Digital Controller. (Programmable Type) User's Manual. Cat. No. H088-E1-01A

Size: px
Start display at page:

Download "Digital Controller. (Programmable Type) User's Manual. Cat. No. H088-E1-01A"

Transcription

1 Digital Controller (Programmable Type) User's Manual Cat. No. H088-E1-01A

2 Preface PRECAUTIONS IN USING THE PRODUCT About this manual (1) All rights reserved. No part of this publication may be reproduced, stored in a retrieval system or transmitted, in any form, or by any means, mechanical, electronic, photocopying, recording, or otherwise, without the prior written permission of OMRON. (2) Moreover, because OMRON is constantly striving to improve its high-quality products, the information in this manual is subject to change without notice. (3) Every precaution has been taken in the preparation of this manual. Nevertheless, if you find any errors or omissions, please contact the branch of OMRON or sales office listed at the end of this manual, and inform them of the catalog No. on the front cover. I

3 Conventions Used in This Manual Meanings of Abbreviations Symbol Term How to Read Display Symbols A B C D E F G H I J K L M N O P Q R S T U V W X Y Z Reference mark II

4 How This Manual is Organized Purpose Title Description Learning about the general features of the E5AK-T Setting up Basic E5AK-T operations Applied E5AK-T operations Using a Position-proportional type controller Communications with a host computer Calibration Troubleshooting III

5 PRECAUTIONS ON SAFETY Marks For Ensuring Safe Use and Their Meanings WARNING Incorrect handling may cause death or injury. WARNING Do not touch the terminals while the power is ON. This may cause an electric shock. IV

6 NOTICE V

7 VI

8 Table of Contents Preface Conventions Used in This Manual Precautions on Safety I II V CHAPTER 1 INTRODUCTION This chapter introduces the names of parts on the E5AK-T and their functions. For details on how to use the controller and parameter settings, see Chapter 2 onwards. 1.1 Names of parts Input and Output Program Parameters and Menus About the Communications Function About Calibration CHAPTER 2 PREPARATIONS This chapter describes the operations (e.g. setup, installation and wiring) you should carry out before turning the E5AK-T ON. 2.1 Setup Installation Wiring Terminals CHAPTER 3 BASIC OPERATION This chapter describes actual examples for understanding the basic operation of the E5AK-T. 3.1 Convention Used in this Chapter Setting Input Specifications Setting Output Specifications Setting Alarm Type Setting Patterns Protect Mode Starting and Stopping Operation Adjusting Control Operation CHAPTER 4 APPLIED OPERATION This chapter describes each of the parameters required for making full use of the features of the E5AK-T. Read this chapter while referring to the parameter descriptions in chapter Selecting the Control Method Operating Condition Restrictions Ramp Rise Rate Setup Program Program Operation

9 4.5 Wait Operation Program output Setting Running Conditions How to Use Event Input How to Use the Heater Burnout Alarm LBA How to Use Transfer Output CHAPTER 5 PARAMETERS This chapter describes the parameters of the E5AK-T. Use this chapter as a reference guide. Conventions Used in this Chapter Protect Mode Manual Mode Level 0 Mode Program Mode Level 1 Mode Level 2 Mode Setup Mode Expansion Mode Option Mode Calibration Mode CHAPTER 6 USING THE COMMUNICATIONS FUNCTION This chapter mainly describes communications with a host computer and communications commands. 6.1 Outline of the Communications Function Preparing for Communications Command Structure Commands and Responses How to Read Communications Error Information Program Example CHAPTER 7 CALIBRATION This chapter describes procedures for each calibration operation. Read this chapter only when the controller must be calibrated. 7.1 Parameter Structure Calibrating Thermocouples Calibrating Platinum Resistance Thermometers Calibrating Current Input Calibrating Voltage Input

10 7.6 Checking Indication Accuracy CHAPTER 8 TROUBLESHOOTING This chapter describes how to find out and remedy the cause if the E5AK-T does not function properly. Remedy E5AK-T trouble in the order of the descriptions in this chapter 8.1 Initial Checks How to Use the Error Display How to Use the Error Output Checking Operation Restrictions APPENDIX SPECIFICATIONS A 2 ABOUT CURRENT TRANSFORMER (CT)... A 5 CONTROL BLOCK DIAGRAM A 6 SETTING LIST A 8 MODEL LIST A 12 PARAMETER OPERATIONS LIST A 13 ASCII CODE LIST A 15 INDEX REVISION HISTORY

11 CHAPTER 1 INTRODUCTION CHAPTER11 INTRODUCTION 1 1

12 CHAPTER 1 INTRODUCTION 1.1 Names of parts Main parts Terminals P 2-6 Rear case Front panel This page Front panel Program state indicators No.1 display Bar graph Pattern No. Operation status indicators OUT1 OUT2 SUB1 SUB2 MANU RMT HOLD RST WAIT AT E5AK No.2 display Run/Reset key Display key Down key Up key RUN/RST 1 2

13 1.1 Names of parts About the displays No.1 display No.2 display Pattern No. Program status indicators Operation status indicators Bar graph 1 3

14 CHAPTER 1 INTRODUCTION How to use keys RUN/RST key key key RUN/RST 1 4

15 1.2 Input and Output 1.2 Input and Output Temperature input Voltage input Current input Controller Control output (heat) Control output (cool) Alarm 1 Control output 1 Control output 2 CT input Potentiometer Alarm 2 Auxiliary output 1 Alarm 3 HBA Auxiliary output 2 LBA Event input Time signal 1 Transfer output Time signal 2 Program end Stage output Error 1 Error 2 Input Temperature input/voltage input/current input CT input/potentiometer 1 5

16 CHAPTER 1 INTRODUCTION Event input Output Output assignments 1 6

17 1.2 Input and Output Control Method Standard control Heating and cooling control Position-proportional control Model E5AK-TAA2 AC E5AK-TAA2 AC/DC24 E5AK-TAA2 AC E5AK-TAA2 AC/DC24 E5AK-TPRR2 AC E5AK-TPRR2 AC/DC24 Control Output 1/ Control Output 2 Control output (heat) / Alarm, etc. Control output (heat) / Control output (cool) Open/Close Transfer output 1 7

18 CHAPTER 1 INTRODUCTION 1.3 Program How programs are structured Pattern 7 Pattern 1 Pattern 0 Step 0 Step 1 Step 2 Step 15 opera- Program tion Step operation Wait operation Alarm output Program output 1 8

19 1.4 Parameters and Menus 1.4 Parameters and Menus Parameter types Protect mode Manual mode Level 0 mode Program mode Level 1 mode Level 2 mode Setup mode 1 9

20 CHAPTER 1 INTRODUCTION Expansion mode Option mode Calibration mode Selecting modes 1 second min. Power ON Level 0 mode + 1 second min. Manual mode 1 second min. Program mode + 1 second min. 1 second min. 1 second min. 1 second min. 1 second min. Level 1 mode Level 2 mode Setup mode Expansion mode RUN/RST RUN/RST + 1 second min. 1 second min. Protect mode + 1 second min. RUN/RST + 1 second min. Option mode 1 second min. Calibration mode 1 10

21 1.4 Parameters and Menus RUN/RST Selecting parameters Parameter 1 Parameter 2 Parameter 3 Parameter n Fixing settings 1 11

22 CHAPTER 1 INTRODUCTION 1.5 About the Communications Function RS-232C RS-422 RS

23 1.6 About Calibration 1.6 About Calibration Calibrating inputs Calibrating transfer output Registering calibration data 1 13

24 CHAPTER 1 INTRODUCTION 1 14

25 CHAPTER 2 PREPARATIONS CHAPTER22 PREPARATIONS 2 1

26 CHAPTER 2 PREPARATIONS 2.1 Setup Draw-out Fixing Screw for Front Panel 2 2

27 2.1 Setup Setting up the output unit Before setup Procedure OUT1 OUT2 Bracket 2 3

28 CHAPTER 2 PREPARATIONS Setting up the option unit Before setup Procedure 2 1 Option 2 E53 AKF: Transfer output Option 1 E53 AKB: Event inputs 1/2 E53 AK01: RS 232C E53 AK02: RS 422 E53 AK03: RS 485 Option 3 E53 AKB: Event inputs 3/4 2 4

29 2.2 Installation 2.2 Installation Dimensions Panel cutout Unit (mm) 110 min. 120 min

30 CHAPTER 2 PREPARATIONS Mounting 2 6

31 2.2 Installation Setting up the terminal covers E5AK-T E53-COV

32 CHAPTER 2 PREPARATIONS 2.3 Wiring Terminals Terminal arrangement SOURCE OUT1 OUT2 SUB1 SUB TRSF EV3/ EV1/2 RS232C RS422 RS485 CT PTMR TRSF : Transfer output EV1 to 4 : Event inputs PTMR : Potentiometer SOURCE : 100 to 240 VAC, 50/60 Hz 16VA or 24VAC/DC, 50/60 Hz, 12VA 8W TC Pt I V Precautions when wiring 7.2mm max. 7.2mm max. Wiring Power supply

33 2.3 Wiring Terminals Sensor input Control output Thermocouple Platinum resistance thermometer V Voltage input ma 33 + Current input ma GND GND Relay SSR NPN PNP E53-R E53-S E53-Q E53-Q4 E53-Q to 20mA/0 to 20mA E53-C3 E53-C3D L V to 10V/0 to 5V E53-V34 E53-V35 L +v + L +v + L Model Output Type Output Mode Specifications E53-R Relay Pulse 250 VAC, 5 A E53-S SSR Pulse 75 to 250 VAC, 1 A E53-Q E53-Q3 E53-Q4 E53-C3 E53-C3D E53-V34 E53-V35 Voltage (NPN) Voltage (NPN) Voltage (PNP) 4 to 20 ma 0 to 20 ma 0 to 10 V 0 to 5 V Pulse Pulse Pulse Linear Linear Linear Linear NPN : 12 VDC, 40 ma (with short-circuit protection) NPN : 24 VDC, 20 ma (with short-circuit protection) PNP : 24 VDC, 20 ma (with short-circuit protection) 4 to 20 ma, Permissible load impedance: 600 Ω max., Resolution: Approx to 20 ma, Permissible load impedance: 600 Ω max., Resolution: Approx to 10 VDC, Permissible load impedance: 1 kω min., Resolution: Approx to 5 VDC, Permissible load impedance: 1 kω min., Resolution: Approx Open 5 Close 2 9

34 CHAPTER 2 PREPARATIONS Auxiliary output CT input/ Potentiometer Auxiliary output Auxiliary output CT input CT O 17 W C Potentiometer Ω Ω About Isolation B E A B C F C D 2 10

35 2.3 Wiring Terminals Event input EV1 20 EV EV2 19 EV4 25 COM COM - Event input 1 and 2 Event input 3 and 4 Contact input No-contact input ON: 1 kω max., OFF: 100 kω min. ON: residual voltage 1.5 V max., OFF: leakage current 0.1 ma max. EV1 EV EV3 EV COM 18 - COM 24 - Event input 1 and 2 Event input 3 and 4 Transfer output to 20mA L 29 - Ω Communications 2 11

36 CHAPTER 2 PREPARATIONS 2 12

37 CHAPTER 3 BASIC OPERATION CHAPTER33 BASIC OPERATION 3 1

38 CHAPTER 3 BASIC OPERATION 3.1 Convention Used in this Chapter Basic Operation Flow Power ON Setup Setting input specifications Setting output specifications Setting alarm output Setting patterns Protecting parameters Operation Start Adjustment Stop Power OFF 3 2

39 3.1 Convention Used in this Chapter Setup examples Temperature sensor: K thermocouple Control target AC V OUT Alarm 2 (upper limit) (alarm value=10 C) SUB E5AK-TAA (Control output 1: E53-R) to 20mA + SP 100 Step 1 Step 2 Step 3 Pattern Time: hr, min 3 3

40 CHAPTER 3 BASIC OPERATION 3.2 Setting Input Specifications Setting input specifications Input type Setup mode Temperature input? N Y Temperature unit Scaling Decimal point Temperature input shift Level 2 mode End of setup Input type 3 4

41 3.2 Setting Input Specifications Temperature input Temperature unit Temperature input shift Temperature Upper limit value Input shift upper limit value After shift Before shift Lower limit value 0 Input shift lower limit value 100 Input (%FS) Analog input Readout (humidity) Scaling upper limit value (95.0%) Scaling lower limit value (10.0%) 0 100%FS Input (4 to 20 ma) 3 5

42 CHAPTER 3 BASIC OPERATION Setting Example 1 second min. 1 second min. 1 second min. 3 6

43 3.3 Setting Output Specifications 3.3 Setting Output Specifications Output assignments Standard type Parameter Standard Type Positionproportional Type Control output 1 assignment Control output 2 assignment Auxiliary output 1 assignment Auxiliary output 2 assignment Direct/reverse operation Control period (heat) Control period (cool) ( Indicates that an output specification is supported.) Assignment Control Output Auxiliary Output Destination Output Function Control output (heat) Control output (cool) Alarm 1 Alarm 2 Alarm 3 HBA LBA Time signal 1 Time signal 2 Program end Stage output Error 1 : Input error Error 2 : A/D convertor error 3 7

44 CHAPTER 3 BASIC OPERATION Position-proportional type Assignment Control Output Auxiliary Output Destination Output Function Alarm 1 Alarm 2 Alarm 3 Time signal 1 Time signal 2 Stage output Program end output Error 1 : Input error Error 2 : A/D converter error Direct/reverse operation Control period 3 8

45 3.3 Setting Output Specifications Setting Example 1 second min. 1 second min. 1 second min. 3 9

46 CHAPTER 3 BASIC OPERATION 3.4 Setting Alarm Type Alarm type Alarm Type Alarm Output Operation When X is positive When X is negative 1 Upper-and lower-limit alarm (deviation) ON OFF X X SP Always ON 2 Upper-limit alarm (deviation) ON OFF X SP ON OFF X SP Lower-limit alarm (deviation) Upper-and-lower-limit range alarm (deviation) Upper-and-lower-limit alarm with standby sequence (deviation) ON OFF ON OFF ON OFF X SP X X SP X X SP ON OFF Always OFF Always OFF X SP 6 Upper-limit alarm with standby sequence (deviation) ON OFF X SP ON OFF X SP 7 Lower-limit alarm with standby sequence ON OFF X SP ON OFF X SP 8 Absolute-value upper-limit alarm ON OFF 0 X ON OFF X 0 9 Absolute-value lower-limit alarm ON OFF 0 X ON OFF X 0 10 Absolute-value upper-limit alarm with standby sequence ON OFF 0 X ON OFF X 0 11 Absolute-value lower-limit alarm with standby sequence ON OFF 0 X ON OFF X 0 Alarm value 3 10

47 3.4 Setting Alarm Type Alarm hysteresis Upper limit alarm Lower limit alarm Alarm hysteresis Alarm hysteresis ON ON OFF Alarm value OFF Alarm value Standby sequence Close in alarm/open in alarm Close in alarm Open in alarm Alarm Output Output LED ON ON Lit OFF OFF Not lit ON OFF Lit OFF ON Not lit 3 11

48 CHAPTER 3 BASIC OPERATION Summary of alarm operations Alarm type: lower limit alarm with standby sequence PV Alarm value Alarm hysteresis Alarm output Standby sequence canceled Time ON OFF ON (closed) OFF (open) 3 12

49 3.4 Setting Alarm Type Setting Example 1 second min. 1 second min. 1 second min. 3 13

50 CHAPTER 3 BASIC OPERATION 3.5 Setting Patterns If you want to set parameters in the program mode during controller operation, you must first stop operation. Operation may continue only in special instances, for example, to change SP during controller operation. Select the program mode. Select pattern No. Set number of steps Step time/rate of rise programming Rate of rise setting Step time setting Set step SP/step time Set SP/Ramp time /Soak time of each step Set pattern execution count Set alarm value Set time signal 1, 2 Step/ON time/off time n All patterns completed? y End of program 3 14

51 3.5 Setting Patterns Pattern No. Number of steps Step SP/Step time SP B Step 0 Step 1 Step 2 Step 3 A Step 0 time Step 1 time Step 2 time Step 3 time A: SP of steps 0 and 3 B: SP of steps 1 and 2 Time 3 15

52 CHAPTER 3 BASIC OPERATION Alarm value SP Step 0 Step 1 Step 2 Step 1 SP Step 0 SP Alarm value Alarm type: upper-limit alarm Time About the Alarm Value Decimal Point 3 16

53 3.5 Setting Patterns Setting Example SP 100 Step 1 Step 2 Step 3 1 second min Time: hr, min SP Time (hr, min.) Alarm value 2 Step Step Step Step

54 CHAPTER 3 BASIC OPERATION 3 18

55 3.6 Protect Mode 3.6 Protect Mode Security Mode Set value Calibration Option Expansion Setup Level 2 Level 1 Program Level 0 *1 *1 Only the PV/Present SP parameter can be displayed. Key protect Set value Description 0 Key protection OFF 1 A/M cannot be selected. 2 RUN/RST cannot be selected. 3 Both A/M and RUN/RST cannot be selected. 3 19

56 CHAPTER 3 BASIC OPERATION Setting Example 1 second min. RUN/RST RUN/RST RUN/RST 1 second min. RUN/RST 3 20

57 3.7 Starting and Stopping Operation 3.7 Starting and Stopping Operation RUN/RST RUN/RST RUN/RST Manipulated variable at reset Using Event Input 3 21

58 CHAPTER 3 BASIC OPERATION 3.8 Adjusting Control Operation Changing currently running programs Changing the SP SP Before change After change Changing point Step N Step N+1 Time Changing the time value SP Changing point Time Before change After change Step N Step N+1 Step N Step N+1 About Changing the Number of Steps 3 22

59 3.8 Adjusting Control Operation Setting Example 1 second min. 1 second min. 1 second min. 1 second min. 3 23

60 CHAPTER 3 BASIC OPERATION Manual operation Standard type Manipulated variable (%) Balance-less, bump-less points 0 Manual Auto Manipulated variable switched OFF ON Power interruption + + Time Position-proportional type Balance-less, Bump-less Operation 3 24

61 3.8 Adjusting Control Operation Auto-tuning (A.T.) 40%AT Deviation at start of AT execution 10% FS Deviation at start of AT execution < 10% full-scale Limit cycle of MV change width 40% Limit cycle of MV change width 40% Set point Set point Deviation 10% full-scale Deviation 10% full-scale Start of AT execution End of AT execution Time Start of AT execution End of AT execution Time 100%AT Limit cycle of MV change width 100% Set point Start of AT execution End of AT execution Time 3 25

62 CHAPTER 3 BASIC OPERATION Setting Example 1 second min. AT execute End of AT execution About PID Parameters AT Execution Timing minutes Set value SP Time Step Step

63 CHAPTER 4 APPLIED OPERATION CHAPTER44 APPLIED OPERATION 4 1

64 CHAPTER 4 APPLIED OPERATION 4.1 Selecting the Control Method Heating and cooling control Parameter Control Method Heating control (Standard) Cooling control (Standard) Heating and cooling control Control Output 1 Assignment Control Output 2 Assignment Direct/Reverse operations Control output (heat) - Reverse operation Control output (heat) - Direct operation Control output (heat) Control output (cool) Reverse operation Dead band Output Dead band: dead band width = positive Output Overlap band: dead band width = negative 0 Heating side Cooling coefficient Set point Cooling side Heating side Cooling side PV PV 0 Set point 4 2

65 4.1 Selecting the Control Method Manipulated variable at reset Switching with Manual Operation 4 3

66 CHAPTER 4 APPLIED OPERATION Position-proportional control Open Close O 17 W C Potentiometer Travel time Valve opening monitor Manipulated variable at reset/pv error Other functions Open/close hysteresis Dead band ON OFF -100% 0 MV-Valve opening 100% 4 4

67 4.1 Selecting the Control Method ON/OFF control Hysteresis Hysteresis (heat) ON OFF PV Set point Dead band Hysteresis (heat) OFF ON Heating side Set point Hysteresis (cool) Cooling side PV 4 5

68 CHAPTER 4 APPLIED OPERATION Parameters Symbol Parameter Name: Mode Description Control output 1 For specifying control method assignment : Setup Control output 2 For specifying control method assignment : Setup Direct/reverse For specifying control method operation : Setup Dead band : Level 1 Heating and cooling control Cooling coefficient : Level 1 Heating and cooling control MV at reset : Level 2 Manipulated variable when control operation is stopped MV at PV error : Level 2 Manipulated variable when control operation is PV error Travel time : Option Position-proportional control Motor calibration : Option Position-proportional control Positional-proportional Position-proportional control dead band : Level 1 Open/close Position-proportional control hysteresis : Level 2 Hysteresis (heat) : Level 1 ON/OFF control Hysteresis (cool) : Level 1 ON/OFF control PID / ON/OFF : Expansion ON/OFF control 4 6

69 4.2 Operating Condition Restrictions 4.2 Operating Condition Restrictions Manipulated variable restrictions MV limiter Output (%) 100 MV upper limit value 0 MV lower limit value PV Output (%) 100 MV lower limit value MV upper limit value Heating Cooling side side 0 PV Set point MV change rate limiter Output (%) Switching point MV change rate limit value 1 second Time 4 7

70 CHAPTER 4 APPLIED OPERATION Limiter operation conditions Set point limiter Setting range Changed to upper limit value Scaling (sensor) range Set point limiter Changed to the new upper limit value Input type changed Set point Upper-and lower-limit values of the limitter C Scaling (sensor) upper-and lower-limitter values C A B B Set Point (setting impossible) (setting possible) Set Point Set Point Parameters Symbol Parameter Name: Mode Description MV upper limit : Level 2 For limiting manipulated variable MV lower limit : Level 2 For limiting manipulated variable MV change rate limit : Level 2 For limiting manipulated variable Set point upper limit : Expansion For limiting SP setting Set point lower limit : Expansion For limiting SP setting 4 8

71 4.3 Ramp Rise Rate Setup Program 4.3 Ramp Rise Rate Setup Program Soak time Target SP Rate of rise Time unit of ramp rate Step N N+1 Ramp step Soak step Target SP 1 Soak time 0 Soak time 1 Soak time 2 Target SP 0 Target SP 2 Step Parameter Target SP 0 Target SP 1 Target SP 2 Rate of rise 0 Rate of rise 1 Rate of rise 2 Soak time 0 Soak time 1 Soak time 2 4 9

72 CHAPTER 4 APPLIED OPERATION Relationship with the number of steps Number of steps = even number Number of steps = odd number When the rate of rise is set to 0 Step N is skipped. Step N N-1 N+1 Ramp step Soak step Soak step 4 10

73 4.3 Ramp Rise Rate Setup Program Running the ramp rise rate setup program Changing parameters After change Before change Switching point Time Before change After change Step N Step N+1 Step N Step N

74 CHAPTER 4 APPLIED OPERATION Program example Step 0 Step 1 Step 2 Step Target SP 0 : 100 Target SP 1 : 10 Rate of rise 0 : 3 Rate of rise 1 : 3 Soak time 0 : 0.30 Soak time 1 : 0.30 Number of steps = 4, Time unit of ramp rate = minutes, PV start = 10 Program structure How the program works Parameters Symbol Parameter Name: Mode Description Step time/rate of rise programming : Expansion Ramp rise rate Target SP 0 to 7 : Program Ramp rise rate Rate of rise 0 to 7 : Program Ramp rise rate Soak time 0 to 7 : Program Ramp rise rate : to Operation at Input Error 4 12

75 4.4 Program Operation 4.4 Program Operation Hold/advance Run in level 0 mode Check step No. Hold? N Y Hold = ON End of hold? Continue End Hold = OFF Advance N Y Advance = ON Continue End of advance End End: To program operation 4 13

76 CHAPTER 4 APPLIED OPERATION Pattern operation Repeating execution of the same pattern Executing all patterns Pattern 0 Pattern 1 Pattern 2 Time Pattern 0 Pattern 1 Pattern 3 pattern execution count of pattern 2 is set to 0 Time 4 14

77 4.4 Program Operation Parameters Symbol Parameter Name: Mode Description Hold : Level 0 Pauses program execution. Advance : Level 0 Advances the program one step. Repeatedly executes current Pattern execution count : Program pattern. Run all :Expansion Executes all patterns. About Reset 4 15

78 CHAPTER 4 APPLIED OPERATION 4.5 Wait Operation Wait width SP PV Wait width During wait Counting stop Step updated Time Parameters Symbol Parameter Name: Mode Description Wait width : Expansion Wait operation 4 16

79 4.6 Program output 4.6 Program output Time signal ON time Time Time signal output OFF time About ON conditions About Pattern Elapsing Time 4 17

80 CHAPTER 4 APPLIED OPERATION Program status Program end Final step Time Program end output 1s Stage output 1s Time Stage output Parameters Symbol Parameter Name: Mode Description Time signal set step : Program Time signal Time signal ON time : Program Time signal Time signal ON time : Program Time signal Control output assignment : Setup Program status Auxiliary output assignment : Setup Program status : to 4 18

81 4.7 Setting Running Conditions 4.7 Setting Running Conditions Operation at power ON Continue Reset Run Manual Pattern No. Step No. - - Pattern elapsing time - - Pattern execution count - - Hold status - - Auto/Manual - Run/Reset - - MV at reset *1 - - Manual MV *2 *1 During auto mode at power interruption on a standard type controller *2 During manual mode at power interruption on a standard type controller 4 19

82 CHAPTER 4 APPLIED OPERATION Starting the program run PV start SP Step 0 Step 1 Step 2 Step 3 PV Disabled time Start point Time Standby operation End condition Parameters Symbol Parameter Name: Mode Description Operation at power ON : Expansion Operation when power is turned ON PV start : Expansion Start of program run Standby time : Level 2 Start of program run End condition : Expansion Operation end program run 4 20

83 4.8 How to Use Event Input 4.8 How to Use Event Input Input assignments Setting Function Event input disabled OFF ON: Reset /ON OFF: Run ON: Remote /OFF: Local ON: Manual /OFF: Auto ON: Hold /OFF: Hold cancel Execute at OFF ON Specify by combination of three inputs (*1). *1 The following table shows the relationship between pattern select No. and pattern No. Pattern No Pattern select 0 Pattern select 1 Pattern select

84 CHAPTER 4 APPLIED OPERATION Detailed description of input functions Run/Reset Reset Run Remote/Local Auto/Manual Hold/Hold cancel Advance Advance Pattern select Parameters Symbol Parameter Name: Mode Description Event input assignments 1 to 4: Option Event input functions : to 4 22

85 4.9 How to Use the Heater Burnout Alarm 4.9 How to Use the Heater Burnout Alarm Heater burnout detection To E5AK CT terminal CT Heater wire HBA latch/release Operating conditions 4 23

86 CHAPTER 4 APPLIED OPERATION How to calculate the heater burnout set value 4 24

87 4.9 How to Use the Heater Burnout Alarm Examples of use Example 1 : when using a 200 VAC, 1 kw heater Heater Control output 1KW CT AC200V Heater E5AK-T Control output Example 2 : when using three 200 VAC, 1 kw heaters 1KWx3 CT AC200V E5AK-T Parameters Symbol Parameter Name: Mode Description Heater current monitor : Level 1 Heater current value monitor Heater burnout detection : Level 1 Heater burnout detection Heater burnout latch : Option Heater burnout detection alarm latch 4 25

88 CHAPTER 4 APPLIED OPERATION 4.10 LBA LBA detection time LBA detection width LBA detection example LBA detection time LBA detection time PV LBA detection width Output Heater burnout LBA=ON Time 4 26

89 4.10 LBA Setting the LBA detection time Determining the LBA detection time Measurement time Tm PV 0.2%FS Output LBA detection time = Tm x 2 Time Parameters Symbol Parameter Name: Mode Description AT execute/cancel : Level 1 For automatic setting of LBA detection time LBA detection time : Level 2 For setting LBA detection time LBA detection width : Expansion For changing LBA detection width 4 27

90 CHAPTER 4 APPLIED OPERATION 4.11 How to Use Transfer Output Transfer output type Transfer output scaling Transfer output (ma) Reverse scaling Transfer output (ma) Enlarged scale Transfer output upper limit: 0 Transfer output lower limit: 100 Manipulated variable (%) 4 0 Transfer output lower limit: 10 Transfer output upper limit: Manipulated variable (%) Parameters Symbol Parameter Name: Mode Description Transfer output type : Option Transfer output designation Transfer output upper limit : Option Transfer output scaling Transfer output lower limit : Option Transfer output scaling 4 28

91 CHAPTER 5 PARAMETERS CHAPTER55 PARAMETERS 5 1

92 CHAPTER 5 PARAMETERS Conventions Used in this Chapter The meaning of icons used in this chapter Function Setting Monitor Example of use See Model About parameter display AT Execute/cancel Conditions of Use The controller must be in operation. About the Order in Which Parameters Described in This Chapter 5 2

93 Protect Mode RUN/RST RUN/RST Symbol Parameter Name Page Security 5-3 Key protect 5-4 Security Function Setting Mode Calibration Setting value Option Expansion Setup Level 2 Level 1 Program Level 0 *1 *1 The PV/Present SP parameter is only displayed. See 5 3

94 CHAPTER 5 PARAMETERS Protect Mode Key protect Function Setting Set value 1 No keys are protected. Description 2 AUTO/MANUAL key operation cannot be selected. 3 RUN/RST key cannot be selected. 4 Both the AUTO/MANUAL and RUN/RESET key operations cannot be selected. See 5 4

95 Manual Mode Manual MV Function Setting Control Method Setting Range Unit Default Standard -5.0 to % 0.0 Heating and cooling to % 0.0 Control Method Monitor Range Unit Position-proportional to % See 5 5

96 CHAPTER 5 PARAMETERS Level 0 Mode Symbol Parameter Name Page PV/Present SP 5-6 Pattern No. 5-7 Step No. monitor 5-7 Hold 5-8 Advance 5-8 Standby time monitor 5-9 Pattern elapsing time 5-9 Pattern execution count monitor 5-9 MV monitor (heat) 5-10 MV monitor (cool) 5-10 Valve opening monitor 5-10 PV/Present SP Function Monitor Monitor Range Unit Process Value Scaling lower limit -10%FS to scaling upper limit +10%FS EU Present SP Set point lower limit to set point upper limit EU See 5 6

97 Level 0 Mode Pattern No. Function Setting Range Unit Default 0 to 7 None 0 Setting See Step No. monitor Function Monitor Range Unit 0 to Number of steps-1 None Monitor See 5 7

98 CHAPTER 5 PARAMETERS Level 0 Mode Hold Function Setting Range OFF : Hold cancel / ON: Hold Default Setting See Advance Function Example of use See 5 8

99 Level 0 Mode Standby time monitor Conditions of Use The controller must be in a standby state. Function Monitor Range Unit 0.00 to Hour, minute Monitor See Pattern elapsing time Function Monitor Range Unit 0.00 to Program time unit Monitor Pattern execution count monitor Function Monitor Range Unit 0 to pattern execution count Times Monitor See 5 9

100 CHAPTER 5 PARAMETERS Level 0 Mode MV monitor (heat) MV monitor (cool) Conditions of Use The control must be standard control or heating and cooling control. Function Monitor Control Monitor Range Unit Standard -5.0 to % Heating and cooling 0.0 to % Control Monitor Range Unit Heating and cooling 0.0 to % Model Valve opening monitor Conditions of Use The control must be position-proportional control. Function Monitor Moniter Range Unit to % See Model 5 10

101 Program Mode Symbol Parameter Name Page Pattern No. 5-7 *1 Number of steps 5-12 Step 0 SP or Target SP Ramp rate Step 0 time or Soak time Step 7 SP or Target SP Ramp rate Step 7 time or Soak time Step 8 SP 5-12 Step 8 time 5-13 Step 15 SP 5-12 Step 15 time 5-13 Pattern execution count 5-14 Alarm value Alarm value Alarm value Time signal 1 enabled step 5-15 Time signal 1 ON time 5-15 Time signal 1 OFF time 5-16 Time signal 2 enabled step 5-15 Time signal 2 ON time 5-15 Time signal 2 OFF time

102 CHAPTER 5 PARAMETERS Program Mode Number of steps Function Setting Setting Range Unit Default 1 to 16 None 8 See Step 0 time (Step time) Target SP 0 (Rate of rise programming) to Step 7 SP (Step time) Target SP 7 (Rate of rise programming) Conditions of Use Within the number of steps. Step 8 SP (Step time) to Step 15 SP (Step time) Function Setting Range Unit Default SP lower limit to SP upper limit EU 0 Setting See 5 12

103 Program Mode Ramp rate 0 to Conditions of Use Within the number of steps only in the rate of rise programing. Ramp rate 7 Function Setting See Setting Range Unit Default 0 to 9999 EU/Time unit of ramp rate 0 Step 0 time (Step time) Soak time 0 (Rate of rise programming) to Step 7 time (Step time) Soak time 7 (Rate of rise programming) Conditions of Use Within the number of steps. Step 8 time (Step time) to Step 15 time (Step time) Function Setting See Setting Range Unit Default 0.00 to Program time unit

104 CHAPTER 5 PARAMETERS Program Mode Pattern execution count Function Setting See Setting Range Unit Default 0 to 9999 Time 1 Alarm value 1 Alarm value 2 Alarm value 3 Conditions of Use Alarms must be assigned as outputs. For example, if alarm outputs 1 and 2 only are assigned as outputs, the alarm value 3 parameter cannot be used. Function Setting Range Unit Default to 9999 EU 0 Setting See 5 14

105 Program Mode Time signal 1 enabled step Time signal 2 enabled step Conditions of Use Each of the time signals must be assigned as outputs. Function Setting Range Unit Default 0 to 15 None 0 Setting See Time signal 1 ON time Time signal 2 ON time Conditions of Use Each of the time signals must be assigned as outputs. Function Setting Setting Range Unit Default 0.00 to * See 5 15

106 CHAPTER 5 PARAMETERS Program Mode Time signal 1 OFF time Time signal 2 OFF time Conditions of Use Each of the time signals must be assigned as outputs. Function Setting Range Unit Default 0.00 to Program time unit 0.00 Setting See 5 16

107 Level 1 Mode Symbol Parameter Name Page AT Execute/Cancel 5-18 Proportional band 5-18 Integral time 5-18 Derivative time 5-18 Cooling coefficient 5-19 Dead band 5-19 Position-proportional dead band 5-20 Manual reset value 5-20 Hysteresis (heat) 5-21 Hysteresis (cool) 5-21 Control period (heat) 5-22 Control period (cool) 5-22 Heater current monitor 5-23 Heater burnout

108 CHAPTER 5 PARAMETERS Level 1 Mode AT Execute/Cancel Conditions of Use The controller must be in operation, and control must be advanced PID control. Function Example of use See Proportional band Integral time Conditions of Use The control must be advanced PID control. Derivative time Function Setting Parameter Setting Range Unit Default Proportional band 0.1 to %FS 10.0 Integral time 0 to 3999 *1 Second 233 Derivative time 0 to Second 40 See 5 18

109 Level 1 Mode Cooling coefficient Conditions of Use The control must be either heating and cooling control, or advanced PID control. Function Setting Range Unit Default 0.01 to None 1.00 Setting See Model Dead band Conditions of Use The control system must be heating and cooling control. Function Setting Range Unit Default to %FS 0.00 Setting See Model 5 19

110 CHAPTER 5 PARAMETERS Level 1 Mode Position-proportional dead band Conditions of Use The control must be position-proportional control. Function Setting Range Unit Default 0.1 to 10.0 % 2.0 Setting See Model Manual reset value Conditions of Use The control must be either standard control or advanced PID control, and the integral time parameter must be set to 0. Function Setting Range Unit Default 0.0 to % 50.0 Setting Model 5 20

111 Level 1 Mode Hysteresis (heat) Hysteresis (cool) Conditions of Use The control system must be ON/OFF control. Function Setting Parameter Setting Range Unit Default Hysteresis (heat) 0.01 to %FS 0.10 Hysteresis (cool) 0.01 to %FS 0.10 See Model 5 21

112 CHAPTER 5 PARAMETERS Level 1 Mode Control period (heat) Control period (cool) Conditions of Use Relay, SSR or voltage output must set as the outputs, and the control must be set to advanced PID control, standard control or heating and cooling control. Function Setting See Parameter Setting Range Unit Default Control period (heat) 1 to 99 Second 20 Control period (cool) 1 to 99 Second 20 Model 5 22

113 Level 1 Mode Heater current monitor Conditions of Use The HBA output function must be assigned as the output. Function Monitor Monitor Range Unit 0.0 to 55.0 A See Model Heater burnout Conditions of Use The HBA output function must be assigned as the output Function Setting Range Unit Default 0.0 to 50.0 A 0.0 Setting See Model 5 23

114 CHAPTER 5 PARAMETERS Level 2 Mode Symbol Parameter Name Page Remote/Local 5-25 Standby time 5-25 LBA detection time 5-26 MV at reset 5-26 MV at PV error 5-27 MV upper limit 5-27 MV lower limit 5-27 MV change rate limit 5-27 Input digital filter 5-28 Open/close hysteresis 5-28 Alarm 1 hysteresis 5-29 Alarm 2 hysteresis 5-29 Alarm 3 hysteresis 5-29 Input shift upper limit 5-29 Input shift lower limit

115 Level 2 Mode Remote/Local Conditions of Use The communications function must be in use. Function Setting Range : remote / : local Default Setting See Model Standby time Function Setting Range Unit Default 0.00 to Hour, minute 0.00 Setting See 5 25

116 CHAPTER 5 PARAMETERS Level 2 Mode LBA detection time Conditions of Use The LBA (Loop Break Alarm) function must be assigned as an output. Function Setting Range Unit Default 0 to 9999 Second 0 Setting See MV at reset MV at PV error Conditions of Use Advanced PID control. Function Setting Control Method Setting Range Unit Default Standard -5.0 to % 0.0 Heating and cooling to % 0.0 Setting Range Unit Default : Hold/ : Open/ : Close None See 5 26

117 Level 2 Mode MV upper limit MV lower limit Conditions of Use The control must be advanced PID control. MV change rate limit Function Setting Control Method Setting Range Unit Default Standard MV lower limit +0.1 to % Heating and cooling 0.0 to % Control Method Setting Range Unit Default Standard -5.0 to MV upper limit -0.1 % -5.0 Heating and cooling to 0.0 % Setting Range Unit Default 0.0 to %/S 0.0 See 5 27

118 CHAPTER 5 PARAMETERS Level 2 Mode Input digital filter Function PV before passing through filter A PV after passing through filter 0.63A Time constant Time Input digital filter Setting Range Unit Default 0 to 9999 Second 0 Setting Open/close hysteresis Conditions of Use The control must be position-proportional control. Function Setting Range Unit Default 0.1 to 20.0 % 0.8 Setting See Model 5 28

119 Level 2 Mode Alarm 1 hysteresis Alarm 2 hysteresis Alarm 3 hysteresis Conditions of Use Alarms must be assigned as output. For example, if alarm outputs 1 and 2 only are assigned as outputs, the alarm 3 hysteresis parameter cannot be used. Function Setting Range Unit Default 0.01 to %FS 0.02 Setting See Input shift upper limit Input shift lower limit Conditions of Use The input type must be set to temperature input (thermocouple or platinum resistance thermometer). Function Setting Range Unit Default to C or F 0.0 Setting See 5 29

120 CHAPTER 5 PARAMETERS Setup Mode Symbol Parameter Name Page Input type 5-31 Scaling upper limit 5-32 Scaling lower limit 5-32 Decimal point 5-32 C/ F selection 5-33 Parameter initialize 5-33 Control output 1 assignment 5-34 Control output 2 assignment 5-34 Auxiliary output 1 assignment 5-35 Auxiliary output 2 assignment 5-35 Alarm 1 type 5-36 Alarm 1 open in alarm 5-37 Alarm 2 type 5-36 Alarm 2 open in alarm 5-37 Alarm 3 type 5-36 Alarm 3 open in alarm 5-37 Direct/Reverse operation

121 Setup Mode Input type Function Setting Set value Input Type 0 JPt to ( C) / to ( F) 1 Pt to ( C) / to ( F) Platinum resistance thermometer 2 K1-200 to 1300 ( C) /-300 to 2300 ( F) 3 K2 0.0 to ( C) /0.0 to ( F) 4 J1-100 to 850 ( C) /-100 to 1500 ( F) 5 J2 0.0 to ( C) /0.0 to ( F) 6 T to ( C) / to ( F) 7 E 0 to 600 ( C) /0 to 1100 ( F) 8 L1-100 to 850 ( C) /-100 to 1500 ( F) 9 L2 0.0 to ( C) /0.0 to ( F) Thermocouple 10 U to ( C) / to ( F) 11 N -200 to 1300 ( C) /-300 to 2300 ( F) 12 R 0 to 1700 ( C) /0 to 3000 ( F) 13 S 0 to 1700 ( C) /0 to 3000 ( F) 14 B 100 to 1800 ( C) /300 to 3200 ( F) 15 W 0 to 2300 ( C) /0 to 4100 ( F) 16 PLII 0 to 1300 ( C) /0 to 2300 ( F) 17 4 to 20mA 18 0 to 20mA Current input 19 1 to 5V 20 0 to 5V Voltage input 21 0 to 10V See 5 31

122 CHAPTER 5 PARAMETERS Setup Mode Scaling upper limit Scaling lower limit Conditions of Use The input type must be set to analog input (voltage or current input). Decimal point Function Setting Parameter Setting Range Unit Default Scaling upper limit Scaling lower limit +1 to 9999 None 100 Scaling lower limit to scaling upper limit -1 None 0 Set Value Setting Example digits past decimal point 1 digit past decimal point 2 digits past decimal point 3 digits past decimal point See 5 32

123 Setup Mode C/ F selection Conditions of Use The input type must be set to temperature input (thermocouple or platinum resistance thermometer). Function Setting Range : C / : F Default Setting See Parameter initialize Function Example of use 5 33

124 CHAPTER 5 PARAMETERS Setup Mode Control output 1 assignment Control output 2 assignment Conditions of use The control must be standard control or heating and cooling control. Function Symbol to Function Control output (heat) Control output (cool) Alarms 1 to 3 HBA LBA Setting Symbol to Function Time signals 1 to 2 Program end Stage output See Model 5 34

125 Setup Mode Auxiliary output 1 assignment Auxiliary output 2 assignment Function Symbol to to Function Alarms 1 to 3 HBA LBA Time signals 1 to 2 Setting Symbol Function Program end Stage output Error 1 Error 2 See 5 35

126 CHAPTER 5 PARAMETERS Setup Mode Alarm 1 type Alarm 2 type Alarm 3 type Conditions of Use Alarms must be assigned as outputs. For example, if alarm output 1 and 2 only are assigned as outputs, the alarm 3 type parameter cannot be used. Function Setting See Set Value Settings Set Value Settings 1 Upper- and lower-limit alarm 7 Lower-limit alarm with standby sequence 2 Upper-limit alarm 8 Absolute-value upper-limit alarm 3 Lower-limit alarm 9 Absolute-value lower-limit alarm 4 Upper- and lower-limit range alarm 10 Absolute-value upper-limit alarm with standby sequence 5 Upper- and lower-limit alarm with standby sequence 11 Absolute-value lower-limit alarm with standby sequence 6 Upper-limit alarm with standby sequence 5 36

127 Setup Mode Alarm 1 open in alarm Alarm 2 open in alarm Alarm 3 open in alarm Conditions of Use Alarms must be assigned as outputs. For example, if alarm outputs 1 and 2 only are assigned as outputs, the alarm 3 open in alarm parameter cannot be used. Function Close in alarm Open in alarm Alarm Output Function Alarm Output Output LED ON ON Lit OFF OFF Not lit ON OFF Lit OFF ON Not lit Setting Range : Close in alarm/ :Open in alarm Default Setting See Direct/Reverse operation Function Setting Range : Reverse operation/ :Direct operation Default Setting See 5 37

128 CHAPTER 5 PARAMETERS Expansion Mode Symbol Parameter Name Page Set point upper limit 5-39 Set point lower limit 5-39 PID/ON/OFF 5-39 Operation at power ON 5-40 End condition 5-40 Program time unit 5-41 Step time/rate of rise programming 5-41 Time unit of ramp rate 5-42 PV start 5-42 Wait width 5-43 Alarm during ramp step enable 5-43 Run all enable 5-43 α 5-44 AT calculated gain 5-44 Automatic return of display mode 5-45 AT hysteresis 5-45 LBA detection width

129 Expansion Mode Set point upper limit Set point lower limit Function Setting Parameter Setting Range Unit Default Set point upper limit Set point lower limit +1 to scaling upper limit EU 1300 Set point lower limit Scaling lower limit to set point upper limit -1 EU -200 See PID/ON/OFF Conditions of Use The control must be standard control or heating and cooling control. Function Setting Range :Advance PID/ :ON/OFF Default Setting See Model 5 39

130 CHAPTER 5 PARAMETERS Expansion Mode Operation at power ON Function Setting Range :Continue/ :Reset/ Run/ :Manual Default Setting See End condition Function Setting Range :Reset/ :Continued control using final SP Default Setting See 5 40

131 Expansion Mode Program time unit Function Setting Range :Hour, minute/ :Minute, second Default Setting See Step time/rate of rise programming Function Setting Range :Set time/ :Rate of rise programming Default Setting See 5 41

132 CHAPTER 5 PARAMETERS Expansion Mode Time unit of ramp rate Conditions of Use Rate of rise programming must be set. Function Setting Range : Minute/ : Hour Default Setting See PV start Conditions of Use The set time must be set. Function Setting Range : PV/ :SP Default Setting See 5 42

133 Expansion Mode Wait width Function Setting Range Unit Default 0 to 9999 EU 0 Setting See Alarm during ramp step enable Function Setting Range :/ Default Setting Run all enable Function Setting Range :/ Default 5 43

134 CHAPTER 5 PARAMETERS Expansion Mode α Conditions of Use The control must be advanced PID control. α Function Setting Range Unit Default 0.00 to 1.00 None 0.65 Setting AT calculated gain Conditions of Use The control must be advanced PID control. Function Setting Range Unit Default 0.1 to 10.0 None 1.0 Setting See 5 44

135 Expansion Mode Automatic return of display mode Function Setting Range Unit Default 0 to 99 Second 0 Setting AT hysteresis Conditions of Use The control must be advanced PID control. Function Setting Range Unit Default 0.1 to 9.9 %FS 0.2 Setting LBA detection width Conditions of Use The LBA (Loop Break Alarm) function must be assigned as an output. Function Setting Range Unit Default 0.0 to %FS 0.2 Setting 5 45

136 CHAPTER 5 PARAMETERS Option Mode Symbol Parameter Name Page Event input assignment Event input assignment Event input assignment Event input assignment Communication stop bit 5-48 Communication data length 5-48 Communication parity 5-48 Communication baud rate 5-48 Communication unit No Transfer output type 5-49 Transfer output upper limit 5-49 Transfer output lower limit 5-49 HBA latch 5-50 Motor calibration 5-50 Travel time 5-51 PV dead band

137 Option Mode Event input assignment 1 Event input assignment 3 Event input assignment 2 Event input assignment 4 Function Setting Settings Function Event input disabled OFF ON : Reset /ON OFF : Run ON : Remote /OFF : Local ON : Manual /OFF : Auto ON : Hold /OFF : Hold cancel OFF ON : Execution Specified by combination of three event inputs (*1) Pattern No Pattern select 0 Pattern select 1 Pattern select 2 See Model 5 47

138 CHAPTER 5 PARAMETERS Option Mode Communication stop bit Communication data length Communication parity Communication baud rate Communication unit No. Conditions of Use The communications function must be in use. Function Setting Setting Range Unit Default 1, 2 Bits 2 Setting Range Unit Default 7, 8 Bits 7 Setting : None/ :Even/ :Odd Default Setting Range Unit Default 1.2, 2.4, 4.8, 9.6, 19.2 kbps 9.6 Setting Range Unit Default 0 to 99 None 0 See 5 48 Model

139 Option Mode Transfer output type Transfer output upper limit Conditions of Use The transfer output function must be in use. Transfer output lower limit Function Setting Transfer Output Type Transfer Output Lower Limit to Transfer Output Upper Limit Present SP to 9999 Process Value to 9999 Manipulated variable (heat) -5.0% to 105.0% (standard control), 0.0 to 105.0% (heating and cooling control) Manipulated variable (cool) 0.0 to 105.0% Valve opening to 110.0% See Model 5 49

140 CHAPTER 5 PARAMETERS Option Mode HBA latch Conditions of Use The HBA output function must be assigned as the output. Function Setting Range [ ]: Enabled/[ ]: Disabled Default Setting See Model Motor calibration Conditions of Use The control must be position-proportion control. Function Example of use See Model 5 50

141 Option Mode Travel time Conditions of Use The control must be position-proportion control. Function Setting Range Unit Default 1 to 999 Second 30 Setting See Model PV dead band Conditions of Use The control must be position-proportion control. Function Set point PV dead band Process value Setting Range Unit Default 0 to 9999 EU 0 Setting See Model 5 51

The E5CN provides communications or event input functionality when mounted with one of the following Option Boards.

The E5CN provides communications or event input functionality when mounted with one of the following Option Boards. Digital Temperature Controller Compact and Intelligent Temperature Controller Auto-tuning and self-tuning available. Can auto-tune even during execution of self-tuning Heating or heating/cooling control

More information

Temperature Controller USER S MANUAL

Temperature Controller USER S MANUAL Cat. No. H100-E1-04A E5CN Temperature Controller USER S MANUAL E5CN Temperature Controller User s Manual Revised July 2003 iv Notice: OMRON products are manufactured for use according to proper procedures

More information

Input signal Maximum Range Accuracy. Thermocouple E -50 to 700 C (-58 to 1832 F) ±1 C

Input signal Maximum Range Accuracy. Thermocouple E -50 to 700 C (-58 to 1832 F) ±1 C F4 Process Controller Installation and Operation Guide SAFETY ALERTS The symbols below are used on the equipment and throughout this document to draw the user s attention to important operational and safety

More information

+ A + + - B V B - - + + + NO NC V COM - - - PV PV

+ A + + - B V B - - + + + NO NC V COM - - - PV PV + - A + B B - V + - NO NC COM + - + - V + - PV PV Ramp Soak 100 70 50 30 3 5 3 8 5 3 Minute Steam Heating Sensor Cooling Water PID Hotplate Specifications Input power supply AC 100 to 240V, 50/60Hz, DC

More information

2. Terminal arrangement. Default (PV display) (SV display) Communication protocol selection Selects the Communication protocol. Modbus ASCII mode:

2. Terminal arrangement. Default (PV display) (SV display) Communication protocol selection Selects the Communication protocol. Modbus ASCII mode: COMMUNICATION INSTRUCTION MANUAL TEMPERATURE CONTROLLER KT4, KT8 and KT9 No.KTC1E6 2009.05 To prevent accidents arising from the misuse of this controller, please ensure the operator receives this manual.

More information

Auto-tune PID. Temperature Controller BRAINCHILD FEATURES

Auto-tune PID. Temperature Controller BRAINCHILD FEATURES Auto-tune PID Temperature Controller FEATURES Easy-to-use Fuzzy modified PID heat & cool control Fast A-D sampling rate (5 times/s) Universal input (PT100, thermocouple) with high accuracy 18-bit A-D Analog

More information

TLK 48 MICROPROCESSOR-BASED DIGITAL ELECTRONIC REGULATOR

TLK 48 MICROPROCESSOR-BASED DIGITAL ELECTRONIC REGULATOR TLK 48 MICROPROCESSOR-BASED DIGITAL ELECTRONIC REGULATOR TECHNICAL DATA CARATTERISTICHE MECCANICHE Housing Self-extinguishing plastic, UL 94 V0 Dimensions 48x48 mm DIN depth 98 mm Weight 225 g approx.

More information

Temperature Controller CD401/CD901/CD701/CD501/CD100/CD101 Instruction Manual

Temperature Controller CD401/CD901/CD701/CD501/CD100/CD101 Instruction Manual Ⅰ. Warn Warning of connection Temperature Controller CD401/CD901/CD701/CD501/CD100/CD101 Instruction Manual If the controller fails to operate or error occurs, the system will bring fault for it, please

More information

HONEYWELL DC 1010 / 1020 1030 / 1040 DIGITAL CONTROLLER PRODUCT MANUAL 51-52-25-113 06/02

HONEYWELL DC 1010 / 1020 1030 / 1040 DIGITAL CONTROLLER PRODUCT MANUAL 51-52-25-113 06/02 HONEYWELL DC 1010 / 1020 1030 / 1040 DIGITAL CONTROLLER PRODUCT MANUAL 51-52-25-113 06/02 Before using this manual, please check to ensure the Model number, input type Range and output match your requirements.

More information

DIGITRONIK Digital Indicating Controller SDC10. User s Manual

DIGITRONIK Digital Indicating Controller SDC10. User s Manual No. CP-UM-7E DIGITRONIK Digital Indicating Controller SDC User s Manual Thank you for purchasing the DIGITRONIK Digital Indicating Controller SDC. This manual contains information for ensuring correct

More information

Panel Meters and Controllers Modular Panel Meter Type EDM 35

Panel Meters and Controllers Modular Panel Meter Type EDM 35 Panel Meters and Controllers Modular Panel Meter Type EDM 35 Modular digital panel meter, 3 1/2-digit Indicating or controlling current, voltage, resistance, temperature, tacho or frequency. Easy programming

More information

Delta Temperature Controller User Manual

Delta Temperature Controller User Manual Delta Temperature Controller User Manual Foreword The user manual details the process of using Delta DT series temperature controllers step by step for beginners to easily set up all kinds of parameters

More information

INITIAL SETTING MANUAL

INITIAL SETTING MANUAL REX - C100 REX - C400 REX - C410 REX - C700 REX - C900 INITIAL SETTING MANUAL RKC RKC INSTRUMENT INC. F.M FRANKLIN PTY LTD PH. (07) 3391 4865 This is a manual for the initial setting of the REX-C100, -C400,

More information

Process controller Setpoint programmer 1/16 DIN - 48 x 48 mm gammadue series M5 line

Process controller Setpoint programmer 1/16 DIN - 48 x 48 mm gammadue series M5 line BT. 2.9 M/E Process controller programmer /6 DIN - 48 x 48 mm gammadue series M line Advanced features, customizable and process adaptable High speed data aquisition and signal management. Efficent information

More information

Automation System TROVIS 6400 TROVIS 6493 Compact Controller

Automation System TROVIS 6400 TROVIS 6493 Compact Controller Automation System TROVIS 6400 TROVIS 6493 Compact Controller For panel mounting (front frame 48 x 96 mm/1.89 x 3.78 inch) Application Digital controller to automate industrial and process plants for general

More information

PID Microprocessor temperature controllers CTD43 - CTD46 - CTH46

PID Microprocessor temperature controllers CTD43 - CTD46 - CTH46 PID Microprocessor temperature controllers CTD43 - CTD46 - CTH46 Display 1. Red measurement display (or the set point for CTD 43 by pressing, indicated by a flashing decimal point). 2. Green display of

More information

Specifications H8CA-S H8CA-S RATINGS. Approved by the following standards CHARACTERISTICS

Specifications H8CA-S H8CA-S RATINGS. Approved by the following standards CHARACTERISTICS Solid-State Counter/Timer 1/16 DIN, Easy-to-Operate Combination Counter and Timer Operation selectable as preset counter or timer 6-digit LCD Present Value: 8 mm (.32 in) Set Value: 4 mm (.16 in) Nonsignificant

More information

User's Guide. Integrating Sound Level Datalogger. Model 407780. Introduction

User's Guide. Integrating Sound Level Datalogger. Model 407780. Introduction User's Guide 99 Washington Street Melrose, MA 02176 Phone 781-665-1400 Toll Free 1-800-517-8431 Visit us at www.testequipmentdepot.com Back to the Extech 407780 Product Page Integrating Sound Level Datalogger

More information

SYL-2372 PID TEMPERATURE CONTROLLER INSTRUCTION MANUAL Version 1.4 (May 2016)

SYL-2372 PID TEMPERATURE CONTROLLER INSTRUCTION MANUAL Version 1.4 (May 2016) AUBER INSTRUMENTS Instruction Manual SYL-7 PID TEMPERATURE CONTROLLER INSTRUCTION MANUAL Version 1.4 (May 16) Caution This controller is intended to control equipment under normal operating conditions.

More information

RISH EM 3490 DS Dual Source Energy Meter RISH EM 3490 DS. Application : Product Features:

RISH EM 3490 DS Dual Source Energy Meter RISH EM 3490 DS. Application : Product Features: Application : RISH Master 3490 DS measures important electrical parameters of Utility (in normal mode) & Generators (in Power back up) in three phase and single phase Network & replaces the multiple analog

More information

Multipoint Temperature Controller E5ZE

Multipoint Temperature Controller E5ZE Multipoint Temperature Controller E5ZE Compact, Easy-to-mount Multipoint Temperature Controller (Casing) Compact, Easy-to-use, Board-type Multipoint Temperature Controller (Open) Easy-to-mount, user-friendly

More information

User Manual Auto Tuning PID Temperature Controller

User Manual Auto Tuning PID Temperature Controller User Manual Auto Tuning PID Temperature Controller TUPC-T series (Applicable for accurate controls of Temperature) TEMPSEN DEVICES Plot No : 2&3, Balaji Nagar, 4 th Street, Mettukuppam, Thoraipakkam, Chennai-600097

More information

REGTRONIC OPERATING INSTRUCTIONS

REGTRONIC OPERATING INSTRUCTIONS REGTRONIC OPERATING INSTRUCTIONS 1.FEATURES Electrical connection: M12 8-pin connector Preset pressure range 0.05-10 bar with possible full scale regulation. 10 100 mbar adjustable deadband Supply pressure:

More information

Vroom Hardware manual ver. 1.00 Code 114VROOHWE00. Vroom CANBUS USER INTERFACE WITH LCD GRAPHIC DISPLAY AND WITH TEMPERATURE AND HUMIDITY SENSOR

Vroom Hardware manual ver. 1.00 Code 114VROOHWE00. Vroom CANBUS USER INTERFACE WITH LCD GRAPHIC DISPLAY AND WITH TEMPERATURE AND HUMIDITY SENSOR Vroom CANBUS USER INTERFACE WITH LCD GRAPHIC DISPLAY AND WITH TEMPERATURE AND HUMIDITY SENSOR ENGLISH HARDWARE MANUAL ver. 1.00 CODE 114VROOHWE00 page 1 of 22 Important Important Read these instructions

More information

Smart DeviceNet Remote I/O Terminals

Smart DeviceNet Remote I/O Terminals Smart DeviceNet Remote I/O Terminals ather and Use Information for Effective Preventive Maintenance et more useful data for preventive maintenance when you build cost-effective parallel information systems

More information

PX-series digital temperature controller Example of Applications and Parameter Functions

PX-series digital temperature controller Example of Applications and Parameter Functions PX-series digital temperature controller Example of Applications and Functions ECNO:1158a Introduction This document provides examples of applications and major functions of three types of digital controllers

More information

Temperature & Humidity SMS Alert Controller

Temperature & Humidity SMS Alert Controller Temperature & Humidity Alert Controller METERS 3 simple steps starting the unit: Insert the SIM card Plug in the sensors connectors Connect the AC power cord. Specifications: AC 90~260V Auto Select Internal

More information

E5AN-H/E5EN-H. Advanced Digital Temperature Controller

E5AN-H/E5EN-H. Advanced Digital Temperature Controller Advanced Digital Temperature Controller / (96 x 96 mm and 48 x 96 mm) CSM DS_E A New High-performance Controller: High Resolution, High Speed, and High Input Accuracy. Logic Operations and Preventive Maintenance

More information

Electronic Control Devices The European Product Catalogue 2007

Electronic Control Devices The European Product Catalogue 2007 FX07 Field Controller (1/4) FX07 Field Controller Display Model Dimensions in mm (inches) The FX07 is a terminal unit controller in the Facility Explorer range of products. The controller is designed specifically

More information

M 140i. Multifunction Calibrator. Operation Manual

M 140i. Multifunction Calibrator. Operation Manual M 140i Multifunction Calibrator Operation Manual M-140i Multifunction Calibrator MEATEST, s.r.o. 2 Operation Manual v33 MEATEST, s.r.o. M-140i Multifunction Calibrator Content Operation Manual... 1 Basic

More information

Quick Connect. quick - simple - efficient. www.g-mw.de

Quick Connect. quick - simple - efficient. www.g-mw.de Quick Connect quick - simple - efficient www.g-mw.de Phone: +49 9103 7129-0 Fax: +49 9103 7129-207 Innovative connection technology to plug three single-phase current transformers to multifunctional power

More information

SR1, SR3 Series Digital Controller Instruction Manual

SR1, SR3 Series Digital Controller Instruction Manual SR, SR Series Digital Controller Instruction Manual Please do not begin operating this product until you have read this instruction manual thoroughly and you understand its contents. Safety Rules For matters

More information

Variable Preset Counter signo 723.1

Variable Preset Counter signo 723.1 Variable Preset Counter signo 723.1 Large, 6-digit, 14 mm high LED display Up/down counter with prescaler 2 presets, one programmable as trailing preset Easy direct selection by 2 function keys 2 relay

More information

FLOW CALCULATOR INSTRUCTION MANUAL MESURES BAMOPHOX 759 26-06-2007 759 M1 02 E MES FLOW CALCULATOR 759-02/1

FLOW CALCULATOR INSTRUCTION MANUAL MESURES BAMOPHOX 759 26-06-2007 759 M1 02 E MES FLOW CALCULATOR 759-02/1 BAMOPHOX 759 E - M FLOW CALCULATOR INSTRUCTION MANUAL MESURES 22, Rue de la Voie des Bans - Z.I. de la Gare - 95100 ARGENTEUIL Tél : (33) 01 30 25 83 20 - Web : www.bamo.fr Fax : (33) 01 34 10 16 05 -

More information

Instruction Manual. 2in1 LAN Tester & Multimeter. Model: LA-1011

Instruction Manual. 2in1 LAN Tester & Multimeter. Model: LA-1011 Instruction Manual 2in1 LAN Tester & Multimeter Model: LA-1011 1 Contents Introduction... Features... Safety Precautions.. Meter Description... Electrical Specification... Operation.. AutoRanging Multimeter.

More information

Softstarters. Type PSTX Fieldbus communication, Built-in Modbus RTU. 1SFC132089M0201 April 2015 1SFC132089M0201 1

Softstarters. Type PSTX Fieldbus communication, Built-in Modbus RTU. 1SFC132089M0201 April 2015 1SFC132089M0201 1 Softstarters Type PSTX Fieldbus communication, Built-in Modbus RTU 1SFC132089M0201 April 2015 1SFC132089M0201 1 1 Modbus RTU The Modbus protocol is a fieldbus protocol that provides full control and status

More information

Telefon (+45) 43 43 82 00 Telefax (+45) 43 43 74 75 mail@uni-valve.com www.uni-valve.com. Installation and operating manual

Telefon (+45) 43 43 82 00 Telefax (+45) 43 43 74 75 mail@uni-valve.com www.uni-valve.com. Installation and operating manual Uni-Valve A /S VENTILER & INSTRUMENTER Telefon (+45) 43 43 82 00 Telefax (+45) 43 43 74 75 mail@uni-valve.com www.uni-valve.com UNI-EL Electric actuator Installation and operating manual Remote position

More information

Duct Humidity Transmitter

Duct Humidity Transmitter SDC-H Duct Humidity Transmitter Features Replaceable sensor element Humidity measurement for air ducts Minimum and maximum value memory 0 0V, 0 0mA or 0V, 4 0mA measuring signals selectable with jumpers

More information

Programmer/Controller

Programmer/Controller Systems Plus START 7 8 9 envirotronics ALARM STOP 4 5 6 ALARM ACK Instrument Manual Systems Plus Programmer/Controller OFF HELP 1 2 0 3. ENTER ALARM RESET DEL Revision 6 9/12/97 Table of Contents 2 Menu

More information

Series DFMT Digital Paddlewheel Flowmeter

Series DFMT Digital Paddlewheel Flowmeter Series DFMT Digital Paddlewheel Flowmeter Bulletin F-DFMT Specifications - Installation Operating Instructions -/8 [00] -/ [8] -/8 [00] A The Series DFMT Digital Paddlewheel Flow Transmitter provides instantaneous

More information

DC1000 Series General Purpose UNIVERSAL DIGITAL CONTROLLERS

DC1000 Series General Purpose UNIVERSAL DIGITAL CONTROLLERS DC1000 Series General Purpose UNIVESA DIGITA CONTOES PODUCT SPECIFICATION SHEET OVEVIEW The DC1000 family of microprocessor based controllers combine a high degree of functionality, reliability at a very

More information

MTS Power Products MIAMI FL 33142 ATS-22AG. Automatic Transfer Switch And Control PLC Operator s Manual

MTS Power Products MIAMI FL 33142 ATS-22AG. Automatic Transfer Switch And Control PLC Operator s Manual MTS Power Products MIAMI FL 33142 ATS-22AG Automatic Transfer Switch And Control PLC Operator s Manual Dedicated Single Phase Transfer Switch With Touch Screen Controls Normal Power Connections Emergency

More information

WD-AMX Water Detection Controllers

WD-AMX Water Detection Controllers Page 1 of 5 WD-AMX Water Detection Controllers Features: Benefit: LED Status of leak status VFC output Audible alarm Auto or manual reset alarm output Uses an isolated AC signal which prevents oxidation

More information

Modular I/O System Analog and Digital Interface Modules

Modular I/O System Analog and Digital Interface Modules OPERATING INSTRUCTIONS Modular I/O System Analog and Digital Interface Modules Installation Operation Maintenance Document Information Document ID Title: Operating Instructions Modular I/O System Part

More information

HERZ-Thermal Actuators

HERZ-Thermal Actuators HERZ-Thermal Actuators Data Sheet 7708-7990, Issue 1011 Dimensions in mm 1 7710 00 1 7710 01 1 7711 18 1 7710 80 1 7710 81 1 7711 80 1 7711 81 1 7990 00 1 7980 00 1 7708 11 1 7708 10 1 7708 23 1 7709 01

More information

HCS-3300/3302/3304 USB Remote Programmable Laboratory Grade Switching Mode Power Supply

HCS-3300/3302/3304 USB Remote Programmable Laboratory Grade Switching Mode Power Supply 1. INTRODUCTION HCS-3300/3302/3304 USB Remote Programmable Laboratory Grade Switching Mode Power Supply User Manual This family of efficient, upgraded SMPS with small form factor, auto cross over CV CC,

More information

Application/Connection Examples

Application/Connection Examples This Quick Start Guide is designed to familiarize the user with the connection and configuration of the DTS-305 DIN rail mounted single / 3 phase power & energy meter with RS-485 or TCP communications.

More information

AutoRanging Digital MultiMeter

AutoRanging Digital MultiMeter Owner's Manual AutoRanging Digital MultiMeter Model No. 82139 CAUTION: Read, understand and follow Safety Rules and Operating Instructions in this manual before using this product. Safety Operation Maintenance

More information

DPI 260 SERIES: Digital Pressure Indicators

DPI 260 SERIES: Digital Pressure Indicators DPI 260 SERIES: Digital Pressure Indicators INTRODUCTION The DPI 260, 261 and 262 range of digital pressure instruments measure and indicate pressure in any specified scale units and provide accuracies

More information

TAC I/NETTM MR-VAV-AX. Application Specific MicroRegulator TM

TAC I/NETTM MR-VAV-AX. Application Specific MicroRegulator TM TAC I/NETTM TM TAC s TM has an extensive range ofpre-engineered VAV control sequences, which combined with a fully integrated actuator and airflow transducer, makes it a low Total Installed Cost solution

More information

Dyeing Programmer DP - 01

Dyeing Programmer DP - 01 Dyeing Programmer DP - 01 Display and Controls. 1) Display: 16/2 alphanumeric display 2) Temperature range: 0 to 150 degree. 3) Resolution: 1 degree. 4) Accuracy: +/- 1 degree. 5) Temperature control setting:

More information

Programming Logic controllers

Programming Logic controllers Programming Logic controllers Programmable Logic Controller (PLC) is a microprocessor based system that uses programmable memory to store instructions and implement functions such as logic, sequencing,

More information

How To Control A Power Supply With A Mini Transmitter And Switch (Power Supply)

How To Control A Power Supply With A Mini Transmitter And Switch (Power Supply) transmitter (2 wire) / switch for continuous or On/Off Control Indication, monitoring, transmitting and continuous or On/Off control in one device Output signal 4...20 ma, 2-wire for continuous control

More information

Power source. Input. Contact / Open collector Voltage input (SELECTABLE) AC100-240V DC12-24V AC100-240V. Output indicator

Power source. Input. Contact / Open collector Voltage input (SELECTABLE) AC100-240V DC12-24V AC100-240V. Output indicator SERIES Electronic Preset Counter Instruction Manual Please note that misuse of this device may lead to injury to the user or damage to the device. Please observe all safety precautions and warnings in

More information

NC-12 Modbus Application

NC-12 Modbus Application NC-12 Modbus Application NC-12 1 Table of Contents 1 Table of Contents... 2 2 Glossary... 3 SCADA...3 3 NC-12 Modbus in general... 3 4 Entire system... 4 4.1 PFC to PC connection alternatives...4 4.1.1

More information

Manual Ranging MultiMeter

Manual Ranging MultiMeter Owner s Manual Manual Ranging MultiMeter Model 82345 CAUTION: Read, understand and follow Safety Rules and Operating Instructions in this manual before using this product.! Safety! Operation! Maintenance!

More information

JNIOR. Overview. Get Connected. Get Results. JNIOR Model 310. JNIOR Model 312. JNIOR Model 314. JNIOR Model 410

JNIOR. Overview. Get Connected. Get Results. JNIOR Model 310. JNIOR Model 312. JNIOR Model 314. JNIOR Model 410 The INTEG is an Ethernet I/O (digital, analog) device that monitors and controls a small set of process signals. functions as both basic I/O for integration with another application or system AND as a

More information

E5CC-800 (48 48 mm) Digital Temperature Controller (Simple Type)

E5CC-800 (48 48 mm) Digital Temperature Controller (Simple Type) Digital Temperature Controller (Simple Type) E5CC-8 (48 48 mm) Large White Display That s Easier to Read. Easy to Use, from odel Selection to Setup and Operation. A Complete Range of I/O Capacities, Functions,

More information

Operating Instructions. Single Loop Controller EC48 & EC96

Operating Instructions. Single Loop Controller EC48 & EC96 Operating Instructions Single Loop Controller EC48 & EC96 03/2010 PSG Plastic Service GmbH 1 Operating Instructions EC48 & EC96 Table of Contents 1 Introduction... 3 1.1 Typographical Conventions... 4

More information

#1381-3, Juan-dong, Nam-gu, Incheon, Korea TEL:(82-32) 876-4697 FAX:(82-32) 876-4696 http://www.hynux.com E-mail: sdt@hyelec.co.kr

#1381-3, Juan-dong, Nam-gu, Incheon, Korea TEL:(82-32) 876-4697 FAX:(82-32) 876-4696 http://www.hynux.com E-mail: sdt@hyelec.co.kr #1381-3, Juan-dong, Nam-gu, Incheon, Korea TEL:(8-3) 876-4697 FAX:(8-3) 876-4696 http://www.hynux.com E-mail: sdt@hyelec.co.kr MA01E50110 Recorder & Temperature Controller RT9 INSTRUCTION MANUAL Thank

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS LIGHTING CONTROL PANELS 4 AND 8 RELAYS INSTALLATION INSTRUCTIONS INSTALLATION OVERVIEW The installation instructions contained in this document are provided as a guide for proper and reliable installation.

More information

INSTALLATION & SERVICE MANUAL. Display Panel

INSTALLATION & SERVICE MANUAL. Display Panel INSTALLATION & SERVICE MANUAL Display Panel The PowerLine EMS TM is a specialized power distribution and energy management system intended to be used in recreational vehicles. The Control Module is housed

More information

MP-4000 Alarm List (Software version 2.4.3 or later)

MP-4000 Alarm List (Software version 2.4.3 or later) Service Bulletin SUBJECT: MP4000 Alarm s BULLETIN: C 100 DATE: June 19, 2013 ALARM LIST Where it is possible the alarm number is kept the same as for MP-3000. MP-3000 holds alarm number from 0 to 127.

More information

1. SAFETY INFORMATION

1. SAFETY INFORMATION RS-232 Sound Level Meter 72-860A INSTRUCTION MANUAL www.tenma.com 1. SAFETY INFORMATION Read the following safety information carefully before attempting to operate or service the meter. Use the meter

More information

Multifunction devices

Multifunction devices devices devices devices, electronic Type Page LED multifunction displays pulse, frequency, time (DC) Codix 524 240 pulse, frequency, time (AC+DC) Codix 544 243 LCD multifunction preset counters 1 or 2

More information

Operational Overview and Controls Guide

Operational Overview and Controls Guide DOCUMENT: ECSEQ2-1 EFFECTIVE: 02/14/07 SUPERSEDES: 02/26/03 Operational Overview and Controls Guide Standard Two or Three Pump Type VFD Booster Controls 6700 Best Friend Road. Norcross, GA 30071. (770)

More information

4-Channel Thermometer / Datalogger

4-Channel Thermometer / Datalogger USER GUIDE 4-Channel Thermometer / Datalogger RTD and Thermocouple Inputs Model SDL200 Introduction Congratulations on your purchase of the Extech SDL200 Thermometer, an SD Logger Series meter. This meter

More information

Technical data. General specifications. Indicators/operating means. 30 Hz Multiplex operation 30 Hz / n, n = number of sensors, n 5

Technical data. General specifications. Indicators/operating means. 30 Hz Multiplex operation 30 Hz / n, n = number of sensors, n 5 Model Number Single head system Features Parameterization interface for the application-specific adjustment of the sensor setting via the service program ULTRA 000 programmable switch outputs Hysteresis

More information

ABB i-bus EIB / KNX Analogue Input AE/S 4.2

ABB i-bus EIB / KNX Analogue Input AE/S 4.2 Product Manual ABB i-bus EIB / KNX Analogue Input AE/S 4.2 Intelligent Installation Systems This manual describes the functionality of Analogue Input AE/S 4.2. Subject to changes and errors excepted. Exclusion

More information

Technote. Frese OPTIMA Compact actuators DN10-DN32. Application. Features thermic actuators. Features motoric actuators. Approval. www.frese.

Technote. Frese OPTIMA Compact actuators DN10-DN32. Application. Features thermic actuators. Features motoric actuators. Approval. www.frese. Page 1 of 6 Application Proportional 0-10V or 3-position modulating or On/ Off control of Frese OPTIMA Compact valves in heating, ventilating and air conditioning systems. The actuator can be mounted on

More information

CQM1-SF200/CS1W-SF200

CQM1-SF200/CS1W-SF200 Safety Relay Unit ( I/O Unit Type) CQM1-SF200/CS1W-SF200 CSM_CQM1-SF200_CS1W-SF200_DS_E_2_1 A Safety Relay Unit That Functions as a I/O Unit. Less Installation Space and Wiring Required. Safety Relay Unit

More information

BARDIC. 4 & 8 Zone Fire Panels Zircon range. Data, installation, operation and maintenance. by Honeywell

BARDIC. 4 & 8 Zone Fire Panels Zircon range. Data, installation, operation and maintenance. by Honeywell Data, installation, operation and maintenance 4 & 8 Zone Fire Panels Zircon range BARDIC by Honeywell LED flashing LED Continuous FAULT DISABLE/TEST Power General Fault Sounder Fault/ Disable System Fault

More information

Centro-Matic Automatic Lubrication Systems System Controls

Centro-Matic Automatic Lubrication Systems System Controls Selecting the right controls for your automated lubrication system is one of the last steps in the design process. Several different models may be chosen to control power-operated pumps, depending on the

More information

Preliminary. Dual-line FLOW rate/totalizers. Pr ovu Model PD6200 Analog Input. Pr ovu Model PD6300 Pulse Input. Analog Inputs.

Preliminary. Dual-line FLOW rate/totalizers. Pr ovu Model PD6200 Analog Input. Pr ovu Model PD6300 Pulse Input. Analog Inputs. Dual-line FLOW rate/totalizers Pr ovu PD6200 Analog Input ProVu Se r i e s Pr ovu PD6300 Pulse Input Analog Inputs 0-20 ma, 4-20 ma, 0-5 V, 1-5 V, and ±10 V Inputs Isolated 24 VDC @ 200 ma Transmitter

More information

Meter Relays. 077 Series Analogue Meter Relays. Features. Applications

Meter Relays. 077 Series Analogue Meter Relays. Features. Applications 077 Series Analogue Features Monitors and controls any variable which can be converted to an A.C. or D.C. signal. Rugged, shock and vibration resistant design Indicator, relays and power unit in one housing

More information

3½ DIGIT VOLTMETER MODULE LED- / LCD- SERIES

3½ DIGIT VOLTMETER MODULE LED- / LCD- SERIES 12.02 EA 4035-SERIES 3½ DIGIT VOLTMETER MODULE LED- / LCD- SERIES Splashproof 35,1x22,4 mm FEATURES * IP65 * 2 LED AND 2 LCD TYPES * EASY TO USE OR COMPATIBLE TO DATEL * ±200mV D.C. FULL SCALE READING

More information

1000W Single Output Power Supply 15V 24V. Protection type: Total Power limit, Latch-style (Recovery after reset AC power ON or inhibit)

1000W Single Output Power Supply 15V 24V. Protection type: Total Power limit, Latch-style (Recovery after reset AC power ON or inhibit) 000W Single Output Power Supply AK-000 series Features: Universal AC input / Full range Programmable output Voltage (0% ~ 05%) Programmable output Current (% ~ 05%) + / 0.5A auxiliary output U profile,

More information

Digital and Analog I/O

Digital and Analog I/O 70072-0127-07 TECHNICAL NOTE 02/2007 Digital and Analog I/O This document discusses the application and configuration of digital and analog inputs/outputs (I/O). Details are for both onboard I/O and external

More information

1.44 kw Programmable DC Power Supplies XLN Series

1.44 kw Programmable DC Power Supplies XLN Series Data sheet 1.44 kw Programmable DC Power Supplies XLN Series New Family of High Density System Power Supplies The B&K Precision XLN series are compact, programmable, single-output DC power supplies, suitable

More information

Digi-Motor Installation Guide

Digi-Motor Installation Guide Digi-Motor Installation Guide Installation Video...located at marsdelivers.com Digi-Motor Installation Guide Digi-Motor For technical assistance with your Azure Digi-Motor, call the MARS technical support

More information

Digital Pressure Measuring Instrument MDR480

Digital Pressure Measuring Instrument MDR480 Description The digital panel instrument MDR480 is designed to measure, display, and monitor pressures in industrial applications. The instrument is panel mounted with a front frame dimension of 96 mm

More information

ABB i-bus KNX Fan Coil Controller FC/S 1.1

ABB i-bus KNX Fan Coil Controller FC/S 1.1 Product manual ABB i-bus KNX Fan Coil Controller FC/S 1.1 Intelligent Installation Systems Contents Page 1 Introduction... 2 2 Device technology... 3 3 Application and planning 3.1 Heating, ventilation

More information

Programmable Single-/Dual-/Triple- Tone Gong SAE 800

Programmable Single-/Dual-/Triple- Tone Gong SAE 800 Programmable Single-/Dual-/Triple- Tone Gong Preliminary Data SAE 800 Bipolar IC Features Supply voltage range 2.8 V to 18 V Few external components (no electrolytic capacitor) 1 tone, 2 tones, 3 tones

More information

Multifunction Digital Timer

Multifunction Digital Timer Multifunction Digital Timer 1/16 DIN Timer with Easy-to-use Functions Nine output modes accommodate a wide variety of applications. All parameters set by scroll-through menus accessed from the front panel.

More information

PD 100A. Printing data system

PD 100A. Printing data system PD 100A Printing data system Operating instructions ENGLISH IMPORTANT: Read these instructions carefully before installing and using the device; do not forget following all additional information. Keep

More information

Process modules Digital input PMI for 24 V DC inputs for 120 V AC inputs

Process modules Digital input PMI for 24 V DC inputs for 120 V AC inputs E031026 000823 Process modules Digital input PMI for inputs for 120 V AC inputs PMI Input E4, E5, GND L- PMI 120 V AC Input E4, E5, Common C E6, E7, GND L- E6, E7, Common C LEDs for the inputs operation

More information

WEA-Base. User manual for load cell transmitters. UK WEA-Base User manual for load cell transmitters Version 3.2 UK

WEA-Base. User manual for load cell transmitters. UK WEA-Base User manual for load cell transmitters Version 3.2 UK WEA-Base User manual for load cell transmitters 1 Contents 1. Technical data... 3 2. Assembly... 4 2.1 Power supply... 4 2.2 Load cells... 4 2.3 RS-485... 4 2.4 Relays... 5 2.5 Digital input... 5 2.6 Analogue

More information

IO-DIM6 6-Channel, Digital to Analogue Converters

IO-DIM6 6-Channel, Digital to Analogue Converters Page 1 of 6 IO-DIM6 6-Channel, Digital to Analogue Converters Features: Benefits: Input status indication Calibrated output DIN Rail mounting Expands controller input capacity Fault finding LED indication

More information

TEMON 8-C. Doc. N MO-0370-ING TEMPERATURE MONITOR DEVICE TYPE TEMON 8-C OPERATION MANUAL. Microener - Copyright 2010 FW 2.2 Date 01.12.2008 Rev.

TEMON 8-C. Doc. N MO-0370-ING TEMPERATURE MONITOR DEVICE TYPE TEMON 8-C OPERATION MANUAL. Microener - Copyright 2010 FW 2.2 Date 01.12.2008 Rev. TEMPERATURE MONITOR DEVICE TYPE TEMON 8-C OPERATION MANUAL Microener - Copyright 2010 FW 2.2 Date 01.12.2008 Rev. 0 1. Generality 3 2. Introduction 3 3. Accessories and Options 3 4. Installation 3 5. Connection

More information

How To Use A Ci 2001A/B (I2) With A Power Supply (I3)

How To Use A Ci 2001A/B (I2) With A Power Supply (I3) Weighing Indicator CI-2001A/B OWNER S MANUAL CONTENTS PRECAUTIONS 4 INTRODUCTION 6 THE FEATURES OF CI-2001A/B 6 TECHNICAL SPECIFICATION 7 DIMENSIONS 8 FRONT PANEL(CI-2001A) 9 FRONT PANEL(CI-2001B) 11 REAR

More information

ERMA-Electronic GmbH - Max-Eyth-Str.8-78194 Immendingen - Tel: +49(0)7462/2000-0 - Fax: +49(0)7462/2000-29. Technische Änderungen vorbehalten

ERMA-Electronic GmbH - Max-Eyth-Str.8-78194 Immendingen - Tel: +49(0)7462/2000-0 - Fax: +49(0)7462/2000-29. Technische Änderungen vorbehalten Panel mounting instruments / DIN cabinets mounting different standard housing sizes different supply voltages all usual measured variables Measuring instruments programmable industrialfair execution customized

More information

THYRISTORS T1-1PH from 850A to 2700A Specifications Universal 1 Phase Thyristor Unit 55-77-03-62, March 2012

THYRISTORS T1-1PH from 850A to 2700A Specifications Universal 1 Phase Thyristor Unit 55-77-03-62, March 2012 Technical Information THYRISTORS T1-1PH from 850A to 2700A Specifications Universal 1 Phase Thyristor Unit 55-77-03-62, March 2012 GENERAL DESCRIPTION THYRISTORS T1-1PH is a full digital and universal

More information

Technical Manual. FAN COIL CONTROLLER COOLING or HEATING ANALOG or PWM Art. 119914 631001A

Technical Manual. FAN COIL CONTROLLER COOLING or HEATING ANALOG or PWM Art. 119914 631001A COOLING or HEATING ANALOG or PWM Art. 119914 631001A TOTAL AUTOMATION GENERAL TRADING CO. LLC SUITE NO.506, LE SOLARIUM OFFICE TOWER, SILICON OASIS, DUBAI. UAE. Tel. +971 4 392 6860, Fax. +971 4 392 6850

More information

650W Single Output Power Supply 15V 24V. 27V 48V Rated Current. 0 ~ 100A 0 ~ 50A 0 ~ 40A 0 ~ 27A 0 ~ 24A 0 ~ 13.6A Rated Power

650W Single Output Power Supply 15V 24V. 27V 48V Rated Current. 0 ~ 100A 0 ~ 50A 0 ~ 40A 0 ~ 27A 0 ~ 24A 0 ~ 13.6A Rated Power Features: Universal AC input / Full range Programmable output Voltage (0% ~ 05%) Programmable output Current (% ~ 05%) + / 0.5A auxiliary output Forced current sharing at parallel operation Power OK signal

More information

User Manual THR840DUK Digital Thermostat

User Manual THR840DUK Digital Thermostat User Manual THR840DUK Digital Thermostat 50051982-001 Rev. A WARNING: This product must be correctly installed and configured to work properly (see pages 12-24). If you are not experienced in wiring electrical

More information

MAGTROL. DSP6001 High-Speed Programmable Dynamometer Controller. DSP6001 Data Sheet FEATURES APPLICATIONS MOTOR TESTING SOFTWARE DESCRIPTION

MAGTROL. DSP6001 High-Speed Programmable Dynamometer Controller. DSP6001 Data Sheet FEATURES APPLICATIONS MOTOR TESTING SOFTWARE DESCRIPTION Data Sheet High- Programmable Controller FEATURES Two Channels: Enable the unit to suppt up to two testing instruments with independent tandem configurations. Built-in Alarm System: F power, speed, tque,

More information

Thyristor-controlled power supplies and battery chargers

Thyristor-controlled power supplies and battery chargers Thyristor-controlled power supplies and battery chargers Input voltage: 115 / 230 VAC, single phase, 50 / 60 Hz or 208 / 400 / 480 VAC, three phases, 50 / 60 Hz Output voltage: 12 / 24 / 48 / 60 / 72 /

More information

User Guide. Model 380260 Insulation Tester / Megohmmeter

User Guide. Model 380260 Insulation Tester / Megohmmeter User Guide Model 380260 Insulation Tester / Megohmmeter Introduction Congratulations on your purchase of Extech s Insulation Tester/Megohmmeter. The Model 380260 provides three test ranges plus continuity

More information

Count input Display Time range 999999.9h or 3999d23.9h (selectable) 999h59m59s or 9999h59.9m (selectable) 3. Case Color B: Black

Count input Display Time range 999999.9h or 3999d23.9h (selectable) 999h59m59s or 9999h59.9m (selectable) 3. Case Color B: Black R Self-Powered Time Counter Subminiature Time Counters With Enhanced Appearance and Features H Large display with 8.6 mm (0.338 in) height H Available with backlit LCD H PNP/NPN DC voltage available H

More information

Energy Management Power Analyzer Type WM14-96 Basic Version

Energy Management Power Analyzer Type WM14-96 Basic Version Energy Management Power Analyzer Type WM-96 Basic Version Optional dual pulse output Alarms (visual only) V, An Optional galvanically insulated measuring inputs Product Description 3-phase power analyzer

More information