Corrosion in Fire Sprinkler Systems
|
|
|
- Sharlene Floyd
- 9 years ago
- Views:
Transcription
1 Corrosion in Fire Sprinkler Systems
2 Overview Objectives Discuss the problems corrosion causes in fire sprinkler systems Identify the causes of corrosion Take an in-depth look at the current state of corrosion technology Evaluate the economic impact that corrosion has on fire sprinkler systems
3 Safety The biggest concern is that corrosion will cause a sprinkler system to fail. 50% Blockage (California, 5 year old system ) Failed Sprinkler Head (Illinois, 12 year old system )
4 Issues Corrosion is known to produce many problems in the fire sprinkler market Pinhole leaks Temporary shutdowns Loss of property Loss of production Total system replacements Reduces effectiveness of fire sprinkler design Personal injury
5 Issues What is the life expectancy of a fire sprinkler system?
6 VdS survey of corrosion in sprinkler systems: Class I - Little damage is found the pipe array should just be flushed. Class II - Medium damage is found, so that some but not all pipes show increased damage, those pipes must be replaced. Class III - Considerable corrosion and deposits the complete pipe array or parts of it must be replaced.
7 Cincinnati Dry system Class I 7
8 Minneapolis Dry system Class II 8
9 Illinois Dry system branch line Class III 9
10 VdS Survey Dry systems after being installed for 12½ years: 27% - Class I 51% - Class II 22% - Class III 73% of dry systems have significant corrosion issues
11 Types of Corrosion There are 2 main types of corrosion in FSS 1) Generalized Corrosion (Rust) 2) Microbiologically Influenced Corrosion (MIC) Generalized MIC
12 Generalized Corrosion Generalized Corrosion, also known as rust, requires 3 things: 1)Water 2)Iron 3)Oxygen Generalized Corrosion Cell (Rust reaction)
13 MIC The term Microbiologically influenced corrosion (MIC) is used to designate corrosion due to the presence and activities of bacteria. The three main type of bacteria are Acid Producing Bacteria (APB) Sulfur Reducing Bacteria (SRB) Iron Related Bacteria (IRB)
14 MIC in FSS FM Global study found 40% of corrosion was influenced by MIC and 60% of corrosion was generalized corrosion.
15 Dry and Pre-action Corrosion flourishes in Dry and Pre-action systems because they are NEVER 100% DRY. Trapped water from hydrostatic testing, combined with humid air supplied constantly by the air compressor creates a perfect storm. Typical Dry System
16 Generalized Corrosion Corrosion requires 3 things: 1)Water 2)Iron 3)Oxygen If eliminate one, you stop corrosion. Generalized Corrosion Cell (Rust reaction)
17 Nitrogen Replace the Oxygen with Nitrogen. Nitrogen is an INERT gas. It does not react with metals. Thus, no oxidation or rust occurs!
18 Nitrogen Tests
19 Nitrogen Tests After 20 months Compressed Air
20 After 20 months 98% Nitrogen Nitrogen Tests
21 Nitrogen Tests Compressed Air After 20 months 98% Nitrogen
22 Corrosion Coupon Testing Manifold Nitrogen Tests
23 After 12 Months Steel Coupon Compressed Air Steel Coupon 98% Nitrogen Galvanized Coupon Compressed Air Galvanized Coupon 98% Nitrogen
24 Nitrogen Tests
25 Nitrogen Tests On average, using 98% Nitrogen gas over compressed air increases the life expectancy of a dry fire sprinkler system up to 5.3X
26 Nitrogen Tests
27 Galvanized Pipe 27 No Hydraulic Advantage Source: NFPA 13, 2013
28 Nitrogen Use FM Global Property Loss Prevention Data Sheets Installation Guidelines for Automatic Sprinklers Protection of Sprinkler System Piping Use internally galvanized, stainless steel, or similar corrosion-resistant pipe in all new dry-pipe, pre-action, refrigerated-area, deluge, and exposure-protection sprinkler systems. Do not use galvanized pipe in areas where the ambient temperature could exceed 130 F (54 C) unless the pipe is specifically FM Approved for use in such conditions. Exception: Black steel pipe can be used in dry-pipe sprinkler systems equipped with closed-type sprinklers if the piping system is filled with an inert gas.
29 29 How do you supply nitrogen to a fire sprinkler system? Source: NFPA 13, 2013
30 30 Reliable Source The trick to this is removing that 21% oxygen from the fire sprinkler piping and replacing it with pure nitrogen. The earth s atmosphere is 78% nitrogen and 21% oxygen
31 Nitrogen Generator Nitrogen Cabinet Dryer AMD Air Compressor Nitrogen Storage Tank (98%+ N 2 )
32 Nitrogen Generator The nitrogen membrane is the heart of the nitrogen generator.
33 Nitrogen Generators Sizing a Nitrogen Generator Largest riser size Supervisory pressure Total system capacity
34 Nitrogen Generators Design with Nitrogen in mind Use black steel over galvanized save 30% on average of sprinkler piping Use a lower supervisory pressure smaller compressor needed Feed more than one system Plant Nitrogen Parking garage installation
35 Recommendations Dry Systems Use nitrogen over compressed air Use black steel over galvanized Implement a corrosion monitoring program
36 Questions?
Cost Evaluation of Black Steel Pipe and Galvanized Pipe When Using a Nitrogen Generator
Cost Evaluation of Black Steel Pipe and Galvanized Pipe When Using a Nitrogen Generator Andy L. Kaempfer Business Development Manager Potter Electric Signal Company, LLC 1609 Park 370 Place St. Louis,
Corrosion Inhibition of Dry and Pre-Action Fire Suppression Systems Using Nitrogen Gas
Corrosion Inhibition of Dry and Pre-Action Fire Suppression Systems Using Nitrogen Gas Josh Tihen Corrosion Product Manager Potter Electric Signal Company, LLC 1609 Park 370 Place St. Louis, MO 63042 (800)
This chapter is devided into two sections:
This chapter is devided into two sections: Page Installation requirements........................................................................ 127 The installation process..........................................................................
NFPA 25 FAQs. 1. When inspecting an old system (60 years or older), when/where does NFPA 25 require a system to be upgraded to present standards?
NFPA 25 FAQs Responses to FAQs are prepared by NFPA technical staff to assist users in reading and understanding NFPA codes and standards. The responses, however, are not Formal Interpretations issued
CATHODIC PROTECTION SYSTEM DESIGN
CATHODIC PROTECTION SYSTEM DESIGN Presented By DENIS L ROSSI P.E. CORROSION ENGINEER New England C P Inc. Corrosion Fundamentals What is corrosion? It is defined as the degradation or deterioration of
Inspection and Testing of Water-Based Systems
Inspection and Testing of Water-Based Systems Standard Model/Computer-Based Testing Level III Content Outline The candidate for NICET certification at Level III in the Inspection and Testing of Water-Based
Features. Model EX Low Pressure Dry Pipe Valve System 2 (DN50), 2½ (DN65), 3 (DN80), 76 mm, 4 (DN100 ), 6 (DN150), 165 mm & 8 (DN200)
Features 1. Differential latching clapper-type, lightweight, dependable construction. 2. Low Air Pressurized System, psi -to- 2 psi (0.6 bar -to- 1.9 bar) Max 3. Reset externally. Cover removal is not
ESFR DRY PENDENT SPRINKLER VK502 (K14.0) TECHNICAL DATA
December 19, 2013 Sprinkler 122j 1. DESCRIPTION Viking Early Suppression Fast Response (ESFR) Dry Pendent Sprinkler VK502 is a fast response fusible element type sprinkler designed for use in storage areas
Nitrogen Blanketing for Methanol Storage and Transportation
Nitrogen Blanketing for Methanol Storage and Transportation Overview Air is the enemy of many materials. Not only can oxygen cause safety concerns and product degradation, but moisture, dirt, hydrocarbons
SECTION 15010 GENERAL REQUIREMENTS, MECHANICAL. 1. All piping entering the Shipyard must be controlled per Shipyard Standard Procedure # 21.1-1.
SECTION 15010 June 16, 2005 GENERAL REQUIREMENTS, MECHANICAL A. GENERAL 1. All piping entering the Shipyard must be controlled per Shipyard Standard Procedure # 21.1-1. 2. All piping shall be in accordance
Balancing chemical reaction equations (stoichiometry)
Balancing chemical reaction equations (stoichiometry) This worksheet and all related files are licensed under the Creative Commons Attribution License, version 1.0. To view a copy of this license, visit
FIVE YEAR CERTIFICATION REPORT
GARDEN GROVE FIRE DEPARTMENT FIRE PREVENTION DIVISION FIVE YEAR CERTIFICATION REPORT Service and maintenance report of automatic fire extinguishing systems, including fire sprinklers, dry, deluge, and
Appendix B Forms for Inspection, Testing, and Maintenance
Appendix B Forms for Inspection, Testing, and Maintenance This appendix is not a part of the requirements of this NFPA document but is included for informational purposes only. Forms need to be complete
D. Open hydronic systems, including [condenser] [fluid-cooler spray] water, shall have the following water qualities:
SECTION 232500 - PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following HVAC water-treatment systems: 1. Open Loop Chemical Treatment Systems. 2. Closed Loop Chemical Treatment Systems. 3.
TECHNICAL DATA 2. LISTINGS AND APPROVALS. Spray Nozzle 11. December 20, 2013
Spray Nozzle 11 1. DESCRIPTION Viking Model C-1 Window Sprinklers are non-automatic, open, outside intended for protection of windows, walls, and roofs against exposure fires. The directional discharge
1. A belt pulley is 3 ft. in diameter and rotates at 250 rpm. The belt which is 5 ins. wide makes an angle of contact of 190 over the pulley.
Sample Questions REVISED FIRST CLASS PARTS A1, A2, AND A3 (NOTE: these questions are intended as representations of the style of questions that may appear on examinations. They are not intended as study
Fighting Fire in Sprinklered Buildings. Student Guide
Fighting Fire in Sprinklered Buildings Student Guide Fighting Fire in Sprinklered Buildings Student Guide Table of Contents Purpose........................................................... 3 Instruction
THE INSTRUCTIONS PRESENTED HERE ARE ORIENTED TO USERS OF CNG CYLINDERS AS WELL AS TO TECHNICIANS IN CHARGE OF THEIR INSTALLATION
FOREWORD THE INSTRUCTIONS PRESENTED HERE ARE ORIENTED TO USERS OF CNG CYLINDERS AS WELL AS TO TECHNICIANS IN CHARGE OF THEIR INSTALLATION CAUTION! READ THIS BEFORE This guide only has the objective of
NITROX // safer diving
NITROX // safer diving Always available, easy to use and safe for daily use: NITROX diving gas offers professional divers, yacht owners and offshore facilities the highest level of convenience and independence
Fire Suppression Systems for Your Home
ABN 64 127 735 433 PO Box 395 Mundaring. 6073. Phone/fax 9295 6263. Mob 0439 971 213 [email protected] 18 Wandeara Cres, Mundaring. 6073. Fire Suppression Systems for Your Home Hills residents
SMALL GAS OPERATOR OPERATION AND MAINTENANCE PLAN
SMALL GAS OPERATOR OPERATION AND MAINTENANCE PLAN Facility Name: Address: QUALIFIED PERSONNEL All tasks shall be completed by a person that is qualified to that task (see operators qualification of individuals
Element D Services Plumbing
Medical Vacuum and Gas PART 1 - GENERAL 1.01 OVERVIEW A. This section addresses medical vacuum, waste anesthetic gas disposal, compressed air, oxygen, nitrous oxide, nitrogen and carbon dioxide systems.
Important Ontario Fire Code Information for Building Owners in the City of Windsor
Important Ontario Fire Code Information for Building Owners in the City of Windsor This information is intended to be used a reference only. For a complete listing consult the Ontario Fire Code or contact
Dissimilar Metal Corrosion
PDHonline Course S118 (1 PDH) Dissimilar Metal Corrosion Instructor: D. Matthew Stuart, P.E., S.E., F.ASCE, F.SEI, SECB, MgtEng 2013 PDH Online PDH Center 5272 Meadow Estates Drive Fairfax, VA 22030-6658
Best Practice in Boiler Water Treatment
Best Practice in Boiler Water Treatment Boiler Water Treatment Part 2 Internal Treatment Objectives of Internal Water Treatment 1 To control the level of total dissolved solids (TDS) within the boiler
Determining Equivalent Weight by Copper Electrolysis
Purpose The purpose of this experiment is to determine the equivalent mass of copper based on change in the mass of a copper electrode and the volume of hydrogen gas generated during an electrolysis reaction.
2014 Service Technician Training Program Closed Loop Systems
1/20/14 2014 Service Technician Training Program Closed Loop Systems Daniel S. Krack, CWT 2 Closed Loop Cooling and Heating The Closed Loop Cooling Advantages High Efficiency Chillers, Heat Exchangers,
LASER CUTTING OF STAINLESS STEEL
LASER CUTTING OF STAINLESS STEEL Laser inert gas cutting is the most applicable process type used for cutting of stainless steel. Laser oxygen cutting is also applied in cases where the cut face oxidation
AMEC 6007: Linear Velocity and Acceleration Learning Outcome. CHEM 6012: Oil and Gas Compositions and Sales Specifications Learning Outcome
s/objectives Level F ADMN 6044: Post Job Management It is important to know the proper procedures for closing out a job so that rigging and equipment is maintained for future use and personnel are adequately
NFPA31FuelOilPiping 1 Revised 3-1-11
NFPA 31 Fuel Oil Piping, Installation and Testing Chapter 8 Fuel Piping Systems and Components 8.1 Scope. This chapter shall apply to piping systems and their components used to transfer fuel oil from
A GUIDE TO SELECTING YOUR INDUSTRIAL OVEN
A GUIDE TO SELECTING YOUR INDUSTRIAL OVEN Application 1 The first step in selecting an industrial oven is defining the required heat application that your oven will be used for. Heat processing is extensively
IWMC 2015, Amsterdam, October 28-29, 2015 Practical experience from actual water mist installations. What can be learnt?
IWMC 2015, Amsterdam, October 28-29, 2015 Practical experience from actual water mist installations. What can be learnt? Magnus Arvidson Fire Research SP Technical Research Institute of Sweden [email protected]
Cathodic Protection Use On Tank Bottoms & Underground Piping In Power Generation Plants
Cathodic Protection Use On Tank Bottoms & Underground Piping In Power Generation Plants PG&E Office San Francisco January 18, 2007 Craig K. Meier Corrosion Control Incorporated Corrosion process for tanks
Fire Sprinkler System Maintenance and Testing Page 1 MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS
Page 1 MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS Introduction When properly installed and maintained, automatic fire sprinkler systems have proven to be the most effective means for protecting
ELECTRIC/DIESEL FIRE PUMP CHECK LIST
BUILDING NAME: DESIGNER: SCO REPRESENTATIVE: PUMP MANUF.: LOCATION: INSTALLER: DATE: OWNER NAME: INSTALLATION Certificate for flushing and hydrostatic test furnished Piping been hydrostatically tested
Steel Fire Sprinkler Pipe
Steel Fire Sprinkler Pipe Wheatland Tube Fire Sprinkler Products Wheatland Tube began producing steel fire sprinkler pipe in 1931, and today offers the most complete line of products in the industry. Engineers
Basic Hydraulics and Pneumatics
Basic Hydraulics and Pneumatics Module 1: Introduction to Pneumatics PREPARED BY IAT Curriculum Unit March 2011 Institute of Applied Technology, 2011 ATM 1122 Basic Hydraulics and Pneumatics Module 1:
Case History Report The Dolphin Nonchemical Device Boilers and Cooling Tower
Case History Report The Dolphin Nonchemical Device Boilers and Cooling Tower Device Evaluated "The Dolphin HYTRONIC Series 1000" pulsed power water treatment device (Dolphin) manufactured by Clearwater
12 Ways To Avoid Boiler Tube Corrosion
12 Ways To Avoid Boiler Tube Corrosion By: H. F. Hinst Plant Metallurgist Tubular Products Division, Keystone Plant The Babcock & Wilcox Company Corrosion troubles in low pressure heating boilers -- which
Ontario Fire Code SECTION 5.13 DIP TANKS. Illustrated Commentary. Office of the Ontario Fire Marshal
Ontario Fire Code SECTION 5.13 DIP TANKS Illustrated Commentary Office of the Ontario Fire Marshal Dip Tanks Illustrated Commentary 1 5.13.1. Location 5.13.1.1. Dip tank operations involving flammable
Grounding and Bonding Against Static Electricity. Jon Koppari, CSP, MS Occupational Safety and Health Instructor OSHA Training Institute
Grounding and Bonding Against Static Electricity Jon Koppari, CSP, MS Occupational Safety and Health Instructor OSHA Training Institute Objectives Identify Sources of Ignition. Identify Hazards associated
Comparison of the Corrosion Protection Effectiveness of Vapor Corrosion Inhibitor and Nitrogen Blanketing System
Comparison of the Corrosion Protection Effectiveness of Vapor Corrosion Inhibitor and Nitrogen Blanketing System Behzad Bavarian 1, Jia Zhang 1, Lisa Reiner 1 and Boris Miksic, FNACE 2 Dept. of Manufacturing
Potter Electric Sprinkler Monitoring Training Manual
R Potter Electric Sprinkler Monitoring Training Manual 1 #8704200D 2 Contents Foreword... 4 Introduction... 5 Fire Alarm Signals... 6 Types Of Sprinkler Systems... 7 Wet Pipe Sprinkler Systems... 8 Straight
Regulatory Related FAQs
Process Safety Management (PSM) Shipping Regulations Environmental Issues Waste Disposal Decontamination and Cleaning Process Safety Management (PSM) Regulatory Related FAQs Do you need to follow OSHA
Fire Alarm System Monitoring - CAN/ULC-S561-03
Fire Alarm System Monitoring - CAN/ULC-S561-03 Brian McBain ULC Regulatory Services May 4, 2011 Copyright 1995-2007 Underwriters' Laboratories of Canada. All rights reserved. No portion of this material
An inventory of hazardous materials used in your workplace will prove useful.
Introduction Fire Protection is an organized approach designed to prevent fires. In the event of a fire, a fire protection program will help prevent or minimize personal injuries, losses, and harm to the
Mechanical Systems Competency 1.20
Competency 1.20 Mechanical systems personnel shall demonstrate a working level knowledge of the safety and health fundamentals of mechanical systems and/or components. 1. Supporting Knowledge and Skills
INTRODUCTION INDUSTRIAL INSTALLATIONS AND ERECTIONS QUALITY THAT EXCELS
QUALITY THAT EXCELS INTRODUCTION Established in July 1996, aiming at attending market needs, Munhoz positively has taken charge of supplying high standard solutions, in the projects, civil constructions,
PLAN SUBMITTAL REQUIREMENTS FOR SPRAY BOOTHS AND SPRAYING ROOMS EXTINGUISHING SYSTEMS
January 1997 PLAN SUBMITTAL REQUIREMENTS FOR SPRAY BOOTHS AND SPRAYING ROOMS EXTINGUISHING SYSTEMS 1.0 PERMIT 1.1 After receipt of a Building Permit from the City of San Jose Building Department, submit
Environmentally Friendly Solutions for Industry MEXEL 432 CASE STUDY - GEOTHERMAL POWER GENERATION
MEXEL 432 CASE STUDY - GEOTHERMAL POWER GENERATION The company SOCOMINE operates a geothermal power station in eastern France near Soultz-sous-Forêt. Concerns about corrosion of the drill pipe caused them
esfr pendent sprinkler vk510 (k25.2)
January 17, 2014 Sprinkler 124a 1. DESCRIPTION Viking Early Suppression Fast Response (ESFR) Pendent Sprinkler VK510 incorporates the capability to suppress specific high-challenge fires. The addition
Aerosol Fire Suppression. Your Choice for Special Hazard Fire Protection
Aerosol Fire Suppression Your Choice for Special Hazard Fire Protection Traditional Special Hazard Fire Protection Centers Around Two Technologies Water deluge and chemical agent fixed systems protect
Biocorrosion Risk Assessment
Biocorrosion Risk Assessment Andrew M.Pritchard European Summer School on Biologically Influenced Corrosion, University of Portsmouth 7-13 July 2002 Contents T Management and assessment of risks T A definition
SCBA Frequently Asked Questions
SCBA Frequently Asked Questions Q. WHEN SHOULD I USE SCBA? A. An SCBA is the choice when dealing with any oxygen deficient atmosphere that is IDLH (Immediately Dangerous to Life or Health), or any environment
www.klmtechgroup.com TABLE OF CONTENT
Page : 1 of 38 Project Engineering Standard www.klmtechgroup.com KLM Technology #03-12 Block Aronia, Jalan Sri Perkasa 2 Taman Tampoi Utama 81200 Johor Bahru Malaysia GENERAL COMMISSIONING TABLE OF CONTENT
CNG & Hydrogen Tank Safety, R&D, and Testing
> Powertech Labs Inc. CNG & Hydrogen Tank Safety, R&D, and Testing 012.10.2009 Presented by Joe Wong, P.Eng. PRESENTATION OBJECTIVES Present experience from CNG in-service tank performance. The process
www.klmtechgroup.com TABLE OF CONTENT
Page : 1 of 19 Project Engineering Standard www.klmtechgroup.com KLM Technology #03-12 Block Aronia, Jalan Sri Perkasa 2 Taman Tampoi Utama 81200 Johor Bahru Malaysia TABLE OF CONTENT SCOPE 2 REFERENCES
Department of Transportation Hazardous Material Regulations General Awareness, Safety & Security Training. For: University of Dayton Hazmat Employees
Department of Transportation Hazardous Material Regulations General Awareness, Safety & Security Training For: University of Dayton Hazmat Employees February, 2014 Overview Hazardous materials are substances
ASMECourseCatalog. www.energyu.org www.midwestenergy.org
ASMECourseCatalog www.energyu.org www.midwestenergy.org ASME Abnormal Operating Conditions... 6 ASME GAS01 Hazards of Natural Gas and Prevention of Accidental Ignition... 6 ASME 0001 Measure Structure-to-Electrolyte
Restoring bore pump performance
Factory 28, no 94-102 Keys Rd. Tel: 03 9555 2524 Moorabbin Vic 3189 Fax: 03 9553 2090 Website: www.aquariusdrilling.com.au Email: [email protected] Restoring bore pump performance Do you have
THE USE OF OZONE IN COOLING TOWERS
THE USE OF OZONE IN COOLING TOWERS Paul D. McNicholas Ozonia Ltd Duebendorf, Switzerland Abstract Ozone has been successfully applied to industrial cooling water systems with the resultant improvement
ANNEX 17 DRAFT AMENDMENTS TO SOLAS REGULATIONS II-2/4 AND II-2/16. Part B Prevention of fire and explosion
Annex 17, page 1 ANNEX 17 DRAFT AMENDMENTS TO SOLAS REGULATIONS II-2/4 AND II-2/16 Part B Prevention of fire and explosion Regulation 4 Probability of ignition 1 The existing paragraph 5.5 is replaced
1-1/2 Inch (DN40) 9 lbs. (4,1 Kg) 8 lbs. (3,6 Kg) Flange Groove* N/A N/A. Flange Flange N/A N/A
Worldwide Contacts www.tyco-fire.com DV-5 Deluge Valve Diaphragm Style General Description The TYCO 1-1/2 thru inch (DN40 thru DN200), DV-5 Deluge Valves are diaphragm type valves designed for vertical
Facility Operations Physical Safety Guidance Document
Facility Operations Physical Safety Guidance Document Title: Guide on Pipe Identification Standards (ASME A13.1-1996) Original Date: December 18, 2000 Section: 4.0 Facility Operations Revised Date: Number:
LONDON BOROUGH OF CAMDEN HIGHGATE NEWTOWN: PIPEWORK CONDITION REVIEW. Revision 002
LONDON BOROUGH OF CAMDEN HIGHGATE NEWTOWN: PIPEWORK CONDITION REVIEW Revision 002 Prepared by Michael Doyle and Stewart Park, reviewed by Alex Maguire. Issued for comment 10 th January 2013 Updated by
New York City 2014 Building Code Fire Protection Revisions. Presented by John Bower
New York City 2014 Building Code Fire Protection Revisions Presented by John Bower NYC Building Code History History In 1625, the Dutch West India Company established rules for the types and locations
Gas Cylinder Safety. https://www.youtube.com/watch?v=c4kb-8cjvyg
Gas Cylinder Safety Acetylene cylinder-related damage http://my.firefighternation.com/forum/topics/even-a-small-cylinder-of?q=forum/topics/even-a-small-cylinder-of Gas Cylinder Safety https://www.youtube.com/watch?v=c4kb-8cjvyg
Preaction System with DV-5 Deluge Valve Single Interlock, Supervised Wet Pilot Actuation 1-1/2 thru 8 Inch (DN40 thru DN200) General Description
Worldwide Contacts www.tycofire.com Preaction System with DV5 Deluge Valve Single Interlock, Supervised Wet Pilot Actuation /2 thru 8 Inch (DN thru DN200) General Description The DV5 Supervised Single
BRAZED PLATE INSTALLATION MANUAL
www.brazedplate.com BRAZED PLATE INSTALLATION MANUAL S.E.C. Heat Exchangers P.E.I. CANADA C0A 1A0 tel; 902-659-2424 fax; 902-659-2800 Table of Contents Description...2 Mounting position...3 Piping connections......3
Enhancing SRUs with oxygen-enriched air
M ost refiners have now moved toward a higher standard of s u l p h u r - r e c o v e ry efficiency to comply with clean fuels regulations that impose a reduction of sulphur in refined products. While
ESFR "PRE-PRIMED SINGLE INTERLOCKED PREACTION" COLD STORAGE SYSTEM MANUAL
ESFR "PRE-PRIMED SINGLE INTERLOCKED PREACTION" COLD STORAGE SYSTEM MANUAL The Viking Corporation 210 N Industrial Park Road Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax:
LIST PRICE BOOK MALLEABLE CAST IRON PRESS FITTINGS FOR SCH. 10 40 BLACK & GALVANIZED STEEL PIPE
FASTLOCK fittings are not currently approved for use with gas or fire protection applications. FITTINGS FOR STEEL PIPE LIST PRICE BOOK MALLEABLE CAST IRON FITTINGS FOR SCH. 10 40 BLACK & GALVANIZED STEEL
TECHNICAL DATA. Dry 122a. November 12, 2013
Dry 122a 1. PRODUCT DESCRIPTION The Viking is a quick-opening device. When installed with the required external Anti-flood Device, the assembly is designed to increase the operating speed of Viking Model
Hydrostatic Testing of Aviation Components
Hydrostatic Testing of Aviation Components 1) What is Cylinder Requalification? a. The process of inspecting and testing pressure cylinders i. Pressure cylinders must be inspected and tested at specific
WHAT YOU DON T KNOW ABOUT ACCUMULATORS CAN KILL YOU!
WHAT YOU DON T KNOW ABOUT ACCUMULATORS CAN KILL YOU! Atlanta (Monroe) GA 770-267-3787 [email protected] www.gpmhydraulic.com What You Don t Know About Hydraulic Accumulators Can Kill You TABLE OF CONTENTS
Compressed Air Filters
Compressed Air Filters Superior Filtration for Increased Productivity What happens when you don t use an air filter? Kaeser Gives You the Air Quality You Require Ambient air contains contaminants that
Sprinkler Systems in Hospitals. Lisbon 6 November 2008
Sprinkler Systems in Hospitals Lisbon 6 November 2008 Some Statistics from NFPA USA 1994-1998 1998 2,600 fires/year in healthcare facilities Causes of fire: Other equipment 20% Cooking equipment 18% Appliances/tools/air-conditioning
Steam System Best Practices Condensate System Piping
Steam System Best Practices Condensate System Piping Summary The best method for improving steam system energy efficiency, reducing chemical costs, and reducing make-up water costs is to return the maximum
A SHORT INTRODUCTION TO CORROSION AND ITS CONTROL
A SHORT INTRODUCTION TO CORROSION AND ITS CONTROL CORROSION OF METALS AND ITS PREVENTION WHAT IS CORROSION Corrosion is the deterioration of materials by chemical interaction with their environment. The
Nauki ścisłe priorytetem społeczeństwa opartego na wiedzy Artykuły na platformę CMS
S t r o n a 1 Author: Marta Miedźwiedziew METAL CORROSION AND PROTECTION AGAINST CORROSION Introduction The article is intended for high school students having courses in chemistry at both the basic and
Metals and Non-metals. Comparison of physical properties of metals and non metals
Metals and Non-metals Comparison of physical properties of metals and non metals PHYSICAL PROPERTY METALS NON-METALS Physical State Metallic lustre (having a shining surface) Mostly solids (Liquid -mercury)
SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST RESIDENTIAL FIRE SPRINKLERS NFPA 13R
July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST RESIDENTIAL FIRE SPRINKLERS NFPA 13R Address: Permit #: Inspector: Date: Status: Inspector: Date: Status: A-Approved;
FPS4 APPENDIX A (INTERIM) SPECIFICATION FOR THE INSPECTION AND TESTING OF AUTOMATIC FIRE SPRINKLER SYSTEMS
FPS4 APPENDIX A (INTERIM) SPECIFICATION FOR THE INSPECTION AND TESTING OF AUTOMATIC FIRE SPRINKLER SYSTEMS To be used in conjunction with the Fire Protection Association Australia FPS4-2000: Agreement
REGULATIONS for INSTALLATION, MAINTENANCE, and TESTING APPLICATION PACKET
REGULATIONS for INSTALLATION, MAINTENANCE, and TESTING FIRE SUPPRESSION SYSTEMS APPLICATION PACKET CITY OF NAPERVILLE 400 S. EAGLE STREET NAPERVILLE, Il 60540 PHONE: 630.420.6070 FAX: 630.420.6657 Fire
Domestic Chemical Water Treatment Manufacturers Association
Domestic Chemical Water Treatment Manufacturers Association Code of Practice for Chemical Cleaning and Inhibiting of Domestic Hot Water Central Heating Systems A Guide for Installers and Specifiers Prepared
Determination of the Percentage Oxygen in Air
CHEM 121L General Chemistry Laboratory Revision 1.1 Determination of the Percentage Oxygen in Air In this laboratory exercise we will determine the percentage by volume of Oxygen in Air. We will do this
Lecture 35: Atmosphere in Furnaces
Lecture 35: Atmosphere in Furnaces Contents: Selection of atmosphere: Gases and their behavior: Prepared atmospheres Protective atmospheres applications Atmosphere volume requirements Atmosphere sensors
North American Stainless
Introduction: North American Stainless Flat Products Stainless Steel Grade Sheet 309S (S30908)/ EN1.4833 SS309 is a highly alloyed austenitic stainless steel used for its excellent oxidation resistance,
Treatment options for hydrogen sulfide. Testing for hydrogen sulfide
Sometimes hot water will have a sour smell, similar to that of an old damp rag. This smell often develops when the thermostat has been lowered to save energy or reduce the potential for scalding. Odor-causing
Atlas Copco Quality Air Solutions. Compressed Air Filters
Atlas Copco Quality Air Solutions Compressed Air Filters Total capability, total responsibility Right at the heart of your business, Atlas Copco delivers quality compressed air for superior operational
CHAPTER. Standpipes and Hose Systems OVERVIEW. Standpipe and Hose Systems Defined
Standpipes and Hose Systems CHAPTER 3 This chapter, which opens with an overview of standpipe and hose systems, is intended to assist the registered design professional (RDP), commissioning agent, authority
The Use of Magnesium Hydroxide Slurry as a Safe and Cost Effective Solution for H 2
The Use of Magnesium Hydroxide Slurry as a Safe and Cost Effective Solution for H 2 S Odor and Corrosion in Sanitary Sewer Systems Aileen Gibson Chris Knapp Steve Leykauf Wastewater Treatment History In
Sulfites for Oxygen Control
If you would like a more detailed version of this report, please request SOS from [email protected] along with your e-mail address. A. Introduction Sulfites for Oxygen Control Robert R. Cavano
Guidance Notes For Provision Of Water Expansion For 10 & 15 Litre Unvented Hot Water Heaters
Guidance Notes For Provision Of Water Expansion For 10 & 15 Litre Unvented Hot Water Heaters When water is heated, it naturally expands and allowance has to be made for this. Vented water heaters usually
