery operation. Reinforced container walls and covers Page 5

6 further ensure this. Handles have been designed into the covers or the battery end-walls to facilitate handling. Separators Electrolyte Valves Construction The special separators, which ensure reliable operation of the oxygen recombination cycle, are one of the most important and basic components of GT-F batteries. These separators are made of microfibre glass sheets by a special process, which results in a high porosity with very small pore diameters to ensure maximum oxygen diffusion while maintaining high plate utilization and low internal impedance. Thanks to the chemical nature of the separator material (silica), it is fully inert to the sulfuric acid and the lead dioxide, and remains unchanged during the life of the battery. The excellent electrical and mechanical characteristics remain constant over a very wide temperature range. The very low internal resistance of the separator material combined with the special plates designed for GT-F batteries results in excellent utilization of the active materials in the plates over a wide range of high and low discharge rates. The plates are completely wrapped by the separator and the electrolyte is completely absorbed in the separator and plates. As a result, the shedding of active material, which can cause shorting with flooded batteries, is avoided. The electrolyte is sulfuric acid with a specific gravity of at 25 C with the same purity characteristics as other types of high quality lead acid batteries. Each cell has a one-way valve to permit the release of gases from the cell whenever the internal pressure exceeds the fixed safety value. The valve is rated at approximately 0.1 atmospheres (1.5 PSIG or 10 kpa). Suitable threaded pillars with solid or flexible connectors are provided to ensure low ohmic losses. Post-to-cover seals are designed to prevent leakage over a wide range of internal pressures and temperatures. Inter-cell connections in the GT-F design are electrically welded through the cell walls to minimize the internal impedance while maintaining complete separation of the individual cells. 6. OPERATING FEATURES Capacity Cell Voltage The battery capacity is rated in ampere hours (Ah) and is the quantity of electricity which it can supply during discharge. The capacity depends on the quantity of the active materials contained in the battery (thus on dimensions and weight) as well as the discharge rate and temperature. The European standard for nominal capacity is typically the C 10 rate (ten hour discharge) to an end voltage of 1.80 VPC at 20 C. This Ah capacity is very close to the American standard which is often stated at the C 8 (eight hour discharge) rate to an end voltage of 1.75 VPC at 25 C, especially for Telecom batteries. Sometimes though, Manufacturers will present their nominal capacities at the C 20 discharge rate, which is inherently higher than the C 8 rate. The user needs to be very careful when comparing batteries from different families or manufacturers to make sure that the Ah ratings are compared under the same conditions. The voltage of lead acid cells is due to the electrochemical potential differences between the active electrode materials (PbO 2 and Pb) in the presence of electrolyte (sulfuric acid). Its value depends on the electrolyte concentration in contact with these electrodes, but is approximately 2 Volts under most open circuit conditions. More precisely, it is a function of the state of charge of the battery; the open circuit voltage of a GT-F cell at ambient temperature can be represented by the following figure 2: Page 6

7 Open Circuit Voltage (V) State of charge (%) Figure 2: Open Circuit Voltage in Relation to the State-of-Charge of the Cell Internal impedance The internal impedance of a lead acid battery is a direct result of the type of internal construction, plate thickness, number of plates, separator material, electrolyte specific gravity, temperature and state of charge. The inverse of impedance is conductance. Larger batteries have lower impedance and higher conductance. There are devices available on the market that measure either impedance, or conductance, and estimate the capacity of the battery. It should be understood that neither conductance nor impedance are perfect predictors of battery capacity. A customer can pass many bad cells and reject many good cells using these instruments as Go / No-Go gauges. The best way to use impedance or conductance instruments is to trend the change over long periods of time. The user should establish a baseline value for each block at the time of installation. Throughout the battery s life, the impedance or conductance should be compared against this baseline. GASTON BATTERY INDUSTRIAL LTD. can provide guidelines for impedance and conductance values, but it is far more meaningful to establish the baseline for each individual block at the time of installation. Contact either the instrument manufacturer or GASTON BATTERY INDUSTRIAL LTD. to get more details on what change in impedance or conductance over time should trigger maintenance and/or replacement of the blocks. Capacity in relation to the discharge rate The capacity available from a battery depends on the rate of discharge. The higher the discharge rate, the lower the available capacity. This relationship is described in the Peukert equation; I n * t = C or t = C / I n Where I = current, t = time and C & n are constants that vary for each battery type. As I (the discharge rate) increases, the standby time of the battery decreases exponentially. Suppose a certain battery had the constants C=185, and n = Page 7

8 For I = 10 amps: t = 185 / = 10.4 hours for a total of 104 Ah For I = 100 amps: t = 185 / = 0.6 hours for a total of 60 Ah Life The end of service life of batteries is defined as the point at which the battery s actual capacity has reached 80% of its nominal capacity. The life of a VRLA battery primarily depends on the following parameters: temperature, charging voltage, float voltage for a given temperature (temperature compensation), number of discharges, and AC ripple from chargers. In standby applications, the battery reaches end of life when there is no longer enough positive grid material to conduct electricity (grid corrosion), or there is not enough fluid left in the separators to support ohmic transfer between the plates (dry out). In cycling applications, the end of life can also be characterized by an irreversible sulfation of the plates. In a laboratory, it is easy to control all of these factors. Battery manufacturers typically talk about design life. The design life is usually stated under a rigid set of conditions. For standby applications, those conditions are usually: Constant voltage charging at 2.27 VPC; fixed temperature at 20 C; negligible AC ripple from chargers; minimal discharges (typically cycles per year). Under these stringent conditions, the FA family of batteries will delivery 15 years of float life. Users cannot always control temperature, voltage and AC ripple to this extent. Therefore 15 years should not always be expected. A rule of thumb often used is that battery life will halve for every 8-10 C above nominal (20 C). This relationship allows battery designers to accelerate the decay of battery life. Life and Float Current Float current can be a good measurement of aging, if measured accurately. The challenge is to find a good measurement technique that eliminates the noise on the bus from AC equipment. Options for measurement include shunts, Hall Effects sensors and specially designed Hall effects sensors for battery float determination. Float current primarily is the combination of energy required to support the following reactions inside the battery: 1) Self discharge 2) Grid Corrosion 3) Gassing / recombination The float current will approximately double for every 8 to 10 C above ambient, and/or for every 50 mv per cell above the recommended float voltage. GT-F batteries will normally float around 30 ma per 100 Ah at 2.27 VPC and 20 C. The relative portion of the float current going into the three reactions listed above (self discharge, grid corrosion and gassing/recombination) is not constant. The gassing/recombination reaction tends to dominate as the float current increases. It also is important to understand that grid corrosion contributes to dry out. Water in the electrolyte provides the oxygen for the oxidation of the lead (Pb) positive grid. That is why dry out is a major failure mode for VRLA in high temperature applications. The relationship between float current and float voltage is typically displayed in a Tafel curve. These are complex curves that show the positive plate and negative plate polarization voltages as a function of the charging current on a fully charged battery. Contact GASTON BATTERY INDUSTRIAL LTD. for more information on Tafel curves. Capacity versus temperature The capacity available from a battery, at any particular discharge rate, varies with temperature. As batteries get colder, the available capacity is reduced. This is related to the kinetics of the electrochemical reactions and the resistivity of the electrolyte. The graph in Figure 3 shows the available capacity at different temperatures and discharge rates. Page 8

9 120% 110% 100% 90% 1-10 hours available capacity 80% 70% 60% 50% 5-59 min. 40% 30% 20% temperature ( C) Figure 3: Capacity as a Function of Temperature and Discharge Rate Short circuit Open circuit GT-F batteries are designed to withstand a short circuit current for 1 minute without damage. When a battery is left open circuit, two major things are happening: 1) Sulfate is leaving the electrolyte and reacting with the plates causing a reduction in the State of Charge of the battery. 2) Grid corrosion is accelerated, especially when the open circuit voltage of the battery is allowed to go below 2.05 VPC. The state of charge of lead acid batteries slowly decreases on open circuit due to selfdischarge. In GT-F batteries, the rate of self-discharge is about 2-3% per month at 25 C. During prolonged storage it is necessary to boost- charge the battery at least every 6 months according to the instructions in paragraph 8 to maintain a fully charged condition of the battery.; Excessive open circuit storage of any lead acid battery without recharge will result in some permanent loss of capacity. When stored at higher temperatures, the boost interval should be more frequent. The key is to keep the open circuit voltage (measured in a fully rested state of at least 16 hours) at or above 2.05 VPC to minimize the amount of irreversible grid corrosion. Storage Temperature Boost Interval 25ºC 6 Months 35ºC 3 Months 45ºC 1 Month Page 9

10 Cycling Gassing The GT-F range of batteries will deliver 200 cycles (at C 8 to 1.75 VPC and 25 C). Cycle life varies greatly based on the amount of energy removed during each cycle. FA batteries will deliver thousands of shallow cycles, but only hundreds of deep cycles. Special care should be used when comparing various manufacturers claims. Every manufacturer has slight variations in defining the Depth of Discharge. A claim of 500 cycles might seem great, until the fine print is read and the User finds out that the Depth of Discharge on each cycle was for a very shallow discharge. When comparing cycle life, make sure to carefully define the conditions (e.g. C 8, 25 C, to 1.75 VPC) for an apples to apples comparison. As previously stated, GT-F batteries have a high recombination efficiency (>98%) and for cells operated at 20 C under normal operating conditions venting is virtually negligible. Laboratory test measurements show the following gassing rates: 2 ml/ah/cell/month at a float voltage of 2.27 V/cell 10 ml/ah/cell/month at a recharge voltage of 2.40 V/cell. The quantity of gas (it basically consists of 80-90% hydrogen) given off is very low and thus it is clear that GT-F VRLA recombination batteries can be installed in rooms containing electrical equipment with no explosion danger or corrosion problems under normal conditions. The only requirement is that these rooms or cabinets must have natural ventilation and not be fully sealed. Hydrogen should never be allowed to exceed 2% by volume in any enclosed space. Also, customers should be aware that hydrogen is very light, and can pocket in portions of the room or cabinet. Designers should take this into account when designing the room or cabinet. Thermal Runaway As previously discussed in the Life section, float current is primarily a function of voltage and temperature. As either voltage or temperature increases, the float current also increases exponentially. Much of the float current is going into the recombination reaction, which is exothermic. If the heat generated by recombination exceeds the rate at which heat can be transferred out of the battery (based on conduction, convection, and black body radiation), a dangerous cycle can begin. This condition is known as thermal runaway. The battery will continue to take very large amounts of current from the rectifier and excessive gassing and overheating will result. In the most severe cases, equipment can be damaged by sulfuric acid mist that escapes the battery, hydrogen can build up to dangerous levels, and battery cases can rupture because of weakening and melting of the plastic. Ruptured cases can lead to ground faults. The importance of minimizing risk of thermal runaway cannot be overemphasized. The most effective methods for minimizing the risk of thermal runaway are: 1) Use temperature compensated chargers 2) Never allow the batteries to exceed 55 C 3) Make sure cabinets are properly ventilated 4) Provide spacing between batteries to enhance convective cooling 5) Visit sites annually to check for shorted cells, improperly set voltages, filter cleaning on ventilation systems, etc. Operation of batteries in parallel When the required capacity is greater than the maximum available from our range, it is possible to connect batteries in parallel to obtain the desired capacity. Use only blocks of the same model Make all electrical connections of parallel circuits as equal and symmetrical as possible between the batteries (e.g., length and type of connector) to minimize possible impedance variations Page 10

11 7. CHARGING Introduction After installation, batteries are an energy source ready to be used whenever necessary. It is very important that batteries are: Float-charged in order to be maintained in a fully charged condition during the standby period. Completely recharged after a discharge. Recharge as soon as possible to ensure maximum protection against subsequent power outages. Early recharge also ensures maximum battery life. Recharge can be done in many ways, depending on the needs of recharge time or life of the batteries. In general, charging is performed as follows: at recharge voltages equal to the float voltage and low currents (long recharge time); at recharge voltage not higher than 2.4 V/cell and high currents (faster recharge). The IU recharge method, also known as modified constant potential, has been used for many years and in a variety of applications. It satisfies the need to have the battery quickly recharged while ensuring maximum battery life. With this method, recharge starts at a constant current rate. The voltage increases up to a pre-set value. The pre-set voltage is maintained and the current then decreases to a minimum defined value. Finally, the recharge is completed at a final constant voltage value equal to or less than that defined for float charge with the current decreasing to the value used in float. Recommended procedure for charging and floating of GT-F batteries It is important to recharge VRLA batteries using methods which do not cause excessive gassing. Such methods would cause excessive water consumption and a loss of battery life as well as present unsafe conditions do to the venting of gases. The only charging methods which should be used are those which operate automatically with a preset constant voltage value supplying a charging current whose maximum value cannot be exceeded; i.e., constant voltage charging with current limit and automatic crossover. a) Float Charge and Temperature Compensation The voltage recommended for float charge, which will ensure the maximum life of GT- F batteries is 2.26 V at 25 C. These batteries can operate over a temperature range of 20 to +60 C, as performance and life are greatly reduced outside of this temperature range. The recommended float voltages to maximize the battery life over the range of temperatures between -20 and +60 C are shown in Figure 5A. Temperature Recommended Float Voltage Per Cell -20 C C C C C 2.17 Figure 4A: Recommended Float Voltages at Various Temperatures An acceptable range of float voltages is shown in the graph in Figure 4B. The equation for the midline of the acceptable float range in Figure 5B is: Y = * T (-2.5 mv per C temperature compensation slope) Page 11

12 2.4 The minimum and maximum are V on either side of this midline. Batteries floated at voltages above the range will have an increased risk of dry out, grid corrosion and thermal runaway. Batteries floated below the range will not receive enough charge, and will be subject to sulfation Volt per cell temperature ( C) Figure. 4B Float Voltage vs. temperature The normal float current observed in fully charged GT-F batteries at 2.27 VPC and a temperature of 20 C is approximately 30 ma per 100 Ah. Because of the nature of recombination phenomena, the float current observed in GT-F batteries is normally higher than that of vented batteries and is not an indication of the state of charge of the batteries. b) Recharge following discharge The recommended recharge method of GT-F batteries to maximize battery life is to use a constant voltage equal to the float charge voltage (2.27 VPC at 20 C) with a maximum charge current of 0.25 C 8 amperes. Users need to be careful of situations where excess current is available to recharge the battery. This happens in conditions when the DC load is low relative to the charger or maximum rectifier output, and the battery is fully discharged. If too much current is allowed to go into the battery, it can cause the battery to heat up excessively and be damaged. This scenario is especially likely at sites when the DC power plant has been fully installed and turned up before all of the DC loads have been attached to the bus. Figure 5 demonstrates three recharge profiles using (3) different current limits. Using a current limit of 0.1 C 10, it takes approximately 9 hours to restore 80% of the discharge, and 11 hours to restore 90%. This can be compared to a current limit of 0.25 C10, whereby 80% is returned in approximately 4 hours, and 90% within 5 hours. When sizing the charger, keep the following in mind: - More charger (rectifier) amps = More $ Page 12

13 - Less charger (rectifier) amps = longer recharge time - Too many charger (rectifier) amps can damage the battery 110% 100% 90% 80% 70% e ch ar ge 60% 50% 40% 30% 20% 01C % 0% 8. BATTERY SIZING hours Fig. 5 Recharge Time and % Restored as a Function of Current Limit If it is necessary to reduce the recharge time, the IU recharge method previously explained can be used with a maximum voltage of 2.4 V/cell at 25 C with a maximum current of 0.25 C 8. However this recharge should be limited to no more than once per month to ensure the maximum service life of the battery. To use the GASTON BATTERY specification data tables, the User must determine the voltage per cell (VPC) at the end of discharge, the backup time and the required load. The constant current tables require the load amperage. The Constant Power tables require the load Watts per Cell (WPC). Nominal Voltage All lead-acid cells have a nominal voltage of 2 VDC per cell. Some typical nominal system voltages are: Typical Values Telecom: Cellular: Utility: Single Phase UPS: Three Phase UPS: 48 VDC 24 VDC 120 VDC 48 and 120 VDC 240/360/480 VDC Cells per String When selecting the number of cells per string, the user must take into account the following: Page 13

14 - Operating temperature and charger maximum DC output voltage - Minimum voltage of the load, inverter or low voltage disconnect - Voltage losses in the cabling GT-F batteries require different float voltages for different temperatures. Recalling Figure 5A, we know: Temperature Recommended Float Voltage Per Cell -20 C C C C C 2.17 The maximum number of cells per string is defined as the maximum DC output voltage of the charger divided by the required float voltage per cell for a given temperature. Whenever possible, try and select a Cells Per String that is divisible by 2, 3 or 6 so that multi-cell blocks can be utilized. Application Telecom 48 VDC, Charger V max 54 VDC: Telecom 48 VDC, Charger V max < 54 VDC: Cellular 24 VDC, Charger V max 27.5 VDC: Utility 120 VDC, Charger V max 135 VDC: Utility 120 VDC, Charger V max < 130 VDC: 24 cells per string 23 cells per string 12 cells per string 60 cells per string 58 cells per string Low Voltage Interruption Often times DC loads will shutoff if the voltage gets too low. Other equipment can be damaged if the DC bus voltage gets too low. As a battery discharges, the terminal voltage will drop. Many Engineers elect to use Low Voltage Disconnects (LVD s) to protect sensitive equipment from low voltages, and to prevent the battery from being overdischarged. LVD s can be placed on the load side, or on the battery side. Keep in mind that a string of batteries is a series of individual 2V cells working together. At the end of discharge, the voltages of the individual cells will vary based on the exact capacity of each cell. Most users try to terminate the load when the batteries reach 1.75 VPC to assure that no individual cells go below 0 VDC. Cells that go below 0 VDC are said to have been reversed, and usually need to be replaced. Other Engineers elect not to use any type of LVD. They are willing to sacrifice the battery to maximize the backup time, and to eliminate a potential failure point (i.e. an LVD that does not operate properly) in the DC power plant. GASTON BATTERY strongly recommends that any cells that have gone into reverse should be replaced immediately. To maximize battery life, GASTON BATTERY recommends that LVD s be used. Voltage Losses When sizing a battery, the Engineer must take into account that there are voltage losses between the battery terminals and the load or inverter. Therefore, to ensure that the voltage at the load is at the prescribed level, the cable losses must be added to the load cutoff voltage to properly arrive at the battery terminal voltage at end of discharge (required to use the Discharge Data Tables). The battery terminal voltage at end of discharge, divided by the total number of cells per string, is the required VPC to use the discharge tables. Page 14

15 VPC at End Discharge Battery Terminal Voltage at End of Discharge / # Cells per String where the Battery Terminal Voltage = Minimum Load Voltage + Cable Losses Watts per Cell For Constant Power discharges, the Watts per cell (WPC) is given by: WPC = Battery Watts (kwb) / Number of Cells Note: Make sure to get the inverter efficiency and Power Factor from the UPS manufacturer in order to convert the UPS kva output to the required battery load kwb. Each UPS is different. Aging Factor Temperature Factor Parallel Strings As previously discussed, a battery has reached end of life when the capacity of the battery is 80% of the nominal capacity. Taking this into account, most Engineers will multiply their load by 1.25 to assure enough capacity at end of life. Useful battery capacity is diminished as the battery gets colder. Consult Figure 4 to determine an appropriate de-rating factor. Most Engineers will multiply their load by a temperature capacity correction factor to take this into account. If more than one string is to be used, the total load should be divided equally by the number of strings. Then do the sizing for one string, and remember to order all strings. The major issue with parallel strings involves voltage imbalances in the wiring scheme. If the strings are properly cabled, with equal voltage losses for each string, then there is not practical limit to the maximum number of parallel strings. The easiest way to ensure that there are no voltage imbalances is to tie each string individually back to a heavy duty copper bus, and to make sure that the cable ampacity and length is the same for each string. Type of cell to use Once the minimum cell voltage has been calculated and the desired back up time has been defined it is possible to determine the most suitable cell type using the discharge tables listed at the end of this manual. Examples 1) Constant power discharge - Telecom Required Info Maximum charger voltage = 53 VDC Voltage Drop Between Load and Battery Terminals=1.24 VDC Load Cutoff Voltage = 42 VDC Nominal Load = 7300 Watts throughout the entire life Minimum site temperature = 25 C # of Strings = 1 Backup Time = 4 Hours Sizing 1) Cells per String = 23 (Charger can t reach 2.26 VPC * 24 cells) 2) Aging Factor = ) No temperature de-rate 4) Corrected Load / String = 7300 Watts * 1.25 = 9125 Watts 5) WPC = 9125 Watts / 23 Cells = 397 WPC 6) VPC at End of Discharge = (42 VDC VDC) / 23 cells = 1.88 VPC Going to the Constant Power Tables based on 4 hours, and 1.88 VPC, the GTS-1000 is selected. Since the GTS-1000 is 2 VDC per block, we would order a 23 cell system. Page 15

16 3) Constant power discharge - UPS Required Info Maximum charger voltage = 450 VDC Voltage Drop Between Inverter and Battery Terminals= 5 VDC Inverter Cutoff Voltage = 322 VDC Nominal Battery Load = 14.7 kwb (not kva!) Minimum site temperature = 25 C # of Strings = 1 Backup Time = 1 Hour Sizing 1) Cells per String Maximum = 450 VDC / 2.26 VPC = 200 cells 2) Cells per String Minimum = (322 VDC + 4 VDC) / 1.65 VPC = 198 cells 3) Aging Factor = ) No temperature de-rate 5) Corrected Load / String = 14.7 kwb * 1.25 = 18.4 kwb 6) Maximum WPC = 18,400 Watts / 198 cells = 92.9 WPC 7) Minimum WPC = 18,400 Watts / 200 cells = 92.0 WPC Going to the Constant Power Tables based on 1 hour, and 1.65 VPC, the GT12-75F is selected. Since the GT12-75F is 12 VDC per block, and six cells per block, it would be best to size the system using (33) GT12-75F s in series which gives us (198) cells. 4) Constant Current discharge - Utility Required Info Maximum charger voltage = 140 VDC Battery Side LVD Voltage = 105 VDC (negligible cable losses) Nominal Battery Load = 50 amps Minimum site temperature = 25 C # of Strings = 1 Backup Time = 1 Hour Sizing 1) Required Float Voltage = 2.26 VPC 2) Cells per String Maximum = 140 VDC / 2.26 VPC = 62 3) Cells per String = 60 4) VPC at End of Discharge = 105 VDC / 60 cells = 1.75 VPC 5) Aging Factor = ) No temperature de-rate 7) Corrected Load / String = 50 amps * 1.25 = 62.5 amps Going to the Constant Power Tables based on 1 hour, and 1.75 VPC, the GT12-105F is selected. Since the GT12-105F is 12 VDC per block, and three cells per block, 10 units would need to be ordered. IEEE Sizing The IEEE has a recommended procedure for sizing batteries. This technique takes into account dynamic or changing loads throughout a discharge. Contact Stand Power Industrial Co.,Ltd. for additional information regarding IEEE sizing methodologies. 9. APPLICABLE STANDARDS FA batteries fully comply with: British Standards N 6290 Part 4: Specification for lead acid batteries Page 16

17 IEC Part 2 Stationary lead-acid battery - General requirements and test methods - Part 2: Valve regulated types Norme CEI 21.6 fascicolo 1434: Batterie di accumulatori stazionari al piombo Eurobat Guide to the specification of valve regulated Lead acid stationary cells and batteries: Group I: 10 + year-high integrity Australian Standard AS Stationary batteries - Lead-acid - Part 2: Valve - regulated sealed type. 10. STORAGE Batteries are delivered filled, charged and ready for installation. No operation such as filling, commissioning or other type is required. They need only to be connected in series and/or in parallel as required by the particular application. If they cannot be installed immediately, batteries are to be kept in fresh, clean dry rooms. Furthermore, considering that on open circuit batteries lose part of their capacity due to self discharge (2-3% per month at 25 C), a float recharge is recommended at least every 6 months. If the batteries are stored at temperatures above 25 C, then the boost interval will be more frequent. Float recharge consists of applying a voltage of 2.26 V/cell for approx. 48 hours with a current limit of 0.25 * C 8. Never allow the terminal voltage of any blocks to go below 2.1 VPC to avoid the risk of open circuit corrosion or irreversible sulfation. Never double stack pallets Never store batteries in direct sunlight. Avoid exposure to salt laden air. 11. INSTALLATION FA valve regulated recombination batteries can be fitted on stands or into cabinets. GASTON BATTERY offers a wide selection of stands, from one tier/one row to six tiers/three rows, to suit most applications. Cabinets are available with or without circuit breaker and its relevant compartment. GASTON BATTERY does not recommend pre-installing the batteries into racks or cabinets prior to shipment. Location Considerations 1) The battery should be installed in a cool, dry location with plenty of access for installation and maintenance. Pick a location that has the temperature maintained around 25 C, that is not in direct sunlight, underneath an air duct, or any other location that would cause temperature variations within the battery. 2) The work area should have plenty of ventilation. There must be enough Air Changes per Hour (ACH) to keep hydrogen from reaching 2% by volume. Never place any batteries in a sealed cabinet or enclosure. 3) Batteries are heavy. Make sure the flooring is designed to accommodate the weight. GASTON BATTERY can provide floor loading data for each system. Make sure the floor is level. If the rack needs to be anchored for seismic ratings, then make sure the floor is rated for anchors. Unpacking 1) Carefully check the Bill of Lading against the shipment to make sure everything has arrived. Carefully inspect the batteries for any sign of damage during transit. Immediately report damage to the Carrier. Damaged batteries should be replaced immediately. 2) Batteries are very heavy, and should be lifted with care. Whenever possible, use (2) or more people to lift. 3) Care should always be taken to avoid shorting the positive and negative terminals. 4) Make sure not to throw away any of the hardware or accessories that accompanies the battery shipment. 5) Dispose of the packing material properly. Page 17

18 Loading Cabinet or Rack 1) Special precautions must be taken to avoid accidental short circuits during the installation. Only used insulated tools, and never wear jewelry. 2) Upon installation of GT-F blocs into a cabinet or on a stand, first place the single units at their correct position according to the electrical layout. 3) Start with the lowest shelf to ensure stability. Carefully preserve the sequence: positive, negative, positive, negative throughout the whole battery. 4) Flexible cable connectors for connecting from one shelf to the one below, will be applied once all the blocs have been connected. Connect inter-shelf or inter-row cable connectors at the final user s premises only. 5) Torque all terminal connections to the specified values. Improper torquing can result in loose connections or damaged terminals. Page 18

LEAD CRYSTAL. User Manual. Valve-regulated lead-crystal batteries Energy storage Cells

LEAD CRYSTAL. User Manual. Valve-regulated lead-crystal batteries Energy storage Cells Engineering Production Sales LEAD CRYSTAL Valve-regulated lead-crystal batteries Energy storage Cells User Manual www.axcom-battery-technology.de info@.axcom-battery-technology.de Chapter 1: 1. Introduction

More information

THE PROPER CHARGING OF STATIONARY LEAD-ACID BATTERIES. (YOUR BATTERY IS ONLY AS GOOD AS HOW YOU CHARGE IT.)

THE PROPER CHARGING OF STATIONARY LEAD-ACID BATTERIES. (YOUR BATTERY IS ONLY AS GOOD AS HOW YOU CHARGE IT.) THE PROPER CHARGING OF STATIONARY LEAD-ACID BATTERIES. (YOUR BATTERY IS ONLY AS GOOD AS HOW YOU CHARGE IT.) J. Allen Byrne Engineering, Training and Tech Support Manager Interstate PowerCare, a Division

More information

If you accidentally get battery acid on your skin, flush it with lots of water

If you accidentally get battery acid on your skin, flush it with lots of water RV Battery Savvy To properly maintain and extend the life of your RV batteries you need to have a basic understanding of what a battery is and how it works. Batteries used in RVs are lead acid batteries.

More information

LEAD ACID BATTERY working LIFETIME STUDY

LEAD ACID BATTERY working LIFETIME STUDY LEAD ACID BATTERY working LIFETIME STUDY Valve Regulated Lead Acid (VRLA) Batteries Overview The most common type of battery used on UPS systems and for backup of telecommunications systems. VRLA batteries

More information

Solar Wind Microhydro Water Pumping Inverters Batteries Professional system design and installation

Solar Wind Microhydro Water Pumping Inverters Batteries Professional system design and installation Solar Wind Microhydro Water Pumping Inverters Batteries Professional system design and installation BATTERY CHARGING GUIDELINES FOR GLOBAL/DAVIDSON TUBULAR PLATE BATTERIES Introduction Your Global/Davidson

More information

Substation Battery & Charger Maintenance

Substation Battery & Charger Maintenance Document title AUTHORIZED COPY Substation Battery & Charger Maintenance Document number MNT-TRMX-00015 Applies to: Keywords: Transmission Operations & Planning Department Carolinas and Florida maintenance;

More information

BATTERY CHARGING GUIDELINES FOR 6-VOLT DEEP CYCLE BATTERIES

BATTERY CHARGING GUIDELINES FOR 6-VOLT DEEP CYCLE BATTERIES BATTERY CHARGING GUIDELINES FOR 6-VOLT DEEP CYCLE BATTERIES Introduction Your 6-volt deep cycle battery set has been specially formulated for long cycle life and has particular voltage and specific gravity

More information

NorthStar Battery (NSB) Telecom Installation and Operation Guide

NorthStar Battery (NSB) Telecom Installation and Operation Guide 15DOC0020 NorthStar Battery (NSB) Telecom Installation and Operation Guide Contents 0 Definitions... 3 1 Battery Safety... 3 1.1 Old Batteries... 3 2 Handling... 4 2.1 Receiving the shipment... 4 2.2 Do...

More information

Height w/o Terminals (in)

Height w/o Terminals (in) EaglePicher Technologies, LLC Commercial Power P.O. Box 47 Joplin, MO 6482 (417) 623-8 inquiry.carefree@eaglepicher.com Carefree Sealed Lead Acid (SLA) MSDS EaglePicher s Carefree lead acid batteries are

More information

Technical Handbook Valve-Regulated Lead-Acid Batteries

Technical Handbook Valve-Regulated Lead-Acid Batteries Technical Handbook Valve-Regulated Lead-Acid Batteries Aerial view of the italian factory in Avezzano A ll FIAMM-GS batteries have been specifically developed to enhance economy of operation, reliability

More information

Constant Voltage Charger Selection for VRLA Batteries

Constant Voltage Charger Selection for VRLA Batteries TECHNICAL BULLETIN 41-2129 Constant Voltage Charger Selection for VRLA Batteries Please Note: The information in this technical bulletin was developed for C&D Dynasty 12 Volt VRLA products. While much

More information

NP Series VALVE REGULATED LEAD-ACID BATTERIES

NP Series VALVE REGULATED LEAD-ACID BATTERIES NP Series VALVE REGULATED LEAD-ACID BATTERIES NP RELIABILITY IS YOUR SECURITY Yuasa NP, NPC and NPH Batteries Utilising the latest advance design Oxygen Recombination Technology, Yuasa have applied their

More information

10 Year VRLA Battery Periodic Maintenance Instructions

10 Year VRLA Battery Periodic Maintenance Instructions TECHNICAL BULLETIN 41-7546 Valve Regulated Lead Acid Battery 20 to 200 ampere-hours capacity 10 Year VRLA Battery Periodic Maintenance Instructions 41-7546/0213/CD www.cdtechno.com General Information

More information

Tel.X Ni-Cd battery. The compact maintenance-free solution for telecom networks

Tel.X Ni-Cd battery. The compact maintenance-free solution for telecom networks Tel.X Ni-Cd battery The compact maintenance-free solution for telecom networks Tel.X, delivering high-energy performance in a compact maintenance-free package Tel.X: guaranteed power continuity for remote

More information

SOLAR PV SYSTEM MAINTENANCE GUIDE

SOLAR PV SYSTEM MAINTENANCE GUIDE SOLAR PV SYSTEM MAINTENANCE GUIDE GUYANA HINTERLANDS STAND-ALONE SOLAR PV INSTALLATIONS IMPROVING HEALTH FACILITY INFRASTRUCTURE (IHFI) GUYANA CONTRACT NO. EPP-I-00-03-00008-00, TASK ORDER 07 APRIL 2013

More information

DataSafe HX Top Terminated Batteries 6 and 12 Volt HX

DataSafe HX Top Terminated Batteries 6 and 12 Volt HX DATASAFE HX TOP TERMINATED BATTERIES DataSafe HX Top Terminated Batteries 6 and 12 Volt HX Available exclusively from EnerSys, the world leader in stored power solutions. DataSafe HX Top Terminated Batteries.

More information

CHARGING METHODS. Methods of Charging the Valve Regulated (Sealed) Lead-Acid Battery. 19 Valve Regulated (Sealed) Lead-Acid Batteries

CHARGING METHODS. Methods of Charging the Valve Regulated (Sealed) Lead-Acid Battery. 19 Valve Regulated (Sealed) Lead-Acid Batteries CHARGNG METHODS Methods of Charging the alve Regulated (Sealed) Lead-Acid Battery For charging the alve Regulated (Sealed) lead-acid battery, a well-matched charger should be used because the capacity

More information

Effects of AC Ripple Current on VRLA Battery Life. A Technical Note from the Experts in Business-Critical Continuity

Effects of AC Ripple Current on VRLA Battery Life. A Technical Note from the Experts in Business-Critical Continuity Effects of AC Ripple Current on VRLA Battery Life A Technical Note from the Experts in Business-Critical Continuity Introduction Given the importance of battery life to UPS system users and the fact that

More information

Height w/o Terminals (in)

Height w/o Terminals (in) EaglePicher Technologies, LLC Commercial Power P.O. Box 47 Joplin, MO 6482 (417) 623-8 inquiry.carefree@eaglepicher.com Carefree Sealed Lead Acid (SLA) MSDS EaglePicher s Carefree lead acid batteries are

More information

BATTERY BASICS. This Automotive Series 12-volt Lead Acid BATTERY BASICS has been developed by. Kevin R. Sullivan

BATTERY BASICS. This Automotive Series 12-volt Lead Acid BATTERY BASICS has been developed by. Kevin R. Sullivan BATTERY BASICS This Automotive Series 12-volt Lead Acid BATTERY BASICS has been developed by Kevin R. Sullivan Professor of Automotive Technology Skyline College All Rights Reserved v1.1 Visit us on the

More information

12 Volt 30 Amp Digital Solar Charge Controller

12 Volt 30 Amp Digital Solar Charge Controller 12 Volt 30 Amp Digital Solar Charge Controller User s Manual WARNING Read carefully and understand all INSTRUCTIONS before operating. Failure to follow the safety rules and other basic safety precautions

More information

Battery Handbook. By: RON SMITH

Battery Handbook. By: RON SMITH Battery Handbook By: RON SMITH Information compiled from the Battery Charger Handbook and the Battery Handbook written by Alvin G. Graham, Chief Engineer, Ratelco Electronics Inc. Introduction The purpose

More information

Carefree Sealed Lead Acid (SLA) MSDS

Carefree Sealed Lead Acid (SLA) MSDS EaglePicher Technologies, LLC Commercial Power P.O. Box 47 Joplin, MO 6482 (417) 623-8 inquiry.carefree@eaglepicher.com Carefree Sealed Lead Acid (SLA) MSDS EaglePicher s Carefree lead acid batteries are

More information

BC-5000 OPERATIONS MANUAL BATTERY CAPACITY TESTER COFKO LLC.

BC-5000 OPERATIONS MANUAL BATTERY CAPACITY TESTER COFKO LLC. BC-5000 BATTERY CAPACITY TESTER OPERATIONS MANUAL COFKO LLC. COPYRIGHT 2010 1 UNPACKING As you unpack your new BC-5000 battery capacity tester, inspect the tester for signs of shipping damage. If shipping

More information

OUTPUT CABLE CONNECTIONS:

OUTPUT CABLE CONNECTIONS: Tender Plus: Models: 12V1.25A and 6V1.25A The Tender Plus 12 Volt, 1.25 Amp 6 Volt, 1.25 Amp GENERAL DESCRIPTION: The Tender Plus battery charger is a desktop, portable, linear power converter that has

More information

CHARGING SYSTEMS INTERNATIONAL

CHARGING SYSTEMS INTERNATIONAL CHARGING SYSTEMS INTERNATIONAL INSTALLATION AND OPERATING INSTRUCTIONS FOR THE FOLLOWING BATTERY CHARGING SYSTEMS: MODELS MAX AMPS/BANK NO. OF BANKS BATTERY SYSTEM PRO XL 6 1 12 DUAL PRO XL 6 2 12/24 PRO

More information

Standard Operating Procedure (SOP) Car/Truck Battery Safety

Standard Operating Procedure (SOP) Car/Truck Battery Safety INTRODUCTION Lead-acid batteries contain sulfuric acid and only trained and authorized personnel should handle them. When talking about lead-acid batteries, people usually call sulfuric acid "battery acid"

More information

Features of Power-Sonic Sealed Lead Acid Batteries...1. Battery Construction...2. Theory of Operation...3 & 4. Battery Capacity...

Features of Power-Sonic Sealed Lead Acid Batteries...1. Battery Construction...2. Theory of Operation...3 & 4. Battery Capacity... Table of Contents Features of Power-Sonic Sealed Lead Acid Batteries...1 Battery Construction...2 Theory of Operation...3 & 4 Battery Capacity...5 & 6 Battery Capacity Selector...7 Performance Data...8

More information

Charger Output AC Ripple Voltage and the affect on VRLA batteries

Charger Output AC Ripple Voltage and the affect on VRLA batteries TECHNICAL BULLETIN 41-2131 Charger Output AC Ripple Voltage and the affect on VRLA batteries Please Note: The information in this technical bulletin was developed for C&D Dynasty 12 Volt VRLA products.

More information

NorthStar Battery (NSB) Telecom Red Application, Installation, and Operation Manual

NorthStar Battery (NSB) Telecom Red Application, Installation, and Operation Manual NorthStar Battery (NSB) Telecom Red Application, Installation, and Operation Manual To help us better serve you, please visit our web site at /survey and complete our Customer Survey. We value and appreciate

More information

875 Dearborn Drive Columbus, Ohio 43085 Tel: (614) 846-7500 Fax: (614) 885-3990

875 Dearborn Drive Columbus, Ohio 43085 Tel: (614) 846-7500 Fax: (614) 885-3990 Selection and Sizing of Batteries for UPS Backup 875 Dearborn Drive Columbus, Ohio 43085 Tel: (614) 846-7500 Fax: (614) 885-3990 Selection and Sizing of Batteries for UPS Backup Abstract Introduction Battery

More information

Amps Per Bank. Total Output. Battery System. Model Name. 6 amps 12 amps 10 amps 20 amps 30 amps 40 amps 15 amps 30 amps 45 amps

Amps Per Bank. Total Output. Battery System. Model Name. 6 amps 12 amps 10 amps 20 amps 30 amps 40 amps 15 amps 30 amps 45 amps Model Name Total Output Amps Per Bank Battery System Pro XL Dual Pro XL Pro SE Dual Pro SE Three Bank Pro SE Four Bank Pro SE Pro Charger Dual Pro Charger Three Bank Pro Charger 6 amps 12 amps 10 amps

More information

Lead Acid Battery Terminology Glossary

Lead Acid Battery Terminology Glossary TECHNICAL BULLETIN 41-7745 Lead Acid Battery Terminology Glossary Please Note: The information in this technical bulletin was developed for C&D Dynasty 12 Volt VRLA products. While much of the information

More information

MULTI XS 3600. Battery charger. For lead-acid batteries 1,2-120Ah

MULTI XS 3600. Battery charger. For lead-acid batteries 1,2-120Ah MULTI XS 3600 Battery charger For lead-acid batteries 1,2-120Ah User s Manual and a guide to professional battery charging For Starter/Deep Cycle batteries EN INTRODUCTION Congratulations on your purchase

More information

TELEDYNE BATTERY PRODUCTS. INSTRUCTIONS FOR CONTINUED AIRWORTHINESS and COMPONENT MAINTENANCE MANUAL. For

TELEDYNE BATTERY PRODUCTS. INSTRUCTIONS FOR CONTINUED AIRWORTHINESS and COMPONENT MAINTENANCE MANUAL. For TELEDYNE BATTERY PRODUCTS INSTRUCTIONS FOR CONTINUED AIRWORTHINESS and COMPONENT MAINTENANCE MANUAL For TSO-C173/C173a Authorized (GILL ) 7000 Series LT Valve-Regulated Lead-Acid Aircraft Batteries REFER

More information

VRLA BATTERIES AUGUST

VRLA BATTERIES AUGUST CHARGNG METHODS Methods of Charging the alve-regulated Lead-Acid Battery For charging the valve-regulated lead-acid battery, a well-matched charger should be used because the capacity or life of the battery

More information

Spec. No. ICR18650-26C Version No. 0.0

Spec. No. ICR18650-26C Version No. 0.0 1. Scope This product specification has been prepared to specify the rechargeable lithium-ion cell 2. Description and Model 2.1 Description Cell (lithium-ion rechargeable cell) 2.2 Model ICR18650-26C 3.

More information

POWER TO GET THE JOB DONE

POWER TO GET THE JOB DONE 52720 1.5 AMP SLOW 12 VOLT BATTERY CHARGER OWNER S MANUAL KEEPS BATTERIES FULLY CHARGED IN STORAGE Automatic over-charging protection Short circuit protection Reverse hook-up protection Overheat protection

More information

Ametek Prestolite Power AC power / Charger / Battery terms

Ametek Prestolite Power AC power / Charger / Battery terms Ametek Prestolite Power AC power / Charger / Battery terms Basic Values: Voltage: The potential difference at the battery (DC) or at the charger input (AC) measured in Volts. Current: The rate of flow

More information

12 Volt 30 Amp Digital Solar Charge Controller Installation & Operation Manual

12 Volt 30 Amp Digital Solar Charge Controller Installation & Operation Manual 12 Volt 30 Amp Digital Solar Charge Controller Installation & Operation Manual This 30Amp charge controller is designed to protect your 12Volt Lead-acid or Gel-cell battery from being overcharge by solar

More information

MOBILE DC POWER SYSTEMS FOR SUBSTATION APPLICATIONS

MOBILE DC POWER SYSTEMS FOR SUBSTATION APPLICATIONS MOBILE DC POWER SYSTEMS FOR SUBSTATION APPLICATIONS Gary P. Guagliardi Director Sales & Marketing HindlePower, Inc. Easton, PA Introduction This paper explores the use of mobile DC power systems for three

More information

Installation and Operating Instructions (for chargers shown below)

Installation and Operating Instructions (for chargers shown below) Installation and Operating Instructions (for chargers shown below) For additional information please call our Technical Support Group 800.742.2740 PRO CHARGING SYSTEMS, LLC 1551 Heil Quaker Boulevard,

More information

Thyristor-controlled power supplies and battery chargers

Thyristor-controlled power supplies and battery chargers Thyristor-controlled power supplies and battery chargers Input voltage: 115 / 230 VAC, single phase, 50 / 60 Hz or 208 / 400 / 480 VAC, three phases, 50 / 60 Hz Output voltage: 12 / 24 / 48 / 60 / 72 /

More information

Tel.X Ni-Cd battery. The compact solution for stationary applications

Tel.X Ni-Cd battery. The compact solution for stationary applications Tel.X NiCd battery The compact solution for stationary applications Tel.X, delivering highenergy performance in a compact maintenancefree package Tel.X: guaranteed power continuity for remote or hard to

More information

TROJAN BATTERY USER S GUIDE

TROJAN BATTERY USER S GUIDE Congratulations on your purchase from Trojan Battery Company, the manufacturer of the world s most trusted deep cycle batteries. The battery you purchased was engineered by Trojan to deliver superior power,

More information

Stationary Storage Battery Systems

Stationary Storage Battery Systems ORANGE COUNTY FIRE AUTHORITY Planning & Development Services Section 1 Fire Authority Road, Building A Irvine, CA 92602 714-573-6100 www.ocfa.org Stationary Storage Battery Systems Guideline G-10 Date:

More information

New York City Fire Code & Energy Storage Systems

New York City Fire Code & Energy Storage Systems New York City Fire Code & Energy Storage Systems Winnie Lei on behalf of Tamara Saakian, P.E. Director of Engineering & Technology Management Technology Management Unit Bureau of Fire Prevention Fire Department

More information

Battery Technology for Data Centers and Network Rooms: Lead-Acid Battery Options

Battery Technology for Data Centers and Network Rooms: Lead-Acid Battery Options Battery Technology for Data Centers and Network Rooms: Lead-Acid Battery Options By Stephen McCluer White Paper #30 Revision 11 Executive Summary The lead-acid battery is the predominant choice for Uninterruptible

More information

Batteries and inverters

Batteries and inverters Batteries and other energy storage devices store energy so that it can be used when needed. In a stand-alone power system, the energy stored in batteries can be used when energy demand exceeds the output

More information

OWNER S MANUAL. Model AE150/AE300/AE500 1.5AMP MULTI-USE SMART BATTERY CHARGER READ ENTIRE MANUAL BEFORE USING THIS PRODUCT

OWNER S MANUAL. Model AE150/AE300/AE500 1.5AMP MULTI-USE SMART BATTERY CHARGER READ ENTIRE MANUAL BEFORE USING THIS PRODUCT Model AE150/AE300/AE500 MULTI-USE SMART BATTERY CHARGER Certified by Californiia BCS Regulations AE300E AE500E 5AMP MULTI-USE AUTOMOTIVE BATTERY CHARGER 3AMP MULTI-USE SMART BATTERY CHARGER AE500E 5AMP

More information

EPSOLAR LS0512R / LS0524R. Solar Light Controller INSTRUCTION MANUAL. Please read this manual carefully before using the product!

EPSOLAR LS0512R / LS0524R. Solar Light Controller INSTRUCTION MANUAL. Please read this manual carefully before using the product! EPSOLAR LS0512R / LS0524R Solar Light Controller INSTRUCTION MANUAL Please read this manual carefully before using the product! LandStar LS0512R / LS0524R Solar Light Controller Nominal system voltage

More information

400 Amp Rechargeable Jump Start System RAC-HP082

400 Amp Rechargeable Jump Start System RAC-HP082 400 Amp Rechargeable Jump Start System RAC-HP082 MAINTENANCE Always inspect the tool before use to ensure the cables are in good condition and the clamps are clean and free from corrosion. Keep clean by

More information

Solar Controller / Battery Charger User s Manual

Solar Controller / Battery Charger User s Manual Solar Controller / Battery Charger User s Manual 1 Congratulations! You have made an excellent choice by purchasing this high quality KORR PWM solar controller which has been manufactured to the highest

More information

RG 7 SERIES AIRCRAFT BATTERY OWNER/OPERATOR MANUAL

RG 7 SERIES AIRCRAFT BATTERY OWNER/OPERATOR MANUAL RG 7 SERIES AIRCRAFT BATTERY OWNER/OPERATOR MANUAL CONCORDE BATTERY CORPORATION 2009 San Bernardino Road West Covina, CA 91790 Phone: 626-813-1234 www.concordebattery.com Document No. 5-0324 Revision C

More information

Temperature Compensated Charging of Lead Acid Batteries

Temperature Compensated Charging of Lead Acid Batteries Technical Note Batteries 512-0101-01-01 Rev 1 Temperature Compensated Charging of Lead Acid Batteries Introduction To ensure optimum charging of lead acid batteries, the charge voltages should be adjusted

More information

MANUAL D250S DUAL. Solar panel + Vehicle ground/solar panel

MANUAL D250S DUAL. Solar panel + Vehicle ground/solar panel MANUAL CONGRATULATIONS on the purchase of your new CTEK professional battery management unit. This unit is part of a range of professional battery chargers from CTEK SWEDEN AB. It represents the latest

More information

LITHIUM BATTERY CR123A SPECIFICATION

LITHIUM BATTERY CR123A SPECIFICATION LITHIUM BATTERY CR123A SPECIFICATION Date: April 24, 2012 Approved by: Scotty Scott PANASONIC ENERGY CORPORATION OF AMERICA LITHIUM BATTERY DIVISION 1. Designation : CR123A 2. Nominal Voltage : 3 V 3.

More information

IMPORTANT SAFETY INSTRUCTIONS WARNING READ AND SAVE THESE OPERATING AND SAFETY INSTRUCTIONS BEFORE USING THIS HEATER.

IMPORTANT SAFETY INSTRUCTIONS WARNING READ AND SAVE THESE OPERATING AND SAFETY INSTRUCTIONS BEFORE USING THIS HEATER. THERMAWAVE CERAMIC HEATER Model HZ-850 Series Model HZ-860 Series IMPORTANT SAFETY INSTRUCTIONS WARNING READ AND SAVE THESE OPERATING AND SAFETY INSTRUCTIONS BEFORE USING THIS HEATER. Warning Failure to

More information

MANUAL. * Supply plugs may differ to suit your wall socket. EN 3. Continue to press the MODE-button to combine charging program with charging options.

MANUAL. * Supply plugs may differ to suit your wall socket. EN 3. Continue to press the MODE-button to combine charging program with charging options. MX MANUAL CONGRATULATIONS to the purchase of your new professional switch mode battery charger. This charger is included in a series of professional chargers from CTEK SWEDEN AB and represents the latest

More information

Switch Mode, Automatic, Lead Acid Battery Charger 3 Stage (IUoU)

Switch Mode, Automatic, Lead Acid Battery Charger 3 Stage (IUoU) AUTOMATIC BATTERY CHARGER Switch Mode, Automatic, Lead Acid Battery Charger 3 Stage (IUoU) Model No. SEC - 1260A SEC - 1280A SEC - 2440A Item No. 08021 08061 08077 OWNER S MANUAL Please read this manual

More information

Installation and Operating Instructions (for chargers shown below)

Installation and Operating Instructions (for chargers shown below) Installation and Operating Instructions (for chargers shown below) For additional information please call our Technical Support Group 800.742.2740 PRO CHARGING SYSTEMS, LLC 1551 Heil Quaker Boulevard,

More information

DOE HANDBOOK PRIMER ON LEAD-ACID STORAGE BATTERIES. U.S. Department of Energy Washington, D.C. 20585 METRIC. DOE-HDBK-1084-95 September 1995

DOE HANDBOOK PRIMER ON LEAD-ACID STORAGE BATTERIES. U.S. Department of Energy Washington, D.C. 20585 METRIC. DOE-HDBK-1084-95 September 1995 TS METRIC DOE-HDBK-1084-95 September 1995 DOE HANDBOOK PRIMER ON LEAD-ACID STORAGE BATTERIES U.S. Department of Energy Washington, D.C. 20585 FSC-6910 DISTRIBUTION STATEMENT A. Approved for public release;

More information

ACHIEVING CHARGE QUALITY FOR LEAD ACID BATTERIES IN INDUSTRIAL MOTIVE APPLICATIONS

ACHIEVING CHARGE QUALITY FOR LEAD ACID BATTERIES IN INDUSTRIAL MOTIVE APPLICATIONS ACHIEVING CHARGE QUALITY FOR LEAD ACID BATTERIES IN INDUSTRIAL MOTIVE APPLICATIONS Delta-Q Technologies success as an industrial battery charger supplier to original equipment manufacturers (OEMs) has

More information

Manual. Solar Fountain Mobile Phone Charger

Manual. Solar Fountain Mobile Phone Charger EN Manual Solar Fountain Mobile Phone Charger Copyrights 2008 Victron Energy B.V. All Rights Reserved This publication or parts thereof may not be reproduced in any form, by any method, for any purpose.

More information

BATTERIES. Battery Types. General. Battery Functions

BATTERIES. Battery Types. General. Battery Functions General The battery is the primary "source" of electrical energy on Toyota vehicles. It stores chemicals, not electricity. Two different types of lead in an acid mixture react to produce an electrical

More information

TECHNICAL MANUAL For Sun Xtender Batteries

TECHNICAL MANUAL For Sun Xtender Batteries TECHNICAL MANUAL For Sun Xtender Batteries Manufactured by: Concorde Battery Corporation 2009 San Bernardino Road West Covina, CA 91790 Phone 626-813-1234 Fax 626-813-1235 www.sunxtender.com Document No.

More information

ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013

ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013 ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013 READ CAREFULLY These instructions are intended to cover good practices in

More information

MULTI XS 4003 Battery charger

MULTI XS 4003 Battery charger MULTI XS 4003 Battery charger For lead-acid batteries 1.2 140Ah FI NO DK SE NL QUICK GUIDE EN DE IT ES FR Model 1035 User s Manual and a guide to professional battery charging for starter/deep cycle batteries.

More information

3000W Power Inverter

3000W Power Inverter 3000W Power Inverter OWNER S MANUAL Model number-4573000 TO REDUCE THE RISK OF INJURY, USER MUST READ AND UNDERSTAND THIS INSTRUCTIONAL MANUAL. THIS MANUAL CONTAINS IMPORTANT INFORMATION REGARDING THE

More information

PRODUCT SAFETY DATA SHEET

PRODUCT SAFETY DATA SHEET Page 1 / 5 This product is a consumer product which is used in a hermetically sealed state. So, it is not an object of the SDS system. This document is provided to customers as reference information for

More information

Mobile Data Power Model: MDP-25

Mobile Data Power Model: MDP-25 Mobile Data Power Model: MDP-25 Topic Section Features... 2 Operational Features Summary... 2 Back-up Battery Power Internal Charger Voltage Spike Protection RF Noise Filtering Warning of Imminent Loss

More information

Battery Technology for Data Centers and Network Rooms: Ventilation of Lead-Acid Batteries

Battery Technology for Data Centers and Network Rooms: Ventilation of Lead-Acid Batteries Battery Technology for Data Centers and Network Rooms: Ventilation of Lead-Acid White Paper 34 Revision 3 by Stephen McCluer > Executive summary Lead-acid batteries are the most widely used method of energy

More information

Installation Instructions for Alarm Module Kit A043F059

Installation Instructions for Alarm Module Kit A043F059 Instruction Sheet 07-2013 Installation Instructions for Alarm Module Kit A043F059 1 Introduction The information contained within is based on information available at the time of going to print. In line

More information

BATTERY SERVICE. This Automotive Series BATTERY SERVICE has been developed by. Kevin R. Sullivan. Professor of Automotive Technology Skyline College

BATTERY SERVICE. This Automotive Series BATTERY SERVICE has been developed by. Kevin R. Sullivan. Professor of Automotive Technology Skyline College BATTERY SERVICE This Automotive Series BATTERY SERVICE has been developed by Kevin R. Sullivan Professor of Automotive Technology Skyline College All Rights Reserved v1.1 Visit us on the web at: www.autoshop101.com

More information

National- Spencer Inc.

National- Spencer Inc. 9-27-2010 National- Spencer Inc. 19.2V HEAVY DUTY GREASE GUN PRODUCT SPECIFICATION Charger Input Power 110 VAC Battery Output Power 19.2V Battery Capacity 1500 MAH Battery Pack Charge Time 1 Hour Maximum

More information

Battery Cell Balancing: What to Balance and How

Battery Cell Balancing: What to Balance and How Battery Cell Balancing: What to Balance and How Yevgen Barsukov, Texas Instruments ABSTRACT Different algorithms of cell balancing are often discussed when multiple serial cells are used in a battery pack

More information

Lithium Ion Battery Specifications

Lithium Ion Battery Specifications Lithium Ion Battery Specifications Type: Cylindrical Lithium Iron Phosphate Battery Mode: LFP-26650-3300 AA Portable Power Corp. Prepared by Checked by Approved by 1 . Product Specifications Type ------------

More information

Li-ion Rechargeable Battery. Specification

Li-ion Rechargeable Battery. Specification Customer: Specification Model: GMB043450S Prepared By/Date Checked By/Date Approved By/Date Note:1.Kindly please sign on the above and send it back to us if the sample is approved. 2.Kindly please contact

More information

Odyssey of the Mind Technology Fair. Simple Electronics

Odyssey of the Mind Technology Fair. Simple Electronics Simple Electronics 1. Terms volts, amps, ohms, watts, positive, negative, AC, DC 2. Matching voltages a. Series vs. parallel 3. Battery capacity 4. Simple electronic circuit light bulb 5. Chose the right

More information

Battery Discharge Testing: Implementing NERC Standards and Field Experiences

Battery Discharge Testing: Implementing NERC Standards and Field Experiences Battery Discharge Testing: Implementing NERC Standards and Field Experiences Dinesh Chhajer Applications Engineer Megger Dallas, TX 75237 Robert Foster Applications Engineer Abstract Periodic testing and

More information

DC GROUND FAULT DETECTION PROVIDED FOR UNINTERRUPTIBLE POWER SUPPLIES

DC GROUND FAULT DETECTION PROVIDED FOR UNINTERRUPTIBLE POWER SUPPLIES DC GROUND FAULT DETECTION PROVIDED FOR UNINTERRUPTIBLE POWER SUPPLIES Edward P. Rafter, P. E. Principal Tier IV Consulting Group Lee s Summit, Missouri 64064 INTRODUCTION There are concerns among owners

More information

Battery Power Inverters

Battery Power Inverters Battery Power Inverters Renogy 500W 1000W 2000W Pure Sine Wave Inverter Manual 2775 E. Philadelphia St., Ontario, CA 91761 1-800-330-8678 1 Version 1.1 Important Safety Instructions Please save these instructions.

More information

SBC90. Abrasive Blast Cabinet Assembly & Operating Instructions

SBC90. Abrasive Blast Cabinet Assembly & Operating Instructions SBC90 Abrasive Blast Cabinet Assembly & Operating Instructions READ ALL INSTRUCTIONS AND WARNINGS BEFORE USING THIS PRODUCT. SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE. This manual provides important

More information

Application Manual. Nickel Cadmium 11/06/01 Page 1 of 12

Application Manual. Nickel Cadmium 11/06/01 Page 1 of 12 Page 1 of 12 Nickel Cadmium Batteries Application Manual The nickel-cadmium battery is a remarkable device. More than fifty years of successful use has proved this point. Nickel-cadmium batteries may be

More information

Advanced Fuel Cells A Reliable and Green Solution to Reduce Operating Expenses of Telecommunication Networks

Advanced Fuel Cells A Reliable and Green Solution to Reduce Operating Expenses of Telecommunication Networks Advanced Fuel Cells A Reliable and Green Solution to Reduce Operating Expenses of Telecommunication Networks White Paper Anil K. Trehan, Vice President, Energy Solutions CommScope, Inc. May 28, 2013 Contents

More information

BATTERY CHARGER OWNER S MANUAL

BATTERY CHARGER OWNER S MANUAL SAVE THESE INSTRUCTIONS This manual contains important safety and operating instructions for the automatic battery charger. Do not expose charger to rain or snow. Do not use and an attachment not recommended

More information

Battery Technology for Data Centers and Network Rooms: Fire Safety Codes USA

Battery Technology for Data Centers and Network Rooms: Fire Safety Codes USA Battery Technology for Data Centers and Network Rooms: Fire Safety Codes USA By Stephen McCluer White Paper #31 Revision 6 Executive Summary Fire safety regulations and their application to UPS battery

More information

Installation and Operation Guide for PD4000 Series Power Control Center

Installation and Operation Guide for PD4000 Series Power Control Center Extended warranties are available for purchase at www.progressivedyn.com Installation and Operation Guide for PD4000 Series Power Control Center Member Thank you for selecting Progressive Dynamics as your

More information

LS1024B / LS2024B/ LS3024B. Solar Charge Controller USER MANUAL

LS1024B / LS2024B/ LS3024B. Solar Charge Controller USER MANUAL EPSOLAR LS1024B / LS2024B/ LS3024B Solar Charge Controller USER MANUAL Thank you very much for selecting our product! This manual offers important information and suggestions with respect to installation,

More information

Table Of Contents 6 6 6 7 7 8 8 9-11 12 12-13 14 15 16 17 18 19 20-21 22 22 23 24 24 24

Table Of Contents 6 6 6 7 7 8 8 9-11 12 12-13 14 15 16 17 18 19 20-21 22 22 23 24 24 24 USER S GUIDE Table Of Contents Package Contents Accessories: Sold Separately Product Specifications Intended Use Compatibility ResMed Device Warning Battery Pack Run Times Power Backup Usage Getting Started

More information

CHAPTER 5 PHOTOVOLTAIC SYSTEM DESIGN

CHAPTER 5 PHOTOVOLTAIC SYSTEM DESIGN CHAPTER 5 PHOTOVOLTAIC SYSTEM DESIGN 5.1 Introduction So far in the development of this research, the focus has been to estimate the available insolation at a particular location on the earth s surface

More information

Wet vs Sealed Batteries A detailed explanation of the differences between charging "Wet" Batteries and charging "Sealed" Batteries.

Wet vs Sealed Batteries A detailed explanation of the differences between charging Wet Batteries and charging Sealed Batteries. Service Bulletins & Tips February 2006 Volume 3, Issue 1 In this issue: Wet vs Sealed Batteries A detailed explanation of the differences between charging "Wet" Batteries and charging "Sealed" Batteries.

More information

Model HPX10 Series Automatic Battery Charger User s Manual Rev. 1.0 October 17, 2006

Model HPX10 Series Automatic Battery Charger User s Manual Rev. 1.0 October 17, 2006 B R A N D Model HPX10 Series Automatic Battery Charger User s Manual Rev. 1.0 October 17, 2006 For Sales, Support and Service phone: 407-331-4793 fax: 407-331-4708 website: www.xenotronix.com email: information@xenotronix.com

More information

Small Traction powerbloc powerbloc dry Hawker XFC TM

Small Traction powerbloc powerbloc dry Hawker XFC TM Small Traction powerbloc powerbloc dry Hawker XFC TM Bigger power for small traction Powerbloc Powerbloc dry Hawker XFC TM Powerbloc, powerbloc dry and Hawker XFC are ranges of bloc batteries for all applications

More information

AUTOMATIC BEST BATTERY SELECTOR INSTALLATION & OPERATION BBS-1600 BBS-1600E

AUTOMATIC BEST BATTERY SELECTOR INSTALLATION & OPERATION BBS-1600 BBS-1600E AUTOMATIC BEST BATTERY SELECTOR INSTALLATION & OPERATION BBS-1600 BBS-1600E SENS part no: 101314 Document revision: F DCN No. 106811 Date 8/3/15 1840 Industrial Circle Longmont, CO 80501 Fax: (303) 678-7504

More information

Eveready Carbon Zinc (Zn/MnO ² ) Application Manual

Eveready Carbon Zinc (Zn/MnO ² ) Application Manual Page 1 of 13 Eveready Carbon Zinc (Zn/MnO ² ) Application Manual Eveready carbon zinc batteries are marketed in two basic categories--classic and Super Heavy Duty. The Classic category, our least expensive

More information

13 Watt PORTABLE SOLAR POWER KIT

13 Watt PORTABLE SOLAR POWER KIT 3 Watt PORTABLE SOLAR POWER KIT User s Manual Thank you for purchasing a Sunforce Portable Solar Power Kit. Please read these instructions carefully and thoroughly before using the product. Your new Portable

More information

TROUBLESHOOTING GUIDE

TROUBLESHOOTING GUIDE TROUBLESHOOTING GUIDE LESTRONIC II BATTERY CHARGER FOR MOTIVE POWER BATTERIES PLEASE SAVE THESE IMPORTANT SAFETY AND OPERATING INSTRUCTIONS For correct operation of the equipment, it is important to read

More information

Title Li-ion Battery Specifications (Steel) Page 1/11

Title Li-ion Battery Specifications (Steel) Page 1/11 Title Li-ion Battery Specifications (Steel) Page 1/11 1. Scope This Specification is applied to rechargeable lithium ion battery cell of the following mentioned type for various applications in mobile

More information

User s Manual Before using the inverter, you need to read and save the safety instructions.

User s Manual Before using the inverter, you need to read and save the safety instructions. User s Manual Before using the inverter, you need to read and save the safety instructions. STI SERIES (STI200, STI300, STI500, STI700, STI1000) Power Frequency Pure Sine Wave Inverter The information

More information