Rev Building Environmental Control (BEC) Installation and Operation Manual

Size: px
Start display at page:

Download "Rev Building Environmental Control (BEC) Installation and Operation Manual"

Transcription

1 Rev Building Environmental Control (BEC) Installation and Operation Manual

2

3 Computer Process Controls, Inc Airport Road Suite #104 Kennesaw, GA Phone (770) Fax (770) ALL RIGHTS RESERVED The information contained in this manual has been carefully checked and is believed to be accurate. However, Computer Process Controls, Inc. assumes no responsibility for any inaccuracies that may be contained herein. In no event will Computer Process Controls, Inc. be liable for any direct, indirect, special, incidental, or consequential damages resulting from any defect or omission in this manual, even if advised of the possibility of such damages. In the interest of continued product development, Computer Process Controls, Inc. reserves the right to make improvements to this manual, and the products described herein, at any time without notice or obligation.

4

5 Table of Revisions Revision Description Page REV 1... ADDED OPTION TO DEFINE FAN FAIL PROOF SIGNAL REV 1... SIXTEEN HOLIDAY DATES MAY NOW BE DEFINED (PREVIOUSLY 8) REV 1... ADDED SCHEDULE PROOFS SETUP SCREEN REV 1... ADDED I/O STATUS AND BYPASS SCREENS REV 1... ADDED I/O MODULE STATUS AND BYPASS SCREENS REV 1... ADDED SCHEDULE PROOFS REV 1... ADDED VARIABLE-SPEED FAN OUTPUTS (AHU 1 VS-AHU 6 VS) REV 1... ADDED FAHRENHEIT TO CELSIUS CONVERSION SCREEN REV 1... ADDED FAN FAILURE ALARM BYPASS SCREEN REV 1... ADDED ALARM SETPOINT SHIFT FEATURE TO SENSOR CONTROL REV 1... ADDED IRLDS ALARM SUPPORT REV 1... ADDED 485 ALARM FILTERING SCREEN BEC I&O Manual Table of Revisions i

6

7 Table of Contents 1 INTRODUCTION BEC MANUAL HARDWARE OVERVIEW INTRODUCTION Building Environmental Control INPUT COMMUNICATION BOARDS AI Board OUTPUT COMMUNICATION BOARDS RO Board RO Form C Board AO Analog Output Board DO Digital Output Board SPECIAL PURPOSE COMMUNICATION BOARDS IO Board ALARM PANEL REMOTE COMMUNICATION RS232 Bus Amplifier Modems UltraSite HARDWARE MOUNTING BUILDING ENVIRONMENTAL CONTROL I/O BOARDS AND ENCLOSURES IOs Without Enclosures Mounting ALARM PANEL RS232 BUS AMPLIFIER TEMPERATURE SENSORS Inside Temperature Sensor Outside (Ambient) Temperature Sensor Insertion Temperature Probe HUMIDITY SENSORS AND HUMIDISTATS DEW POINT SENSORS AND CONTROL SWITCHES Dew Cell Dew Point Probe Dew Point Control Switch LIGHT LEVEL SENSOR POWER MONITORS TRANSFORMERS THE REFLECS NETWORK INTRODUCTION RS485 INPUT/OUTPUT (I/O) NETWORK (COM A AND D) RS485 HOST NETWORK (COM B) RS232 REMOTE COMMUNICATION NETWORK (COM C) LEGS AND SEGMENTS LEG AND SEGMENT WIRE LENGTH NUMBER OF DEVICES PER SEGMENT DAISY CHAINS BEC I&O Manual Table of Contents iii

8 4.9. STAR CONFIGURATIONS TERMINATING RESISTANCE JUMPERS (COM A, COM B, AND COM D ONLY) NETWORK DIP SWITCHES AND ROTARY DIALS (COM A AND D ONLY) Baud Rate Dip Switches (COM A and D only) NETWORK SETTINGS Network Addresses BAUD RATE DIP SWITCH SETTINGS COM A and D Networks COM B Network COM C Network FAIL-SAFE DIP SWITCH SETTINGS WIRING FOR NETWORK & POWER CONNECTIONS WIRING SPECIFICATIONS COM A AND D WIRING COM B WIRING COM C WIRING SENSOR AND TRANSDUCER WIRING POWER CONNECTION WIRING Power Requirements Power Transformers SOFTWARE OVERVIEW HEATING AND COOLING Single Set Point Strategy Separate Set Points Strategy Night Set Back and Warm-Up Seasonal Lock-Out and Seasonal Set Point Shifts Cool Termination DEHUMIDIFICATION Minimum Building Temperature Dehumidification Reheat Set Point FAN CONTROL Single-Speed Fans Two-Speed Fans Variable-Speed Fans BOILER CONTROL Override ON/OFF ANTI-SWEAT CONTROL SCHEDULES Schedule Overrides Schedule Priorities DEMAND CONTROL Demand Monitoring Predicting Energy Consumption Load Shedding SENSOR CONTROL Output Control Sensor Alarms Unoccupied Settings Sensor Overrides DIMMER CONTROL INPUT/OUTPUT CONTROL Cells and Modules iv Table of Contents Rev

9 BEC I/O Module Descriptions SYSTEM CONFIGURATION GUIDE GENERAL HVAC SETUP SET HEATING & COOLING SETPOINTS DEFINE SCHEDULES SETUP ANTI-SWEAT SETUP SENSORS SETUP DEMAND MONITORING IF IT IS NECESSARY TO BYPASS A SYSTEM SETTING SYSTEM SETUP MAIN STATUS SCREEN LOG ON MAIN MENU HVAC MENU Main Status Screen HVAC Setpoints Menu Setup Manual Bypasses Boiler Menu SCHEDULES MENU Schedules Status Schedule Overrides Schedules Holidays Light Level Sensor Setup & Control Maintenance Overrides Dimmer Control Menu Dimmer Setpoints Schedule Proofs ANTI-SWEAT CONTROL MENU Anti-Sweat Status Menu Anti-Sweat Setup Anti-Sweat Circuit Setpoints Anti-Sweat Overrides SENSOR CONTROL MENU Sensor Status Menu Sensor Setup Sensor Setpoints Menu Sensor Alarms Menu Overrides Menu Sensor Scheduling Input/Output Control Analog Input Module Status Analog Output Module Status Digital Output Module Status Analog Input Module Bypass Analog Output Module Bypass Digital Output Module Bypass STATUS MENU HVAC Status Input Status BEC I&O Manual Table of Contents v

10 Sensor Status Menu Demand Status Anti-Sweat Status Menu Schedules Boiler Status Dimmer Status CONFIGURATION MENU Input Definition Output Definition System Information Temperature Display Format D.P./Humidity Sensor Offsets Communication Host Network Menu I/O Board Setup Satellite Communications DEMAND CONTROL MENU Demand Status Demand Setpoints KW Sensor Select KW Sensor Setup Load Shed Status Load Shed Setpoints Menu Load Shed Setup Menu LOGS AND GRAPHS AHU LOGS Logs Run Times Reset Run Times Graphs Log Interval ANTI-SWEAT DAILY LOGS SENSOR LOGS MENU Interval Daily Min/Max Logs Daily ON Time/# ON Events DEMAND LOGS MENU Window Log Daily Log Monthly Log GRAPHS Control Menu View Graph ALARMS ALARM LOG HEAT/COOL ALARMS ALARMS FAN FAIL ALARM BYPASS DIGITAL ALARMS ANALOG ALARMS (ALL TYPES EXCEPT IRLDS) ANALOG ALARMS (IRLDS ONLY) ALARM OVERRIDES vi Table of Contents Rev

11 10.9. SEND TO 485 ALARM PANEL ALARM SETPOINTS APPENDIX A TROUBLESHOOTING GUIDE FOR THE BEC... A-1 APPENDIX B BEC TECHNICAL SPECIFICATIONS... B-1 APPENDIX C BEC FRONT PANEL SCREENS... C-1 APPENDIX D SENSOR HARDWARE/SOFTWARE SETUP TABLE... D-1 INDEX... I-1 BEC I&O Manual Table of Contents vii

12

13 1 Introduction 1.1. BEC The Building Environmental Control (BEC) (P/N ) is a microprocessor-based control system designed to monitor and control all aspects of heating, air conditioning, and environmental conditions in medium to large buildings. Up to six air handling units (AHUs), each with six cooling stages and eight heating stages, can be controlled by a single BEC. AHU fans may be single-speed, two-speed, or variable-speed. The BEC can be programmed with environmental set points that change based on the time of day, season, and occupancy of the building and control AHUs accordingly. The BEC controls space humidity in a building by monitoring either dewpoint or relative humidity and activating stages of cooling within an AHU. To control condensation on windows, the BEC may control up to eight anti-sweat heaters in two different zones. Schedules can be used to control loads such as indoor lighting or outdoor signs. The BEC contains 24 individual time schedules that can be set as needed. Schedules may also be used by AHUs, sensors, and other components as a means of changing operational settings during periods when the building is unoccupied. Up to 64 sensor inputs and sensor-controlled outputs are available on the BEC to control and monitor items such as exhaust fans, unit heaters, and satellite air conditioners. In conjunction with a light dimmer panel, the BEC may control the light level within a building based upon the amount of outside light. The BEC can control up to four separate lighting zones. The BEC may be configured to monitor and control the amount of power used by a building. The BEC predicts the amount of power that the building will use based upon the rate of consumption and then sheds loads to keep the power usage under the demand level. The BEC sheds loads by examining user-defined priority settings. Like all REFLECS products available from CPC, the BEC keeps a historical log of alarms and inputs, and when equipped with a modem, it may be configured to automatically dial a remote location whenever an alarm condition occurs. Complete control of the BEC from a remote location may be achieved using UltraSite Manual This manual has been revised to give CPC customers better access to BEC information. This manual has been divided into smaller sections that are arranged in an order that correlates with a typical BCU installation. The manual begins with a hardware overview and hardware mounting instructions. The next two sections (4 & 5) include information that describes how the REFLECS network operates and is configured. Section 6 is an overview of the software that is used by the BEC. Section 7 presents an outline that can be used as a guide for users who have not installed a BEC system before. The system navigation section of previous manuals has been broken into three new sections: Section 8, System Setup; Section 9, Logs and Graphs; and Section 10, Alarms. Appendix A is a guide to troubleshooting commonly experienced problems with the BEC for first time users. If you are experiencing a problem, please refer to Appendix A before calling CPC s technical support department. If your problem is not addressed in Appendix A, contact CPC for additional help. Appendix B contains a table that lists the technical specifications of the BEC. Screen trees for the BEC are included in Appendix C. BEC I&O Manual Introduction 1-1

14

15 2 Hardware Overview 2.1. Introduction Computer Process Controls uses both an RS485 host network, I/O network, and an RS232 remote communication network to monitor and manage all aspects of building control. Within the framework of each of these networks various components are required to monitor environmental conditions and system performance; control system operation; and interact with remote communication packages. The brain of any CPC network is the REFLECS controller. REFLECS is an acronym for (REF)rigeration, (L)ighting, and (E)nvironmental (C)ontrol (S)ystem. The following list categorizes the current REFLECS line of controllers: Environmental Control Building Control Unit (BCU) Building Environmental Control (BEC) Data Logging Intelligent Data Logger (IDL) Refrigeration Control Refrigeration Monitor and Control (RMC) Refrigeration Monitor and Case Control (RMCC) CPC REFLECS controllers are designed to perform three specific tasks: system control, system monitoring, and data storage. Each controller depending on its software package is tailored to perform one or all of these three tasks. In general, a standard environmental control network will consist of the following components: 1. BEC 2. Various input and output communication boards Alarm Panel 4. RS232 Bus Amplifier 5. Remote communication modem & UltraSite 6. Network wiring 7. Sensors and loads The following sections provide an overview of the function of each of these components Building Environmental Control The Building Environmental Control primarily interacts with AHUs. In addition, the BEC provides extensive load scheduling and power management features that allow the user to develop HVAC and lighting schedules based on building occupancy levels. All building control system components must be connected to the BEC for proper monitoring and control of the system. The BEC has connections for I/O, host, and remote communication components. Sensors, lights, and AHUs, while not directly connected to the BEC, are accessed by the controller through communication boards. The BEC consists of a rugged steel enclosure containing a processor board and Power Interface Board (PIB). The Processor Board (Figure 2-1) contains the LCD screen, the main processor, and the memory chips that hold all the code required to operate the BEC and the data entered at the front panel or through UltraSite. The Processor Board is mounted on the door of the enclosure and is connected to the PIB with a ribbon cable. The PIB (Figure 2-2) contains all power and network connections required to power the BEC and drive the network, and is attached to the rear wall of the enclosure. Installation of the BEC consists of mounting the unit in an easily accessible location. All communication boards, additional BECs, alarm panels, and remote communication equipment must be wired to the BEC. A 120/208 volt power supply is required to provide power to the unit. The BEC must be configured based on the HVAC components to be controlled and the operational schedule of the building. BEC I&O Manual Hardware Overview 2-1

16 Input Communication Boards To properly interact with any environmental control system, the REFLECS requires constant, accurate system information. CPC provides this information to the REFLECS through a series of input communication boards. Except for boards designed to supply both input and output functions, the 16AI Analog Input Board is the only input board used by CPC LEGEND 7 Ribbon Cable Connection to Power LCD Screen Contrast Dial Interface Board Main Processor Chip Ribbon Cable Connection to Keypad 8 RAM Battery Flash Memory Chips 9 Clock Battery Manufacture Date 10 Network Baud Rate Dip Switch RAM Chips 16AI Board The 16AI Analog Input Board (P/N ) is a general-purpose input board capable of receiving an input signal through any of 16 two-wire input connections. To function, the 16AI must be connected through the RS485 I/O network to the REFLECS. When properly installed, the board receives either digital or analog data from sensors wired to any of the 16 input connections located on the board. Input definition screens within the REFLECS allow the user to define each input for building environmental control. A maximum of ten 16AIs may be connected to a BEC through the RS485 COM A and D networks Figure REFLECS Processor Board Within an environmental control system, the 16AI may be connected to a watt-hour transducer, power monitor, and temperature and humidity sensors.the 16AI Board is designed with several features that make it easy to install, wire, and configure. These main user interface features are shown in Figure 2-3. Figure AI Analog Input Board Figure Power Interface Board 2-2 Hardware Overview Rev

17 Output Communication Boards When a REFLECS receives data from the 16AI board, it interprets that information based on current stored set points. System changes required as a result of this examination are then made through one of several output communication boards. CPC offers four different output boards for environmental control: 1) 8RO, Relay Output Board, 2) 8RO FC, Form C Relay Output Board, 3) 4AO, Analog Output Board, and 4) 8DO, Digital Output Board. A maximum of twelve 8ROs and 8RO-FCs may be connected to a BCU through the RS485 COM A and D networks RO Board The 8RO Relay Board (P/N ) is a general purpose board capable of supplying an output signal through any of eight standard contact relays. A maximum of fifteen 8ROs or 8RO-FCs may be connected to a BEC through the RS485 COM A and D networks. To function, the 8RO board must be connected through the RS485 I/O network to the REFLECS. When properly installed, the 8RO receives an electrical impulse from the REFLECS, which either opens or closes any of eight contact relays. Output definitions within the REFLECS allow the user to configure the 8RO board to interact with any environmental control component. Figure RO Relay Output Board RO Form C Board A maximum of fifteen 8ROs or 8RO-FCs may be connected to a BEC through the RS485 COM A and D networks. The 8RO Relay Output Board with Form C contacts (P/N ) (Figure 2-5) is identical in function to the standard 8RO board, except that it uses relays with form C contacts and does not use fail-safe jumpers (wiring the contacts as either normally open or normally closed creates the failsafe condition). The 8RO-FC is slightly larger than the standard 8RO; therefore, use the mounting instructions for the 8RO-FC provided in Section 3.2., I/O Boards and Enclosures. The 8RO board is the direct link between the REFLECS and environmental control component operation. Information gathered by the controller from the 16AI board or 8IO board is checked against current stored set points. If differences in the received input data and the set point information are detected, a signal is either sent to the proper 8RO relay, or an existing signal is discontinued. Through the use of this relay signal, environmental control functions can be properly maintained by a simple contact closure sequence that is determined by the REFLECS. Like the 16AI input board, the 8RO board is easily installed and operated within the CPC network environment because of its straight forward design. Several of these features are shown in Figure 2-4 Figure RO-FC Relay Output Board with Form C Contacts BEC I&O Manual Hardware Overview 2-3

18 AO Analog Output Board A single 4AO may be connected to a REFLECS through the RS485 COM A and D networks. The 4AO Analog Output Board (Figure 2-6), is configured with four analog output connections that provide a variable voltage signal to any of four variable speed compressors that may be controlled by a single RMCC. Figure DO Digital Output Board 2.4. Special Purpose Communication Boards Figure AO Analog Output Board DO Digital Output Board Up to two 8DOs may be connected to a BEC through the RS485 COM A and D networks. The 8DO digital output board (Figure 2-7) is similar to the 8RO board, except that instead of a relay that closes on and off, each output generates either a high (12 V DC) or low (0 V DC) signal. The 8DO has eight outputs which may pulse up to 150 ma at 12 V DC. The 8DO s primary functions are to control anti-sweat heaters and light dimmer panels. Special purpose communication boards are boards that either possess greater capabilities than standard input and output boards, or combine the features of both input and output boards into a single package IO Board The 8IO combination input and output board (P/N ) is a communication board designed to provide input and output functions within the same board when space restrictions do not allow for installation of dedicated boards. Like the 16AI and the 8RO, the 8IO must be connected to the REFLECS to perform input retrieval and output transmission functions. The 8IO has input and form C relay output connections for monitoring of sensors and control of loads. The 8IO has no memory capability or hand-held terminal jack for direct connection to the board. The 8IO is shown in Figure 2-8. When programming the REFLECS, the 8IO must be listed as one 16AI board and one 8RO board. A maximum of nine 8IO boards can be connected to a single BEC controller. 2-4 Hardware Overview Rev

19 1. Alarm reset. 2. Date and time adjustment. 3. Storage of twenty separate alarms. 4. Audible annunciation can be set to either pulsed or continuous mode. 5. Interfaces with existing facility alarm system pin parallel printer port. Wiring of the alarm panel to the REFLECS is discussed in Section 4.3., RS485 Host Network (COM B) Figure IO Combination Input/Output Communication Board 1 Date/Time Button 2 Screen Scroll Buttons 3 Alarm Reset Button LEGEND 4 LED Power Indicator 5 LCD Alarm Screen 6 LED Alarm Indicator Alarm Panel One of the most important requirements of any network environment is its ability to notify personnel of system failures or possible problems. The REFLECS is designed with sophisticated logging, graphing, notification, and alarming features that put system data at the fingertips of the service technician or store manager. However, no network is complete without the basic ability to provide annunciated alarms in the event of a serious system problem. CPC uses the 485 Alarm Panel (P/N or ) (Figure 2-9) to accomplish this task. The 485 Alarm Panel is linked to all REFLECS Controllers through the RS485 COM B Host Network. Although the alarm panel has many features that make it a powerful notification tool, the primary and most important function of the alarm panel is to receive signals from the REFLECS and deliver alarm annunciation. The REFLECS constantly compares real time system conditions against user-defined alarm set points. When a system reading falls outside of a set point, a signal is sent to the alarm panel, which in turn, emits an alarm signal and displays the alarm information on the notification screen. Other features of the alarm panel provide the user with additional information and capabilities. Some of the alarm panel s features include: Figure Alarm Panel 2.6. Remote Communication RS232 Bus Amplifier The RS232 Bus Amplifier (P/N ), shown in Figure 2-10, is used to connect CPC controllers together as an integrated communication system. Communication problems sometimes associated with large control systems such as limited cable lengths, data rate limitations, and terminal and modem communication interference are eliminated through the use of the RS232 Bus Amplifier. BEC I&O Manual Hardware Overview 2-5

20 Figure RS232 Bus Amplifier Modems To communicate with a site from a remote location, the network must be connected to a modem directly, or through the RS232 Bus Amplifier. CPC offers a standard data modem (P/N ) for use with the REFLECS network. The REFLECS and CPC s RS232 Remote Communication Network are designed to connect to and be compatible with most modems in use today UltraSite Remote communication with a site controlled by the REFLECS is accomplished using UltraSite (P/N ), CPC s remote communication software package. UltraSite is a Microsoft Windows -based program that uses animated graphics, icons, buttons, and tabular and graphical data to display real-time conditions of a site. UltraSite accesses a site controller through the on-site modem, and, if present, the RS232 Bus Amplifier. All commands available through the front panel of the REFLECS as well as some screens not available through the front panel may be accessed through UltraSite using pop-up dialog boxes. Dialog boxes that appear in Ultra Site display the same information as would appear on the screen of the controller. Changes made to set points in the dialog boxes of UltraSite are immediately transferred to the unit. Individuals who have access to a laptop or a desktop computer may find it easier to program the REFLECS especially during a start-up using UltraSite. A comprehensive guide to UltraSite (UltraSite User s Guide) is available from CPC. 2-6 Hardware Overview Rev

21 3 Hardware Mounting 3.1. Building Environmental Control Location The operating environment of the BEC is -20 F (-28.9 C) to 120 F (48.9 C), and 0% to 95% humidity non-condensing. The Building Environmental Control (BEC) is the main controller of the CPC refrigeration control network. As such, it is the component most accessed by store managers and service technicians. The BEC should be located in an easily accessible area, but away from customers and most supermarket employees. Generally, the BEC is mounted in a motor room where access can be controlled. The BEC should be mounted in a location that can be limited in its access. It is a good idea to keep the controller as close to I/ O boards as possible. Mounting The REFLECS is supplied with 4 mounting holes in the rear panel of the enclosure. The mounting holes can be accessed without removing any of the boards inside the enclosure. Figure 3-1 shows the enclosure dimensions and weight. Figure BEC Mounting Dimensions 3.2. I/O Boards and Enclosures Location The 16AI, 8RO, 8RO-FC, 8DO, 4AO, and 8IO boards are usually installed within the refrigeration rack or the condenser by the equipment manufacturer. Therefore, the installer need only make the necessary connections between the REFLECS, the condenser boards, and the refrigerated cases. In some instances, an installer may be required to mount an I/O board. There are no restrictions on the location of these boards; however, for ease of network configuration, it is recommended that the boards be located adjacent to the REFLECS. If the boards are not located near the REFLECS, ensure the leg and segment length restrictions described in Section 4.6. are followed. I/O boards may be mounted without an enclosure, but they should be mounted in a location that is not easily accessible to avoid tampering or damage. Single Enclosure Mounting for I/O Boards The Single enclosure is supplied with 4 mounting holes in the rear panel of the enclosure. The mounting holes can be accessed without removing any of the boards inside the enclosure. Figure 3-2 shows the enclosure dimensions and weight. Figure 3-6 shows mounting dimensions for the 16AI, 8RO, and the 8DO. Figure 3-7 shows mounting dimensions for the 8RO-FC. BEC I&O Manual Hardware Mounting 3-1

22 8IO Weather Resistant Enclosure Mounting The 8IO Combination Input/Output Board is generally supplied with a weather resistant enclosure. The weather resistant enclosure is supplied with 4 mounting holes on flanges at the top and bottom of the enclosure. The mounting holes can be accessed without removing any of the boards inside the enclosure. Figure 3-4 shows the enclosure dimensions and weight. Figure 3-8 provides mounting dimensions for the 8IO/ARTC. Figure Single Enclosure Mounting Dimensions Double Enclosure Mounting for I/O Boards The Double enclosure is supplied with 4 mounting holes in the rear panel of the enclosure. The mounting holes can be accessed without removing any of the boards inside the enclosure. Figure 3-3 shows the enclosure dimensions and weight. Figure 3-6 shows mounting dimensions for the 16AI, 8RO, and the 8DO. Figure 3-7 shows mounting dimensions for the 8RO-FC. Figure Weather Resistant Enclosure 16AI, 8RO, and 8DO Boards Without Enclosures 16AI, 8RO, and 8DO boards not supplied with an enclosure are supplied with a snap-track for easy installation. The insulation sheet and I/O board must be removed from the track before the track is mounted. The snap-track is mounted using the.1875-inch mounting slots. Figure 3-5 shows this installation procedure. Figure 3-6 provides mounting dimensions for the 16AI, 8RO, and the 8DO boards. Figure Double Enclosure Mounting Dimensions 3-2 Hardware Mounting Rev

23 1. REMOVE THE 16AI OR 8RO BOARD AND THE INSULATOR FROM THE SNAP-TRACK. 2. MOUNT THE SNAP-TRACK USING THE.1875" SLOTS PROVIDED. 4. REINSTALL THE 16AI OR 8RO BOARD IN THE SLOTS IN THE SNAP-TRACK. 3. REINSTALL THE INSULATOR IN THE SNAP-TRACK. Figure RO-FC Mounting Dimensions IOs Without Enclosures Mounting 8IO boards not supplied with an enclosure are supplied with.500-inch long metal stand-off dowels that are pressed into the mounting holes in the board. Figure 3-8 shows the mounting dimensions for the 8IO and ARTC boards Figure AO, 8RO, or 16AI Snap-Track Installation Figure AI/8RO/8DO Mounting Dimensions 8RO Form C Boards Without Enclosures The 8RO Form C board is slightly larger than the 16AI and 8RO boards, and is not supplied with a snap-track. If the 8RO-FC is supplied without an enclosure it is supplied with.500-inch long metal stand-off dowels which are pressed into the mounting holes in the board. Figure 3-7 shows the mounting dimensions for the 8RO-FC. Figure IO/ARTC Mounting Dimensions 4AO Boards Without Enclosures Mounting 4AO boards not supplied with an enclosure are supplied with a snap-track for easy installation. The insulation sheet and I/O board must be removed from the track, and the track mounted using the.1875-inch mounting slots. Figure 3-5 shows this installation procedure for 16AI and 8RO boards. Installation for the 4AO board is identical. Figure 3-9 provides mounting dimensions for the 4AO board. BEC I&O Manual Hardware Mounting 3-3

24 3.4. RS232 Bus Amplifier Figure AO Mounting Dimensions Alarm Panel Location The 485 Alarm Panel is used to alert store personnel to system problems that require immediate attention; therefore, it is important to mount the panel where it will be visible and easily accessible. Mounting The 485 Alarm Panel is supplied with 4 mounting holes in the rear panel of the enclosure. The mounting holes can be accessed without removing any of the boards inside the enclosure. Figure 3-10 shows the enclosure dimensions and weight. Location Although there are no specific location requirements for installation of the RS232 Bus Amplifier, it is recommended that the amplifier be located close to the bussed CPC controllers to prevent data loss over long cable lengths. It is also recommended that the bus amplifier be located adjacent to the modem and, if present, the local computer terminal to provide easy access to all components necessary for building control. In some cases, location of the modem and local terminal will not allow location of the bus amplifier to both the modem and local terminal and the CPC controllers. Since data loss is possible when multiple CPC controllers transmit data over long cable lengths, it may be necessary to connect the CPC controllers to a remote amplifier adjacent to the controllers, and then connect the remote amplifier to a main amplifier connected to the modem and local terminal. For complete information on operation of the RS232 Bus Amplifier, refer to , RS232 Bus Amplifier Installation and Operation Manual. Mounting To mount the RS232 Bus Amplifier, 1. Remove the 4 front panel screws. 2. Remove the front panel (with circuit board attached). 3. Mount the empty amplifier body, with the power connection cut-out down. 4. Replace the front panel. Figure 3-11 shows the enclosure dimensions and weight. Figure RS232 Bus Amplifier Mounting Dimensions Figure Alarm Panel Mounting Dimensions 3-4 Hardware Mounting Rev

25 3.5. Temperature Sensors Inside Temperature Sensor Location Inside temperature sensors are supplied within a wallmounted enclosure for attachment to a standard switch plate. The temperature sensor should be located in a central location within the zone to be measured away from doors, windows, vents, heaters, and outside walls that could affect temperature readings. The sensor should be between 4 and 6 feet from the floor. Mounting Mount the sensor using the screws provided as shown in Figure and clamp (P/N ) which may be mounted as shown in Figure 3-13 (fasteners are not provided). Figure Outside Temperature Sensor with Cover and Clamp Insertion Temperature Probe Location The 12-inch insertion temperature probe may be used to monitor temperature in either the supply or return air ducts of the AHU. Mounting The insertion probe may be mounted in any orientation within the duct as long as the probe is in the air flow of the duct. The probe housing should be secured using self-tapping screws. A diameter hole is required for the probe. Figure 3-14 shows the installation of the insertion probe (self-tapping screws are not provided). Figure Inside Temperature Sensor Mounting Outside (Ambient) Temperature Sensor Location The outside or ambient temperature sensor should be located on the north side of the building, preferably under an eave to prevent sun-heated air from affecting the temperature of the sensor. Mounting The temperature sensor may be mounted using any standard tubing clamp. CPC also offers an aluminum cover Figure Inch Insertion Probe Mounting Supply and Return Air Sensors In addition to the 12-inch insertion temperature probe, CPC uses the same temperature sensor used for outside and BEC I&O Manual Hardware Mounting 3-5

26 inside temperature to monitor supply and return air temperature. When used in this application, the sensors are supplied without enclosure covers. The sensors should be mounted directly in the air stream of the supply or return air duct. The sensors are not supplied with any mounting hardware for this application Humidity Sensors and Humidistats Use the installation and operation instructions supplied with these products for all mounting information Light Level Sensor Location The Light Level Sensor should be located facing north (away from direct sunlight). Mounting The light level sensor is not supplied with mounting hardware. The sensor should be mounted horizontally through the knockout of a standard weather-resistant junction box. Figure 3-16 shows a typical mounting configuration Dew Point Sensors and Control Switches Dew Cell Dew Point Probe Location The Dew Cell Dew Point Probe should be located 4 to 6 feet from the floor with the probe pointing up. It is recommended that the Dew Cell Dew Point Probe be mounted in an area where it will be exposed only to minimal amounts of dust. Mounting Mount the probe using the standard switch cover supplied with the unit as shown in Figure Figure Light Level Sensor Typical Mounting 3.9. Power Monitors CPC uses standard off-the-shelf power monitors for power monitoring. Installation instructions supplied with monitoring units should be used for both the watt-hour transducer and the transducer power supply Transformers Figure Dew Cell Dew Point Probe Mounting Dew Point Control Switch Use the installation and operation instructions supplied with this product for all mounting information. Transformers should be located within 10 feet of the board it is powering, preferably within the board enclosure. Use the installation instructions supplied with the transformer for specific mounting details. 3-6 Hardware Mounting Rev

27 4 The REFLECS Network 4.1. Introduction The REFLECS uses four separate networks: 1. The RS485 Input/Output (I/O) Network (COM A) connects the controller to the input and output communication boards. 2. The RS485 Host Bus Network (COM B) connects multiple controllers to a 485 alarm panel. 3. The RS232 Remote Communication Network (COM C) connects multiple controllers to a modem, thus allowing remote communication. 4. The RS485 Input/Output (I/O) Network (COM D) is an additional I/O network that connects the controller to the input and output communication boards. The following sections provide an overview of the basic network components and their function. Wiring requirements for each of the networks is provided in Section 5, Wiring for Network & Power Connections RS485 Input/Output (I/O) Network (COM A and D) The RS485 Input/Output (I/O) network connects all input and output communication boards together in an open communication loop. This loop connects the REFLECS to multiple input and output communication boards, and terminates at the last input or output board on the network. The term daisy-chain is applied to this open loop arrangement. The REFLECS is configured to monitor and control two separate RS485 input/output communication networks. These two networks are labeled as either COM A or COM D. Each network is capable of supporting up to 31 separate input or output boards, plus the single REFLECS controller. This means that a single REFLECS can monitor or control up to sixty-one individual input or output boards. Figure 4-1 shows the I/O network configurations. The concept of a loop is critical to operation of the I/O network. The REFLECS cannot properly interact with the input and output boards unless the boards are connected and identified within the confines of the loop. The I/O network is always identified as COM A or COM D on the controller. Input and output communication boards are configured with a RS 485 network connection only, which can be used to connect the board to either COM A or COM D. In addition to the primary loop arrangement, a single star configuration may be connected to the loop. A more indepth explanation of CPC network wiring practices is provided in Section 5, Wiring for Network & Power Connections. Figure Network Loop Wiring Configurations 4.3. RS485 Host Network (COM B) Similar to the I/O network loop, the host network, shown in Figure 4-2, also uses an open loop configuration. The primary function of the Host Network Loop is to allow single or multiple REFLECS Controllers to be connected together to one common 485 Alarm Panel. The Host Network is always labeled as COM B on the REFLECS. Input and output boards cannot be connected directly to the host network. Figure RS485 Host Communication Network (COM B) BEC I&O Manual The REFLECS Network 4-1

28 4.4. RS232 Remote Communication Network (COM C) The RS232 Remote Communication Network connects single or multiple REFLECS Controllers to a modem to provide remote access using a remote communication software package. In some configurations, an RS232 Bus Amplifier may be installed to improve transmission rates and overall data quality. Like the host network, input and output boards cannot be connected directly to the remote communication network. Figure 4-3 shows a typical remote communication network layout Leg and Segment Wire Length A single segment connected to COM A, B, or D may not exceed 4000 feet. Therefore, the combined length of all legs in a single segment may not exceed 4000 feet. This length restriction includes the length of legs in a single star configuration described in Section 4.9., Star Configurations. A single segment connected to COM C may not exceed 2500 feet Number of Devices per Segment Figure RS232 Remote Communication Network (COM C) 4.5. Legs and Segments A leg is defined as a cable running between two devices such as two communication boards, or a REFLECS unit and a communication board. A segment is defined as the total combined length of all legs connected to one REFLECS power interface board output connection such as the COM A or COM D connections. Figure 4-4 demonstrates the relationship between legs and segments. A single segment may have no more than 32 devices. A device is considered to be any controller, board, or alarm panel and includes the parent controller. That is, a unit with a single segment connected to COM A may have an additional 31 devices connected to the segment. There are restrictions to the number of each board type that may be connected to the COM A and D networks. No more than fifteen 8ROs or 8RO-FCs, ten 16AIs, four 4AO, and two 8DOs may be connected to both the COM A and COM D networks at the same time. In addition, an 8IO board must be listed as one 16AI and one 8RO and possibly a 4AO (see Section ) Daisy Chains Except for the single star configuration described below, all devices in a segment must be connected in an open loop or daisy chain configuration. A daisy chain must start with the first device in the segment and continue to the last device. Branching from a device in the middle of the segment is prohibited. Figure 4-5 demonstrates correct and incorrect daisy chain configurations. Figure Relationship Between Legs and a Segment Figure Correct and Incorrect Loop Configurations 4-2 RS232 Remote Communication Network (COM C) Rev

29 4.9. Star Configurations Within a single segment, a single star branching from a single device is allowable. A star is multiple devices connected to a single device within a segment. The device from which the star extends is called the hub. The legs within a star may not exceed 100 feet. No more than one star in a single segment is permitted. Star configurations are not permitted on the COM B, Host, and COM C, Remote Communication, networks. Figure 4-6 shows correct and incorrect star configurations. DAISY CHAIN CONFIGURATION SET TERMINATING JUMPERS: UP DOWN DOWN UP Figure 4-7-Terminating Jumpers for a Daisy Chain Configuration Figure Correct and Incorrect Star Configurations Terminating Resistance Jumpers (COM A, COM B, and COM D Only) Each device that may be connected to a segment has a set of terminating resistance jumpers (one jumper for each wire lead). These jumpers are always labeled JU1, JU2, and JU3 for COM A. COM B jumpers are always labeled JU4, JU5, and JU6. COM D jumpers are always labeled JU9, JU10, and JU11. The purpose of the jumpers is to indicate the two ends, or termination points, of the segment. If a segment contains a star, the hub of the star must be one of the segment termination points. The other termination point in the star configuration is the longest leg contained in the network. If a device is at either end of a segment (Figure 4-7), or if the device is the hub of a star (Figure 4-8), the terminating resistance jumpers must be set in the up position. All other devices in a segment should have their jumpers set to the down position. No segment shall have more than two devices with the terminating resistance jumpers in the up position. Figure 4-8-Jumper Settings for Star Network Network Dip Switches and Rotary Dials (COM A and D only) Each device that may be connected to a segment has either a network dip switch or rotary dials that provide a unique identifier for each device on the network. Devices on a segment may be numbered in any order; however, gaps or omissions in the numbering sequence are not permitted. As an example, if a segment contains four devices, then board addresses one, two, three, and four must be used; one, two, three, and five would not be permitted. When setting network dip switches and dials, both COM A, COM B, and COM D must be considered together. If the last device on COM A is numbered five, then the first device on COM D must be numbered six. BEC I&O Manual The REFLECS Network 4-3

30 The REFLECS identifies the board types on the network; therefore, boards that are the same type are numbered together. For example, if a segment contains four 16AI boards and five 8RO boards, the 16AIs are numbered one, two, three, and four; and the 8ROs are numbered one, two, three, four, and five. Figure 4-9 provides a graphic representation of board numbering. Actual dip switch and rotary dial setup is described fully in Section , Baud Rate Dip Switches (COM A and D only). 1 and 31; however, network restrictions limit the actual number of boards that may reside on both the COM A and COM D networks at one time. These restrictions are given in Section 4.7., Number of Devices per Segment. Use Figure 4-10 to determine the switch settings for 16AI, 8RO, and 8RO-FC boards. If a pulse type input is connected to a 16AI Board with software older than version E.02, it must be connected to input one and rocker number eight on the board s network dip switch and must be configured to the ON or up position. Figure Network Device Numbering Baud Rate Dip Switches (COM A and D only) All networks (COM A, B, C, D) have specific baud rate requirements; however, only COM A and COM D require manual setting of the baud rate dip switch. Currently, the baud rate dip switch in network components may be set at either 4800, 9600, 19,200, and 38,400. Setting of the baud rate is accomplished using switch S1 on the REFLECS processor board, the RS485 alarm panel board, and 4AO, 8RO, and 8RO-FC output boards; and switch S3 on the 16AI input board. The COM B baud rate is preset on the REFLECS and 485 Alarm Panel dip switch S1 at The 8IO board automatically adjusts to the required baud rate Network Settings For all boards, except 8IO and 8DO boards, the network dip switch labeled S1 (or S3 for the 16AI board) is used to set the unique board number of the unit and the baud rate. The 8IO uses rotary dials to set the board number of the unit and the baud rate is set internally at Network Addresses Board numbering is accomplished using the first five rockers on dip switch S3 on the 16AI board, the first five rockers on dip switch S1 on the 8RO and 8RO-FC boards, and two rotary dials on the 8IO and 8DO boards. Dip Switches Each of the first five rockers of either S1 or S3 is given a value which is twice as large as the value for the rocker to the left of it. The first rocker is given a value of one. With these five rockers, a board may be given any value between Figure Network Address Settings for Dip Switch S1 or S3 on I/O Boards Network Addresses for 8IO & 8DO Boards The 8IO and 8DO boards use rotary dials to set the network address instead of dip switches. The rotary dial S1 is used to define the output portion of the board. Therefore, the board may only be defined as board 1 through 9. Likewise, dial S2 is used to define the input portion of the board and may be set from 1 to 9. LED Indicator Lights Each board contains a green LED Power Indicator Light. This light indicates whether or not the board is receiving power. It also indicates if the board is on-line with the network by sending a pulsing signal Baud Rate Dip Switch Settings The ARTC, 8IO, and 8RO-FC have a dip switch (S2) which indicates the state of the relay (NC or NO). When the relay is set normally closed, the appropriate LED relay indicator (1 through 8) is illuminated. Dip switch rockers 1 through 8 should be set to the up position if the relay is 4-4 Network Settings Rev

31 wired normally closed and down if the relay is wired normally open COM A and D Networks The COM A and D networks may be set to either 4800, 9600, 19,200, or 38,400 baud. Positions one and two of the dip switch located on the processor board of the RMCC are used to set the baud rate. A different baud rate setting may not be set for the COM A and D networks. Positions six and seven on dip switch S1 of the 4AO, 8RO, and 8RO-FC, and switch S3 of the 16AI, are used to set the baud rate for the communication boards. This baud rate should match the setting for the RMCC. Figure 4-11 shows the possible baud rate settings and dip switch positions for the COM A and D networks. Boards using Form C contacts do not have fail-safe devices, since the contacts are wired for the position required during power loss, but have a dip switch which illuminates the LED relay indicator depending on the contact position. The 8RO has both a fail-safe dip switch (S2) to force the contacts open or closed if the network fails, and a jumper for each output (JU4 through JU11) that forces the contact open or closed during a power loss. Figure 4-12 shows the possible settings for the dip switch and jumpers. COM A AND D BAUD RATE COM A AND D BAUD RATE COM B BAUD RATE (PRESET AT 4800) AO, 8RO, AND 8RO-FC (SWITCH S1) 16AI (SWITCH S3) REFLECS PROCESSOR BOARD Figure Baud Rate Dip Switch Settings 8IO Baud Rates Baud rate settings for the 8IO board are automatically adjusted by the board based on the baud rate setting of the RMCC. The 8IO can communicate at baud rate settings between 4800 and 38, COM B Network The COM B baud rate is preset on the RMCC and 485 Alarm Panel dip switch S1 at 4800 since the 485 alarm panel can only communicate at 4800 baud COM C Network The COM C baud rate setting is established within the remote communications screens in the RMCC and is related to the speed of the modem being used at the supermarket. The RMCC can communicate at 300, 1200, 2400, and 9600 baud. It is recommended that a baud rate of 9600 be used for remote communication. Figure RO Board Fail-Safe Dip Switch and Jumper Settings The ARTC, 8IO, and 8RO-FC have a dip switch (S2) which indicates the state of the relay (NC or NO). When the relay is set normally closed, the appropriate LED relay indicator (one through eight) is illuminated. Dip switch rockers one through eight should be set to the up position if the relay is wired normally closed and down if the relay is wired normally open Fail-Safe Dip Switch Settings CPC uses two fail-safe devices on its output boards: a dip switch and jumpers. These two devices are used to provide fail-safe operation of equipment in the event of either power loss or network communication loss. The use of these devices differs depending on the board or controller. BEC I&O Manual The REFLECS Network 4-5

026-1608 Rev 0 6-13-00. NetCom Card Installation and Programming Guide

026-1608 Rev 0 6-13-00. NetCom Card Installation and Programming Guide 026-1608 Rev 0 6-13-00 NetCom Card Installation and Programming Guide 1640 Airport Road, Suite 104 Kennesaw, GA 31044 Phone: (770) 425-2724 Fax: (770) 425-9319 ALL RIGHTS RESERVED. The information contained

More information

PART 8: FIELD WIRING. n WARNING NOTICE. Boiler Manual

PART 8: FIELD WIRING. n WARNING NOTICE. Boiler Manual PART 8: FIELD WIRING A. INSTALLATION MUST COMPLY WITH: 1. National Electrical Code and any other national, state, provincial or local codes or regulations. 2. In Canada, CSA C22.1 Canadian Electrical Code

More information

ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL

ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL RANCO INSTALLATION INSTRUCTIONS ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL Relay Electrical Ratings PRODUCT DESCRIPTION The Ranco ETC is a microprocessor-based family of electronic temperature controls,

More information

Variable Air Volume - VAV

Variable Air Volume - VAV Mode Enable Sensor Options Variable Air Volume - VAV The temperature of this sensor will determine if the unit is in heating, cooling or vent mode during occupied operation. The following options are available:

More information

Workshop 7 PC Software - Tracker

Workshop 7 PC Software - Tracker Workshop 7 PC Software - Tracker Goal: You will startup and perform advanced setup functions using Tracker PC software. You will also setup equations to control MP503 binary outputs. The Binary Output

More information

IPX AUTOMATIC IP NETWORK LOSS BACKUP A/B SWITCH INSTRUCTION BOOK IB6444-02

IPX AUTOMATIC IP NETWORK LOSS BACKUP A/B SWITCH INSTRUCTION BOOK IB6444-02 IPX AUTOMATIC IP NETWORK LOSS BACKUP A/B SWITCH INSTRUCTION BOOK IB6444-02 TABLE OF CONTENTS DESCRIPTION 2 MOUNTING INSTRUCTIONS 2 HOW TO CABLE THE IPX 2/3 POWER SUPPLY INSTALLATION 3 OPERATION 3 CARE

More information

026-1610 Rev 12 25-APR-2011. E2 Installation and Operation Manual for RX Refrigeration, BX HVAC, and CX Convenience Store Controllers

026-1610 Rev 12 25-APR-2011. E2 Installation and Operation Manual for RX Refrigeration, BX HVAC, and CX Convenience Store Controllers 026-1610 Rev 12 25-APR-2011 E2 Installation and Operation Manual for RX Refrigeration, BX HVAC, and CX Convenience Store Controllers Retail Solutions 3240 Town Point Drive NW, Suite 100 Kennesaw, GA 30144,

More information

Applied Electronics. Commercial Dimming System UPDATE NOTICE

Applied Electronics. Commercial Dimming System UPDATE NOTICE REV. A Applied Electronics Commercial Dimming System UPDATE NOTICE This notice is to inform the end user of an additional feature added to this DP12/2400 dimming unit. This unit has been outfitted with

More information

3500/93 System Display

3500/93 System Display 3500/93 System Display Bently Nevada* Asset Condition Monitoring Description The 3500/93 System Display is designed to meet the requirements of American Petroleum Institute (API) Standard 670 and provide

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS LIGHTING CONTROL PANELS 4 AND 8 RELAYS INSTALLATION INSTRUCTIONS INSTALLATION OVERVIEW The installation instructions contained in this document are provided as a guide for proper and reliable installation.

More information

TABLE 1: Wiring Terminals. Connect to... 1C 1H 2C 2H 1H1C 2H1C 2H2C 3H2C

TABLE 1: Wiring Terminals. Connect to... 1C 1H 2C 2H 1H1C 2H1C 2H2C 3H2C Installation TURN OFF POWER TO THE SYSTEM AT THE MAIN POWER PANEL TO AVOID ELECTRICAL SHOCK. Installation should be carried out by an electrician or a qualified technician. 1.1 Find a Location for the

More information

Liebert Universal Monitor

Liebert Universal Monitor Infrastructure Management & Monitoring For Business-Critical Continuity Liebert Universal Monitor User Manual TABLE OF CONTENTS 1.0 INTRODUCTION 1.1 Methods of Viewing and Configuring the Liebert Universal

More information

User Guide. Temperature and Humidity Datalogger. Model 42280

User Guide. Temperature and Humidity Datalogger. Model 42280 User Guide Temperature and Humidity Datalogger Model 42280 Introduction Congratulations on your purchase of the Extech 42280 Thermometer and Relative Humidity Datalogger. The 42280 is a wall-mount, tripod

More information

Temperature & Humidity SMS Alert Controller

Temperature & Humidity SMS Alert Controller Temperature & Humidity Alert Controller METERS 3 simple steps starting the unit: Insert the SIM card Plug in the sensors connectors Connect the AC power cord. Specifications: AC 90~260V Auto Select Internal

More information

Electronic Control Devices The European Product Catalogue 2007

Electronic Control Devices The European Product Catalogue 2007 FX14 Field Controller (1/4) FX14 Field Controller The FX14 is an equipment field controller in the Facility Explorer range of products. The controller is designed specifically for commercial Heating, Ventilating,

More information

EMBEDDED ACCESS CONTROL Hardware Installation Guide

EMBEDDED ACCESS CONTROL Hardware Installation Guide EMBEDDED ACCESS CONTROL Hardware Installation Guide Lenel goentry Hardware Installation Guide, product version 1.00. This guide is item number DOC- ENHW-ENU, revision 1.003, April 2009 Copyright 2009 Lenel

More information

026-1610 Rev 10 06-APR-2010. E2 Installation and Operation Manual for RX Refrigeration, BX HVAC, and CX Convenience Store Controllers

026-1610 Rev 10 06-APR-2010. E2 Installation and Operation Manual for RX Refrigeration, BX HVAC, and CX Convenience Store Controllers 026-1610 Rev 10 06-APR-2010 E2 Installation and Operation Manual for RX Refrigeration, BX HVAC, and CX Convenience Store Controllers 3240 Town Point Drive NW, Suite 100 Kennesaw, GA 30144, USA Phone 770-425-2724

More information

OZW30. Central Unit SYNERGYR

OZW30. Central Unit SYNERGYR 2 841 SYNERGYR Central Unit OZW30 Collects billing data from the apartments. Generates an image of each apartment's heat consumption and makes it available for readout. Acts on room temperature control

More information

Repeaters and Mimics Data Sheet

Repeaters and Mimics Data Sheet Repeaters and Mimics Data Sheet IDR series repeaters and mimics allow vital information from a Notifier fire system to be communicated to points around a building remote from the fire alarm control panel.

More information

Installation Guide. VisionPRO. TH8000 Series. Need Help? This manual covers the following models. System Types

Installation Guide. VisionPRO. TH8000 Series. Need Help? This manual covers the following models. System Types Installation Guide VisionPRO TH8000 Series Touch-screen Programmable Thermostat This manual covers the following models TH8110U: For 1 Heat/1 Cool systems TH8320U: For up to 3 Heat/2 Cool systems TH8321U:

More information

INSTALLER S & OWNER S MANUAL

INSTALLER S & OWNER S MANUAL INSTALLER S & OWNER S MANUAL HVAC INSTALLER: PLEASE LEAVE MANUAL FOR HOMEOWNER DEH 3000 DEH 3000 Part No. 4028539 Dehumidifier & Ventilation System Controller P.O. Box 8680 Madison, WI 53708 TOLL-FREE

More information

Electronic Control Devices The European Product Catalogue 2007

Electronic Control Devices The European Product Catalogue 2007 FX07 Field Controller (1/4) FX07 Field Controller Display Model Dimensions in mm (inches) The FX07 is a terminal unit controller in the Facility Explorer range of products. The controller is designed specifically

More information

NOTE: It is the responsibility of the installation organization to have only technically qualified personnel performing the installation.

NOTE: It is the responsibility of the installation organization to have only technically qualified personnel performing the installation. This quick start guide provides, basic installation information, drawings, first time power-on instructions, and short descriptions of key terms and concepts for installing the EntraGuard Platinum Telephone

More information

Sigma Control PC INSIDE. 97 psi 187 F R on load

Sigma Control PC INSIDE. 97 psi 187 F R on load Sigma Control PC INSIDE 97 psi 187 F R on load Innovation Sigma Control with a PC inside At Kaeser, we pride ourselves on being the world s leading innovator in air system technology. Over twenty-five

More information

Communication Capabilities via a Touch Screen or a Web Browser Further Expand Air-Conditioning Control Possibilities.

Communication Capabilities via a Touch Screen or a Web Browser Further Expand Air-Conditioning Control Possibilities. Communication Capabilities via a Touch Screen or a Web Browser Further Expand Air-Conditioning Control Possibilities. More Freedom to Administrators Connectable up to 128 Indoor Unit Groups (256 indoor

More information

Daker DK 1, 2, 3 kva. Manuel d installation Installation manual. Part. LE05334AC-07/13-01 GF

Daker DK 1, 2, 3 kva. Manuel d installation Installation manual. Part. LE05334AC-07/13-01 GF Daker DK 1, 2, 3 kva Manuel d installation Installation manual Part. LE05334AC-07/13-01 GF Daker DK 1, 2, 3 kva Index 1 Introduction 24 2 Conditions of use 24 3 LCD Panel 25 4 Installation 28 5 UPS communicator

More information

Table of Contents. 1 - Specifications...3. 2 - Installation...3. 3 - Wiring...5. 4 - User controls...7

Table of Contents. 1 - Specifications...3. 2 - Installation...3. 3 - Wiring...5. 4 - User controls...7 THERMOSTATS Table of Contents Page 1 - Specifications...3 1.1 - Product range...3 ARTTH001 (DSL-610)...3 ARTTH002 (DSL-700)...3 ARTTH003 (DSL-600)...3 1.2 - Technical data...3 1.3 - Power failures...3

More information

HMI display Installation Guide

HMI display Installation Guide HMI display Installation Guide Product Description Specifications Important Information o Package Contents o Related Documents o Accessories Cautions and Warnings Mounting and Dimensions o BAC-DIS-ENC

More information

SM6 Series Circuit Breaker Monitors CONSOLIDATED. Electronics, Inc. MONITORING THE FUTURE

SM6 Series Circuit Breaker Monitors CONSOLIDATED. Electronics, Inc. MONITORING THE FUTURE Series Circuit Breaker Monitors CONSOLIDATED Electronics, Inc. MONITORING THE FUTURE Why SF Gas Density Monitors? 6 Cut Maintenance Costs Your capital investment may be recovered with the elimination of

More information

Operation and Installation Manual

Operation and Installation Manual Operation and Installation Manual RCM-10 Remote Control Monitor and RSM-10 Remote Status Monitor for the CNA-100 & CNA-200 Automations Revision 1.1 9/98 WARRANTY INFORMATION The RCM-10 Remote Control

More information

Model: DC-A2IO Advanced HVAC Controller

Model: DC-A2IO Advanced HVAC Controller Model: DC-A2IO Advanced HVAC Controller Job Name: Schedule Reference: Date: DC-A2IO Advanced HVAC Controller Package PAC-IF01 M-Net Adapter AL2-14MR-D α2 Simple Application Controller Accessories AL2-2DA

More information

T0118 T2118 T3118. Instruction Manual

T0118 T2118 T3118. Instruction Manual Programmable indoor transmitter of temperature T0118 Programmable indoor transmitter of atmospheric pressure T2118 Programmable indoor transmitter of temperature, relative humidity and other derived humidity

More information

PowerLogic Sub Meter Display (SMD and SMDOPN)

PowerLogic Sub Meter Display (SMD and SMDOPN) Instruction Bulletin Z203742-0B PowerLogic Sub Display (SMD and SMDOPN) CONTENTS Introduction... 2 Parts of the Sub Display... 3 Dimensional Drawing... 4 Installation... 5 Mounting the SMD... 5 Mounting

More information

AC-115 Compact Networked Single Door Controller. Installation and User Manual

AC-115 Compact Networked Single Door Controller. Installation and User Manual AC-115 Compact Networked Single Controller Installation and User Manual December 2007 Table of Contents Table of Contents 1. Introduction...5 1.1 Key Features... 6 1.2 Technical Specifications... 7 2.

More information

Alliance System Ordering Guide

Alliance System Ordering Guide Alliance System Ordering Guide Multiple Technologies Versatile Hardware Powerful Software One family of parts and accessories Version 12-Nov-03 Alliance System Ordering Guide Table of Contents Controllers

More information

AMICO Information. Management System (AIMS)

AMICO Information. Management System (AIMS) AMICO Information Management System (AIMS) ALERT- 2 Installation and Maintenance Manual v 2.5 Table of Contents INTRODUCTION...3 Theory of Operation... 3 Network Diagram... 4 INSTALLATION... 5 Medical

More information

TCP/IP MODULE CA-ETHR-A INSTALLATION MANUAL

TCP/IP MODULE CA-ETHR-A INSTALLATION MANUAL TCP/IP MODULE CA-ETHR-A INSTALLATION MANUAL w w w. c d v g r o u p. c o m CA-ETHR-A: TCP/IP Module Installation Manual Page Table of Contents Introduction...5 Hardware Components... 6 Technical Specifications...

More information

INSTALLATION & SERVICE MANUAL. Display Panel

INSTALLATION & SERVICE MANUAL. Display Panel INSTALLATION & SERVICE MANUAL Display Panel The PowerLine EMS TM is a specialized power distribution and energy management system intended to be used in recreational vehicles. The Control Module is housed

More information

PRODUCT LIST Facility DDC Access WebXL DDC

PRODUCT LIST Facility DDC Access WebXL DDC PRODUCT LIST Facility DDC Access WebXL DDC Effective from 01/10/2014 Sphere Systems Pty Ltd Unit 6 / 9 Mirra Crt Bundoora Victoria Australia 3083 ABN 98 006 579 004 Phone +61 3 9470 8844 Fax +61 3 9470

More information

GSM Autodialer Professional GJD700 Speech & Text Autodialer

GSM Autodialer Professional GJD700 Speech & Text Autodialer Text Edit message GSM Autodialer Professional GJD700 Speech & Text Autodialer Introduction The GSM Autodialer Professional works in conjunction with standard alarm systems and makes use of your preferred

More information

HP 5 Microprocessor Control for Mammoth Water Source Heat Pumps

HP 5 Microprocessor Control for Mammoth Water Source Heat Pumps HP 5 Microprocessor Control for Mammoth Water Source Heat Pumps Operation and Maintenance Manual Model: 71028004 Applies to: Single Circuit Water-to-Water Twin Circuit Units Without DDC Controls MAMM WHSP

More information

OWNERS MANUAL. Status Monitor. for Windows 95, 98, ME, NT 4, 2000 & XP. SIGNALCRAFTERS TECH, INC. www.signalcrafters.com

OWNERS MANUAL. Status Monitor. for Windows 95, 98, ME, NT 4, 2000 & XP. SIGNALCRAFTERS TECH, INC. www.signalcrafters.com OWNERS MANUAL Status Monitor for Windows 95, 98, ME, NT 4, 2000 & XP SIGNALCRAFTERS TECH, INC. www.signalcrafters.com 57 Eagle Rock Avenue, East Hanover, NJ 07936 Tel: 973-781-0880 or 800-523-5815 Fax:

More information

Wireless Data Logger Monitoring Systems

Wireless Data Logger Monitoring Systems Wireless Data Logger Monitoring Systems Table of Contents About MadgeTech, Inc. Wireless Systems & Components Wireless Data Loggers 2000A Wireless Data Logger Models MadgeTech Cloud Services MadgeTech

More information

User Manual. Humidity-Temperature Chart Recorder. Model RH520

User Manual. Humidity-Temperature Chart Recorder. Model RH520 User Manual Humidity-Temperature Chart Recorder Model RH520 Introduction Congratulations on your purchase of the Extech RH520 Temperature + Humidity Chart Recorder. The RH520 measures and displays Temperature,

More information

User's Guide. Integrating Sound Level Datalogger. Model 407780. Introduction

User's Guide. Integrating Sound Level Datalogger. Model 407780. Introduction User's Guide 99 Washington Street Melrose, MA 02176 Phone 781-665-1400 Toll Free 1-800-517-8431 Visit us at www.testequipmentdepot.com Back to the Extech 407780 Product Page Integrating Sound Level Datalogger

More information

Air conditioning, electrical testing

Air conditioning, electrical testing just a test. Air conditioning, electrical testing 01-253 Wire and component test using VAG1598 A test box Special tools and equipment VAG 1598 A test box and VAG 1598/11 adapter cable and VAG 1598/12 VAG1526

More information

026-1704 Rev 6 06-APR-10. MultiFlex I/O Board Installation and Operation Manual

026-1704 Rev 6 06-APR-10. MultiFlex I/O Board Installation and Operation Manual 026-704 Rev 6 06-APR-0 MultiFlex I/O Board Installation and Operation Manual 3240 Town Point Drive NW Suite 00 Kennesaw, GA 3044, USA Phone: 770-425-2724 Fax: 770-425-939 ALL RIGHTS RESERVED. The information

More information

JNIOR. Overview. Get Connected. Get Results. JNIOR Model 310. JNIOR Model 312. JNIOR Model 314. JNIOR Model 410

JNIOR. Overview. Get Connected. Get Results. JNIOR Model 310. JNIOR Model 312. JNIOR Model 314. JNIOR Model 410 The INTEG is an Ethernet I/O (digital, analog) device that monitors and controls a small set of process signals. functions as both basic I/O for integration with another application or system AND as a

More information

Aurora UPC ZS Zone Sensors User Guide

Aurora UPC ZS Zone Sensors User Guide Aurora Universal Protocol Converter (UPC) ZS Zone Sensors User Guide Aurora UPC ZS Zone Sensors User Guide IG1581EW 04/14 Table of Contents Using ZS Sensors... 1 ZS Standard Sensor... 2 ZS Plus Sensor...

More information

T7079A,B Solid State Remote Temperature Controllers

T7079A,B Solid State Remote Temperature Controllers T7079A,B Solid State Remote Temperature Controllers FEATURES PRODUCT DATA Switch selection of heat or cool mode. Temperature sensing up to 400 feet. Does not require field calibration. 0K NTC temperature

More information

Automatic Transfer Switch FT-10 Network Control Communications Module (CCM-T) Kit 541 0811

Automatic Transfer Switch FT-10 Network Control Communications Module (CCM-T) Kit 541 0811 Instruction Sheet 1-2003 Automatic Transfer Switch FT-10 Network Control Communications Module (CCM-T) Kit 541 0811 PURPOSE OF KIT A CCM-T is used to monitor and control an automatic transfer switch. The

More information

543-0032-00, 943-0032-00. User s Manual

543-0032-00, 943-0032-00. User s Manual 543-0032-00, 943-0032-00 User s Manual 1 Comfort Alert Diagnostics Faster Service And Improved Accuracy The Comfort Alert diagnostics module is a breakthrough innovation for troubleshooting heat pump and

More information

USER MANUAL WARNING! CONTENTS MODEL 1 SPECIFICATIONS READ ALL INSTRUCTIONS BEFORE PROCEEDING. Non-Programmable Single Stage Heat/Cool Thermostat

USER MANUAL WARNING! CONTENTS MODEL 1 SPECIFICATIONS READ ALL INSTRUCTIONS BEFORE PROCEEDING. Non-Programmable Single Stage Heat/Cool Thermostat Builder MODEL 1010 Series Non-Programmable Single Stage Heat/Cool Thermostat USER MANUAL Compatible with low voltage single stage gas, oil or electric heating or cooling systems, including single stage

More information

Overview. Alarm console supports simultaneous viewing of both live and recorded video when alarm events are selected

Overview. Alarm console supports simultaneous viewing of both live and recorded video when alarm events are selected Niagara Security Overview Niagara Security by Tridium, is an open, web-based security management solution that allows you to manage and monitor your facility anytime, anywhere. Built on Tridium s Niagara

More information

PD 100A. Printing data system

PD 100A. Printing data system PD 100A Printing data system Operating instructions ENGLISH IMPORTANT: Read these instructions carefully before installing and using the device; do not forget following all additional information. Keep

More information

NortechCommander Software Operating Manual MAN-00004 R6

NortechCommander Software Operating Manual MAN-00004 R6 NortechCommander Software Operating Manual MAN-00004 R6 If the equipment described herein bears the symbol, the said equipment complies with the applicable European Union Directive and Standards mentioned

More information

Electronics Ltd. Presenting. Power, Intelligence... with a sense of feeling

Electronics Ltd. Presenting. Power, Intelligence... with a sense of feeling Electronics Ltd Presenting Power, Intelligence... with a sense of feeling By Appointment to Her Majesty The Queen Supplier of Fire Detection Equipment Kentec Electronics Ltd. Dartford Plug in slots K772

More information

Manual & Technical Documentation V1.1

Manual & Technical Documentation V1.1 Manual & Technical Documentation V1.1 tado Smart Thermostat tado Extension Kit ENGLISH Content Product Packages Compatibility Intelligence & Security Functions Smart Thermostat Usage Menu Structure Special

More information

AGRI-ALERT 128 TOUCH AGRI-ALERT 800EZE ALARM SYSTEMS

AGRI-ALERT 128 TOUCH AGRI-ALERT 800EZE ALARM SYSTEMS AGRI-ALERT 128 TOUCH AGRI-ALERT 800EZE ALARM SYSTEMS AGRI-ALERT ALARM SYSTEMS Peace of Mind Agri-Alert is a complete alarm system for monitoring temperature, power, feed and watering systems, burglary,

More information

MAKING MODERN LIVING POSSIBLE. AK-SC255 On-Site Installation Guide DANFOSS ELECTRONIC CONTROLS & SENSORS

MAKING MODERN LIVING POSSIBLE. AK-SC255 On-Site Installation Guide DANFOSS ELECTRONIC CONTROLS & SENSORS MAKING MODERN LIVING POSSIBLE AK-SC255 On-Site Installation Guide DANFOSS ELECTRONIC CONTROLS & SENSORS How to Use This Guide Read this Guide completely as you install and start up your new AK-SC 255 controller.

More information

01-3 0000-00 6810-20 AIR CONDITIONING SYSTEM 1. FFH SPECIFICATION AIR CONDITIONING SYSTEM RODIUS 2004.09

01-3 0000-00 6810-20 AIR CONDITIONING SYSTEM 1. FFH SPECIFICATION AIR CONDITIONING SYSTEM RODIUS 2004.09 0000-00 01-3 6810-20 1. FFH SPECIFICATION 01-4 0000-00 2. SYSTEM LAYOUT AND COMPONENTS 0000-00 01-5 01-6 0000-00 3. FFH GENERAL INFORMATION The system is to increase the coolant temperature quickly by

More information

Programmable Thermostat MODEL 3312026.XXX With Dehumidify 3312024.XXX With Out Dehumidify

Programmable Thermostat MODEL 3312026.XXX With Dehumidify 3312024.XXX With Out Dehumidify Comfort Control Center 2 Thermostat Operating Instructions Programmable Thermostat MODEL 3312026.XXX With Dehumidify 3312024.XXX With Out Dehumidify TABLE OF CONTENTS About your new thermostat Features...2

More information

026-1002 Rev 3 9-28-99 8OWUD6LWH8VHU V*XLGH

026-1002 Rev 3 9-28-99 8OWUD6LWH8VHU V*XLGH 026-1002 Rev 3 9-28-99 8OWUD6LWH8VHU V*XLGH Computer Process Controls, Inc. 1640 Airport Road Suite #104 Kennesaw, GA 31044 Phone (770) 425-2724 Fax (770) 425-9319 ALL RIGHTS RESERVED The information

More information

* DISCLAIMER: Contents. How to Use This Guide: COMMERCIAL INSTALL GUIDE 2

* DISCLAIMER: Contents. How to Use This Guide: COMMERCIAL INSTALL GUIDE 2 COMMERCIAL INSTALL GUIDE 2 Contents How to Use This Guide: The first section of this guide is designed to assist you with the installation of your DECK Monitoring hardware. The revenue grade meter and

More information

Operations and Programming Manual. ERC/EC-1000 Environmental Control. Supermarket Refrigeration

Operations and Programming Manual. ERC/EC-1000 Environmental Control. Supermarket Refrigeration Supermarket Refrigeration Operations and Programming Manual ERC/EC-1000 Environmental Control REFRIGERATION AND AIR CONDITIONING Literature No. RS.8B.J1.22 Code No. 084R9900 Release: Version 5.30/7.30

More information

ENGLISH INSTRUCTION & INSTALLATION MANUAL DUCTLESS MINI SPLIT AIR CONDITIONING SYSTEMS

ENGLISH INSTRUCTION & INSTALLATION MANUAL DUCTLESS MINI SPLIT AIR CONDITIONING SYSTEMS ENGLISH INSTRUCTION & INSTALLATION MANUAL DUCTLESS MINI SPLIT AIR CONDITIONING SYSTEMS Céliera Corporation. All rights reserved. Unauthorized duplication, reproduction prohibited. CONTENTS SAFETY PRECAUTIONS...

More information

Master Time Clock MTC-200 MTC-400 MTC-600. Users Manual

Master Time Clock MTC-200 MTC-400 MTC-600. Users Manual Master Time Clock MTC-200 MTC-400 MTC-600 Users Manual Toll Free (888)713-0373 Phone (972)987-4408 FAX (877)720-9291 www.midwest-time.com sales@midwest-time.com TABLE OF CONTENTS TOPIC PAGE GENERAL DESCRIPTION

More information

Section 16935 TELEPHONE AUTOMATIC DIALER SYSTEM

Section 16935 TELEPHONE AUTOMATIC DIALER SYSTEM Section TELEPHONE AUTOMATIC DIALER SYSTEM PART 1 GENERAL 1.01 SYSTEM DESCRIPTION A. Design Requirements: 1. Electronic monitoring system shall interface plant alarms to public telephone system or cellular

More information

R22. K Control. Indoor Unit. Nomenclature. Compatibility PL H 3 G K H B. Unit style Heat Pump Horse Power

R22. K Control. Indoor Unit. Nomenclature. Compatibility PL H 3 G K H B. Unit style Heat Pump Horse Power R22. K Control. Indoor Unit. Nomenclature. PL H 3 G K H B Compatibility Unit style Heat Pump Horse Power Control Boost Heaters R22. K Control. Outdoor Unit. Nomenclature. PU H 3 Y K A Compatibility Outdoor

More information

Wireless Indoor/ Outdoor Thermometer

Wireless Indoor/ Outdoor Thermometer Wireless Indoor/ Outdoor Thermometer Owner s Manual Please read before using this equipment. ˆ Contents FCC Information... 3 FCC Declaration of Conformity... 5 Preparation... 5 Installing Batteries...

More information

FX07 Field Controller

FX07 Field Controller Product Bulletin FX07 Field Controller Issue Date March 25, 2008 FX07 Field Controller The FX07 is a high performance field controller designed specifically for commercial Heating, Ventilating, Air Conditioning,

More information

Auto Dialer. Manual E-921APQ E-921GPQ

Auto Dialer. Manual E-921APQ E-921GPQ Troubleshooting: Auto dialer will not arm/disarm Auto dialer will not dial out Unit doesn t respond to a call-back Difficulty in activating room monitor by telephone remote control Make sure that you have

More information

Vision Engravers and Routers PRE-Installation Guide. 2015 Vision Engraving & Routing Systems

Vision Engravers and Routers PRE-Installation Guide. 2015 Vision Engraving & Routing Systems Vision Engravers and Routers PRE-Installation Guide Revised: 8/19/2015 Vision Engravers and Routers PRE-Installation Guide All rights reserved. No parts of this work may be reproduced in any form or by

More information

Short Range Wireless Switch System Handheld 8 Installation and Operations Guide

Short Range Wireless Switch System Handheld 8 Installation and Operations Guide Phone: (866) 701-1146 Fax: (425) 216-7558 www.remotecontroltech.com Short Range Wireless Switch System Handheld 8 Installation and Operations Guide Introduction... 2 Before Installation... 2 Receiver Installation...

More information

026-1400 Rev 2 12-APR-10. Facility Status Display (FSD) Installation and Operation Manual

026-1400 Rev 2 12-APR-10. Facility Status Display (FSD) Installation and Operation Manual 026-1400 Rev 2 12-APR-10 Facility Status Display (FSD) Installation and Operation Manual 3240 Town Point Drive NW Suite 100 Kennesaw, GA 30144, USA Phone: 770-425-2724 Fax: 770-425-9319 ALL RIGHTS RESERVED.

More information

HEAT HEAT COOL HEAT PUMP COOL

HEAT HEAT COOL HEAT PUMP COOL OWNER S MANUAL RESIDENTIAL THERMOSTAT P/N P374-1800 HEAT COOL HEAT PUMP Su AUTO 0I20: Pm 74 COOL HEAT 27 7-DAY MABLE DIGITAL THERMOSTAT 3 Configurable Outputs Accepts Optional Humidity Module: Control

More information

T7560A,B,C Digital Wall Module

T7560A,B,C Digital Wall Module T7560A,B,C Digital Wall Module HONEYWELL EXCEL 5000 OPEN SYSTEM BEFORE INSTALLATION All wiring must comply with local electrical codes and ordinances or as specified on installation wiring diagrams. Digital

More information

ABB i-bus KNX Fan Coil Controller FC/S 1.1

ABB i-bus KNX Fan Coil Controller FC/S 1.1 Product manual ABB i-bus KNX Fan Coil Controller FC/S 1.1 Intelligent Installation Systems Contents Page 1 Introduction... 2 2 Device technology... 3 3 Application and planning 3.1 Heating, ventilation

More information

2.0 Installation 1. Remove the cover using a small flat blade screwdriver. Figure 2: Cover Removal

2.0 Installation 1. Remove the cover using a small flat blade screwdriver. Figure 2: Cover Removal O N DS160/DS161 Installation Guide High Performance Request-to-Exit Sensors 1.0 Description The DS160/161 is a passive-infrared (PIR) detector designed for Request to Exit (REX) interior applications.

More information

Part Number 129777-01 Revision A, January 1996. 3500 Monitoring System Rack Configuration and Utilities Guide

Part Number 129777-01 Revision A, January 1996. 3500 Monitoring System Rack Configuration and Utilities Guide Part Number 129777-01 Revision A, January 1996 3500 Monitoring System Rack Configuration and Utilities Guide Copyright 1995 Bently Nevada Corporation All Rights Reserved. No part of this publication may

More information

Troubleshooting and Diagnostics

Troubleshooting and Diagnostics Troubleshooting and Diagnostics The troubleshooting and diagnostics guide provides instructions to assist in tracking down the source of many basic controller installation problems. If there is a problem

More information

Firmware version: 1.10 Issue: 7 AUTODIALER GD30.2. Instruction Manual

Firmware version: 1.10 Issue: 7 AUTODIALER GD30.2. Instruction Manual Firmware version: 1.10 Issue: 7 AUTODIALER GD30.2 Instruction Manual Firmware version: 2.0.1 Issue: 0.6 Version of the GPRS transmitters configurator: 1.3.6.3 Date of issue: 07.03.2012 TABLE OF CONTENTS

More information

Advantium 2 Plus Alarm

Advantium 2 Plus Alarm ADI 9510-B Advantium 2 Plus Alarm INSTALLATION AND OPERATING INSTRUCTIONS Carefully Read These Instructions Before Operating Carefully Read These Controls Corporation of America 1501 Harpers Road Virginia

More information

Please read this owner s Manual carefully before operating the unit. - Cooling - Heating - Dehumidifying - Fan

Please read this owner s Manual carefully before operating the unit. - Cooling - Heating - Dehumidifying - Fan Please read this owner s Manual carefully before operating the unit. - Cooling - Heating - Dehumidifying - Fan TABLE OF CONTENTS INTRODUCTION 2 IMPORTANT SAFEGUARDS...2 PACKAGE CONTAINS..2 NAMES OF PARTS.3

More information

for DNE-K07 Reference and Installation Manual

for DNE-K07 Reference and Installation Manual for DNE-K07 Reference and Installation Manual TABLE OF CONTENTS INTRODUCTION...2 Specifications... 3 Navigation... 3 INSTALLATION...4 Viewing Angle... 4 Keypad Cover Clearance... 4 Mounting the Metal

More information

Model 53603. Owner s Manual. Español - P. 19 Français - P. 39

Model 53603. Owner s Manual. Español - P. 19 Français - P. 39 Model 53603 Owner s Manual Español - P. 19 Français - P. 39 Table of Contents I. Introduction............................ 1 Sample Watering Plan.......................... 1 II. Installation...........................

More information

WEB log. Device connection plans

WEB log. Device connection plans WEB log LIGHT+ 20 BASIC 100 PRO unlimited Device connection plans Version 20160425* Copyright Copyright for this manual remains with the manufacturer. No part of this manual may be reproduced or edited,

More information

A99B Series Temperature Sensors

A99B Series Temperature Sensors FANs 125, 121, 930, 930.5 Product/Technical Bulletin A99 Issue Date 0615 A99B Series Temperature s The A99B Series Temperature s are passive PTC (Positive Temperature Coefficient) sensors. The A99B sensors

More information

Home Theater PC Chassis

Home Theater PC Chassis Home Theater PC Chassis Model: HTPC 180 BA & SA Color: Black & Silver Quick Installation Guide (U.S. & Canada Only) Version 1.0 DISCLAIMER No warranty or representation, either expressed or implied, is

More information

T 3 Series VAV Diffusers Analog Diffuser Steel Square Panel Horizontal Pattern Model: T 3 SQ

T 3 Series VAV Diffusers Analog Diffuser Steel Square Panel Horizontal Pattern Model: T 3 SQ TSQ--0 7-7-07 T Series VAV Diffusers Analog Diffuser Steel Square Panel Horizontal Pattern Model: T SQ Model Configuration T SQ- Heating / Cooling Border Type (Lay-In) Full Face Nominal Round Duct Size

More information

TAC I/NETTM MR-VAV-AX. Application Specific MicroRegulator TM

TAC I/NETTM MR-VAV-AX. Application Specific MicroRegulator TM TAC I/NETTM TM TAC s TM has an extensive range ofpre-engineered VAV control sequences, which combined with a fully integrated actuator and airflow transducer, makes it a low Total Installed Cost solution

More information

Digital and Analog I/O

Digital and Analog I/O 70072-0127-07 TECHNICAL NOTE 02/2007 Digital and Analog I/O This document discusses the application and configuration of digital and analog inputs/outputs (I/O). Details are for both onboard I/O and external

More information

KACO-monitoring. onlinecomponents.com. Integrated monitoring available. Monitor up to 32 inverters per prolog. Reliable and accurate data

KACO-monitoring. onlinecomponents.com. Integrated monitoring available. Monitor up to 32 inverters per prolog. Reliable and accurate data KACO-monitoring watchdog insight prolog Integrated monitoring available Monitor up to 32 inverters per prolog Reliable and accurate data Email alarms to maximize uptime Historical, current and production

More information

NC State University Design and Construction Guidelines Division 26 Fire Alarm Systems

NC State University Design and Construction Guidelines Division 26 Fire Alarm Systems NC State University Design and Construction Guidelines Division 26 Fire Alarm Systems 1.0 Purpose A. The following guideline provides the minimum standards and requirements for fire alarm systems. 2.0

More information

LiteKeeper 4 & 8 Programming Guide and User Manual

LiteKeeper 4 & 8 Programming Guide and User Manual LiteKeeper 4 & 8 Programming Guide and User Manual Table of Contents Safety Instructions... 3 Chapter 1: Introduction... 4 p1 How It Works... 4 What are relays?... 4 What are inputs?... 4 How do I program

More information

for Windows Media Center User's Guide

for Windows Media Center User's Guide for Windows Media Center User's Guide Table of Contents Introduction System Requirements Installation Running HAI Home Control Using HAI Home Control Product Support Introduction Thank you for purchasing

More information

User Manual. Air-conditioner Controller SB-DN-HVAC (MAC01.331) www.hdlautomation.com

User Manual. Air-conditioner Controller SB-DN-HVAC (MAC01.331) www.hdlautomation.com Air-conditioner Controller SB-DN-HVAC (MAC01.331) www.hdlautomation.com Document updates: Version Data Description V1.0 2015.05.25 Finish new document HVAC Controller User Manual INDEX 1. Overview...1

More information

sip Sanyo Modbus Guide Technical Specification Pinouts, Cable Connections & Wiring Issue 2: February 2009 Synapsys Solutions Ltd, all rights reserved

sip Sanyo Modbus Guide Technical Specification Pinouts, Cable Connections & Wiring Issue 2: February 2009 Synapsys Solutions Ltd, all rights reserved Sanyo Section : Section : Section : Section : Section : sip Modbus Guide Configuration Modbus Table Technical Specification Pinouts, Cable Connections & Wiring Alarm Fault Codes Issue : February 009 Section

More information

IN-OUT Thermometer with Cable Free Sensor and Clock

IN-OUT Thermometer with Cable Free Sensor and Clock IN-OUT Thermometer with Cable Free Sensor and Clock MODEL: RAR232 USER'S MANUAL INTRODUCTION Congratulations on your purchase of the RAR232 In-Out Thermometer with 433MHz cable free sensor and calendar

More information

A+ Guide to Managing and Maintaining Your PC, 7e. Chapter 1 Introducing Hardware

A+ Guide to Managing and Maintaining Your PC, 7e. Chapter 1 Introducing Hardware A+ Guide to Managing and Maintaining Your PC, 7e Chapter 1 Introducing Hardware Objectives Learn that a computer requires both hardware and software to work Learn about the many different hardware components

More information