Measurement of the Harmonic Impedance of the Aggregated Distribution Network

Size: px
Start display at page:

Download "Measurement of the Harmonic Impedance of the Aggregated Distribution Network"

Transcription

1 Measurement of the Harmonic Impedance of the Aggregated Distribution Network V. Ćuk, F. Ni, W. Jin, J.F.G. Cobben A. Jongepier H.E. van den Brom, G. Rietveld, M. Ačanski Eindhoven University of Technology Enduris B.V. VSL Eindhoven, the Netherlands Goes, the Netherlands Delft, the Netherlands Abstract--This paper presents a method for measurement of the harmonic impedance of an aggregated distribution network using multiple Phasor Measurement Units (PMUs) with the additional capability of synchronized voltage and current spectrum measurement. The perturbations of the harmonic voltages which originate from the higher voltage levels are distinguished based on the measurements from multiple busbars, and used as the input for the calculation. Results of a test case using measurements from a 5 kv network are given to illustrate the method. Index Terms Power Quality, Power system harmonics, Impedance measurement, Harmonic impedance, Load modeling, Phasor measurement units. T I. INTRODUCTION o perform studies of harmonic distortion propagation in an electricity grid, the impedance information of the network is needed as well as information on the emission of disturbing loads. For network elements such as transformers, lines, cables and capacitor banks, harmonic impedance models are considered to be mature knowledge and are standardly used as such for system studies. The two main challenges in the modeling of harmonic impedances are: modeling of the aggregated upstream network (e.g. the high voltage network when analyzing the distribution system) and modeling of the aggregated loads which may have a known or unknown composition. In an early CIGRE report [1], three approaches to the modeling of aggregated loads are proposed: - Representing them only with equivalent resistance, where the value is obtained from the fundamental active power value (measured or assumed) and a scaling factor to take skin-effect into account, - Complementary to the equivalent resistance, using a parallel inductive reactance, with the value determined based on the short-circuit impedance of assumed motor loads in service, This work is carried out as part of a joint European research project called Measurement Tools for Smart Grid Stability and Supply Quality Management. The project is part of the European Metrology Research Program (EMRP), which is jointly funded by the EMRP participating countries within EURAMET and the European Union. Additional funding is received from the Dutch Ministry of Economic Affairs. - Using a generalized impedance equivalent, as shown in Figure 1, with values of components derived from field measurements. In the third method, the values of the equivalent resistance R, the series harmonic reactance X sh and the shunt harmonic reactance X ph are calculated using: = (1) =.73 h (2) h = 6.7 (3).74 where U is the nominal voltage of the observed system, P 1 is the measured fundamental active power, h is the harmonic order and Q 1 is the measured fundamental reactive Figure 1.Generalized harmonic load equivalent, as proposed in [1], with the values of components based on field measurements. An overview of alternative aggregated equivalents is given in [2], where it was discussed that most of the equivalents used differ only in coefficients, namely the way motor loads are taken into account. There are two reasons to assume that the generality of these equivalents is limited. The first one is that the network composition (share of overhead lines and cables) and load composition (types of loads and consumption profiles) differ per country and per region. The second reason is that the loads are evolving in time, in particular the share of power electronic loads is considerably larger than in the time these equivalents were developed and measurements were made, which was the end of 197s and early 198s /16/$ IEEE 834

2 The reliability of these equivalents is difficult to assess, as the simulation results are also dependent on the way the emission is modeled. One approach to analyze the uncertainty of the models is to use new measurement results, which can also include the dependency to the measured power levels. This paper proposes a method to measure the equivalent harmonic impedance of the loads from synchronously measured spectra of voltages and currents on consecutive busbars in the network. In Chapter II, the general approaches to load impedance measurement are introduced, and the differences to measurement of the upstream network impedance. In Chapter III the proposed method is introduced and in Chapter IV the test case, measurements from a 5 kv network in the Netherlands, is introduced. Measurement results and discussion are presented in Chapter V, followed by the conclusions in Chapter VI. II. MEASUREMENT OF HARMONIC IMPEDANCE Measurement of harmonic impedances is addressed in a number of papers, with a summary given in [3]. The basic approach of all of the mentioned methods is: = (4) where Z h is the harmonic impedance of the order h, ΔU h is change of the h th harmonic voltage and ΔI h is the change of the h th harmonic current. The reason to use changes of the spectrum, instead of simply measurements of a single moment in time, is to reduce the uncertainty which comes from the fact that distortion is caused by multiple sources operating at the same time. In particular, if the loads downstream from the measurement point are causing most of the voltage distortion (or its change), we are able to calculate the supply impedance. In this case the background distortion originating in the upstream part of the system is a source of measurement error. Conversely, if we want to calculate the equivalent impedance of the loads, the upstream distortion should is the dominant source of information, and the emission of loads downstream become a source of error. Many of the practical applications utilize injection of harmonic or inter-harmonic perturbations into the network, and then calculate the harmonic impedances based on the differences of voltage and current spectra before and during the perturbation [4] [7], whereas other methods make use of load changes, transients or data selection for this purpose [8] [11]. With the exception of the work in [7], the other papers are addressing the measurement of the supply side impedance, with the challenge of reducing the impact of supply side distortion. For the measurement of load side impedance, which is the topic of this paper, one of the main challenges is to reduce the impact of load side emissions, i.e. using the changes of distortion which originate from the upstream network. In [7], this problem was dealt with by using the current and voltage waveforms during a deliberately induced switching transients (capacitor bank switching), upstream from the observed distribution system feeders. The results showed good matching with the excepted (calculated) results. The aim of this paper is to propose a method which can effectively identify upstream network induced changes of distortion, e.g. due to load variations, and calculate the equivalent harmonic impedance of loads based on measured spectra rather than waveforms. III. PROPOSED METHODOLOGY As discussed in the previous chapter, one of the main challenges in determining the load side impedance is the identification of the changes in the voltage and current spectra which are caused by variations on the supply side (large load or generation changes in the upstream network). For this reason, in this paper it is proposed to use synchronized voltage spectrum measurements e.g. using synchronized measurement data from PMUs with additional harmonic spectrum functionality on several consecutive busbars, to identify time moments when harmonic voltages are changing by (almost) equal amounts on all of them. If there are time moments when: (5) where the underscore designates the complex value, and ΔU hi is the change of the harmonic voltage on busbar i, we can conclude that the change is caused by the upstream system. These changes will differ from each other due to the measurement uncertainty and simultaneous changes caused by the loads and generators downstream from each of the busbars. The threshold for considering the changes close enough is debatable; in this paper the approach is to calculate the vectorial difference between each two busbar voltage changes and compare the magnitude of this difference to a threshold set e.g. to the class of voltage transformers used.5 %. After the perturbations originating from the upstream network are identified, the simultaneous changes of the voltage and current harmonicsof the harmonic current flowing downstream are calculated, and the impedance is calculated based on the identified simultaneous changes of voltage harmonics and current harmonics using (4). IV. TEST CASE To test the methodology, a 5 kv network from Enduris in the Netherlands is used, where PMUs are installed in five consecutive substations. The PMUs have the capability of measuring the voltage and current spectrum at time intervals of 1 s, next to the normal PMU functionality of measuring the fundament voltage and current phasors [12], [13]. The schematic of the test network is shown in Figure 2. The currents of aggregated loads flowing through the 5 kv/1 kv transformers, are not measured directly, but can be calculated based on the currents of the incoming and outgoing 5 kv feeders. In some of the feeders the current measurement is placed on the other end of the feeder. This results in an 835

3 extra uncertainty of the transformers current calculation, additional to the uncertainty caused by the current transformers and PMUs. Current transformers on the feeder Zierikzee Oosterland (according to Figure 2) are of Class 1 and the current transformer in the feeder Oosterland Tholen is of Class.1. Voltage transformers at substation Oosterland are of Class.5 and voltage transformers at substation Zierikzee and Tholen are of class 1. The influence of frequency on the uncertainty of instrument transformers is not characterized, but for the observed harmonic orders (up to the 17 th ) it is expected that there is no influence of the first parallel resonance [14]. the relevant changes of harmonic voltages (caused by the upstream network) are selected based on the following criteria: - changes of harmonic voltages at the observed substation and two neighboring substations do not differ by more than.5 % in magnitude, - voltage changes lower than.1% of the nominal voltage are not taken into account for sensitivity reasons, - current changes lower than.1 A are not taken into account, also due to the sensitivity;.1 A also roughly corresponds to.1 % of the nominal fundamental current. Figure 2. Schematic of the 5 kv test network. Measurement of the aggregated load impedances are calculated for substation Oosterland i.e. for the loads connected to the 5 kv/1 kv transformer, including the transformer and outgoing 1 kv feeders (in this case cables). Unlike the IEC compliant power quality devices, which use data windows of 1/12 cycles of the fundamental frequency and starting at zero crossings for spectral measurements, the PMUs in this study use 1 ms data windows triggered by 1-pulse-per-second GPS-based clock signals. So the length of the measurement is not dependent on the fundamental frequency and its start is not synchronized to the signals zero crossing. This means that the angles of spectral components are not relative to any reference electrical grid signal typically the fundamental voltages. Additionally, the angles of harmonic components do not include any form of averaging over the 1 s time intervals the results of each 1 s measurement is in fact the result of a single 1 ms data window within the 1 s [15]. This makes the angle information unreliable for time intervals which include (significant) changes over the 1 ms data windows. For magnitudes, time aggregation is used, which reduces the effect of variations on results (averaging of 1 ms resutls). For this reason, in this paper only the magnitude of the impedance is calculated. The analysis of the real and imaginary components of the impedance will be the objective of future work, which could further process the measured phase angles to determine reliable changes of the angle within the 1 s time intervals. The test case uses the measurements over one week in total about 6, measurement points. From these points, V. RESULTS AND DISCUSSION Over the observed time period, only five out of the 25 measured harmonic orders had voltage and current changes which satisfy all of the mentioned criteria the 5 th, 7 th, 11 th, 13 th and 17 th (which also have the highest levels for harmonic voltages in general). From the one week time period, up to 4 changes between 1 s time intervals could be used for impedance calculation in the light of the given criteria. The measured impedance values for the 5 th, 11 th and 13 th order against the active and reactive power values are given in Figure 3 - Figure 8. These orders are chosen as they have the most measured points. It can be observed that the impedance values are highest at the 11 th harmonic order, and have the highest number of selected observation intervals (due to the highest signal to noise ratio). If the impedance of the upstream system shows such behavior, it would indicate the first parallel resonance at the 11 th order. However, the effect is different for the load impedances. As the upstream system act closer to an ideal voltage source than an ideal current source, this impedance does not lead to very high harmonic voltages. In fact, it reduces the secondary emission of loads). The change of the 11 th harmonic voltage in notable, as shown in Figure 9 for. The maximal value is around.5 % of the nominal fundamental voltage. Impedance 5 th order [Ω] Active power [W] Figure 3. Dependency between the 5 th harmonic impedance and active 836

4 Impedance 5 th order [Ω] Impedance 13 th order [Ω] Reactive power [var] Figure 4. Dependency between the 5 th harmonic impedance and reactive Active power [W] Figure 7. Dependency between the 13 th harmonic impedance and active Impedance 11 th order [Ω] Impedance 13 th order [Ω] Active power [W] Figure 5. Dependency between the 11 th harmonic impedance and active Reactive power [var] Figure 8. Dependency between the 13 th harmonic impedance and reactive Impedance 11 th order [Ω] th harmonic voltage [V] Reactive power [var] Figure 6. Dependency between the 11 th harmonic impedance and reactive Time [s] x 1 5 Figure 9. Magnitudes of the 11 th harmonic voltage in during the one week measurement. 837

5 For the 11 th and 13 th orders, a connection between the power levels and impedance magnitude can be observed, with some points which seem to be different from the trend. A fitted relation would however not be sufficient to define a load model, until the resistive and reactive components of the impedance are calculated. As a more general description of the aggregated impedance, in Figure 1 the mean value, 5 % and 95 % nonexceeded values of impedances are shown. Harmonic Ipedance [Ω] % Average 95 % Harmonic order [-] Figure 1. Mean values and 5 % and 95 % non-exceeded values of harmonic impedances for all analyzed orders. The validation of results is not possible at this stage, until the real and imaginary parts of the impedance are derived. Additionally, the connections between powers and impedance values are to be re-examined with the results, so the existing ones cannot be used as a reference with the measured power in general conditions. To validate the results, the following steps are proposed: - Derive the real and imaginary parts of the impedance, - Derive the connection between power and resistance/reactance for a known loading condition e.g. near zero loading (transformer losses), or at a location with a capacitor bank or shunt reactor connected. For further research and improvements of this analysis, the following aspects can be considered: - To better define the uncertainty of the calculation, the instrument transformers should be characterized over the frequency range of interest (which is limited by the magnitudes of variations in operation, in this case up to the 17 th harmonic order), - To further improve the calculation accuracy it would be beneficial to measure the transformer currents directly, preferably on the low-voltage side; alternatively, if the transformer currents are is to be calculated based on ingoing and outgoing feeders, it is beneficial to measure all currents in the observed substation (due to the capacitive leakage between the substations, especially for cable networks), - To determine the resistive and reactive components of the harmonic impedances, the phase-angle aggregation needs to be resolved (a single 1 ms data window representing the whole 1 s time interval). One possibility is to use the 2 ms fundamental voltage/current measurements of the PMU to filter out the time intervals in which the measurements are not (relatively) stable over the 1 s time intervals, - Once the resistive and reactive components are determined, the connection between the results and the measured active and reactive powers can be further analyzed, e.g. to evaluate the performance of the generalized model given in (1) (3). VI. CONCLUSIONS This paper presents a method for the measurement of harmonic impedances of aggregated loads based on synchronized spectrum measurements using the (almost) equal perturbations of harmonic voltages of nearby substations to identify the changes originating from the upstream network. The method is demonstrated on a test case of a 5 kv network from Enduris in the Netherlands, with results for the magnitudes of the harmonic impedances presented. The magnitude of the aggregated 1 kv network impedance at this location showed close values for the 5 th, 7 th, 13 th and 17 th harmonic. At the 11 th harmonic a peak is observed, indicating that the transformer, cables and loads have a parallel resonance at this frequency observed without the upstream network. The limitations of the method and the setup used in the test case are discussed and propositions for improvements and further analysis are given: characterizing the instrument transformers over the analyzed frequency range, adding additional current measurement points and determining the parameters of the aggregated load model based on more advanced phase angle analysis. VII. ACKNOWLEDGMENT The authors would like to thank Joeri van Seters and Marco Visser from Enduris B.V., the Netherlands, for providing the measurement data to perform this study. VIII. REFERENCES [1] CIGRE Working Group 36-5, Harmonics, characteristic parameters, methods of study, estimates of existing values in the network, [2] P. F. Ribeiro, Investigations of harmonic penetration in transmission systems, PhD thesis, The Victoria University of Manchester, UK, [3] A. Robert, Guide for assessing the network harmonic impedance, in Proc. 14th International Conference and Exhibition on Electricity Distribution (CIRED), [4] M. Ciobotaru, R. Teodorescu, and F. Blaabjerg, On-line grid impedance estimation based on harmonic injection for grid-connected PV inverter, in Proc. 27 IEEE International Symposium on Industrial Electronics, pp [5] M. Sumner, B. Palethorpe, D. W. P. Thomas, P. Zanchetta, and M. C. Di Piazza, A technique for power supply harmonic impedance estimation using a controlled voltage disturbance, IEEE Trans. Power Electronics., vol. 17, no. 2, pp , Mar. 22. [6] A. de Oliveira, J. C. de Oliveira, J. W. Resende, and M. S. Miskulin, Practical approaches for AC system harmonic impedance measurements, IEEE Trans. Power Delivery., vol. 6, no. 4, pp , [7] A. S. Morched and P. Kundur, Identification and modelling of load characteristics at high frequencies, IEEE Trans. Power Delivery., vol. 2, no. 838

6 1, pp , [8] R. Langella and A. Testa, A New Method for Statistical Assessment of the System Harmonic Impedance and of the Background Voltage Distortion, in Proc. 26 International Conference on Probabilistic Methods Applied to Power Systems, pp [9] F. Karimzadeh, S. Esmaeili, and S. H. Hosseinian, A Novel Method for Noninvasive Estimation of Utility Harmonic Impedance Based on Complex Independent Component Analysis, IEEE Trans. Power Delivery., vol. 3, no. 4, pp , Aug [1] D. Borkowski, A. Wetula, and A. Bien, New method for noninvasive measurement of utility harmonic impedance, in Proc. 212 IEEE Power and Energy Society General Meeting, 212, pp [11] J. Hui, W. Freitas, J. C. M. Vieira, H. Yang, and Y. Liu, Utility Harmonic Impedance Measurement Based on Data Selection, IEEE Trans. Power Delivery, vol. 27, no. 4, pp , Oct [12] G. Rietveld, A. Jongepier, J. van Seters, M. Visser, P. Liu, M. Acanski, D. Hoogenboom, and H. van den Brom, Application of PMUs for monitoring a 5 kv distribution grid, in Proc. CIRED 215. [13] B. Dickerson, Applications of synchronised power quality measurements, [Online]. Available: asurements.pdf [14] J. Arrillaga and N. R. Watson, Power system harmonics, 2nd ed. John Wiley & Sons, 23. [15] ArbiterSystems, Model 1133A Power Sentinel Functional Description., [Online]. Available: 839

The effect of inrush transients on PV inverter s grid impedance measurement based on inter-harmonic injection

The effect of inrush transients on PV inverter s grid impedance measurement based on inter-harmonic injection European Association for the Development of Renewable Energies, Environment and Power Quality (EA4EPQ) International Conference on Renewable Energies and Power Quality (ICREPQ 10) Granada (Spain), 23rd

More information

INTRODUCTION TO HARMONIC ASSESSMENT IN POWER SYSTEMS

INTRODUCTION TO HARMONIC ASSESSMENT IN POWER SYSTEMS INTRODUCTION TO HARMONIC ASSESSMENT IN POWER SYSTEMS LIST OF CONTENT 1. INTRODUCTION... 1 2. HARMONIC VOLTAGE ASSESSMENT REQUIREMENT IN THE UK... 2 3. THE ASSESSMENT... 2 3.1. SYSTEM MODELLING...3 3.2.

More information

The design and performance of Static Var Compensators for particle accelerators

The design and performance of Static Var Compensators for particle accelerators CERN-ACC-2015-0104 Karsten.Kahle@cern.ch The design and performance of Static Var Compensators for particle accelerators Karsten Kahle, Francisco R. Blánquez, Charles-Mathieu Genton CERN, Geneva, Switzerland,

More information

EMTP STUDIES PERFORMED TO INSERT LONG AC CABLES IN THE FRENCH GRID

EMTP STUDIES PERFORMED TO INSERT LONG AC CABLES IN THE FRENCH GRID Tension (kv) Impedance (Ohms) EMTP STUDIES PERFORMED TO INSERT LONG AC CABLES IN THE FRENCH GRID frequency (Hz) Simon DESCHANVRES Yannick VERNAY RTE, CNER, Substations Department t (ms) EMTP-RV Users Group

More information

MINISTERIE VAN ECONOMISCHE ZAKEN GENERAL COST COMPARISON BETWEEN UNDERGROUND CABLES AND O.H. LINE SYSTEMS FOR H.V. TRANSMISSION

MINISTERIE VAN ECONOMISCHE ZAKEN GENERAL COST COMPARISON BETWEEN UNDERGROUND CABLES AND O.H. LINE SYSTEMS FOR H.V. TRANSMISSION MINISTERIE VAN ECONOMISCHE ZAKEN GENERAL COST COMPARISON BETWEEN UNDERGROUND CABLES AND O.H. LINE SYSTEMS FOR H.V. TRANSMISSION REPORT ON NETWORK RELIABILITY ASPECTS OF THE CHOICE LINE VERSUS CABLE FOR

More information

HARMONIC DISTORTION IN THE ELECTRIC SUPPLY SYSTEM

HARMONIC DISTORTION IN THE ELECTRIC SUPPLY SYSTEM Technical Note No.3 March 2000 HARMONIC DISTORTION IN THE ELECTRIC SUPPLY SYSTEM This Technical Note discusses harmonic distortion, its causes and adverse effects, what levels are unacceptable and how

More information

7. Reactive energy compensation

7. Reactive energy compensation 593 7. Reactive energy compensation 594 7. REACTIVE ENERGY COMPENSATION Reactive energy compensation is an important element for reducing the electricity bill and improving the quality of the electrical

More information

General Validation Test Program for Wind Power Plants Connected to the Hydro-Québec Transmission System

General Validation Test Program for Wind Power Plants Connected to the Hydro-Québec Transmission System General Validation Test Program for Wind Power Plants Connected to the Hydro-Québec Transmission System Direction Planification des actifs et expertise de transport February 2011 TABLE OF CONTENTS 1. CONDUCTING

More information

Laboratory and field measurements of the power factor and the harmonic emission from energy-efficient lamps

Laboratory and field measurements of the power factor and the harmonic emission from energy-efficient lamps Laboratory and field measurements of the power factor and the harmonic emission from energy-efficient lamps Sarah K. Rönnberg (1), Math H.J. Bollen (1,2), Mats Wahlberg (1,3) (1) Luleå University of Technology,

More information

Distributed Generation and Power Quality Case Study

Distributed Generation and Power Quality Case Study 16 Distributed Generation and Power Quality Case Study Vu Van Thong and Johan Driesen C16.1 DISTRIBUTION NETWORK A segment of an existing Belgian medium-voltage distribution system is used to study the

More information

LIMITING SHORT-CIRCUIT CURRENTS IN MEDIUM-VOLTAGE APPLICATIONS

LIMITING SHORT-CIRCUIT CURRENTS IN MEDIUM-VOLTAGE APPLICATIONS LIMITING SHORT-CIRCUIT CURRENTS IN MEDIUM-VOLTAGE APPLICATIONS Terence Hazel Senior Member IEEE Schneider Electric 38050 Grenoble France Abstract The power requirements for large industrial sites is increasing.

More information

Synchronized real time data: a new foundation for the Electric Power Grid.

Synchronized real time data: a new foundation for the Electric Power Grid. Synchronized real time data: a new foundation for the Electric Power Grid. Pat Kennedy and Chuck Wells Conjecture: Synchronized GPS based data time stamping, high data sampling rates, phasor measurements

More information

Introduction. Harmonics and IEEE 519 Page 1 of 19

Introduction. Harmonics and IEEE 519 Page 1 of 19 Introduction In an ideal power system, the voltage supplied to customer equipment, and the resulting load current are perfect sine waves. In practice, however, conditions are never ideal, so these waveforms

More information

POWER SYSTEM HARMONICS. A Reference Guide to Causes, Effects and Corrective Measures AN ALLEN-BRADLEY SERIES OF ISSUES AND ANSWERS

POWER SYSTEM HARMONICS. A Reference Guide to Causes, Effects and Corrective Measures AN ALLEN-BRADLEY SERIES OF ISSUES AND ANSWERS A Reference Guide to Causes, Effects and Corrective Measures AN ALLEN-BRADLEY SERIES OF ISSUES AND ANSWERS By: Robert G. Ellis, P. Eng., Rockwell Automation Medium Voltage Business CONTENTS INTRODUCTION...

More information

Understanding Power Factor and How it Affects Your Electric Bill. Presented by Scott Peele PE

Understanding Power Factor and How it Affects Your Electric Bill. Presented by Scott Peele PE Understanding Power Factor and How it Affects Your Electric Bill Presented by Scott Peele PE Understanding Power Factor Definitions kva, kvar, kw, Apparent Power vs. True Power Calculations Measurements

More information

Typical Data Requirements Data Required for Power System Evaluation

Typical Data Requirements Data Required for Power System Evaluation Summary 66 Carey Road Queensbury, NY 12804 Ph: (518) 792-4776 Fax: (518) 792-5767 www.nepsi.com sales@nepsi.com Harmonic Filter & Power Capacitor Bank Application Studies This document describes NEPSI

More information

Variable Frequency Drives - a Comparison of VSI versus LCI Systems

Variable Frequency Drives - a Comparison of VSI versus LCI Systems Variable Frequency Drives - a Comparison of VSI versus LCI Systems Introduction TMEIC is a leader in the innovative design and manufacture of large ac variable f requency drive systems. TMEIC has been

More information

Sensitivity Analysis of Waveform Distortion Assessment for Wind Plants

Sensitivity Analysis of Waveform Distortion Assessment for Wind Plants Sensitivity Analysis of Waveform Distortion Assessment for Wind Plants Mariana B. Pereira 1, Einar V. Larsen 2, Sebastian A. Achilles 3 Energy Consulting General Electric 1 Av. Magalhães de Castro 4800,

More information

Three phase circuits

Three phase circuits Three phase circuits THREE PHASE CIRCUITS THREE-PHASE ADVANTAGES 1. The horsepower rating of three-phase motors and the kva rating of three-phase transformers are 150% greater than single-phase motors

More information

High Intensify Interleaved Converter for Renewable Energy Resources

High Intensify Interleaved Converter for Renewable Energy Resources High Intensify Interleaved Converter for Renewable Energy Resources K. Muthiah 1, S.Manivel 2, Gowthaman.N 3 1 PG Scholar, Jay Shriram Group of Institutions,Tirupur 2 Assistant Professor, Jay Shriram Group

More information

Harmonics and Noise in Photovoltaic (PV) Inverter and the Mitigation Strategies

Harmonics and Noise in Photovoltaic (PV) Inverter and the Mitigation Strategies Soonwook Hong, Ph. D. Michael Zuercher Martinson Harmonics and Noise in Photovoltaic (PV) Inverter and the Mitigation Strategies 1. Introduction PV inverters use semiconductor devices to transform the

More information

2. A conductor of length 2m moves at 4m/s at 30 to a uniform magnetic field of 0.1T. Which one of the following gives the e.m.f. generated?

2. A conductor of length 2m moves at 4m/s at 30 to a uniform magnetic field of 0.1T. Which one of the following gives the e.m.f. generated? Extra Questions - 2 1. A straight length of wire moves through a uniform magnetic field. The e.m.f. produced across the ends of the wire will be maximum if it moves: a) along the lines of magnetic flux

More information

PHASOR MEASUREMENT UNIT (PMU) AKANKSHA PACHPINDE

PHASOR MEASUREMENT UNIT (PMU) AKANKSHA PACHPINDE PHASOR MEASUREMENT UNIT (PMU) AKANKSHA PACHPINDE INTRODUCTION OUTLINE Conventional control centers Introduction to Synchrophasors A generic PMU Applications of PMU Role of GPS Cost profile of PMU with

More information

Power System review W I L L I A M V. T O R R E A P R I L 1 0, 2 0 1 3

Power System review W I L L I A M V. T O R R E A P R I L 1 0, 2 0 1 3 Power System review W I L L I A M V. T O R R E A P R I L 1 0, 2 0 1 3 Basics of Power systems Network topology Transmission and Distribution Load and Resource Balance Economic Dispatch Steady State System

More information

Voltage Stability Improvement using Static Var Compensator in Power Systems

Voltage Stability Improvement using Static Var Compensator in Power Systems Leonardo Journal of Sciences ISSN 1583-0233 Issue 14, January-June 2009 p. 167-172 Voltage Stability Improvement using Static Var Compensator in Power Systems Department of Electrical/Computer Engineering,

More information

Line Reactors and AC Drives

Line Reactors and AC Drives Line Reactors and AC Drives Rockwell Automation Mequon Wisconsin Quite often, line and load reactors are installed on AC drives without a solid understanding of why or what the positive and negative consequences

More information

Power Quality Centre VOLTAGE FLUCTUATIONS IN THE ELECTRIC SUPPLY SYSTEM. Technical Note No. 7 August 2003

Power Quality Centre VOLTAGE FLUCTUATIONS IN THE ELECTRIC SUPPLY SYSTEM. Technical Note No. 7 August 2003 Technical Note No. 7 August 2003 Power Quality Centre VOLTAGE FLUCTUATIONS IN THE ELECTRIC SUPPLY SYSTEM This Technical Note discusses voltage fluctuations, their causes and adverse effects, what levels

More information

RLC Resonant Circuits

RLC Resonant Circuits C esonant Circuits Andrew McHutchon April 20, 203 Capacitors and Inductors There is a lot of inconsistency when it comes to dealing with reactances of complex components. The format followed in this document

More information

Integration of Distributed Generation in the Power System. IEEE Press Series on Power Engineering

Integration of Distributed Generation in the Power System. IEEE Press Series on Power Engineering Brochure More information from http://www.researchandmarkets.com/reports/2171489/ Integration of Distributed Generation in the Power System. IEEE Press Series on Power Engineering Description: A forward

More information

UNDERSTANDING AND CONTROLLING COMMON-MODE EMISSIONS IN HIGH-POWER ELECTRONICS

UNDERSTANDING AND CONTROLLING COMMON-MODE EMISSIONS IN HIGH-POWER ELECTRONICS Page 1 UNDERSTANDING AND CONTROLLING COMMON-MODE EMISSIONS IN HIGH-POWER ELECTRONICS By Henry Ott Consultants Livingston, NJ 07039 (973) 992-1793 www.hottconsultants.com hott@ieee.org Page 2 THE BASIC

More information

Test & Data Management Software

Test & Data Management Software Test & Data Management Software TDMS protective relays energy meters transducers power quality CT-VT-PT transformers ground grid circuit breakers batteries surge arresters The Integrated Testing Solution

More information

EMC STANDARDS STANDARDS AND STANDARD MAKING BODIES. International. International Electrotechnical Commission (IEC) http://www.iec.

EMC STANDARDS STANDARDS AND STANDARD MAKING BODIES. International. International Electrotechnical Commission (IEC) http://www.iec. EMC STANDARDS The EMC standards that a particular electronic product must meet depend on the product application (commercial or military) and the country in which the product is to be used. These EMC regulatory

More information

Interpreting IEEE Std 519 and Meeting its Harmonic Limits in VFD Applications

Interpreting IEEE Std 519 and Meeting its Harmonic Limits in VFD Applications Interpreting IEEE Std 519 and Meeting its Harmonic Limits in VFD Applications Copyright Material IEEE Paper No. PCIC-2003-15 Tony Hoevenaars, P. Eng. Kurt LeDoux, P.E. Matt Colosino Member IEEE Member,

More information

Distributed Flexible AC Transmission System (D FACTS) Jamie Weber. weber@powerworld.com, 217 384 6330 ext. 13

Distributed Flexible AC Transmission System (D FACTS) Jamie Weber. weber@powerworld.com, 217 384 6330 ext. 13 Distributed Flexible AC Transmission System (D FACTS) Jamie Weber weber@powerworld.com, 217 384 6330 ext. 13 Slide Preparation: Kate Rogers Davis kate@powerworld.com, 217 384 6330, Ext 14 2001 South First

More information

Laboratory 4: Feedback and Compensation

Laboratory 4: Feedback and Compensation Laboratory 4: Feedback and Compensation To be performed during Week 9 (Oct. 20-24) and Week 10 (Oct. 27-31) Due Week 11 (Nov. 3-7) 1 Pre-Lab This Pre-Lab should be completed before attending your regular

More information

Hybrid Power System with A Two-Input Power Converter

Hybrid Power System with A Two-Input Power Converter Hybrid Power System with A Two-Input Power Converter Y. L. Juan and H. Y. Yang Department of Electrical Engineering National Changhua University of Education Jin-De Campus, Address: No.1, Jin-De Road,

More information

Nuclear Power Plant Electrical Power Supply System Requirements

Nuclear Power Plant Electrical Power Supply System Requirements 1 Nuclear Power Plant Electrical Power Supply System Requirements Željko Jurković, Krško NPP, zeljko.jurkovic@nek.si Abstract Various regulations and standards require from electrical power system of the

More information

SHORT CIRCUIT CURRENT CALCULATION AND PREVENTION IN HIGH VOLTAGE POWER NETS

SHORT CIRCUIT CURRENT CALCULATION AND PREVENTION IN HIGH VOLTAGE POWER NETS Bachelor's Thesis Electrical Engineering June 2014 SHORT CIRCUIT CURRENT CALCULATION AND PREVENTION IN HIGH VOLTAGE POWER NETS MD FARUQUL ALAM SALMAN SAIF HAMID ALI School of Engineering Blekinge Tekniska

More information

Reactive Power and Importance to Bulk Power System OAK RIDGE NATIONAL LABORATORY ENGINEERING SCIENCE & TECHNOLOGY DIVISION

Reactive Power and Importance to Bulk Power System OAK RIDGE NATIONAL LABORATORY ENGINEERING SCIENCE & TECHNOLOGY DIVISION Reactive Power and Importance to Bulk Power System OAK RIDGE NATIONAL LABORATORY ENGINEERING SCIENCE & TECHNOLOGY DIVISION Outline What is Reactive Power and where does it come from? Why is it important?

More information

TDMS Test & Data Management Software

TDMS Test & Data Management Software Test & Data Management Software TDMS protective relays energy meters transducers power quality CT-VT-PT transformers ground grid circuit breakers batteries surge arresters The Integrated Testing Solution

More information

Performance Enhancement of Wound Rotor Induction Motor by VSI with Dynamic Capacitor Controlled Rotor Circuit

Performance Enhancement of Wound Rotor Induction Motor by VSI with Dynamic Capacitor Controlled Rotor Circuit Performance Enhancement of Wound Rotor Induction Motor by VSI with Dynamic Capacitor Controlled Rotor Circuit K.Ranjith kumar kumar, Dr.S.Palaniswami K.Priyadharsini, Senior Senior Lecturer Lecturer Professor

More information

A COMPARISON ON PERFORMANCE OF TCSC/SSSC FOR A RADIAL SYSTEM

A COMPARISON ON PERFORMANCE OF TCSC/SSSC FOR A RADIAL SYSTEM IMPACT: International Journal of Research in Engineering & Technology (IMPACT: IJRET) ISSN(E): 31-8843; ISSN(P): 347-4599 Vol. 3, Issue 9, Sep 015, 7-18 Impact Journals A COMPARISON ON PERFORMANCE OF TCSC/SSSC

More information

Solar Power Plant Design and Interconnection

Solar Power Plant Design and Interconnection Solar Power Plant Design and Interconnection Wind & Solar Super Session July 27, 2011 E.H. Camm, S.E. Williams S&C Electric Company Outline Introduction Utility-scale PV power plant Grounding Reactive

More information

MICRO HYDRO POWER PLANT WITH INDUCTION GENERATOR SUPPLYING SINGLE PHASE LOADS

MICRO HYDRO POWER PLANT WITH INDUCTION GENERATOR SUPPLYING SINGLE PHASE LOADS MICRO HYDRO POWER PLANT WITH INDUCTION GENERATOR SUPPLYING SINGLE PHASE LOADS C.P. ION 1 C. MARINESCU 1 Abstract: This paper presents a new method to supply single-phase loads using a three-phase induction

More information

Power Quality Standards for Electric Service

Power Quality Standards for Electric Service Power Quality Standards for Electric Service Effective June 1, 2008 A transition period will exist from June 1 through December 31, 2008 in which installations may be approved and connected as long as

More information

Simulation and Design of Printed Circuit Boards Utilizing Novel Embedded Capacitance Material

Simulation and Design of Printed Circuit Boards Utilizing Novel Embedded Capacitance Material Simulation and Design of Printed Circuit Boards Utilizing Novel Embedded Capacitance Material Yu Xuequan, Yan Hang, Zhang Gezi, Wang Haisan Huawei Technologies Co., Ltd Lujiazui Subpark, Pudong Software

More information

Pierre Archambault, PEng. VP Engineering Power Survey International Inc. 16 September 2009

Pierre Archambault, PEng. VP Engineering Power Survey International Inc. 16 September 2009 PotashCorp New Brunswick Division Picadilly Potash Project ETAP SIMULATION Prepared by: Carlos Reinel Senior Engineer R&D Department Power Survey International Approved by: Pierre Archambault, PEng. VP

More information

Analysis of the Effect of Tap Changing Transformer on Performance of SVC

Analysis of the Effect of Tap Changing Transformer on Performance of SVC Analysis of the Effect of Tap Changing Transformer on Performance of SVC Dipesh A. Patel 1, Nirav P. Patani 2, Prabhat Kumar 3 1 Senior Lecturer, Electrical Engineering Department, M.L.I.D.S. Bhandu, Gujarat.

More information

SURVEY OF HARMONIC DISTORTION IN LV AND MV NETWORKS: RESULTS AND CORRECTIVE STRATEGIES

SURVEY OF HARMONIC DISTORTION IN LV AND MV NETWORKS: RESULTS AND CORRECTIVE STRATEGIES SURVEY OF HARMONIC DISTORTION IN LV AND MV NETWORKS: RESULTS AND CORRECTIVE STRATEGIES E Bompard*, E Carpaneto*, R Napoli*, P Ribaldone**, C Vercellino** * Dipartimento di Ingegneria Elettrica Industriale,

More information

EXTENDING THE LIFE OF POWER FACTOR CAPACITORS

EXTENDING THE LIFE OF POWER FACTOR CAPACITORS by John Houdek, President, Allied Industrial Marketing, Inc., and Cesar Chavez, Engineering Manager, ARTECHE / Inelap Abstract: The addition of power factor improvement capacitors to individual motors

More information

MOBILE SYSTEM FOR DIAGNOSIS OF HIGH VOLTAGE CABLES (132KV/220KV) VLF-200 HVCD

MOBILE SYSTEM FOR DIAGNOSIS OF HIGH VOLTAGE CABLES (132KV/220KV) VLF-200 HVCD MOBILE SYSTEM FOR DIAGNOSIS OF HIGH VOLTAGE CABLES (132KV/220KV) VLF-200 HVCD VERY LOW FREQUENCY (VLF) - PARTIAL DISCHARGES AND TANGENT DELTA HV/EHV POWER CABLES DIAGNOSTIC AND ON-SITE FIELD TESTING WITH

More information

A Fuzzy Based Solution for Improving Power Quality in Electric Railway Networks

A Fuzzy Based Solution for Improving Power Quality in Electric Railway Networks A Fuzzy Based Solution for Improving Power Quality in Electric Railway Networks Mohammad Ali Sandidzadeh School of Railway Engineering, Iran University of Science & Technology, Tehran, Iran Tel: 98-21-7749-1030

More information

UNDERSTANDING POWER FACTOR AND INPUT CURRENT HARMONICS IN SWITCHED MODE POWER SUPPLIES

UNDERSTANDING POWER FACTOR AND INPUT CURRENT HARMONICS IN SWITCHED MODE POWER SUPPLIES UNDERSTANDING POWER FACTOR AND INPUT CURRENT HARMONICS IN SWITCHED MODE POWER SUPPLIES WHITE PAPER: TW0062 36 Newburgh Road Hackettstown, NJ 07840 Feb 2009 Alan Gobbi About the Author Alan Gobbi Alan Gobbi

More information

Power Quality Issues in Railway Electrification

Power Quality Issues in Railway Electrification International Journal of Computer Sciences and Engineering Open Access Survey Paper Volume-4, Issue-1 E-ISSN: 2347-2693 Power Quality Issues in Railway Electrification Rajshree S Thorat 1*, M. M. Deshpande

More information

CONDUCTED EMISSION MEASUREMENT OF A CELL PHONE PROCESSOR MODULE

CONDUCTED EMISSION MEASUREMENT OF A CELL PHONE PROCESSOR MODULE Progress In Electromagnetics esearch C, Vol. 42, 191 203, 2013 CONDUCTED EMISSION MEASUEMENT OF A CELL PHONE POCESSO MODULE Fayu Wan *, Junxiang Ge, and Mengxiang Qu Nanjing University of Information Science

More information

Wide Area Monitoring Current Continental Europe TSOs Applications Overview

Wide Area Monitoring Current Continental Europe TSOs Applications Overview Wide Area Monitoring Current Continental Europe TSOs Applications Overview Version 5 System Protection & Dynamics Working Group 20th September 2015 1. Content 1. Content... 2 2. Introduction... 3 3. Main

More information

SIMULATING HYBRID ENERGY GRIDS IN SMART CITIES FOCUS ON ELECTRIC ENERGY SYSTEMS

SIMULATING HYBRID ENERGY GRIDS IN SMART CITIES FOCUS ON ELECTRIC ENERGY SYSTEMS Sawsan Henein AIT Austrian Institute of Technology Electric Energy Systems Research Group SIMULATING HYBRID ENERGY GRIDS IN SMART CITIES FOCUS ON ELECTRIC ENERGY SYSTEMS Sustainable Places 2015 Savona,

More information

Data center power dynamics within the settings of regional power grid

Data center power dynamics within the settings of regional power grid Data center power dynamics within the settings of regional power grid Gulnara Zhabelova 1, Alireza Yavarian 1, Valeriy Vyatkin 1,2 1 Department of Computer Science, Electrical and Space Engineering Lulea

More information

Grid Interconnection of Renewable Energy Sources Using Modified One-Cycle Control Technique

Grid Interconnection of Renewable Energy Sources Using Modified One-Cycle Control Technique Grid Interconnection of Renewable Energy Sources Using Modified One-Cycle Control Technique NKV.Sai Sunil 1, K.Vinod Kumar 2 PG Student, GITAM University, Visakhapatnam, India. Asst.Professor, Department

More information

A Low Cost Power Quality and Energy Savings Laboratory for Undergraduate Education and Research

A Low Cost Power Quality and Energy Savings Laboratory for Undergraduate Education and Research Session #3133 A Low Cost Power Quality and Energy Savings Laboratory for Undergraduate Education and Research Abdullatif Bagegni, Vance Poteat Merrimack College Abstract This paper describes the design

More information

Hybrid processing of SCADA and synchronized phasor measurements for tracking network state

Hybrid processing of SCADA and synchronized phasor measurements for tracking network state IEEE PES General Meeting, Denver, USA, July 2015 1 Hybrid processing of SCADA and synchronized phasor measurements for tracking network state Boris Alcaide-Moreno Claudio Fuerte-Esquivel Universidad Michoacana

More information

How To Understand And Understand The Theory Of Electricity

How To Understand And Understand The Theory Of Electricity DIRECT CURRENT AND ALTERNATING CURRENT SYSTEMS N. Rajkumar, Research Fellow, Energy Systems Group, City University Northampton Square, London EC1V 0HB, UK Keywords: Electrical energy, direct current, alternating

More information

Keywords: Electric circuits, passive circuits, active circuits, voltage source inverter, reactive power theory, active filters.

Keywords: Electric circuits, passive circuits, active circuits, voltage source inverter, reactive power theory, active filters. ACTIVE NETWORKS Davor Vujatovic Engineering Manager, EDF Energy Services Ltd., UK Keywords: Electric circuits, passive circuits, active circuits, voltage source inverter, reactive power theory, active

More information

Electromagnetic Compatibility (EMC) Low-Frequency Standards. Standards on Low-Frequency Emission: IEC 61000-3-2

Electromagnetic Compatibility (EMC) Low-Frequency Standards. Standards on Low-Frequency Emission: IEC 61000-3-2 Electromagnetic Compatibility (EMC) Low-Frequency Standards Summary IEC 61000-3-2: Limits for harmonic current emissions (equipment input current 16A per phase) IEC 61000-3-4: Limitation of emission of

More information

IMPROVED NETWORK PARAMETER ERROR IDENTIFICATION USING MULTIPLE MEASUREMENT SCANS

IMPROVED NETWORK PARAMETER ERROR IDENTIFICATION USING MULTIPLE MEASUREMENT SCANS IMPROVED NETWORK PARAMETER ERROR IDENTIFICATION USING MULTIPLE MEASUREMENT SCANS Liuxi Zhang and Ali Abur Department of Electrical and Computer Engineering Northeastern University Boston, MA, USA lzhang@ece.neu.edu

More information

TESTS OF 1 MHZ SIGNAL SOURCE FOR SPECTRUM ANALYZER CALIBRATION 7/8/08 Sam Wetterlin

TESTS OF 1 MHZ SIGNAL SOURCE FOR SPECTRUM ANALYZER CALIBRATION 7/8/08 Sam Wetterlin TESTS OF 1 MHZ SIGNAL SOURCE FOR SPECTRUM ANALYZER CALIBRATION 7/8/08 Sam Wetterlin (Updated 7/19/08 to delete sine wave output) I constructed the 1 MHz square wave generator shown in the Appendix. This

More information

ANN Based Fault Classifier and Fault Locator for Double Circuit Transmission Line

ANN Based Fault Classifier and Fault Locator for Double Circuit Transmission Line International Journal of Computer Sciences and Engineering Open Access Research Paper Volume-4, Special Issue-2, April 2016 E-ISSN: 2347-2693 ANN Based Fault Classifier and Fault Locator for Double Circuit

More information

Using Simple Calibration Load Models to Improve Accuracy of Vector Network Analyzer Measurements

Using Simple Calibration Load Models to Improve Accuracy of Vector Network Analyzer Measurements Using Simple Calibration Load Models to Improve Accuracy of Vector Network Analyzer Measurements Nick M. Ridler 1 and Nils Nazoa 2 1 National Physical Laboratory, UK (www.npl.co.uk) 2 LA Techniques Ltd,

More information

SYNCHRONOUS MACHINES

SYNCHRONOUS MACHINES SYNCHRONOUS MACHINES The geometry of a synchronous machine is quite similar to that of the induction machine. The stator core and windings of a three-phase synchronous machine are practically identical

More information

HARMONICS AND HOW THEY RELATE TO POWER FACTOR. W. Mack Grady The University of Texas at Austin Austin, Texas 78712

HARMONICS AND HOW THEY RELATE TO POWER FACTOR. W. Mack Grady The University of Texas at Austin Austin, Texas 78712 Abstract HARMONICS AND HOW THEY RELATE TO POWER FACTOR W. Mack Grady The University of Texas at Austin Austin, Texas 787 Robert J. Gilleskie San Diego Gas & Electric San Diego, California 93 We are all

More information

Understanding Power Impedance Supply for Optimum Decoupling

Understanding Power Impedance Supply for Optimum Decoupling Introduction Noise in power supplies is not only caused by the power supply itself, but also the load s interaction with the power supply (i.e. dynamic loads, switching, etc.). To lower load induced noise,

More information

Engineering innovation

Engineering innovation Eaton's Electrical Engineering Services & Systems Solutions Focus Seamless Solutions for Reliable, Efficient and Safe Power Systems Engineering innovation Progressive solutions for today s power systems

More information

High Voltage Power Supplies for Analytical Instrumentation

High Voltage Power Supplies for Analytical Instrumentation ABSTRACT High Voltage Power Supplies for Analytical Instrumentation by Cliff Scapellati Power supply requirements for Analytical Instrumentation are as varied as the applications themselves. Power supply

More information

Chapter 3 AUTOMATIC VOLTAGE CONTROL

Chapter 3 AUTOMATIC VOLTAGE CONTROL Chapter 3 AUTOMATIC VOLTAGE CONTROL . INTRODUCTION TO EXCITATION SYSTEM The basic function of an excitation system is to provide necessary direct current to the field winding of the synchronous generator.

More information

System Protection Schemes in Eastern Denmark

System Protection Schemes in Eastern Denmark System Protection Schemes in Eastern Denmark Joana Rasmussen COWI A/S, Energy Department System Protection Schemes in Eastern Denmark 1.Advanced system protection schemes are investigated and perspectives

More information

Pre-Compliance Test Method for Radiated Emissions of Automotive Components Using Scattering Parameter Transfer Functions

Pre-Compliance Test Method for Radiated Emissions of Automotive Components Using Scattering Parameter Transfer Functions PreCompliance Test Method for Radiated Emissions of Automotive Components Using Scattering Parameter Transfer Functions D. Schneider 1*, S. Tenbohlen 1, W. Köhler 1 1 Institute of Power Transmission and

More information

Requirements for Offshore Grid Connections. in the. Grid of TenneT TSO GmbH

Requirements for Offshore Grid Connections. in the. Grid of TenneT TSO GmbH Requirements for Offshore Grid Connections in the Grid of TenneT TSO GmbH Bernecker Straße 70, 95448 Bayreuth Updated: 21 December 2012 1/10 Requirements for Offshore Grid Connections in the Grid of TenneT

More information

Transformers. Special transformers Reactors products

Transformers. Special transformers Reactors products Transformers Special transformers Reactors products Reactors Custom designed, custom built ABB Oy Transformers has extensive experience and numerous references from different reactor applications, having

More information

Wind Turbine Operation in Power Systems and Grid Connection Requirements

Wind Turbine Operation in Power Systems and Grid Connection Requirements Wind Turbine Operation in Power Systems and Grid Connection Requirements A. Sudrià 1, M. Chindris 2, A. Sumper 1, G. Gross 1 and F. Ferrer 1 1 Centre for Technological Innovation in Static Converters and

More information

Simulation and Analysis of Parameter Identification Techniques for Induction Motor Drive

Simulation and Analysis of Parameter Identification Techniques for Induction Motor Drive International Journal of Electronic and Electrical Engineering. ISSN 0974-2174 Volume 7, Number 10 (2014), pp. 1027-1035 International Research Publication House http://www.irphouse.com Simulation and

More information

Impedance Matching and Matching Networks. Valentin Todorow, December, 2009

Impedance Matching and Matching Networks. Valentin Todorow, December, 2009 Impedance Matching and Matching Networks Valentin Todorow, December, 2009 RF for Plasma Processing - Definition of RF What is RF? The IEEE Standard Dictionary of Electrical and Electronics Terms defines

More information

Session 10: General Overview of Interconnection Standards & Grid Codes for High Penetration PV October 21, 2015 Santiago, Chile

Session 10: General Overview of Interconnection Standards & Grid Codes for High Penetration PV October 21, 2015 Santiago, Chile Session 10: General Overview of Interconnection Standards & Grid Codes for High Penetration PV October 21, 2015 Santiago, Chile Michael Coddington National Renewable Energy Laboratory Golden, Colorado,

More information

Triplen Harmonics Mitigation 3 Phase Four-Wire Electrical Distribution System Using Wye- Zig-Zag Transformers

Triplen Harmonics Mitigation 3 Phase Four-Wire Electrical Distribution System Using Wye- Zig-Zag Transformers Journal Journal of of Emerging Emerging Trends Trends in in Engineering Engineering and and Applied Applied Sciences Sciences (JETEAS) (JETEAS) 1 1 (1): (1): 72-78 72-78 Scholarlink Research Institute

More information

Implementation of High Step-Up Solar Power Optimizer for DC Micro Grid Application

Implementation of High Step-Up Solar Power Optimizer for DC Micro Grid Application Implementation of High tepup olar Power Optimizer for C Micro Grid Application hihming Chen, KeRen Hu, TsorngJuu Liang, and YiHsun Hsieh Advanced Optoelectronic Technology Center epartment of Electrical

More information

GUIDE FOR TESTING POWER TRANSFORMERS

GUIDE FOR TESTING POWER TRANSFORMERS GUIDE FOR TESTING POWER TRANSFORMERS Routine test 11/11/02 Pagina 1 di 10 INDEX Introduction... 3 1 Dielectric tests Separate-source voltage withstand test... 4 2 Induced voltage test... 5 3 Voltage ratio

More information

2012 San Francisco Colloquium

2012 San Francisco Colloquium 2012 San Francisco Colloquium http : //www.cigre.org HVDC and Power Electronic Systems for Overhead Line and Insulated Cable Applications B4-8 Trans Bay Cable A Breakthrough of VSC Multilevel Converters

More information

New Method for Optimum Design of Pyramidal Horn Antennas

New Method for Optimum Design of Pyramidal Horn Antennas 66 New Method for Optimum Design of Pyramidal Horn Antennas Leandro de Paula Santos Pereira, Marco Antonio Brasil Terada Antenna Group, Electrical Engineering Dept., University of Brasilia - DF terada@unb.br

More information

Radiated Emission and Susceptibility

Radiated Emission and Susceptibility Radiated Emission and Susceptibility Tzong-Lin Wu, Ph.D. EMC Lab Department of Electrical Engineering National Taiwan University Differential-Mode v.s. Common-mode Currents 1 Differential-Mode v.s. Common-mode

More information

Calculation of Voltage Sag Indices for Distribution Networks

Calculation of Voltage Sag Indices for Distribution Networks Calculation of Voltage Sag Indices for Distribution Networks Juan A. Martinez-Velasco, Member, IEEE, Jacinto Martin-Arnedo, Nonmember Abstract This paper is presenting the main results of a work aimed

More information

Impact of electric vehicles on the IEEE 34 node distribution infrastructure

Impact of electric vehicles on the IEEE 34 node distribution infrastructure International Journal of Smart Grid and Clean Energy Impact of electric vehicles on the IEEE 34 node distribution infrastructure Zeming Jiang *, Laith Shalalfeh, Mohammed J. Beshir a Department of Electrical

More information

Efficient Interconnect Design with Novel Repeater Insertion for Low Power Applications

Efficient Interconnect Design with Novel Repeater Insertion for Low Power Applications Efficient Interconnect Design with Novel Repeater Insertion for Low Power Applications TRIPTI SHARMA, K. G. SHARMA, B. P. SINGH, NEHA ARORA Electronics & Communication Department MITS Deemed University,

More information

Linear Parameter Measurement (LPM)

Linear Parameter Measurement (LPM) (LPM) Module of the R&D SYSTEM FEATURES Identifies linear transducer model Measures suspension creep LS-fitting in impedance LS-fitting in displacement (optional) Single-step measurement with laser sensor

More information

An Isolated Multiport DC-DC Converter for Different Renewable Energy Sources

An Isolated Multiport DC-DC Converter for Different Renewable Energy Sources An Isolated Multiport DC-DC Converter for Different Renewable Energy Sources K.Pradeepkumar 1, J.Sudesh Johny 2 PG Student [Power Electronics & Drives], Dept. of EEE, Sri Ramakrishna Engineering College,

More information

The Quest for Energy Efficiency. A White Paper from the experts in Business-Critical Continuity

The Quest for Energy Efficiency. A White Paper from the experts in Business-Critical Continuity The Quest for Energy Efficiency A White Paper from the experts in Business-Critical Continuity Abstract One of the most widely discussed issues throughout the world today is the rapidly increasing price

More information

EDEXCEL NATIONAL CERTIFICATE/DIPLOMA UNIT 5 - ELECTRICAL AND ELECTRONIC PRINCIPLES NQF LEVEL 3 OUTCOME 4 - ALTERNATING CURRENT

EDEXCEL NATIONAL CERTIFICATE/DIPLOMA UNIT 5 - ELECTRICAL AND ELECTRONIC PRINCIPLES NQF LEVEL 3 OUTCOME 4 - ALTERNATING CURRENT EDEXCEL NATIONAL CERTIFICATE/DIPLOMA UNIT 5 - ELECTRICAL AND ELECTRONIC PRINCIPLES NQF LEVEL 3 OUTCOME 4 - ALTERNATING CURRENT 4 Understand single-phase alternating current (ac) theory Single phase AC

More information

Low Frequency AC Transmission System

Low Frequency AC Transmission System , pp. 315-326 http://dx.doi.org/10.14257/ijsip.2015.8.5.32 Low Frequency AC Transmission System G. Sirisha Kumari 1 and K.Veerendranath 2 1 M. Tech student in EEE Department 2 Asst. Professor in EEE Department

More information

Programmable-Gain Transimpedance Amplifiers Maximize Dynamic Range in Spectroscopy Systems

Programmable-Gain Transimpedance Amplifiers Maximize Dynamic Range in Spectroscopy Systems Programmable-Gain Transimpedance Amplifiers Maximize Dynamic Range in Spectroscopy Systems PHOTODIODE VOLTAGE SHORT-CIRCUIT PHOTODIODE SHORT- CIRCUIT VOLTAGE 0mV DARK ark By Luis Orozco Introduction Precision

More information

POWER FACTOR CORRECTION

POWER FACTOR CORRECTION [CATALOGUE PFC-SFC] POWER FACTOR CORRECTION INDUSTRIAL SWITCHGEAR & AUTOMATION SPECIALISTS A component of nhp s green star solution... www.nhp.com.au Power Factor - What does it mean? Where open electricity

More information

Application Note. So You Need to Measure Some Inductors?

Application Note. So You Need to Measure Some Inductors? So You Need to Measure Some nductors? Take a look at the 1910 nductance Analyzer. Although specifically designed for production testing of inductors and coils, in addition to measuring inductance (L),

More information

Power Quality Analysis and Evaluation at Water Pumping Station Supplied by Medium Voltage

Power Quality Analysis and Evaluation at Water Pumping Station Supplied by Medium Voltage Power Quality Analysis and Evaluation at Water Pumping Station Supplied by Medium Voltage Mustafa SEKKELI 1,*, Süleyman EROL 2 1 Sutcu Imam University, Faculty of Engineering, Electrical and Electronics

More information