Article 440 Air-Conditioning and Refrigeration Equipment
|
|
- Georgina McCormick
- 7 years ago
- Views:
Transcription
1 Mike Holt s Illustrated Guide to Understanding the NEC Requirements for Article 440 Air-Conditioning and Refrigeration Equipment Extracted from Mike Holt s Illustrated Guide to Understanding the National Electrical Code, Volume Edition Mike Holt Enterprises, Inc. 888.NEC.CODE ( ) Info@MikeHolt.com
2 ARTICLE 440 Air-Conditioning and Refrigeration Equipment IntroDUctIon to article 440 air-conditioning and refrigeration equipment This article applies to electrically driven air-conditioning and refrigeration equipment. The rules in this article add to, or amend, the rules in Article 430 and other articles. Each equipment manufacturer has the motors for a given air-conditioning unit built to its own specifi cations. Cooling and other characteristics are different from those of nonhermetic motors. For each motor, the manufacturer has worked out all of the details and supplied the correct protection, conductor sizing, and other information on the nameplate. The application itself with the compressor motor often on the other side of an exterior building wall from the normal power sources so it can exchange heat with free air poses additional problems, which the NEC addresses in Article 440. Part I. general scope. Article 440 applies to electrically driven airconditioning and refrigeration equipment Definitions. Hermetic Refrigerant Motor-Compressor. A compressor and motor enclosed in the same housing, operating in the refrigerant. rated-load current. The current resulting when the motor-compressor operates at rated load and rated voltage other articles. (B) Equipment with No Hermetic Motor-Compressors. Airconditioning and refrigeration equipment that do not have hermetic refrigerant motor-compressors, such as furnaces with evaporator coils, must comply with Article 422 for appliances, Article 424 for electric space-heating, and Article 430 for motors. (C) Household Refrigerant Motor-Compressor Appliances. Household refrigerators and freezers, drinking water coolers, and beverage dispensing machines are listed as appliances, and their installation must also comply with Article 422 for appliances. Figure Figure ampacity and rating. (A) Hermetic Refrigerant Motor-Compressor. For a her metic refrigerant motor-compressor, the rated-load current marked on the nameplate of the equipment is to be used in determining the rating of the disconnecting means, the branch-circuit conductors, the controller, and the branch-circuit short-circuit and ground-fault protection. Mike Holt Enterprises, Inc NEC.CODE ( ) 1
3 440.6 Air-Conditioning and Refrigeration Equipment Exception No. 1: The branch-circuit selection current must be used instead of the rated-load current if provided on the equipment nameplate. Part II. Disconnecting Means Author s Comment: Within Sight is visible and not more than 50 ft from each other [Article 100]. The disconnecting means can be mounted on or within the air-conditioning equipment, but it must not be located on panels designed to allow access to the equipment, or where it will obscure the equipment name plate. Figure Location. The disconnecting means for air-conditioning or refrigeration equipment must be located within sight from and readily accessible from the equipment. Figures and Figure Figure Exception No. 1: A disconnecting means isn t required to be within sight from the equipment, if the disconnecting means is capable of being individually locked in the open position, and if the equipment is essential to an industrial process in a facility that has written safety procedures, and where the conditions of maintenance and supervision ensure only qualified persons service the equipment. The provision for locking or adding a lock to the disconnecting means must be on the switch or circuit breaker, and it must remain in place with or without the lock installed. Exception No. 2: An accessible attachment plug and receptacle can serve as the disconnecting means. Author s Comment: The receptacle for the attachment plug isn t required to be readily accessible. Figure Mike Holt s Illustrated Guide to Understanding the National Electrical Code, Volume 1
4 Part III. overcurrent ProtectIon general. The branch-circuit conductors, control apparatus, and circuits supplying hermetic refrigerant motorcompressors must be protected against short circuits and ground faults in accordance with Author s Comment: If the equipment nameplate specifies Maximum Fuse Size, then a one-time or dual-element fuse must be used. Air-Conditioning and Refrigeration Equipment short-circuit and ground-fault overcurrent Device size. (A) Single Motor-Compressors. The short-circuit and groundfault protective device must not be more than 175 percent of the motor-compressor current rating. If the protective device sized at 175 percent isn t capable of carrying the starting current of the motor-compressor, the next size larger protective device can be used, but in no case can it exceed 225 percent of the motor-compressor current rating. Question: What size conductor and protection are required for a 24A motor-compressor connected to a 240V circuit? Figure (a) 10 AWG, 40A (c) a or b Answer: (a) 10 AWG, 40A (b) 10 AWG, 60A (d) 10 AWG, 90A Step 1: Determine the branch-circuit conductor [Table and ]: 24A x 1.25 = 30A, 10 AWG, rated 30A at 75 C [Table ] Step 2: Determine the branch-circuit protection [240.6(A) and (A)]: 24A x 1.75 = 42A, next size down = 40A If the 40A short-circuit and ground-fault protective device isn t capable of carrying the starting current, then the protective device can be sized up to 225 percent of the equipment load current rating. 24A x 2.25 = 54A, next size down 50A (B) Several Motor-Compressors. Where the equipment incorporates more than one hermetic refrigerant motor-compressor, or a hermetic refrigerant motor-compressor and other motors or other loads, the equipment short-circuit and ground-fault protection must be sized as follows: Figure (1) Motor-Compressor Largest Load. The rating of the branch-circuit short-circuit and ground-fault protective device must not be more than the largest motor-compressor short-circuit ground-fault overcurrent device, plus the sum of the rated-load currents of the other compressors. Author s Comment: The branch-circuit conductors are sized at 125 percent of the larger motor-compressor current, plus the sum of the rated-load currents of the other compressors [440.33]. Part IV. conductor sizing conductor size for single Motor-compressors. Branch-circuit conductors to a single motor-compressor must have an ampacity not less than 125 percent of the motor-compressor rated-load current or the branch-circuit selection current, whichever is greater. Author s Comment: Branch-circuit conductors for a single motor-compressor must have short-circuit and ground-fault protection sized between 175 percent and 225 percent of the rated-load current [440.22(A)]. Mike Holt Enterprises, Inc NEC.CODE ( ) 3
5 Air-Conditioning and Refrigeration Equipment Question: What size conductor and overcurrent device are required for an 18A motor compressor? Figure (a) 12 AWG, 30A (c) a or b Answer: (a) 12 AWG, 30A (b) 10 AWG, 50A (d) 10 AWG, 60A Step 1: Determine the branch-circuit conductor [Table and ]: 18A x 1.25 = 22.50A, 12 AWG, rated 25A at 75 C [Table ] Step 2: Determine the branch-circuit protection [240.6(A) and (A)]: 18A x 1.75 = 31.50A, next size down = 30A If the 30A short-circuit and ground-fault protection device isn t capable of carrying the starting current, then the protective device can be sized up to 225 percent of the equipment load current rating. 18A x 2.25 = 40.50A, next size down 40A conductor size for several Motor-compressors. Conductors that supply several motor-compressors must have an ampacity not less than 125 percent of the highest motor-compressor current of the group, plus the sum of the rated load or branch-circuit selection current ratings of the other compressors. Author s Comment: These conductors must be protected against short circuits and ground faults in accordance with (B)(1). Part VII. room air conditioners The requirements in this Part apply to a cord-and-plug-connected room air conditioner of the window or in-wall type that incorporates a hermetic refrigerant motor-compressor rated not over 40A, 250V, single-phase [440.60] Branch-circuit requirements. (A) Sizing Conductors and Protection. Branch-circuit conductors for a cord-and-plug-connected room air conditioner must have an ampacity not less than 125 percent of the ratedload currents [440.32]. (B) Separate Circuit. Where the room air conditioner is the only load on a circuit, the marked rating of the air conditioner must not exceed 80 percent of the rating of the circuit overcurrent device [210.3]. (C) Other Loads on Circuit. The total rating of a cord-andplug-connected room air conditioner must not exceed 50 percent of the rating of a branch circuit where lighting outlets, other appliances, or general-use receptacles are also supplied. Figure Disconnecting Means. An attachment plug and receptacle can serve as the disconnecting means for a room air conditioner, provided: Figure Figure Author s Comment: A 30A or 40A overcurrent device is permitted to protect a 12 AWG conductor for an air-conditioning circuit. See 240.4(G) for details. (1) The manual controls on the room air conditioner are readily accessible and within 6 ft of the floor, or (2) A readily accessible disconnecting means is within sight from the room air conditioner. Author s Comment: Within Sight is visible and not more than 50 ft from each other [Article 100]. 4 Mike Holt s Illustrated Guide to Understanding the National Electrical Code, Volume 1
6 Air-Conditioning and Refrigeration Equipment Supply Cords. Where a flexible cord is used to supply a room air conditioner, the cord must not exceed 10 ft for 120V units, or 6 ft for 208V or 240V units Leakage Current Detector-Interrupter and Arc-Fault Circuit Interrupter. Single-phase cord-andplug-connected room air conditioners must be provided with a factory-installed leakage current detector, or with an arcfault circuit-interrupter (AFCI). Figure Figure Mike Holt Enterprises, Inc NEC.CODE ( ) 5
7 Article 440 Practice Questions ARTICLE 440 Practice Questions article 440. air-conditioning and refrigerating equipment PractIce QUestIons 1. Article 440 applies to electric motor-driven air-conditioning and refrigerating equipment that has a hermetic refrigerant motor-compressor. (a) True (b) False 2. Equipment such as shall be considered appliances, and the provisions of Article 422 apply in addition to Article 440. (a) room air conditioners (b) household refrigerators and freezers (c) drinking water coolers and beverage dispensers (d) all of these 3. Where the air conditioner disconnecting means is not within sight from the equipment, the provision for locking or adding a lock to the disconnecting means shall be on the switch or circuit breaker and remain in place the lock installed. (a) with (b) without (c) with or without (d) none of these 4. Branch-circuit conductors supplying a single a/c motorcompressor shall have an ampacity not less than percent of either the motor-compressor rated-load current or the branch-circuit selection current, whichever is greater. (a) 100 (b) 125 (c) 150 (d) An attachment plug and receptacle can serve as the disconnecting means for a single-phase room air conditioner rated 250 volts or less if. (a) the manual controls on the room air conditioner are readily accessible and located within 6 ft of the floor (b) an approved manually operable disconnecting means is installed in a readily accessible lo cation within sight from the room air conditioner (c) a or b (d) a and b Answers: 1. (a) (d) 440.3(C) 3. (c) Ex 1 4. (b) (c) Mike Holt s Illustrated Guide to Understanding the National Electrical Code, Volume 1
BRANCH CIRCUIT AND FEEDER REQUIREMENTS
CHAPTER 36 BRANCH CIRCUIT AND FEEDER REQUIREMENTS SECTION E3601 GENERAL E3601.1 Scope. This chapter covers branch circuits and feeders and specifies the minimum required branch circuits, the allowable
More informationPREFACE. Your comments or suggestions are welcome and appreciated. They should be sent to:
PREFACE Because of changes in installation codes, the increasing complexity of the equipment involved, and other factors, more and more markings are being used on electrical heating and cooling equipment.
More informationMike Holt s Illustrated Guide to. Rule 220.87, Articles 445, 700, 701, and 702. Based on the 2011 NEC
Mike Holt s Illustrated Guide to NEC Requirements for Generators and Standby Power Systems Rule 220.87, Articles 445, 700, 701, and 702 Based on the 2011 NEC Extracted from Mike Holt s Illustrated Guides
More informationRequirements for Electrical Installations
ARTICLE 110 Requirements for Electrical Installations INTRODUCTION TO ARTICLE 110 REQUIREMENTS FOR ELECTRICAL INSTALLATIONS Article 110 sets the stage for how you ll implement the rest of the NEC. This
More informationQuestions and Answers for Heating and A/C Contractors
1. How do we accomplish grounding of furnaces and / or water heaters on two wire circuits? 250.134 Equipment Fastened in Place or Connected by Permanent Wiring Methods (Fixed) Grounding. Unless grounded
More information2012 Canadian Electrical Code, Part I (CEC) Top Fifteen changes
2012 Canadian Electrical Code, Part I (CEC) Top Fifteen changes 1) Tamper resistant receptacles. 2009 CEC Required in dwelling units 2012 CEC Expanded to child care facilities First introduced in the 2009
More informationRESIDENTIAL ELECTRICAL REQUIREMENTS (REVISED 3/28/2008) PERMIT REQUIREMENTS:
RESIDENTIAL ELECTRICAL REQUIREMENTS (REVISED 3/28/2008) PERMIT REQUIREMENTS: Signed completed Electrical Permit application form. Minnesota law requires all electrical work is to be performed by licensed,
More informationGUIDELINES FOR WIRING SINGLE FAMILY DWELLING UNITS
GUIDELINES FOR WIRING SINGLE FAMILY DWELLING UNITS This guideline has been prepared to assist the owner/occupant of a single family dwelling with compliance to the requirements of the National Electrical
More informationNEC 2014 Code Changes
NEC 2014 Code Changes Articles 400-408.55 CHANGES FROM 2011 TO 2014 CODE ARE IN RED Chapter 4 Equipment for General Use ARTICLE 400 Flexible Cords and Cables 400.4 Types Flexible cords and flexible cables
More informationOntario Electrical Safety Code 25 th Edition/ 2012
Ontario Electrical Safety Code 25 th Edition/ 2012 Ted Olechna Director, Codes and Standard Chief Engineer 1 What I Will Cover ESA s role is as the regulator Highlight of 2012 Code changes The Code and
More informationSolar Photovoltaic (PV) Systems
ARTICLE 690 Solar Photovoltaic (PV) Systems INTRODUCTION TO ARTICLE 690 SOLAR PHOTOVOLTAIC (PV) SYSTEMS You ve seen, or maybe own, photocell-powered devices such as night lights, car coolers, and toys.
More informationELECTRICAL - WIRING DESIGN AND PROTECTION SELF INSPECTION CHECKLIST
Name of School: OPTIONAL INFORMATION Date of Inspection: Vocational Program/Course/Room: Signature of Inspector: ELECTRICAL - WIRING DESIGN AND PROTECTION SELF INSPECTION CHECKLIST Guidelines: This checklist
More information2011/2008/2005 NATIONAL ELECTRICAL CODE SOLAR PV CODE COMPLIANCE REFERENCE
2011/2008/2005 NATIONAL ELECTRICAL CODE SOLAR PV CODE COMPLIANCE REFERENCE PAGE 1 OF 5 This Reference provides a very comprehensive list of aspects of a solar PV installation that could be reviewed, clarifying
More informationFirst Published in The Wichita Eagle on January 2, 2015 ORDINANCE NO. 49-897
OCA #230100 First Published in The Wichita Eagle on January 2, 2015 ORDINANCE NO. 49-897 AN ORDINANCE AMENDING SECTIONS 4.A.080, 4.1.020, 4.1.110, 4.2.010, 4.2.070, 4.2.125, 4.2.170, 4.2.175 AND 4.2.220;
More informationGuidelines on the Short Circuit Current Rating for Industrial Control Panels
usa.siemens.com/sccr Guidelines on the Short Circuit Current Rating for Industrial Control Panels Technical Paper for Practical Applications White Paper I October 2014 As per NEC Edition 2014, and UL508A
More information2014 NEC Guide Lines for Home Owner Doing Electrical Work on their Property
2014 NEC Guide Lines for Home Owner Doing Electrical Work on their Property A brief summary of the most used code references for residential wiring State of Idaho Division of Building Safety Electrical
More informationCity of Riverside Building & Safety Division Phone: (951) 826-5697 www.riversideca.gov
City of Riverside Building & Safety Division Phone: (951) 826-5697 www.riversideca.gov PHOTOVOLTAIC PERMITTING GUIDELINES The information provided in this document is general and is intended only as a
More informationGROWTH MANAGEMENT DEPARTMENT 201 SE 3 rd ST, (Second Floor), Ocala, FL 34471 (352) 629-8421; FAX: (352) 629-8264
BUILDING CODE GUIDELINES FOR ELECTRICAL INSPECTIONS Building Code compliance is the obligation of design professionals and/or contractors. Plan Review and Inspection Guidelines are intended to be used
More informationCommon Electrical Hazards in the Workplace Including Arc Flash. Presented by Ken Cohen, PhD, PE & CIH (Ret.)
Common Electrical Hazards in the Workplace Including Arc Flash Presented by Ken Cohen, PhD, PE & CIH (Ret.) 1 What s New In February 1972, OSHA incorporated the 1971 edition of the National Fire Protection
More informationPALM BEACH COUNTY AMENDMENTS TO THE NATIONAL ELECTRICAL CODE, 1999 EDITION
PALM BEACH COUNTY AMENDMENTS TO THE NATIONAL ELECTRICAL CODE, 1999 EDITION CODING: Words underlined are additions to the 1999 NEC Words stricken are deletions to the 1999 NEC Adopted by Ordinance 99-73
More information2011 National Electrical Code Questions & Answers
443 Lafayette Road North St. Paul, Minnesota 55155 www.dli.mn.govw www.electricity.state.mn.us (651) 284-5064 1-800-DIAL-DLI Fax: (651) 284-5743 TTY: (651) 297-4198 2011 National Electrical Code Questions
More informationWhat are the basic electrical safety issues and remedies in solar photovoltaic installations?
What are the basic electrical safety issues and remedies in solar photovoltaic installations? Presented by: Behzad Eghtesady City of Los Angeles Department of Building and Safety Topics Covered Photovoltaic
More informationSiemens STEP 2000 Course Basics of Electrical Products
Siemens STEP 2000 Course Basics of Electrical Products It's easy to get in STEP! Download any course. Hint: Make sure you download all parts for each course and the test answer form. Complete each chapter
More informationHelp protect your home, possessions and family.
Help protect your home, possessions and family. A guide to your Square D electrical distribution system SM Make the most of your energy Understanding your home s electrical distribution system As one of
More informationElectrical Contractors. and the. New Jersey. Rehabilitation Code
Electrical Contractors and the New Jersey Rehabilitation Code Alan Chech Electrical Seminars 609-890-7072 www.alanchech.com Information is based on the presently adopted electrical subcode NEC 2005. Current
More informationELECTRICAL REQUIREMENTS Specific Information for Electrical Work Installers
ELECTRICAL REQUIREMENTS Specific Information for Electrical Work Installers This handout is intended to be a general overview of residential electrical requirements as noted in the 2014 National Electrical
More informationDepartment of Labor and Industry Electrical Licensing
Department of Labor and Industry Electrical Licensing License Examination Guide The information in this guide is provided by the Licensing Unit of the Department of Labor and Industry to ensure that applicants
More information2004 Standard For Performance Rating Of Positive Displacement Refrigerant Compressors And Compressor Units
2004 Standard For Performance Rating Of Positive Displacement Refrigerant Compressors And Compressor Units ANSI/AHRI Standard 540 (formerly ARI Standard 540) IMPORTANT SAFETY RECOMMENDATIONS ARI does not
More informationCity of Riverside Building & Safety Division Residential Electric Vehicle (EV) Charger Guidelines
Western Riverside County Code Uniformity Program City of Riverside Building & Safety Division Residential Electric Vehicle (EV) Charger Guidelines PHONE (951) 826-5697 3900 Main Street, Riverside, CA 92522
More informationErrata NFPA 70. Proposed 2014 Edition
Errata NFPA 70 National Electrical Code (Report on Proposals) Reference: 12-109 (Log #1618) Panel Meeting Action Proposed 2014 Edition The National Electrical Code Technical Correlating Committee notes
More informationSUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original
SUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original A motor starter is a combination of devices to allow an induction motor to start, run and stop according
More informationResidential Electrical Inspection Checklist
Residential Electrical Inspection Checklist Based on the 2008 National Electrical Code Generally, Minnesota law requires all electrical work to be performed by licensed, bonded and insured electrical contractors
More informationELECTRICAL GUIDELINES FOR SINGLE-FAMILY HOME OWNERS:
ELECTRICAL GUIDELINES FOR SINGLE-FAMILY HOME OWNERS: Chapter 12 of the Burlington Code of ordinances allows owner occupants of single family homes to do their own wiring if they choose. If you choose to
More informationElectrician s Math and Basic Electrical Formulas
UNIT 1 Electrician s Math and Basic Electrical Formulas INTRODUCTION TO UNIT 1 ELECTRICIAN S MATH AND BASIC ELECTRICAL FORMULAS In order to construct a building that will last into the future, a strong
More informationGENERAL ELECTRICAL REQUIREMENTS
GENERAL ELECTRICAL REQUIREMENTS RECEPTACLE SPACING Within 6-feet of the edge of any door HABITABLE Not more than 12-feet apart along wall ROOMS: At all wall spaces 24 or more wide Within 24 of edge of
More informationTop Commercial / Residential Electrical Requirements *
Department of Community Development Building Division 4800 West 92 nd Avenue Westminster, Colorado 80031 For Information call (303) 658-2075 Fax (303) 706-3922 www.westminsterpermits.com Top Commercial
More informationElectrical Extension Cords & Relocatable Power Taps: (RPT s)
Electrical Extension Cords & Relocatable Power Taps: (RPT s) If either device is not use correctly, a fire can happen The new FDNY Fire Code (eff. 7.08) addresses these issues in 605.4 and 605.5 A recent
More informationMONTGOMERY COUNTY EXECUTIVE REGULATION Offices of the County Executive. 101 Monroe Street. Rockville, Maryland 20850
Montgomery County Regulation on: ADOPTION OF THE 2008 NATIONAL ELECTRICAL CODE DEPARTMENT OF PERMITTING SERVICES Issued by County Executive Regulation # 15-09 Authority: Code Section 17-2 and 17-3 Supersedes:
More informationSignificant Changes in the 2011 NEC Prepared by Bryan Holland City of North Port
Significant Changes in the 2011 NEC Prepared by Bryan Holland City of North Port Code-Wide Code Change Section 90.5(C). Fine Print Notes are now referred to as "Informational Notes." The purpose, intent,
More informationINSPECTION GUDELINES
GENERAL REQUIREMENTS Building permit and approved set of plans Building permit on the card is the same as on the route "If this is not the first inspection, read inspection records and notes on permit
More informationBASIC NEC CODE RULES AND DESIGN PRACTICE
BASIC NEC CODE RULES AND DESIGN PRACTICE Wire Ampacity and Size Circuit Breaker Size 1. Maximum loading for any branch circuit is 80% of rating of circuit for ampacity of wire for any load. NEC 220-2,
More informationSWITCHGEAR Section 16. SECTION INCLUDES This Section includes service and distribution switchboards rated 600 V and less.
PART 1 - GENERAL SECTION INCLUDES This Section includes service and distribution switchboards rated 600 V and less. RELATED SECTIONS Division 16 Section "Basic Electrical Materials and Methods" for general
More informationGrounding & Bonding Why it is done And How to Install Properly
Grounding & Bonding Why it is done And How to Install Properly The technical information provided herein is to assist qualifi ed persons in planning and installing electric service to farms and residences.
More informationSERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS
SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS TABLE OF CONTENTS 1. Warnings...2 2. Accessibility Of Appliance...3 3. Unit Dimensions And Specifications...3 4. Unit Specifications
More informationSection 3: Load Planning Bill Brown, P.E., Square D Engineering Services
Section 3: Load Planning Bill Brown, P.E., Square D Engineering Services Basic Principles The most vital, but often the last to be acquired, pieces of information for power system design are the load details.
More informationCHAPTER 4 UTILITY SYSTEMS ELECTRICAL. Utility Systems Electrical. Main Panel
CHAPTER 4 UTILITY SYSTEMS ELECTRICAL Utility Systems Electrical The electrical supply to your home begins outside, where you will see either an overhead feed and piping down the side of your home or (if
More informationMotor Protection Voltage Unbalance and Single-Phasing
Motor Protection Voltage Unbalance and Single-Phasing Cooper Bussmann contributes the following information, which is an excerpt from their 190-page handbook SPD Selecting Protective Devices Based on the
More informationCommercial Garages, Repair, and Storage
ARTICLE 511 Commercial Garages, Repair, and Storage Introduction to Article 511 Commercial Garages, Repair, and Storage Article 511 covers locations used for the service and repair of vehicles which use
More informationSOLAR PV STANDARD ELECTRICAL PLAN Microinverter Systems for Single Family Dwellings
*** Provide this document to the inspector along with ALL system installation instructions *** Project Address: Scope: Standard plan for the installation of grounded microinverter solar PV systems, not
More informationCONTINUING EDUCATION FOR OREGON ELECTRICIANS. 2014 NEC Code Changes. AMERICAN ELECTRICAL INSTITUTE PO Box 31131 Spokane, WA 99223. www.aeitraining.
American Electrical Institute 2014 PART 2 43 CONTINUING EDUCATION FOR OREGON ELECTRICIANS 2014 NEC Code Changes AMERICAN ELECTRICAL INSTITUTE PO Box 31131 Spokane, WA 99223 www.aeitraining.com 44 PART
More informationEntrances to and from Electrical Equipment Rooms
Electrical Code Requirements for Commercial and Residential Buildings Presented by Bob Nuzzi State Electrical Inspector Entrances to and from Electrical Equipment Rooms 2005 NEC Section 110.26(C)(2) Large
More information2011 NEC Summary of Changes. Chapter 1 2011 Summary of Changes. Article Section Summary of Change
Chapter 1 2011 Summary of Changes 90 90.2(b)(5)(c) Section 90.2(B)(5) was revised to clarify which utility installations are outside the scope of the NEC. New text has been added to specify what types
More informationCounty of Riverside Building and Safety Department
County of Riverside Building and Safety Department Mike Lara Director Photovoltaic Permitting Guidelines The information provided in this document is general and is intended only as a guide. Each project
More informationFundamentals of Power
Fundamentals of Power Fundamentals of Power 2008 American Power Conversion Corporation. All rights reserved. All trademarks provided are the property of their respective owners. Learning Objectives At
More informationResidential Electrical Inspection. Checklist
443 Lafayette Road N. St. Paul, Minnesota 55155 www.doli.state.mn.us Residential Electrical Inspection (651) 284-5064 1-800-DIAL-DLI Fax: (651) 284-5743 TTY: (651) 297-4198 Checklist Generally, Minnesota
More informationSi10-417_C. Pocket Manual. Service Diagnosis SPLIT & MULTI
Pocket Manual Service Diagnosis SPLIT & MULTI Service Diagnosis SPLIT & MULTI 1. Troubleshooting with LED...5 1.1 Indoor Unit... 5 1.2 Outdoor Unit... 10 2. Troubleshooting by Symptoms...11 2.1 Air conditioner
More informationSimplified Guide To Understanding Short-Circuit Current Rating FIND IT, FIX IT, FORGET IT
Simplified Guide To Understanding Short-Circuit Current Rating FIND IT, FIX IT, FORGET IT Are You Ready For The New SCCR Marking Requirements? What Is A Short-Circuit Current Rating (SCCR)? SCCRs on components
More information800 Communications Circuits
ARTICLE 800 Communications Circuits INTRODUCTION TO ARTICLE 800 COMMUNICATIONS CIRCUITS This article has its roots in telephone technology. Consequently, it addresses telephone and related systems that
More informationHOUSING QUALITY STANDARDS (HQS)
HOUSING QUALITY STANDARDS (HQS) Series 5 Electrical Safety And INSPECTIONS 5.01 ELS Revised 8-17-06 Electricity is Dangerous All electrical repairs should be made by licensed professionals. Touching any
More informationBranch Circuit Calculations
Branch Circuit Calculations by Gerald Newton October 31, 1999 1. A 20 ampere, 120 volt, 2-wire branch circuit has a maximum load capacity of watts or volt-amperes. Reference: Using the following for Single
More informationInstallation Instructions
H5HK Series Installation Instructions 3 Phase Electric Heater Kits 7.5 and 0 TON Package A/C Systems Description Installation of 08/40V and 480V H5HK 3 Phase Heater Kits in 7.5 and 0 TON Packaged Air Conditioners.
More informationCONDUCTOR SHORT-CIRCUIT PROTECTION
CONDUCTOR SHORT-CIRCUIT PROTECTION Introduction: This paper analyzes the protection of wire from fault currents. It gives the specifier the necessary information regarding the short-circuit current rating
More informationGENERAL WIRING RULES FOR HOUSES
GENERAL WIRING RULES FOR HOUSES 1. Romex has to be installed in drilled holes in joists or studs even above suspended ceilings - No stapling to bottom edges of joists or studs. You may staple wire to flat
More information0150506194 C Limited 2nd through 5th Year Functional Parts Warranty During the 2nd through 5th year,haier will provide functional parts which prove to be defective due to workmanship
More informationShort Circuit Current Calculations
Introduction Several sections of the National Electrical Code relate to proper overcurrent protection. Safe and reliable application of overcurrent protective devices based on these sections mandate that
More informationLow Voltage Fuses For Motor Protection
Code Requirements The NEC or CEC requires that motor branch circuits be protected against overloads and short circuits. Overload protection may be provided by fuses, overload relays or motor thermal protectors.
More informationREAD AND SAVE THESE INSTRUCTIONS. INSTALLATION AND WIRING MUST BE IN ACCORDANCE WITH CEC, NEC AND LOCAL ELECTRICAL CODES.
16EC SERIES UPFLOW PACKAGED TERMINAL AIR CONDITIONERS Electric Heating and Cooling Unit Cooling - Only Unit INSTALLATION & OPERATION MANUAL IMPORTANT: READ AND SAVE THESE INSTRUCTIONS. INSTALLATION AND
More informationElectrical Wiring Guide
Electrical Wiring Guide In order to wire your own home, you must comply with the requirements of the 2011 edition of the National Electrical Code (NEC). NEC code articles are indicated by brackets ([ ]),
More informationSWIMMING POOLS CHAPTER 41
CHAPTER 41 SWIMMING POOLS SECTION E4101 GENERAL E4101.1 Scope [Section 680.1]. The provisions of this chapter shall apply to the construction and installation of electric wiring and equipment associated
More informationCrawford Inspection Services C.C.B. # 76914 www.crawfordinspections.com
Crawford Inspection Services C.C.B. # 76914 www.crawfordinspections.com Portland Area PO Box 665 West Linn, OR 97068 Ph: (503) 650-6957 Salem Area 5434 River Rd. N; #192 Keizer, OR 97303 Ph: (503) 362-5809
More informationPREFACE. Your comments or suggestions are welcome and appreciated. They should be sent to:
PREFACE UL developed the Dead-Front Switchboard Marking Guide for code authorities, electric utilities, contractors, installers, users, designers, and other interested parties to aid in understanding deadfront
More informationUL guidelines, chapter 6.2 / 6.3 Motor Branch Circuits acc. to UL
UL guidelines, chapter 6.2 / 6.3 Motor Branch Circuits acc. to UL Definition of Terms / Explanations Overview of Basic Devices Construction Types acc. to UL 508 Self-Protected Combination Motor Controller
More informationINSTALLATION & SERVICE MANUAL. Display Panel
INSTALLATION & SERVICE MANUAL Display Panel The PowerLine EMS TM is a specialized power distribution and energy management system intended to be used in recreational vehicles. The Control Module is housed
More informationResidential Electrical Inspection. Checklist
Electrical Licensing and Inspection 443 Lafayette Road North St. Paul, Minnesota 55155-4342 www.doli.state.mn.us 651-284-5064 Fax: 651-284-5743 TTY: 651-297-4198 1-800-DIAL-DLI Residential Electrical Inspection
More informationSingle Zone LCD Thermostat Operating Instructions
Fan Cool Furnace *Heat Pump or Heat Strip On/Off F Single Zone LCD Thermostat Operating Instructions MODEL 3313192.XXX Cool/Furnace 3313193.XXX Cool/Furnace/Heat Pump 3313194.XXX Cool/Furnace/Heat Strip
More informationPROAIR Water-Cooled Air Conditioner. CR43WC Model INSTRUCTION MANUAL. Rev. E 2013 Pentair Technical Products P/N 10-1008-167
PROAIR Water-Cooled Air Conditioner CR43WC Model INSTRUCTION MANUAL Rev. E 2013 Pentair Technical Products P/N 10-1008-167 87976466 TABLE OF CONTENTS HANDLING & TESTING THE AIR CONDITIONER...3 INSTALLATION
More informationMOTOR PROTECTION AGAINST SINGLE-PHASING
THE SINGLE-PHASE DILEMMA: FACT OR FICTION PROTECTION AGAINST SINGLE-PHASING Bulletin PSP The Single-Phasing Issue: Fact or Fiction Overview Before discussing SINGLE-PHASING, let s take a look at some of
More informationArticle 10 - ADMINISTRATIVE SECTION
Article 10 - ADMINISTRATIVE SECTION 10.1 TITLE These Administrative Regulations along with the requirements included in the 2011 Edition of the National Electrical Code (NFiPA-70-2011) as adopted by the
More informationTOP 10 CHANGES 2013 CALIFORNIA ELECTRICAL CODE 2013 CALIFORNIA ENERGY CODE (ELECTRICAL)
LOS ANGELES BASIN CHAPTER OF ICC MONTHLY CHAPTER MEETING ALHAMBRA, CA TOP 10 CHANGES 2013 CALIFORNIA ELECTRICAL CODE 2013 CALIFORNIA ENERGY CODE (ELECTRICAL) RON TAKIGUCHI, P.E. BUILDING OFFICIAL -CITY
More informationNZECP 14: 1995 ISSN 0114-0663 COVER PAGE
NZECP 14: 1995 ISSN 0114-0663 COVER PAGE NZECP 14:1995 NEW ZEALAND ELECTRICAL CODE OF PRACTICE FOR CONTROL PROTECTION AND SWITCHBOARDS Issued by the Office of The Chief Electrical Engineer, Energy and
More informationNEC CODE QUESTIONS. Western Section IAEI 101 st Annual Meeting September 19-21, 2005
The Code Panels were as follows: NEC CODE QUESTIONS Western Section IAEI 101 st Annual Meeting September 19-21, 2005 CODE PANEL NO. 1 MIKE FORISTER, MODERATOR Mark Earley - 1, 9, 17, 25, 33, 41, 49 Monte
More informationE2 Series Electric Furnaces
E2 Series Electric Furnaces Service Manual Table of Contents Electrical Requirements... 10 Codes, Specifications Requirements... 10 Connection Supply Service Wires... 10 Furnace Sequence of Operation...
More informationEfficiency and Other Benefits of 208 Volt Over 120 Volt Input for IT Equipment
Efficiency and Other Benefits of 208 Volt Over 120 Volt Input for IT Equipment By Neil Rasmussen White Paper #27 Revision 2 Executive Summary Decisions made regarding the distribution of 208V or 120V power
More informationElectric Vehicle Charging Station Installation Guidelines: Residential and Commercial Locations
Electric Vehicle Charging Station Installation Guidelines: Residential and Commercial Locations Streamlining Permitting and Inspection of Residential and Commercial Electric Vehicle Charging Station Installations
More informationUSER S MANUAL HSC-24A
AIRREX AIR CONDITIONER USER S MANUAL HSC-24A Thank you for purchasing an AIRREX AIR CONDITIONER. BEFORE operation please read this user s manual carefully. Keep this manual readily available. It is ESSENTIAL
More informationMISCELLANEOUS ELECTRICAL JOBS REQUIRING PERMITS
MISCELLANEOUS ELECTRICAL JOBS REQUIRING PERMITS 01. SAFETY INSPECTION of service equipment at FPL Power Source 02. Construction GFI power outlets (Temp Pole for Construction) 03. 90 day temporary power
More informationInstructions & Safety Information Models A220-20D and A220-20L Version 2
Quick 220 Voltage Converting Power Supply Instructions & Safety Information Models A220-20D and A220-20L Version 2 Quick 220 Systems LLC PO Box 47489 Phoenix, Arizona 85068-7489 800-347-0394 602-938-6057
More informationTroubleshooting Your Refrigerator
Troubleshooting Your Refrigerator With conscientious care, a refrigerator will perform for years with little or no repairs. Refrigerators are categorized according to the way frost is removed from them.
More informationLaboratory Safety Guideline Electrical Safety
Introduction The typical laboratory contains a wide variety of electrically-powered equipment including stirrers, shakers, pumps, hot plates, heaters, power supplies, ovens, and electrophoresis equipment.
More informationPERMITS REQUIRED & PERMIT EXEMPTIONS
PERMITS REQUIRED & PERMIT EXEMPTIONS This guideline is intended to assist the applicant in determining what types of construction work require a permit. The 1997 California Uniform Administrative Code,
More informationAll work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.
DIVISION 16 ELECTRICAL SECTION 16100 - ELECTRICAL PART 1 - GENERAL SCOPE All electrical work as shown on the drawings and as necessary to provide a complete electrical system. Include primary service,
More informationCommercial/Industrial Electricity
1 ELC 210 Commercial/Industrial Electricity Course Package Presented and Approved July 31, 2008 2 Contact person(s) DAVE WHITE Date of proposal to JULY 31, 2008 Curriculum Committee NEW COURSE PACKAGE
More informationReverse-feed applications for circuit breakers
Technical Publication PU01200001E Contents Description Page Intoduction.......................................................................... 2 breaker classifications..........................................................
More informationElectronic Trip Circuit Breaker Basics Circuit Breaker Application Guide Class 0600
Electronic Trip Circuit Breaker Basics Circuit Breaker Application Guide Class 0600 Data Bulletin 0600DB1104 03/2012 Retain for future use. Electronic Trip Circuit Breaker Basics 0600DB1104 Table of Contents
More informationSERVICE MANUAL 12VDC WALL THERMOSTAT AIR CONDITIONING SYSTEMS ROOFTOP UNITS ONLY
SERVICE MANUAL 12VDC WALL THERMOSTAT AIR CONDITIONING SYSTEMS ROOFTOP UNITS ONLY! WARNING - SHOCK HAZARD! TO PREVENT THE POSSIBILITY OF SEVERE PERSONAL INJURY, DEATH, OR EQUIPMENT DAMAGE DUE TO ELECTRICAL
More informationUnderstanding HUD s UPCS Protocol for Inspecting Electrical Devices Revised Oct. 2010
PIH REAC is providing the following information to assist in properly identifying and mitigating electrical hazards that may exist on the property. This information presents common electrical hazards but
More informationELECTRICAL INSPECTION BULLETIN (Effective 2000-03-01)
ELECTRICAL INSPECTION BULLETIN (Effective 2000-03-01) Rule 28-900 Standby Generator Installations Due to the increasing number of standby generator installations being established to maintain continuity
More informationTRANSFORMERS. Unit 14 OBJECTIVES
Unit 14 TRANSFORMERS OBJECTIVES After studying this unit, the student will be able to state the purpose of a transformer. explain the principle of mutual induction. determine the output voltage of a transformer
More informationAir Conditioning Sign-Off Sheet
Air Conditioning Sign-Off Sheet Printed Technician Name Address Social Security Number Telephone Number City State Zip Code Install Or Verify The Accuracy Of An Air Conditioner s Installation The candidate
More informationHeating, Ventilation, Air Conditioning and Refrigeration (HVACR)
Heating, Ventilation, Air Conditioning and Refrigeration (HVACR) I. Demonstrate safety skills in typical HVACR work situations to NATE Core Installer Knowledge Areas for Technician Excellence for Safety
More information