Customer Requirements at Cell Sites

Size: px
Start display at page:

Download "Customer Requirements at Cell Sites"

Transcription

1 Customer Requirements at Cell Sites Recommendations and Requirements INTRODUCTION The AT&T Requirements for Cell Sites was developed first, to provide a high level guideline for proper equipment installation and maintenance at cell sites necessary for AT&T to terminate its network facilities and provide services, and second, to ensure consistency of procedures across all regions. Proper installation and maintenance of AT&T facilities and equipment ( AT&T facilities ) can reduce failure frequencies. Installations of AT&T facilities at newly constructed sites must meet the AT&T specifications prior to installation and service activation. Installations at existing cell sites will be inspected by AT&T to ensure adherence to these requirements. Improperly installed wireless carrier equipment necessary for installation of AT&T facilities should be corrected and/or upgraded, by the wireless carrier. The AT&T engineer will work with the customer to ensure all requirements are met. The AT&T engineer will provide specific requirements based on current and future needs that are uncovered during initial meetings. Throughout the following document the term cell site contact will be used. In this document it can mean either the Operator ( Operator as used herein, depending on the circumstances, means the cell site operator or lessor/licensor), or an individual tenant at the cell site. The requirements are the same regardless of who the site contact is. Decisions for approval and responsibility of modifications at the site may need to be coordinated by the tenant with the Operator, if AT&T is not dealing directly with the Operator. Additionally, this document does not cover location and installation of AT&T s facilities outside the cell site premises. The term carrier when used applies specifically to wireless carriers other than the cell site operator. The term AT&T engineer will be used to mean the design engineer, the dedicated BIC (Building Industry Consultant) engineer where they exist, or the Inductive Coordination and 2008 AT&T Intellectual Property. All rights reserved. AT&T, the AT&T logo and all other AT&T marks contained herein are trademarks of AT&T Intellectual Property and/or AT&T affiliated companies. All other marks contained herein are the property of their respective owners.

2 Electrical Protection (ICEP) engineer where they exist. The AT&T engineer will be available to further elaborate on all of the requirements below during the initial on-site meeting. 1.0 Cell site contact Requirements The cell site contact is required to provide a safe and maintained entrance, parking, and exit for AT&T vehicles. 1.1 Access If the cell site/building is located inside a secured area, the cell site contact must agree to an access plan for AT&T maintenance and installation activities. This access plan is required to ensure that service quality can be maintained all hours of the day, and especially in afterhours conditions. One method used is daisy-chained locks (meaning that each provider at the site has one lock and chain in the lock loop to allow access to their authorized employees). 1.2 Conduit Requirements For underground entrance facilities, the cell site contact will provide conduit from the property line to AT&T's cable termination/protector location. The AT&T engineer will specify conduit runs as necessary to accommodate cable/fiber runs from the AT&T feeder termination (i.e., outside pedestal or in-building terminal) to each carrier's Network Interface (NI) location. Note that the NI location will be at an AT&T provided enclosure, as discussed in Section 1.5, installed by AT&T. These cell site contact provided conduits should be Schedule 40 PVC sized according to need. Note, however, that recommending a minimum 2 inch conduit makes sense even for short runs since this will easily accommodate future additions and changes of Network Terminating Wire (NTW). The following are recommended specifications: One conduit to house the initial facility (Note: the cell site contact is encouraged to place a second conduit for future fiber optic cable reinforcement). Conduit(s) will be at least 2 inch ID schedule 40 PVC (Conduit requirements greater than 2 inches will be specified by the AT&T engineer during the initial site visit). Conduits placed below ground must be buried between 24 and 36 inches deep. Conduit bends should optimally be minimized to one or two 90 degree bends (minimum 40 radius). This means that each conduit run should have no more than 180 degrees in bends between end points. Additionally, all bends in conduits will be electrical sweep bends with radii of at least 10X the conduit diameter (per BICSI TDMM, 11 th edition, section 4.19 table 4.4 Building Industry Consulting Services

3 International Telecommunications Distribution Methods Manual). All bends and off sets with a radius less than 80 are required to be encased in 3 of 2500 psi concrete with a 7 slump. All pull boxes placed after the second 90 degree bend are required to be 12 times the diameter of the conduit per TDMM 11 th edition, Chapter 4, section 1 subsection Pull Boxes for Conduit. Conduit should be sealed, capped, marked for AT&T s exclusive use, and turned up 3 above finished grade where appropriate to aid in subsequent locating. If the final environment is already established to a building or structure, the conduit should not protrude more than 1 beyond the inside wall or structure, with all rough or sharp edges having been de-burred. Conduit should be left clean, dry, and free of debris. Conduit should be equipped with either a 200-lb test pull wire/twin installed end to end for verification and pulling purposes. Conduits are to be placed in accordance with National Electric Code and other local and national standards. AT&T engineer may specify additional conduit requirements not specified. 1.3 Power Requirements As needed, the cell site contact must provide DC power with backup where available (-48V, -24V or +24V) to AT&T equipment as first choice. If DC is not available, the owner/tenant must provide 120VAC, 20A, convenience outlet and/or a dedicated outlet for local powering needs if any (i.e. loopback devices, etc.). Note: 1. Some circuit terminating equipment requires local powering for operation, so power service without backup can result in interruption of service. 1.4 Grounding Requirements A grounding system that covers the tower, structure, and site must be provided to insure the dispersal of lightning and foreign voltages. The grounding system should include grounding electrodes (rods), a ground ring(s), radial (counterpoise) conductors, either individually or in combination. To provide the best possible protection, a combination of all items should be used. Actual design should be determined based on lightning exposure, soil resistivity, as well as location and design of site. It is recommended that the ground system meets the following minimum requirements

4 Metallic ground rods that are 8 x 5/8. A ground ring that is composed of a minimum of #2 AWG bare copper conductor. The ground ring is to be buried a minimum of 30 below final grade. Each part is bonded using either an exothermic weld or irreversible connector. The attachment to the grounding system or tower/structure ring ground must be via #6 AWG or larger insulated copper ground wire provided by either the cell site contact or the AT&T engineer. In either case, the ground wire should be protected from damage and, in some cases, this may require owner/tenant-provided conduit. (Ground bar specifications will be based on the forecasted number of circuits, etc.) If a pedestal-type terminal is used for entrance cable protection, the AT&T engineer will request that the owner/tenant provide a #6 ground wire and coil sufficient slack wire in the vicinity of the proposed pedestal location. If the protectors will be located inside a building at the site, normal design procedures for inbuilding terminations protectors should be followed. All local building codes are to be followed as well as the specifications listed in the NFPA 70: National Electric Code, Article 250 Grounding and Bonding and ANSI T , "Electrical Protection of Communications Towers and Associated Structures", and any other applicable standards. 1.5 H-Frame Structures AT&T provides the outside enclosures to house DS1 network interface devices. The AT&T engineer will advise the cell site contact during the initial site visit to provide H-Frame structures upon which one or more enclosures will be mounted. Multiple carriers will not be housed in the same AT&T provided enclosure. The following is a list of requirements for H- Frame structures used to mount AT&T provided enclosures: The H-Frame structure must provide at least 96 inches of horizontal mounting space. However, more space may be required, depending on the number of carriers being served. The H-Frame structure must be at least 3 feet from any fence or other structure. A ground connection to the site grounding system is to be provided at the H-Frame to allow for grounding of the AT&T enclosure(s). The H-Frame should be connected to the grounding system. The H-Frame should be placed in a location where the AT&T enclosure is protected from damage.

5 Notes: 1. The H-Frame is recommended for all outside enclosures. See Section 1.6 for Inside Building Locations. 2. AT&T provided weatherproof enclosures may be pedestal, pole, or wall-mounted, if mutually agreed upon by the cell site contact and AT&T. 3. See Section 1.4 above for Site Bonding & Grounding Requirements. 1.6 Inside Building Locations If an inside building location will be used for AT&T facility termination and protection, the following guidelines apply and are consistent with normal in-building terminals: Backboard: A plywood backboard of sufficient size to mount all required AT&T equipment (AT&T contact will provide size specifications, a minimum of 4 feet x 4 feet x ¾ inches backboard). Busbar: The building owner must provide a busbar, mounted at the bottom of the backboard, to provide a single point ground for all telecom equipment at the backboard (Busbar Specification/Size will be based on the forecasted number of circuits, etc.). The busbar should be bonded to the building s power grounding system. 1.7 Roof-Top Sites Normally, AT&T establishes the demarcation point and places the network interface at the carrier s location. However, at some roof-top installations, AT&T and the carrier may agree to place the NI at the last AT&T serving terminal. Any wire beyond the point of demarcation is non-regulated and therefore may be provided by the carrier's vendor of choice, including AT&T. The carrier may be required to provide conduit. This would be specified by the AT&T engineer. Generally, the carrier will need the building owner's approval to have the conduit placed. Note: 1. Per Section 2.3 below, it is recommended that cable/wire placed on the customer's side of demarcation point be shielded and bonded.

6 1.8 High Voltage Locations Cell sites within a High Voltage area (such as power substation, power generating plant and high tension tower) require special high voltage isolation equipment to protect telecommunications facilities and personnel. The AT&T Inductive Coordination and Electrical Protection (ICEP) Engineer for the area must be engaged for assistance in designing the proper high voltage protection system necessary to protect AT&T facilities. Special Construction Charges or a Special Assembly may be applicable for high voltage protection equipment. 1.9 Outside Plant Cabinets AT&T may deploy an Outside Plant cabinet at the cell site to provide telecommunication facilities. The cabinet may be mounted to H-frame, exterior wall, pole or pad mounted. The carrier should provide DC power with backup where available. This ensures that as long as the carrier has power, the AT&T facilities serving the carrier will have power. This will also eliminate the delays associated with establishing commercial power to the cabinet. Generally, the DC power to the cabinet must be dual feed, fused at the source and 15 amps at the cabinet. AT&T will need access to the fuse/breaker at the power source, in case AT&T technicians need to work on the cabinet DC plant. AT&T is not liable for any power outages. Battery backup will not be provided with the Outside Plant cabinet with DC power from AT&T. In some instances, AT&T may need access to provide temporary generator to power cabinet. 2.0 Carrier Recommendations 1 In addition to the requirements listed in Section 1, carriers should adhere to the recommendations in this section in order to ensure continuous and effective service to their end users. 2.1 Loop Length Requirement 1 These additional network recommendations are mentioned for informational purposes only, and are not intended to be an exhaustive list of necessary measures to implement for continuity of service, or to impose additional obligations upon AT&T beyond what is contained in applicable contracts, tariffs and/or guidebooks relating to the services AT&T provides at cell site locations. It is the customer s sole obligation beyond AT&T s point of demarcation to take reasonable and necessary precaution, based on customer s engineering guidelines, to provide continuity of service to its end-user customers.

7 The following requirements apply to DS1, DS3 or Ethernet services: DS1 services: The carrier's equipment should be placed as close as possible to the demarcation point. Standards allow for up to 5.5 db of loss beyond the network interface unit. This is approximately 1,000 feet of CAT 5e wire. The closer to the network interface unit the stronger the signal will be for the carrier s equipment. DS3 services: The carrier's equipment must be placed within 450 feet of AT&T's point of demarcation. Ethernet services: The carrier's equipment must be placed within 50 feet of AT&T's point of demarcation when the handoff is electrical. It is strongly recommended that the customer use Cat 5 or better Shielded Cable with a protector designed for Ethernet. The shielding limits the amount of electrical interference and noise to the cable itself as well as limiting the amount of radiated interference from the cable. 2.2 Shielded Wire & Surge Protection Device Recommendation To ensure the highest possible level of service, AT&T recommends that carriers use shielded wire, with the shield grounded on both ends, to connect carrier equipment to the AT&T network interface. A listed primary protector used on both the AT&T end and the customer end of a shielded customer cable, grounded on each end, will help to achieve added protection - to both AT&T and customer equipment - from damage and service outage due to lightning strikes at cell sites. Primary protection should be placed as close as possible to the CPE and NIU. AT&T does not recommend using alternatives, such as unshielded wire in metallic conduit which is grounded on both ends, or the placement of a stranded #12 AWG coupled bonding conductor which is grounded on both ends and tie-wrapped to the unshielded wire at 12" intervals. Further, if it is determined that a circuit failure occurred as the result of improper installation of carrier s equipment beyond AT&T s point of demarcation, AT&T will bill the carrier for maintenance charges. AT&T may contact the carrier and request placement of shielded wire. AT&T will bill the carrier for maintenance resulting from problems with the wiring or equipment, such as this deviation. 2.3 Bonding and Grounding The purpose of grounding a metallic cable shield or strength member is to limit voltages that may be present from external sources such as lightning or accidental power contact. A low impedance path to ground is especially critical in locations with tall tower or antenna structures since they are particularly susceptible to damage from lightning. Each cell site location will have site-specific electrical protection or grounding requirements. The service

8 reliability of circuits terminating at a cell site largely depends on the grounding system of the cell site and associated structure. It is the carrier's responsibility to ensure that the site grounding system meets or exceeds requirements as listed in NFPA 70: National Electric Code, Article 250 Grounding and Bonding. It is also recommended that the requirements listed in ATIS , "Electrical Protection of Communications Towers and Associated Structures" be followed. The AT&T Engineer should serve as a technical resource for the requirements outlined in this document. The AT&T Engineer will work closely with carriers to resolve site ground system inadequacies. The following are a few bonding and grounding wire recommendations, based on site design, service offerings ordered, and facilities provided; additional requirements may be necessary based on a site s unique circumstances as determined by the carrier, with assistance from the AT&T Engineer: Notes: All grounding and bonding wires should be as short and straight as possible. Wires should be accessible for future visual inspections. Sharp bends in grounding and bonding conductors should be avoided. One splice is permitted in bond wires used for protector grounding, per the National Electrical Code Article 250, if an approved irreversible connector or exothermic welding process is used. The splice must be tagged with an AT&T ground wire tag. Only ground wires that are equal in size may be spliced. Splices are NOT permitted in the #6 AWG wires used for bonding cable shields, strength members, or splice cases. It is preferable to use a continuous length of wire for all grounds. It is recommended that all connections to ground system be #6 AWG. In order to insure proper grounding of AT&T services and equipment, all construction of the cell site/tower should be complete. This includes, but is not limited to the ground ring/system, conduit, permanent power, and supporting structures (H-Frame, Backboards). 1. The AT&T Engineer will clarify these requirements at the initial site meeting and provide follow-up clarification as needed. 2. At an outside enclosure, pedestal, or the building location, the protector, NCTE, cable shields, strength members, splice cases, etc. must all be bonded to the same location

9 (ground bar/busbar) to minimize differences in potential between these network components. 3. OSHA (s) (13) defines effectively grounded as: Intentionally connected to earth through a ground connection or connections of sufficiently low impedance and having sufficient current-carrying capacity to prevent the build-up of voltages which may result in undue hazard to connected equipment or to persons.

800 Communications Circuits

800 Communications Circuits ARTICLE 800 Communications Circuits INTRODUCTION TO ARTICLE 800 COMMUNICATIONS CIRCUITS This article has its roots in telephone technology. Consequently, it addresses telephone and related systems that

More information

Standards. www.nordx.com 5 ANSI/TIA/EIA-569-A (CSA T530)

Standards. www.nordx.com 5 ANSI/TIA/EIA-569-A (CSA T530) The primary focus of this standard is to provide design specifications and guidance for all building facilities relating to telecommunications cabling systems and components. This standard identifies and

More information

CUSTOMER REQUIREMENTS AT POWER SUBSTATIONS

CUSTOMER REQUIREMENTS AT POWER SUBSTATIONS CUSTOMER REQUIREMENTS AT POWER SUBSTATIONS Customer Handout Date Aug 2, 2010 Version 1.0 File Name Customer Requirements At Power Substations Document Id Outside Plant Engineering 1 Table Of Contents 1.0

More information

HOUSTON COMMUNITY COLLEGE HCC ALIEF CAMPUS MAIN BUILDING, FIRST, SECOND & FOURTH FLOORS RENOVATION ISSUE DATE: 10.17.12

HOUSTON COMMUNITY COLLEGE HCC ALIEF CAMPUS MAIN BUILDING, FIRST, SECOND & FOURTH FLOORS RENOVATION ISSUE DATE: 10.17.12 SECTION 27 05 26 - GROUNDING AND BONDING FOR COMMUNICATIONS SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes grounding and bonding products, design requirements and installation for communications

More information

Chapter 9. Bonding and Grounding

Chapter 9. Bonding and Grounding Chapter 9 Bonding and Grounding Objectives Describe why the cable should be bonded Describe bonding and grounding procedures Define Bonding and Grounding Explain Safety Benefits and intent of bonding and

More information

AT&T Specifications Trenching Conduit Boxes and M anholes Aerial Entrance Masts Service Cabinets Bonding and Grounding

AT&T Specifications Trenching Conduit Boxes and M anholes Aerial Entrance Masts Service Cabinets Bonding and Grounding AT&T Specifications Trenching Conduit Boxes and M anholes Aerial Entrance Masts Service Cabinets Bonding and Grounding A Guide for California Developers of Com m ercial Property This guide consists of

More information

CONSTRUCTION STANDARD ELECTRIC OPERATIONS ORGANIZATION

CONSTRUCTION STANDARD ELECTRIC OPERATIONS ORGANIZATION Page 1 of 11 ****This Standard Supercedes BECo CS2.13-2.3 & ComElectric OH Construction Manual, System Grounding Section, drawings CGND, GRDSUM, and C2**** 1.0 Bill of Materials GROUNDING AND BONDING POLE-MOUNTED

More information

Video Camera Installation Guide

Video Camera Installation Guide Video Camera Installation Guide The intent of this guide is to provide the information needed to complete or modify a video camera installation to avoid lightning and induced power surge damage. This guide

More information

www.klmtechgroup.com TABLE OF CONTENT

www.klmtechgroup.com TABLE OF CONTENT Page : 1 of 13 Project Engineering Standard www.klmtechgroup.com KLM Technology #03-12 Block Aronia, Jalan Sri Perkasa 2 Taman Tampoi Utama 81200 Johor Bahru Malaysia ELECTIRAL GROUNDING TABLE OF CONTENT

More information

NORTH ORANGE COUNTY COMMUNITY COLLEGE DISTRICT SECTION 27 05 26 GROUNDING AND BONDING FOR COMMUNICATION SYSTEMS

NORTH ORANGE COUNTY COMMUNITY COLLEGE DISTRICT SECTION 27 05 26 GROUNDING AND BONDING FOR COMMUNICATION SYSTEMS SECTION GROUNDING AND BONDING FOR COMMUNICATION SYSTEMS RELATED SECTIONS: Section 27 00 00 General Requirements Section 27 02 00 Communication General Requirements Section 27 05 28 Pathways for Communications

More information

SECTION 22 LIGHTNING PROTECTION SYSTEM

SECTION 22 LIGHTNING PROTECTION SYSTEM SECTION 22 LIGHTNING PROTECTION SYSTEM 22.01 SCOPE: A. These Specifications shall form a part of the Contract Documents and shall govern construction work for all buildings to be built or modified for

More information

DIVISION 26 - ELECTRICAL SECTION 26 05 20 CABLES FOR INSTRUMENTATION

DIVISION 26 - ELECTRICAL SECTION 26 05 20 CABLES FOR INSTRUMENTATION DIVISION 26 - ELECTRICAL PART 1 - GENERAL 1.01 SUMMARY A. Section Includes 1. Instrumentation Cables 1.02 SUBMITTALS A. Submit in accordance with requirements of Section 01 33 00. B. Product Data: Submit

More information

270526-TC Grounding and Bonding for Telecommunications Systems

270526-TC Grounding and Bonding for Telecommunications Systems 270526-TC Grounding and Bonding for Telecommunications Systems Part 1 - General Related Documents The following related sections of the OT standards shall also be applicable to this section. OT Engineer

More information

TS 813 GROUNDING AND BONDING TTD 813.001 TRAFFIC SIGNAL INSTALLATION AND CONTROLLER CABINET GROUNDING SYSTEM TTD 813.005 CONTROLLER CABINET GROUNDING

TS 813 GROUNDING AND BONDING TTD 813.001 TRAFFIC SIGNAL INSTALLATION AND CONTROLLER CABINET GROUNDING SYSTEM TTD 813.005 CONTROLLER CABINET GROUNDING TORONTO TRANSPORTATION January 2012 TS 813 GROUNDING AND BONDING TABLE OF CONTENTS 1. DRAWINGS TTD 813.001 TRAFFIC SIGNAL INSTALLATION AND CONTROLLER CABINET GROUNDING SYSTEM TTD 813.005 CONTROLLER CABINET

More information

Security Cameras, CATV, GPS & Satellite Protection. White Paper

Security Cameras, CATV, GPS & Satellite Protection. White Paper Security Cameras, CATV, GPS & Satellite Protection White Paper Security Cameras, CATV, GPS & Satellite Protection Surge Protection Solutions for PTC 1 Security Cameras, CATV, GPS & Satellite Protection

More information

Canopy Surge. User Manual

Canopy Surge. User Manual Canopy Surge Suppressor User Manual SS00-UM-en Issue 2 May 2003 2003 Motorola, Inc. All rights reserved. Printed in the U.S.A Notices Safety Precautions: Before beginning your installation, please read

More information

STREETLIGHT SYSTEM GROUNDING AND BONDING

STREETLIGHT SYSTEM GROUNDING AND BONDING Page: 1 of 8 STREETLIGHT SYSTEM GROUNDING AND BONDING 1. Scope This Construction Standard covers the grounding and bonding requirements for single phase streetlight systems served by the Looped Radial

More information

IRRIGATION PUMPING Table of Contents - Section 900

IRRIGATION PUMPING Table of Contents - Section 900 IRRIGATION PUMPING Table of Contents - Section 900 PARAGRAPH 900.1 GENERAL 1 900.2 METERING REQUIREMENTS 1 900.3 CUSTOMER S CONTROL EQUIPMENT 2 900.4 SERVICE CONDUCTOR REQUIREMENTS 2 900.5 RECOMMENDATIONS

More information

1. Franklin Rod Performance 2. LEC/DAS Performance

1. Franklin Rod Performance 2. LEC/DAS Performance THREE ESSENTIALS OF LIGHTNING PROTECTION: BONDING, GROUNDING AND SURGE PROTECTION by Richard Kithil, President and Orlando Alzamora, Vice-President National Lightning Safety Institute (NLSI) 1.0 Summary.

More information

0095.05 June 30. 2011 July 18, 2014 1 of 7

0095.05 June 30. 2011 July 18, 2014 1 of 7 Standard Number: Superseding: Effective Date: Page: 0095.05 June 30. 2011 July 18, 2014 1 of 7 Pole Attachments, Automated Meter Reading and Cellular Phone Antennas 1. Scope 2. Application This standard

More information

The National Armored Cable Manufacturers Association Presents. Installation Standard for Types AC and MC Cables

The National Armored Cable Manufacturers Association Presents. Installation Standard for Types AC and MC Cables The National Armored Cable Manufacturers Association Presents Installation Standard for Types AC and MC Cables An ANSI Standard Original document jointly produced by NECA and NACMA as Standard for Installing

More information

Electrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, 2016. Underground branch circuit feeding a detached garage:

Electrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, 2016. Underground branch circuit feeding a detached garage: Electrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, 2016 * Garage construction requires permits (electrical, building) * Permits must be applied for at the time. * Dial

More information

Grounding & Bonding Why it is done And How to Install Properly

Grounding & Bonding Why it is done And How to Install Properly Grounding & Bonding Why it is done And How to Install Properly The technical information provided herein is to assist qualifi ed persons in planning and installing electric service to farms and residences.

More information

GROWTH MANAGEMENT DEPARTMENT 201 SE 3 rd ST, (Second Floor), Ocala, FL 34471 (352) 629-8421; FAX: (352) 629-8264

GROWTH MANAGEMENT DEPARTMENT 201 SE 3 rd ST, (Second Floor), Ocala, FL 34471 (352) 629-8421; FAX: (352) 629-8264 BUILDING CODE GUIDELINES FOR ELECTRICAL INSPECTIONS Building Code compliance is the obligation of design professionals and/or contractors. Plan Review and Inspection Guidelines are intended to be used

More information

GUIDELINES FOR UTILITY INSTALLATIONS Part 1 - Wire Lines and Communications Cables

GUIDELINES FOR UTILITY INSTALLATIONS Part 1 - Wire Lines and Communications Cables Engineering Department SEPTEMBER, 2007 GUIDELINES FOR UTILITY INSTALLATIONS Part 1 - Wire Lines and Communications Cables General Requirements This section applies to all public and private utilities,

More information

SECTION 611 ACCEPTANCE PROCEDURES FOR TRAFFIC CONTROL SIGNALS AND DEVICES

SECTION 611 ACCEPTANCE PROCEDURES FOR TRAFFIC CONTROL SIGNALS AND DEVICES SECTION 611 ACCEPTANCE PROCEDURES FOR TRAFFIC CONTROL SIGNALS AND DEVICES 611-1 Description. This Section sets forth Contract acceptance procedures for installations of traffic control signals and devices

More information

Coaxial Cable Entry Panels, Coax and Grounding Connectors. Technical Note

Coaxial Cable Entry Panels, Coax and Grounding Connectors. Technical Note Coaxial Cable Entry Panels, Coax and Grounding Connectors Technical Note Coaxial Cable Entry Panels, Coax and Grounding Connectors Surge Protection Solutions for PTC 2 Coaxial Cable Entry Panels, Coax

More information

Section 21. Telecommunication Hardware. www.geindustrial.com BuyLog Catalog 21-1

Section 21. Telecommunication Hardware. www.geindustrial.com BuyLog Catalog 21-1 Introduction...21-1 Fiber Closure Hardware...21-2 Cable Location Surge Protectors...21-4 Introduction GE has been manufacturing Telecommunication Hardware products for over 20 years and has become a leader

More information

Fibre Optic Wiring Guide for Multiple Dwelling Units (MDUs)

Fibre Optic Wiring Guide for Multiple Dwelling Units (MDUs) Fibre Optic Wiring Guide for Multiple Dwelling Units (MDUs) Greenfield/Brownfield Renovations Table of Contents Future-Proof your Building... 1 MTS Fibre Optics Installation Guidelines... 2 MTS Fibre Optics

More information

AC and DC Drive System Installation Information

AC and DC Drive System Installation Information Purpose This document contains the Parker SSD Drives recommendations for installing drive systems. These instructions must be followed for safe and reliable operation. Instructions CODES AND REGULATIONS

More information

Aerial Fibre Optics. Complete One Stop Solution for Aerial Fibre Optics. OPGW Cable and Fittings for OPGW

Aerial Fibre Optics. Complete One Stop Solution for Aerial Fibre Optics. OPGW Cable and Fittings for OPGW Complete One Stop Solution for OPGW Cable and Fittings for OPGW 53, Justice Chandra Madhav Road, Kolkata - 700020. India. Phone: 91-33-24748575 / 7565 Fax: 91-33-2476-1955 Email: sales@supremeco.com Website:

More information

Application Bulletin 103 - NEC Reference Guide for SolarBridge-Enabled AC Module Installers

Application Bulletin 103 - NEC Reference Guide for SolarBridge-Enabled AC Module Installers 9229 Waterford Centre Dr. Bldg C, Suite 110 Austin, Tx 78758 Application Bulletin 103 - NEC Reference Guide for SolarBridge-Enabled AC Module Installers Current Version: 13 AC Modules are a new product

More information

ELECTRICAL SERVICE REQUIREMENTS FOR MOBILE HOME DEVELOPMENTS

ELECTRICAL SERVICE REQUIREMENTS FOR MOBILE HOME DEVELOPMENTS Prepared by: ABB1 ELECTRICAL SERVICE REQUIREMENTS FOR MOBILE HOME DEVELOPMENTS 052521 Asset Type: Electric Metering Function: Construction Issued by: Quoc Hoang (QxH1) Date: 07-01-16 Rev. #06: This document

More information

CONTENTS. Yale University Design Standards. Underground Electrical Duct Bank. A. Summary. B. System Design and Performance Requirements

CONTENTS. Yale University Design Standards. Underground Electrical Duct Bank. A. Summary. B. System Design and Performance Requirements 16600 Underground Electrical Duct Bank This document provides design standards only, and is not intended for use, in whole or in part, as a specification. Do not copy this information verbatim in specifications

More information

EH-20 20m antenna. By VE3RGW

EH-20 20m antenna. By VE3RGW EH-20 20m antenna By VE3RGW Equivalent circuit of EH-20 (prototype 2A) antenna system. Upper cylinder Lower cylinder Ground Counter pose Phasing coil Impedance transformer and tune circuit Tune coil Feed

More information

Electric Engineering Division FIBER CONDUIT RULES AND REGULATIONS

Electric Engineering Division FIBER CONDUIT RULES AND REGULATIONS Electric Engineering Division FIBER CONDUIT RULES AND REGULATIONS TABLE OF CONTENTS I. RULES AND REGULATIONS A. TABLE OF CONTENTS... 2 B. TERMS AND DEFINITIONS... 3 C. DEVELOPER S/CONTRACTOR S RESPONSIBILITIES...

More information

SERVICE - GENERAL Residential, Commercial, Industrial

SERVICE - GENERAL Residential, Commercial, Industrial PAGE 1 OF 9 USE: Rules and procedures for overhead or underground services. PREVIOUS REVISION 10-01-01 ORIGINATED 03-94 PREVIOUS NUMBER ER 1-290-B, 07-15-93 LATEST REVISION: Remove details of Facility

More information

Comm5 Wiring Installation

Comm5 Wiring Installation Comm5 Wiring Installation This wiring information applies to the following Trane products: Tracer Summit systems (Comm5 communications, Version 12.0 and higher) Tracker systems (BMTK models) Tracer loop

More information

Hyperlinks are Inactive

Hyperlinks are Inactive Prepared by: NIB/EOB PLANNING GUIDE FOR SINGLE CUSTOMER SUBSTATIONS SERVED FROM TRANSMISSION LINES 05503 Department: Electric T&D Section: T&D Engineering and Technical Support Approved by: G.O. Duru (GOD)

More information

CP2 Buried Cable Pedestal Initial & Rehab Installation Instructions

CP2 Buried Cable Pedestal Initial & Rehab Installation Instructions Printing 3 March 2008 CP2 Buried Cable Pedestal Initial & Rehab Installation Instructions This instruction is intended for CP2 cable pedestal installations and replacements. The following tools will be

More information

Lightning Arresters P30027 18 KVA P30038 10 KVA. Description & Installation

Lightning Arresters P30027 18 KVA P30038 10 KVA. Description & Installation Lightning Arresters P30027 18 KVA P30038 10 KVA Description & Installation Printed in USA 09/11 TO330 Rev. B Table of Contents Page 1.0 SCOPE 2 2.0 PRODUCT OVERVIEW 2 2.1 Intended Uses 2 2.2 Lightning

More information

SECTION 18370 SIGNAL WIRE AND CABLE

SECTION 18370 SIGNAL WIRE AND CABLE SECTION 18370 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes requirements for all cable and wire required for signal and signal power system wiring to wayside shelters, junction boxes, and factory

More information

SOLAR PV STANDARD ELECTRICAL PLAN Microinverter Systems for Single Family Dwellings

SOLAR PV STANDARD ELECTRICAL PLAN Microinverter Systems for Single Family Dwellings *** Provide this document to the inspector along with ALL system installation instructions *** Project Address: Scope: Standard plan for the installation of grounded microinverter solar PV systems, not

More information

PXL-250: Network Wiring

PXL-250: Network Wiring This document provides the network wiring requirements for a PXL-250 access control network. Network Requirements The PXL-250 uses a half-duplex, RS-485 communication bus. Per the RS-485 specification,

More information

Grounding Practice at Data and Communications Centers. David Brender, P.E., CPQ National Program Manager Copper Development Association Inc.

Grounding Practice at Data and Communications Centers. David Brender, P.E., CPQ National Program Manager Copper Development Association Inc. Grounding Practice at Data and Communications Centers David Brender, P.E., CPQ National Program Manager Copper Development Association Inc. Overview of This Presentation Elements of building wiring and

More information

EARTHING AND BONDING AT SECONDARY SUBSTATIONS

EARTHING AND BONDING AT SECONDARY SUBSTATIONS DISTRIBUTION CONSTRUCTION MANUAL SECTION 4 - SUBSTATIONS ISSUE B SEPT 1996 4.4.4 EARTHING AND BONDING AT SECONDARY SUBSTATIONS 1 SCOPE This section of the Distribution Construction Manual lays down the

More information

DIVISION 27 COMMUNICATIONS. A. System design shall be completed by a Registered Communications Distribution Designer (RCDD).

DIVISION 27 COMMUNICATIONS. A. System design shall be completed by a Registered Communications Distribution Designer (RCDD). DIVISION 27 COMMUNICATIONS 27 00 00 COMMUNICATIONS A. System design shall be completed by a Registered Communications Distribution Designer (RCDD). B. Comply with American National Standards Institute

More information

DEPARTMENT OF LICENSING AND REGULATORY AFFAIRS DIRECTOR S OFFICE CONSTRUCTION SAFETY STANDARDS

DEPARTMENT OF LICENSING AND REGULATORY AFFAIRS DIRECTOR S OFFICE CONSTRUCTION SAFETY STANDARDS MIOSHA-STD-1313 (10/15) 6 Pages For further information Ph: 517-284-7740 www.michigan.gov/mioshastandards DEPARTMENT OF LICENSING AND REGULATORY AFFAIRS DIRECTOR S OFFICE CONSTRUCTION SAFETY STANDARDS

More information

Wireless LAN Outdoor Bridge Solution

Wireless LAN Outdoor Bridge Solution 309-2273-001AA.fm Page 1 Monday, February 3, 2003 4:54 PM Quick Start Guide Wireless LAN Outdoor Bridge Solution 3CRWEASY96A Outdoor solution for secure long-distance wireless connections The 3Com Wireless

More information

Business Customer Demarcation Information

Business Customer Demarcation Information Building Industry Consulting Service (BICS) Business Customer Demarcation Information The intent of this document is to clearly define Communications terminology and deployment with reference to business

More information

Building Telecommunications Infrastructure Requirements

Building Telecommunications Infrastructure Requirements Building Telecommunications Infrastructure Requirements This page identifies specific requirements for the design of telecommunications infrastructure for buildings at Clemson University. (Revised October,

More information

Requirements for the Attachment of Communication Cable Facilities on PPL Poles

Requirements for the Attachment of Communication Cable Facilities on PPL Poles Page 99 of 137 Requirements for the Attachment of Communication Cable Facilities on Replaces: URS-3002 URS-3004 URS-101C-304 A-157649 Page 100 of 137 Reference Notes for Drawings: General 1. The term communication

More information

Underground Service Requirements and Instructions

Underground Service Requirements and Instructions This packet includes all FKEC underground service requirements, instructions, procedures and drawings. If you are considering underground power service please review this document in its entirety (3 page

More information

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION 17650 SECURITY SYSTEMS

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION 17650 SECURITY SYSTEMS PART 0 DESIGN STANDARDS 0.01 GENERAL DESIGN GUIDELINES A. Inspections and observations by the Owner do not relieve the A/E of contract responsibilities. B. Chain of command 1. The DPS Project Manager is

More information

METER REQUIREMENTS GENERAL REQUIREMENTS SECTION D

METER REQUIREMENTS GENERAL REQUIREMENTS SECTION D 12 - ELECTRIC SERVICE HANDBOOK SECTION D METER REQUIREMENTS This chapter gives you information on Central Lincoln s metering requirements. It's divided into three sections: General requirements This section

More information

Specifications for Lightning Protection. ASAE Engineering Practice

Specifications for Lightning Protection. ASAE Engineering Practice Chapter 8: Lightning Specifications for Lightning Protection ASAE safety standards are not laws. They are recommended voluntary standards used by designers, engineers, manufacturers and users of the equipment,

More information

GUIDELINES HAS/PDC/DESIGN DIVISION TITLE

GUIDELINES HAS/PDC/DESIGN DIVISION TITLE SECTION 270526 TELECOMMUNICATIONS GROUNDING & BONDING (-TAB) PART 1 GENERAL 1.01 SCOPE SUMMARY Designer shall provide a detailed narrative of the tasks to be performed under this specification section.

More information

SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT

SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT The purpose of these specifications is to insure that there are minimum

More information

Underground Commercial Electric Service

Underground Commercial Electric Service Underground Commercial Electric Service SCANA Corporation 2013 Revised: June 2013 Table of Contents SECTION PAGE I. Specification and Requirements 2 A. General B. Definition of Terms C. Company and Developer

More information

Top Commercial / Residential Electrical Requirements *

Top Commercial / Residential Electrical Requirements * Department of Community Development Building Division 4800 West 92 nd Avenue Westminster, Colorado 80031 For Information call (303) 658-2075 Fax (303) 706-3922 www.westminsterpermits.com Top Commercial

More information

Addendum #2 Contract UK-11-13

Addendum #2 Contract UK-11-13 Addendum #2 Contract UK-11-13 Utilities Kingston Purchase and Replacement of Switchgear at Kingston Hydro Substation MS11 March 25, 2011 Delivered to: All RFP recipients Total number of pages: Nine (9)

More information

Recommendations for Marking Communication Facilities with Use of 3M EMS Electronic Markers

Recommendations for Marking Communication Facilities with Use of 3M EMS Electronic Markers Recommendations for Marking Communication Facilities with Use of 3M EMS Electronic Markers Near-Surface Marker A small marker which is well-suited for bore holes in concrete or asphalt for marking flush-mount

More information

The Contractor shall furnish and install all shielded power cable suitable for use on this project.

The Contractor shall furnish and install all shielded power cable suitable for use on this project. Section 16122 PRIMARY POWER CABLES PART 1 GENERAL: WORK INCLUDED The Contractor shall furnish and install all shielded power cable suitable for use on this project. RELATED WORK Section 16020: Tests SUBMITTALS

More information

Specifying an IT Cabling System

Specifying an IT Cabling System Specifying an IT Cabling System This guide will help you produce a specification for an IT cabling system that meets your organisation s needs and gives you value for money. You will be able to give your

More information

Current Probes. User Manual

Current Probes. User Manual Current Probes User Manual ETS-Lindgren L.P. reserves the right to make changes to any product described herein in order to improve function, design, or for any other reason. Nothing contained herein shall

More information

TELUS Residential Service Conduit Requirements for Stand Alone Homes and Duplexes in Fibre Only Communities

TELUS Residential Service Conduit Requirements for Stand Alone Homes and Duplexes in Fibre Only Communities 1 TELUS Residential Service Conduit Requirements for Stand Alone Homes and Duplexes in Fibre Only Communities Beginning in January 2010 TELUS began designing new subdivisions within the Top 48 population

More information

David Brender Copper Development Association Inc. david.brender@copperalliance.us. Miramar, March 8, 2013

David Brender Copper Development Association Inc. david.brender@copperalliance.us. Miramar, March 8, 2013 Grounding and Bonding in Communications Systems David Brender Copper Development Association Inc. david.brender@copperalliance.us Ennes Workshop Miramar, March 8, 2013 MMXIII This talk concentrates on:

More information

Grounding and Shield Termination. Application Note 51204

Grounding and Shield Termination. Application Note 51204 Grounding and Shield Termination Application Note 51204 DEFINITIONS This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages that follow this

More information

Table of Contents. Inductive Loop Vehicle Detector Applications

Table of Contents. Inductive Loop Vehicle Detector Applications Table of Contents Introduction Design Essentials Loop Installation Techniques Determining Loop Phasing Equipment Installation 1 020907 Inductive Loop Vehicle Detector Applications Parking Revenue Control

More information

FIREFINDER XLS ADDRESSABLE FIRE ALARM SYSTEM SECTION 13851

FIREFINDER XLS ADDRESSABLE FIRE ALARM SYSTEM SECTION 13851 FIREFINDER XLS ADDRESSABLE FIRE ALARM SYSTEM SECTION 13851 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and

More information

2014 NEC Guide Lines for Home Owner Doing Electrical Work on their Property

2014 NEC Guide Lines for Home Owner Doing Electrical Work on their Property 2014 NEC Guide Lines for Home Owner Doing Electrical Work on their Property A brief summary of the most used code references for residential wiring State of Idaho Division of Building Safety Electrical

More information

DYNAMIC MESSAGE SIGN WALK-IN

DYNAMIC MESSAGE SIGN WALK-IN See Sheet 6 of 10 1. If no guardrail or barrier wall exists, structure shall be outside the clear zone. lear zone shall be measured to edge of the drilled shaft if drilled shaft is more than 4" above adjacent

More information

Unarmored Variable Frequency Drive (VFD) Cable Termination Guide

Unarmored Variable Frequency Drive (VFD) Cable Termination Guide Authorized Distributor Unarmored Variable Frequency Drive (VFD) Cable Termination Guide Be Certain with Belden A Step-by-Step Look at the Connection/Termination of Unarmored VFD Cables Terminating Unarmored

More information

Lake County EOC. Vendor Quotes for Lightning Protection

Lake County EOC. Vendor Quotes for Lightning Protection Lake County EOC Vendor Quotes for Lightning Protection January 18, 2012 Electric Services Attn: Debbie Sutton Project: Subject: Lake County Emergency Communications & Operations Center Tavares, FL Lightning

More information

Installation Instructions Hustler 6-BTV Trap Vertical

Installation Instructions Hustler 6-BTV Trap Vertical Installation Instructions Hustler 6-BTV Trap Vertical ASSEMBLY 1. Check the package contents against the parts list on page 2. 2. WARNING. Installation of this product near power lines is dangerous. For

More information

Grounding of Electrical Systems NEW CODE: Grounding and Bonding

Grounding of Electrical Systems NEW CODE: Grounding and Bonding Grounding of Electrical Systems NEW CODE: Grounding and Bonding Presented By Scott Peele PE Grounding of Electrical Systems Outline Defining the Terms Why should I Ground? Types of Grounding Systems Separately

More information

DESIGN GUIDELINES. Local Area Network

DESIGN GUIDELINES. Local Area Network DESIGN GUIDELINES Local Area Network The total oversight and management responsibilities for information assurance (IA) and protection of DoDEA s critical infrastructure fall under the purview of the DoDEA

More information

COMMERCIAL CONDUIT RULES AND REGULATION

COMMERCIAL CONDUIT RULES AND REGULATION Electric Engineering Division COMMERCIAL CONDUIT RULES AND REGULATION S:\COO_ACM_US_Electric_Telecommunications\COO_ET_Engineering\Conduit Policies\Residential 1805 NE 30th Ave., Bldg. 400 Ocala, FL 34470-4875

More information

Short Range Wireless Switch System Handheld 8 Installation and Operations Guide

Short Range Wireless Switch System Handheld 8 Installation and Operations Guide Phone: (866) 701-1146 Fax: (425) 216-7558 www.remotecontroltech.com Short Range Wireless Switch System Handheld 8 Installation and Operations Guide Introduction... 2 Before Installation... 2 Receiver Installation...

More information

Minimum Standards for Data/Voice Infrastructure in New Building Construction

Minimum Standards for Data/Voice Infrastructure in New Building Construction UNIVERSITY OF WATERLOO Minimum Standards for Data/Voice Infrastructure in New Building Construction 12/17/2012 Offices 1. Two Work Area Outlets (WAO) on opposite walls, each with 2 jacks 2. Each WAO shall

More information

Electrical Grounding. Appendix C

Electrical Grounding. Appendix C Appendix C Electrical Grounding Low-Voltage Equipment Grounding The most frequently cited Office of Safety and Health Administration (OSHA) electrical violation is improper occupational grounding of equipment

More information

SECTION 28 05 00 COMMON WORK RESULTS FOR ELECTRONIC SAFETY AND SECURITY

SECTION 28 05 00 COMMON WORK RESULTS FOR ELECTRONIC SAFETY AND SECURITY SECTION 28 05 00 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specifications Sections, apply

More information

ELECTRICAL GUIDELINES FOR SINGLE-FAMILY HOME OWNERS:

ELECTRICAL GUIDELINES FOR SINGLE-FAMILY HOME OWNERS: ELECTRICAL GUIDELINES FOR SINGLE-FAMILY HOME OWNERS: Chapter 12 of the Burlington Code of ordinances allows owner occupants of single family homes to do their own wiring if they choose. If you choose to

More information

BERTHOLD ELECTRIC GENERATOR CONNECTION CABINET

BERTHOLD ELECTRIC GENERATOR CONNECTION CABINET BERTHOLD ELECTRIC GENERATOR CONNECTION CABINET Berthold Electric Company s Generator Connection Cabinet provides a quick and convenient station to connect a portable generator to a facility s main service

More information

Trial Exams C. Standards and Regulations. Examination No: GH-08-C- 1 hour and 5 minutes plus 10 minutes reading time

Trial Exams C. Standards and Regulations. Examination No: GH-08-C- 1 hour and 5 minutes plus 10 minutes reading time Trial Exams C Standards and Regulations Examination No: GH-08-C- This test is intended to gauge your knowledge of essential information contained within AS/CA S009:2013. To qualify for an allpication to

More information

Standards Affecting a Premise T-1 Installation

Standards Affecting a Premise T-1 Installation Standards Affecting a Premise T-1 Installation The T-carrier system originated many years ago as a technology developed by AT&T. The intended use of the scheme was to increase the voice channel capacity

More information

Application Note: Modbus/RS485 Wiring for Conext Core XC Series Inverters

Application Note: Modbus/RS485 Wiring for Conext Core XC Series Inverters Application Note: Modbus/RS485 Wiring for Conext Core XC Series Inverters AP-XC-025 Revision B DANGER RISK OF ELECTRIC SHOCK, EXPLOSION, ARC FLASH, AND FIRE This Application Note is in addition to, and

More information

SECTION 16715 TELECOMMUNICATIONS ACCEPTANCE TESTING

SECTION 16715 TELECOMMUNICATIONS ACCEPTANCE TESTING PART 1 - GENERAL 1.1 SECTION INCLUDES A. Testing Publications and Standards B. Inspection and testing procedures for copper and fiber optic cable, RF CATV / MATV systems, and the antenna systems. C. Documentation

More information

Section 27 05 26 Grounding and Bonding for Communications

Section 27 05 26 Grounding and Bonding for Communications Part 1 General 1.1 General 1.1.1 Summary A. This section governs the products and execution requirements relating to furnishing and installing grounding and bonding for the communication systems. B. Description

More information

INDUSTRY WIDE LABOR-MANAGEMENT SAFETY COMMITTEE SAFETY BULLETIN #23

INDUSTRY WIDE LABOR-MANAGEMENT SAFETY COMMITTEE SAFETY BULLETIN #23 INDUSTRY WIDE LABOR-MANAGEMENT SAFETY COMMITTEE SAFETY BULLETIN #23 GUIDELINES FOR WORKING WITH PORTABLE POWER DISTRIBUTION SYSTEMS AND OTHER ELECTRICAL EQUIPMENT "ADDENDUM C" WORKING WITH 480 VOLT SYSTEMS

More information

ELECTRIC METERING COMMERCIAL & INDUSTRIAL

ELECTRIC METERING COMMERCIAL & INDUSTRIAL ELECTRIC METERING COMMERCIAL & 1.0 INDEX 1.0 INDEX 2.0 SCOPE 3.0 GENERAL REQUIREMENTS 4.0 METER LOCATIONS 5.0 UNDERGROUND TERMINATIONS 6.0 METERING TRANSFORMER ENCLOSURES 7.0 SINGLE CUSTOMER METER INSTALLATIONS

More information

FTW 175 VERIZON Wireless Monitoring System Reference Manual Part Number 7911751VERIZON

FTW 175 VERIZON Wireless Monitoring System Reference Manual Part Number 7911751VERIZON FTW 175 VERIZON Wireless Monitoring System Reference Manual Part Number 7911751VERIZON SERIAL NUMBER Flash Technology, 332 Nichol Mill Lane, Franklin, TN 37067 (615) 261-2000 Front Matter Abstract This

More information

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-27 05 14.00 10 (April 2006) -------------------------------- Preparing Activity: USACE Superseding UFGS-27 05 14.00 10 (April 2004) UNIFIED FACILITIES GUIDE SPECIFICATIONS

More information

Model Number Electrical Compatibility Module Connector Type. M250-60-2LL-S22 60 cell PV module MC-4 Type 2 Locking

Model Number Electrical Compatibility Module Connector Type. M250-60-2LL-S22 60 cell PV module MC-4 Type 2 Locking TECHNICAL BRIEF M250 Microinverter System Installation Planning The M250 Microinverter The Enphase M250 Microinverter is a powerful and efficient grid-tied microinverter. It is compatible with most 60-cell

More information

2011/2008/2005 NATIONAL ELECTRICAL CODE SOLAR PV CODE COMPLIANCE REFERENCE

2011/2008/2005 NATIONAL ELECTRICAL CODE SOLAR PV CODE COMPLIANCE REFERENCE 2011/2008/2005 NATIONAL ELECTRICAL CODE SOLAR PV CODE COMPLIANCE REFERENCE PAGE 1 OF 5 This Reference provides a very comprehensive list of aspects of a solar PV installation that could be reviewed, clarifying

More information

REQUIREMENTS AND SPECIFICATIONS FOR HIGH VOLTAGE CUSTOMER BUILT FACILITIES PEPCO ENGINEERING

REQUIREMENTS AND SPECIFICATIONS FOR HIGH VOLTAGE CUSTOMER BUILT FACILITIES PEPCO ENGINEERING REQUIREMENTS AND SPECIFICATIONS FOR HIGH VOLTAGE CUSTOMER BUILT FACILITIES PEPCO ENGINEERING Revised October, 2013 TABLE OF CONTENTS 1.0 INTRODUCTION... 3 2.0 REQUIRED DRAWINGS... 3 2.1 Site Plan... 3

More information

Enphase Microinverters and Ungrounded Renewable Energy Systems: Canadian Electrical Code Compliance

Enphase Microinverters and Ungrounded Renewable Energy Systems: Canadian Electrical Code Compliance WHITE PAPER Enphase Microinverters and Ungrounded Renewable Energy Systems: Canadian Electrical Code Compliance Overview Enphase has developed a new microinverter family that includes the M250 and new

More information

PLEASE NOTE. For more information concerning the history of these regulations, please see the Table of Regulations.

PLEASE NOTE. For more information concerning the history of these regulations, please see the Table of Regulations. PLEASE NOTE This document, prepared by the Legislative Counsel Office, is an office consolidation of this regulation, current to August 1, 2013. It is intended for information and reference purposes only.

More information

Stand Alone POTS Fiber Optic System. P31372 Station (Subscriber) Unit P31379 Remote (Exchanger) Unit. Description & Installation

Stand Alone POTS Fiber Optic System. P31372 Station (Subscriber) Unit P31379 Remote (Exchanger) Unit. Description & Installation Stand Alone POTS Fiber Optic System P31372 Station (Subscriber) Unit P31379 Remote (Exchanger) Unit Description & Installation Printed in USA 09/11 TO466 Rev. A Table of Contents Page 1.0 SCOPE 2 2.0 PRODUCT

More information

INSTALLATION INSTRUCTIONS HUSTLER 4-BTV, 5-BTV TRAP VERTICAL WARNING INSTALLATION OF THIS PRODUCT NEAR POWER LINES IS DANGEROUS

INSTALLATION INSTRUCTIONS HUSTLER 4-BTV, 5-BTV TRAP VERTICAL WARNING INSTALLATION OF THIS PRODUCT NEAR POWER LINES IS DANGEROUS INSTALLATION INSTRUCTIONS HUSTLER 4-BTV, 5-BTV TRAP VERTICAL WARNING INSTALLATION OF THIS PRODUCT NEAR POWER LINES IS DANGEROUS FOR YOUR SAFETY, FOLLOW THE INSTALLATION DIRECTIONS GENERAL DESCRIPTION:

More information