2016 Fire Code. Flammable and Combustible Liquids. Reinhard Hanselka, PhD, PE, CRB. Presentation images provided by International Code Council (ICC)

Size: px
Start display at page:

Download "2016 Fire Code. Flammable and Combustible Liquids. Reinhard Hanselka, PhD, PE, CRB. Presentation images provided by International Code Council (ICC)"

Transcription

1 2016 Fire Code Flammable and Combustible Liquids PRESENTED BY Reinhard Hanselka, PhD, PE, CRB Presentation images provided by International Code Council (ICC)

2 Description This course provides a basic understanding of the flammable and combustible liquid storage, use, dispensing, handling and mixing requirements in IFC Chapter 57 and NFPA 30, Flammable and Combustible Liquids Code. General fire code requirements for hazardous materials and specialized requirements for Laboratories, Bio-Pharm, vehicle fuel-dispensing activities (IFC Chapter 23), dry cleaning (IFC Chapter 12) and other specialized uses of flammable and combustible liquids are not covered in detail due to the time limitations of a single-day course.

3 Course Outline Definitions and classification of flammable & combustible liquids Above-ground vessel storage Underground tank storage Containers and portable tank storage

4 Course Outline (cont.) Use, dispensing, mixing and handling Biotech and Laboratory use Special processes involving flammable & combustible liquids Special requirements Spill control and secondary containment Classified electrical locations Ventilation

5 Improper Ventilation

6 Flammable and Combustible Liquids How do you keep this from becoming this?

7 Focus on Flammable & Combustible Liquids Flammable Liquids If vapor can is suspended & present and combustible two- in air or in threedimension space, those be a easily deflagration liquids fires (pool a confined liquids are may that ignitable or can dripping/running occur. are capable and have of supporting high spill) heat that spread release combustion rates. rapidly Vapor can migrate to ignition sources remote from a spill. A Real Problem with HPLC s

8 Classification of Flammable & Combustible Liquids The CFC classifies liquids that burn as either FLAMMABLE or COMBUSTIBLE. To classify a flammable liquid, the flash point and boiling pointmust be determined. Flash points and boiling points are determined by experimentation. Combustible liquidsare also classified by flash pointtests but do not require determination of the material s boiling point.

9 Understanding the Flash Point System Section defines FLASH POINTas: The minimum temperature in degrees Fahrenheit at which a liquid will give off sufficient vapors to form an ignitable mixture with air near the surface or in the container, but will not sustain combustion. The flash point of a liquid shall be determined by appropriate test procedure and apparatus as specified in ASTM D 56, ASTM D 93 or ASTM D 3278.

10 Understanding the Flash Point System Section defines FIRE POINT as: The lowest temperature at which a liquid will ignite and achieve sustained burning when exposed to a test flame in accordance with ASTM D 92.

11 Understanding the Flash Point System All of the adopted flash point tests are closed cup tests. More conservative More reproducible Flash point testing is a LIMITED method for determining the ignitability of a particular liquid. Serves better as a basis of comparing liquids than as an absolute measure of fire risk The CFC defines: Liquids with a flash point less than 100 F as FLAMMABLE Liquids with a flash point at or above 100 F as COMBUSTIBLE This differs from DOT

12 DOT Classification of Liquids Flammable Liquid Generally applies to liquids with a flash point less than 140 F There are MANY exceptions In some cases, a liquid with a flash point exceeding 100 F may be reclassified as a combustible liquid Combustible Liquid Generally applies to liquids with a flash point 140 F to 200 F Liquids with flash points exceeding 200 F are not considered combustible under DOT regulations FLAMMABLE 3

13 DOT Classification of Liquids Be careful that differences between the IFC, CMC and DOT classification systems don t lead to miscommunication between an owner (who often deals with transportation regulations) and a fire inspector (who primarily deals in fire codes) when speaking about flammable liquids. FLAMMABLE 3

14 FL-1B Use Open Max. Qty. Per Control Area = 30 Gallons FLOOR = 60 Gallons Max. Qty. Per Floor = 30 Gallons Qty. with 4 Lab Suites Per Floor 10 5% 3 50% 50% 50% 50% % 5% 6 50% 50% 50% 50% % 5% 6 50% 50% 50% 50% % 5% 6 50% 50% 50% 50% % 12.50% 15 75% 75% 75% 75% 90 4 TH FLOOR LIMITS % 12.50% 15 75% 75% 75% 75% % 12.50% 15 75% 75% 75% 75% % 50% % 100% 100% 100% % 75% 75% % 100% 100% 100% % 100% 100% 100% % 100% 100% 100% TOTALS Basement Level - 1 Basement Level % 75% 75% % 100% 100% 100% % 50% 60 75% 75% 75% 75% UFC TOTAL IFC L-Occupancy 1080

15 CLASSIFICATION OF FLAMMABLE AND COMBUSTIBLE LIQUIDS CLASSIFICATION 1 FLASH POINT (ºF) VAPOR PRESSURE (PSI ABSOLUTE) BOILING POINT (ºF) Class IA Less than 73 Less than or equal to 40 Less than 100 Class IB Less than 73 Less than or equal to 40 Greater than or equal to 100 Greater than 73 and Class IC less than or equal to Less than or equal to 40 N/A 100 Class II Greater than 100 and less than 140 N/A N/A Class IIIA Greater than or equal to 140 and less than 200 N/A N/A Class IIIB Greater than or equal to 200 N/A N/A N/A = Not applicable to classification. 1 When heated, sprayed or mixed, Class II or III liquids can assume the characteristics of lower flash point liquids. Under such conditions the appropriate provisions of Chapter 34 for the actual flash point shall apply. When flammable or combustible liquids present multiple hazards, all hazards must be addressed.

16 Ignition and Burning Comparison of Two Class I Liquid Types Heptane Heptane is a typical flammable liquid. Styrene resin is viscous and has a low vapor pressure, both important considerations in evaluating true fire risk. Flash point doesn t necessarily indicate how easily a liquid ignites and burns. It is simply a relative measure of ignitibility of vapors in a test environment Styrene Resin

17 Navigating the IFC The CFC is organized into 7 parts. Unlike some legacy codes, the parts are Not formally identified; Not separated by breaks in chapter numbering. The CFC has 47 chapters and 10 appendices.

18 Chapter 57 Flammable and Combustible Liquids Chapter 57 is largely derived from the legacy 1997 Uniform Fire Code, but it gives more deference to NFPA 30, Flammable and Combustible Liquids Code. Most IFC regulations are similar to provisions in NFPA 30, but there are some differences.

19 Chapter 57 Major Subsections 5701 General 5702 Definitions 5703 General requirements 5704 Storage Above-ground and underground tank storage Indoor portable tank and container storage Outdoor portable tank and container storage 5705 Dispensing, use, mixing and handling 5706 Special operations

20 Chapter 57 Flammable and Combustible Liquids It should be noted that Chapter 57 differs from the other hazardous material chapters in that many of the requirements in Sections 5704 and 5705 apply regardless of the indoor or outdoor Maximum Allowable Quantities (MAQs).

21 Section 5701 General Provisions in this section apply to all storage, use and handling of flammable and combustible liquids, exceptf

22 Section Non-applicability Chapter 57 requirements do not apply to the following: Specific provisions for liquids in vehicle fueling stations, repair garages, airports and marinas (Chapter 22). Medicine; foodstuffs; cosmetics; commercial, institutional and industrial products in similar packaging to the items listed here that are maximum 50 percent by volume water-miscible flammable or combustible liquid with the remainder being nonflammable in retail or wholesale storage uses. Alcoholic beverages not exceeding 1.3 gallon containers in retail or wholesale sales or storage uses; distilled spirits and wines in wooden barrels and casks.

23 Section Non-applicability (cont.) Chapter 57 requirements do not apply to the following: Storage and use of fuel oil tanks and containers connected to oil-burning equipment. Refrigerant liquids and oils in refrigeration systems. Storage and display of aerosols. Liquids without fire points.

24 Section 5701 Material Classification Section Flammable and combustible liquids with multiple hazards must also comply with Chapter 50. Example: Acetic acid is a Class II combustible liquid that is also corrosive. Example: Methyl Ethyl Ketone Peroxide which is a Class II or IIIA combustible liquid and a Class II or III organic peroxide Section When combustible liquids are heated above their flash points, they are regulated as flammable liquid.

25 Section 5703 General Requirements Electrical Fire Protection Spill Control and Secondary Containment Labels and Signs Piping, Valves and Fittings

26 Section Piping Systems Piping systems must be designed in accordance with NFPA 30 and ASME B31.3, Process Piping. Piping systems may be either metallic or nonmetallic. Low melt point materials At a minimum, the system design should indicate the: Design temperature and ressure Pipe and fitting specifications Method of pipe assembly Method of pipe erection and support Method of testing and test medium

27 A Properly Designed and Installed Piping System

28 And then there is thisf

29 Section 5704 Storage

30 Section Tank Storage Section addresses tanks over 660 gallons: Construction Installation Venting Normal vents Emergency vents Separation requirements Secondary containment Protection from corrosion

31 Section Tank Storage Use of tank vehicles and cars for storage Labeling and signs Sources of ignition Explosion control

32 Section Tank Storage (cont.) Separation from incompatible materials Design and construction Normal venting 60 gallons!!! Emergency venting Tank openings other than vents Vaults

33 Section Tank Storage Aboveground tanks Existing noncompliant installations Fire protection Supports Above-ground storage tanks in buildings Location of tanks outdoors Protected tanks

34 Section Tank Storage (cont.) Drainage and diking Underground tanks Testing Abandonment of tanks

35 Section Design and Construction of Tanks The IFC permits the use of the following types of storage tanks: Shop-fabricated tanks which can be listed for underground or above-ground installation Field erected above-ground tanks Protected above-ground tanks Vaulted tanks Special enclosures ( See Chapter 22 motor fueling)

36 Section Design and Construction of Tanks Design, fabrication and construction must be in accordance with NFPA 30 s recognized standards. UL 58 Steel Underground Tanks for Flammable & Combustible Liquids UL 142 Steel Aboveground Tanks for Flammable & Combustible Liquids API 620 Welded, Low-pressure Storage Tanks API 650 Welded Steel Tanks for Oil Storage API 2000 Venting Atmospheric & Low-pressure Storage Tanks ASME Boiler and Pressure Vessel Code Section VIII -Pressure Vessels UL 2085 Protected Aboveground Tanks for Flammable & Combustible Liquids UL 2245 Below-Grade Vaults for Flammable Liquid Storage IFC Section requires a permanent marking or nameplate on ASTs indicating the standard used as the basis of design, fabrication and construction (origin 1997 UFC).

37 Field-Erected versus Shop-Fabricated Above-ground Storage Tanks Field-Erected ASTs Volume and the diameter are unlimited. The tank bottom is the thickest part of the tank. Generally constructed inside of a containment dike. Are subject to a periodic internal and external corrosion examination. Are approved. Shop-Fabricated ASTs Volume is limited to 50,000 gallons. The tank wall is thinner than the tank heads. Can be constructed with integral secondary containment. Are not subject to a periodic internal corrosion examination. Are listed.

38 API 650 Field-Erected AST

39 UL 2245 Vaulted Below-grade AST

40 2,000 Gallon w.c. ASME Pressure Vessel

41 Section Use of Tank Vehicles and Tank Cars for Storage Tank vehicles and tank cars are not permitted to be used as storage tanks. However, Section permits their use for bulk transfer and process transfer operations.

42 Use of a DOT Tanker as an Aboveground Storage Tank

43 Section Existing Noncompliant Installations Section ensures that any existing aboveground storage tank (AST) is properly installed and maintained. An existing AST found to be in violation of the IFC or the NFPA standards adopted by reference that were in effect at the time of construction must be brought into compliance or removed from service.

44 Section Fire Protection The requirements for fire protection systems on fielderected storage tanks are found in Section and apply to: Tanks operating at atmospheric pressure. Contents that are Class I or II liquids or crude oil. All tanks within a group having a surface area > 1,500 ft². Tanks located in relation to fired fuel sources. Situations when required by the fire code official.

45 Section Foam Fire Protection Systems Section requires foam fire protection systems to be in accordance with NFPA 11, Low-, Medium-and High-Expansion Foam Systems. The requirements in NFPA 11 are dependent on several variables including: Tank diameter and height, The classification of the stored liquid, If ATC type foam is required, When fixed foam chambers are used, if the roof is either fixed or floating, and If the roof is floating, the design of the foam dam. Photograph courtesy of Tyco/AnsulProducts, Marinette WI

46 Section Foam Storage The IFC permits the storage of AFFF on site or off site. If off-site storage is the selected method, it must comply with the following: The foam is compatible with the hazards being protected. Adequate material handling and logistical resources are available. A sufficient volume of AFFF is accumulated before commencing the fire attack. Photograph courtesy of Tyco/Ansul Products, Marinette WI

47 Section Fire Protection of Tank Supports Tanks storing Class I, II or IIIA liquids elevated more than 12 inches above grade require that columns or supports have a minimum 2- hour fire-resistance rating based on the fire exposure criteria in ASTM E Protected ASTs, tanks protected by a water spray system or tanks inside of buildings protected by an approved automatic sprinkler system are exempt from the requirement.

48 Section Above-ground Tank Location Section allows the jurisdiction to establish locations where aboveground storage of Class I and II liquids is prohibited. The NFPA 30 tank siting requirements depend on the type of tank, and the classification and stability of the liquid stored.

49 Table (a) Location of Aboveground Storage Tanks Storing Stable Liquids Internal Pressure Not to Exceed a Gauge Pressure of 2.5 PSI (17 kpa) Type of Tank Floating roof Vertical with weak roof-toshell seam Horizontal and vertical tanks with emergency relief venting to limit pressures to 2.5 PSIG (17.2 kpa gauge) Protected aboveground tank Minimum Distance (ft) From Property Line From Nearest Side of That Is or Can Be Built Any Public Way or from Upon, Including the Nearest Important Opposite Side of A Building on the Same Protection Public Way a Property a Protection from ½ x diameter of tank 1/6 x diameter of tank exposures b None Diameter of tank but 1/6 x diameter of tank need not exceed 175 ft Approved foam or ½ x diameter of tank 1/6 x diameter of tank inerting system on tanks not exceeding 150 ft. in diameter d Protection from Diameter of tank 1/3 x diameter of tank exposures b None Approved foam or inerting system b on the tank or approved foam system on vertical tanks Protection of 2 x diameter of tank but need not exceed 350 feet ½ x Table (b) 1/3 x diameter of tank ½ x Table (b) b Table (b) Table (b) None 2 x Table (b) Table (b) None ½ x Table (b) ½ x Table (b) a. The minimum distance cannot be less than 5 feet (1.5 m) b. See , Protection for Exposures c. See NFPA 69, Standard on Explosion Protection Systems d. For tanks over 150 ft (45 m) in diameter, use Protection for exposures or none as applicable

50 Table (b) Reference Table for Use in Tables (a), , and Tank Capacity (gal) Minimum Distance From Property Line That Is or Can Be Built Upon, Including the Opposite Side of A Public Way (ft) Minimum Distance From Nearest Side of Any Public Way or from Nearest Important Building on the Same Property (ft) 275 or less to to 12, ,001 to 30, ,001 to 50, ,001 to 100, ,001 to 500, ,001 to 1,000, ,000,001 to 2,000, ,000,001 to 3,000, ,000,001 or more

51 Table Minimum Shell-to-Shell Spacing of Aboveground Storage Tanks Tank Diameter All tanks not over 150 ft (45 m) in diameter Tanks larger than 150 ft (45 m) in diameter: Floating Roof Tanks 1/6 x of adjacent tank diameters but not less than 3 ft (0.9 m) Fixed or Horizontal Tanks Class I or II Liquids 1/6 x of adjacent tank diameters but not less than 3 ft (0.9 m) Class IIIA Liquids 1/6 x of adjacent tank diameters but not less than 3 ft (0.9 m) If remote impounding is provided in accordance with /6 x of adjacent tank diameters ¼ x of adjacent tank diameters ¼ x of adjacent tank diameters If open diking is provided is provided in accordance with ¼ x of adjacent tank diameters 1/3 x of adjacent tank diameters 1/3 x of adjacent tank diameters

52 Location of ASTs Four 65,000-gallon (nominal) vertical API 12F ASTs are being installed at a terminal. Each tank will store Class IC stable flammable liquids. Each tank has an emergency vent with an opening pressure of 1 psig. All four tanks are within a single containment dike. Protection of exposures will be provided by a public fire department.

53 AST Site Plan NFPA 30 The distance to the South and West terminal Property Line (PL) The distance to the Control Building, which is an Important Building (IB) The Shell to Shell (SS) tank separation distance PL PL SS IB Control Building Property Line N

54 Solution: Location of ASTs Separation Distance to Property Lines (PL) Apply Table (a). Minimum PL distance is based on Table (b). For a nominal 65,000-gallon AST, the minimum PL separation distance is 50 feet. Separation Distance to Important Building (IB) The control building is on the same property as the ASTs. Table (a) states the separation distance is based on Table (b). For a nominal 65,000-gallon AST the minimum IB separation distance is 15 feet. Tank Shell to Shell (SS) Separation Distance Apply Table The each tank s diameter < 150 feet. Shop drawings indicate each tank has a nominal 14 foot diameter. The sum diameter of the three adjacent tanks is 42 feet. (42 feet x = Minimum 7 foot SS distance).

55 Section Above-ground Tank Openings Atmospheric ASTs are constructed with openings to accommodate: Normal vent Emergency vent Other tank openings Other tank openings may be located above or below the liquid level of the tank, except if it is a protected AST or is used for motor vehicle fuel dispensing.

56 Section Normal Tank Vents Atmospheric storage tanks require a method of relieving the internal pressure caused by the introduction or withdrawal of product. Section requires the normal vents for tanks that contain Class I, II or IIIA liquids be terminated: At a safe point outside of buildings Not less than 12 feet above the adjacent ground level Not less than 5 feet from property lines and building openings

57 This SUCKED literally Normal vent pressure vacuum type 2009 IFC Flammable and Combustible Liquids 57

58 If you only remember ONE THING from this classf Make sure that it is the IMPORTANCE OF EMERGENCY VENTS! Workbook Page

59 Practical Application

60 Explosive Limits Chemical LEL UEL Optimal Acetone 2.5% 15% 5.0% Acetylene 2.5% 83% 8.0% Ammonia 15% 28% 17% Gasoline 1.4% 7.6% 1.6% Hydrogen 4.0% 75% 8.0% Methane 5.0% 15% 9.0% Toluene 1.2% 7.1% 2.5%

61 Section Emergency Relief Venting for Tanks Stationary ASTs require emergency relief vents to relieve excessive internal pressures resulting from fire exposure on or near the tank. Incidents in Kansas City, KS, Amarillo and Kennadale, TX and Gadsden, AL, resulted in fire fighters deaths because adequate emergency venting was not provided or the vents were disabled. Vent designs include long-bolt vents, venting by construction or the use of direct-action emergency vents.

62 Emergency Vent Normal Vent 62

63 Graphite rupture pin on hinged vent Emergency vents An absolute must to prevent explosive tank ruptures IFC FLammable and Combustible Liquids 63

64 Section Emergency Relief Venting for Tanks Determining the required vent capacity for an atmospheric storage tank is based on the tank s orientation, its wetted area, and the minimum volume of free air discharged per hour specified in NFPA 30, Section 22.7 and Annex B [2008 ed.]. Three steps to determine adequacy of emergency vent: 1. Calculating the tank wetted area 2. Determining the required discharge flow rate based on the material stored in the tank 3. Ensuring the emergency vent will relieve enough vapor to achieve the required flow rate

65 Section Emergency Relief Venting for Tanks Listed shop-fabricated ASTs will often have a nameplate specifying the minimum flow rate required for emergency vent. NFPA 30 Section [2008 ed.] requires the vent discharge capacity to be indicated on the emergency vent. To determine if the emergency vent is properly sized, compare the nameplate data to the emergency vent flow rate. Vent device flows assume a maximum 1-foot pipe extension based on calculations in API 2000, Venting Atmospheric and Low Pressure Storage Tanks: Nonrefrigerated and Refrigerated.

66 Section Emergency Relief Venting for Tanks Hopper Model 34 Emergency Vent 198,000 8 oz. Methyl Iso Bad Karma Emergency Vent Discharge Rate: 233,000 SCFH

67 What s Missing? 67

68 Pitting indicates a reused underground tank. 68

69 Other ConsiderationsF Pressure Relief for Vessels Short on space for your tank farm?

70 Section Protected Above-ground Tanks A protected above-ground storage tank is one method of resolving safety concerns regarding above-ground tanks for liquid storage PASTs must: Be listed to UL 2085 (2-hour temp. limited fire test) Have impact protection Have secondary containment Have overfill protection Have openings on top only NFPA 30A fire-resistant tanks are not recognized.

71 Section Protected Above-ground Tanks Tanks for fuel storage are specifically regulated in Chapter 22. Above-ground tanks for fuel storage are limited to a volume of: 12,000 gallons per tank 48,000 gallons aggregate Table specifies tank siting requirements based on tank volume and exposures such as property lines, important buildings and adjacent tanks.

72 Section Tank Vaults Vaults are used for installing ASTs below grade. Premanufacturedvaults must be listed in accordance with UL Construction must be a minimum of 6-inches of reinforced concrete. Vaults containing Class I liquids require mechanical ventilation. Overfill protection, leak monitoring and alarm systems are required. Vaults require approved automatic or manual means of applying a fire suppression agent.

73 Section Stationary Tanks Inside Buildings Typically requires a Group H occupancy in accordance with the IBC. Tanks for Class I, II and IIIA liquids require a means of overfill protection to prevent liquid from spilling into the building. Section requires connections that are made and broken, including fill connections, to be outside.

74 Section Drainage and Diking for Tanks An area surrounding tanks must be provided with drainage control or diking to prevent accidental discharge from endangering other tanks, adjoining property or waterways. Depending on the total volume within the containment basin, intermediate diking may be required by NFPA 30.

75 Section Drainage and Diking for Tanks The IFC requires a dike to contain the volume of the largest tank in the dike plus the volume displaced by other tanks in the same dike. Walls to be earth, steel, concrete or solid masonry. Must have method to remove excess water.

76 Section Underground Storage Tanks Photograph courtesy of the Steel Tank Institute, Lake Zurich IL Underground Storage Tanks (USTs) are constructed of carbon steel or fiberglass reinforced plastic. Tanks must be located: Away from loads caused by foundations, At least 3 feet from nearest wall of a basement, pit, cellar or property line, and At least 1 foot from other tanks.

77 Section Underground Storage Tanks Tanks must be sufficiently covered with earth or other coverings to prevent damage. Fill pipes require a spill container and an overfill prevention device. Spill containers must have a capacity of at least 5 gallons and be equipped with a drain valve.

78 Section Underground Storage Tanks An overfill prevention system must: Activate an audible and visual alarm when 90% of tank capacity is reached, Shut off flow when 95% of tank capacity is reached, or Reduce the flow to 15 gpm, the tank will not fill for 30 minutes and none of the fittings is exposed to product.

79 Section Container and Portable Tank Storage addresses portable tanks 660 gallons and containers 60 gallons in volume. Their design, construction and maximum volume requirements are established in NFPA 30.

80 Section Container and Portable Tank Storage Design, construction and capacity Liquid storage cabinets Indoor storage Quantity limits for indoor storage Storage in control areas Wholesale and retail sales Liquid storage rooms Liquid storage warehouses

81 Section Containers and Portable Tanks Section defines a container as a vessel of 60 gallons or less used for transporting or storing flammable or combustible liquids. The IFC, by reference to NFPA 30, requires containers storing Class I, II and IIIA liquids to be constructed in accordance with DOT requirements. NFPA 30 limits the volume of a container or portable tank based on container construction materials and the class of liquid contained. NFPA 30 regulates storage of plastic containers in other than Group M occupancies. Special regulations for storage in plastic containers in Group M occupancies are set forth in the IFC.

82 NFPA 30 Table Table Maximum Allowable Size Containers, Intermediate Bulk Containers (IBCs) and Portable Tanks Flammable Liquids Combustible Liquids Container Type Class IA Class IB Class IC Class II Class IIIA Glass 1 pint (0.5 L) 1 quart (1 L) 1.3 gal (5 L) 1.3 gal (5 L) 5.3 gal (20 L) Metal (other than drums) or approved plastic 1.3 gal (5 L) 5.3 gal (20 L) 5.3 gal (20 L) 5.3 gal (20 L) 5.3 gal (20 L) Safety cans 2.6 gal (10 L) 5.3 gal (20 L) 5.3 gal (20 L) 5.3 gal (20 L) 5.3 gal (20 L) Metal drum (e.g., UN 1A1/1A2) Approved metal portable tanks and IBCa Rigid plastic IBCs (UN 31H1 or 31H2) and composite IBCs with rigid inner receptacle (UN 31HZ1) Composite IBCs with flexible inner receptacle (UN 31HZ2) and DOT/UN approved flexible IBCs 119 gal (450 L) 119 gal (450 L) 119 gal (450 L) 119 gal (450 L) 119 gal (450 L) 793 gal (3000 L) 793 gal (3000 L) 793 gal (3000 L) 793 gal (3000 L) 793 gal (3000 L) NP NP NP 793 gal (3000 L) 793 gal (3000 L) NP NP NP NP NP Non-bulk Bag-In-Box NP NP NP NP NP Polyethylene UN 1H1 and UN 1H2, or as authorized by DOT exemption Fiber drum NMFC or UFC Type 2A; Type 2a, 3B-H, or 3B-L; or Type 4A 1.3 gal (5 L) 5.3 gal (20 L) 5.3 gal (20 L) 119 gal (450 L) 119 gal (450 L) NP NP NP 119 gal (450 L) 119 gal (450 L) NP: Not permitted for the container categories so classified unless a fire protection system is provided that is Developed in accordance with and is approved for specific container and protection against static electricity is provided.

83 Fire Protection Issues for Containers and Intermediate Bulk Containers Two issues that require special consideration with respect to fire protection are: Storage of plastic containers of Class I and II liquids in Group S-1 occupancies Use of relieving-style containers for storage

84 Plastic Containers For a fire code official to approve a container, it must comply with NFPA 30, Table and Chapter 12. Section , Liquids in Plastic Containers states: Class I and II liquids in plastic containers shall not be stored in general-purpose warehouses but shall be stored in inside liquid storage areas that meet the requirements of this chapter. This section has two exceptions.

85 Plastic Containers Exception No. 1: The following liquids, packaged in plastic containers, are permitted to be stored in general-purpose warehouses in accordance with the protection and storage limitations specified in Section 12.8 as follows: (1) Products containing not more than 50 percent by volume of water- miscible liquids, with the remainder of the product consisting of components that do not burn and where packaged in individual containers (2) Products containing more than 50-percent watermiscible liquids in individual containers not exceeding 16 oz (0.5 L) capacity in cartons

86 Plastic Containers Exception No. 2: Class I and II liquids in plastic containers are permitted to be stored in a general-purpose warehouse if the packaging systems are listed and labeled for use with these commodities. All other provisions of Section 12.8 also apply.

87 Fire Protection of Plastic Containers In the case of liquid storage rooms and liquid storage warehouses, fire protection of plastic containers containing Class I and II liquids will generally need to be designed as an Alternative Means and Method to Note b in Table (3): In buildings protected by an automatic sprinkler system, the storage height for containers and portable tanks shall not exceed the maximum storage height permitted for the fire protection scheme set forth in NFPA 30 or the maximum storage height demonstrated in a full-scale fire test, whichever is greater. NFPA 30 criteria and fire test results for metallic containers and portable tanks shall not be applied to nonmetallic containers and portable tanks.

88 Relieving Style Containers Plastic caps (bungs) can reduce the risk of rupturing a drum in a fire event. Have a liquid storage room?

89 Relieving Style Containers Protection schemes in NFPA 30 for liquid storage call for relieving style containers. The listed plastic bungs are designed to melt during a fire and prevent explosive rupture of the vessel. Covering plastic bungs with a foil seal may prevent proper operation and is not permitted.

90 Pressure Relief for Vessels There s This more was to styrene sprinkler monomer heptane design than just hanging would have sprinklers leveled from the building! a pipe Even plastic bungs cannot entirely ensure that rupture will not occur.

91 Pressure Relief for Vessels This was styrene monomer heptane would have leveled the building! Even plastic bungs cannot entirely ensure that rupture will not occur.

92 Venting is the desired result

93 Section Portable Tanks The IFC does not define PORTABLE TANK; however, it is any packaging over 60 gallons that is designed to be loaded into, onto or temporarily attached to a transport vehicle. NFPA 30 requires portable tanks to be equipped with an emergency vent. Portable tanks and intermediate bulk containers must also meet the requirements in NFPA 30 Table

94 Section Intermediate Bulk Containers Intermediate Bulk Containers, often called totes, are portable tanks with a volume up to 793 gallons (3000 L). They can be designed for a one-time use or continuous duty Normally designed for gravity dispensing A significant fire protection concern is the use of plastic IBCs for the storage liquids.

95 Section Intermediate Bulk Containers The National Fire Protection Research Foundation fire testing of Intermediate Bulk Containers found: Sprinkler protection using only water can protect plastic IBCs storing Class II and IIIA water-miscible liquids. NFPA 30 does not permit storage of Class I liquids in nonmetallic IBCs, due to concerns about static causing ignition during filling.

96 Section Container & Portable Tank Storage Inside of Buildings Section applies to containers with capacities less than 60 gallons and portable tanks less than 660 gallons. Storage of liquid in vehicle fuel tanks and liquor in wooden barrels or casks is exempt from these provisions.

97 Section Maximum Allowable Quantity & Control Areas A control area is an area in a building where limited quantities of flammable or combustible liquids are allowed to be stored or used without requiring reclassification to more hazardous occupancy. IBC Section requires two or more control areas be separated from each other by 1-hour or greater fire barriers, with floor construction and members supporting the floor rated for 2 hours. The concept of the control area is to limit the Maximum Allowable Quantity (MAQ) of hazardous materials per control area rather than per building, and then limit the number of control areas within each building. Any combination of hazardous materials up to the MAQ is allowed in a control area.

98 TABLE (1) MAXIMUM ALLOWABLE QUANTITY PER CONTROL AREA OF HAZARDOUS MATERIALS POSING A PHYSICAL HAZARD a,j,m,n,p GROUP STORAGE b USE-CLOSED SYSTEM b USE-OPEN SYSTEM b WHEN MAXIMUM Gas Solid ALLOWABLE Solid Liquid cubic Solid Liquid Gas pounds Liquid QUANITY IS pounds gallons feet at pounds gallons cubic feet (cubic gallons EXCEEDED (cubic feet) (pounds) NTP (cubic feet) (pounds) at NTP feet) (pounds) MATERIAL CLASS Combustible II liquids c, i IIIA IIIB Flammable liquids c IA IB and IC Organic peroxide UD I II III IV V H-2 or H-3 H-2 or H-3 Not Applicable H-2 or H-3 H-1 H-2 H-3 H-3 Not Applicable Not Applicable Not Applicable Not Applicable 1 e,g 5 d,e 50 d,e 125 d,e Not Limited Not Limited 120 d,e 330 d,e 13,200 e,f 30 d,e 120 d,e (1)e,g (5)d,e (50)d,e (125)d,e No Limit No Limit Not Applicable Not Applicable Not Applicable Not Applicable Not Applicable 0.25 e,g 1 d,e 50 d,e 125 d,e Not Limited Not Limited 120 d 330 d 13,200 f 30 d 120 d (0.25) e,g (1) d,e (50) d,e (125) d,e No Limit No Limit Not Applicable Not Applicable Not Applicable Not Applicable Not Applicable 0.25 g 1 e 50 e 125 e Not Limited Not Limited a. For use of control areas, see Section b. The aggregate quantity in use and storage shall not exceed the quantity listed for storage. c. The quantities of alcoholic beverages in retail and wholesale sales occupancies shall not be limited providing the liquids are packaged in individual containers not exceeding 1.3 gallons. In retail and wholesale sales occupancies, the quantities of medicines, foodstuffs, consumer or industrial products, and cosmetics containing not more than 50 percent by volume of water-miscible liquids with the remainder of the solutions not being flammable shall not be limited, provided that such materials are packaged in individual containers not exceeding 1.3 gallons. d. Maximum allowable quantities shall be increased 100 percent in buildings equipped throughout with an approved automatic sprinkler system in accordance with Section Where Note e also applies, the increase for both notes shall be applied accumulatively. e. Maximum allowable quantities shall be increased 100 percent when stored in approved storage cabinets, day boxes, gas cabinets, exhausted enclosures or listed safety cans. Where Note d also applies, the increase for both notes shall be applied accumulatively. g. Allowed only in buildings equipped throughout with an approved automatic sprinkler system. i. The maximum allowable quantity shall not apply to fuel storage complying with Section j. Quantities in parenthesis indicate quantity units in parenthesis at the head of each column. 30 d 80 d 3,300 d 10 d 30 d (0.25) g (1) e (50) e (125) e No Limit No Limit

99 Section Maximum Allowable Quantity The number of control areas in a building is limited by IBC Table and IFC Table

100 Table (1) Fuel Oil Systems IFC Table (1), Note i allows up to 3,000 gallons of fuel oil when the installation complies with Section IMC Section 202 defines a fuel oil as a liquid with a flash point temperature > 100 F. Tanks inside buildings must meet IFC Section Piping must meet ASME B31.9, Building Services Piping, in accordance with Section and IMC Chapter 13, Fuel Oil Systems.

101 Table (1) Safety Cans Note e and Section require the use of listed safety cans to increase the MAQ of Class I, II and IIIA liquids. Safety cans must be listed as meeting UL 30 or Factory Mutual Global standards. UL listings are limited to metallic cans. FM listings cover nonmetallic and metallic cans. Photograph courtesy of Justrite Manufacturing Inc., LLC, Des Plaines IL

102 Section Liquid Storage Cabinets Cabinets are required to be listed as meeting UL 1275 or can be constructed of metal or wood based on the prescriptive requirements in Section The IFC permits up to 120 gallons of liquid inside of each cabinet. Doors shall be self-closing and equipped with a 3-point latch. The bottom 2 inches of the cabinet shall be liquid tight. Photograph courtesy of JustriteManufacturing Inc., LLC, Des Plaines IL

103 Flammable Liquid Cabinet After Fire

104 Section Idle Combustible Pallets Because of their heat release and burning rates, Section requires a minimum 8-foot separation between idle combustible pallets and liquid storage. In a sprinkleredbuilding, the height of storage is limited by the requirements in Section 12.1 of NFPA 13. In an unsprinkleredbuilding, pallets are limited to a maximum storage height of 6 feet and a maximum pile area of 2,500 ft.²

105 Section Storage in Basements Section permits basement storage of Class I liquids. The quantity limit is based on the use-open system MAQ and that the basement is protected by a fire protection system in accordance with IFC Chapter 9. For Class I liquids in each of 3 control areas in a basement located one level below the grade plane: Class IA MAQ: 15 gallons/ca Class IB & IC MAQ: 45 gallons/ca

106 Section Group M Occupancies Group M provisions were developed recognizing demonstrated fire protection designs and understanding that the density method of regulating liquid storage and display in retail occupancies was difficult to enforce. Table allows 7,500 gallons of Class IB, IC, II and IIIA liquids in one control area of Group M occupancies when the automatic sprinkler design is in accordance with Note b. Up to 15,000 gallons can be stored when the automatic sprinkler protection meets the criteria in Tables (4) through (8).

107 Section Group M Occupancies To obtain the 7,500 gallon quantity limit: Shelf storage is limited to 6 feet and cartoned, palletized, or racked storage is limited to 4 feet, 6 inches, the height of a typical pallet load. The height of liquid storage is limited by Table (1). To assist in the enforcement of these requirements, the code official may require a storage plan to be developed. Class I liquid containers in Group M occupancies must be constructed of metal Except for not more than 120 gallons of nonmetallic containers not exceeding 16 ounces capacity. Maximum container size is 5 gallons.

108 Section Group M Occupancies

109 Section Because Plastic Containers Are Limited Some retailers have switched to steel packaging to make use of the increased MAQ amounts allowed in Group M occupancies, due to the required use of steel containers.

110 Sections and Liquid Storage Rooms & Warehouses When the MAQ is exceeded in a control area, three options are available: 1) reduce the quantity below the MAQ amount; 2) move the storage outdoors; or 3) construct a liquid storage room or warehouse. To determine if an occupancy is a LIQUID STORAGE ROOM or LIQUID STORAGE WAREHOUSE, the quantity is compared to the values in Table (2) for solidpile and palletized storage or Table (3) for rack storage.

111 Section Liquid Storage Rooms A Group H-2 or H-3 occupancy is assigned when the amount of Class I, II or IIIA liquids exceeds the MAQ. Quantity limits are based on the amount stored in containers or portable tanks and the method of storage. For solid pile & palletized storage, see the Maximum Quantity Per Room column in Table (2). For rack storage see the Maximum Quantity Per Room column in Table (3).

112 Section Liquid Storage Warehouse Required when quantities exceed those for liquid storage rooms. Liquid storage warehouses are classified as Group H-2 or H-3 occupancies, and must meet the same requirements of the IBC and IFC for liquid storage rooms. Warehouses must also have occupantuse hose lines to reach all portions of the storage areas. Pile arrangements and aisle spacing are limited, but quantities are not.

113 Sections and Liquid Storage Rooms Liquid storage rooms and warehouses are classified as Group H-3 or H-2 occupancies. Rooms or warehouses must meet the requirements of IBC Sections 307, 414 and 415. Automatic sprinkler protection must comply with IFC Chapter 57 and NFPA 30. Rooms require spill control, secondary containment and mechanical ventilation in accordance with CMC Section 505.

114 Laboratory Fires 1/11/02 University of California at Santa Cruz A three-alarm fire Friday on the fourth floor of Sinsheimer Laboratories injured no one but gutted two large research labs, damaged other areas of the building, and closed several other buildings in the Science Hill area of campusf

115 Fire Protection of Flammable & Combustible Liquids In comparison to other stored commodities and goods, designing automatic sprinkler systems for the protection of flammable and combustible liquids represents a challenge. Fire protection for these hazardous materials is an either/or proposition.

116 Fire Protection of Flammable & Combustible Liquids Automatic sprinkler systems for liquid storage rooms and warehouses must also comply with NFPA 30 (see Sections and ). The following variables must be evaluated: Container, portable tank or IBC? Container material of construction Miscibility of the stored liquid Viscosity of the stored liquid Pressure-relieving construction Solid-pile, palletized or rack storage? Classification and chemical stability of the stored liquid Weight (percent flammable or combustible liquid component) Viscosity at room temperature [in thousands of centipoise (cp)]

117 Fire Protection of Flammable & Combustible Liquids In many cases the only viable protection option is the use of rack storage. When rack storage is selected NFPA 30, Chapter 16 commonly specifies fire protection based on four various design schemes. Schemes A through D all require the construction of horizontal barriers and the installation of in-rack or in-rack and face sprinklers.

118 Containers and Portable Tanks Inside of Buildings 1. A sprinkleredgroup F occupancy contains 90 gallons of Class IB liquids stored in two approved liquid cabinets (split 45 gallons in each cabinet). The 9,000-square-foot building is considered as one control area. What is the MAQ for this control area? 2. What is minimum air exchange rate required for a ventilation system in a Group H, Division 3, liquid storage room?

119 Containers and Portable Tanks Inside of Buildings 3. What is the maximum amount of liquid permitted in a single control area of Group M occupancy which contains rack storage of Class IB, IC, II and IIIA liquids protected in accordance with Table (4)? 4. How many gallons of Class IC flammable liquids can be stored in an unsprinklered basement located one level below the grade plane?

120 Section Outdoor Storage of Containers and Portable Tanks Plans Location on property Spill control and containment Security Protection from vehicles Clearance from combustibles Weather protection Empty container and tank storage

121 Section Outdoor Container & Portable Tank Storage Storage requirements and pile volume limits in Table are based on the classification of the liquid and if it is stored in containers or portable tanks. Quantity/pile limits are based on the most hazardous class of liquid present. Limited quantities are permitted adjacent to buildings.

122

123 Section 5705 Dispensing, Use, Mixing and Handling

124 Section 5705 Dispensing, Use, Mixing and Handling When flammable and combustible liquids are taken out of storage and put into use, the fire risk increases. Because product transfer, dispensing, mixing, blending and a variety of other processes may liberate flammable vapors into the atmosphere, where they can be ignited, additional safeguards and protection methods are often required.

125 Section 5705 Dispensing, Use, Mixing and Handling Section 5705 sets forth minimum safety requirements to prevent or control fires and explosions associated with the use of flammable and combustible liquids.

126 Section 5705 Dispensing, Use, Mixing and Handling Permitted liquid transfer methods Cleaning with flammable and combustible liquids Solvent distillation units Use, dispensing, mixing rooms Explosion control Special ventilation for open systems

127 Section Liquid Transfer Class I liquids and Class II and IIIA liquids heated above their flash point in containers exceeding 5.3 gallons must be transferred: From UL 30 listed safety cans, Through approved closed piping system, From containers or tanks by a pump taking suction from the top, By gravity through an approved self-or automatic closing valve when spill control and secondary containment are provided and only Class IB, IC, II or III liquids are used, or Using approved engineered systems. 127

128 Section Maximum Allowable Quantities Quantities per control area are limited to those in Table (1) and occupancy limits of Section Quantities are limited in open or closed systems. The MAQ may be increased 100% in sprinklered buildings. When the MAQ is exceeded the use must occur in a Group H, Division 2 or 3, liquid use, dispensing and (UDM) mixing room. (See IBC Section and IFC Section )

129 Section Cleaning Operations Cleaning with flammable and combustible liquids is only permitted in a: Code-compliant Group H-2 or H-3 UDM room, or Listed parts cleaning machine. Listed machines must use a solvent that is approved for use in the cleaning machine and not exceed the quantity limits in Section Multiple machines require separation in accordance with Section Photograph courtesy of Safety Kleen Corporation, Plano TX

130 Section Closed System UDM Rooms Mechanical ventilation designed to exhaust not less than 1 cfm per square foot. Explosion control in accordance with the IBC is required for: Class IA liquids, and Otherwise where an explosive environment can occur as a result of the process. Spill control and secondary containment are required when: Individual container volume exceeds 55 gallons, or The aggregate capacity of containers is greater than 1,000 gallons.

131 Section Open System UDM Rooms Requirements for useopen systems are more restrictive because of the ease that vapor can be ignited: Explosion control is required for Class IA and IB liquids. Spill control is required when liquids are dispensed into containers greater than 1.1 gallon capacity, or liquids are used and mixed in open containers greater than 5.3 gallon capacity.

132 Section Dispensing, Use, Mixing & Handling Outside Buildings Refer to Chapter 23 for motor-vehicle fuel dispensing. Spill control and drainage control are required. Location on property must satisfy the distances in Section Table specifies dispensing MAQ for outdoor areas. These MAQs are much lower than those in Chapter 50.

133 Section Solvent Distillation Units SDUs are an appliance that receives contaminated flammable or combustible liquids and distills the contents to remove contaminants and recover the solvents. Section limits SDUs to a maximum capacity of 60 gallons and requires they be listed in accordance with UL 2208.

134 Closed Cup Flash Point and Boiling Point Temperatures for 4 Solvents Acetone Hexane Methyl Ethyl Ketone Toluene Tbp ( F) Tfp ( F)

135 Section Solvent Distillation Units SDUs that exceed 60 gallons are treated by Section as process vessels. SDUs are prohibited in basements and must be listed for processing any liquids that are also classified as unstable (reactive), including nitrocellulose. These appliances require labeling and a manufacturer s instruction manual. 135

136 Section 5706 Special Operations

137 Section 5706 Special Operations Farms and construction sites Well drilling and operations Bulk plants or terminals Bulk transfer and process transfer operations Tank vehicles and vehicle operation Refineries Vapor recovery and vapor-processing systems

138 Special Controls for Flammable and Combustible Liquids

139 Spill Control and Secondary Containment From Chapter 50 Spill control Largest single container Secondary containment Largest container + 20 minutes of sprinkler water discharge (indoor) Unlike other hazardous materials, additional free board for rainwater accumulation is not required for outdoor tank dikes or outdoor tank car and tank vehicle loading and unloading areas For storage and closed use, thresholds are 55-gallon individual container and 1,000-gallon aggregate (aggregate for secondary containment only) For open use, thresholds are 1.3-gallon individual container and 5.3-gallon aggregate

NFPA 30-2008: Basic Requirements for Storage Tanks

NFPA 30-2008: Basic Requirements for Storage Tanks NFPA 30-2008: Basic Requirements for Storage Tanks New York City Metro Chapter Society of Fire Protection Engineers New York, NY February 22, 2011 NFPA 30, Flammable and Combustible Liquids Code Storage

More information

Ethanol Vehicle and Infrastructure Codes and Standards Citations

Ethanol Vehicle and Infrastructure Codes and Standards Citations Ethanol Vehicle and Infrastructure Codes and Standards Citations This document lists codes and standards typically used for U.S. ethanol vehicle and infrastructure projects. To determine which codes and

More information

Technical Requirements for Aboveground Storage Tanks (ASTs) Storing Class IIIB Liquids (other than used oil)

Technical Requirements for Aboveground Storage Tanks (ASTs) Storing Class IIIB Liquids (other than used oil) Technical Requirements for Aboveground Storage Tanks (ASTs) Storing Class IIIB Liquids (other than used oil) References: Comm 10 2009 EDITION / NFPA 30 2008 EDITION ITEM DESCRIPTION Comm 10 / NFPA General

More information

FLAMMABLE AND COMBUSTIBLE LIQUIDS. n OSHA Changes

FLAMMABLE AND COMBUSTIBLE LIQUIDS. n OSHA Changes FLAMMABLE AND COMBUSTIBLE LIQUIDS OSHA Changes Introduction This module covers the two primary hazards associated with flammable and combustible liquids: explosion and fire. In order to prevent these hazards,

More information

In accordance with NFPA 30, these containers are not to store Class I flammable liquids.

In accordance with NFPA 30, these containers are not to store Class I flammable liquids. In accordance with NFPA 30, these containers are not to store Class I flammable liquids. Zurich recommends storing these containers in dedicated liquid storage rooms, detached buildings, or in listed dispensing

More information

FLAMMABLE AND COMBUSTIBLE LIQUIDS

FLAMMABLE AND COMBUSTIBLE LIQUIDS GAP.8.1.0 A Publication of Global Asset Protection Services LLC FLAMMABLE AND COMBUSTIBLE LIQUIDS INTRODUCTION National Fire Protection Association (NFPA) documents describe a level of fire protection

More information

The following definitions apply with regard to requirements specified in this document:

The following definitions apply with regard to requirements specified in this document: GUIDELINES FOR INSTALLATION OF TEMPORARY AND PERMANENT ABOVEGROUND DIESEL FUEL TANKS FOR EMERGENCY AND STANDBY POWER SYSTEMS LOCATED OUTSIDE OF BUILDINGS For Use by Unidocs Member Agencies or where approved

More information

OREGON FIRE CODE Interpretations and Technical Advisories

OREGON FIRE CODE Interpretations and Technical Advisories OREGON FIRE CODE Interpretations and Technical Advisories A collaborative service by local and state fire professionals, along with our stakeholders and customers, to provide consistent and concise application

More information

Flammable Liquids 29 CFR 1910.106

Flammable Liquids 29 CFR 1910.106 Flammable Liquids 29 CFR 1910.106 OSHA s Directorate of Training and Education These materials were developed by OSHA s Directorate of Training and Education and are intended to assist employers, workers,

More information

Ontario Fire Code SECTION 5.13 DIP TANKS. Illustrated Commentary. Office of the Ontario Fire Marshal

Ontario Fire Code SECTION 5.13 DIP TANKS. Illustrated Commentary. Office of the Ontario Fire Marshal Ontario Fire Code SECTION 5.13 DIP TANKS Illustrated Commentary Office of the Ontario Fire Marshal Dip Tanks Illustrated Commentary 1 5.13.1. Location 5.13.1.1. Dip tank operations involving flammable

More information

Waste Oil Collection / Storage

Waste Oil Collection / Storage ENVIRONMENTAL & REGULATORY SERVICES Storage Tank Regulation Section P. O. Box 7837 Madison, Wisconsin 53707-7837 TDD #: (608) 264-8777 http://www.commerce.state.wi.us http://www.wisconsin.gov Jim Doyle,

More information

527 CMR: BOARD OF FIRE PREVENTION REGULATIONS 527 CMR 14.00: FLAMMABLE AND COMBUSTIBLE LIQUIDS, FLAMMABLE SOLIDS OR FLAMMABLE GASES

527 CMR: BOARD OF FIRE PREVENTION REGULATIONS 527 CMR 14.00: FLAMMABLE AND COMBUSTIBLE LIQUIDS, FLAMMABLE SOLIDS OR FLAMMABLE GASES 527 CMR 14.00: FLAMMABLE AND COMBUSTIBLE LIQUIDS, FLAMMABLE SOLIDS OR FLAMMABLE GASES Section 14.01: Scope 14.02: Definitions 14.03: Storage 14.04: Handling of Flammable Fluids 14.05: Handling of Flammable

More information

BP WIND ENERGY POLICIES AND PROCEDURES

BP WIND ENERGY POLICIES AND PROCEDURES BP WIND ENERGY POLICIES AND PROCEDURES Document Control Details 1.0 Purpose/Scope 1.1 This procedure provides the minimum requirements to be followed for the storage of flammable or combustible materials

More information

Notes. Material 1. Appropriate Flammable Liquids

Notes. Material 1. Appropriate Flammable Liquids 29 CFR 1910.106 Flammable Materials Flammable Liquids Preparation 1. Read Applicable Background information and related Company Policy Chapter. 2. Make Copies of this Lesson Plan for Personnel 3. Make

More information

ADMINISTRATIVE SERVICES MANUAL

ADMINISTRATIVE SERVICES MANUAL Purpose Responsibilities Proper Storage and use of flammable liquids can significantly reduce the possibility of accidental fires and injuries. To minimize risk to life and properly, the requirements of

More information

OSHA Tank Venting DEFINITIONS

OSHA Tank Venting DEFINITIONS OSHA Tank Venting DEFINITIONS 1910.106 - Flammable and combustible liquids. 1910.106(a)(2) (a) Definitions. As used in this section: (2) Atmospheric tank shall mean a storage tank which has been designed

More information

FLAMMABLE AND COMBUSTIBLE LIQUIDS

FLAMMABLE AND COMBUSTIBLE LIQUIDS CHAPTER 57 FLAMMABLE AND COMBUSTIBLE LIQUIDS SECTION 5701 GENERAL 5701.1 Scope and application. Prevention, control and mitigation of dangerous conditions related to storage, use, dispensing, mixing and

More information

HealthandSafetyOntario.ca. Introduction. Storage Containers. Storing Flammable Liquids

HealthandSafetyOntario.ca. Introduction. Storage Containers. Storing Flammable Liquids Flammable Liquids Storage Introduction This guideline is designed to help you store flammable liquids safely. It is based on the requirements of the Ontario Fire Code, Part 4, and of the Regulations for

More information

TYPICAL FIRE SAFETY INSPECTION VIOLATIONS

TYPICAL FIRE SAFETY INSPECTION VIOLATIONS TYPICAL FIRE SAFETY INSPECTION VIOLATIONS The following is a list of typical violations often found by inspectors and a generic solution. You can use this list to improve the safety of your facility, to

More information

Requirements for Hydrogen Storage and Use

Requirements for Hydrogen Storage and Use Requirements for Hydrogen Storage and Use I. INTRODUCTION Fire and Life-Safety Group (FLS) The following is a summary of the fire and building code requirements for the storage and use of hydrogen. These

More information

Flammable and Combustible Liquids. Slide 1 (of 23)

Flammable and Combustible Liquids. Slide 1 (of 23) Flammable and Combustible Liquids Slide 1 (of 23) Introduction The two primary hazards associated with flammable and combustible liquids are explosion and fire Safe handling and storage of flammable liquids

More information

Sample Written Program. For. Flammable Liquids

Sample Written Program. For. Flammable Liquids Sample Written Program For Flammable Liquids 1 Flammable Liquids. (YOUR COMPANY NAME) Purpose Proper Storage and use of flammable liquids can significantly reduce the possibility of accidental fires and

More information

MOTOR FUEL DISPENSING SAFETY

MOTOR FUEL DISPENSING SAFETY STRATEGIC OUTCOMES PRACTICE TECHNICAL ADVISORY BULLETIN January 2010 MOTOR FUEL DISPENSING SAFETY Fire! Not an alarm anyone wants to hear, especially not when the fire is burning at a major fuel source.

More information

FLAMMABLE AND COMBUSTIBLE LIQUIDS

FLAMMABLE AND COMBUSTIBLE LIQUIDS CHAPTER 34 FLAMMABLE AND COMBUSTIBLE LIQUIDS SECTION 3401 GENERAL 3401.1 Scope and application. Prevention, control and mitigation of dangerous conditions related to storage, use, dispensing, mixing and

More information

NFPA31FuelOilPiping 1 Revised 3-1-11

NFPA31FuelOilPiping 1 Revised 3-1-11 NFPA 31 Fuel Oil Piping, Installation and Testing Chapter 8 Fuel Piping Systems and Components 8.1 Scope. This chapter shall apply to piping systems and their components used to transfer fuel oil from

More information

The following definitions apply with regard to requirements specified in this document:

The following definitions apply with regard to requirements specified in this document: GUIDELINES FOR INSTALLATION OF TEMPORARY AND PERMANENT ABOVEGROUND DIESEL FUEL TANKS FOR EMERGENCY AND STANDBY POWER SYSTEMS LOCATED OUTSIDE OF BUILDINGS For Use by Unidocs Member Agencies or where approved

More information

FLAMMABLE AND COMBUSTIBLE LIQUIDS

FLAMMABLE AND COMBUSTIBLE LIQUIDS CHAPTER 34 FLAMMABLE AND COMBUSTIBLE LIQUIDS SECTION 3401 GENERAL 3401.1 Scope and application. Prevention, control and mitigation of dangerous conditions related to storage, use, dispensing, mixing and

More information

Flammable liquid classes: Combustible Liquid Classes. Class IC. Class II. Class IB F.P. below 22.8 C (73 F), boiling point at or above 37.

Flammable liquid classes: Combustible Liquid Classes. Class IC. Class II. Class IB F.P. below 22.8 C (73 F), boiling point at or above 37. BCFC Part 4 Flammable and Combustible Liquids Application: BCFC Part 4 Part 4 provides for the storage, handling, use and processing of flammable liquids and combustible liquids in buildings,, structures

More information

Queen's University Environmental Health and Safety

Queen's University Environmental Health and Safety April, 2009 1 SOP-Chem-08 1.0 Introduction This document is intended as a guide to the Queen s University requirements for handling and storing flammable and combustible material in non-laboratories areas.

More information

Flammable Liquids Storage

Flammable Liquids Storage A Health and Safety Guideline for Your Workplace Flammable Liquids Storage Introduction This guideline is designed to help you store flammable liquids safely. It is based on the requirements of the Ontario

More information

OSHA Office of Training and Education 1

OSHA Office of Training and Education 1 Flammable and Combustible Liquids OSHA Office of Training and Education 1 Introduction The two primary hazards associated with flammable and combustible liquids are explosion and fire Safe handling and

More information

MAINE DEPARTMENT OF ENVIRONMENTAL PROTECTION

MAINE DEPARTMENT OF ENVIRONMENTAL PROTECTION Oxford Hills Bus Garage 36 Brown St, Norway, ME Oil Storage Inspection 2/20/14 CONDITIONS OBSERVED Underground Oil Storage: 12,000 gallon underground oil storage tank (split 10,000 gallon diesel/2,000

More information

Flammable Liquids Storage

Flammable Liquids Storage A Health and Safety Guideline for Your Workplace Flammable Liquids Storage Introduction This guideline is designed to help you store flammable liquids safely. It is based on the requirements of the Ontario

More information

Formal Interpretation NFPA 30. Flammable and Combustible Liquids Code. 2012 Edition

Formal Interpretation NFPA 30. Flammable and Combustible Liquids Code. 2012 Edition Reference: 1.1, Scope F.I. 84-4 Background: Tank trailers and semi-trailers are loaded with flammable or combustible liquid and moved to a storage yard. There, the tank vehicles may be kept for days, weeks,

More information

Denver Fire Department Idle Pallet Storage Guidelines Per NFPA 13_Chpt 12

Denver Fire Department Idle Pallet Storage Guidelines Per NFPA 13_Chpt 12 Idle wood and plastic pallets introduce a severe fire condition. Stacking idle pallets in piles is the best arrangement of combustibles to promote rapid spread of fire, heat release, and complete combustion.

More information

How To Safely Handle A Spill

How To Safely Handle A Spill WD DWGB 22 6 2010 Best Management Practices for Fueling and Maintenance of Excavation and Earthmoving Equipment Env Wq 401, Best Management Practices for Groundwater Protection, applies to a variety of

More information

Static Spark Ignites Flammable Liquid during Portable Tank Filling Operation

Static Spark Ignites Flammable Liquid during Portable Tank Filling Operation Static Spark Ignites Flammable Liquid during Portable Tank Filling Operation No. 2008-02-I-IA (September 2008) Key Lessons for Safe Handling and Storage of Flammables Ensure that equipment, such as fill

More information

Steel Tank Institute AST Inspections. Dana Schmidt, PE STI/SPFA

Steel Tank Institute AST Inspections. Dana Schmidt, PE STI/SPFA Steel Tank Institute AST Inspections Dana Schmidt, PE STI/SPFA Agenda Brief review of SPCC Rule SPCC relevance to small tanks and small facilities. SP001 Standard for Inspection of Aboveground Storage

More information

Section III Hazardous Materials Management

Section III Hazardous Materials Management Section III Hazardous Materials Management This section of the Everyday Hazmat User s Training Guide covers various types of hazardous materials commonly found in the USDA Forest Service. Federal regulations

More information

List of Frequently Utilized Storage Tank Standards and Practices

List of Frequently Utilized Storage Tank Standards and Practices List of Frequently Utilized Storage Tank Standards and Practices Below is a list of frequently used storage tank standards and practices from organizations that are referenced in 25 PA Code, Chapter 245.

More information

Containment Requirements

Containment Requirements Introduction: Building and fire codes are developed by associations for adoption by federal, state and local authorities having jurisdiction. The local municipalities often make amendments or changes to

More information

Application for the Construction or Installation of Aboveground Storage Tank (AST) Systems or Associated Underground or Over-water Piping Systems

Application for the Construction or Installation of Aboveground Storage Tank (AST) Systems or Associated Underground or Over-water Piping Systems Page 1 of 5 Application for the Construction or Installation of Aboveground Storage Tank (AST) Systems or Associated Underground or Over-water Piping Systems New Hampshire Department of Environmental Services

More information

Warehouse Checklist. Warehouse Construction

Warehouse Checklist. Warehouse Construction PAGE 1 Warehouse Checklist Recent NFPA statistics estimate that in 1998 approximately 36,000 fires occurred in structures used for storage, accounting for $687mm of damage (over 10% of total fire damage

More information

LIQUEFIED PETROLEUM GASES

LIQUEFIED PETROLEUM GASES CHAPTER 38 LIQUEFIED PETROLEUM GASES SECTION 3801 GENERAL 3801.1 Scope. Storage, handling and transportation of liquefied petroleum gas (LP-gas) and the installation of LP-gas equipment pertinent to systems

More information

CHAPTER 10 BOILERS, WATER HEATERS AND PRESSURE VESSELS

CHAPTER 10 BOILERS, WATER HEATERS AND PRESSURE VESSELS CHAPTER 10 BOILERS, WATER HEATERS AND PRESSURE VESSELS SECTION 1001 GENERAL 1001.1 Scope. This chapter shall govern the installation, alteration and repair of boilers, water heaters and pressure vessels.

More information

1. Site plans assist the Fire Department to determine where a potential spill can be contained. The detailed site plan shall include the following:

1. Site plans assist the Fire Department to determine where a potential spill can be contained. The detailed site plan shall include the following: Secondary Containment, Spill Control and Drainage Guidelines for Hazardous Materials per 2010 CFC PURPOSE The intent of this guideline is to provide the requirements for the design and construction of

More information

Fixed or Semi-Fixed Fire Protection Systems for Storage Tanks

Fixed or Semi-Fixed Fire Protection Systems for Storage Tanks Fixed or Semi-Fixed Fire Protection Systems for Storage Tanks In the early years of the oil industry, fire in a storage tank was a common occurrence. Virtually all products were stored in cone roof tanks

More information

Fire Pump Plan Review March 2010

Fire Pump Plan Review March 2010 Fire Pump Plan Review March 2010 Date of Review: / / Permit Number: Business/Building Name: Address of Project: Designer Name: Designer s Phone: Contractor: Contractor s Phone: Occupancy Classification:

More information

A Code Review for Emergency Generators and Indoor Use of Portable Generators

A Code Review for Emergency Generators and Indoor Use of Portable Generators A Code Review for Emergency Generators and Indoor Use of Portable Generators By: the Fire and Life-Safety Group (FLS) Fire Code requires that emergency generators be stationary generators. Therefore, a

More information

Model Safety Program

Model Safety Program Model Safety Program DATE: SUBJECT: Flammable and Combustible Liquids Safety Program REGULATORY STATUTE: OSHA 29 CFR 1910.106 OVERALL RESPONSIBILITY: The (YOUR COMPANY) Safety Officer is. He/she is solely

More information

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION Fire Pump Plan Review 2009 International Fire Code and NFPA 20 Date of Review / / BLD201 - Project Address: Project Name: Contractor s Business

More information

Section A SPCC Plan Implementation Checklist This section of the report addresses compliance with certain requirements of Federal Regulations 40 CFR 112. I. STATUS OF SPCC PLAN (40 CFR 112.3) YES NO A.

More information

FLAMMABLE AND COMBUSTIBLE LIQUIDS

FLAMMABLE AND COMBUSTIBLE LIQUIDS FLAMMABLE AND COMBUSTIBLE LIQUIDS These guidelines provide requirements for all University faculty, staff, and students using, handling, or storing flammable and combustible liquids. These requirements

More information

COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES

COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES These guidelines are to be used for ALL commercial cooking hoods, ventilation systems and related fire suppression

More information

ENVIRONMENT, SAFETY, HEALTH, AND QUALITY DIVISION

ENVIRONMENT, SAFETY, HEALTH, AND QUALITY DIVISION ENVIRONMENT, SAFETY, HEALTH, AND QUALITY DIVISION Chapter 40: Chemical Lifecycle Management Chemical Storage Asset Requirements Product ID: 223 Revision ID: 1487 Date published: 20 May 2013 Date effective:

More information

Flammable Storage in a Biotech Facility

Flammable Storage in a Biotech Facility Deputy Chief Gerard Mahoney; Chairman 100 Smith Place Cambridge, MA, 02138 (617) 349-4944 Fax: (617) 349-4905 Mailing Address: 491 Broadway Cambridge, MA 02138 Flammable Storage - Intro Date: 12/09/2009

More information

CHAPTER 30 COMPRESSED GASES

CHAPTER 30 COMPRESSED GASES CHAPTER 30 COMPRESSED GASES SECTION 3001 GENERAL 3001.1 Scope. Storage, use and handling of compressed gases in compressed gas containers, cylinders, tanks and systems shall comply with this chapter, including

More information

Flammable Liquids Bulk Storage: Guidelines for British Columbia s Provincial Industrial Railways

Flammable Liquids Bulk Storage: Guidelines for British Columbia s Provincial Industrial Railways Flammable Liquids Bulk Storage: Guidelines for British Columbia s Provincial Industrial Railways Guidelines Respecting the Design, Location, Construction, Operation and Maintenance of Stationary Bulk Storage

More information

ALVERNIA UNIVERSITY OSHA REGULATION: 29 CFR 1910.252 WELDING, CUTTING, AND BRAZING ( HOT WORK ) SECTION: 3600

ALVERNIA UNIVERSITY OSHA REGULATION: 29 CFR 1910.252 WELDING, CUTTING, AND BRAZING ( HOT WORK ) SECTION: 3600 OSHA REGULATION: 9 CFR 90.5 WELDING, CUTTING, AND BRAZING ( HOT WORK ) A. POLICY. This procedure follows requirements set forth in 9 CFR 90.5.. This policy applies to all Hot Work operations being done

More information

Presented by: Rich Perry Marsh Risk Consulting

Presented by: Rich Perry Marsh Risk Consulting Flammable and Combustible Liquids Presented by: Rich Perry Marsh Risk Consulting What s the Big Deal? Flammable and combustible liquids are easily ignited Ignite with explosive force Burn readily and give

More information

CITY OF WASHINGTON SPILL PREVENTION, CONTROL AND COUNTERMEASURE PLAN

CITY OF WASHINGTON SPILL PREVENTION, CONTROL AND COUNTERMEASURE PLAN CITY OF WASHINGTON SPILL PREVENTION, CONTROL AND COUNTERMEASURE PLAN Adopted October 5, 2009 Table of Contents Chapter Description Page 1 Facility Descriptions... 3 1.1 Municipal Power Plant, 1001 Park

More information

Spray Booth Guideline

Spray Booth Guideline Department of Development Service 135 North D Street, Perris CA. 92570 Phone: (951) 443-1029 Fax: (951) 943-3293 PURPOSE The intent of this guideline is to provide the information necessary to ensure that

More information

Flammable and Combustible Liquid

Flammable and Combustible Liquid Flammable and Combustible Liquid Storage Challenges Christopher J. Wieczorek, Ph.D., FM Global David Nugent, The Valspar Corporation Global Research Update: High Challenge Storage Protection 27 June 2012,

More information

ENGINEERED DRAWINGS FOR PETROLEUM STORAGE TANKS

ENGINEERED DRAWINGS FOR PETROLEUM STORAGE TANKS Facility Name: ENGINEERED DRAWINGS FOR PETROLEUM STORAGE TANKS The following is intended to be used as a guideline for information required to appear on engineered drawings involving petroleum storage

More information

STORAGE AND HANDLING OF FLAMMABLE AND COMBUSTIBLE LIQUIDS

STORAGE AND HANDLING OF FLAMMABLE AND COMBUSTIBLE LIQUIDS Page 1 of 10 STORAGE AND HANDLING OF These guidelines provide requirements for all University faculty, staff, and students using, handling, or storing flammable and combustible liquids. These requirements

More information

COMPRESSED GASES. 1.2 The contents of each cylinder and container must be clearly identified (by tag or stamp) on the cylinder.

COMPRESSED GASES. 1.2 The contents of each cylinder and container must be clearly identified (by tag or stamp) on the cylinder. Page 1 of 5 COMPRESSED GASES A compressed gas is defined as any mixture of gases in a container with a pressure exceeding 40 psi. at 70 o F, or 104 psi. at 130 o F; or any flammable liquid with an absolute

More information

Air Eliminators and Combination Air Eliminators Strainers

Air Eliminators and Combination Air Eliminators Strainers Description Air Eliminators and Combination Air Eliminator Strainers are designed to provide separation, elimination and prevention of air in piping systems for a variety of installations and conditions.

More information

OPERATIONS & MAINTENANCE (O&M) FOR PROPANE STORAGE FACILITIES

OPERATIONS & MAINTENANCE (O&M) FOR PROPANE STORAGE FACILITIES OPERATIONS & MAINTENANCE (O&M) FOR PROPANE STORAGE FACILITIES Reference: National Fire Protection Association (NFPA) Pamphlet No. 58 Liquefied Petroleum Gas Code, 2001, Chapter 11 Type of Facility: Petroleum

More information

Pressure Vessels (Air Compressors) and LPG Tanks

Pressure Vessels (Air Compressors) and LPG Tanks Pressure Vessels (Air Compressors) and LPG Tanks 1. Identification of Workplace Hazard Any container, tank or vessel that contains pressurized material is a potential hazard to employees due to the force

More information

Practical Guidelines for Electrical Area Classification in Combustion Turbine-Generator Power Plants

Practical Guidelines for Electrical Area Classification in Combustion Turbine-Generator Power Plants Practical Guidelines for Electrical Area Classification in Combustion Turbine-Generator Power Plants Ram K. Saini, P.E. Principal Engineer, Chuck Emma, P.E. Principal Engineer, Burns and Roe Enterprises,

More information

Civil Engineering Sector Labour-Management Health and Safety Committee

Civil Engineering Sector Labour-Management Health and Safety Committee PROCEDURE FOR THE STORAGE AND HANDLING OF FUEL ON CONSTRUCTION SITES Civil Engineering Sector Labour-Management Health and Safety Committee July 2008 PROCEDURE FOR THE STORAGE AND HANDLING OF FUEL ON CONSTRUCTION

More information

Site and Storage Conditions for Class 3.1 Flammable Liquids

Site and Storage Conditions for Class 3.1 Flammable Liquids Site and Storage Conditions for Class 3.1 Flammable Liquids Introduction Contents Introduction... 1 SITE AND STORAGE CONDITIONS...2 Part 1 General Flammability Conditions...2 Part 2 Conditions Relating

More information

Morrison Bros. Co. General Product Specifications

Morrison Bros. Co. General Product Specifications Morrison Bros. Co. General Product Specifications Tank Mounted Spillbox The spill containment device is manufactured to contain spills and drips that may occur at the fill point on aboveground storage

More information

General Fire Code Requirements Within Commercial Tenant Spaces

General Fire Code Requirements Within Commercial Tenant Spaces FIRE DEPARTMENT in cooperation with Scope: General Fire Code Requirements Within Commercial Tenant Spaces This handout is designed to assist owners, architects, contractors and others in understanding

More information

SELF-INSPECTION PROGRAM FOR FIRE PROTECTION EQUIPMENT

SELF-INSPECTION PROGRAM FOR FIRE PROTECTION EQUIPMENT SELF-INSPECTION PROGRAM FOR FIRE PROTECTION EQUIPMENT INTRODUCTION No matter how reliable fire protection equipment may seem, periodic maintenance is needed to ensure proper operation. Fire protection

More information

Hazardous Waste Accumulation, Storage, & Labeling

Hazardous Waste Accumulation, Storage, & Labeling Nadine Deak, Kalamazoo District Office 269-567-3592 or deakn@michigan.gov Jenny Bennett, Gaylord District Office 989-705-2421 or bennettj6@michigan.gov Hazardous Waste Accumulation, Storage, & Labeling

More information

Department of Transportation Hazardous Material Regulations General Awareness, Safety & Security Training. For: University of Dayton Hazmat Employees

Department of Transportation Hazardous Material Regulations General Awareness, Safety & Security Training. For: University of Dayton Hazmat Employees Department of Transportation Hazardous Material Regulations General Awareness, Safety & Security Training For: University of Dayton Hazmat Employees February, 2014 Overview Hazardous materials are substances

More information

Compressed Gases The Dangers

Compressed Gases The Dangers Compressed Gases COMPRESSED Compressed gases are any gases or mixture of gases exerting a gauge pressure of 6 pounds per square inch at 68 F. Federal regulations specify how these gases must be stored

More information

FUEL-OIL PIPING AND STORAGE

FUEL-OIL PIPING AND STORAGE CHAPTER 13 FUEL-OIL PIPING AND STORAGE SECTION MC 1301 GENERAL 1301.1 Scope. This chapter shall govern the design, installation, construction and repair of fuel-oil storage and piping systems. The storage

More information

Flammable and Combustible Storage Checklist

Flammable and Combustible Storage Checklist Flammable and Combustible Storage Checklist Occupational Safety and Health Bureau Montana Department of Labor and Industry Prepared for Montana Employers by the Occupational Safety & Health Bureau Department

More information

ASME B31.3 Process Piping. Scope of B31.3 Course

ASME B31.3 Process Piping. Scope of B31.3 Course ASME B31.3 Process Piping Charles Becht IV, PhD, PE Don Frikken, PE Instructors BECHT ENGINEERING COMPANY, INC. Introduction -1 Scope of B31.3 Course This course covers piping as typically used in process

More information

Electrical Classification

Electrical Classification Electrical Classification Using NFPA 70 and NFPA 499 to Classify Hazardous Locations Electrical classifications are established in accordance with the National Electrical Code, NFPA 70, also referred to

More information

Recommended Product Specifications Fuel Day Tank System Tramont UTRS Fuel Day Tank

Recommended Product Specifications Fuel Day Tank System Tramont UTRS Fuel Day Tank Recommended Product Specifications Fuel Day Tank System Tramont UTRS Fuel Day Tank This specification describes requirements for a Diesel Fuel Day Tank System consisting of one or more fuel tanks, an Electronic

More information

A GROUNDWATER PROTECTION PLAN FOR HOME HEATING OIL TANKS

A GROUNDWATER PROTECTION PLAN FOR HOME HEATING OIL TANKS A GROUNDWATER PROTECTION PLAN FOR HOME HEATING OIL TANKS What is a groundwater protection plan? A groundwater protection plan identifies the activities being conducted that can pollute groundwater and

More information

UltraTech International, Inc. Canadian Secondary Containment Requirements

UltraTech International, Inc. Canadian Secondary Containment Requirements UltraTech International, Inc. 11542 Davis Creek Court Jacksonville, Florida 32256 Canadian Secondary Containment Requirements The Canadian Council of Ministers of the Environment (CCME) is the major intergovernmental

More information

FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011

FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011 FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011 COLORADO SPRINGS FIRE DEPARTMENT Division of the Fire Marshal If you have any questions or comments regarding the

More information

SECTION FC 2706 NON-PRODUCTION CHEMICAL LABORATORIES

SECTION FC 2706 NON-PRODUCTION CHEMICAL LABORATORIES New York City Administrative Code - Title 29 New York City Fire Code SECTION FC 2706 NON-PRODUCTION CHEMICAL LABORATORIES 2706.1 Scope. This section shall govern the storage, handling and use of laboratory

More information

CITY AND COUNTY OF DENVER POLICY DENVER FIRE DEPARTMENT

CITY AND COUNTY OF DENVER POLICY DENVER FIRE DEPARTMENT Reference: IFC 34&27, Denver Amendments, and NFPA 30, 33, 704 Approved: Joseph L. Gonzales, Division Chief, Fire Prevention and Investigation Division Number: IFC-3403-1 Effective Date: February 1 st 2012

More information

Used Oil Guidance. Tank and Secondary Containment Requirements For Used Oil Processors

Used Oil Guidance. Tank and Secondary Containment Requirements For Used Oil Processors Used Oil Guidance Tank and Secondary Containment Requirements For Used Oil Processors Washington State Department of Ecology Publication Number 05-04-016 November 2005 For more information The Washington

More information

Standard Operating Procedure: Flammable Liquids

Standard Operating Procedure: Flammable Liquids Standard Operating Procedure: Flammable Liquids Standard operating procedures (SOP) are intended to provide you with general guidance on how to safely work with a specific class of chemical or hazard.

More information

IAC 7/2/08 Agriculture and Land Stewardship[21] Ch 44, p.1

IAC 7/2/08 Agriculture and Land Stewardship[21] Ch 44, p.1 IAC 7/2/08 Agriculture and Land Stewardship[21] Ch 44, p.1 CHAPTER 44 ON-SITE CONTAINMENT OF PESTICIDES, FERTILIZERS AND SOIL CONDITIONERS [Prior to 7/27/88, see 21 Ch 9] PESTICIDES 21 44.1(206) Definitions.

More information

Above-Ground Petroleum Storage Tank Manual With Data on NC Gasoline Vapor Recovery & EPA Spill Plan Information

Above-Ground Petroleum Storage Tank Manual With Data on NC Gasoline Vapor Recovery & EPA Spill Plan Information Above-Ground Petroleum Storage Tank Manual With Data on NC Gasoline Vapor Recovery & EPA Spill Plan Information By The North Carolina Petroleum & Convenience Marketers 7300 Glenwood Avenue Raleigh, North

More information

Trade Name of this Product Isopropyl Rubbing Alcohol 91% USP. Corporate Compliance Team 1666 East Touhy Avenue

Trade Name of this Product Isopropyl Rubbing Alcohol 91% USP. Corporate Compliance Team 1666 East Touhy Avenue Page 1 of 5 MSDS Document Product 1. Chemical Product and Company Identification Trade Name of this Product Manufacturer Contact Name Lawson Products, Inc. Corporate Compliance Team 1666 East Touhy Avenue

More information

STORE HAZARDOUS SUBSTANCES SAFELY. incompatibles gas cylinders

STORE HAZARDOUS SUBSTANCES SAFELY. incompatibles gas cylinders STORE HAZARDOUS SUBSTANCES SAFELY Suitable containers incompatibles gas cylinders Oxy-Acetylene welding flammable substances 35 36 STORE HAZARDOUS SUBSTANCES SAFELY STORE HAZARDOUS SUBSTANCES SAFELY Storing

More information

Recommended Fuel Piping Specification For UPP Piping, UL-971

Recommended Fuel Piping Specification For UPP Piping, UL-971 Recommended Fuel Piping Specification For UPP Piping, UL-971 1.0 General The primary delivery piping system shall be for suction or pressure applications and have semi-rigid coaxial type double wall construction,

More information

Tank Environmental Regulations. Aisha Beaty Barr Engineering Company

Tank Environmental Regulations. Aisha Beaty Barr Engineering Company Federal SPCC vs. State Storage Tank Environmental Regulations Aisha Beaty Barr Engineering Company purpose most industrial facilities utilize storage tanks in some capacity Federal and State regulations

More information

Installation Guidance: CNG Refueling Stations

Installation Guidance: CNG Refueling Stations Installation Guidance: CNG Refueling Stations Gas Technology Institute > Delaware Valley Regional Planning Commission (DVRPC) Webinar Gas Technology Institute (GTI) Overview Natural Gas Research and Development

More information

Hazardous Waste Determination and Management Plan

Hazardous Waste Determination and Management Plan Hazardous Waste Determination and Management Plan Prepared By: Triumvirate Environmental Developed: November 2014 Updated: Program Approval Associate Vice President of Public Safety & Administrative Services

More information