animeo KNX/EIB 4 DC/E Motor Controller WM V AC Installation manual
|
|
|
- Leon Dixon
- 9 years ago
- Views:
Transcription
1 somfy.com animeo KNX/EIB 4 DC/E Motor Controller WM V AC Installation manual Ref , SOMFY SAS. ALL RIGHTS RESERVED. REF /04/2008
2 Table of contents Introduction... 3 Definitions Slat position Screen position for DC Encoder Motors (LW 25 E83)... 5 Assembly... 6 Wiring Diagram Motor outputs Cabling Checking the running direction of the blinds Checking the turning direction of the slats... 8 Settings on delivery status Function of the Reset/Prog button Selection of different user ergonomics Mode selection DC or DCE Manual setting of the running and tilting times Manual setting of the intermediate position Reset to delivery status Communication objects Parameters Diagnosis LEDs on the animeo KNX/EIB Motor Controller Information during operation Status of configurations First diagnosis Technical Data m Before installation, please read the safety instructions carefully. Failure to respect these instructions automatically invalidates warranty and all liability claims against SOMFY (e.g. wrong installation, maloperation etc.). The product must be installed by a qualified electrician! All connections have to be disconnected from mains before mounting! Make precautions against switching on by accident! The installation of Somfy products has to be made at easily accessible places only. For maintenance and repairs which are difficult to perform because of bad accessibility (e.g. clotted or extensive clotted floors, installation behind lamps or behind façades) additional costs cannot be claimed against the seller. A proper functioning of the Motor Controllers and motors is assured only if the animeo DC or DC/E Motor Controllers are combined with compatible Somfy motors or with motors which are expressly approved by Somfy for this purpose. In case the buyer should use motors or DC power supplies made by other producers in combination with such made by Somfy, the warranty and responsibility of Somfy will be excluded both for the Somfy product itself and its suitability as part of a functioning system as a whole. The checking and decision whether external products are suitable without restraint is exclusively within buyer s own responsibility. animeo KNX/EIB 4 DC/E MoCo REF /45
3 1 Introduction The KNX 4 DC/E Motor Controller WM AC is for controlling motors in the Concept 25 motor series (24V DC). It is suited for the controlling of up to four individually parameterable motors for venetian blinds or roller blinds. This Motor Controller, thanks to its integrated current supply, enables low installation costs. In combination with the Concept 25 Encoder Motor and the CTS Roll-up System Motor it facilitates especially an exact positioning of the slats and an exact positioning of the venetian blinds. Additionally, the combination of the Motor Controller with the Concept 25 Encoder Motor offers the advantage of a longer life expectancy through protection of the venetian blinds. By using the animeo RTS radio module, four motors can be controlled via remote individually and per device. Functions and Advantages Time saving through easy-installation, for example, with spring clips, pull relief with cable binders, sufficient clip space Less wiring and space needed thanks to integrated current supply. A group input can be used to control all four motors independent of the ETS programming. Testing of running direction of the motors without ETS possible. The device can be used in the factory-delivered state without necessary programming via the ETS. The four local push button inputs can be used as maximum 8 universal KNX/EIB binary inputs, for example, to connect window contacts, temperature sensors, or occupancy detectors. Using a conventional push button, light actuators can also be controlled and dimmed. Via the dimming object, venetian blinds can also be turned slowly. User-friendly and intuitive parameter settings in the ETS software. Intelligent switching between manual and automatic operation to guarantee excellent user-friendliness and energy savings. Positioning messaging of the connected motors during the move and when reaching the upper and bottom end positions. Two free configurable security levels per motor output. Excess current and short circuit identifying with LED display and messaging via object for each individual motor. LED error display when the set operational speed is not reached. Free configurable action at mains power return. Automatic cascading of the motor outputs to limit the peak current in case of mains power return and bus safety functions. Plug and Play! At any time extendable with the animeo RTS Radio module. Without additional wiring the four motors, using Somfy RTS Technology, can be controlled individually per remote. In buildings where radio technology can not be used, such as in hospitals, radio control is also possible through animeo infrared technology. Special advantages when using the Encoder Motor Settable end position of the venetian blinds. Settable virtual upper end position to guarantee a visually, uniform façade. Separate settable UP and DOWN speeds to optimise noise levels. Settable slats tilting speeds. Longer life expectancy of the end product, e.g. venetian blinds, thanks to soft-stop function in the upper and bottom end positions. For exact positioning of the venetian blinds, the cycle for reference moves are freely definable per motor. Exactness of the venetian blinds orientation in combination with several encoder motors. High level of user comfort using the wheel on the Modulis RTS hand transmitter. animeo KNX/EIB 4 DC/E MoCo REF /45
4 2 Definitions All indications in the manual marked with * refers to the following terms: Manual order A manual order is a command generated by a local conventional switch or by a Somfy RTS radio hand transmitter. A telegram received on the objects 0-7 is also understood as manual command. Automatic order A telegram received on the objects 8-15 is understood as an automatic order. US switch ergonomics With this parameter it is specified that the venetian blind is headed in US ergonomics over the local switch inputs or over Somfy RTS radio hand transmitter. Short manipulation of the switch (< 0.5 s): A move command is executed. Long manipulation of the switch (> 0.5 s): A tilting command is executed as long as the switch is pressed. When releasing the switch the tilting command is stopped. If the current position of the venetian blind is outside the tilting time, a driving command is implemented with pressed button. EU switch ergonomics Screen switch ergonomics (roller blind) With this parameter it is specified that the venetian blind is headed in European Union ergonomics over the local switch inputs or over Somfy RTS radio hand transmitter. Short manipulation of the switch (< 0.5 s): A tilting step is implemented. Long manipulation of the switch (> 0.5 s): A tilting command is implemented as long as the switch is pressed. If the current position of the venetian blind is outside the tilting time, a driving command is executed. With this parameter it is specified that the end product is headed for screen (roller blinds) ergonomics over the local switch inputs or over Somfy RTS radio hand transmitter. Short manipulation of the switch when the end product is in full swing: A stop command is executed. Long manipulation when the end product is not in full swing: A driving command is executed. m This ergonomic is used to control screens, roller blinds, awnings and windows. DC Motors without encoder DC Motors with encoder Running time (mode selection DC) Tilting time (mode selection DC) Running length (mode selection DCE) Turn impulse (mode selection DCE) Reference move (mode selection DCE) DC Motors without encoder have a two-wire connecting cable (white, gray). DC Motors with encoder have a three-wire connecting cable (white, gray, purple). As running time, the time is defined that the corresponding end product needs from the upper end position to the bottom end position. The time for the UP move and for the DOWN move can be individually parametered. As tilting time, the time is defined necessary for the slats to make one complete turn. As running length, the length is defined that the corresponding end product needs from the upper end position to the bottom end position. The length for the UP move and for the DOWN move can be individually parametered. With turn impulse the time is defined necessary for a complete slats turn. A reference move is carried out with each 20th UP command after programming the end positions. Here, the venetian blinds move to the reference position (see 2.2). The frequency of the reference move is settable via the ETS. animeo KNX/EIB 4 DC/E MoCo REF /45
5 2.1 Slat position INSIDE OUTSIDE 2.2 Screen position for DC encoder motors (LW 25 E83) animeo KNX/EIB 4 DC/E MoCo REF /45
6 3 Assembly 63 mm min. 120 mm 140 mm Mounting of the Motor Controller 4 DC/E WM Connect power supply and wiring to the Motor Controller Bus > 10 cm Bus 4 Wiring diagram Encodermotor 1 LW25-E83 Encodermotor 2 LW25-E83 Encodermotor 3 LW25-E83 Encodermotor 4 LW25-E83 Motor 24 V DC (without Encoder) M purple M purple M purple M purple M LV 25 B44, B64 LW 25, B44, B83 LT 28 B73 L1 N PE mm 2 Junction box mm 2 Junction box mm 2 Junction box mm 2 Junction box alternatively mm 2 -mains 230 V 50 Hz L L N N 1 2 E M1 1 2 E M2 1 2 E M3 1 2 E M4 1 2 E Mx In 1-4 C Out 1-4 C SCR EU US Reset / Prog 1 A B C Somfy animeo KNX/EIB 4 DC/E Motor Controller WM C D C 3 E F C 4 G H C EIB LED EIB Prog Bus - + sw rt animeo RTS module MHz Group control C UP Down + UP Down + UP Down + UP Down + UP Down + red - black EIB-bus cable 2 x 2 x 0.8 mm 2 (green) Local push button Motor 1 Local push button Motor 2 Local push button Motor 3 Local push button Motor 4 Local push button inputs can be used as binary inputs! animeo KNX/EIB 4 DC/E MoCo REF /45
7 4.1 Motor outputs Max. current per output: 500 ma. Compatibel with the following Somfy motors in combination with the CTS 25 enrolling system for venetian blinds: LV 25-B44, -B64 DC-Mode 2 wires LW 25-B44, -B83 DC-Mode 2 wires LW 25-E83 DCE-Mode 3 wires LT 28-B73 DC-Mode 2 wires Stehle J wires m Control of non Somfy motors only on request 4.2 Cabling m As soon as 230 V and the EIB bus voltage supply are attached the US LED will blink regularly. The device is operational when the US LED is blinking continuously. CABLE Connections to... Cables Twisted Pairs Max. distance Motors Switches Group control Min.: 2 oder 3 x 0.6 mm 2 /19 AWG Max.: 2 oder 3 x 2.5 mm 2 /13 AWG Min.: 3 x 0.6 mm 2 /19 AWG Max.: 3 x 2.5 mm 2 /13 AWG Min.: 2 x 0.6 mm 2 /19 AWG Max.: 2 x 1.5 mm 2 /13 AWG Recommended Recommended EIB Bus 2 x 2 x 0.8 mm 2 Required, following KNX/EIB topology guidelines 230 V AC Min.: 3 x 0.75 mm 2 /16 AWG Max.: 3 x 2.5 mm 2 /13 AWG 20 m 150 m 1000 m 4.3 Checking the running direction of the blinds Group control of the motors 1-4 over the group control input Over the group control input the running directions of the connected motors can be tested. All four motor outputs are switched together. This input can become disabled in the ETS parameters. In the case of a bus voltage failure it is always enabled in order to make an emergency operation possible. m Absolutely guarantee with start-up that the motors run into the correct direction. By cable links at the group control input this test can be accomplished. Check the correct direction of the end product DOWN: The end product heads in the down direction (cable link between C + q) STOP: The end product stops (Cable link between C + q + p) UP: The end product heads in the up direction (C + p) animeo KNX/EIB 4 DC/E MoCo REF /45
8 4.4 Checking the turning direction of the slats Should the venetian blinds at the beginning of operation be moved down fully or partly, care must be taken when checking the turning direction for slats position (attention to manufacturer s instructions!). Should the slats position according to manufacturer s description not match to the move direction, only after first contacting the venetian blind manufacturer can the venetian blinds be corrected. Then, the turning direction can be checked. animeo KNX/EIB 4 DC/E MoCo REF /45
9 5 Settings on delivery status The KNX/EIB Motor Controller 4 DC/E can be used in the factory-delivered state also without programming via ETS software. Sensible presettings are implemented in the device. These settings are valid for all four motor outputs. l l Running and turning times/lengths* In the factory-delivered state or after setting back to the factory-delivered state, the pre-determined running and turning times/lengths* are already preset. Mode selection DCE A running length* of approx. 35 cm is preset. The turning impulses* are preset to 110 (suitable for 25 mm slats in combination with CTS winding system). The impulses for mechanical compensation are preset to 0,5 seconds. Mode selection DC A running time of 3 minutes and a turning time of 3 seconds are preset. The time for mechanical compensation is preset to 0,5 seconds. Connection of local push buttons possible The local press buttons inputs are assigned directly to the motor outputs: push button 1 controls motor output 1. Through wire bridges on the push button inputs, the motor outputs can be controlled as desired. * n See chapter 2 definitions 5.1 Function of the Reset/Prog button m Over this switch base settings at the Moco KNX/EIB can be made. These base settings are only possible in delivery status before the device is programmed with the ETS or after the device is unloaded by the ETS. The base settings are overwritten by the ETS settings. 5.2 Selection of different user ergonomics Over the Reset/Prog button different switch user ergonomics can be defined for the local switch inputs and/or Somfy RTS radio hand transmitters. These settings are only possible in delivery status before the device was programmed with the ETS or after the device became to unload by the ETS. As soon as the device was programmed with the ETS the user ergonomics can no more be made over the Reset/Prog button. If the device became to unload by the ETS, setting of the user ergonomics is again possible over the Reset/ Prog button. m The selection of the user ergonomics should be consistent with the appropriate end product. ))) = Configuration of the animeo RTS radio module SCR = Screen ergonomics* EU = Venetian blind, EU ergonomics* US = Venetian blind, US ergonomics* * see Chapter 2 Definitions Change the ergonomics: SCR EU US Reset / Prog Reset / Prog SCR EU US Reset / Prog Reset / Prog SCR EU US Reset / Prog SCR EU US Reset / Prog SCR EU US Reset / Prog Reset / Prog 2 s 2 s The delivery status is venetian blind with EU ergonomics. To switch between the different ergonomics press shortly the Reset/Prog button. Continue to do so until the desired LED is lighting. 2 s Save and exit of configuration to mode. animeo KNX/EIB 4 DC/E MoCo REF /45
10 5.3 Mode selection DC or DCE Type of motors that can be controlled (m Preset mode is DCE): DC DCE when a LW25-E3 motor is used it is identifiable by the three wires (white, grey, purple) 9s DC DCE SCR DC DCE 2s Reset / Prog DCE SCR Reset / Prog DC Reset / Prog US SCR Reset / Prog EU Reset / Prog SCR Reset / Prog ll Reset / Prog ll 2s The motor can be damaged through an unauthorised function mode! The mode for all four motor outputs are commonly defined! 5.4 Manual setting of the running and tilting times Over the local conventional switch and by radio hand transmitters the running and tilting times per motor output can be adjusted. These settings are only possible on delivery status before the device is programmed with the ETS. As soon as the device is programmed with the ETS, the running and tilting times cannot be programmed over the local conventional switches or by radio hand transmitters. If the device is unloaded by the ETS, it is again possible to program the running and tilting times over the local conventional switches or by radio hand transmitters. 0.5 s 0.5 s m Press immediately when lower end limit is reached. >6s m Keep Stop pressed during entire tilting. animeo KNX/EIB 4 DC/E MoCo REF /45
11 5.5 Manual setting of the intermediate position 1 Intermediate position 1 can also be programmed over a conventional local switch or by radio hand transmitters individually per motor output. At the same time it is possible to define the intermediate position 1 over settings in the ETS parameters. Before the intermediate position 1 is programmed it is obligatory to set the running and tilting times. m The last learned position is valid. 1 Move screen in desired position 2 Store position 1 > 2 s 0,5 s m With conventional unlocked push buttons the stop order can be generated by pressing the up and down button simultaneously m Whilst saving the screen tilts shortly up and down m The stored position will be moved m When using DCE motors (LW25-E83) a complete UP command must be executed after learning the running and tilting times (lengths) so that the according blind can find its upper reference point. 5.6 Reset to delivery status 1. If the device has not yet been programmed with the ETS software. SCR EU US Reset / Prog SCR EU US Reset / Prog SCR EU US Reset / Prog Complete RESET: The configurations realized over the Reset/Prog button, local conventional push buttons or radio transmitters can be reset over the Reset/Prog button by pressing 10 s. 14 s 2. If the device with the ETS software has already been programmed. If the device with the ETS has already been programmed, a reset to delivery status is not possible over the Reset/Prog button. Over the function Unload in the ETS all settings of the device can be reset to delivery status. The Reset/Prog button can then be used again. animeo KNX/EIB 4 DC/E MoCo REF /45
12 6 Communication objects A maximum of 109 communication objects are available, which however cannot be used at one time. Maximally 90 group addresses can be linked. No. Objekt name Type Description 0 1 Motor 1 UP/DOWN, CLOSE/OPEN Motor 2 UP/DOWN, CLOSE/OPEN 1 Bit (EIS 7) 1 Bit (EIS 7) If a telegram with the value 0 is received on this communication object, the appropriate blind goes up. If a telegram with the value 1 is received, the appropriate blind goes down. At expiration of 2 Motor 3 UP/DOWN, CLOSE/OPEN 1 Bit (EIS 7) the adjusted running time for the UP and DOWN direction the relays of the outputs are deactivated. 3 Motor 4 UP/DOWN, CLOSE/OPEN 1 Bit (EIS 7) 4 5 Motor 1 STEP / STOP Motor 2 STEP / STOP 1 Bit (EIS 7) 1 Bit (EIS 7) For venetian blinds: If the venetian blind is in a fully moving process, the venetian blind stops with the receipt of a telegram on the appropriate object, independently whether a telegram with the 6 Motor 3 STEP / STOP 1 Bit (EIS 7) value 0 or 1 is received. If the venetian blind is in passive state, a step will be executed whereas with the receipt of a telegram with 7 Motor 4 STEP / STOP 1 Bit (EIS 7) the value 1 the slat will close and with the receipt of a telegram with the value 0 the slat will open. The step length is defined in the parameter settings for the appropriate motor. For screens (roller blinds): If one of these end products is in a fully moving process, the end product stops with the receipt of a telegram on the appropriate object, indepen-dently of whether a telegram with the value 0 or 1 is received. If one of these end products is in passive state, then with the receipt of a telegram on one of these communication objects no action is executed. 8 9 Motor 1 Position UP / DOWN Motor 2 Position UP / DOWN 1 Byte (EIS 6) 1 Byte (EIS 6) If one of these communication objects receives a telegram, the appropriate blind will go into the position which is defined by the received value. 10 Motor 3 Position UP / DOWN 1 Byte (EIS 6) 0 = UP 255 = DOWN For venetian blinds: If the position is reached, the same slat angle starts up in which the venetian blind was previously. 11 Motor 4 Position UP / DOWN 1 Byte (EIS 6) Motor 1 Slat position Motor 2 Slat position 1 Byte (EIS 6) 1 Byte (EIS 6) For venetian blinds: If one of these communication objects receives a telegram, the appropriate slat will go to that position which is defined by the received value. If the venetian blind is in full moving 14 Motor 3 Slat position 1 Byte (EIS 6) process while receiving a telegram on the appropriate object, the position of the slat will be started up when the move is finished. 15 Motor 4 Slat position 1 Byte (EIS 6) Depending on the parameter setting on parameter card General the position is defined as follows: 255 = slat maximal closed / 0 = slat maximal reversed value (0/255) or 0 = slat maximal closed / 255 = slat maximal reversed value (255/0) Motor 1 Slow movement Motor 2 Slow movement 4 Bit (EIS 2) 4 Bit (EIS 2) When a telegram is received on one of these communication objects then the venetian blind slats move either slowly to maximal closed or maximal reversed position. The slats turning speed is para metered 18 Motor 3 Slow movement 4 Bit (EIS 2) on the card Motor 1 4. This function is fulfilled by a longer operating of a push button sensor, 19 Motor 4 Slow movement 4 Bit (EIS 2) application dimming. m These objects can also be controlled with conventional push buttons when local push button inputs of the Motor Controller are used as universal binary inputs (basis function dimming ). A time difference of 2 seconds between the receipt of a telegram on the objects 8-11 m and the receipt of a telegram on the objects should be respected. animeo KNX/EIB 4 DC/E MoCo REF /45
13 No. Objekt name Type Description Motor 1 Move to IP 1 Motor 2 Move to IP 1 1 Bit (EIS 1) 1 Bit (EIS 1) If a telegram with the value 1 is received on this communication object, the appropriate blind goes to the intermediate position 1 which was configured by local switch or by remote control or parameterised 22 Motor 3 Move to IP 1 1 Bit (EIS 1) in the ETS parameters. The last position which has been configured is active. Receiving a telegram with the value 0 on one 23 Motor 4 Move to IP 1 1 Bit (EIS 1) of these communication objects the appropriate blind goes to the upper end position. 24 Motor 1-4 Move to IP 1 1 Bit (EIS 1) If a telegram with the value 1 is received on this communication object, the blinds 1-4 go to the intermediate position 1 which was configured by local switch or by remote control and parameterised in the ETS parameters. The position which has been configured at last is active. Receiving a telegram with the value 0 on one of these communication objects the blinds 1-4 go to the upper end position Motor 1 Move to IP 2 Motor 2 Move to IP 2 1 Bit (EIS 1) 1 Bit (EIS 1) If a telegram with the value 1 is received on this communication object, the appropriate blind goes to the intermediate position 2 which was parameterised in the ETS parameters. Receiving a 27 Motor 3 Move to IP 2 1 Bit (EIS 1) telegram with the value 0 on one of these communication objects the blind goes to the upper end position. 28 Motor 4 Move to IP 2 1 Bit (EIS 1 29 Motor 1-4 Move to IP 2 1 Bit (EIS 1) If a telegram with the value 1 is received on this communication object, the blinds 1-4 go to the intermediate position 2 which was parameterised in the ETS parameters. Receiving a telegram with the value 0 on one these communication objects the blinds 1-4 go to the upper end position. 30 Motor 1-4 Reference Move 1 Bit (EIS 1) If a telegram with the value 1 or 0 is received on this communication object, a reference move will be generated for the Motors 1-4. m Explanation reference move see chapter 2 Definitions Motor 1 Security, low prio Motor 2 Security, low prio 1 Bit (EIS 1) 1 Bit (EIS 1) If a telegram with the value 1 is received on this communication object, the appropriate blind goes to the position which was parameterised in the ETS parameters. When one of the communication 33 Motor 3 Security, low prio 1 Bit (EIS 1) objects receives a telegram with value 0 no action will be executed. Only with the selection Repeat the last telegram after 34 Motor 4 Security, low prio 1 Bit (EIS 1) security (Yes) in the ETS parameters this action will be executed on the appropriate blind. If one of these communication objects is active through a telegram with the value 1 and if then on one of the communication objects (security position, high priority) a telegram with value 1 is received, the appropriate blind will move to the position configured in the ETS parameters (security position, high priority). 35 Motor 1-4 Security, low prio 1 Bit (EIS 1) If a telegram with the value 1 is received on this communication object, the blinds 1-4 go to the position which was parameterised in the ETS parameters. When the communication object receives a telegram with value 0 no action will be executed. Only with the selection Repeat the last telegram after security (Yes) in the ETS parameters this action will be executed on the blinds 1-4. If this communication object is active through a telegram with the value 1 and if then, on the communication object 35 (security position, high priority) a telegram with the value 1 is received the blinds 1-4 will move to the position configured in the ETS parameters (security position, high priority). animeo KNX/EIB 4 DC/E MoCo REF /45
14 No. Objekt name Type Description Motor 1 Security, high prio Motor 2 Security, high prio 1 Bit (EIS 1) 1 Bit (EIS 1) If a telegram with the value 1 is received on this communication object, the appropriate blind goes to the position which was parameterised in the ETS parameters. When one of the communication 38 Motor 3 Security, high prio 1 Bit (EIS 1) objects receives a telegram with value 0 no action will be executed. Only with the selection Repeat the last telegram after security 39 Motor 4 Security, high prio 1 Bit (EIS 1) (Yes) in the ETS parameters this will be executed in the appropriate blind. If an object for security position, low priority is active ( 1 ), the appropriate para-meterised position will be started up. 40 Motor 1-4 Security, high prio 1 Bit (EIS 1) If a telegram with the value 1 is received on this communication object, the blinds 1-4 go to the position which was parameterised in the ETS parameters. When the communication object receives a telegram with value 0 no action will be executed. Only with the selection Repeat the last telegram after security (Yes) in the ETS parameters this action will be executed in the blinds 1-4. If an object for security position, low priority is active ( 1 ) the appropriate parameterised position will be started up. 41 Mains power failure (230 V) 1 Bit (EIS 1) With this communication object a mains voltage failure can be signaled. As soon as the mains voltage precipitates a telegram with the value 1 it is sent to the bus. With mains voltage return this communication object sends a telegram with the value Motor 1 Error indication Motor 2 Error indication 1 Bit (EIS 1) 1 Bit (EIS 1) Over this communication object an error for the corresponding motor can be signalled. When an error occurs, a telegram with the value 1 is sent. When the error has been corrected, a telegram with the 44 Motor 3 Error indication 1 Bit (EIS 1) value 0 is sent. The following errors are identified: Short circuit on the motor output or at least a wire is not connected. 45 Motor 4 Error indication 1 Bit (EIS 1) Encoder wire (purple) is connected incorrectly on the motor output (e.g. M1 connector 1 or 2). A DCE motor is connected, the Motor Controller is however in the DC mode Motor 1 Feedback UP / DOWN Motor 2 Feedback UP / DOWN 1 Byte (EIS 6) 1 Byte (EIS 6) On these communication objects the current position (UP / DOWN direction) of the respective blind is sent to the bus based on the programmed running time. The type of feedback (on demand, 48 Motor 3 Feedback UP / DOWN 1 Byte (EIS 6) status change, cyclic) is defined in the ETS parameters. 0 = UP / 255 = DOWN 49 Motor 4 Feedback UP / DOWN 1 Byte (EIS 6) Motor 1 Feedback Slat Motor 2 Feedback Slat 1 Byte (EIS 6) 1 Byte (EIS 6) On these communication objects the current slat position of the respective blind is sent to the bus based on the programmed tilting time. The type of feedback is defined in the ETS parameters. Depending 52 Motor 3 Feedback Slat 1 Byte (EIS 6) on the parameter setting on parameter card General the position is defined as follows: 53 Motor 4 Feedback Slat 1 Byte (EIS 6) 255 = slat maximal closed / 0 = slat maximal reversed or 0 = slat maximal closed / 255 = slat maximal reversed 54 Motor 1-4 Status positions 1 Bit (EIS 1) On this communication object if a telegram with the value 1 or 0 is received, then the current status positions are sent on the bus (objects 46-53) Motor 1 Upper end position Motor 2 Upper end position 1 Bit (EIS 1) 1 Bit (EIS 1) Over these communication objects for the appropriate blind a telegram with the value 1 is sent if the upper end position is reached. When leaving the upper end position of the appropriate blind a 57 Motor 3 Upper end position 1 Bit (EIS 1) telegram with the value 0 is sent. The upper and the lower end position result from the parameterised running times. 58 Motor 4 Upper end position 1 Bit (EIS 1) animeo KNX/EIB 4 DC/E MoCo REF /45
15 No. Objekt name Type Description 59 Motor 1-4 Upper end position 1 Bit (EIS 1) Over this communication object for the blinds 1-4 a telegram with the value 1 is sent if all 4 blinds have reached the upper end position. If all 4 blinds have left the upper end position, a telegram with the value 0 is sent Motor 1 Lower end position Motor 2 Lower end position 1 Bit (EIS 1) 1 Bit (EIS 1) Over these communication objects for the appropriate blind a telegram with the value 1 is sent after the lower end position is reached. When leaving the lower end position of the appropriate 62 Motor 3 Lower end position 1 Bit (EIS 1) blind a telegram with the value 0 is sent. The upper and the lower end position result from the parameterised running times. 63 Motor 4 Lower end position 1 Bit (EIS 1) 64 Motor 1-4 Lower end position 1 Bit (EIS 1) Over this communication object for the blinds 1-4 a telegram with the value 1 is sent after all 4 blinds have reached the lower end position. After all 4 blinds have left the lower end position, a telegram with the value 0 is sent. The upper and the lower end position result from the parameterised running times Motor 1 Block functions Motor 2 Block functions 1 Bit (EIS 1) 1 Bit (EIS 1) If a telegram with the value 1 is received on one of these communication objects the functions which are selected in ETS parameters will be blocked for the appropriate blind. If on one of these 67 Motor 3 Block functions 1 Bit (EIS 1) communication objects a telegram with the value 0 is received the functions for the appropriate blind will be enabled again. 68 Motor 4 Block functions 1 Bit (EIS 1) 69 Motor 1-4 Block functions 1 Bit (EIS 1) If a telegram with the value 1 is received on this communication object the functions which are selected in ETS parameters will be blocked for the blinds 1-4. If on this communication object a telegram with the value 0 is received the functions for the blind 1-4 will be enabled again Motor 1 Prio automatic/manual Motor 2 Prio automatic/manual 1 Bit (EIS 1) 1 Bit (EIS 1) Over these communication objects priority between automatic functions and manual functions can be switched. If on one of these communication objects a telegram with the value 1 is received 72 Motor 3 Prio automatic/manual 1 Bit (EIS 1) priority automatic functions is active for the appropriate blind. If on one of these communication objects a telegram with the value 0 73 Motor 4 Prio automatic/manual 1 Bit (EIS 1) is received priority manual functions are active for the appropriate blind Motor 1 Reset priority Motor 2 Reset priority 1 Bit (EIS 1) 1 Bit (EIS 1) If on one of these communication objects a telegram with the value 1 or 0 is received the appropriate priority for the appropriate blind is reset. Priority automatic functions or priority manual functions 76 Motor 3 Reset priority 1 Bit (EIS 1) are then again actively switched. The active priority depends on which communication object is active and/or which priority has been selected in the ETS parameters. 77 Motor 4 Reset priority 1 Bit (EIS 1) 78 Input 1: UP / DOWN 1 Bit (EIS 1) A long pressing of the switch at the input A generates a telegram with the value 0 on this communication object. The venetian blind goes UP. A long pressing of the switch at the input B generates a telegram with the value 1 on this communication object. The venetian blind goes DOWN. animeo KNX/EIB 4 DC/E MoCo REF /45
16 No. Objekt name Type Description 79 Input 1: Step/Stop 1 Bit (EIS 1) A short pressing of the switch at the input A generates a telegram with the value 0 on this communication object. The slat will tilt to reverse (open). If the venetian blind is in the fully moving process with a short pressing of the switch at the input A, a stop order is generated. A short pressing of the switch at the input B generates a telegram with the value 1 on this communication object. The slat will tilt to close. If the venetian blind is in a fully moving process with a short pressing of the switch at the input B a stop order is generated. 80 Input 1: A, Switch 1 Bit (EIS 1) According to the parameter settings and the state at input 1, contact A, over this communication object a switching telegram with the value 1 or 0 is generated. 81 Input 1: B, Switch 1 Bit (EIS 1) According to the parameter settings and the state at input 1, contact B, over this communication object a switching telegram with the value 1 or 0 is generated. 82 Input 1: A, 8-Bit value 1 Bit (EIS 6) According to the parameter settings with a rising edge at the input 1, contact A, the configured value (0-255) is sent. 83 Input 1: B, 8-Bit value 1 Bit (EIS 6) According to the parameter configurations with a rising edge at the input 1, contact B, the configured value (0-255) is sent. 84 Input 1: A/B, Dimming 1 Bit (EIS 2) On/Off: According to the parameter settings of the input 1 contact A/B with a short actuation a telegram with the value 1 and/or 0 will be generated. Toggle/Toggle: According to the parameter settings of the input 1 contact A/B with a short actuation a telegram with the value 1 and/or 0 is generated. 85 Input 1: A/B, Dimming, Value 4 Bit (EIS 2) Brighter/darker dimming: According to the parameter settings of the input 1 contact A with a long actuation it is dimmed brighter. According to the parameter settings of the input 1 contact B with a long actuation it is dimmed darker. Brighter/darker toggle: According to the parameter settings of the input 1 contact A with a long actuation it is dimmed 100 %. When releasing the appropriate switch at the input A a stop order is generated. The dimming action operated last is thus inverted. According to the parameter settings of the input 1 contact B with a long actuation it is dimmed 100 %. When releasing the appropriate switch at the input B a stop order is generated. The dimming action operated last is thus inverted. animeo KNX/EIB 4 DC/E MoCo REF /45
17 No. Objekt name Type Description 86 Input 2: UP / DOWN 1 Bit (EIS 7) see description of object 69, C/D instead of A/B 87 Input 2: Step/Stop 1 Bit (EIS 7) see description of object 70, C/D instead of A/B 88 Input 2: C, Switch 1 Bit (EIS 1) see description of object 71, C instead of A 89 Input 2: D, Switch 1 Bit (EIS 1) see description of object 72, D instead of B 90 Input 2: C, 8-Bit-value 1 Byte (EIS 6) see description of object 73, C instead of A 91 Input 2: D, 8-Bit-value 1 Byte (EIS 6) see description of object 74, D instead of B 92 Input 2: C/D, Dimming 1 Bit (EIS 2) see description of object 75, C/D instead of A/B 93 Input 2: C/D, Dimming, value 4 Bit (EIS 2) see description of object 76, C/D instead of A/B 94 Input 3: UP / DOWN 1 Bit (EIS 7) see description of object 69, E/F instead of A/B 95 Input 3: Step/Stop 1 Bit (EIS 7) see description of object 70, E/F instead of A/B 96 Input 3: E, Switch 1 Bit (EIS 1) see description of object 71, E instead of A 97 Input 3: F, Switch 1 Bit (EIS 1) see description of object 72, F instead of B 98 Input 3: E, 8-Bit value 1 Byte (EIS 6) see description of object 73, E instead of A 99 Input 3: F, 8-Bit value 1 Byte (EIS 6) see description of object 74, F instead of B 100 Input 3: E/F, Dimming 1 Bit (EIS 2) see description of object 75, E/F instead of A/B 101 Input 3: E/F, Dimming, value 4 Bit (EIS 2) see description of object 76, E/F instead of A/B 102 Input 4: UP / DOWN 1 Bit (EIS 7) see description of object 69, G/H instead of A/B 103 Input 4: Step/Stop 1 Bit (EIS 7) see description of object 70, G/H instead of A/B 104 Input 4: G, Switch 1 Bit (EIS 1) see description of object 71, G instead of A 105 Input 4: H, Switch 1 Bit (EIS 1) see description of object 72, H instead of B 106 Input 4: G, 8-Bit value 1 Byte (EIS 6) see description of object 73, G instead of A 107 Input 4: H, 8-Bit value 1 Byte (EIS 6) see description of object 74, H instead of B 108 Input 4: G/H, Dimming 1 Bit (EIS 2) see description of object 75, G/H instead of A/B 109 Input 4: G/H, Dimming, value 4 Bit (EIS 2) see description of object 76, G/H instead of A/B animeo KNX/EIB 4 DC/E MoCo REF /45
18 7 Parameters The options of the individual parameters are described in each case. The default values are shown in italic. In the following illustrations of the different parameter cards a maximum of parameters is always presented. Parameter card General Selection of the motor type DC without encoder DC with encoder Over the parameters it is defined which motors are to be connected to the motor outputs. DC motors without encoder have a two-wire connecting cable (white, gray). DC motors with encoder have a three-wire connecting cable (white, grey, purple). DC motors without encoder: Somfy LV 25-B44 and B64, Somfy LW 25-B44 and B83, Somfy LT 28-B73, J101 DC motors with encoder: Somfy LW 25-E83 m The selection of the motor type applies to all four motor outputs. Connecting of the motor outputs Over this parameter, the motor outputs can be connected to each other device-internally. A connection is then necessary when for example, two motors are used to control a screen. This means that two motors are integrated into one Din rail and move one motor. Independent of the type of connection, or 2+2, all motor cables must be connected to the motor outputs. To control the motor outputs, only the object and parameter of one motor must be parametered. For example when connecting only the object for motor 1.. animeo KNX/EIB 4 DC/E MoCo REF /45
19 Motor output configuration Combined Individual With these parameters it can be specified whether the configurations of the motor outputs are to be done Combined or Individual. If the parameter Combined is selected for the basic settings of all four motor outputs, only one parameter card will be visible (Motor 1-4). m This setting ( Combined ) is recommendable for projects where the configurations of the motor outputs are equal. If the parameter Individual is selected for the basic settings of the motor outputs four individual cards will be visible (Motor 1, Motor 2, ). Slat position closed/reversed ONLY FOR VENETIAN BLINDS Max. closed (255) / Max. reversed (0) Max. closed (0) / Max. reversed (255) l l Max. closed (255) / Max. reversed (0) If a value of 255 is received by the appropriate object (12-15) the slat will be maximal closed. If a value of 0 is received by the appropriate object (12-15) the slat will be maximal reversed (opened). Max. closed (0) / Max. reversed (255) If a value of 0 is received by the appropriate object (12-15) the slat will be maximal closed. If a value of 255 is received by the appropriate object (12-15) the slat will be maximal reversed (opened). Value (0/255) Value (255/0) Motor 1 4 Automatic/Manuell Functions None Priority automatic functions Priority manual functions l None: The moving commands are processed in detailed order. Priority automatic function: If an automatic command (1 Byte move command) takes place before a manual command (1 Bit move command), all manual commands are disabled. Also the objects to move to the intermediate positions 1 and 2 (objects 20-29) are disabled. A manual command is generated also over the local switch inputs or the radio hand transmitter. A tilting command (1 Bit) can however, always be executed within the configured tilting time. A reset of the priority automatic function is effected if on the appropriate objects Reset priority (74-77) a telegram with the value 1 or 0 is received. Switching between priority manual functions (value 0 ) and priority automatic functions (value 1 ) is made by the appropriate objects (70-73). Following adjust-over, the appropriate priority is active again in the reset state. This means for priority automatic functions that the manual commands become again disabled only through the next automatic command. Priority manual function: If a manual command (1 Bit) takes place before an automatic command (1 Byte), all automatic commands are disabled. A manual command is generated also over the local switch inputs or the radio hand transmitter. A reset of the priority manual functions is effected if a telegram with the value 1 or 0 is received on the appropriate object Reset priority (74-77). Switching between priority manual functions (value 0 ) and priority automatic functions (value 1 ) is made by the appropriate objects (70-73). Following adjust-over, the appropriate priority is active again in the reset state. This means for functions priority manual that the automatic commands become again disabled only through the next manual command. m See explanations in chapter 2. animeo KNX/EIB 4 DC/E MoCo REF /45
20 l m Over the priority manual functions the user has the possibility to disable the automatic functions. For example, over a timer the user comfort can be defined. At 8:00 o clock over the appropriate object (70-73) the priority manual functions are activated and the user can move the end product to a desired position with the next manual command. At 5:00 o clock the priority automatic function is again activated. Over the appropriate object (70-73) it is always possible to switch between priority manual functions and priority automatic functions. To use timer functions it is ideal to use the central unit AS 315 N (Ref ). Universal binary inputs use No Yes With the parameter Yes four further parameter cards (binary input 1 4) are opened. The local switch inputs can be linked now over the appropriate objects (78-109). A conventional switch can be used thus for most diverse functions. For example switching, venetian blind function, dimming or sending values. Group control input disabled enabled Over this parameter it can be specified whether the group control input is disabled or enabled. Over this input all four motors are moved at the same time. Independently of the parameter configurations the security configurations (objects 31-40) have higher priority. If one of the security objects is active the group control input is disabled. m With bus voltage failure this input is enabled even if it is disabled over the parameter configurations and can be used for an emergency operation. With bus power return this input is disabled or enabled according to the parameter configurations. animeo KNX/EIB 4 DC/E MoCo REF /45
21 Parameter card Motor 1...4, with encoder/motor 1-4, with encoder Four individual parameter cards (Motor 1 4) are visible when on the card General for the basic setting of the motor to individual, is parametered. An individual card (Motor 1 4) is visible when on the card General for the basic setting of the motor to Combined, is parametered. m The basic setting of the motors are different independent of the selection of the motor type (DC without encoder or DC with encoder on the card General ). The following parameter descriptions concern the selection of the motor type DC with encoder : Type of end product/ User ergonomics Venetian blind with EU ergonomics Venetian blind with US ergonomics Roller blind l l Venetian blind with EU ergonomics With this parameter it is specified that the venetian blind is in EU ergonomics over the local switch inputs or over Somfy RTS radio hand transmitter. If the local switch inputs are used as universal binary inputs, the control ergonomics is defined over the appropriate parameters (short/long depressing the button). n See explanation EU, US, screen switch ergonomics in chapter 2. Venetian blind with US ergonomics Over this parameter it is specified that the venetian blind is in US ergonomics over the local switch inputs or over Somfy RTS radio hand transmitter. If the local switch inputs are used as universal binary inputs, the control ergonomics is defined over the appropriate parameters (short/long depressing of the button). n See explanation EU, US, screen switch ergonomics in chapter 2. l Roller blind Over this parameter it is specified that the appropriate blind is directed for move/stop commands, if the control is made by means of the local switch inputs or by Somfy RTS radio hand transmitter. If the local switch inputs are used as universal binary inputs, the control ergonomics is defined over the appropriate parameters (short/long depressing of the button). n See explanation EU, US, screen switch ergonomics in chapter 2. animeo KNX/EIB 4 DC/E MoCo REF /45
22 Upper end limit in mm (0-5000) millimetres The parametered lengths in millimetres defines the upper end position of the blinds. n Explanation; see chapter 2, blinds position for DC motors with encoder (LW 25 E83) Lower end limit in mm (0-5000) millimetres The parametered lengths in millimetres defines the bottom end position of the blinds. n Explanation; see chapter 2, blinds positions for DC motors with encoder (LW 25 E83) Speed UP in RPM (25-56) The parametered speed defines the speed for the move in the upper end position. Speed DOWN in -RPM (25-56) The parametered speed defines the speed for the move in the bottom end position. Impulses for tilting The parametered impulses here define the maximum slat turn. This parameter is only visible when the type of product/user ergonomics, either venetian blinds with EU ergonomics or venetian blinds with US ergonomics, is selected. n Setting recommendation: with a slats width of 25 mm = approx. 110 impulses for the turn. With a slats width of 16 mm = approx. 90 impulses for the turn. Step impulses (3-255) The parametered impulses define the impulses for a turning step. This parameter is only visible when the type of product/user ergonomics, either venetian blinds with EU ergonomics or venetian blinds with US ergonomics, is selected. Speed tilting in RPM (5-56) The parametered speed here defines the slats turning speed. This parameter is only visible when the type of product/user ergonomics, either venetian blinds with EU ergonomics or venetian blinds with US ergonomics, is selected. animeo KNX/EIB 4 DC/E MoCo REF /45
23 Impulses for slack compensation Basis 0,05 s (0-255) The parametered impulses here define the impulses that shall be added for the turn to balance out mechanical tolerances. This parameter is only visible when the type of product/user ergonomics, either venetian blinds with EU ergonomics or venetian blinds with US ergonomics, is selected. Parameter card Motor 1...4/Motor 1-4 Four individual parameter cards (Motor 1 4) are visible when on the card General for the basic setting of the motor to Individual, is parametered. An individual card (Motor 1 4) is visible when on the card General for the basic setting of the motor to Combined, is parametered. m The basic setting of the motors are different independent of the selection of the motor type (DC without encoder or DC with encoder on the card General. The following parameter descriptions concern the selection of the motor type DC without encoder : Type of end product/ user ergonomics Venetian blind with EU ergonomics Venetian blind with US ergonomics Roller blind l Venetian blind with EU ergonomics: With this parameter it is specified that the venetian blind is in EU ergonomics over the local switch inputs or over Somfy RTS radio hand transmitter.if the local switch inputs are used as universal binary inputs, the control ergonomics is defined over the appropriate parameters (short/long depressing the button). n See explanation EU, US, screen switch ergonomics in chapter 2. Venetian blind with US ergonomics Over this parameter it is specified that the venetian blind is in US ergonomics over the local switch inputs or over Somfy RTS radio hand transmitter.if the local switch inputs are used as universal binary inputs, the control ergonomics is defined over the appropriate parameters (short/long depressing of the button). n See explanation EU, US, screen switch ergonomics in chapter 2. animeo KNX/EIB 4 DC/E MoCo REF /45
24 l Roller blind Over this parameter it is specified that the appropriate blind is directed for move/stop commands, if the control is made by means of the local switch inputs or by Somfy RTS radio hand transmitter. If the local switch inputs are used as universal binary inputs, the control ergonomics is defined over the appropriate parameters (short/long depressing of the button). m See explanation EU, US, screen switch ergonomics in chapter 2. Running time UP (1-320 s) seconds The configured time here is the maximum running time from the lower end position to the upper end position and/or the maximum running time that one window motor needs in order to close the appropriate window. An overlapping time of 5 seconds is always added except in case of positioning telegrams (objects 8-11). However, if a telegram with the value 0 is received by the appropriate object (objects 8-11) an overlapping time of 5 seconds is added. Running time DOWN (1-320 s) seconds The configured time here is the maximum running time from the upper end position into the lower end position, and/or the maximum running time a particular window motor needs, in order to open the appropriate window. An overlapping time of 5 seconds is always added except in the case of positioning telegrams (objects 8-11). However, if a telegram with the value 255 is received by the appropriate object (objects 8-11) an overlapping time of 5 seconds is added. Complete tilting time Basis 0,01 s (0-100) The configured time here defines the complete tilting time of the slat. This parameter is visible only if as type of end product either venetian blind with EU ergonomics or venetian blind with US ergonomics were selected. Step length Basis 0,01 s (3-255) The confiured time here defines the time for a tilting step. This parameter is visible only if as type of end product either venetian blind with EU ergonomics or venetian blind with US ergonomics were selected. Turning speed (0-100 %) This parameter defines the speed the venetian blinds slats should turn. Here, by selecting the value 0 the slowest turning speed is defined and with the selection 100, the fastest turning speed. Slack compensation 0,05 s (0-100) The time for slack compensation is active as soon as a higher value than 0 is registered. The time configured here defines the time to add to the complete tilting time in order to adjust mechanical tolerances. This time is always added with the first UP (reverse/open) command of the slat if as type of end product either venetian blind with EU ergonomics or venetian blind with US ergonomics were selected. animeo KNX/EIB 4 DC/E MoCo REF /45
25 Tension relief when reaching the upper end limit No Yes m With this parameter it is possible to extend the life of the end product (venetian blinds). By selecting Yes the venetian blinds are relieved when reaching the upper end position. This means shortly after reaching, a minimal DOWN command is generated. This results in the venetian blinds not being under strain whilst standing in the upper end position. By relieving the pull cord, it is thus not unnecessarily stressed and life expectancy is extended. Automatic slat shake No Yes When the parameter Yes is selected, an automatic slat shake is carried out when reaching the bottom end limit. Here, the slats are one time completely opened and closed. m Through this function it is possible also to set up the slats automatically. It can happen that in a DOWN command some of the slats whilst turning get entangled and therefore do not stand in the mechanical default position. Through completely opening and closing the slats, the entangled slats are brought into the mechanical default position. Parameter card Functions Motor / Functions Motor 1-4 Four individual parameter cards (Functions Motor 1...4) become visible if on the parameter card General the basic adjustment of the motors is set to Individual. Only one parameter card (Functions Motor 1-4) becomes visible, if on the parameter card General the basic adjustment of the motors is set to Combined. m The parameters which become visible on this parameter card are independent of the selection of the motor type (DC without Encoder or DC with Encoder) on the parameter card General. The parameters for the setting of functions are identical for both motor types. animeo KNX/EIB 4 DC/E MoCo REF /45
26 Intermediate position 1 UP / DOWN position (0-100 %) With this parameter the intermediate position 1 UP / DOWN is defined. The adusted value in % refers to the configured running time of the appropriate venetian blind of the parameter cards Motor 1 4/Motor 1-4. Slat position (0-100 %) 100 % With this parameter the slat position of the intermediate position 1 is defined. The adjusted value in % refers to the configured complete tilting time of the appropriate venetian blind of the parameter cards Motor 1 4/Motor % m Intermediate position 1 can be stored also over the conventional local switch or individually by radio hand transmitters per motor output. The position learned last is valid. Intermediate position 2 UP / DOWN Position (0-100 %) With this parameter the intermediate position 2 UP / DOWN is defined. The adjusted value in % refers to the configured running time of the appropriate blinds of the parameter cards Motor 1 4/Motor 1-4. Slat position (0-100 %) 100 % With this parameter the slat position of the intermediate position 3 is defined. The adjusted value in % refers to the configured complete tilting time of the appropriate venetian blind of the parameter cards Motor 1 4/Motor % Block UP / DOWN orders (1 Byte) No Yes Over this parameter the move orders (Byte) can be blocked by object (65-69). If the appropriate object receives a telegram with the value 1 during a blind is in full moving process, this action will first be executed completely. Only then, further move commands (Byte) are blocked. If the appropriate object receives a telegram with the value 0 the move orders (Byte) are again enabled. Block slat orders (1 Byte und 4 Bit) No Yes Over this parameter the slat tilting orders (1 Byte und 4 Bit) can be blocked by object (65-69). If the appropriate object receives a telegram with the value 1 when the slats of a venetian blind are in full moving process, this action will first be executed completeley. Only then, further tilting orders (1 Byte und 4 Bit) are closed. If the appropriate object receives a telegram with the value 0 the slat tilting orders (1 Byte und 4 Bit) are enabled. animeo KNX/EIB 4 DC/E MoCo REF /45
27 Block UP / DOWN orders (1 Bit) No Yes Over this parameter the move orders (1 Bit) can be blocked by object (56-60). If the appropriate object receives a telegram with the value 1 when a blind is in full moving process, this action will first be executed completely. Only then, further move orders (1 Bit) are blocked. If the appropriate object receives a telegram with the value 0, move orders (1 Bit) are again enabled. Block step/stop orders (1 Bit) No Yes Over this parameter the step/stop and/or tilting order (1 Bit) can be blocked by object (56-60). If the appropriate object receives a telegram with the value 1 when the slat of a venetian blind is tilting this action will first be executed completely. Only then, further tilting orders (1 Bit) are blocked. If the appropriate object receives a telegram with the value 0, step/stop orders (1 Bit) are again enabled. Block local push button inputs and Somfy RTS orders No Yes Over this parameter the local push button inputs and the Somfy RTS radio orders can be blocked by object (56-60). If the appropriate object receives a telegram with the value 1 when an end product is in full moving process, this action will first be executed completely. Only then, further commands over the local push button inputs and the Somfy RTS radio will be blocked. If the appropriate object receives a telegram with the value 0 the local push button inputs and the Somfy RTS radio orders are again enabled. Repeat last telegram after security No Yes If this parameter is set on Yes the last move command after security is repeated. This means, the according blind will move to the position at which it was previously before on one of the security objects, low or high security, a telegram with the value 1 was received. animeo KNX/EIB 4 DC/E MoCo REF /45
28 Parameter card Binary input General information For each binary input four different basic functions are available: Venetian blind UP / DOWN Switch/dry contact 8-Bit value (rising edge) Dimming The individual functions and parameters depend on the selection of the basic function and are now described. The four different possibilities are described using screenshots of the binary input 1, contact A/B and are identical for the binary inputs 2-4, contacts C/D, E/F and G/H. The default setting of the basic function for the parameter cards binary input 1 4 is venetian blind, UP / DOWN. m When the basic function Venetian blind, UP / DOWN is selected please be certain about which contact controls the UP order and which contact controls the DOWN order. The same attention is necessary when the basic function Dimming is selected. Please be certain about which contact controls dimming brighter and which contact controls dimming darker. Basis function Venetian blind UP / DOWN Switch/dry contact 8-Bit value (rising edge) Dimming Long operating (move) after 0,5 seconds 0,3...5,0 seconds This parameter defines the operating time of the appropriate switch, which differentiates between sending a short-term telegram (step/stop) and a long-term telegram (UP / DOWN motor). If the time is, for example, set to 0,5 seconds, only with a duration of application which is generated longer than 0,5 seconds, a long-term telegram will be executed. With duration of an application which is smaller than 0,5 seconds a short-term telegram is generated. animeo KNX/EIB 4 DC/E MoCo REF /45
29 Contact type input A Normally closed Normally open Specified over this parameter is the contact type at the local input A. Normally open contact: The contact at the local input is not operated open and operated closed. Normally closed contact: The contact at the local input is operated opened and not operated closed. Contact type input B Normally closed Normally open Specified over this parameter is the contact type at the local input B. Normally open contact: The contact at the local input is not operated open and operated closed. Normally closed contact: The contact at the local input is operated opened and not operated closed. Parameter card Binary input 1 Basis function Venetian blind UP / DOWN Switch/dry contact 8-Bit value (rising edge) Dimming Edge evaluation contact A Rising ON, falling OFF Rising OFF, falling ON Rising ON Falling ON Rising OFF Falling OFF Rising toggle Falling toggle Rising toggle, falling toggle No evaluation On ( 1 ) Off ( 0 ) Toggle ( 1/0 ) Depending on which edge evaluation was selected the appropriate object value 0 or 1 will be generated. animeo KNX/EIB 4 DC/E MoCo REF /45
30 Rising ON, falling OFF If a rising edge at the local input appears, the object value OFF is produced. If a falling edge at the local input appears, the object value ON is produced. The duration of the manipulation is not evaluated. Rising OFF, falling ON If a rising edge at the local input appears, the object value ON is produced. If a falling edge at the local input appears, this is not evaluated. The duration of the manipulation is not evaluated. Rising ON If a falling edge at the local input appears, the object value ON is produced. If a rising edge at the local input appears, this is not evaluated. The duration of the manipulation is not evaluated. Falling ON If a falling edge at the local input appears, the object value ON is produced. If a rising edge at the local input appears, this is not evaluated. The duration of the manipulation is not evaluated. Rising OFF If a rising edge at the local input appears, the object value OFF is produced. If a falling edge at the local input appears, this is not evaluated. The duration of the manipulation is not evaluated. Falling OFF If a falling edge at the local input appears, the object value OFF is produced. If a rising edge at the local input appears, this is not evaluated. The duration of the manipulation is not evaluated. Rising toggle If a rising edge at the local input appears, the object value is inverted. If a falling edge at the local input appears, this is not evaluated. The duration of the manipulation is not evaluated. Falling toggle If a falling edge at the local input appears, the object value is inverted. If a rising edge at the local input appears, this is not evaluated. The duration of the manipulation is not evaluated. Rising toggle, fallling toggle If a rising or falling edge at the local input appears, the object value is inverted. The duration of the manipulation is not evaluated. No evaluation If a rising or falling edge at the local input appears, this is not evaluated. Edge contakt B Rising ON, falling OFF Rising OFF, falling ON Rising ON Falling ON Rising OFF Falling OFF Rising toggle Falling toggle Rising toggle, falling toggle No evaluation Description see Edge evaluation contact A Send starting value on bus power return Yes No If this parameter is set to Yes with bus power return the current status of the input is then sent. If this parameter is set to No the current adjusted status of the input is not sent. animeo KNX/EIB 4 DC/E MoCo REF /45
31 Contact A und B Cycling sending of status No cyclic sending On Off On and off Over this parameter it is specified whether the appropriate switching value of the communication object is to be sent cyclically. No cyclic sending The switching value of the communication object is not cyclically sent. On Only if the object value is 1 it is cyclically sent. If the object value changes due to a change of edge status at the input or due to a receipt of a Bus telegram from 0 to 1, the cyclic sending is stopped. Off Only if the object value is 0 it is cyclically sent. If the object value changes due to a change of edge status at the input or due to a receipt of a Bus telegram from 1 to 0, the cyclic sending is stopped. On and Off If the object value is 1 or 0 then the appropriate one is cyclically sent. If the object value changes due to a change of edge status at the input or due to a receipt, a bus telegram of the new value is sent. Cyclic sending in seconds (1-3600) Over this parameter the time intervals are fixed in which the appropriate object value is sent cyclically. m With active cyclic sending it is to be made certain that the time of the cyclic time received is greater approx. 1/4 than the configured cyclic time of the sender. animeo KNX/EIB 4 DC/E MoCo REF /45
32 Parameter card Binary input 1 Basis function Venetian blind UP / DOWN Switch/dry contact 8-Bit value (rising edge) Dimming Contact A Value on rising edge (0-255) Over this parameter the value is adjusted which is sent with receipt of a rising edge at the local input 1 contact A. Contact type input A Normally closed Normally open Specified over this parameter is the contact type at the local input A. Normally open contact: The contact at the local input is not operated open and operated closed. Normally closed contact: The contact at the local input is operated opened and not operated closed. Contact B Value on rising edge (0-255) Over this parameter the value is adjusted which is sent with receipt of a rising edge at the local input 1 contact B. Contact type input B Normally closed Normally open Specified over this parameter is the contact type at the local input B. Normally open contact: The contact at the local input is not operated open and operated closed. Normally closed contact: The contact at the local input is operated opened and not operated closed. animeo KNX/EIB 4 DC/E MoCo REF /45
33 Parameter card Binary input 1 Basis function Venetian blind UP / DOWN Switch/dry contact 8-Bit value (rising edge) Dimming Long operation (dimming) after 0,5 seconds 0,3-5,0 seconds This parameter defines the operating time of the appropriate switch, which differentiates between sending a switching telegram and a dimming telegram. If the time is, for example, set at 0,5 seconds, only with duration of an application which is longer than 0,5 seconds a dimming telegram is generated. With duration of application which is smaller than 0,5 seconds, a switching telegram is generated. Input A/B On/Off Toggle/toggle On ( 1 ) Off ( 0 ) Toggle ( 1/0 ) This parameter defines the value which is sent with short manipulation of the appropriate input. On/Off With a short manipulation of the switch at the input A an Off telegram is generated. With a short manipulation of the switch at the input B an On telegram is generated. These functions can be inverted by changing the wiring. Toggle/toggle With every short manipulation of the switch at the input A or B, toggling occurs. This means the value that is in the appropriate switching object is inverted and then sent. Contact type input A Normally closed Normally open Specified over this parameter is the contact type at the local input A. Normally open contact: The contact at the local input is not operated open and operated closed. Normally closed contact: The contact at the local input is operated opened and not operated closed. animeo KNX/EIB 4 DC/E MoCo REF /45
34 Contact type input B Normally closed Normally open Specified over this parameter is the contact type at the local input B. Normally open contact: The contact at the local input is not operated open and operated closed. Normally closed contact: The contact at the local input is operated opened and not operated closed. Dimming with Stop telegram Cyclic intervals Stop telegram With a short manipulation of the switch at the local input 1 contact A or B a telegram is generated over the appropriate object (1 Bit). With a long manipulation of the switch at the local input A brightness is dimmed further over the appropriate object (4 Bit). With a long manipulation of the switch at the local input B over the appropriate object (4 Bit) more darkness is dimmed. When releasing the appropriate switch at the local input 1 contact A or B, a stop command is generated. Cyclic intervals With a short manipulation of the switch at the local input 1 contact A or B over the object (1 Bit) an On or Off telegram is generated. With a long manipulation of the switch at the local input 1 contact A over the object (4 Bit) more brightly is being dimmed as long as the switch is depressed. The dimming step width and the time for more brightness dimming, results out of the parameters Long operation (dimming) and Interval for cyclic dimming. When the switch is released the cyclic sending is stopped. With a long manipulation of the switch at the local input 1 contact B over the appropriate object (4 Bit) more darkness is dimmed as long as the switch is depressed. The dimming step width and the time for more darkness dimming results out of the parameters Long operation (dimming) and Interval for cyclic dimming. When the switch is released the cyclic sending is stopped. Long operation (dimming) Adjust by 100 % Adjust by 1/2 Adjust by 1/4 Adjust by 1/8 Adjust by 1/16 Adjust by 1/32 Adjust by 1/64 This parameter defines the dimming step width of the telegrams after a long manipulation of the switch at the according input. m If Dimming with cyclic sending is selected in the parameters, it is to made certain, that the dimming step width is configured together with the parameter Interval for cyclic dimming depending on the dimming time of the according actuator. Interval for cycling dimming 0,5 seconds 0,5-7,0 seconds This parameter defines the length of time of an interval for cyclic sending. Example: the dimming time (0-100%) in the according switch/ dimming actuator is set to 4 seconds, and Adjust by 1/8 with an Interval for cyclic dimming 0,5 seconds is selected. The result is that a dimming command brighter or darker is sent every 0,5 seconds. With a configuration of 8 x 12,5 % and 8 x 0,5 seconds, this matches the dimming speed of the switch/dimming actuator. animeo KNX/EIB 4 DC/E MoCo REF /45
35 Parameter card General: Binary input These parameters concern binary inputs Start-up delay 0 seconds 0-21 seconds This parameter defines the time after bus power return which runs off before the first telegram can be sent. Limit number of telegrams No Yes If this parameter is set on Yes it opens the parameter Limit for adjusting the limit of telegrams. Limit 30 telegrams per 17 sec. 60 telegrams per 17 sec. 100 telegrams per 17 sec. 127 telegrams per 17 sec. This parameter defines the number of telegrams to be sent within 17 seconds. animeo KNX/EIB 4 DC/E MoCo REF /45
36 Parameter card Bus safety On this parameter card the reaction can be defined for bus power failure and bus power return of each individual motor output. MOTOR Reaction at bus power failure Upper end position Lower end position Ignore Intermediate position 1 Intermediate position 2 This parameter defines the position which will be generated at bus power failure. MOTOR Reaction at bus power failure Upper end position Lower end position Ignore Intermediate position 1 Intermediate position 2 This parameter defines the position which is generated at bus power return. MOTOR Reaction at main power return (230 V) Upper end position Lower end position Ignore This parameter defines the position which is generated at main power return (230 V). Automatic cascading No Yes If the parameter Yes is selected, each motor output with 1 second of delay will move to the appropriate position. This deceleration time arises considered in the case of Reaction at Bus power return and Reaction at main power return (230V). The position selected in the parameters for the according motor output will be moved to. m Advantage: The current peaks can be lowered thus in larger projects. animeo KNX/EIB 4 DC/E MoCo REF /45
37 Paremeter card Feedback motor position On this parameter card the parameters can be selected in order to announce the status positions of the individual blinds on the bus. The status positions generated thus are based on the configured running and tilting times of the parameter cards Motor 1 4 or On this parameter card the parameters can be selected in order to announce the status positions of the individual blinds on the bus. The status positions generated thus are based on the configured running and tilting times of the parameter cards Motor 1 4 or Motor 1-4. Feedback of status Upper/lower end positions No Yes This parameter opens the parameter Type of feedback upper/lower end positions. Type of feedback Combined when all are UP / DOWN Individual Combined when all are UP / DOWN If this parameter is selected, the appropriate end position, UP or DOWN, is sent only to the bus when all four blinds have reached the upper end limit (object 59), and respectively when all four end products have reached the lower end position (object 64). Individual If this parameter is selected, the appropriate end position, UP or DOWN, is sent to the bus individually for each blind. Two objects are available per motor output (objects and 60-63). MOTOR Feedback for UP / DOWN positions Slat position UP / DOWN and slat position None value (0/255) 100 % value (255/0) 0 % UP / DOWN position Over this parameter the position UP / DOWN is sent to the bus for the appropriate motor, depending on the parameter Motor 1-4 type of feedback. 0 = UP/ 255 = DOWN. animeo KNX/EIB 4 DC/E MoCo REF /45
38 Slat position Over this parameter the position of the slat is sent to the bus for the appropriate motor, depending on the parameter Motor 1-4 type of feedback. 0/255 = slat opened, 255/0 = slat closed. The value for the slat position which is sent depends on the parameter selection on the parameter card General, slat position closed/reversed ONLY FOR VENETIAN BLINDS. UP / DOWN and slat postion Over this parameter the position UP / DOWN and the position of the slat is sent to the bus for the appropriate motor, depending on the parameter Motor 1-4 type of feedback. 0/255 = slat opened, 255/0 = slat closed. The value for the slat position which is sent depends on the parameter selection on the parameter card General, slat position closed/reversed ONLY FOR VENETIAN BLINDS. None No positions are sent to the bus. Type of feedback Motor 1-4 On demand Status change Cyclic On demand The current position of the blinds must be requested over object 54. Status change The current position of the appropriate blind is sent to the bus after every change of position. The position is only sent to the bus if the target postion is reached. Cyclic This parameter opens a further parameter ( Every ) in the time for cycling sending is configured. Every 5 seconds 10 seconds 20 seconds 30 seconds 60 seconds 15 minutes 30 minutes 60 minutes 120 minutes Over this parameter it is defined in which time intervals the current position of the appropriate blind is sent to the bus. animeo KNX/EIB 4 DC/E MoCo REF /45
39 Parameter card Security motor 1-2 / motor 3-4 / motor 1-4 Two individual cards (Safety motor 1-2 / Safety motor 3-4) are visible when on the card General for the motor output configuration Individual is parametered. One card (Security motor 1-4) is visible when on the card General for the motor output configuration Combined is parametered. The parameter for motor 1 is described as follows. The parameters for motors 2-4 are the same. MOTOR 1, Security position Low priority Upper end limit Lower end limit Intermediate position 1 Intermediate position 2 Ignore Security Stop Over this parameter the security position low security is specified for the appropriate blind. If on one of the communication objects (objects 31-35) a telegram with the value 1 is received, then the appropriate blind moves to the position which is configured in the ETS parameters. If on one of these communication objects a telegram with the value 0 is received no action will be executed. Only if in the ETS parameters Repeat the last telegram after security (Yes) is selected, then this action for the appropriate blind will be executed. If one of these communication objects is active by a telegram with the value 1 and on one of the communication objects (security position, high priority) a telegram with the value 1 is received, the appropriate blind moves to the position configured in the ETS parameters (security position, high priority). MOTOR 1, Security position High priority Upper end limit Lower end limit Ignore security Over this parameter the security position high security is specified for the appropriate blind. If on one of the communication objects (objects 36-40) a telegram with the value 1 is received, then the appropriate blind moves to the position configured in the ETS parameters. If on one of these communication objects a telegram with the value 0 is received no action will be executed. Only if in the ETS parameters Repeat the last telegram after security (Yes) is selected, then this action for the appropriate blind will be executed. animeo KNX/EIB 4 DC/E MoCo REF /45
40 Cyclic monitoring time in seconds (0-255) Cyclic monitoring time is active as soon as a higher value than 0 is registered and refers to both security objects, low and high priority. m With active cyclic monitoring it is to be made certain that the time of the cyclic transmitter is smaller, approx. 1/4 than the configured cyclic monitoring time for the security objects, low and high priority. If the default value remains adjusted 0 the security objects react statically to the values 1 and 0. Parameter card Special functions motors 1-4 The parameter for motor 1 is described as follows. The parameters for motors 2-4 are the same. m This card is only visible with Selection motor type DC with encoder on the card General. Motor 1 Automatic slat shake No Yes When the parameter Yes is selected, an automatic slat shake is carried out when reaching the bottom end position. Here, the slats are one time completely opened and closed. m Through this function it is possible also to set up the slats automatically. It can happen that in a DOWN command some of the slats whilst turning get entangled and therefore do not stand in the mechanical default position. Through completely opening and closing the slats, the entangled slats are brought into the mechanical default position. animeo KNX/EIB 4 DC/E MoCo REF /45
41 Motor 1 Reference counter (0-255) This parameter defines when a reference move is carried out. This means for example, that after 20 UP/STOP telegrams, a reference move will be carried out. n See also Chapter 2, definitions. Motor 1-4 Reference move after ETS download No Yes When selecting Yes, a reference move is carried out with each ETS download. n See also Chapter 2, definitions. animeo KNX/EIB 4 DC/E MoCo REF /45
42 8 Diagnosis 8.1 LEDs on the animeo KNX/EIB Motor Controller The LEDs on the animeo KNX/EIB Motor Controller can be used for the following functions: Operability of the device during operation (230 V / KNX/EIB bus power attached, indication of radio signals,...) A limited overview of the configurations First diagnosis 8.2 Information during the operation Receipt of a radio telegram... Security low/high or object Block functions active... The device is operational, display of receipt of EIB telegrams Status of configurations m The inquiry of the status of the configurations is only possible on delivery before the device is programmed with the ETS. As soon as the device is programmed with the ETS, the status of the configurations can no longer be checked via the Reset/Prog button. If the device is unloaded by the ETS, the status of the configurations can again be queried over the Reset/Prog button. The inquiry of the status of the radio functionality (green upper LED) is always possible. LED On (2 s) Blinking ))) = Green Radio remote configured No radio configuration SCR = Yellow Screen with configured running and tilting times Screen without configured running and tilting times EU = Orange Venetian blind, EU ergonomics, with configured running and tilting times Venetian blind, EU ergonomics, without configured running and tilting times US = Red Venetian blind, US ergonomics, with configured running and tilting times Venetian blind, US ergonomics, without configured running and tilting times animeo KNX/EIB 4 DC/E MoCo REF /45
43 8.4 First diagnosis Warning LED (m) on the Motor Controller When an UP or DOWN command is given and the warning LED flashes red (excess current), the following points must be checked: Short circuit on the motor output or at least a wire is not connected Encoder wire (purple) is connected incorrectly on the motor output (e.g. M1 connector 1 or 2) A DCE motor is connected, the Motor Controller is however in the DC mode A DC motor is connected, the Motor Controller is however in the DCE mode In the mode selection DCE: When an UP or DOWN command is given and the warning LED flashes yellow (regulator error), the set speed concerning the size of the venetian blinds is too high. The set time for the UP and DOWN direction must be appropriate (increased) Visual display with error identifying Motor 1... Motor 2... Motor 3... Motor 4... To switch off the error display briefly press the Reset/Prog button (0,5 seconds) animeo KNX/EIB 4 DC/E MoCo REF /45
44 9 Technichal Data The 4 DC/E Motor Controller animeo KNX/EIB is an electronic operated, independently mounted control with looped-through PE-connection. 4 DC/E Motor Controller KNX/EIB Art Supply voltage Stand-by current Stand-by energy consumption Supply voltage from KNX/EIB bus Rated current consumption KNX/EIB Max. motor current consumption Max. power per motor output V AC / 50/60 Hz 16 ma 3.5 VA KNX/EIB-voltage V DC, SELV as per KNX/EIB guidelines 4 x 500 ma Max. 500 ma at 24 V DC Supply voltage of group control input SELV, 16 VDC = Supply voltage of local push buttons SELV, 16 VDC = Input/output Terminals Terminals KNX/EIB Running time per output (relay contact) Fuses Operation temperature Relative humidity 85 % Material of housing Housing dimensions (H x B x W) Degree of protection IP 20 Protection class Automatic action Pollution degree 2 Rated impulsive voltage Temperature of ball pressure test Short circuit protected Spring connectors KNX/EIB bus terminal (black/red) max. 5 minutes or mm T4A (not replacable) 0 C - 45 C CC-ABS polycarbonate 180 x 255 x 63 mm II, corresponding to the installation Typ 1; Typ 1.C micro interruption 4 kv 75 C Conformity CE by EN animeo KNX/EIB 4 DC/E MoCo REF /45
45 i AUSTRALIA SOMFY Pty Limited Tel.: (61) FINLAND SOMFY Nordic AB Tel.: (358) JAPAN SOMFY K.K Tel.: (81) RUSSIA SOMFY LLC Tel.: (7) AUSTRIA SOMFY GmbH Tel.: (43) FRANCE SOMFY France Tel.: (33) KOREA SOMFY JOO Tel.: (82) KINGDOM OF SAUDI ARABIA SOMFY Jeddah Tel.: (966) BELGIUM SOMFY NV SA Tel.: (32) GERMANY SOMFY GmbH Tel.: (49) KUWAIT SOMFY Kuwait Tel.: (965) SERBIA MIGRO Tel.: (381) BRASIL SOMFY BRASIL Ltda Tel.: (5511) GREAT BRITAIN SOMFY Ltd. Tel.: (44) LEBANON SOMFY Lebanon Tel.: (961) SINGAPORE SOMFY PTE LTD Tel.: (65) Canada SOMFY ULC Tel.: (1) GREECE SOMFY Hellas SA Tel.: (30) MEXICO SOMFY MEXICO S.A. de C.V. Tel.: (52) SPAIN SOMFY España S.A. Tel.: (34) CHINA SOMFY China Co Ltd. Tel.: (86) HONG KONG SOMFY Co. Ltd. Tel.: (852) NETHERLANDS SOMFY Nederland B.V Tel.: (31) SWEDEN SOMFY Nordic AB Tel.: (46) CROATIA BFT Adria d.o.o. Tel.: (385) CYPRUS SOMFY Middle East Co. Ltd. Tel.: (357) HUNGARY SOMFY Kft Tel.: (36) INDIA SOMFY India Pvt Ltd Tel.: (91) NORWAY SOMFY Nordic AB Tel.: (47) POLAND SOMFY Sp. z o. o. Tel.: (48) SWITZERLAND SOMFY AG Tel.: (41) TAIWAN SOMFY Development Taiwan Branch Tel.: (886) CZECH REPUBLIC SOMFY, spol. s r.o. Tel.: (420) DENMARK SOMFY Nordic AB Denmark Tel.: (45) ISRAEL SISA HOME AUTOMATION LTD Tel.: (972) ITALY SOMFY Italia S.R.L Tel.: (39) PORTUGAL SOMFY Portugal Tel.: (351) ROMANIA SOMFY SRL Tel.: (40) TURKEY SOMFY EV OTOMASYON SISTEMLERI LTD STI Tel.: (90) USA SOMFY Systems Inc. Tel.: (1)
ABB i-bus EIB Universal Interfaces US/U 4.2 US/U 2.2
Product Manual ABB i-bus EIB US/U 4.2 US/U 2.2 Intelligent Installation Systems Intelligent and limitless Contents Page 1 General............................................. 3 1.1 Product and functional
ABB i-bus EIB Logic Module LM/S 1.1
Product Manual ABB i-bus EIB Logic Module LM/S 1.1 Intelligent Installation System Contents page 1 General... 3 1.1 About this manual... 3 1.2 Product and functional overview... 3 2 Device technology...
ABB i-bus EIB Shutter Actuators JA/S 2.230.1, JA/S 4.230.1, JA/S 8.230.1, JA/S 4.230.1M, JA/S 8.230.1M, JA/S 4.24.1
Product Manual ABB i-bus EIB Shutter Actuators JA/S 2.230.1, JA/S 4.230.1, JA/S 8.230.1, JA/S 4.230.1M, JA/S 8.230.1M, JA/S 4.24.1 Intelligent Installation Systems Contents Page 1 Introduction.......................................
Inwall 4 Input / 4 Output Module
Inwall 4 Input / 4 Output Module IO44C02KNX Product Handbook Product: Inwall 4 Input / 4 Output Module Order Code: IO44C02KNX 1/27 INDEX 1. General Introduction... 3 2. Technical data... 3 2.1 Wiring Diagram...
How To Use A Power Supply On A Powerline 2.2 (Ai)
KNX/EIB Product documentation Issue: 05.08.2010 629x1220 Push button sensor 3 comfort 1-gang Push button sensor 3 comfort 2-gang (1+1) Push button sensor 3 comfort 3-gang Push button sensor 3 comfort 4-gang
Analogue Input, 4-fold, MDRC AE/S 4.1, GH Q605 0054 R0001
Analogue Input, -fold, MDRC, GH Q605 005 R0001 The analogue input is a DIN rail mounted device for insertion in the distribution board. It is connected to the EIB via the bus connecting terminal supplied.
Application Unit, MDRC AB/S 1.1, GH Q631 0030 R0111
, GH Q631 0030 R0111 SK 0010 B 98 The application unit is a DIN rail mounted device for insertion in the distribution board. The connection to the EIB is established via a bus connecting terminal at the
ABB i-bus KNX Fan Coil Controller FC/S 1.1
Product manual ABB i-bus KNX Fan Coil Controller FC/S 1.1 Intelligent Installation Systems Contents Page 1 Introduction... 2 2 Device technology... 3 3 Application and planning 3.1 Heating, ventilation
Shutter Actuator Standard, 4-fold, 230 VAC, MDRC RA/S 4.230.1, GH Q631 0076 R0111. ABB i-bus EIB
, GH Q631 0076 R0111 2CDC 071 240 F0003 The Shutter Actuator Standard is used to control a maximum of four independent 230 VAC drives for positioning shutters, blinds, awnings and other hangings as well
Switch Actuator, 8-fold, 10 A, MDRC AT/S 8.10.1, GH Q631 0075 R0111
, GH Q631 0075 R0111 The 8-fold switch actuator is a DIN rail mounted device for insertion in the distribution board. It is connected to the EIB via a bus terminal. In the event of bus voltage failure,
KNX Gateway RGK02-5023E-01
KNX Gateway RGK02-5023E-01 Table of contents Page 1 General Information 1.1 Technical data 5 1.2. Intended Use 6 1.3 Specifications 6 1.4 Compatibility 6 1.5 Scope of delivery 6 2 Information about the
Inwall Room Temperature Unit
Inwall Room Temperature Unit TM11B01KNX TM11B11KNX TM11B21KNX Product Handbook Product: Inwall Room Temperature Unit Order Code: TM11B01KNX TM11B11KNX TM11B21KNX Application Program ETS: TM11B_1KNX Inwall
PRODUCT MANUAL IRSC. IRSC-Plus. Air-Conditioning controller ZN1CL-IRSC. Program version: 5.14 Manual edition: 5.14_a
PRODUCT MANUAL IRSC IRSC-Plus. Air-Conditioning controller ZN1CL-IRSC Program version: 5.14 Manual edition: 5.14_a INDEX Document updates... 3 1. Introduction... 4 1.1. IRSC controller... 4 1.2. Installation...
Shutter Actuator, 8-fold, 230 V AC, MDRC JA/S 8.230.1, GH Q631 0063 R0111. ABB i-bus EIB / KNX
, GH Q631 0063 R0111 2CDC 071 238 F0003 For controlling a maximum of eight independent 230 V AC shutter or sunblind drives via ABB i-bus including the functions Up/Down, Step/Stop, Move to position, Sun
Technical Manual. FAN COIL CONTROLLER COOLING or HEATING ANALOG or PWM Art. 119914 631001A
COOLING or HEATING ANALOG or PWM Art. 119914 631001A TOTAL AUTOMATION GENERAL TRADING CO. LLC SUITE NO.506, LE SOLARIUM OFFICE TOWER, SILICON OASIS, DUBAI. UAE. Tel. +971 4 392 6860, Fax. +971 4 392 6850
Tebis application software
Tebis application software Input products / ON / OFF output / RF dimmer Electrical / Mechanical characteristics: see product user manual Product reference Product designation TP device RF devices WYC81xQ
Light scene push button 8gang comfort flush-mounted 751688xx
751688xx Documentation Product name: Light scene push button 8gang comfort Design: flush-mounting type (Up) ETS search path: Push button / Push button general / Light scene push button 8gang comfort Functional
Product and functional description
Product and functional description The KNX / DALI gateway N 141/02 is a 4 MU wide, DINrail mounted KNX device with one DALI interface to which up to 64 DALI actuators (e.g. DALI ballasts) can be connected
Modular I/O System Analog and Digital Interface Modules
OPERATING INSTRUCTIONS Modular I/O System Analog and Digital Interface Modules Installation Operation Maintenance Document Information Document ID Title: Operating Instructions Modular I/O System Part
ABB i-bus EIB / KNX Analogue Input AE/S 4.2
Product Manual ABB i-bus EIB / KNX Analogue Input AE/S 4.2 Intelligent Installation Systems This manual describes the functionality of Analogue Input AE/S 4.2. Subject to changes and errors excepted. Exclusion
B.IQ push button 3-5gang with room thermostat and display V2, flush-mounted 7566359x, 7566459x, 7566559x
B.IQ push button 3-5gang with room Product name: Design: ETS search path: B.IQ push button 3-, 4-, 5gang with room thermostat and display V2 Flush-mounted Push button / B.IQ / B.IQ push button xgang with
Push button 3gang standard flush-mounted 751633xx
Documentation Product name: Push button 3gang standard Design: device (up) ETS search path: Push button / Push button 3gang / Push button 3gang standard Functional description: The push button 3gang standard
ABB i-bus EIB / KNX EIB Monitoring Unit EUB/S 1.1
Product Manual ABB i-bus EIB / KNX EIB Monitoring Unit EUB/S 1.1 Intelligent Installation Systems This manual describes the function of the EIB monitoring module EUB/S 1.1 with the Application program
VARIO PROX CARD READER INSTALLATION MANUAL
VARIO PROX CARD READER INSTALLATION MANUAL TABLE OF CONTENTS 1.0 INTRODUCTION...2 1.1 Legend...3 1.2 Terminology...4 2.0 MOUNTING...5 3.0 WIEGAND CONNECTION...6 4.0 AUX BUTTON INPUT...7 5.0 INSTALLER PROGRAMMING...8
Push button 2, 3, 5gang with room thermostat (RTR) and display flush-mounted 756627xx, 756637xx, 756657xx
756627xx, 756637xx, 756657xx Documentation Product name: Push button 2-, 3-, 5- gang RTR + display Design: UP (flush-mounting type) ETS search path: Push button / Push button xgang / Push button xgang
Product Manual. ABB i-bus KNX Data Logging Unit BDB/S 1.1. Intelligent Installation Systems ABB
Product Manual ABB i-bus KNX Data Logging Unit BDB/S 1.1 Intelligent Installation Systems ABB This manual describes the function of the Data Logging Unit BDB/S 1.1. Subject to changes and errors excepted.
PRESENCE DETECTOR PD-C360i/24 KNX ECO (EP10425844)
In the Master function, the remote control entries will be acknowledged as follows: acknowledged 3 x with the red LED In the Slave function, each detection is acknowledged 2 x with the green LED. 6 TEST
mecotron Safety relay ESTOP-2 For emergency stop monitoring
E0006 000824 Safety relay E-2 For emergency stop monitoring Description The safety module E-2 for emergency stop monitoring is used for safety breaking one or more circuits and is designed to be incorporated
Busch-Watchdog Presence EIB Type: 6131-74-102-500
Type: 6131-74-102-500 Contents Technical data 2-2 Application programs (List) 2-3 Circuit diagrams 2-3 in combination with Bus coupler FM (6120-102): Switch Value Cyclic Monitoring /3 2-4 Switch Value
Product Manual. ABB i-bus KNX. Universal Dim Actuator, MDRC UD/S 2.300.2. Intelligent Installation Systems ABB
Product Manual ABB i-bus KNX Universal Dim Actuator, MDRC UD/S 2.300.2 Intelligent Installation Systems ABB UD/S 2.300.2 Universal Dim Actuator, MDRC This manual describes the function of the Universal
Transmitter Actuator 230V wave UP 560. Operation
Transmitter ctuator 230V wave UP 560 5WG3 560-201 Product- and pplication Description Diagram The transmitter actuator 230V wave UP 560 (Diagram ) is a flush-mounted device with radio communication for
ABB i-bus KNX DALI-Gateway DG/S 8.1
Product manual ABB i-bus KNX DALI-Gateway DG/S 8.1 Intelligent Installation Systems This manual describes the function of the DALI-Gateway DG/S 8.1 with the application program Dim Slave Lightscenes Dynamic
PAC1 Door Access Controller
PAC1 Door Access Controller Series 2 IMPORTANT DIFFERENCES FROM SERIES 1 1. A PACDL data logger revision 4.0 or higher attached to the DLOG terminal is able to program all features (i.e. times, relay type,
Technical Manual MDT Rain sensor
9/2012 Technical Manual MDT Rain sensor SCN-RS1R1.01 Technical Manual Rain sensor SCN RS1R1.01 1.1. Settings at the ETS Software Selection at the product database: Manufacturer: MDT Technologies Product
ABB i-bus EIB / KNX DALI-Gateway DG/S 8.1
Product manual ABB i-bus EIB / KNX DALI-Gateway DG/S 8.1 Intelligent Installation Systems This manual describes the function of the DALI-Gateway DG/S 8.1 with the application program Dim Slave Lightscenes
Quick start: Energy Switch EU
Technical specifications Normal operating voltage Quick start: Energy Switch EU 230Vac/50Hz Recommended max. load 3000W 600W Frequency range Wireless range Energy measurement 868.42 MHz 30~100 meters in
Unica for KNX system 226
Unica for KNX system 6 P117504 Greater flexibility and comfort, better energy efficiency with KNX More and more electronic appliances are needed for modern comfortable homes that contain everything from
IntesisBox KNX Mitsubishi Heavy Industries AC
IntesisBox KNX Mitsubishi Heavy Industries AC Gateway for integration of Mitsubishi Heavy Indsutries (MHI) Air Conditioners with KNX control systems. 1. Main Features Direct connection to KNX TP-1 (EIB)
ELABOTrainingsSysteme. Aus- und Weiterbildung GmbH. Home and Building Control KNX / EIB. www.elabo-ts.com
Aus- und Weiterbildung GmbH Home and Building Control KNX / EIB www.elabo-ts.com Design and commissioning of KNX/EIB systems www.elabo-ts.com Hardware page 2-5 Software page 6-9 Projects page 10-15 LOGO!
LGAC-KNX PROGRAMMING MANUAL. Integrations V1.0 TECHNICAL SUPPORT. Tel (+34) 985 113 339 [email protected]
Integrations LGAC-KNX V1.0 PROGRAMMING MANUAL Parque Tecnológico de Asturias, Parcela 50, 33428 Llanera Asturias - Spain Tel (+34) 985 118 859 Fax (+34) 984 283 560 [email protected] www.ingeniumsl.com
Glass sensor 2gang with room thermostat Glass sensor 3gang with room thermostat
KNX/EIB Product documentation Glass sensor 2gang with room thermostat Glass sensor 3gang with room thermostat Issue: 16.01.2009 65750120 Page 1 of 240 KNX/EIB Product documentation Content 1 Product definition...
Product Manual. ABB i-bus KNX IP Interface IPS/S 2.1. Intelligent Installation Systems ABB
Product Manual ABB i-bus KNX IP Interface IPS/S 2.1 Intelligent Installation Systems ABB This manual describes the function of the IP Interface IPS/S 2.1 with the application program IP Interface. Subject
IntesisBox KNX Modbus TCP master
IntesisBox KNX TCP master Gateway for integration of TCP slave devices into KNX control systems. Integrate any TCP slave device into KNX. KNX TCP slave EIB Bus IntesisBox Ethernet slave LinkBoxEIB Configuration
ABB Drives. User s Manual. Pulse Encoder Interface Module RTAC-01
ABB Drives User s Manual Pulse Encoder Interface Module RTAC-0 Pulse Encoder Interface Module RTAC-0 User s Manual 3AFE 64486853 REV A EN EFFECTIVE:.5.00 00 ABB Oy. All Rights Reserved. Safety instructions
Drayton Digistat +2RF/+3RF
/+3RF Programmable Room Thermostat Wireless Model: RF700/22090 Model: RF701/22092 Power Supply: Battery - Thermostat Mains - Digistat SCR Invensys Controls Europe Customer Service Tel: 0845 130 5522 Customer
ABB i-bus EIB / KNX Weather Station WS/S 4.1
Product Manual ABB i-bus EIB / KNX Weather Station WS/S 4.1 Intelligent Installation Systems This manual describes the function of the Weather station WS/S 4.1. Subject to changes and errors excepted.
IntesisBox KNX Modbus RTU master
IntesisBox KNX RTU master Gateway for integration of RTU devices into KNX control systems. Integrate RTU devices (Chillers, Roof Tops, electricity meters, heating floors, heat pumps, PLCs ) into KNX control
Operating instructions IV / 2007
General Operating instructions IV / 2007 Contents General Installation Application and function Application and function... 2 Safety information... 2 Design and dimensions... 3 Wiring diagram... 3 Installation
Telephone Controller INSTRUCTION MANUAL MODEL CT240-01
INSTRUCTION MANUAL Telephone Controller We thank you for trusting Aube technologies and hope that you will be entirely satisfied. For any questions concerning the CT240 telephone remote control, please
Process modules Digital input PMI for 24 V DC inputs for 120 V AC inputs
E031026 000823 Process modules Digital input PMI for inputs for 120 V AC inputs PMI Input E4, E5, GND L- PMI 120 V AC Input E4, E5, Common C E6, E7, GND L- E6, E7, Common C LEDs for the inputs operation
ABB i-bus KNX Switch Actuators SA/S Product Information
ABB i-bus KNX Switch Actuators SA/S Product Information ABB Stotz-Kontakt GmbH Your Partner with Know-How for Future-Oriented Electrical Installation Hugo Stotz, the company founder of ABB Stotz-Kontakt,
PRODUCT MANUAL. InZennio Z38i. KNX Touch Panel ZN1VI-TP38i. Program version: 2.2 Manual edition: a
PRODUCT MANUAL InZennio Z38i KNX Touch Panel ZN1VI-TP38i Program version: 2.2 Manual edition: a INDEX Document updates... 3 1. Introduction... 4 1.1. InZennio Z38i... 4 1.2. Installation... 5 2. Configuration...
Product Information. Gateway For Connecting EnDat Encoders to PROFIBUS-DP
Product Information Gateway For Connecting EnDat Encoders to PROFIBUS-DP April 2012 PROFIBUS Gateway For Connecting EnDat Encoders Encoders with EnDat interface for connection via gateway All absolute
Product and Applications Description. Application Programs. Example of Operation. GAMMA instabus Technical Product-Information.
Product and Applications Description The power supply units N 125/x2 can supply DC 24 V power from an additional pair of terminals (yellowwhite). This DC 24 V output voltage can be used to power e.g. an
ZME_05459 Wall Blind Control Set for Busch-Jaeger DURO 2000 Firmware Version : 1.8
ZME_05459 Wall Blind Control Set for Busch-Jaeger DURO 2000 Firmware Version : 1.8 Quick Start A This device is a Z-Wave Actuator. Triple click one of the buttons on the device will include the device.
Operating instructions II / 2004
Operating instructions II / 2004 Light and presence sensor TOUCH DIM LS/PD LI OSRAM GmbH Costumer-Service-Center (CSC) Steinerne Furt 62 86167 Augsburg, Germany www.osram.com www.osram.de Tel. : (+49)
ABB i-bus KNX Switch Actuators SA/S Product Information
ABB i-bus KNX Switch Actuators SA/S Product Information ABB Stotz-Kontakt GmbH Your Partner with Know-How for Future-Oriented Electrical Installation Hugo Stotz, the company founder of ABB Stotz-Kontakt,
DALI DIM/CONVERTER CONTROL (DC NV) 1 10V (0-10 V) analog DALI Converter with (Multi-) Sensor-control and 1 and 2-Switch dim functions
DAI DIM/COVERTER COTRO (DC V) 1 10V (0-10 V) analog DAI Converter with (Multi-) Sensor-control and 1 and 2-Switch dim functions Dim-and Switch Functions: The DAI Dim/Converter Control DC V is suitable
ABB Drives. User s Manual HTL Encoder Interface FEN-31
ABB Drives User s Manual HTL Encoder Interface FEN-31 HTL Encoder Interface FEN-31 User s Manual 3AUA0000031044 Rev B EN EFFECTIVE: 2010-04-06 2010 ABB Oy. All Rights Reserved. 5 Safety instructions
Duct Humidity Transmitter
SDC-H Duct Humidity Transmitter Features Replaceable sensor element Humidity measurement for air ducts Minimum and maximum value memory 0 0V, 0 0mA or 0V, 4 0mA measuring signals selectable with jumpers
EBDSPIR-PRM, EBDSPIR-PRM-IP
Product Guide EBDSPIR-PRM, EBDSPIR-PRM-IP Ceiling PIR presence/absence detector Overview The EBDSPIR-PRM PIR (passive infrared) presence detector provides automatic control of lighting loads with optional
B/S/H/ Error codes and service programmes PH
1 ERROR CODES AND APPLIANCE MESSAGES... 3 1.1 Complete overview of all error codes (in order)... 3 Automatic switch-off... 3 Display is dark and any individual LEDs are lit... 3 E 005... 3 E 011... 3 E
FL ballasts Electronic dimming. PCA T5 BASIC lp Y II, 14 80 W BASIC T5
T5 TC-L PCA T5 BASIC lp Y II, 1 80 W BASIC T5 Product description Processor-controlled ballast with y II inside Highest possible energy class CELMA EEI = A1 BAT 1 Noise-free precise control via DSI signal,
ABB i-bus EIB / KNX Switch Actuator Modules for the Room Controller SA/M 2.6.1 ES/M 2.230.1, ES/M 2.24.1
Product Manual ABB i-bus EIB / KNX Switch Actuator Modules for the Room Controller SA/M 2.6.1 ES/M 2.230.1, ES/M 2.24.1 Intelligent Installation Systems This manual describes the function of the Switch
KNX System Principles
Application Module Bus Transceiver KNX b a T1 C1 T2 Left II Left On Left II Right Off Left X Left Off Left X Right On Left II Left On Left II Right Off Left X Left Off Left X Right On c b a c E2 Bus Cable
Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency
echnical data sheet NV24A--RE Communicative globe valve actuator for 2-way and 3-way globe valves Actuating force 1000 N Nominal voltage AC/DC 24 V Control Modulating DC (0)2...10 V Variable Nominal stroke
Features, Benefits, and Operation
Features, Benefits, and Operation 2014 Decibel Eleven Contents Introduction... 2 Features... 2 Rear Panel... 3 Connections... 3 Power... 3 MIDI... 3 Pedal Loops... 4 Example Connection Diagrams... 5,6
NC-12 Modbus Application
NC-12 Modbus Application NC-12 1 Table of Contents 1 Table of Contents... 2 2 Glossary... 3 SCADA...3 3 NC-12 Modbus in general... 3 4 Entire system... 4 4.1 PFC to PC connection alternatives...4 4.1.1
Tebis KNX Product Documentation. DALI Gateway. Date of issue: 21.11.2006 64540020.111. Order no. 6 4540 020 Page 1 of 131
Tebis KNX Product Documentation DALI Gateway Date of issue: 21.11.2006 64540020.111 Order no. 6 4540 020 Page 1 of 131 Tebis KNX Product Documentation Table of Contents 1 Product definition... 3 1.1 Product
Operating instructions Diffuse reflection sensor. OJ50xx 701396 / 01 07 / 2004
Operating instructions Diffuse reflection sensor OJ50xx 7096 / 0 07 / 004 Contents Preliminary note. Symbols used Function and features Installation. Installation of the supplied mounting fixture 4 4 Electrical
Installation and Operating Instructions
General The INSTABUS DALI gateway brings the lighting control specfic DALI-Bus and the pluridisciplinary and cross-functional EIB/KNX bus together. Cost effective DALI ECGs can therefore be seamlessly
Comfort 250, 252 Operator System for Garages Anriebssystem für Garagen Anriebssystem für Garagen Anriebssystem für Garagen Anriebssystem für Garagen
Comfort 250, 252 Operator System for Garages Anriebssystem für Garagen Anriebssystem für Garagen Anriebssystem für Garagen Anriebssystem für Garagen Installation and Operating Instructions GB Einbau- und
KNX Panasonic Air Conditioners
IntesisBox KNX Panasonic Air Conditioners Gateway for Panasonic ECOi and PACi system integration into KNX networks Up to 30 Outdoor units Up to 64 Indoor units PA-AC-KNX-64/128 EIA485 U1U2 line U1U2 line
EBDSPIR-DD, EBDSPIR-DD-IP
Product Guide EBDSPIR-DD, EBDSPIR-DD-IP Ceiling PIR presence detector DALI / DSI dimming Overview The EBDSPIR-DD PIR (passive infrared) presence detector provides automatic control of lighting loads with
Power Supply and Indicator Unit Type 5024-1. Fig. 1 Type 5024-1. Mounting and Operating Instructions EB 9539 EN
Power Supply and Indicator Unit Type 5024-1 Fig. 1 Type 5024-1 Mounting and Operating Instructions EB 9539 EN Edition October 2003 Application 1 Application The Type 5024-1 Power Supply and Indicator Unit
DALIX PROGRAMMING MANUAL. Gateway KNX-DALI V1.0 TECHNICAL SUPPORT. Tel (+34) 985 113 339 [email protected]
Gateway KNX-DALI DALIX V1.0 PROGRAMMING MANUAL Parque Tecnológico de Asturias, Parcela 50, 33428 Llanera Asturias - Spain Tel (+34) 985 118 859 Fax (+34) 984 283 560 [email protected] www.ingeniumsl.com
is then retained absolutely without interruption.
Page 1 of 11 DC UPS uninterruptible power supplies - DC UPS module 15 A Compact design, only 50 mm wide Absolutely interruption-free buffering of power failures through immediate electronic connection
GENERATOR START CONTROL MODULE - MINI (2 Wire to 3 Wire)
FEATURES & APPLICATIONS Inexpensive 2 wire to 3 wire start controller for electric start high speed gas generators. Optimized for use with Outback Invertors. Supports three types of 3 wire generator control
SERVICE INSTRUCTION R410A. WALL MOUNTEDtype INVERTER SPLIT TYPE ROOM AIR CONDITIONER. Models Indoor unit Outdoor unit
SERVICE INSTRUCTION SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTEDtype INVERTER Models Indoor unit Outdoor unit ASYG07LECA ASYG09LECA ASYG12LECA ASYG14LECA AOYG07LEC AOYG09LEC AOYG12LEC AOYG14LEC R410A CONTENTS
PRODUCT MANUAL LUMENTO X4 LED. LED Controller ZN1DI-RGBX4. Program version: 1.0 Manual edition: a
PRODUCT MANUAL LUMENTO X4 LED LED Controller ZN1DI-RGBX4 Program version: 1.0 Manual edition: a INDEX 1. Introduction...3 1.1. Lumento X4... 3 1.2. Installation... 4 2. Configuration...6 3. ETS Parameterization...7
Smarthome SELECT Bluetooth Wireless Stereo Audio Receiver and Amplifier INTRODUCTION
Smarthome SELECT Bluetooth Wireless Stereo Audio Receiver and Amplifier INTRODUCTION The Smarthome SELECT Bluetooth Wireless Stereo Audio Receiver and Amplifier is a multi-functional compact device. It
HERZ-Thermal Actuators
HERZ-Thermal Actuators Data Sheet 7708-7990, Issue 1011 Dimensions in mm 1 7710 00 1 7710 01 1 7711 18 1 7710 80 1 7710 81 1 7711 80 1 7711 81 1 7990 00 1 7980 00 1 7708 11 1 7708 10 1 7708 23 1 7709 01
DUAL SENSING DIGITAL THERMOSTAT PRODUCT INSTRUCTIONS. Construction Automotive Industry
DUAL SENSING DIGITAL THERMOSTAT PRODUCT INSTRUCTIONS www.rehau.com Construction Automotive Industry SCOPE This guide gives instruction regarding REHAU Programmable Digital Thermostat installation and operation.
SDN INSTRUCTIONS 07/10, Ver 1.2. Somfy Digital Network (SDN) Installation and Programming
Somfy Digital Network (SDN) Installation and Programming SSoomffyy SSyysst teemss IInncc.. 1 Table of Contents 1 General Information and Features... 3 1.1 ILT2 Motor... 3 1.2 SDN Switches... 4 1.3 ILT2
DeviceNet Bus Software Help for Programming an Allen Bradley Control System
FBP FieldBusPlug V7 DeviceNet Bus Software Help for Programming an Allen Bradley Control System DeviceNet Software Help for Programming an Allen Bradley Control System Contents Page General Purpose...
Technical data. General specifications. Signal voltage 15... 30 V DC Signal duration. 1 s Input 2. Signal voltage. 1 s Analog output.
Model Number Features Very small housing High climatic resistance 4 Bit multiturn Analog output Surge and reverse polarity protection Description This absolute rotary encoder with internal magnetic sampling
The ABB i-bus KNX Room Master Concept Your first step into the KNX world
The ABB i-bus KNX Room Master Concept Your first step into the KNX world The Room Master Concept 1 New Step 1,000 New Options You specialize in installing electrical systems. With the ABB Room Master,
Multi-Protocol decoder 76 400
Multi-Protocol decoder 76 For locomotives with DC motors on digital layouts operating in the DCC- and Motorola data format. Features Regulated multi-protocol decoder for DCC and Motorola Suitable for DC
contents Leading the way in intelligent automation INELS Wireless? Why Click Accessories Complete control
Wireless Control Systems Accessories Leading the way in intelligent automation contents Range Overview Typical Installations Transmitters Combined Modules Accessories Programming Switching & Dimmer Functions
T0118 T2118 T3118. Instruction Manual
Programmable indoor transmitter of temperature T0118 Programmable indoor transmitter of atmospheric pressure T2118 Programmable indoor transmitter of temperature, relative humidity and other derived humidity
PCS0100en 02.2008. Persy Control Services B.V. Netherlands
P-Bus Gateway PBGW2.128 Universal gateway between the P-bus protocol and open standard protocols. The variety of available electrical interfaces on the gateway offers a wide range of possibilities for
KNX IP Gateway. Light-Control R. User manual-ver.1 LC-IPGW-001. KNX Gateway. KNX/EIB Intelligent Installation Systems
KNX Gateway Light-Control R User manual-ver.1 LC-IPGW-001 Intelligent Installation Systems Contents 1. Summary ---------------------------------------------------------------------------------------------------------------------
Movement/monitoring 1307/1.0 (6325xx)
/monitoring 1307/1.0 (6325xx) General In the following the device will be referred to as the movement detector. The movement block will only switch off when there is no more movement in front of the device
www.burntec.com User's Guide Integrating Sound Level Datalogger Model 407780
User's Guide Integrating Sound Level Datalogger Model 407780 Introduction Congratulations on your purchase of the Extech 407780 Integrating Sound Level Meter. The 407780 with programmable integrating time
Telefon (+45) 43 43 82 00 Telefax (+45) 43 43 74 75 [email protected] www.uni-valve.com. Installation and operating manual
Uni-Valve A /S VENTILER & INSTRUMENTER Telefon (+45) 43 43 82 00 Telefax (+45) 43 43 74 75 [email protected] www.uni-valve.com UNI-EL Electric actuator Installation and operating manual Remote position
UniTec-868, UniTec-915 Nr. 28 330 0006, Nr. 28 330 0906
UniTec-868, UniTec-915 Nr. 28 330 0006, Nr. 28 330 0906 EN Operating instructions (translation) Please take care of the operating instructions! 181006706_EN_0815 Contents Contents Device explanation...3
Multi-Protocol decoder 76 200 with Load regulation
Multi-Protocol decoder 76 2 with Load regulation For locomotives with universal motors on digital layouts operating in the DCC and Motorola data format. Features 76 2 Load regulated multi-protocol decoder
ZME_WALLC-S Z-Wave Secure Wall Controller
ZME_WALLC-S Z-Wave Secure Wall Controller Firmware Version : 1.0 Quick Start S This device operates as Z-Wave sensor in two modes: the normal control mode (daily use) or in management mode for setup. Pushing
PRODUCTIVITY THROUGH INNOVATION 600 CONTROL DIRECT DRIVE TECHNICAL/OPERATION MANUAL
Rev. D PRODUCTIVITY THROUGH INNOVATION 600 CONTROL DIRECT DRIVE TECHNICAL/OPERATION MANUAL 10 BORIGHT AVENUE, KENILWORTH NEW JERSEY 07033 TELEPHONE: 800-524-0273 FAX: 908-686-9317 TABLE OF CONTENTS Page
PD 100A. Printing data system
PD 100A Printing data system Operating instructions ENGLISH IMPORTANT: Read these instructions carefully before installing and using the device; do not forget following all additional information. Keep