BLOW DOWN. PURPOSE: To control the concentration of one or more natural components of boiler water. * * * * * * * * * * * * *
|
|
- Joella Howard
- 7 years ago
- Views:
Transcription
1 BLOW DOWN PURPOSE: To control the concentration of one or more natural components of boiler water. * * * * * * * * * * * * * Boiler feed water usually contains dissolved or suspended materials introduced with raw or treated make-up water or picked up by condensate returns. These solids concentrate as evaporation proceeds in the boiler. Unless something is done to keep the boiler water solids from concentrating excessively, serious difficulties may result. The boiler water may take on a foaming character which causes water to be entrained in the out going steam; this is the most immediate effect of excessive solids concentrations. Sludge may build up abnormally to such an extent that it interferes with the heat transfer, hampers circulation, or necessitates an undue amount of boiler cleaning. Boiler water silica, if allowed to concentrate without restraint, may participate in formation of siliceous scale, or it may leave the boiler as an entrained or volatilized contaminant in the steam, especially in high pressure boilers. Blow down represents the most direct -- often the only-- means for effectively controlling the concentration of solids in boiler water. When properly controlled, blow down removes solids in the concentrated boiler water solution at exactly the same rate with which they are introduced. Blow down is regulated to avoid exceeding some specified maximum concentration of either total dissolved solids, iron silica or alkalinity. suspended solids, Although the permissible maximum concentrations are lower with increase in boiler pressures, there actually is no simple rule for judging what the limiting concentrations should be in any given boiler. It depends upon steam pressure, steam temperature (whether saturated or super heated), the type of boiler involved, steam purification facilities in the steam drum, method of blow down (whether manual or continuous), water level control, the nature of fluctuations in boiler load, the purposes for which steam is used, and the kind of turbines involved, if any -- plus, of course, the kinds and the amounts of impurities in the boiler feed water. 1
2 As a guide for blow down control in your particular boilers, maximum and minimum concentrations have been recommended for one or more components of the boiler water. You may be controlling blow down directly on the basis of the test for boiler water alkalinity, silica, or solids (dissolved, suspended, or total). Or you may be testing for some reference constituent such as chloride, sulfate, or total electrolytes (conductivity); by regulating blow down so as to keep the reference constituent within some specified concentration range, you automatically maintain proper control over other constituents in the boiler water (dissolved solids, suspended solids, total solids, or silica, whichever the case may be. In any case, the blow down rate must be increased whenever the maximum limiting concentration is approached or exceeded. This may sometimes call for emergency manual blow downs, for operating with concentrations that are to high can be seriously detrimental to boiler and plant performance. Minimum limiting concentrations are specified to avoid undue wastage of water, heat and treating chemicals through blow down. In general, the range of permissible concentrations is fixed at the highest level considered to be safe for the particular boilers involved. Antifoam materials are sometimes used to allow an increase towards the tolerance for higher solids concentrations. This allows a reduction in blow down losses. Antifoam treatment is economically justified for this purpose if the cost of such treatment does not off set the resulting savings in blow down. The risk of serious consequences, however, can not too great if there is a sudden and unavoidable interruption in antifoam feed. Blow down losses can be reduced, also, by the use of pre-treating equipment to remove raw water constituents which otherwise would have to be removed through boiler blow down. This is a very important economic consideration in the selection of pre-treatment equipment. Good blow down control is one of the most important requirements in boiler water conditioning. If blow down is not regulated properly, it will be almost impossible to maintain satisfactory control over the chemical treatment program. Blow down has a direct influence over the concentrations of all constituents in the boiler water. Take particular pains to stay within the limiting concentrations specified for blow down. A continuous blow down valve is the preferred method for the control of boiler water component build up. This will gradually remove boiler water on a continuous basis, thus preventing the radical change in boiler water chemistry as seen during excessive manual bottom blow downs. Manual bottom (sludge) blow downs are still required to remove the heavy sludge, even with continuous blow down systems. Boiler makers usually provide instructions covering manual blow down from drums and headers. 2
3 Heavy manual blow downs should be avoided where practical. Mud drum connections should be "tried" at least every 24 hours. It is generally poor practice to blow down water wall headers while the boiler is in full load service. Continuous blow down represents the most effective means for controlling boiler water solids concentrations. It: Provides ideal boiler water samples for testing and control purposes. Permits close regulation of blow down without wide fluctuations in concentration. Makes possible the use of blow down heat recovery equipment--an important economic factor in many plants. 3
4 ALKALINITY CONTROL PURPOSE: To aid in formation of desirable sludge and to maintain a protective coating of iron oxide on steel surfaces. * * * * * * * * * * * * * The total alkalinity of boiler water includes all dissolved components that are capable of reacting with acid: These are most commonly hydroxide (OH),carbonate (CO), bicarbonate (HCO), phosphate (PO), and silicate (Sio). Among these alkaline components, the hydroxide is most important from a chemical control standpoint; it is measured directly by ph determination or by titration. Boiler water must contain a certain amount of caustic (i.e. Hydroxide alkalinity in order to accomplish three things: 1. To maintain a protective coating of iron oxide over the metal and thereby prevent certain types of corrosion. 2. To provide a proper environment for precipitation of desirable sludge materials. 3. To keep silica in solution so as to avoid deposition of siliceous scales. Excessively high concentrations of hydroxide alkalinity may result in foaming difficulties or caustic corrosion of the boiler steel. Caustic alkalinity may also cause caustic embrittlement of boiler steel under some conditions. Alkalinity control is correct when the boiler water contains enough hydroxide to secure the desired benefits without inviting trouble associated with aggressively high concentrations of caustic. The P alkalinity test provides a sound basis for control of the alkalinity in boiler water. ph determination is also widely used for this purpose where a low level alkalinity is to be maintained. Hydroxide alkalinity in boiler water may come from a variety of sources. It may be added directly in the form of caustic soda (sodium hydroxide). When soda ash is fed as a water conditioning chemical, it 4
5 decomposes under boiler steaming conditions, producing sodium hydroxide (plus carbon dioxide which goes off with the steam). Sodium hydroxide and/or sodium carbonate may be present as excess treating chemicals in the effluent from a lime-soda softener; the use of such pre-treating equipment automatically provides the alkali required for alkalinity control in the boiler water. Most raw waters contain bicarbonate (HCO). So do effluent waters from sodium cycle and from most sodium-acid cycle zeolite softeners. Under boiler water conditions, bicarbonate decomposes first to carbonate and then to hydroxide. In all cases it is the boiler water alkalinity, as measured by the p alkalinity test or ph value, that concerns us, regardless of whether this hydroxide is added as such or represents the decomposition product of soda ash or alkaline components in raw water or treated makeup water. Maximum and minimum P alkalinity values (and/or ph) limits are specified for proper control of boiler water alkalinity in your plant. Alkalinity concentrations below the specified minimum may result in corrosion difficulties or the formation of objectionable sludge or scale. Whenever boiler water alkalinities fall below the recommended minimum. do not hesitate to increase the feed of alkali (caustic soda or soda ash) or to increase the total alkalinity of the treated water if a softener is involved. Alkalinities above the specified maximum may result in foam-type carry over or caustic corrosion, and they may complicate protective measures employed to prevent caustic embrittlement. When boiler water alkalinities rise above the recommended maximum, reduce the feed of alkali (caustic soda or soda ash) or reduce the total alkalinity of the treated water if a softener is used. In an emergency, increase the blow down rate if necessary to bring boiler water alkalinity under control. Sodium hydroxide is the preferred approach, as the break down components do not form carbon dioxide. Carbon dioxide will carry off the steam and form carbonic acid in the condensate return lines. For this reason, sodium carbonate is not generally used in todays boilers. It is never recommended for use by good water treatment consultants. 5
6 ANTIFOAM MATERIALS Purpose: To minimize the amount of solids carried by the steam * * * * * * * * * * * * * Many different factors - some chemical, some mechanical -- entrained boiler water in the steam leaving the boiler. "Foaming" is a general term applied to carryover, which is caused by objectionable concentrations of certain components of the boiler water. Foam aggravating substances such as excessive concentration of mineral solids, high alkalinity, or some types of organics) steam bubbles do not allow steam bubbles to collapse or coalesce as rapidly as they should. They rather collect as a relatively stable layer of foam on the surface of the water. When this foam layer becomes thick enough to invade the active steam separation section of the boiler, masses of foam are sucked off with the steam and carryover results. Antifoam agents (polyalkylene glycol) are used specifically to speed up the coalescence of steam bubbles and thereby minimize the tendency for foam to accumulate in any part of the boiler.antifoam treatment is often effective in preventing carryover caused by uncontrollable feed water contamination or by high concentrations of boiler water solids, which for physical or economic reasons, can not be adequately controlled by normal blowdown. Even when no foaming problem exists, the cost of antifoam treatment can be justified because of savings resulting from reduced blowdown and the maintenance of higher boiler water solids. Under certain operating conditions, some types of boilers may have a tendency to allow steam bubbles to collect in downcomer tubes and thereby cancel part of the hydrostatic head required for proper circulation of water through the boiler. Antifoam treatment may improve circulation in such cases. An antifoam may be beneficial by producing a higher quality boiler water that is ideal for uniform steaming and by encouraging steam bubbles to coalesce with the greatest possible speed. It also can minimize the carryover effects of mechanical or operating factors for which there is no immediately practical or economic remedy. Of course, the best approach to problems of this nature is through physical changes, which correct the difficulty at its source. 6
7 Whenever possible, antifoam should be fed continuously, although shot feeding is permissible if additions are made at frequent intervals. Antifoam can be fed in solution along with other chemicals used for internal treatment of boiler water. Avoid over-feed of antifoam in that gross over-treatment may actually cause boiler water to foam. Another consideration is that starting with a full boiler antifoam treatment program to boilers that contain foam may result in low water because of to the sudden coalescence of steam bubbles in certain banks of tubes. When the application is to be intermittent, feed about one-fourth of the required amount durng the first hour. Follow this with one-third the second hour, one-half the third hour, three-fourths the fourth hour and the full treatment requirement for each hour there after. Unlike most other water conditioning chemicals, antifoam loses its effectiveness rather rapidly under boiler steaming conditions, therefore, feed antifoam continuously or in shots at frequent intervals. Take special precautions to assure that the antifoam treatment is not interrupted once it gets under way. 7
Best Practice in Boiler Water Treatment
Best Practice in Boiler Water Treatment Boiler Water Treatment Part 2 Internal Treatment Objectives of Internal Water Treatment 1 To control the level of total dissolved solids (TDS) within the boiler
More informationBoiler Blowdown Analysis In An Industrial Boiler
IOSR Journal of Engineering (IOSRJEN) ISSN (e): 2250-3021, ISSN (p): 2278-8719 Vol. 05, Issue 07 (July. 2015), V3 PP 22-28 www.iosrjen.org Boiler Blowdown Analysis In An Industrial Boiler Keerthi R Lekshmi
More informationBASIC WATER TREATMENT OF STEAM BOILERS
BASIC WATER TREATMENT OF STEAM BOILERS Steve Kenny and Dave Pope Chemco Water Technology Vancouver, WA This is a brief discussion on low-pressure steam boiler chemistry. It provides dry kiln boiler operators
More informationThe National Board of Boiler and Pressure Vessel Inspectors 1055 Crupper Avenue Columbus, Ohio 43229 614.888.8320
TheNationalBoardofBoilerandPressureVesselInspectors 1055CrupperAvenue Columbus,Ohio43229 614.888.8320 NB-410, Revision 3 Sept, 2015 1 1.0 GENERAL The purpose of this document is to provide basic guidelines
More informationWater Efficiency. Water Management Options. Boilers. for Commercial, Industrial and Institutional Facilities. Boiler Water Impurities
Water Efficiency Water Management Options Boilers for Commercial, Industrial and Institutional Facilities Boiler Water Impurities All boiler make-up water contains impurities. As clean steam is released
More informationWater Softening for Hardness Removal. Hardness in Water. Methods of Removing Hardness 5/1/15. WTRG18 Water Softening and Hardness
Water Softening for Removal 1 in Water High concentration of calcium (Ca2+) and magnesium (Mg2+) ions in water cause hardness Generally, water containing more than 100 mg/l of hardness expressed as calcium
More informationI. STEAM GENERATION, BOILER TYPES
I. STEAM GENERATION, BOILER TYPES and BOILER PLANT SYSTEMS 1 Steam Generation Water s Unique Properties: High Thermal Capacity (Specific Heat) High Critical Temperature Ideal Medium for Heat Delivery High
More informationThe role of CO 2 in pool water
The role of CO 2 in pool water A series of e-mail articles from the research group onbalance, January 2006 The role of CO 2 in pool water #1 While some service techs go about their business taking care
More informationDEIONIZATION IN A "NUT SHELL"
Deionized Water (DI) DEIONIZATION IN A "NUT SHELL" City water is passed through dark amber colored, caviar sized plastic beads called cation ion exchange resin. The cation resin is in the hydrogen form
More informationSilica Over-Saturation, Precipitation, Prevention and Remediation In Hot Water Systems Edited By Dave Peairs, Cal Water, Technical Director
Silica Over-Saturation, Precipitation, Prevention and Remediation In Hot Water Systems Edited By Dave Peairs, Cal Water, Technical Director Background Silica scaling becomes a problem when any hot water
More informationHardness ions also interfere with many chemical processes such as chemical compounding and aqueous cleaners.
Water Softeners Industrial Water Purification (800) CAL-WATER By Dave Peairs, Cal Water, Technical Director Rev: 06/08/2004 Before any discussion of water softeners, we must first define what hard water
More informationA Primer on Protecting Idle Boilers By Howard Benisvy, Member ASHRAE
The following article was published in ASHRAE Journal, December 2002. Copyright 2002 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. It is presented for educational purposes
More informationInferred ph in Steam Plant Water Chemistry Monitoring
Application Data Sheet ADS 4900-87/rev.B January 2009 Power Industry Inferred ph in Steam Plant Water Chemistry Monitoring INTRODUCTION Inferred ph means ph calculated from straight and cation conductivity.
More informationTechnical Presentation IMPORTANT TOPICS
BOILER WATER TREATMENT FOR KILN DRY OPERATIONS Technical Presentation IMPORTANT TOPICS PRETREATMENT TEMPERATURE VS OXYGEN FEED WATER / DA BOILER WATER CONDENSATE 1 Boiler Water Pretreatment Purpose - Statistically
More informationChapter 2.2: Boilers
Chapter 2.2: Boilers Part I: Objective type Questions and Answers 1. The minimum capacity of any closed vessel which generates steam under Indian Boilers Regulation Act is. a) 2.275 liters b) 22.75 kilo
More informationReuse of Alternative Water Sources for Cooling Tower Systems Two Case Studies Using Non-Traditional Water Sources
Reuse of Alternative Water Sources for Cooling Tower Systems Two Case Studies Using Non-Traditional Water Sources Matthew L. Haikalis Veolia Water Solutions & Technologies April 24, 2013 Operational Priorities
More informationCase History Report The Dolphin Nonchemical Device Boilers and Cooling Tower
Case History Report The Dolphin Nonchemical Device Boilers and Cooling Tower Device Evaluated "The Dolphin HYTRONIC Series 1000" pulsed power water treatment device (Dolphin) manufactured by Clearwater
More informationHydrogen Exchange Resin. Steam Purity Analysis
Circular No. 47 1955 STATE OF ILLINOIS WILLIAM G. STRATTON, Governor Hydrogen Exchange Resin ror Steam Purity Analysis by R. W. Lane, T. E. Larson and J. W. Pankey Issued by Department of Registration
More informationWATER CHEMISTRY AND POOL WATER BALANCE
C R6 H A PT E WATER CHEMISTRY AND POOL WATER BALANCE LEARNING OBJECTIVES After completely studying this chapter, you should be able to: Understand and list the parameters upon which water balance is based.
More informationWATER TREATMENT THE NEED FOR CONTROL COMMON IMPURITIES FOUND IN WATER. CALCIUM CARBONATE (CaCO3) CALCIUM SULFATE (CaSO4) MAGNESIUM SULFATE (MgSO4)
THE NEED FOR CONTROL Vecom Marine clean ships - clean seas BOILER WATER TREATMENT Whether distilled or raw (city) water is used for boiler make-up, chemical treatment is necessary to counteract harmful
More informationINSTRUCTION MANUAL. Boil-Out TABLE OF CONTENTS SAFETY WARNINGS 2-3 RESPONSIBILITY 3 INTRODUCTION 3 PRE-BOIL OUT PROCEDURES 3-5 BOIL OUT PROCESS 5-9
TABLE OF CONTENTS Description Page Number SAFETY WARNINGS 2-3 RESPONSIBILITY 3 INTRODUCTION 3 PRE-BOIL OUT PROCEDURES 3-5 BOIL OUT PROCESS 5-9 Indeck Keystone Energy, LLC. 5451 Merwin Lane, Suite 100 Erie,
More informationGlob. J. Petrol. Chem. Eng. 002
Global Journal of Petroleum and Chemical Engineering ISSN: XXXX-XXXX Vol. 2 (1), pp. 1-1, January, 214. Global Science Research Journals Full Length Research Paper Corrosion-erosion on waste heat recovery
More informationsteam centre of excellence Steam Boiler System Optimization
Steam Boiler System Optimization Introduction Gas Cost Metering Fluids Fuel, Water, Steam Steam Costs Boiler House Stack Losses Boiler Waterside Surfaces Blowdown Current Natural Gas Cost Projected Cost
More informationCHAPTER 7 THE DEHYDRATION AND SWEETENING OF NATURAL GAS
CHAPTER 7 THE DEHYDRATION AND SWEETENING OF NATURAL GAS Natural gases either from natural production or storage reservoirs contain water, which condense and form solid gas hydrates to block pipeline flow
More informationIon Exchange Softening
Ion Exchange Softening Ion-exchange is used extensively in small water systems and individual homes. Ion-exchange resin, (zeolite) exchanges one ion from the water being treated for another ion that is
More informationGUIDELINES FOR LEACHATE CONTROL
GUIDELINES FOR LEACHATE CONTROL The term leachate refers to liquids that migrate from the waste carrying dissolved or suspended contaminants. Leachate results from precipitation entering the landfill and
More informationSUGAR MILL BOILER CYCLE CHEMISTRY: AN UPDATE ON BEST PRACTICES DAVID RODMAN. Nalco Australia Pty Ltd, Townsville
SUGAR MILL BOILER CYCLE CHEMISTRY: AN UPDATE ON BEST PRACTICES By DAVID RODMAN Nalco Australia Pty Ltd, Townsville KEYWORDS: Sugar, Boiler, Water Chemistry, Deposit, Water Treatment. Abstract SUGAR mill
More informationScale and Deposit Formation in Steam Assisted Gravity Drainage (SAGD) Facilities
Scale and Deposit Formation in Steam Assisted Gravity Drainage (SAGD) Facilities Reprint R-1014 By W. Hugh Goodman, Martin R. Godfrey, and Thomas M. Miller, Nalco Comany, Naperville, IL ABSTRAST Produced
More informationEnergy Efficient Operations and Maintenance Strategies for Boilers
Energy Efficient Operations and Maintenance Strategies for Boilers Large, complex and widely used, industrial boilers are major consumers of fuel. Proper operations and maintenance (O&M) procedures must
More informationBoiler Blowdown. Boiler Blowdown Benefits. Best Operating Practices for Boiler Blowdown
Boiler Blowdown Even with the best pretreatment programs, boiler feedwater often contains some degree of impurities, such as suspended and dissolved solids. The impurities can remain and accumulate inside
More informationThe control of corrosive conditions caused by concentration of low-volatility solutes in boilers and steam generators
P R E P R I N T ICPWS XV Berlin, September 8 11, 2008 The control of corrosive conditions caused by concentration of low-volatility solutes in boilers and steam generators Geoffrey J Bignold GJB Chemistry
More informationIndustrial Water Reuse and Wastewater Minimization
Technical Paper Industrial Water Reuse and Wastewater Minimization Author: James P. McIntyre, P.E. Abstract Many industrial users of fresh water are under increasing pressure to reuse water within their
More informationScaletec Plus. Descaling Overview, Guidelines, Cleanup Tips, And Question & Answers
INFORMATION RELEASE Synergy Technology for Pool, Spa, & Fountains Scaletec Plus Product technical guidelines for calcium descaling and stain removal from swimming pool surfaces, tile, and equipment to
More informationSulfites for Oxygen Control
If you would like a more detailed version of this report, please request SOS from lcavano@scrantonassociates.com along with your e-mail address. A. Introduction Sulfites for Oxygen Control Robert R. Cavano
More informationWorld Class Water Chemistry By Accident? BRO Chemistry Session 8/5/2014
World Class Water Chemistry By Accident? BRO Chemistry Session 8/5/2014 From Safe by Accident? by Judy Agnew & Aubrey Daniels Despite decades of reduction in safety related deaths and injuries on the job,
More informationDEGASSED CATION CONDUCTIVITY MEASUREMENT
(Presented at EPRI's 8th International Conference on Cycle Chemistry in Fossil and Combined Cycle Plants with Heat Recovery Steam Generators - June 20-23, 2006 Calgary, Alberta Canada) DEGASSED CATION
More informationSteam Generation Efficiency Module Blowdown Losses Section
Steam End User Training Steam Generation Efficiency Module Blowdown Losses Section Slide 1 Blowdown Losses Module This section will discuss blowdown loss and its affect on boiler efficiency. [Slide Visual
More informationTHE USE OF OZONE IN COOLING TOWERS
THE USE OF OZONE IN COOLING TOWERS Paul D. McNicholas Ozonia Ltd Duebendorf, Switzerland Abstract Ozone has been successfully applied to industrial cooling water systems with the resultant improvement
More informationBoiler Preparation, Start-Up and Shutdown
Boiler Preparation, Start-Up and Shutdown Learning Outcome When you complete this module you will be able to: Describe the basic preparation of a boiler for start-up, and the start-up and shutdown procedures.
More informationCorrosivity of Water Supplies
WD-DWGB-3-4 2009 Corrosivity of Water Supplies What is meant by Corrosivity? Corrosive water can be defined as a condition of water quality which will dissolve metals from metallic plumbing at an excessive
More informationRoutine and Emergency Boiler Operation
Routine and Emergency Boiler Operation Learning Outcome When you complete this module you will be able to: Describe the routine safe and efficient operation of a packaged boiler. Learning Objectives Here
More informationCoagulation and Flocculation
Coagulation and Flocculation Groundwater and surface water contain both dissolved and suspended particles. Coagulation and flocculation are used to separate the suspended solids portion from the water.
More informationHardness - Multivalent metal ions which will form precipitates with soaps. e.g. Ca 2+ + (soap) Ca(soap) 2 (s)
Water Softening (Precipitation Softening) (3 rd DC 178; 4 th DC 235) 1. Introduction Hardness - Multivalent metal ions which will form precipitates with soaps. e.g. Ca 2+ + (soap) Ca(soap) 2 (s) Complexation
More informationSODIUM CATION EXCHANGE (ZEOLITE) WATER SOFTENING PROCESS
SODIUM CATION EXCHANGE (ZEOLITE) WATER SOFTENING PROCESS A. History The name zeolite comes from the two Greek words zein and lithos which mean boiling stone. It was first applied by Granstedt, a Swedish
More informationENE 806, Project Report 3 CHEMICAL PRECIPITATION: WATER SOFTENING. Grégoire Seyrig Wenqian Shan
ENE 806, Project Report 3 CHEMICAL PRECIPITATION: WATER SOFTENING Grégoire Seyrig Wenqian Shan College of Engineering, Michigan State University Spring 2007 ABSTRACT The groundwater with high level initial
More information2014 Service Technician Training Program Closed Loop Systems
1/20/14 2014 Service Technician Training Program Closed Loop Systems Daniel S. Krack, CWT 2 Closed Loop Cooling and Heating The Closed Loop Cooling Advantages High Efficiency Chillers, Heat Exchangers,
More informationGuidelines for Produced Water Evaporators in SAGD
Guidelines for Produced Water Evaporators in SAGD DAN PETERSON, HPD West, Bellevue Washington IWC-07-68 KEYWORDS: Produced Water, Zero Liquid Discharge (ZLD), evaporator, evaporation of wastewater, crystallizer,
More informationHigh-Pressure Steam Cycle and Boiler Water Treatment
High-Pressure Steam Cycle and Boiler Water Treatment High Pressure Boilers Pressure range 60-84 bar Critical needs High quality makeup water External pre-treatment through distillation and mechanical deaeration
More informationWater Water Treatment Plant Tour
Water Water Treatment Plant Tour Don Rankin, Superintendent Topeka, KS 66606 785-368-3111 Tel 785-368-3825 FAX For a complete list of contacts with phone numbers, FAX numbers and email addresses, click
More informationRemoving Heavy Metals from Wastewater
Removing Heavy Metals from Wastewater Engineering Research Center Report David M. Ayres Allen P. Davis Paul M. Gietka August 1994 1 2 Removing Heavy Metals From Wastewater Introduction This manual provides
More informationGROUP II ELEMENTS. Beryllium to Barium
1 GROUP II ELEMENTS Beryllium to Barium Introduction Elements in Group I (alkali metals) and Group II (alkaline earths) are known as s-block elements because their valence (bonding) electrons are in s
More informationExperiment 16-Acids, Bases and ph
Definitions acid-an ionic compound that releases or reacts with water to form hydrogen ion (H + ) in aqueous solution. They taste sour and turn litmus red. Acids react with certain metals such as zinc,
More informationRecovery Boiler Research Needs An Industry Perspective
Recovery Boiler Research Needs An Industry Perspective Andrew Jones International Paper 7th International Colloquium on Black Liquor Combustion and Gasification International Paper Recovery Operation Goals
More informationCHALLENGES IN A DILUTION STEAM GENERATOR SYSTEM
CHALLENGES IN A DILUTION STEAM GENERATOR SYSTEM Lee Siang Hua Titan Petrochemicals (M) Sdn Bhd Cheah Phaik Sim Titan Petrochemicals (M) sdn Bhd piximmink@yahhoo.com Karl Kolmetz Westlake Group, Lake Charles,
More informationUsing Magnesium Hydroxide
Industrial Wastewater Neutralization Using Magnesium Hydroxide May 15, 2012 Steve Leykauf, Presenter Discussion Topics What is Magnesium Hydroxide? Technical Benefits of Magnesium Hydroxide Economic Benefits
More informationGuidelines for Selecting and Maintaining Glycol Based Heat Transfer Fluids
Guidelines for Selecting and Maintaining Based Heat Transfer Fluids David Berry Engineering Manager, Chem-Aqua Canada Allan Browning Technical Marketing Manager, Chem-Aqua, Inc. Based Heat Transfer Fluids
More informationEnergy Efficiency in Steam Systems
Energy Efficiency in Steam Systems Fundamentals of Energy Efficiency: An Introductory Workshop April 2008 John S. Raschko, Ph.D. Mass. Office of Technical Assistance www.mass.gov/envir/ota (617) 626-1093
More informationCHEMICAL DETERMINATION OF EVERYDAY HOUSEHOLD CHEMICALS
CHEMICAL DETERMINATION OF EVERYDAY HOUSEHOLD CHEMICALS Purpose: It is important for chemists to be able to determine the composition of unknown chemicals. This can often be done by way of chemical tests.
More informationb. Alkalinity make your life easier and get the alkalinity between 80 and 120 PPM. c. ph from 7.2 and 7.8 so that the other chemicals work properly
1. Adding Chemicals to your water: Chemicals should be added slowly over a period of time. Pool owner/operators need to remember that all chemicals added will have an effect beyond their intended purpose.
More informationProviding the basis for success. Gas applications for the pulp and paper industry.
Providing the basis for success. Gas applications for the pulp and paper industry. 02 Pulp and paper industry Pulp and paper industry 03 Enhancing productivity and performance. Gas applications and know-how
More informationChemistry at Work. How Chemistry is used in the Water Service
Chemistry at Work How Chemistry is used in the Water Service WATER TREATMENT Everyday, more than 100 water treatment works in Northern Ireland put approximately 680 million litres of water into the supply
More informationTemperature N Source and Rate CEC (less when high) Application method + H +
Ammonia Volatilization Urease activity Air Exchange Temperature N Source and Rate CEC (less when high) Application method NH 4 NH 3 H Urea If ph and temperature can be kept low, little potential exists
More informationCooling Tower Sidestream Filtration A Green, Proven Cost Reduction Technology
Cooling Tower Sidestream Filtration A Green, Proven Cost Reduction Technology TAB0411 Typical crossflow cooling tower installation Due to the large air-water interface needed to obtain good evaporative
More informationINCINERATION IN JAPAN
INCINERATION IN JAPAN DR. CHIAKI IZUMIKAWA Regulations in the environmental field are becoming severe and severe. At the same time, NIMBY syndrome is becoming stronger day by day. The cost of incineration
More informationSanta Monica College Chemistry 11
Types of Reactions Objectives The objectives of this laboratory are as follows: To perform and observe the results of a variety of chemical reactions. To become familiar with the observable signs of chemical
More informationBoiler Chemistry Management Using Coordinated Approach of Chemicals, Membranes and Online Monitoring
Technical Paper Boiler Chemistry Management Using Coordinated Approach of Chemicals, Membranes and Online Monitoring Authors: Rajendra Prasad Kalakodimi, Lead Technologist, and Mel J. Esmacher, Engineering
More informationIron and Manganese BACTERIA AND IRON AND MANGANESE
Iron and Manganese Iron and manganese control is the most common type of municipal water treatment in Minnesota. Iron and manganese occur naturally in groundwater. Neither element causes adverse heath
More information9707 Key West Avenue, Suite 100 Rockville, MD 20850 Phone: 301-740-1421 Fax: 301-990-9771 E-Mail: awt@awt.org
9707 Key West Avenue, Suite 100 Rockville, MD 20850 Phone: 301-740-1421 Fax: 301-990-9771 E-Mail: awt@awt.org Part of the recertification process is to obtain Continuing Education Units (CEUs). One way
More informationThe Single Absorption Scrubbing Sulfuric Acid Process
The Single Absorption Scrubbing Sulfuric Acid Process Leonard J. Friedman, Samantha J. Friedman Acid Engineering & Consulting, Inc. 17770 Deauville Lane, 33496, USA LJ.Friedman@Acideng.com Keywords: Sulfuric
More informationSubject: Technical Letter 22 April 1977 Removal of Water Supply Contaminants -- Copper and Zinc
STATE OF ILLINOIS Department of Registration and Education JOAN G. ANDERSON DIRECTOR. SPRINGFIELD BOARD OF NATURAL RESOURCES AND CONSERVATION JOAN G. ANDERSON CHAIRMAN BIOLOGY THOMAS PARK CHEMISTRY H.
More informationThe Chemical Adjustment Reference Cheat Sheet
The Chemical Adjustment Reference Cheat Sheet By Terry Duff Howdy! I hope this information finds you well. In this easy to read, short report, you ll find a few charts that will show you what to add and
More informationAdditional Lecture: TITRATION BASICS
Additional Lecture: TITRATION BASICS 1 Definition and Applications Titration is the incremental addition of a reagent solution (called titrant) to the analyte until the reaction is complete Common applications:
More informationHYBRID WAY EAF OFF GAS HEAT RECOVERY -ECORECS- MASANARI YAMAZAKI*1, YASUHIRO SATO*2, RYUTARO SEKI*3
HYBRID WAY EAF OFF GAS HEAT RECOVERY -ECORECS- BY MASANARI YAMAZAKI*1, YASUHIRO SATO*2, RYUTARO SEKI*3 SYNOPSIS JP Steel Plantech Co. has developed Hybrid system for EAF off-gas heat recovery, with EAF
More informationHeating Water by Direct Steam Injection
Heating Water by Direct Steam Injection Producing hot water by direct steam injection provides a solution where large volumes of hot water at precise temperatures are required, and where energy and space
More information12 Ways To Avoid Boiler Tube Corrosion
12 Ways To Avoid Boiler Tube Corrosion By: H. F. Hinst Plant Metallurgist Tubular Products Division, Keystone Plant The Babcock & Wilcox Company Corrosion troubles in low pressure heating boilers -- which
More informationIGEMA BOILER LEVEL & TDS CONTROLS
IGEMA BOILER LEVEL & TDS CONTROLS IGEMA offers boiler level and TDS control products of the highest quality standard, being certified to ISO 9001. Made in Germany, IGEMA products are manufactured in compliance
More informationQuestion Bank Electrolysis
Question Bank Electrolysis 1. (a) What do you understand by the terms (i) electrolytes (ii) non-electrolytes? (b) Arrange electrolytes and non-electrolytes from the following substances (i) sugar solution
More information1. Inspection and monitoring... 3
1 Index 1. Inspection and monitoring... 3 1.1 Handling of new elements... 3 1.1.1 Storage of original packaged RO elements... 3 1.1.2 Packing... 3 1.2 Initial start- up checks of a plant... 3 1.2.1 Preparation
More informationIB Chemistry. DP Chemistry Review
DP Chemistry Review Topic 1: Quantitative chemistry 1.1 The mole concept and Avogadro s constant Assessment statement Apply the mole concept to substances. Determine the number of particles and the amount
More informationCOOLING WATER MANAGEMENT
COOLING WATER MANAGEMENT Intent To minimize the carbon-footprint, water usage and environmental impact of HVAC cooling systems and process cooling systems, generally by optimizing the control of water
More informationAssociation of Water Technologies Technical Manual
7.0 Chemical Treatment 7.1 OVERVIEW This section deals with specific chemical treatments. Type, purpose, and application are all discussed. The treatments are divided along the lines of preboiler and condensate
More informationWASTE WATER TREATMENT SYSTEM (OPERATING MANUALS )
Page 1 of 76 1.0 PURPOSE The purpose of the Wastewater Treatment System is to remove contaminates from plant wastewater so that it may be sent to the Final Plant Effluent Tank and eventually discharged
More informationFeasibility study of crystallization process for water softening in a pellet reactor
International A. H. Mahvi, Journal et al. of Environmental Science & Technology Feasibility study of crystallization... Vol. 1, No. 4, pp. 1-4, Winter 5 Feasibility study of crystallization process for
More informationSustainable Water Management. for the Power Industry
Sustainable Water Management for the Power Industry for the Power industry Creating water solutions Water and Wastewater Treatment Specialist Veolia Water Solutions & Technologies has over 300 power generation
More informationChemical Reactions in Water Ron Robertson
Chemical Reactions in Water Ron Robertson r2 f:\files\courses\1110-20\2010 possible slides for web\waterchemtrans.doc Properties of Compounds in Water Electrolytes and nonelectrolytes Water soluble compounds
More informationDissolving of sodium hydroxide generates heat. Take care in handling the dilution container.
TITRATION: STANDARDIZATION OF A BASE AND ANALYSIS OF STOMACH ANTACID TABLETS 2009, 1996, 1973 by David A. Katz. All rights reserved. Reproduction permitted for education use provided original copyright
More informationTRIAL CHEMICAL CLEANING OF FOULED APH BASKETS
TRIAL CHEMICAL CLEANING OF FOULED APH BASKETS Dr. Abhay Kumar Sahay, AGM(CC OS) Bijay Manjul, AGM( Operation) Kahalgaon Boiler has three inputs Steam generator 1. WATER 2. COAL 3. AIR Burner Air preheater
More informationROSS Technology Removal of Oil, Solids and Scale Formers
ROSS Technology Removal of Oil, Solids and Scale Formers Frac Flowback and Produced Treatment for Reuse WATER TECHNOLOGIES Treatment for Reuse and Enhanced Oil Recovery ROSS Technology is a an effective
More informationExperiment 8 - Double Displacement Reactions
Experiment 8 - Double Displacement Reactions A double displacement reaction involves two ionic compounds that are dissolved in water. In a double displacement reaction, it appears as though the ions are
More informationCONTENTS. ZVU Engineering a.s., Member of ZVU Group, WASTE HEAT BOILERS Page 2
WASTE HEAT BOILERS CONTENTS 1 INTRODUCTION... 3 2 CONCEPTION OF WASTE HEAT BOILERS... 4 2.1 Complex Solution...4 2.2 Kind of Heat Exchange...5 2.3 Heat Recovery Units and Their Usage...5 2.4 Materials
More informationOrganic Chemistry Lab Experiment 4 Preparation and Properties of Soap
Organic Chemistry Lab Experiment 4 Preparation and Properties of Soap Introduction A soap is the sodium or potassium salt of a long-chain fatty acid. The fatty acid usually contains 12 to 18 carbon atoms.
More informationCHAPTER 3: MATTER. Active Learning Questions: 1-6, 9, 13-14; End-of-Chapter Questions: 1-18, 20, 24-32, 38-42, 44, 49-52, 55-56, 61-64
CHAPTER 3: MATTER Active Learning Questions: 1-6, 9, 13-14; End-of-Chapter Questions: 1-18, 20, 24-32, 38-42, 44, 49-52, 55-56, 61-64 3.1 MATTER Matter: Anything that has mass and occupies volume We study
More informationwhite paper reviews why the chlor-alkali process is so damaging to ph electrodes and discusses a sensor design that has
INGOLD White Paper Leading Process Analytics No More Tears Elevated temperatures, presence of chlorine and high salt concentration throughout the chlor-alkali process make stable and reliable ph measurement
More informationIron and manganese are two similar elements
L-5451 2-04 Drinking Water Problems: Iron and Manganese Mark L. McFarland, Associate Professor and Extension Soil Fertility Specialist Monty C. Dozier, Assistant Professor and Extension Water Resources
More informationWater for Injection (WFI) and Pure Steam Production in a Lean Manufacturing Environment. Larry Zanko Project Manager STERIS Corporation
Water for Injection (WFI) and Pure Steam Production in a Lean Manufacturing Environment Larry Zanko Project Manager STERIS Corporation Agenda Brief overview of multiple-effect water stills (MWS) Lean advancements
More informationGALVANIZING NOTES MECHANICAL AND CAUSTIC CLEANING PROCESS AND DESIGN NOTES ON HOT DIP GALVANIZING BY CHRISTINE KLEEN AND THOMAS LANGILL, PH.D.
GALVANIZING NOTES PROCESS AND DESIGN NOTES ON HOT DIP GALVANIZING American Galvanizers Association (303) 750-2900 FAX (303)750-2909 email: aga@galvanizeit.org MECHANICAL AND CAUSTIC CLEANING BY CHRISTINE
More informationHEAT RECOVERY OPTIONS FOR DRYERS AND OXIDIZERS
HEAT RECOVERY OPTIONS FOR DRYERS AND OXIDIZERS William K. Scullion, Application Engineering Leader, MEGTEC Systems, De Pere, WI Introduction Competitive pressures continuously motivate us to examine our
More informationNALCO BT-25 Boiler Internal Treatment
PRODUCT NAME NALCO BT-25 Boiler Internal Treatment PRODUCT DESCRIPTION AND APPLICATION NALCO BT-25 is an innovative program that combines the use of polyphosphate and the most advanced synthetic organic
More informationXI. Methods of Analysis DETERMINATION OF POTASSIUM CARBONATE CALCULATIONS REAGENTS PROCEDURE
XI. NOTE: An automatic titrator may be utilized for ease of analysis, especially if this test is performed often. Contact Technical Service for further information concerning automatic titration. Methods
More information5.2. Vaporizers - Types and Usage
5.2. Vaporizers - Types and Usage 5.2.1. General Vaporizers are constructed in numerous designs and operated in many modes. Depending upon the service application the design, construction, inspection,
More information