Dynamic Compensation of Reactive Power by Variable Shunt Reactors; - Control Strategies and Algorithms

Size: px
Start display at page:

Download "Dynamic Compensation of Reactive Power by Variable Shunt Reactors; - Control Strategies and Algorithms"

Transcription

1 21, rue d Artois, F PARIS C1-303 CIGRE 2012 http : // Dynamic Compensation of Reactive Power by Variable Shunt Reactors; - Control Strategies and Algorithms C. BENGTSSON* Z. GAJIC M. KHORAMI ABB AB, Transformers ABB AB, SA Products ABB AB, SA Products Ludvika/Sweden Västerås/Sweden Västerås/Sweden SUMMARY There are two main reasons for compensation of reactive power. First, stability reasons especially on long transmission lines and cables (EHV and HV lines/cables); and second, for the purpose of voltage control. Shunt reactors are widely used in order to compensate for capacitive charging of the transmission lines. A Variable Shunt Reactor (VSR) is a shunt reactor where the inductance can be varied in steps. The reactive power consumption of a VSR can increase up to twice its initial value over the whole regulating range. Generally, when there is a slow variation of the load the VSR works as an efficient reactive power compensator in order to fine tune the voltage in the system. VSRs provide dynamic reactive power compensation with the regulation range around 100% (e.g MVAr) and ratings up to 250 MVAr, 500 kv [1]. The market interest in Variable Shunt Reactors is steadily increasing and from a manufacturer s perspective, tender requests for VSRs become more frequent. Although a few VSRs have been in service for several years and such application is not new, it is within the last years that utilities and network planners have become more interested in this option. With increasing market interest in the application of VSRs, the control strategy of VSRs has become an important issue. This paper discusses a possible control strategy of tap-change Variable Shunt Reactors in order to control the voltage level during different load conditions. The operation of a VSR under various network conditions has been simulated and changes in different parameters of the network have been observed. The study includes investigations of the voltage behaviour after running load flow simulations, and results in the formulation of a control strategy of the VSR through modelling and simulation. In order to find an intelligent and accurate tap changing process, various practical issues have been taken into account and several simulations have been done. It is concluded that a combination of both reactive power and voltage can provide an effective and robust control strategy for VSRs. To implement this new strategy, several simulation studies have been done and corresponding parameters have been determined. Finally, the robustness of the proposed control signal has been demonstrated. KEYWORDS Variable Shunt Reactor - Reactive power balance - Voltage stability - Voltage control - Tap changer Simulation - Load Flow claes.t.bengtsson@se.abb.com

2 1. INTRODUCTION The voltage level along an AC transmission line is influenced by two main factors; the capacitive charging and the loading of the line. The capacitive charging, which is the source of reactive power generation (Q C ), depends on the line geometry and the line voltage level; and arises because of the capacitance between its conductors and the earth. On the other hand, when the line is loaded, both the load and the line consume reactive power (Q L ) as inductive electrical elements [2]. Reactive power consumption depends on loading of the line. In an AC transmission system, it is important to keep the balance between generated and consumed reactive power since it is the reactive power balance which decides the voltage stability of the line [3]. In order to achieve the reactive power balance, the line should be loaded at its natural load (SIL) where the generation and consumption of reactive power along the line are equal. When the load varies in the system, the consumption of reactive power changes, and consequently the voltage fluctuates along the line. If the generated reactive power is more than the consumed reactive power, the voltage increases, whereas the voltage decreases if the consumption is more than generation of reactive power [4], [5]. Shunt Reactors are widely used in transmission and distribution networks. They absorb (consume) reactive power by connecting them to the transmission line. Since they decrease the voltage level, they are typically used during light load conditions. Although reactors reduce over voltages during light load conditions, they can also reduce the line loadability if they are not removed under full-load condition [1]. In some applications there is a need to vary the inductive reactive power consumption in steps. In such a case, several shunt reactor units are needed to connect and disconnect frequently which requires more circuit breakers and foot prints at substation. Instead of having several units, one unit that covers the entire power range could be an economical solution []. 2. VSR DESIGN General A Variable Shunt Reactor (VSR) is a reactor where the inductance can be varied in steps, typically by a factor of two. The speed of regulation is in the order of seconds per step as determined by the operation time of the tap changers used [1]. Compared to shunt reactors with a fixed rating, Variable Shunt Reactors provide several benefits to the operators. The dip in the voltage that occurs when the shunt reactor is switched into the network can be reduced by tuning of the reactor. It will also provide a possibility to reduce the number of circuit breakers by replacing several fixed reactors by one variable and thereby also reducing the needed foot print. The variable shunt reactor makes it also simpler to compensate for the voltage variations depending on load variations during summer/winter and day/night. In addition, other benefits exist such as increased flexibility to move reactors to different positions in the network. One example of applications for VSRs is for wind power energy where the generated power as well as the reactive power exchange varies with wind conditions [7]. Due to new added generation, the system requirements on the existing grid will change and new transmission lines (or cables with an even higher need of reactive power compensation) may have to be constructed, or existing ones will be upgraded. Variable Shunt Reactors become an interesting alternative to stabilise the system voltage. Design Aspects Regulated shunt reactors are based on the same concept as a standard shunt reactor. Nevertheless, the design requires special attention and the regulated shunt reactor should be regarded as a separate product type [1]. To be able to regulate the power in the shunt reactor a separate regulating winding or windings is used. This winding is located outside the main winding around the core limb. The High Voltage (HV) inlet to the main winding could either be located as a yoke entrance or as a centre entrance to the winding. High voltage centre entry design is normally used. Maximum reactive power injection is achieved when minimum number of electrical turns is connected and vice versa. When using plus/minus regulation the highest current flows when all turns (highest resistance) are connected. The reactor will get higher losses. This is especially valid for large power 1

3 rated regulated shunt reactors. A so-called coarse/fine regulation consists of two physical regulating windings in comparison with plus/minus that only use one physical winding. At maximum power minimum number of turns is achieved when the whole regulating arrangement is disconnected. Minimum resistance in the reactor winding at highest current will give much lower losses than for plus/minus regulation. Therefore, at high loss evaluations and voltages equal or less than 400 kv a yoke entry with a coarse/fine regulation is normally used. At low loss evaluations, plus/minus regulation is an alternative. At voltages higher than 400 kv a centre entry solution with a plus/minus regulation should be chosen [3]. The design and selection of the tap changer has impact on the shunt reactor application and must be carefully considered in the design. Especially due to the long electrical length of the regulation, the leakage flux inductance in the regulating circuit could reduce the available valid step power and step voltage for the tap changer []. Today, Variable Shunt Reactors with ratings up to 200 MVAr and 420 kv are in operation. Figure 1 shows a MVAr, 420 kv Variable Shunt Reactor installed in a European network. Figure 1: Variable Shunt Reactor, MVAr, 420 kv 3. CONTROL STRATEGY OF VSR USING VOLTAGE AS CONTROL SIGNAL As with the traditional control of switchable Fixed Shunt Reactors, the first approach to control tapchanging of Variable Shunt Reactors was to use the voltage magnitude at the busbar where the reactor is connected. Here the busbar voltage is used as a feedback to control the reactor. In order to investigate the operation process, problems and results of using this control strategy a simple network has been simulated. Figure 2, shows a single phase pi model of a 420kV, 300km transmission line which is connected to a voltage source from one side and connected to a constant impedance load at the other side. The VSR is connected to the same busbar as the load. 2

4 Figure 2: The Single Phase pi model of 300 km 420kV transmission line Table I, indicates source and line parameters of this simple network. These parameters are taken from an existing transmission network. According to these parameters, the SIL level of this line is about 194MW. Table I: The parameters of the simple simulated network Source Parameters Line Parameters V s kv rms/ph Length 300 km f s 50 Hz R L 0.02 /ph.km R s 2.45 X L 0.31 /ph.km L s 70.2e-03 H b 3.37 µs/ph.km Figure 3, shows the voltage signal changes during the operation of On Load Tap Changer (OLTC). In this figure, each voltage step is corresponding to one tap of OLTC. These small changes are referred as signal step size further in this text. Figure 3: The voltage steps during simulated tap-change VSR operation In conclusion, the VSR is working properly when using the voltage as the Control Signal. However, the voltage steps are small and in the range of 0.3kV 0.43kV (i.e. 0.12% % of the reference voltage) which are so small that they can barely be detected by the IED (Intelligent Electronic 3

5 Device). In practice, considering the measurement devices errors and noise, the control relay cannot detect such small changes in voltage which is a problem to obtain accurate tap-changer control [8]. 4. CONTROL STRATEGY OF VSR USING COMBINATION OF VOLTAGE AND REACTIVE POWER AS CONTROL SIGNAL A more robust control signal is hence needed in order to have more precise tap changing process. In order to achieve this for different network conditions, it is favourable to take advantage of both voltage and reactive power to control the VSR tap changing process. To make a new Control Signal, which comprises both voltage and reactive power, one approach is to add up voltage and reactive power balance and make a new Control Signal. However, since the reactive signal variation is a couple of thousand times greater than the voltage signal variation, the contribution of voltage will be neglected. For this reason, both signals should have comparable values and have same dimensions. On the other hand, due to practical issues regarding measuring and calculation of reactive power consumption on the line, to make the control strategy insensitive to the remained reactive power unbalance value (Residual Reactive Power), it is desired to reduce the contribution of this reactive signal by making it smaller as much as possible. In order to choose a factor to scale down the reactive power contribution, some considerations should be taken. First, the dimension of this factor should be Volts/VAr in order to make the final dimension as Volts. Second, as this factor has a direct effect on the signal s step size, it should be proportional to the voltage regulating range (e.g. ±2% of reference voltage). Third, it is a reasonable decision to use the rated reactive power of each VSR step (approx. 2.5MVAr for this particular VSR design) to make this signal relatively small and make the desired dimension. As a result, factor K is defined as follows: Where, V ref is the single phase reference voltage for a 420kV voltage level and is equal to 242.5kV. (1) Consequently, the final combined control signal would be as follows: Where, V Busbar is the voltage magnitude at the busbar which is intended for regulation, Q C2 is the capacitive reactive power generated by the respective equivalent line capacitance at the load side (C 2 ), Q I is the inductive reactive power consumed by the equivalent line inductance (L), and Q IR is the inductive reactive power consumed by VSR itself. K 1 and K 2 are setting parameters which change the influence of the respective contributions of capacitive and inductive reactive powers of the line. In a real network there are always a percentage of the target line which should be taken into account in the reactive power balance equation, i.e. the VSR is intended to compensate for a part of the line s generated capacitive reactive power according to the network topology. It is assumed that in the pi model, the equivalent line capacitance which is closer to the busbar (C 2 ) has more contribution on reactive power balance and voltage stability on that busbar. Q C2 is calculated from capacitance of the line (C 2 ) and the voltage level (V), while Q I is calculated based on line inductance (L) and current flowing in the line (I L ). As can be inferred from expression (2), this new combined control signal has the contribution of both voltage and reactive power. There is a correlation between different K values and signal s step sizes which needs a trade-off between these two in order to find the optimal K value. For this reason, several simulations with different K factors have been done. Table II indicates the results of all these experiments for each load level. The results from pure voltage control strategy have been repeated in every part of the table which makes it easier to compare the results. (2) 4

6 Table II: The comparison between the results of pure voltage control and combined voltage and reactive power control strategy with different K values Load Pure Voltage Control V-Q Control ±2% Signal V-Q Control ±2% Signal V-Q Control ±2% Signal V-Q Control ±2% Signal MW MVAR 2% K1=1 K2=1 Step K1=1 K2=1 Step K1=1 K2=1 Step K1=1 K2=1 Step K= 2.5%*(0.002) K= 5%*(0.002) K= 7.5%*(0.002) K= 10%*(0.002) 0.17% 0.19% % 0.21% 0.14% % 0.21% % % 0.15% 0.18% % 0.17% 0.18% 0.20% 45 22, Load Pure Voltage Control V-Q Control ±2% Signal V-Q Control ±2% Signal V-Q Control ±2% Signal V-Q Control ±2% Signal MW MVAR 2% K1=1 K2=1 Step K1=1 K2=1 Step K1=1 K2=1 Step K1=1 K2=1 Step K= 12.5%*(0.002) K= 15%*(0.002) K= 17.5%*(0.002) K= 20%*(0.002) 0.34% 0.20% 0.3% 0.37% % 0.19% 0.% 0.3% % % 0.30% 0.18% 0.30% 0.20% 45 22, % % 0.% % 0.35% 0.21% 0.34% % 0.3% Load Pure Voltage Control V-Q Control ±2% Signal V-Q Control ±2% Signal V-Q Control ±2% Signal V-Q Control ±2% Signal MW MVAR 2% K1=1 K2=1 Step K1=1 K2=1 Step K1=1 K2=1 Step K1=1 K2=1 Step K= 22.5%*(0.002) K= 25%*(0.002) K= 27.5%*(0.002) K= 30%*(0.002) 0.44% 0.4% 0.50% % 0.52% 0.41% 0.45% 0.47% % ,5 0.40% 0.39% 0.42% % 0.% 0.30% 0.45% 0.44% % % % 0.45% 0.45% 0.34% Load Pure Voltage Control V-Q Control ±2% Signal V-Q Control ±2% Signal V-Q Control ±2% Signal MW MVAR 2% K1=1 K2=1 Step K1=1 K2=1 Step K1=1 K2=1 Step K= 40%*(0.002) K= 80%*(0.002) K= 100%*(0.002) 0.3% 0.1% 0.% 1.02% % 1.2% 0.3% 0.59% 0.58% 1% % 1.2% ,5 0.35% 0.5% 0.% 0.43% 0.58% 0.9% % 0.93% % % % 1.12% 0.8% 1.12% 0.7% 1.09% 0.5% 1.09% % 0.40% 0.53% 0.9% % 1.07% This particular reactor has tap positions, and the tap-changing order is in opposite direction, i.e. it starts from tap position (Lowest amount of reactive power consumption) and final position is 1 (highest amount of reactive power consumption). The VSR lowers the voltage by tapping from tap 5

7 position to tap position 1. Table II indicates the finally reached tap position number after all tap changer operation for each load level. The control signal step sizes presented in Table II are provided as the percentage of reference voltage. These values correspond to minimum and maximum changes in the control signal amplitude during OLTC operation in each load level. In order to achieve signal s step sizes higher than 0.5% of reference voltage, the scaling factor (K) could be either 80% (K=0.001) or 100% (K=0.002) of its original value. However, since there is no significant difference between the tap positions in these two cases, a more robust signal will be achieved by choosing K equal to its original value (i.e. K=0.002) as there are larger signal s step sizes available in this case. K 1 and K 2 scale the respective contributions of capacitive and inductive reactive powers of the line. Since Q C2 is almost 50% of total generated capacitive reactive power, keeping K 1 equal to 1 means that the contribution of capacitive reactive power is 50%, i.e. 50% of the line capacitive effect is contributing the reactive power balance signal. Similarly, to have 50% of the line inductive effect contribution, factor K 2 could be selected as 0.5. Table III indicates the final resulting tap positions and step sizes after changing the factor K 2. Table III: The final tap position of VSR and signal s step size using K2=0.5 for different load levels and using combined control strategy Load MW MVAR 2% K1=1 K2=0.5 Step K1=1 K2= , Pure Voltage Control 18 2 V-Q Control ±2% K= 80%*(0.002) Signal 0.57% 1% 0.5% 0.95% 0.9% 0.53% 0.88% 0.52% 0.8% 0.52% 0.84% 0.5% 0.83% V-Q Control ±2% K= 100%*(0.002) Signal Step 0.8% 1.2% 0.7% 1.15% 0.5% 1.1% 0.4% 1.08% 0.2% 1.02% 0.3% 1.03% 0.0% 1% As can be seen, although the signal s step sizes have been slightly decreased in both cases (K equal to 80% and 100% of its original value), they are still higher than 0.5% of reference voltage. However, there is a tangible decrease in final tap position s number which makes it closer to the results of pure voltage control; especially in case of K equal to 80% of its original value. It should be noted that having more taps up (smaller tap position number), which is happened at higher load levels, is favourable since it makes the final voltage level to become closer to the reference voltage. 5. CONCLUSION It is concluded that a combination of both reactive power and voltage can provide an effective and robust control strategy for VSRs. To implement this new strategy, several simulation studies have been done and corresponding parameters have been determined. A control signal comprising both reactive power and voltage with appropriate scaling factors is proposed. It is demonstrated that this strategy is robust and can provide a reliable control of Variable Shunt Reactors.

8 BIBLIOGRAPHY [1] C. Bengtsson, T. Olsson and L. Lidén, Recent Advances in Shunt Reactor Design (GCC Power, Riyadh, Nov. 2009). [2] Åke Carlson, Shunt Reactor Manual (ABB Power Technology Products/Transformers, Ludvika-Sweden, ). [3] L. Yamazaki, J C Mendes and C. Bengtsson, VSR Variable Shunt Reactors (Cigré VI Workspot, Foz Du Iguacu, April 2010). [4] Zoran Gaji, Birger Hillström, Fahrudin Meki, HV Shunt Reactor Secrets for Protection Engineers (ABB paper published at WPRC 2003 Conference). [5] Claes Bengtsson, Tomas Olosson, Kent Olsson, Riyadh S. Al-Nassar, Luis Chavez, Design and testing of 300 Mvar shunt reactors (CIGRÉ 2008, Paper A2-305). [] ABB Variable Shunt Reactors; Applications (ABB VSR pamphlet 1ZSE ). [7] M. Bollen et al., Application of Regulated Shunt Reactor for Off-shore Wind Farms (Cigré A2/D1 Colloquium Bruges 2007, paper PS3-42). [8] M. Khorami, Application Fields and Control Principles of Variable Shunt Reactors with Tap- Changer (M.Sc Thesis, Chalmers University of Technology, Västerås-Sweden 20). 7

MOHAMMAD KHORAMI. Examiner: Dr. Anh Tuan Le Senior Lecturer, Electric Power Engineering, Chalmers University of Technology. Master of Science Thesis

MOHAMMAD KHORAMI. Examiner: Dr. Anh Tuan Le Senior Lecturer, Electric Power Engineering, Chalmers University of Technology. Master of Science Thesis Application Fields and Control Principles of Variable Shunt Reactors with Tap-Changer Investigation of Possible Control Strategies of Variable Shunt Reactors through Simulation of a Power System under

More information

EMTP STUDIES PERFORMED TO INSERT LONG AC CABLES IN THE FRENCH GRID

EMTP STUDIES PERFORMED TO INSERT LONG AC CABLES IN THE FRENCH GRID Tension (kv) Impedance (Ohms) EMTP STUDIES PERFORMED TO INSERT LONG AC CABLES IN THE FRENCH GRID frequency (Hz) Simon DESCHANVRES Yannick VERNAY RTE, CNER, Substations Department t (ms) EMTP-RV Users Group

More information

Transformers. Special transformers Reactors products

Transformers. Special transformers Reactors products Transformers Special transformers Reactors products Reactors Custom designed, custom built ABB Oy Transformers has extensive experience and numerous references from different reactor applications, having

More information

Voltage regulation in distribution systems - Tap changer and Wind Power

Voltage regulation in distribution systems - Tap changer and Wind Power CODEN:LUTEDX/(TEIE-5270)/1-59/(2010) Industrial Electrical Engineering and Automation Voltage regulation in distribution systems - Tap changer and Wind Power David Sáez Romero D of Industrial Electrical

More information

CO-ORDINATION OF PARALLEL AC-DC SYSTEMS FOR OPTIMUM PERFORMANCE

CO-ORDINATION OF PARALLEL AC-DC SYSTEMS FOR OPTIMUM PERFORMANCE CO-ORDINATION OF PARALLEL AC-DC SYSTEMS FOR OPTIMUM PERFORMANCE Ana Diez Castro & Rickard Ellström Ying Jiang Häfner Christer Liljegren Vattenfall Utveckling AB ABB Power Systems Gotlands Energiverk AB

More information

Voltage Stability Improvement using Static Var Compensator in Power Systems

Voltage Stability Improvement using Static Var Compensator in Power Systems Leonardo Journal of Sciences ISSN 1583-0233 Issue 14, January-June 2009 p. 167-172 Voltage Stability Improvement using Static Var Compensator in Power Systems Department of Electrical/Computer Engineering,

More information

Requirements for Offshore Grid Connections. in the. Grid of TenneT TSO GmbH

Requirements for Offshore Grid Connections. in the. Grid of TenneT TSO GmbH Requirements for Offshore Grid Connections in the Grid of TenneT TSO GmbH Bernecker Straße 70, 95448 Bayreuth Updated: 21 December 2012 1/10 Requirements for Offshore Grid Connections in the Grid of TenneT

More information

HVDC 2000 a new generation of high-voltage DC converter stations

HVDC 2000 a new generation of high-voltage DC converter stations HVDC 2000 a new generation of high-voltage DC converter stations Improved performance and robustness, shorter lead times and faster delivery, plus reduced maintenance needs, were the development goals

More information

INTRODUCTION TO HARMONIC ASSESSMENT IN POWER SYSTEMS

INTRODUCTION TO HARMONIC ASSESSMENT IN POWER SYSTEMS INTRODUCTION TO HARMONIC ASSESSMENT IN POWER SYSTEMS LIST OF CONTENT 1. INTRODUCTION... 1 2. HARMONIC VOLTAGE ASSESSMENT REQUIREMENT IN THE UK... 2 3. THE ASSESSMENT... 2 3.1. SYSTEM MODELLING...3 3.2.

More information

General Validation Test Program for Wind Power Plants Connected to the Hydro-Québec Transmission System

General Validation Test Program for Wind Power Plants Connected to the Hydro-Québec Transmission System General Validation Test Program for Wind Power Plants Connected to the Hydro-Québec Transmission System Direction Planification des actifs et expertise de transport February 2011 TABLE OF CONTENTS 1. CONDUCTING

More information

VOLTAGE CONTROL IN DISTRIBUTION SYSTEMS AS A LIMITATION OF THE HOSTING CAPACITY FOR DISTRIBUTED ENERGY RESOURCES

VOLTAGE CONTROL IN DISTRIBUTION SYSTEMS AS A LIMITATION OF THE HOSTING CAPACITY FOR DISTRIBUTED ENERGY RESOURCES VOLTAGE CONTROL IN DISTRIBUTION SYSTEMS AS A LIMITATION OF THE HOSTING CAPACITY FOR DISTRIBUTED ENERGY RESOURCES C. Schwaegerl*, M.H.J. Bollen, K. Karoui #, A. Yagmur + *Siemens AG, # Tractebel STRI AB

More information

MINISTERIE VAN ECONOMISCHE ZAKEN GENERAL COST COMPARISON BETWEEN UNDERGROUND CABLES AND O.H. LINE SYSTEMS FOR H.V. TRANSMISSION

MINISTERIE VAN ECONOMISCHE ZAKEN GENERAL COST COMPARISON BETWEEN UNDERGROUND CABLES AND O.H. LINE SYSTEMS FOR H.V. TRANSMISSION MINISTERIE VAN ECONOMISCHE ZAKEN GENERAL COST COMPARISON BETWEEN UNDERGROUND CABLES AND O.H. LINE SYSTEMS FOR H.V. TRANSMISSION REPORT ON NETWORK RELIABILITY ASPECTS OF THE CHOICE LINE VERSUS CABLE FOR

More information

Bill is the author of 15 papers and lectures on transmission lines and other power system topics.

Bill is the author of 15 papers and lectures on transmission lines and other power system topics. Transmission Lines Electricity s Highway This talk starts with an explanation of Surge Impedance Loading and demonstrates how it is used for transmission line work. The St. Clair Curve widely used in transmission

More information

Product brochure Multi Functional Switchgear PASS M00 72.5 kv Flexible and compact switchgear solutions for windfarms

Product brochure Multi Functional Switchgear PASS M00 72.5 kv Flexible and compact switchgear solutions for windfarms Product brochure Multi Functional Switchgear PASS M00 72.5 kv Flexible and compact switchgear solutions for windfarms The future of Wind Farms As offshore wind farms move towards deploying higher capacity

More information

Study to Determine the Limit of Integrating Intermittent Renewable (wind and solar) Resources onto Pakistan's National Grid

Study to Determine the Limit of Integrating Intermittent Renewable (wind and solar) Resources onto Pakistan's National Grid Pakistan Study to Determine the Limit of Integrating Intermittent Renewable (wind and solar) Resources onto Pakistan's National Grid Final Report: Executive Summary - November 2015 for USAID Energy Policy

More information

2012 San Francisco Colloquium

2012 San Francisco Colloquium 2012 San Francisco Colloquium http : //www.cigre.org HVDC and Power Electronic Systems for Overhead Line and Insulated Cable Applications B4-8 Trans Bay Cable A Breakthrough of VSC Multilevel Converters

More information

The design and performance of Static Var Compensators for particle accelerators

The design and performance of Static Var Compensators for particle accelerators CERN-ACC-2015-0104 Karsten.Kahle@cern.ch The design and performance of Static Var Compensators for particle accelerators Karsten Kahle, Francisco R. Blánquez, Charles-Mathieu Genton CERN, Geneva, Switzerland,

More information

OFFSHORE WIND FARM ELECTRICAL CONNECTION OPTIONS. W.Grainger 1 and N.Jenkins 2 SYNOPSIS

OFFSHORE WIND FARM ELECTRICAL CONNECTION OPTIONS. W.Grainger 1 and N.Jenkins 2 SYNOPSIS OFFSHORE WIND FARM ELECTRICAL CONNECTION OPTIONS W.Grainger 1 and N.Jenkins 2 1 Border Wind Ltd, Hexham 2 Dept of Electrical Engineering and Electronics, UMIST SYNOPSIS The development of large scale offshore

More information

100% Stator Ground Fault Detection Implementation at Hibbard Renewable Energy Center. 598 N. Buth Rd 3215 Arrowhead Rd

100% Stator Ground Fault Detection Implementation at Hibbard Renewable Energy Center. 598 N. Buth Rd 3215 Arrowhead Rd 100% Stator Ground Fault Detection Implementation at Hibbard Renewable Energy Center Introduction Roger Hedding Steven Schoenherr, P.E. ABB Inc. Minnesota Power 598 N. Buth Rd 3215 Arrowhead Rd Dousman,

More information

Instrument Transformers Application Guide

Instrument Transformers Application Guide Instrument Transformers Application Guide Edited by ABB AB High Voltage Products Department: Marketing & Sales Text: Knut Sjövall, ABB Layout, 3D and images: Mats Findell, ABB SE-771 80 LUDVIKA, Sweden

More information

Digital Energy ITI. Instrument Transformer Basic Technical Information and Application

Digital Energy ITI. Instrument Transformer Basic Technical Information and Application g Digital Energy ITI Instrument Transformer Basic Technical Information and Application Table of Contents DEFINITIONS AND FUNCTIONS CONSTRUCTION FEATURES MAGNETIC CIRCUITS RATING AND RATIO CURRENT TRANSFORMER

More information

A Live Black-start Capability test of a Voltage Source HVDC Converter

A Live Black-start Capability test of a Voltage Source HVDC Converter CIGRÉ-676 2015 CIGRÉ Canada Conference 21, rue d Artois, F-75008 PARIS http : //www.cigre.org Winnipeg, Manitoba, August 31-September 2, 2015 A Live Black-start Capability test of a Voltage Source HVDC

More information

Dually Fed Permanent Magnet Synchronous Generator Condition Monitoring Using Stator Current

Dually Fed Permanent Magnet Synchronous Generator Condition Monitoring Using Stator Current Summary Dually Fed Permanent Magnet Synchronous Generator Condition Monitoring Using Stator Current Joachim Härsjö, Massimo Bongiorno and Ola Carlson Chalmers University of Technology Energi och Miljö,

More information

Modeling of Transmission Lines

Modeling of Transmission Lines Modeling of Transmission Lines Electric Power Transmission The electric energy produced at generating stations is transported over high-voltage transmission lines to utilization points. The trend toward

More information

Power Transmission and Distribution. Shunt reactors for medium and highvoltage. From development to use

Power Transmission and Distribution. Shunt reactors for medium and highvoltage. From development to use Power Transmission and Distribution Shunt reactors for medium and highvoltage networks: From development to use From the beginning up to today more quality and reliability for your network A safe power

More information

On-line monitoring of substation condition a Romanian experience. V. ZAHARESCU, Vl. ROSCA Nova Industrial SA. CN Transelectrica SA Romania

On-line monitoring of substation condition a Romanian experience. V. ZAHARESCU, Vl. ROSCA Nova Industrial SA. CN Transelectrica SA Romania 21, rue d Artois, F-75008 PARIS http : //www.cigre.org B3_201 CIGRE 2012 On-line monitoring of substation condition a Romanian experience C. MOLDOVEANU*, V. BREZOIANU, S. GAL, V. METIU, A. VASILE, V. URSIANU,

More information

Chapter 3 AUTOMATIC VOLTAGE CONTROL

Chapter 3 AUTOMATIC VOLTAGE CONTROL Chapter 3 AUTOMATIC VOLTAGE CONTROL . INTRODUCTION TO EXCITATION SYSTEM The basic function of an excitation system is to provide necessary direct current to the field winding of the synchronous generator.

More information

2012 San Francisco Colloquium

2012 San Francisco Colloquium 2012 San Francisco Colloquium http : //www.cigre.org Advances in voltage source converter (VSC) technologies B4-6 500 kv VSC Transmission System for lines and cables B. JACOBSON, B. WESTMAN, M. P. BAHRMAN*

More information

CAPACITOR BANK TESTING SWP

CAPACITOR BANK TESTING SWP 1. PURPOSE AND SCOPE The purpose of this Standard Work Practice (SWP) is to standardise and prescribe the method for testing Capacitor Banks including capacitors, tuning reactors and inrush limiting reactors.

More information

Power System review W I L L I A M V. T O R R E A P R I L 1 0, 2 0 1 3

Power System review W I L L I A M V. T O R R E A P R I L 1 0, 2 0 1 3 Power System review W I L L I A M V. T O R R E A P R I L 1 0, 2 0 1 3 Basics of Power systems Network topology Transmission and Distribution Load and Resource Balance Economic Dispatch Steady State System

More information

System Protection Schemes in Eastern Denmark

System Protection Schemes in Eastern Denmark System Protection Schemes in Eastern Denmark Joana Rasmussen COWI A/S, Energy Department System Protection Schemes in Eastern Denmark 1.Advanced system protection schemes are investigated and perspectives

More information

Estimating Line-Flow Limits

Estimating Line-Flow Limits Estimating Line-Flow Limits University of Wisconsin-Madison May 1, 2013 Specifying reasonable line-flow limits requires two quantities: the surge impedance loading for the line and an estimate of the line

More information

COMPARISON OF THE FACTS EQUIPMENT OPERATION IN TRANSMISSION AND DISTRIBUTION SYSTEMS

COMPARISON OF THE FACTS EQUIPMENT OPERATION IN TRANSMISSION AND DISTRIBUTION SYSTEMS COMPARISON OF THE FACTS EQUIPMENT OPERATION IN TRANSMISSION AND DISTRIBUTION SYSTEMS Afshin LASHKAR ARA Azad University of Dezfoul - Iran A_lashkarara@hotmail.com Seyed Ali NABAVI NIAKI University of Mazandaran

More information

Voltage Source HVDC Overview Mike Barnes Tony Beddard

Voltage Source HVDC Overview Mike Barnes Tony Beddard Voltage Source HVDC Overview Mike Barnes Tony Beddard Note: This is a version with images removed which have copyrighted other than from the University of Manchester, for web publication. Should a conference

More information

WHY DIFFERENTIAL? instruments connected to the circuit under test and results in V COMMON.

WHY DIFFERENTIAL? instruments connected to the circuit under test and results in V COMMON. WHY DIFFERENTIAL? Voltage, The Difference Whether aware of it or not, a person using an oscilloscope to make any voltage measurement is actually making a differential voltage measurement. By definition,

More information

SIZING THE PRIMARY POWER SYSTEM FOR RESISTANCE WELDERS

SIZING THE PRIMARY POWER SYSTEM FOR RESISTANCE WELDERS SIZING THE PRIMARY POWER SYSTEM FOR RESISTANCE S By Jack Farrow, May, 2004 WELDING TECHNOLOGY CORPORATION ABSTRACT Information on how to select the correct size of substation transformer and 480V bus to

More information

Line Reactors and AC Drives

Line Reactors and AC Drives Line Reactors and AC Drives Rockwell Automation Mequon Wisconsin Quite often, line and load reactors are installed on AC drives without a solid understanding of why or what the positive and negative consequences

More information

Integration of Distributed Generation in the Power System. IEEE Press Series on Power Engineering

Integration of Distributed Generation in the Power System. IEEE Press Series on Power Engineering Brochure More information from http://www.researchandmarkets.com/reports/2171489/ Integration of Distributed Generation in the Power System. IEEE Press Series on Power Engineering Description: A forward

More information

PRE COMMISSIONING TESTS ON EQUIPMENT AT 33/11 KV SUB STATIONS

PRE COMMISSIONING TESTS ON EQUIPMENT AT 33/11 KV SUB STATIONS PRE COMMISSIONING TESTS ON EQUIPMENT AT 33/11 KV SUB STATIONS TESTS ON TRANSFORMERS 1. IR Values a) For 33/11 KV Power Transformer 2500 V megger is to be need. b) Power Transformer neutral Earthing is

More information

Assessment of the Technical Issues relating to Significant Amounts of EHV Underground Cable in the All-island Electricity Transmission System

Assessment of the Technical Issues relating to Significant Amounts of EHV Underground Cable in the All-island Electricity Transmission System Assessment of the Technical Issues relating to Significant Amounts of EHV Underground Cable in the All-island Electricity Transmission System Summary Report November 2009 Technical Report on using EHV

More information

Understanding Power Factor and How it Affects Your Electric Bill. Presented by Scott Peele PE

Understanding Power Factor and How it Affects Your Electric Bill. Presented by Scott Peele PE Understanding Power Factor and How it Affects Your Electric Bill Presented by Scott Peele PE Understanding Power Factor Definitions kva, kvar, kw, Apparent Power vs. True Power Calculations Measurements

More information

Power transformers. Phase shifting transformers Reliable and efficient power flow control

Power transformers. Phase shifting transformers Reliable and efficient power flow control Power transformers Phase shifting transformers Reliable and efficient power flow control 2 Phase shifting transformers Eliminating bottlenecks in AC networks Phase shifting transformers (PST) are crucial

More information

Distributed Generation and Power Quality Case Study

Distributed Generation and Power Quality Case Study 16 Distributed Generation and Power Quality Case Study Vu Van Thong and Johan Driesen C16.1 DISTRIBUTION NETWORK A segment of an existing Belgian medium-voltage distribution system is used to study the

More information

High Voltage Power Supplies for Analytical Instrumentation

High Voltage Power Supplies for Analytical Instrumentation ABSTRACT High Voltage Power Supplies for Analytical Instrumentation by Cliff Scapellati Power supply requirements for Analytical Instrumentation are as varied as the applications themselves. Power supply

More information

LAB1 INTRODUCTION TO PSS/E EE 461 Power Systems Colorado State University

LAB1 INTRODUCTION TO PSS/E EE 461 Power Systems Colorado State University LAB1 INTRODUCTION TO PSS/E EE 461 Power Systems Colorado State University PURPOSE: The purpose of this lab is to introduce PSS/E. This lab will introduce the following aspects of PSS/E: Introduction to

More information

EXTENDING THE LIFE OF POWER FACTOR CAPACITORS

EXTENDING THE LIFE OF POWER FACTOR CAPACITORS by John Houdek, President, Allied Industrial Marketing, Inc., and Cesar Chavez, Engineering Manager, ARTECHE / Inelap Abstract: The addition of power factor improvement capacitors to individual motors

More information

(3 )Three Phase Alternating Voltage and Current

(3 )Three Phase Alternating Voltage and Current EEE 2015 EECTRCS (3) Monophase 1 Three phase Three phase electric power is a common method of alternating current electric power generation, transmission, and distribution. t is a type of polyphase system

More information

SURVEY OF HARMONIC DISTORTION IN LV AND MV NETWORKS: RESULTS AND CORRECTIVE STRATEGIES

SURVEY OF HARMONIC DISTORTION IN LV AND MV NETWORKS: RESULTS AND CORRECTIVE STRATEGIES SURVEY OF HARMONIC DISTORTION IN LV AND MV NETWORKS: RESULTS AND CORRECTIVE STRATEGIES E Bompard*, E Carpaneto*, R Napoli*, P Ribaldone**, C Vercellino** * Dipartimento di Ingegneria Elettrica Industriale,

More information

Simulation of Cable Overloading Problem on a University Distribution System

Simulation of Cable Overloading Problem on a University Distribution System Advance in Electronic and Electric Engineering. ISSN 2231-1297, Volume 3, Number 6 (2013), pp. 765-770 Research India Publications http://www.ripublication.com/aeee.htm Simulation of Cable Overloading

More information

Product Data Bulletin

Product Data Bulletin Product Data Bulletin Power System Harmonics Causes and Effects of Variable Frequency Drives Relative to the IEEE 519-1992 Standard Raleigh, NC, U.S.A. INTRODUCTION This document describes power system

More information

Size template. Grid Connection Masterclass Energex John Lansley Senior Network Solutions Engineer

Size template. Grid Connection Masterclass Energex John Lansley Senior Network Solutions Engineer Size template Grid Connection Masterclass Energex John Lansley Senior Network Solutions Engineer The average system size has doubled since 2010 Key Network Issues Reverse power on up to 12 off 11 kv feeders

More information

ANCILLARY EQUIPMENT AND ELECTRICAL EQUIPMENT Power Supply Systems and Electrical Equipment for Desalination Plants - Y.M. Hamud and A.H.

ANCILLARY EQUIPMENT AND ELECTRICAL EQUIPMENT Power Supply Systems and Electrical Equipment for Desalination Plants - Y.M. Hamud and A.H. POWER SUPPLY SYSTEMS AND ELECTRICAL EQUIPMENT FOR DESALINATION PLANTS Y.M. Hamud and A.H. Anwar Abu Dhabi Water and Electricity Authority, Abu Dhabi, UAE Keywords : Electrical System, Network for Desalination,

More information

Cost Benefit Methodology for Optimal Design of Offshore Transmission Systems

Cost Benefit Methodology for Optimal Design of Offshore Transmission Systems Centre for Sustainable Electricity and Distributed Generation Cost Benefit Methodology for Optimal Design of Offshore Transmission Systems Predrag Djapic and Goran Strbac July 2008 FUNDED BY BERR URN 08/1144

More information

DEFINING AND COMPUTING EQUIVALENT INDUCTANCES OF GAPPED IRON CORE REACTORS

DEFINING AND COMPUTING EQUIVALENT INDUCTANCES OF GAPPED IRON CORE REACTORS ISEF 20 - XV International Symposium on Electromagnetic Fields in Mechatronics, Electrical and Electronic Engineering Funchal, Madeira, September -3, 20 DEFINING AND COMPUTING EQUIVALENT INDUCTANCES OF

More information

SIMULATING HYBRID ENERGY GRIDS IN SMART CITIES FOCUS ON ELECTRIC ENERGY SYSTEMS

SIMULATING HYBRID ENERGY GRIDS IN SMART CITIES FOCUS ON ELECTRIC ENERGY SYSTEMS Sawsan Henein AIT Austrian Institute of Technology Electric Energy Systems Research Group SIMULATING HYBRID ENERGY GRIDS IN SMART CITIES FOCUS ON ELECTRIC ENERGY SYSTEMS Sustainable Places 2015 Savona,

More information

Topics. HVDC Fundamentals

Topics. HVDC Fundamentals Topics HVDC Fundamentals Conventional Converters Capacitor Commutated Converters Voltage Source Converters Reactive Power Requirements System Configurations Tapping Control basics High Power Transmission

More information

Multi-Terminal DC System line Protection Requirement and High Speed Protection Solutions

Multi-Terminal DC System line Protection Requirement and High Speed Protection Solutions 21, rue d Artois, F-75008 PARIS LUND 2015 http : //www.cigre.org 331 Multi-Terminal DC System line Protection Requirement and High Speed Protection Solutions Jianping Wang, Bertil Berggren, Kerstin Linden,

More information

Control Development and Modeling for Flexible DC Grids in Modelica

Control Development and Modeling for Flexible DC Grids in Modelica Control Development and Modeling for Flexible DC Grids in Modelica Andreas Olenmark 1 Jens Sloth 2 Anna Johnsson 3 Carl Wilhelmsson 3 Jörgen Svensson 4 1 One Nordic AB, Sweden, andreas.olenmark@one-nordic.se.

More information

MEDIUM AND HIGH VOLTAGE CAPACITORS, CAPACITOR BANKS AND SYSTEMS

MEDIUM AND HIGH VOLTAGE CAPACITORS, CAPACITOR BANKS AND SYSTEMS MEDIUM AND HIGH VOLTAGE CAPACITORS, CAPACITOR BANKS AND SYSTEMS Meher Capacitors offers reliable and innovative products and solutions in the fields of Reactive Power Compensation, Power Quality and Energy

More information

Typical Data Requirements Data Required for Power System Evaluation

Typical Data Requirements Data Required for Power System Evaluation Summary 66 Carey Road Queensbury, NY 12804 Ph: (518) 792-4776 Fax: (518) 792-5767 www.nepsi.com sales@nepsi.com Harmonic Filter & Power Capacitor Bank Application Studies This document describes NEPSI

More information

September 13, 2010. Replace Tunis T1 Notification of Conditional Approval of Connection Proposal CAA ID Number: 2010-EX506

September 13, 2010. Replace Tunis T1 Notification of Conditional Approval of Connection Proposal CAA ID Number: 2010-EX506 September 13, 2010 Mr. Charles Wickham General Manager Eastern Operations Capital Power Corporation Suite 1301, 200 University Avenue Toronto, ON M5H 3C6 Dear Mr. Wickham: Replace Tunis T1 Notification

More information

Three Gorges - Changzhou HVDC : Ready to Bring Bulk Power to East

Three Gorges - Changzhou HVDC : Ready to Bring Bulk Power to East The 4 th International Conference on Power Transmission & Distribution Technology 2003 14-16 October, 2003, Changsha 2003 Three Gorges - Changzhou HVDC : Ready to Bring Bulk Power to East Abhay Kumar Mats

More information

INTRODUCTION TO SYSTEM PROTECTION. Hands-On Relay School 2012

INTRODUCTION TO SYSTEM PROTECTION. Hands-On Relay School 2012 INTRODUCTION TO SYSTEM PROTECTION Hands-On Relay School 2012 CONGRATULATIONS On choosing the field of system protection. It is an exciting, challenging profession. System protection has changed considerably

More information

Impedance Matching and Matching Networks. Valentin Todorow, December, 2009

Impedance Matching and Matching Networks. Valentin Todorow, December, 2009 Impedance Matching and Matching Networks Valentin Todorow, December, 2009 RF for Plasma Processing - Definition of RF What is RF? The IEEE Standard Dictionary of Electrical and Electronics Terms defines

More information

POWER TRANSMISSION FROM OFFSHORE WIND FARMS

POWER TRANSMISSION FROM OFFSHORE WIND FARMS POWER TRNSMISSION FROM OFFSHORE WIND FRMS Thorsten Völker University of pplied Sciences Bremerhaven Germany BSTRCT The future for wind power generation in Germany is offshore wind energy. The preferred

More information

CLASS. Customer Load Active System Services

CLASS. Customer Load Active System Services CLASS Customer Load Active System Services 1 Customer Load Active System Services Offer new services and choice for the future Maximise use of existing assets Delivering value to customers Innovative solutions

More information

Introduction to Paralleling of LTC Transformers by the Circulating Current Method

Introduction to Paralleling of LTC Transformers by the Circulating Current Method TAPCHANGER CONTROLS Application Note #11 Introduction to Paralleling of LTC Transformers by the Circulating Current Method 1.0 ABSTRACT This Application Note discusses the elements of paralleling load

More information

Application Note. So You Need to Measure Some Inductors?

Application Note. So You Need to Measure Some Inductors? So You Need to Measure Some nductors? Take a look at the 1910 nductance Analyzer. Although specifically designed for production testing of inductors and coils, in addition to measuring inductance (L),

More information

Knowing the FACTS. FACTS that enhance power quality in rail feeder systems

Knowing the FACTS. FACTS that enhance power quality in rail feeder systems Knowing the FACTS FACTS that enhance power quality in rail feeder systems ROLF GRÜNBAUM, PER HALVARSSON, BJÖRN THORVALDSSON The increase in traffic on existing tracks combined with new high-speed rail

More information

7. Reactive energy compensation

7. Reactive energy compensation 593 7. Reactive energy compensation 594 7. REACTIVE ENERGY COMPENSATION Reactive energy compensation is an important element for reducing the electricity bill and improving the quality of the electrical

More information

LIMITING SHORT-CIRCUIT CURRENTS IN MEDIUM-VOLTAGE APPLICATIONS

LIMITING SHORT-CIRCUIT CURRENTS IN MEDIUM-VOLTAGE APPLICATIONS LIMITING SHORT-CIRCUIT CURRENTS IN MEDIUM-VOLTAGE APPLICATIONS Terence Hazel Senior Member IEEE Schneider Electric 38050 Grenoble France Abstract The power requirements for large industrial sites is increasing.

More information

Measurement, Modeling and Simulation of Capacitor Bank Switching Transients

Measurement, Modeling and Simulation of Capacitor Bank Switching Transients Measurement, Modeling and Simulation of Capacitor Bank Switching Transients Mirza Softić*, Amir Tokić**, Ivo Uglešić*** *Kreka - Dubrave e, Dubrave, Bosnia and Herzegovina (e-mail: softic_mirza@yahoo.com).

More information

Harmonics and Noise in Photovoltaic (PV) Inverter and the Mitigation Strategies

Harmonics and Noise in Photovoltaic (PV) Inverter and the Mitigation Strategies Soonwook Hong, Ph. D. Michael Zuercher Martinson Harmonics and Noise in Photovoltaic (PV) Inverter and the Mitigation Strategies 1. Introduction PV inverters use semiconductor devices to transform the

More information

THE PER-UNIT SYSTEM. (2) The per-unit values for various components lie within a narrow range regardless of the equipment rating.

THE PER-UNIT SYSTEM. (2) The per-unit values for various components lie within a narrow range regardless of the equipment rating. THE PER-UNIT SYSTEM An interconnected power system typically consists of many different voltage levels given a system containing several transformers and/or rotating machines. The per-unit system simplifies

More information

Overhead lines Asset Management in the Belgian network. S. GERMAIN K. VAN DAM B. RISSE JF. GOFFINET Elia Belgium

Overhead lines Asset Management in the Belgian network. S. GERMAIN K. VAN DAM B. RISSE JF. GOFFINET Elia Belgium 21, rue d Artois, F-75008 PARIS B2-208 CIGRE 2012 http : //www.cigre.org Overhead lines Asset Management in the Belgian network. S. GERMAIN K. VAN DAM B. RISSE JF. GOFFINET Elia Belgium SUMMARY The Belgian

More information

Renewable Energy Grid Integration

Renewable Energy Grid Integration Renewable Energy Grid Integration Jian Sun Professor and Director Grid Integration Issues Cost, Reliability & Efficiency of Grid Interface Grid Congestion, Weak Grids Variability of Renewable Production

More information

Residual Current Circuit Breaker

Residual Current Circuit Breaker Introduction Residual Current Circuit Breaker / ELCB The Fault current overloads and short circuits can be detected by circuit breakers like MCB s MCCB s & HRC Fuses etc. But, Circuit breakers don t detect

More information

Selecting Current Transformers Part 1 By Darrell G. Broussard, P.E.

Selecting Current Transformers Part 1 By Darrell G. Broussard, P.E. By Darrell G. Broussard, P.E. Introduction: As engineers, we are aware that electrical power systems have grown. How much have they grown? When was the last time you specified a 2400-volt system, a 4160-volt

More information

Holly STATCOM FACTS to replace critical generation, operational experience

Holly STATCOM FACTS to replace critical generation, operational experience Holly STATCOM FACTS to replace critical generation, operational experience A. Oskoui, B. Mathew, Member, IEEE, J.-P. Hasler, M. Oliveira, Member, IEEE, T. Larsson, Member, IEEE, Å. Petersson, E. John,

More information

MOBILE SYSTEM FOR DIAGNOSIS OF HIGH VOLTAGE CABLES (132KV/220KV) VLF-200 HVCD

MOBILE SYSTEM FOR DIAGNOSIS OF HIGH VOLTAGE CABLES (132KV/220KV) VLF-200 HVCD MOBILE SYSTEM FOR DIAGNOSIS OF HIGH VOLTAGE CABLES (132KV/220KV) VLF-200 HVCD VERY LOW FREQUENCY (VLF) - PARTIAL DISCHARGES AND TANGENT DELTA HV/EHV POWER CABLES DIAGNOSTIC AND ON-SITE FIELD TESTING WITH

More information

Chapter 11. Inductors ISU EE. C.Y. Lee

Chapter 11. Inductors ISU EE. C.Y. Lee Chapter 11 Inductors Objectives Describe the basic structure and characteristics of an inductor Discuss various types of inductors Analyze series inductors Analyze parallel inductors Analyze inductive

More information

Reactive Power and Importance to Bulk Power System OAK RIDGE NATIONAL LABORATORY ENGINEERING SCIENCE & TECHNOLOGY DIVISION

Reactive Power and Importance to Bulk Power System OAK RIDGE NATIONAL LABORATORY ENGINEERING SCIENCE & TECHNOLOGY DIVISION Reactive Power and Importance to Bulk Power System OAK RIDGE NATIONAL LABORATORY ENGINEERING SCIENCE & TECHNOLOGY DIVISION Outline What is Reactive Power and where does it come from? Why is it important?

More information

Power measurement in balanced 3 phase circuits and power factor improvement. 1 Power in Single Phase Circuits. Experiment no 1

Power measurement in balanced 3 phase circuits and power factor improvement. 1 Power in Single Phase Circuits. Experiment no 1 Experiment no 1 Power measurement in balanced 3 phase circuits and power factor improvement 1 Power in Single Phase Circuits Let v = m cos(ωt) = cos(ωt) is the voltage applied to a R-L circuit and i =

More information

EMI and t Layout Fundamentals for Switched-Mode Circuits

EMI and t Layout Fundamentals for Switched-Mode Circuits v sg (t) (t) DT s V pp = n - 1 2 V pp V g n V T s t EE core insulation primary return secondary return Supplementary notes on EMI and t Layout Fundamentals for Switched-Mode Circuits secondary primary

More information

Nuclear Power Plant Electrical Power Supply System Requirements

Nuclear Power Plant Electrical Power Supply System Requirements 1 Nuclear Power Plant Electrical Power Supply System Requirements Željko Jurković, Krško NPP, zeljko.jurkovic@nek.si Abstract Various regulations and standards require from electrical power system of the

More information

The electrical energy produced at the gen

The electrical energy produced at the gen 300 300 Principles of Power System CHAPTER CHAPTER 12 Distribution Systems General 12.1 Distribution System 12.2 Classification of Distribution Systems 12.3 A.C. Distribution 12.4 D.C. Distribution 12.5

More information

Power products and systems. Intelligent solutions for power distribution Zone concept

Power products and systems. Intelligent solutions for power distribution Zone concept Power products and systems Intelligent solutions for power distribution Zone concept Securing continuous power supply ABB is one of the world's leading power and automation technology companies whose products,

More information

Special Publication. Operation and Monitoring of MSCDN-Systems

Special Publication. Operation and Monitoring of MSCDN-Systems Special Publication Operation and Monitoring of MSCDN-Systems The popularity of Mechanical Switched Capacitor with Damping Network (MSCDN) systems in German transmission grid is growing massively. This

More information

Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading. Ramandeep Kaur Aujla S.NO 250447392

Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading. Ramandeep Kaur Aujla S.NO 250447392 1 Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading By Ramandeep Kaur Aujla S.NO 250447392 ES 586b: Theory and applications of protective relays Department of

More information

VOLTAGE REGULATOR AND PARALLEL OPERATION

VOLTAGE REGULATOR AND PARALLEL OPERATION VOLTAGE REGULATOR AND PARALLEL OPERATION Generator sets are operated in parallel to improve fuel economy and reliability of the power supply. Economy is improved with multiple paralleled generators by

More information

Utility Static Var Compensator (SVC)

Utility Static Var Compensator (SVC) Utility Static Var Compensator (SVC) Dear Customer, Customised and customer driven Nokian Capacitors moderate size, overall flexibility and an ability to listen to customers are natural benefits of the

More information

Designing the NEWCARD Connector Interface to Extend PCI Express Serial Architecture to the PC Card Modular Form Factor

Designing the NEWCARD Connector Interface to Extend PCI Express Serial Architecture to the PC Card Modular Form Factor Designing the NEWCARD Connector Interface to Extend PCI Express Serial Architecture to the PC Card Modular Form Factor Abstract This paper provides information about the NEWCARD connector and board design

More information

Electric Power Systems An Overview. Y. Baghzouz Professor of Electrical Engineering University of Nevada, Las Vegas

Electric Power Systems An Overview. Y. Baghzouz Professor of Electrical Engineering University of Nevada, Las Vegas Electric Power Systems An Overview Y. Baghzouz Professor of Electrical Engineering University of Nevada, Las Vegas Overview Power Generation Conventional power generation Power generation from renewables

More information

Estimation of electrical losses in Network Rail Electrification Systems

Estimation of electrical losses in Network Rail Electrification Systems Estimation of electrical losses in Network Rail Electrification Systems Page 1 of 16 Contents 1. BACKGROUND...3 2. PURPOSE...3 3. SCOPE...3 4. DEFINITIONS & ABBREVIATIONS...4 5. NETWORK RAIL INFRASTRUCTURE

More information

Power Technology Issue 106. Modeling of Three-Winding Voltage Regulating Transformers for Positive Sequence Load Flow Analysis in PSS E

Power Technology Issue 106. Modeling of Three-Winding Voltage Regulating Transformers for Positive Sequence Load Flow Analysis in PSS E SIEMENS Siemens Energy, Inc. Power Technology Issue 106 Modeling of Three-Winding Voltage Regulating Transformers for Positive Sequence Load Flow Analysis in PSS E Carlos Grande-Moran, Ph.D. Principal

More information

PHASOR DIAGRAMS HANDS-ON RELAY SCHOOL WSU PULLMAN, WA. RON ALEXANDER - BPA

PHASOR DIAGRAMS HANDS-ON RELAY SCHOOL WSU PULLMAN, WA. RON ALEXANDER - BPA PHASOR DIAGRAMS HANDS-ON RELAY SCHOOL WSU PULLMAN, WA. RON ALEXANDER - BPA What are phasors??? In normal practice, the phasor represents the rms maximum value of the positive half cycle of the sinusoid

More information

Using Thermocouple Sensors Connecting Grounded and Floating Thermocouples

Using Thermocouple Sensors Connecting Grounded and Floating Thermocouples Connecting Grounded and Floating Thermocouples For best performance, Thermocouple sensors should be floating. This will ensure that no noise currents can flow in the sensor leads and that no common-mode

More information

ANN Based Fault Classifier and Fault Locator for Double Circuit Transmission Line

ANN Based Fault Classifier and Fault Locator for Double Circuit Transmission Line International Journal of Computer Sciences and Engineering Open Access Research Paper Volume-4, Special Issue-2, April 2016 E-ISSN: 2347-2693 ANN Based Fault Classifier and Fault Locator for Double Circuit

More information

Type SA-1 Generator Differential Relay

Type SA-1 Generator Differential Relay ABB Automation Inc. Substation Automation and Protection Division Coral Springs, FL 33065 Instruction Leaflet 41-348.11C Effective: November 1999 Supersedes I.L. 41-348.11B, Dated August 1986 ( ) Denotes

More information

Power Supplies. 1.0 Power Supply Basics. www.learnabout-electronics.org. Module

Power Supplies. 1.0 Power Supply Basics. www.learnabout-electronics.org. Module Module 1 www.learnabout-electronics.org Power Supplies 1.0 Power Supply Basics What you ll learn in Module 1 Section 1.0 Power Supply Basics. Basic functions of a power supply. Safety aspects of working

More information