The challenge for busbar disconnectors of gas insulated switchgear (GIS) in a 420kV mixed technology (Hybrid) substation (MTS)

Size: px
Start display at page:

Download "The challenge for busbar disconnectors of gas insulated switchgear (GIS) in a 420kV mixed technology (Hybrid) substation (MTS)"

Transcription

1 21, rue d Artois, F PARIS B3-107 CIGRE 2012 http : // The challenge for busbar disconnectors of gas insulated switchgear (GIS) in a 420kV mixed technology (Hybrid) substation (MTS) P. GLAUBITZ 1, C. WALLNER 1, W. FRÄBEL 2, H. PEIN 2 1 Siemens AG, Germany 2 TenneT TSO GmbH, Germany SUMMARY The demand for electrical energy in the southern part of Germany, with environmentally friendly power generation of increasing on-shore and especially off-shore wind farms in the northern part of Germany, puts high requirements on existing power transmission lines and substations in the 420kV range. The existing 420kV substations have to be modified for the higher energy transmission, from the northern to the southern part of Germany. Transmission lines will be operated on their current limits (transmission loads up to 3000 MVA) which cause feeder currents up to 4000A in the substations. This brings attention to the capability of the busbar disconnectors and their behaviour during busbar-transfer operations. In the product related international standard IEC (2001) [1] the related bus-transfer voltage (transfer voltage) for 420kV Air Insulated Substations (AIS) is given with 300V, while 20V is standard for Gas Insulated Substations (GIS). For the rated bus-transfer current, one common value for air-insulated and gas-insulated disconnectors is given with 1600A. This value considers a current distribution during commutation from one busbar to the other busbar of 80%/20% and therefore, a feeder current up to 2000A. The 1600A was chosen as being typically the highest current which can be switched, although the rated currents of the disconnectors may be substantially higher. These given values for the bus-transfer voltage are not sufficient for the case in which an AISsubstation is modified by using the existing AIS-busbars and installing GIS bays. These Mixed-Technology Substations (MTS) are used due to the higher number of bays which can be installed on an existing footprint. Additionally, a greater flexibility in the substation layouts can be achieved. Investigated substation configurations, which authorize the operator for bus-transfer operations, are double- or multi-busbar arrangements or substations using a transfer busbar for maintenance. The distance, respectively the impedance, of the AIS busbar configuration over the closed coupling bay is very important for commutation. In addition, the feeder current and the load situation on the busbar, define the transfer voltage on the disconnector before, during, and after the bus-transfer operation. christian.wallner@siemens.com

2 Although these voltages are very small compared to the system voltage of the substation, it has to be considered, because the switching capability of the disconnector is very limited to the design. Therefore, the transfer voltage can exceed the values related to the IEC standard. To find and define the maximum value of the transfer voltage for the specific investigated substations, studies were done on typical configurations for TenneT TSO GmbH. The evaluation has shown that the busbar transfer voltages for GIS-disconnectors used in hybrid substations are very well in the range of the values given for AIS configurations. In addition to the above mentioned reasons and from the specific high energy transmission, the required bus-transfer current has to increase up to 3200A. This is twice the recommended rating in the applicable standard. With these results, the technical performance of GIS busbar disconnectors have to be increased for the investigated hybrid substations. The contact system and the drive mechanism have to be modified to achieve the necessary technical requirements. The standard GIS disconnector designed according to the IEC fulfils the requirements for MTS solutions with limitation of transfer-currents and/or voltages. The new developed high-speed disconnector (HSDS) allows extending AIS substations with GIS technology, without recommendations for operation in any MTS configuration. KEYWORDS Air-Insulated-Substation (AIS), Gas-Insulated-Substation (GIS), Mixed-Technology- Substation (MTS), Disconnector, High-Speed Disconnector, Bus-Transfer Voltage, Bus- Transfer Current, IEC INTRODUCTION The task of the European transmission network has changed since the liberalisation of the energy market which started at the end of the 90ies in the last century. Energy-production, -transmission and -distribution play an important role in the European transmission network and is not related to local utilities. The challenge for the European System Operators to develop the European transmission network (so called European Supergrid) under technical, economical and ecologic aspects is the task of the European Network of Transmission System Operators for Electricity (ENTSO-E). The ten-year network development plan shows the three main pillars, security of supply, tackling climate changes and integration of renewable energy sources, and economic efficiency and realisation [2]. The target of the European transmission network can only be reached when the integration of the scheduled renewable energy generation functions properly. Therefore, investigations in the European energy market must be performed. The German Energy Agency (Deutsche Energie-Agentur - DENA) is working on these topics within the German transmission network. The first study, DENA Netzstudie I, was published in 2005 [3]. The second study - DENA Netzstudie II - shows the German transmission network with increased renewable power generation up to 2020 [4]. The conclusion of these studies is that the integration of the renewable energy production from wind and from solar radiation, results in additional requirements in the design- and operation-philosophies of the transmission systems. Therefore, one part beside the required transmission lines is to upgrade the performance of high voltage substations in specific areas. This is required to handle the massive wind power 2

3 generation in northern Germany and transmit the energy to the load centres in southern Germany. 2. SUBSTATION CONCEPTS During the concept phase, the main focus is given to handle the high energy demand. The challenge to the substations in the European Supergrid network is to transmit and distribute the high transmitted energy. As a result, the capability of the required lines is defined by 4000A for the substation. Irrespective of these feeder currents, the currents on the busbar could be higher (e.g. 5000A or 6300A). This corresponds to the general trend for higher rated values [5]. Substation concepts from TenneT TSO GmbH are based on long term experience. Typical configurations are double or in rare cases triple busbar arrangements. Using this kind of substation configurations, the busbar disconnectors has a special function. This function is bus-transfer current switching. From the standpoint of bus-transfer switching capability, the basic concept is always the same. The concept does not differ between AIS, GIS or MTS solutions. The value of the bus-transfer current depends on the ratio between the impedances before and after the bus-transfer operation. The bus-transfer voltage depends on the feeder current and load flow on the busbar. In principle, AIS, GIS and MTS substation were examined. Beside the technical parameters, the life-cycle costs, e.g. available space, maintenance concepts, reliability and availability are very important, but not considered in this technical study. Of course these important parameters must be evaluated differently at each substation. For pure AIS or GIS installations, the existing technology is already capable of theses higher requirements. MTS applications show recommendation for operation, e.g. limitation of the bus-transfer currents and/or voltages. Therefore, the requirements and the development will be done. 3. REQUIREMETNS FOR THE SUBSTATION EQUIPMENT To transfer current from one busbar to another busbar is called bus-transfer current switching (as examples see Figure 1a, 1b). Reasons therefore can be to separate the load flow, limited short-circuit currents or for periodic maintenance. The bus-transfer operation starts with closing the disconnector and the circuit-breaker in the bus-coupler bay. After that, the designated first feeder closes the busbar disconnector to the second busbar. At this moment, the feeder current flows over the original busbar and additionally over the second busbar and the couple bay. The distribution of the currents depends on the impedances of both current paths [6]. A common ratio between the current supplying busbar I and the current supplying busbar II is related to 80%/20%. 3

4 Figure 1: Principle explanation of the bus-transfer current switching case Investigations were done for substations up to 10 feeders. Impedances for AIS busbar are in the range of 0.25mΩ/m and 0.30mΩ/m. For the GIS part, the values are in the range of 0.10mΩ/m and 0.15mΩ/m. The bay width for one feeder is in the range of 20m. For the calculation simulation programs like PSS SINCAL are used. Load flows on the busbar, which can reduce or increase the commutation voltages, can be simulated in a proper way. Beside these detailed calculations, a worst case scenario can be estimate by the following formula: U btv 2 x Z bb x d x I btc (1) U btv Z bb d I btc bus-transfer voltage (V) busbar impedance (Ω/m) distance between the commutating feeder and couple bay (m) bus-transfer current (A) A worst case scenario for bus-transfer switching is a bus-transfer over the maximum length of the busbar. Therefore, the incoming feeder is defined as feeder 1, the first possible outgoing feeder is feeder 3 and the couple bay is places as feeder 10. The feeder current is related to 4000A result in a bus-transfer current of 3200A. The calculated voltage is in the limit between 256V and 307V, which is very well in the range for AIS requirements concerning the bustransfer voltage. 4. DEVELOPMENT OF A HIGH-SPEED DISCONNECTOR The basis for the development is the existing GIS disconnector. Due to MTS applications, the bus-transfer voltage is already designed and tested for 100V, which is 5 times higher than the required 20V according to the IEC standard for GIS equipment. The target for the 4

5 development was to achieve the AIS values at an increased transfer current of 3200A. The main focus during the development was given to the transfer voltage level. The higher current has an impact, but the higher current was neglected during the development phase due to the well known material characteristic of the arcing contacts used. The used graphite nozzles are in similar behaviour used in high-voltage circuit breakers for more than 40 years for short-circuit interruption up to 100kA. In this content, the main focus was given to the transfer voltage, in respect to the commutation time (see Figure 1c). The arc can be spread between the opening contacts as a function of contact stroke during this time. In comparison to AIS disconnectors, there is a limited space for the arc due to the enclosure. The decision was to increase the opening speed to achieve similar conditions (commutation times) between the different bus-transfer voltage levels. Other possible solution, e.g. a contact system with active arc quenching system, is not essential. The assumption was to increase the velocity of the contact between 3 and 4 times. Based on platform concept philosophies, the spring charge mechanism of the high-speed earthing switch was adapted. The weight of a few parts were reduced and several levers were modified to withstand the extended mechanical endurance of 2,000 operatings. Figure 2: 8DQ1-550kV-63kA-5000A with High-Speed Disconnector (HSDS) The time from starting the development, the type testing as far as to the delivery of the first bays, was less than one year (Figure 2). This short development-, purchasing- and manufacturing time could only be achieved by using existing and well known components. The supply chain management was optimized due to involving the purchasing and manufacturing stakeholders at an early stage of development process. TenneT TSO as a potential customer for this solution was witnessing the successful development test. 5. CONCLUSIONS The integration of the renewable energy production in the European Supergrid is a challenge for the TSOs and results in additional requirements in the design- and operation-philosophies 5

6 of the transmission system. In the case of TenneT TSO GmbH, high-voltage substations have to be extended expanded or up-rated. Therefore AIS, GIS and MTS solution have been investigated researched. The transmission capacity is up to 3000 MVA, which corresponds to 4000A for the line respectively for the incoming feeders of the substations. Investigated configurations with double or multi busbar configurations bring attention to the capability of the busbar disconnectors and their behaviour during busbar-transfer operations. In the product related standards, bus-transfer voltages are defined for AIS and GIS equipments. MTS are not specifically mentioned. This study shows that in investigated cases (e.g. AIS extension with MTS, high energy transmission) the MTS values are similar to the AIS guidelines. For AIS and GIS installations, the existing technologies are capable for these high requirements. MTS solutions are not mentioned in the standard. Therefore investigations for MTS substations were made. The results of these investigations show, that the requirements for bus-transfer switching are in the range as for AIS equipment. Recommendations e.g. limitations of transfer-current and voltage would be required. For new installation couple bays could be shifted close to the middle, but not in the case of extension. To bring the MTS technology in a competitive situation, the capability regarding bus-transfer switching of the GIS disconnectors has been improved. The main modification was the spring charge mechanism, required for a higher contact speed. Optimization of a few components of the contact system completed the design modification on the new high-speed disconnector. Finishing the development of the high-speed disconnector, the MTS solutions can be used for extension of AIS substations. AIS, GIS and MTS solutions are now available for TenneT TSO to be implemented in the European Supergird. BIBLIOGRAPHY [1] International Standard IEC ; High-voltage switchgear and controlgear - Part 102: Alternating current disconnectors and earthing switches (First edition. 2001) [2] ENTSOE ENTSO-E s Pilot Ten-Year Network Development Plan. Executive Summary ( 2010) [3] Deutsche Energie-Agentur Energiewirtschaftliche Planung für die Netzintegration von Windenergie in Deutschland an Land und Offshore bis zum Jahr 2020 ( 2005) [4] Deutsche Energie-Agentur DENA-Netzstudie II. Integration erneuerbarer Energien in die deutsche Stromversorgung im Zeitraum mit Ausblick 2025 ( 2010) [5] P. Rudenko, C. Wallner, M. Behne State of the Art GIS Technology and Trends (IEEE PES Transmission & Distribution Conference & Exposition May. Orlando. FL. USA. 2012) [6] H. Lipken, C. Neumann Der Sammelschienenwechsel als Schaltaufgabe für Trennschalter (Elektrizitätswirtschaft. Jg. 83 (1984). Heft 20. Seite ) 6

High-Voltage GIS yesterday - today - tomorrow

High-Voltage GIS yesterday - today - tomorrow High-Voltage GIS yesterday - today - tomorrow Peter Glaubitz, Siemens AG, Principal Expert GIS-Technology siemens.at/future-of-energy Table of content GIS yesterday beginning and establishment of Gas-

More information

High-Voltage Circuit-Breakers 3AP1/2 72.5 kv up to 550 kv. Power Transmission and Distribution

High-Voltage Circuit-Breakers 3AP1/2 72.5 kv up to 550 kv. Power Transmission and Distribution High-Voltage Circuit-Breakers AP/ 7.5 kv up to 550 kv Power Transmission and Distribution The AP/ High-Voltage Circuit-Breakers Now Applicable for 550 kv Decades of our experience in high-voltage switching

More information

High-Voltage Compact Switchgear 3AP1 DTC for 145 kv and 245 kv

High-Voltage Compact Switchgear 3AP1 DTC for 145 kv and 245 kv High-Voltage Compact Switchgear AP1 DTC for 1 kv and kv Answers for energy. The AP1 DTC Complying with our Customers demands Experience you can rely on - at anytime, anywhere Decades of experience in high-voltage

More information

Siemens AG Power Transmission and Distribution Medium Voltage Division Mozartstr. 31c 91052 Erlangen Germany. www.siemens.

Siemens AG Power Transmission and Distribution Medium Voltage Division Mozartstr. 31c 91052 Erlangen Germany. www.siemens. Siemens AG Power Transmission and Distribution Medium Voltage Division Mozartstr. 31c 91052 Erlangen Germany www.siemens.com/energy For questions on power transmission and distribution, please contact

More information

Comparison between Gas- and Air Insulated Network Concepts with the Life Cycle Cost Method

Comparison between Gas- and Air Insulated Network Concepts with the Life Cycle Cost Method Comparison between Gas- and Air Insulated Network Concepts with the Life Cycle Cost Method Ingo Jeromin, Gerd Balzer, Technische Universität Darmstadt, Jürgen Backes, Richard Huber, EnBW Regional AG Stuttgart

More information

IEC and IEEE Standards for High-Voltage Switchgear and Controlgear Present Situation and Future Evolution

IEC and IEEE Standards for High-Voltage Switchgear and Controlgear Present Situation and Future Evolution IEC and IEEE Standards for High-Voltage Switchgear and Controlgear Present Situation and Future Evolution Denis Dufournet Chairman IEC TC 17 & SC17A Fellow IEEE Senior Expert Areva T&D Mumbai, January,

More information

Residual life aspects on GIS with the focus on SF 6

Residual life aspects on GIS with the focus on SF 6 Residual life aspects on GIS with the focus on SF 6 Speaker: Karsten Pohlink 25. March 2015 The presentation refers to CIGRÉ WORKING GROUP B3.17 RESIDUAL LIFE CONCEPTS APPLIED TO HV GIS CIGRE Technical

More information

Product brochure Multi Functional Switchgear PASS M00 72.5 kv Flexible and compact switchgear solutions for windfarms

Product brochure Multi Functional Switchgear PASS M00 72.5 kv Flexible and compact switchgear solutions for windfarms Product brochure Multi Functional Switchgear PASS M00 72.5 kv Flexible and compact switchgear solutions for windfarms The future of Wind Farms As offshore wind farms move towards deploying higher capacity

More information

Disconnectors and Earthing Switches 36 kv up to 800 kv

Disconnectors and Earthing Switches 36 kv up to 800 kv Power Transmission and Distribution Disconnectors and Earthing Switches 36 kv up to 800 kv Ruhrtal & Siemens: A strong and successful team We manufacture high quality high-voltage disconnectors and earthing

More information

ABB s Disconnecting Circuit Breakers Higher substation availability and lower environmental impact

ABB s Disconnecting Circuit Breakers Higher substation availability and lower environmental impact ABB s Disconnecting Circuit Breakers Higher substation availability and lower environmental impact Authors Carl Ejnar Sölver, ABB High Voltage Products Rasmus Larsson, ABB High Voltage Products 2 ABB ABB

More information

The Intelligent AX1 Switchgear for Medium Voltage

The Intelligent AX1 Switchgear for Medium Voltage The Intelligent AX1 Switchgear for Medium Voltage Leif Lundin, Manager of Research and Development, Division Medium Voltage and Compact Substations, ABB Distribution, Sweden Abstract The newly launched

More information

Gas-Insulated Switchgear up to 300 kv, 63 ka, 4000 A Type 8DN9. Answers for energy.

Gas-Insulated Switchgear up to 300 kv, 63 ka, 4000 A Type 8DN9. Answers for energy. Gas-Insulated Switchgear up to 300 kv, 63 ka, 4000 A Type 8DN9 Answers for energy. Gaining from experience Our switchgear ensures extraordinarily high availability at a low operating cost 2 Our 8D series

More information

SF 6 Gas Insulated Switchgear Type SDF for 170 kv

SF 6 Gas Insulated Switchgear Type SDF for 170 kv Three Phase Encapsulated Type SF 6 Gas Insulated Switchgear Type SDF for 170 kv 06B1-E-0001 With Trustworthy Technology, Structure Fuji Electric as a manufacturer of comprehensive substation equipment

More information

LIMITING SHORT-CIRCUIT CURRENTS IN MEDIUM-VOLTAGE APPLICATIONS

LIMITING SHORT-CIRCUIT CURRENTS IN MEDIUM-VOLTAGE APPLICATIONS LIMITING SHORT-CIRCUIT CURRENTS IN MEDIUM-VOLTAGE APPLICATIONS Terence Hazel Senior Member IEEE Schneider Electric 38050 Grenoble France Abstract The power requirements for large industrial sites is increasing.

More information

Permissible ambient temperature Operation Storage, transport

Permissible ambient temperature Operation Storage, transport The Sitras PRO combined DC protective unit and controller is used in the power supply for DC railways in mass transit and main-line systems up 3,000 V DC. It protects DC switch gear and contact line systems

More information

Medium voltage products UniSec for Smart Grid Air-insulated medium-voltage secondary distribution switchgear

Medium voltage products UniSec for Smart Grid Air-insulated medium-voltage secondary distribution switchgear Medium voltage products UniSec for Smart Grid Air-insulated medium-voltage secondary distribution switchgear Index 3 Overview 4 Standard Levels 6 Monitoring & Control 7 Measurements 8 Protection & Logic

More information

IEC 61850 in ZX Gas-insulated medium voltage switchgear

IEC 61850 in ZX Gas-insulated medium voltage switchgear IEC 61850 in ZX Gas-insulated medium voltage switchgear IEC 61850 in ZX Just as the supply of electrical power is becoming more and more important in a networked world, demands for the integration of electrical

More information

NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems. Safe energy distribution that meets the highest industrial requirements

NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems. Safe energy distribution that meets the highest industrial requirements NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems Safe energy distribution that meets the highest industrial requirements NATUS switchgear systems your advantages minimal use of insulant

More information

Power System for Offshore Wind Power

Power System for Offshore Wind Power Wind-Kraft Journal. German Offshore. 1. Auflage 2008. S. 2-3 und Wind-Kraft Journal. German Offshore. 5. Auflage 2008. S. 38-39. Outlook in the future of German North Sea 2020 ower System for Offshore

More information

Unified requirements for systems with voltages above 1 kv up to 15 kv

Unified requirements for systems with voltages above 1 kv up to 15 kv (1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements apply to

More information

www.siemens.com/energy High Voltage Circuit Breakers 3AP Type 72.5 kv to 800 kv Answers for energy.

www.siemens.com/energy High Voltage Circuit Breakers 3AP Type 72.5 kv to 800 kv Answers for energy. s www.siemens.com/energy High Voltage Circuit Breakers AP Type 7.5 kv to 800 kv Answers for energy. The AP High Voltage Circuit Breakers Available up to 800 kv Decades of our experience in high voltage

More information

How To Choose A Transformer

How To Choose A Transformer Consider open loop MV network as an example source 1 source 2 NC NC NC or NO main MV switchboard A B Detail design of substation NC NC NC NO NC NC switchboard 1 switchboard 2 switchboard 3 MV MV MV LV

More information

Comparison of GIS and AIS systems for urban supply networks

Comparison of GIS and AIS systems for urban supply networks Comparison of GIS and AIS systems for urban supply networks Studies carried out by ABB show that for urban supply networks the combination of HV gas-insulated switchgear (GIS) and HV cable has important

More information

HIS Highly Integrated Switchgear up to 145 kv, 40 ka, 3150 A Type 8DN8

HIS Highly Integrated Switchgear up to 145 kv, 40 ka, 3150 A Type 8DN8 HIS Highly Integrated Switchgear up to 145 kv, 40 ka, 3150 A Type 8DN8 Answers for energy. 2 HIS Highly Integrated Switchgear Solves Space Problems You needn t have any space worries with HIS, the gas-insulated

More information

Secondary Unit Substations

Secondary Unit Substations 14 SWITCHGEAR Secondary Unit Substations Overview Siemens offers a wide variety of unit substation designs to meet customer requirements. A unit substation consists of one or more transformers mechanically

More information

Compact and reliable. Decades of benefits: Gas-insulated switchgear from 52 to 1,100 kv Lothar Heinemann, Franz Besold

Compact and reliable. Decades of benefits: Gas-insulated switchgear from 52 to 1,100 kv Lothar Heinemann, Franz Besold Compact and reliable Decades of benefits: Gas-insulated switchgear from 52 to 1,100 kv Lothar Heinemann, Franz Besold It takes decades of experience to develop sophisticated technology. Over many years,

More information

Engineering innovation

Engineering innovation Eaton's Electrical Engineering Services & Systems Solutions Focus Seamless Solutions for Reliable, Efficient and Safe Power Systems Engineering innovation Progressive solutions for today s power systems

More information

The following table shows approximate percentage wise the

The following table shows approximate percentage wise the SHORT-CIRCUIT CALCULATION INTRODUCTION Designing an electrical system is easy and simple, if only the normal operation of the network is taken into consideration. However, abnormal conditions which are

More information

Advantages of Fixed Circuit Breaker Switchgear

Advantages of Fixed Circuit Breaker Switchgear Advantages of Fixed Circuit Breaker Switchgear by Lionel Mackay, EDF Energy, and Mike Adams, Schneider Electric Ltd Introduction The purpose of this paper is to review the advantages of fixed circuit breaker

More information

Modular Systems, PPMV, 2014 UniPack-G Glass Fiber Reinforced Polyester Compact Secondary Substation

Modular Systems, PPMV, 2014 UniPack-G Glass Fiber Reinforced Polyester Compact Secondary Substation Modular Systems, PPMV, 2014 UniPack-G Glass Fiber Reinforced Polyester Compact Secondary Substation Index News Introduction Applications & Segments Main Components Applicable Standards Technical characteristics

More information

VD4. Vacuum circuit-breaker

VD4. Vacuum circuit-breaker VD4 Vacuum circuit-breaker VD4. The economical solution in power distribution. Applications: Power stations Transformer stations Chemicals industry Steel industry Automotive industry Airport power supply

More information

TenneT. Stakeholder engagement and Consultation Process OWFs. Day 1 ONL 15-162. Michiel Müller / Rob van der Hage

TenneT. Stakeholder engagement and Consultation Process OWFs. Day 1 ONL 15-162. Michiel Müller / Rob van der Hage TenneT ONL 15-162 Stakeholder engagement and Consultation Process OWFs Day 1 Expert Meeting, 15-16.04.2015, Arnhem Michiel Müller / Rob van der Hage Stay tuned. Safety first! Voor uw en onze veiligheid

More information

Gas-insulated switchgear type series 8DN8. up to 170 kv, 63 ka, 4000 A. www.siemens.com/energy. Answers for energy.

Gas-insulated switchgear type series 8DN8. up to 170 kv, 63 ka, 4000 A. www.siemens.com/energy. Answers for energy. Gas-insulated switchgear type series 8DN8 up to 170 kv, 63 ka, 4000 A www.siemens.com/energy Answers for energy. Benefiting from experience Our 8D series of gas-insulated switchgear represents a highly

More information

F.C. Chan General Manager, CLP Engineering Ltd., Hong Kong SAR, China

F.C. Chan General Manager, CLP Engineering Ltd., Hong Kong SAR, China ELECTRIC POWER DISTRIBUTION SYSTEMS F.C. Chan General Manager, CLP Engineering Ltd., Hong Kong SAR, China Keywords: Distribution system planning, Load characteristics, Subtransmission Lines, Distribution

More information

QUALITY CONTROL Prepared: V. van Gastel / team TenneT Reviewed: M. Müller 23.06.2015 Approved: F. Wester 23.06.2015 1. BACKGROUND MATERIAL...

QUALITY CONTROL Prepared: V. van Gastel / team TenneT Reviewed: M. Müller 23.06.2015 Approved: F. Wester 23.06.2015 1. BACKGROUND MATERIAL... POSITION PAPER STAKE HOLDER CONSULTATION PROCESS OFFSHORE GRID NL Type: Position paper Work stream Technical Topic: T.2 Number of J-Tubes Filename ONL 15-060-T2_ J tubes_ bays_pp_v2 Version 3 - Public

More information

e 2 ALPHA Medium Voltage Switchgear Data Sheet K-1.1.2 EN

e 2 ALPHA Medium Voltage Switchgear Data Sheet K-1.1.2 EN e 2 ALPHA Medium Voltage Switchgear Data Sheet K-1.1.2 EN We create ideas with power! ELEKTROMETAL ENERGETYKA SA is a new Polish company providing solutions for electrical power engineering. Our services

More information

Siemens Integrated Substation Condition Monitoring System. Circuit Breaker Monitoring

Siemens Integrated Substation Condition Monitoring System. Circuit Breaker Monitoring Siemens Integrated Substation Condition Monitoring System Circuit Breaker Monitoring System Description Introduction The Circuit Breaker Monitor [CBM] is only one example of the way that the Substation

More information

Service Power Technologies. Retrofitting A future-oriented concept in lifecycle management

Service Power Technologies. Retrofitting A future-oriented concept in lifecycle management Retrofitting A future-oriented concept in lifecycle management Retrofit solutions for gas-insulated switchgear > 50 kv to 170 kv ABB-supplied high-voltage substations generally have a service life of approx.

More information

MEDIUM VOLTAGE SUBSTATION PRACTICES Medium Voltage (MV) is defined as: 1000V< MV 44kV

MEDIUM VOLTAGE SUBSTATION PRACTICES Medium Voltage (MV) is defined as: 1000V< MV 44kV MEDIUM VOLTAGE SUBSTATION PRACTICES MEDIUM VOLTAGE SUBSTATION PRACTICES Medium Voltage (MV) is defined as: 1000V< MV 44kV MEDIUM VOLTAGE SUBSTATION PRACTICES This presentation covers some safety aspects

More information

UniGear ZS1. Medium voltage, arc proof, air insulated switchgear for primary distribution

UniGear ZS1. Medium voltage, arc proof, air insulated switchgear for primary distribution UniGear ZS1 Medium voltage, arc proof, air insulated switchgear for primary distribution UniGear ZS1: an innovative solution for all installation requirements ABB UniGear is medium voltage metal-clad,

More information

Metal Enclosed Switchgears Metal Clad Switchgears Gas Insulated RMU's

Metal Enclosed Switchgears Metal Clad Switchgears Gas Insulated RMU's Metal Enclosed Switchgears Metal Clad Switchgears Gas Insulated RMU's Catalogue 2011 Aktif trade mark for Medium voltage switchgears, Switching equipment and Kiosks with high quality and environmentally

More information

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4 CE - BF - C - en - REV.00 2012.4 APPLICATION CE-BF Switchbords up to 40.5 kv are designed for use in public and industrial distribution system up to 40,5KV for the operation and protection of lines, transformers,

More information

Adaption of Cable Accessories for Onshore and Offshore Substation

Adaption of Cable Accessories for Onshore and Offshore Substation Adaption of Cable Accessories for Onshore and Offshore Substation www.pfisterer.com the power connection Impressum Editor PFISTERER Holding AG Rosenstraße 44 73650 Winterbach Phone +49 7181 7005-0 Fax

More information

From 72.5 kv up to 800 kv. High-Voltage Circuit Breakers. www.siemens.com/energy

From 72.5 kv up to 800 kv. High-Voltage Circuit Breakers. www.siemens.com/energy From 7. up to 800 High-Voltage Circuit Breakers www.siemens.com/energy Germany Content 7 7 Russia India China USA Mexico Brazil Foreword 0 Modular design 0 Control 07 Quenching principles 08 Drive systems

More information

30 ms High Speed Transfer System (HSTS) Product Description

30 ms High Speed Transfer System (HSTS) Product Description 30 ms High Speed Transfer System (HSTS) Product Description 2 30 ms High Speed Transfer System (HSTS) Product Description Content Page 1 General 5 1.1 Description of the 30 ms high speed transfer system

More information

Superconducting and Solid-State Electronic Fault Current Limiter Technologies The shift from demonstration projects to Business-as-Usual solutions

Superconducting and Solid-State Electronic Fault Current Limiter Technologies The shift from demonstration projects to Business-as-Usual solutions Superconducting and Solid-State Electronic Fault Current Limiter Technologies The shift from demonstration projects to Business-as-Usual solutions Dr. Detlev Kirsten & Herbert Piereder Solid State SSFCL

More information

Arc Terminator Active Arc-Resistant Switchgear

Arc Terminator Active Arc-Resistant Switchgear Arc Terminator Active Arc-Resistant Switchgear Increasing safety and productivity by extinguishing internal arcing faults within the switchgear. The Square D Arc Terminator from Schneider Electric offers

More information

Ralf Christian, CEO Low and Medium Voltage. Making Things Right with Totally Integrated Power (TIP)

Ralf Christian, CEO Low and Medium Voltage. Making Things Right with Totally Integrated Power (TIP) Ralf Christian, CEO Low and Medium Voltage Making Things Right with Totally Integrated Power (TIP) siemens.com/hannovermesse Making Things Right with Totally Integrated Power (TIP) Trade LV 100 kw Industrial

More information

Type-Tested Power Distribution Board 8PT with Rear Busbars. sivacon

Type-Tested Power Distribution Board 8PT with Rear Busbars. sivacon Type-Tested Power Distribution Board 8PT with Rear Busbars sivacon The Obvious Solution for Global Challenges SIVACON Type-testing is one of today s important issues for low-voltage technology and will

More information

Unit substation solutions with type SIMOSEC primary switches quick reference guide E50001-F710-A389-X-4A00. Answers for energy.

Unit substation solutions with type SIMOSEC primary switches quick reference guide E50001-F710-A389-X-4A00. Answers for energy. Unit substation solutions with type SIMOSEC primary switches quick reference guide E50001-F710-A389-X-4A00 Answers for energy. Unit substation solution with type SIMOSEC primary switches, dry-type transformer

More information

Application-oriented testing of line differential protection end to end in the field using the corresponding RelaySimTest template

Application-oriented testing of line differential protection end to end in the field using the corresponding RelaySimTest template Application Note Application-oriented testing of line differential protection end to end in the field using the corresponding RelaySimTest template Author Jens Baumeister jens.baumeister@omicron.at Date

More information

C I R E D 21 st International Conference on Electricity Distribution Frankfurt, 6-9 June 2011

C I R E D 21 st International Conference on Electricity Distribution Frankfurt, 6-9 June 2011 SOLUTIONS FOR INTERNAL ARC PROTECTION ACC. IEC 62271-200 WITH PRESSURE RELIEF INTO THE SWITCHGEAR ROOM FOR GAS AND AIR INSULATED MEDIUM VOLTAGE SWITCHGEARS Harethe El Ouadhane Mario Haim Helmut Spitzer

More information

Overhead lines Asset Management in the Belgian network. S. GERMAIN K. VAN DAM B. RISSE JF. GOFFINET Elia Belgium

Overhead lines Asset Management in the Belgian network. S. GERMAIN K. VAN DAM B. RISSE JF. GOFFINET Elia Belgium 21, rue d Artois, F-75008 PARIS B2-208 CIGRE 2012 http : //www.cigre.org Overhead lines Asset Management in the Belgian network. S. GERMAIN K. VAN DAM B. RISSE JF. GOFFINET Elia Belgium SUMMARY The Belgian

More information

POWER TRANSMISSION FROM OFFSHORE WIND FARMS

POWER TRANSMISSION FROM OFFSHORE WIND FARMS POWER TRNSMISSION FROM OFFSHORE WIND FRMS Thorsten Völker University of pplied Sciences Bremerhaven Germany BSTRCT The future for wind power generation in Germany is offshore wind energy. The preferred

More information

Product overview brochure. ABB Medium Voltage Products Our one-stop approach for every medium voltage application

Product overview brochure. ABB Medium Voltage Products Our one-stop approach for every medium voltage application Product overview brochure ABB Medium Voltage Products Our one-stop approach for every medium voltage application Overview ABB meets every need for reliable, safe and energy-efficient medium voltage switchgear,

More information

The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies

The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies DATE: November 17, 1999 REVISION: AUTHOR: John Merrell Introduction In some short circuit studies, the X/R ratio is ignored when comparing

More information

Our brand POWER DYNAMIC PASSION COMMITMENT CREATIVITY. A strong brand for strong products: 8PU Premium. MV Energy

Our brand POWER DYNAMIC PASSION COMMITMENT CREATIVITY. A strong brand for strong products: 8PU Premium. MV Energy Our brand A strong brand for strong products: The ENERGOLINE brand represents our product portfolio of INDUSTRIAL SWITCHGEAR SYSTEMS. Our products are characterized by a high degree of safety, flexibility

More information

Gas-insulated switchgear up to 245 kv, 50 ka, 4000 A Type 8DN9. siemens.com/energy. Answers for energy.

Gas-insulated switchgear up to 245 kv, 50 ka, 4000 A Type 8DN9. siemens.com/energy. Answers for energy. Gas-insulated switchgear up to 245 kv, 50 ka, 4000 A Type 8DN9 siemens.com/energy Answers for energy. Gaining from experience Our switchgear ensures extraordinarily high availability with low operating

More information

Presentation to CIGRE Next Generation Network. Visit of Seine substation

Presentation to CIGRE Next Generation Network. Visit of Seine substation Presentation to CIGRE Next Generation Network Visit of Seine substation Projet Seine 30 août 2012 Contents 0. Presentation of RTE 1. Power supply of «Ile-de-France» and Paris 2. 225 kv Paris substations

More information

Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components

Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components Course No: E02-010 Credit: 2 PDH Boris Shvartsberg, Ph.D., P.E., P.M.P. Continuing Education

More information

How To Understand The Electrical Power Supply Of A Power Supply System

How To Understand The Electrical Power Supply Of A Power Supply System 17 Circuit diagram symbols E 18 CIRCUIT DIAGRAM SYMBOLS electrical network elements three-phase line or cable single-phase line or cable short circuit earth electrode outgoing feeder supply incoming feeder

More information

Requirements for Offshore Grid Connections. in the. Grid of TenneT TSO GmbH

Requirements for Offshore Grid Connections. in the. Grid of TenneT TSO GmbH Requirements for Offshore Grid Connections in the Grid of TenneT TSO GmbH Bernecker Straße 70, 95448 Bayreuth Updated: 21 December 2012 1/10 Requirements for Offshore Grid Connections in the Grid of TenneT

More information

64 Siemens Energy Sector Power Engineering Guide Edition 7.0

64 Siemens Energy Sector Power Engineering Guide Edition 7.0 64 Siemens Energy Sector Power Engineering Guide Edition 7.0 .1 High-Voltage Substations 66.1.1 Turnkey Substations 66.1.2 High-Voltage Switchgear Overview 67.1. Circuit Configuration 68.1.4 Air-Insulated

More information

INTERNATIONAL POWER DISTRIBUTION CONGRESS CIDEL ARGENTINA 2002

INTERNATIONAL POWER DISTRIBUTION CONGRESS CIDEL ARGENTINA 2002 INTERNATIONAL POWER DISTRIBUTION CONGRESS CIDEL ARGENTINA 2002 NEW GAS INSULATED SWITCHGEAR (GIS) FOR ALL MEDIUM VOLTAGE APPLICATIONS H. Fink, ABB Calor Emag Mittelspannungs GmbH; M. Hyrenbach, ABB Calor

More information

Product brochure. Gas-insulated switchgear ELK-3 C, 420 kv High performance in a smaller footprint

Product brochure. Gas-insulated switchgear ELK-3 C, 420 kv High performance in a smaller footprint Product brochure Gas-insulated switchgear ELK-3 C, 420 kv High performance in a smaller footprint ABB and 50 years of GIS innovation ABB is a leader in power and automation technologies that enable utility

More information

The standards mentioned in this document

The standards mentioned in this document The standards mentioned in this document Where can you order IEC publications? Central Offices of the International Electrotechnical Commission 1, rue de Varembé Geneva - Switzerland. The documentation

More information

FAQs-Main switchboard design criteria

FAQs-Main switchboard design criteria FAQs-Main switchboard design criteria Q: What is the Australian standard for main switchboards? Current Australian standard is AS/NZS 3439.1: 2002 originating from IEC 60439. The new series of standard

More information

CAS 36 Ring Main Unit

CAS 36 Ring Main Unit Power distribution networks Ring Main Unit Catalogue 2008 A new path for achieving your electrical installations A comprehensive offer The range is part of a comprehensive offer of products that are perfectly

More information

Relion. Power system protection and automation reference Extending substation life cycle with IEC 61850

Relion. Power system protection and automation reference Extending substation life cycle with IEC 61850 Relion Power system protection and automation reference Extending substation life cycle with IEC 61850 Extending substation life cycle with IEC 61850 A step-by-step power system retrofit approach for optimizing

More information

Preliminary Results from Present Cigre Survey

Preliminary Results from Present Cigre Survey Cigre WG A3-06 HV Equipment Reliability Preliminary Results from Present Cigre Survey Gas Insulated Substations (GIS) DB status : August 2007 Focus on population cards and major failure cards (namely 2004

More information

We appreciate your feedback

We appreciate your feedback Publishing date: 23/07/2015 Document title: We appreciate your feedback Please click on the icon to take a 5 online survey and provide your feedback about this document REPORT ON UNIT INVESTMENT COST INDICATORS

More information

GUIDE FOR TESTING POWER TRANSFORMERS

GUIDE FOR TESTING POWER TRANSFORMERS GUIDE FOR TESTING POWER TRANSFORMERS Routine test 11/11/02 Pagina 1 di 10 INDEX Introduction... 3 1 Dielectric tests Separate-source voltage withstand test... 4 2 Induced voltage test... 5 3 Voltage ratio

More information

What will MV switchgear look like in the future? by Jean-Marc Biasse

What will MV switchgear look like in the future? by Jean-Marc Biasse What will MV switchgear look like in the future? by Jean-Marc Biasse Table of contents Introduction... 2 Brief history of the technologies used in medium voltage switchgear and control gear... 4 Evolution

More information

A3-301 CURRENT INTERRUPTION WITH HIGH VOLTAGE AIR-BREAK DISCONNECTORS. J.H. SAWADA BC HYDRO (Canada) J.G. KRONE HAPAM B.V.

A3-301 CURRENT INTERRUPTION WITH HIGH VOLTAGE AIR-BREAK DISCONNECTORS. J.H. SAWADA BC HYDRO (Canada) J.G. KRONE HAPAM B.V. 21, rue d'artois, F-75008 Paris http://www.cigre.org A3-301 Session 2004 CIGRÉ CURRENT INTERRUPTION WITH HIGH VOLTAGE AIR-BREAK DISCONNECTORS D.F. PEELO* DF PEELO & ASSOCIATES R.P.P. SMEETS KEMA HIGH-POWER

More information

CITY OF GLENDALE CALIFORNIA REPORT TO CITY COUNCIL

CITY OF GLENDALE CALIFORNIA REPORT TO CITY COUNCIL FORM CM-36 CITY OF GLENDALE CALIFORNIA REPORT TO CITY COUNCIL February 7,2012 AGENDA ITEM Request for Approval to Issue a Request for Qualification (RFQ) of Firms, and Request for Proposal (RFP) to Engineer,

More information

ABB Power Systems. Substations References

ABB Power Systems. Substations References ABB Power Systems Substations References Jingzhou, China BA PTPS - 2 - Connection of power from the 3-Gorges-Project to Guandong province (940km away) HVDC Transmission station, Filter banks and GIS Extremely

More information

Power Quality Paper #3

Power Quality Paper #3 The Effect of Voltage Dips On Induction Motors by: M D McCulloch 1. INTRODUCTION Voltage depressions caused by faults on the system affect the performance of induction motors, in terms of the production

More information

A Live Black-start Capability test of a Voltage Source HVDC Converter

A Live Black-start Capability test of a Voltage Source HVDC Converter CIGRÉ-676 2015 CIGRÉ Canada Conference 21, rue d Artois, F-75008 PARIS http : //www.cigre.org Winnipeg, Manitoba, August 31-September 2, 2015 A Live Black-start Capability test of a Voltage Source HVDC

More information

GIS. Gas Insulated Switchgear

GIS. Gas Insulated Switchgear GIS Gas Insulated Switchgear LSIS who has been a leader in electricity and automation in the fields of industry as a consequence of developing stateoftheart technology, presents customer desiring new technology

More information

Welcome IEEE Members and Guests Jan 20, 2014

Welcome IEEE Members and Guests Jan 20, 2014 Welcome IEEE Members and Guests Jan 20, 2014 Copyright Siemens AG 2010. All rights reserved. MEDIUM VOLTAGE GAS INSULATED SWITCHGEAR By Sharif Ahmed of Siemens Canada Copyright Siemens AG 2010. All rights

More information

UFES Active protection for switchgear

UFES Active protection for switchgear Active protection for switchgear ABB AG Oberhausener Strasse 4047 Ratingen, Germany Phone: +49 0-0 Fax: +49 0-7 77 Note: We reserve the right to make technical changes or modify the contents of this document

More information

www.siemens.com/energy High-Voltage Circuit-Breakers: Trends and Recent Developments Answers for energy.

www.siemens.com/energy High-Voltage Circuit-Breakers: Trends and Recent Developments Answers for energy. www.siemens.com/energy High-Voltage Circuit-Breakers: Trends and Recent Developments Answers for energy. Chief Executive Officer Dear Reader, The availability of electric energy is vital for the development

More information

Session Four: Internal Arc Safety in New and Existing Switchgear

Session Four: Internal Arc Safety in New and Existing Switchgear Session Four: Internal Arc Safety in New and Existing Switchgear Richard Blakeley RPS SWITCHGEAR LIMITED 1. INTRODUCTION Commercial pressures are increasing on organisations to maximise their plant utilisation,

More information

Network Consulting for Power Grid Optimization

Network Consulting for Power Grid Optimization Network Consulting for Power Grid Optimization Project experience in India Network Consulting Competences Page 1 Our worldwide representation Manchester The Hague Denver Schenectady San Diego Houston Mexico

More information

The 50Hertz power junctions How substations work

The 50Hertz power junctions How substations work The 50Hertz power junctions How substations work 2 50Hertz The 50Hertz power junctions Secure supply of electricity The basis of modern society It is impossible to imagine modern society without electricity.

More information

Session Eleven: Development of Standards for MV Switchgear Rated for Arc Protection

Session Eleven: Development of Standards for MV Switchgear Rated for Arc Protection Session Eleven: Development of Standards for MV Switchgear Rated for Arc Protection Bryan Johnson Product Group Manager, MV Switchgear ABB South Africa Contents Introduction... 3 What is an internal arc

More information

TENNET, NL OFFSHORE WIND FARM TRANSMISSION SYSTEMS

TENNET, NL OFFSHORE WIND FARM TRANSMISSION SYSTEMS TENNET, NL OFFSHORE WIND FARM TRANSMISSION SYSTEMS 66 kv Systems for Offshore Wind Farms TenneT Report No.: 113799-UKBR-R02, Rev. 2 Document No.: 74107077-1 Date: 2015-03-05 Project name: Tennet, NL Offshore

More information

Hyperlinks are Inactive

Hyperlinks are Inactive Prepared by: NIB/EOB PLANNING GUIDE FOR SINGLE CUSTOMER SUBSTATIONS SERVED FROM TRANSMISSION LINES 05503 Department: Electric T&D Section: T&D Engineering and Technical Support Approved by: G.O. Duru (GOD)

More information

Isolated-Parallel UPS Configuration

Isolated-Parallel UPS Configuration Isolated-Parallel UPS Configuration 1 Inhalt 1 Introduction... 4 2 IP systems configuration... 6 3 Projects... 17 4 Conclusions... 17 2 Abstract The isolated-parallel UPS configuration has become well

More information

Agenda February 28 PM: Medium Voltage. SIPROTEC technical workshop. Medium Voltage: cleverly & reliably switched. Q&A, Conclusion.

Agenda February 28 PM: Medium Voltage. SIPROTEC technical workshop. Medium Voltage: cleverly & reliably switched. Q&A, Conclusion. Agenda February 28 PM: Medium Voltage SIPROTEC technical workshop Medium Voltage: cleverly & reliably switched Q&A, Conclusion Reception End of the workshop Restricted Siemens AG 2013 All rights reserved.

More information

Modern Subterranean Substations in GIS Technology Challenges and Opportunities in Managing Demographic Change and Infrastructure Requirements

Modern Subterranean Substations in GIS Technology Challenges and Opportunities in Managing Demographic Change and Infrastructure Requirements Modern Subterranean Substations in GIS Technology Challenges and Opportunities in Managing Demographic Change and Infrastructure Requirements Bert Strassburger, Peter Glaubitz Siemens AG, Energy Sector,

More information

8. Switchgear and switchgear installations for high voltage up to and including 52 kv (medium voltage)

8. Switchgear and switchgear installations for high voltage up to and including 52 kv (medium voltage) 8 ABB_11_E_08 13.08.2007 9:07 Uhr Seite 379 8. Switchgear and switchgear installations for high voltage up to and including 52 kv (medium voltage) 8.1 Switchgear apparatus (< 52 kv) This voltage range

More information

CONSULTATION PAPER FOR PROPOSED MODIFICATIONS TO THE TRANSMISSION CODE

CONSULTATION PAPER FOR PROPOSED MODIFICATIONS TO THE TRANSMISSION CODE CONSULTATION PAPER FOR PROPOSED MODIFICATIONS TO THE TRANSMISSION CODE Closing date for submission of representations: 30 th Sep 2014, 5 pm 18 AUG 2014 ENERGY MARKET AUTHORITY 991G Alexandra Road #01-29

More information

Annex to the Accreditation Certificate D-ZE-11326-01-00 according to DIN EN ISO/IEC 17065:2013

Annex to the Accreditation Certificate D-ZE-11326-01-00 according to DIN EN ISO/IEC 17065:2013 Deutsche Akkreditierungsstelle GmbH Annex to the Accreditation Certificate D-ZE-11326-01-00 according to DIN EN ISO/IEC 17065:2013 Period of validity: 27.01.2015 to 16.11.2019 Date of issue: 27.01.2015

More information

Gas-Insulated Switchgear up to 420 kv, 50 ka, 5000 A Type 8DQ1. Answers for energy.

Gas-Insulated Switchgear up to 420 kv, 50 ka, 5000 A Type 8DQ1. Answers for energy. Gas-Insulated Switchgear up to 420 kv, 50 ka, 5000 A Type 8DQ1 Answers for energy. Economic efficiency and high operational reliability are the basic characteristics of our substations. 2 Leading worldwide

More information

ALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU

ALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU ALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU George CURCANU, Constantin ILINCA, Ilie SBORA ICMET Craiova, Romania, Calea Bucuresti 144, phone:

More information

For a phase-to-phase voltage between 100 V and 1000 V. The standard ratings are: 400 V - 690 V - 1000 V (at 50 Hz)

For a phase-to-phase voltage between 100 V and 1000 V. The standard ratings are: 400 V - 690 V - 1000 V (at 50 Hz) 24 1. NETWORK CONFIGURATIONS definition Standard IEC 38 defines voltage ratings as follows: - Low voltage () For a phase-to-phase voltage between 100 V and 1000 V. The standard ratings are: 400 V - 690

More information

Modan 3000 ADVANCED TECHNOLOGY, INDUSTRIAL GRADE MOTOR CONTROL CENTER. Systems Products and Services. Motor Control Centers Modan 3000

Modan 3000 ADVANCED TECHNOLOGY, INDUSTRIAL GRADE MOTOR CONTROL CENTER. Systems Products and Services. Motor Control Centers Modan 3000 Systems Products Motor Control Centers Modan 3 Modan 3 UL / CSA ADVANCED TECHNOLOGY, INDUSTRIAL GRADE MOTOR CONTROL CENTER MODAN 3 Motor Control Centers Offer: Over 1 years of Motor Control experience

More information

Modular Systems wind portfolio overview Power Collection and Grid Connection products

Modular Systems wind portfolio overview Power Collection and Grid Connection products Modular Systems wind portfolio overview Power Collection and Grid Connection products Slide 1 Modular Systems wind portfolio Wind power - definition A wind turbine is a device that converts kinetic energy

More information

3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance

3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance SPECIFICATION FOR LOW VOLTAGE SWITCHBOARD SEN I N D E X Description 10 STANDARD TECHNICAL REQUIREMENTS 11 Standards 12 General Operating Conditions 13 General Description Of Switchboard 131 Structure 132

More information