Direct Current Motor Electrical Evaluation Using Motor Circuit Analysis
|
|
|
- Madeline Moore
- 9 years ago
- Views:
Transcription
1 Direct Current Motor Electrical Evaluation Using Motor Circuit Analysis Howard W. Penrose, PhD ALL-TEST Pro, LLC Old Saybrook, CT Introduction Electrical testing of Direct Current (DC) electric motors is a challenge within industry, manufacturing and repair centers alike. The key issue has to do with the ability to compare one coil to the next, should exact information not be provided. In this article, the issue of simple tests to increase the confidence of testing and analysis conclusions using Motor Circuit Analysis (MCA) shall be discussed. The term MCA is derived from a test method that provides information on the basic components of an AC or DC electric motor. These basic components include: resistance, measured in Ohms; impedance, measured in Ohms; inductance, measured in Henries; the induction winding phase angle, measured in degrees; and, insulation resistance, measured in Meg-Ohms. The instrument that will be referred to in this article provides these readings by generating a low voltage, true sine-wave, alternating current (impedance, inductance, phase angle), signal at frequencies from 100 to 800 hertz, a low voltage DC signal for resistance, and 500 or 1,000 volts DC for the insulation resistance test. In addition, a special test called I/F is performed in which the applied frequency is doubled and a ratio results from the change in the winding impedance. This test is introduced to identify early winding shorts that may exist in the winding. Using the applied data, the condition of a DC motor winding can be evaluated through coil comparisons, comparisons to known readings, or by trending changes to the windings over a period of time. The DC electric motors that will be included in this article are: series, shunt, and compound DC motors. Some of the basic tests described can be performed on permanent magnet, DC servo, DC machine tools, and others (although brushless DC motors are evaluated in a similar fashion to AC motors). The types of DC electric motors can be described by their windings and connections. DC Motor Theory Direct Current electric motors operate under a basic principle of electricity: interaction between two magnetic fields positioned at an angle from each other will attract/repel resulting in movement. In the case of a DC electric motor, power is provided to a stator field and an armature creating magnetic fields that are, electrically, about 90 degrees from each other. The resulting attraction/repulsion of the armature from the field generates a torque and the armature turns. The basic components of a DC electric motor include: Frame Makes up the outer structure of the machine. It is used to mount most of the other components of the motor Fields Are coils mounted on field pole pieces that generate a stationary magnetic field. Interpoles Are coils that are placed between the field coils that generate a field that is used to prevent excessive sparking of the brushes. Endshields Also called bearing housings, are used to house the brushes, brush rigging, and to house the shaft bearings, holding the armature centered in the frame. Brush rigging Holds and positions the brushes above the armature commutator. Usually, a tension device is used to maintain a constant pressure on the brushes. Brushes Are used to provide DC to the armature. The brushes ride on the commutator. Commutator Consists of many copper bars that are separated by mica. Each bar is connected to coils in the armature. Armature Is the rotating portion of the motor that contains coils.
2 Unlike most AC motors, DC motors require separate power to be provided to both the fields and the armature. The DC provided to the stator fields generate a constant North and South set of fields. DC provided to the armature generates North and South fields that are 90 electrical degrees from the stationary field. As the armature generates a torque and moves towards the appropriate North or South pole, the brushes change position on the commutator, energizing another set of coils 90 electrical degrees from the stationary field. This actually makes the armature an Alternating Current component as the current will travel in one direction, based upon brush position, then in another direction as the motor operates. The brushes are set in such a position that they are electrically neutral (no induced current from the stator fields) in order to reduce sparking. In most DC motor connections, by varying the armature voltage, the operating speed may be changed. One general danger that is inherent in DC motors is that if field current is lost while armature current is maintained, the motor may take off and the speed increase until the armature self-destructs. The three basic winding types that can be used to identify the type of DC motor include: Series: Normally found in applications that need a high starting torque. They consist of a set of field windings of large wire and relatively few turns, marked S1 and S2, that are connected in series to the interpoles and armature, marked A1 and A2 (See Figure 1). Series connected motors are normally used as traction motors and have a very low basic resistance. Figure 1: Series Motor Shunt: Normally found in applications that require constant speed. They consist of a set of field windings of smaller wire with many turns, marked F1 and F2 for single voltage and F1, F2, F3 and F4 for dual voltage, and A1 and A2 for the interpoles and armature (See Figures 2). Shunt connected motors are normally used as crane and machine tool motors and have a relatively high basic resistance. Figure 2: Shunt Wound Motor Compound: Combine the benefits of both the series and shunt wound motors. They provide a relatively high torque with a basic resistance to a change in operating speed. The connections combine both the series and shunt connections (See Figure 3). Compound motors are the most common and are commonly found in industrial manufacturing.
3 Figure 3: Compound Wound Motor As it can be seen, there are few coils to compare to each other in an assembled DC machine. However, procedures can be developed for winding testing that provide a high level of test result confidence. Common DC Motor Electrical Faults There are a number of common DC motor electrical faults of which the most common will be described here. These result from issues specific to DC motor design as a result of temperature, friction and internal contaminants such as carbon or graphite. One of the most common causes of winding faults in a DC motor is from winding contamination from carbon or graphite (carbon) dust from the brushes. The fine powder permeates all of the stationary and rotating windings and will create a path between conductors or between conductors to ground. Carbon is often trapped and problems aggravated further through cleaning and maintenance practices when the carbon is blown with compressed air or the armature is cleaned and baked. In either case, the carbon may become tightly packed in corners, usually just behind the commutator. This will end as a ground fault or shorted turns right at the commutator connection. Another common fault, that is often not considered, is cooling of the DC machine. This may occur because cooling passages are blocked, the armature is turned too slow with no additional cooling, or from dirty filters (the most common cooling-related fault). Temperature is the greatest enemy of electrical equipment, particularly the insulation system, of which the life will be reduced by half for every 10 degrees centigrade increase in temperature (accepted rule of thumb). As the insulation weakens, its reliability decreases until winding faults between turns occur. In addition to the insulation system degrading, brushes also degrade faster, causing increased wear on the commutator and additional carbon contamination of the windings. Another fault that is related to heat is generated from practices that have the fields energized with the armature at rest (de-energized). This is a common mode of operation that requires a separate blower to provide cooling to the motor that normally has filters that must be kept clean. This type of fault normally results in shorted shunt coils, reducing the motor s ability to produce torque and may end with the dangerous condition of armature overspeed if not maintained properly. The commutator also provides opportunities for faults, as well as an indicator of motor operation and condition. A properly operating DC motor will have a fine glaze of carbon on the commutator with the bars looking uniform. Burned commutator bars, streaked glazing, heavy carbon, or overheated commutator conditions indicate potential problems that should be addressed. Armature Testing DC armatures are the most time consuming but easiest component to test. There are three basic methods that will be introduced: trending; assembled; and, disassembled. In the case of trending, all measurements are used, however, in the case of assembled and disassembled testing a bar to bar impedance measurement will be used. Impedance is viewed because the armature is an AC component and simple resistance measurements may miss some faults including shorts and grounds. Trending will be reviewed in an overall trending procedure for DC motors later in this article. When testing an assembled DC motor armature, the best method is to perform what s commonly known as a bar-to-bar test using the motor brushes. In the case of a DC motor that has two brushes, none of the brushes needs to be raised, in the case of a DC motor that has four or more sets of brushes, all but two sets
4 90 degrees from each other need to be raised, which takes them out of the testing circuit. Make sure that good contact is maintained on the commutator by ensuring that 90%+ of the brush is in contact with the commutator bars and that the commutator bars are clean. If they are not clean, polish the armature gently, using an approved method, before testing. If the commutator is badly worn, it will need to be disassembled and the commutator turned and undercut, in which case a disassembled bar to bar test would be appropriate. Once set, mark the position of one bar on the commutator, then bring the bar to a position where it is just under the leading edge of one of the brushes. In the assembled test, you will probably be covering at least one and a half bars with the brush. Perform an impedance test, mark down the reading, and move the armature so that the leading edge of the brush is over the next commutator bar. Take the next impedance reading and continue until each bar has been tested. A good result will show a consistent pattern, while an inconsistent pattern will identify a poor armature. Disassembled bar-to-bar testing is similar to assembled testing, other than the armature is out of the frame and the tester has full access to the commutator. In this case, the tester will use an armature fixture or test leads to connect from bar to bar. The spacing between each impedance reading should be constant and about 90 to 180 degrees from each other. The first bar should be marked and testing continue until one leg of the testing fixture or test lead has made it 360 degrees around the commutator. Mark the impedance for each bar-to-bar test then look to ensure that there was a consistent pattern. Series Motor Testing Series electric motors are very challenging to troubleshoot as they do not provide sets of fields to compare to. Readings may be taken from S1 to S2 and A1 to A2 then trended over time or compared to other similar machines. When trending the readings over time, simple resistance readings must be corrected for temperature, usually relative to 25 o C. Impedance and Inductance normally has limited change due to temperature while the phase angle and I/F readings will remain constant, regardless of temperature. Variations in the I/F and phase angle will indicate shorted turns, while changes in Impedance and Inductance will normally indicate dirty windings. Comparing like motors will require additional information. The operator will have to ensure that the motor is of the same manufacturer and design, as well as speed, power, etc. The model motor must be new or rebuilt to original manufacturer s specifications. When performing comparative readings, the testing temperature should be similar from motor to motor, however, the I/F and phase angle readings can be directly compared. These readings should not change more than +/- 2 points for I/F and +/-1 degree for phase angle. A common error when series field windings are rebuilt, although less common that shunt coils, is an incorrect replacement of wire size, which will impact the ability of the motor to generate torque. Shunt Motor Testing Dual voltage shunt motors provide the ability to compare two sets of windings while single voltage motors will have the same test procedure as testing series motor windings, using F1 to F2 as opposed to S1 to S2. With dual voltage, the shunt windings are labeled F1 to F2 and F3 to F4 allowing the analyst to test and compare these two sets of windings. When testing and troubleshooting the readings over time, simple resistance readings must be corrected for temperature, usually relative to 25 o C. Impedance and Inductance will change more than a series wound motor because of the higher simple resistance of the circuit. The phase angle and I/F will remain constant, within 1 to 2 points, regardless of temperature. Variations in the I/F and phase angle will indicate shorted turns, while changes in Impedance and Inductance will normally indicate dirty windings. Comparisons between F1 to F2 and F3 to F4 should be less than 3% in resistance, inductance and impedance and no more than 1 point different in I/F or phase angle.
5 Like motors can be tested and compared the same as series wound motors. When possible, the motors should be tested, when trending readings, at the same temperature as the previous tests. For instance, within minutes of shutting down operating equipment or before starting equipment, this allows for the tests to be performed at like temperatures. Compound Motor Testing In place testing, trending and troubleshooting is much simpler with a compound motor. Single voltage compound motors are normally labeled A1 to A2, S1 to S2 and F1 to F2, dual voltage compound motors are normally labeled A1 to A2, S1 to S2, F1 to F2 and F3 to F4. A key additional point to a compound wound motor is that the series winding is normally wound on top of the shunt winding, allowing for possible faults between these two windings. Trending a compound motor, the tests are normally taken from the DC drive terminals. Standard MCA tests using the ALL-TEST involve low voltage, higher frequency signals that will not harm the output electronics of the equipment, reducing the need to disconnect the leads from the drive while testing. However, if the analyst wishes to check insulation resistance between the series and shunt windings, the leads must be disconnected from the drive. When trending from the DC drive, test A1 to S2 and the two field leads then perform a 500 Volt insulation resistance test between the S2 and F1 leads and compare to previous tests or similar motors, in either case, insulation resistance readings should remain above 100 Meg-Ohms. The ALL-TEST unit allows the analyzer to immediately compare the past to present readings as a quick check allowing the analyzer to make a quick decision to test the windings further. As mentioned in series and shunt motor testing techniques, the I/F and phase angle readings should not change more than 1 point between tests, over time, the series and field windings will vary dramatically from each other, however. Troubleshooting compound motors should be performed at the motor, itself. Disconnect all motor leads and separate them. Test the series and field windings as outlined in the series and shunt winding instructions, then perform an insulation resistance test between the series and shunt windings, the insulation resistance should be greater than 100 Meg-Ohms. General DC MCA Testing Notes Several key points can be made using MCA testing on any type of DC motor: 1. Any I/F reading outside the range of 15 to 50, for instance, -56, indicates a winding fault. 2. If the test shows an infinite resistance between leads of the same circuit indicates an open winding. 3. An increase in simple resistance between tests, when corrected for temperature, indicates a loose connection, in particular when impedance and inductance readings change. A reduced simple resistance, when corrected for temperature, may indicate a short, usually accompanied by changes in impedance, inductance, phase angle and I/F. 4. When testing like motors, the I/F and phase angle should not change more than 2 points, any difference greater than this should prompt a full analysis. 5. Changes when testing through the armature circuit should prompt a bar to bar test. By following these simple instructions, using an MCA device, will allow you to capture early faults long before the equipment fails during operation. If performing tests as part of a predictive maintenance program, the interval should be at least those shown in Table 1. Table 1: DC Motor Test Frequency Test Type Non-Critical General Critical General Maintenance 1 year 6-9 months 3-6 months Predictive Maintenance 6 months 3 months 1 month Armature Test 1 year 6 months 3 months
6 General maintenance tests are those that are not trended over time. Usually accompanied with vibration, bearing greasing, commutator inspection and brush inspection. Predictive maintenance testing normally involves trending readings over time looking to detect potential faults then to determine the best time to remove the motor for corrective maintenance. Once a potential fault is detected, the testing frequency should increase until it is determined that the motor needs to be removed. A complete armature test should be performed either in conjunction with a general or predictive maintenance test due to the high stresses at the commutator and carbon contamination. Conclusion General electrical testing of direct current electric motors is made much easier with new techniques available with static motor circuit analysis. For the first time, early turn faults can be detected in series, shunt and armature windings before they take equipment out of operation. Predictive maintenance tests can be performed from the drive with troubleshooting tests being performed at the motor. In general, the tests are relatively quick, requiring less than five minutes per motor for predictive maintenance testing, with additional time required for troubleshooting. Overall, MCA testing dramatically improves DC motor testing over the traditional methods of continuity tests. About the Author Dr. Howard W. Penrose, Ph.D. has over 15 years in the electric motor and electric motor repair industry. Starting as an electric motor repair journeyman in the US Navy to field service and evaluation of small through large rotating equipment of all types, as the Chief Engineer of a large Midwestern motor repair shop. Dr. Penrose has been directly involved in rewinding, training and troubleshooting AC, DC, wound rotor, synchronous, machine tool, and specialty equipment. His further studies involve electric motor and industrial reliability, test methods, energy efficiency and maintenance impact on production. Dr. Penrose is a past Chair of the Chicago Section of IEEE, a past Chair of Dielectrics and Electrical Insulation Society of IEEE Chicago, a Professional Member of the Electrical Manufacturing Coil and Winding Association, a US Department of Energy Certified MotorMaster Professional, a Vibration Analyst, Infrared Analyst and Motor Circuit Analyst.
Single and Three Phase Transformer Testing Using Static Motor Circuit Analysis Techniques
Single and Three Phase Transformer Testing Using Static Motor Circuit Analysis Techniques Howard W. Penrose, Ph.D On behalf of ALL-TEST Pro, LLC Old Saybrook, CT Introduction Field and shop testing of
SYNCHRONOUS MACHINE TESTING WITH MOTOR CIRCUIT ANALYSIS INSTRUMENTATION
SYNCHRONOUS MACHINE TESTING WITH MOTOR CIRCUIT ANALYSIS INSTRUMENTATION Introduction Howard W. Penrose, Ph.D., CMRP Vice President, Engineering and Reliability Services Dreisilker Electric Motors, Inc.
DC MOTOR ANALYSIS & TROUBLESHOOTING
DC MOTOR ANALYSIS & TROUBLESHOOTING By Don Shaw Condition assessment of DC motors requires a basic understanding of the design and operating characteristics of the various types available: the series motor,
APPLICATIONS FOR MOTOR CURRENT SIGNATURE ANALYSIS
APPLICATIONS FOR MOTOR CURRENT SIGNATURE ANALYSIS An ALL-TEST Pro White Paper By Howard W Penrose, Ph.D. General Manager ALL-TEST Pro A Division of BJM Corp 123 Spencer Plain Rd Old Saybrook, CT 06475
2. A conductor of length 2m moves at 4m/s at 30 to a uniform magnetic field of 0.1T. Which one of the following gives the e.m.f. generated?
Extra Questions - 2 1. A straight length of wire moves through a uniform magnetic field. The e.m.f. produced across the ends of the wire will be maximum if it moves: a) along the lines of magnetic flux
Motor Fundamentals. DC Motor
Motor Fundamentals Before we can examine the function of a drive, we must understand the basic operation of the motor. It is used to convert the electrical energy, supplied by the controller, to mechanical
SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS
SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS UNIT OBJECTIVES After studying this unit, the reader should be able to Describe the different types of open single-phase motors used to drive
The DC Motor/Generator Commutation Mystery. Commutation and Brushes. DC Machine Basics
The DC Motor/Generator Commutation Mystery One small, yet vital piece of the DC electric motor puzzle is the carbon brush. Using the correct carbon brush is a key component for outstanding motor life,
DC GENERATOR THEORY. LIST the three conditions necessary to induce a voltage into a conductor.
DC Generators DC generators are widely used to produce a DC voltage. The amount of voltage produced depends on a variety of factors. EO 1.5 LIST the three conditions necessary to induce a voltage into
Single-Phase AC Synchronous Generator
ST Series Single-Phase AC Synchronous Generator Instructions for Operation and Maintenance English to English translation by R.G. Keen, May 2004. ST Series of Single-Phase AC Synchronous Generators Description
Motors and Generators
Motors and Generators Electro-mechanical devices: convert electrical energy to mechanical motion/work and vice versa Operate on the coupling between currentcarrying conductors and magnetic fields Governed
DIRECT CURRENT GENERATORS
DIRECT CURRENT GENERATORS Revision 12:50 14 Nov 05 INTRODUCTION A generator is a machine that converts mechanical energy into electrical energy by using the principle of magnetic induction. This principle
Application Information
Moog Components Group manufactures a comprehensive line of brush-type and brushless motors, as well as brushless controllers. The purpose of this document is to provide a guide for the selection and application
AC-Synchronous Generator
Design Description AC Generators come in two basic types synchronous and non-synchronous. Synchronous generators lock in with the fundamental line frequency and rotate at a synchronous speed related to
Welcome to Linear Controls Quarterly Training
Welcome to Linear Controls Quarterly Training Introduction to Power Generation Objectives Supply attendees with basic knowledge of power generators and voltage regulators and provide the fundamentals of
Induction Motor Theory
PDHonline Course E176 (3 PDH) Induction Motor Theory Instructor: Jerry R. Bednarczyk, P.E. 2012 PDH Online PDH Center 5272 Meadow Estates Drive Fairfax, VA 22030-6658 Phone & Fax: 703-988-0088 www.pdhonline.org
(3) Explosion proof. Designed to prevent ignition of any explosive gases or dust and dirt which may surround the motor.
ELECTRIC MOTORS Enclosures for Motors Types of motor enclosures generally used in farm applications: (1) Open type; drip proof or splash-proof. A general purpose motor for use in dry locations which are
Lab 8: DC generators: shunt, series, and compounded.
Lab 8: DC generators: shunt, series, and compounded. Objective: to study the properties of DC generators under no-load and full-load conditions; to learn how to connect these generators; to obtain their
Understanding the Alternator
http://www.autoshop101.com THIS AUTOMOTIVE SERIES ON ALTERNATORS HAS BEEN DEVELOPED BY KEVIN R. SULLIVAN PROFESSOR OF AUTOMOTIVE TECHNOLOGY AT SKYLINE COLLEGE SAN BRUNO, CALIFORNIA ALL RIGHTS RESERVED
Tuning Up DC Motors and Generators for Commutation and Performance
Tuning Up DC Motors and Generators for Commutation and Performance Rich Hall- National Electrical Carbon Western Mining Electrical Association June 8, 2007, Billings Montana Sometimes your machine may
Evaluating Induction Motor Rotor Bars with Electrical Signature Analysis
Evaluating Induction Motor Rotor Bars with Electrical Signature Analysis Howard W Penrose, Ph.D., CMRP SUCCESS by DESIGN Reliability Services Hello and welcome to our presentation on Evaluating Induction
Chen. Vibration Motor. Application note
Vibration Motor Application note Yangyi Chen April 4 th, 2013 1 Table of Contents Pages Executive Summary ---------------------------------------------------------------------------------------- 1 1. Table
1. The diagram below represents magnetic lines of force within a region of space.
1. The diagram below represents magnetic lines of force within a region of space. 4. In which diagram below is the magnetic flux density at point P greatest? (1) (3) (2) (4) The magnetic field is strongest
AC Induction Motor Slip What It Is And How To Minimize It
AC Induction Motor Slip What It Is And How To Minimize It Mauri Peltola, ABB Oy, Helsinki, Finland The alternating current (AC) induction motor is often referred to as the workhorse of the industry because
4 LEAD DEDICATED SINGLE PHASE LIMA MAC GENERATOR MODELS 250MSL1185 AND 250MSL1152
4 LEAD DEDICATED SINGLE PHASE LIMA MAC GENERATOR MODELS 250MSL1185 AND 250MSL1152 SERVICE PROCEDURE ELECTRICAL COMPONENT TESTING HI POTENTIAL TETS None of the windings, either rotating or stationary should
Principles and Working of DC and AC machines
BITS Pilani Dubai Campus Principles and Working of DC and AC machines Dr Jagadish Nayak Constructional features BITS Pilani Dubai Campus DC Generator A generator consists of a stationary portion called
INSTALLATION AND MAINTENANCE INSTRUCTIONS FOR THREE PHASE INDUCTION MOTORS
INSTALLATION AND MAINTENANCE INSTRUCTIONS FOR THREE PHASE INDUCTION MOTORS Frames 143T - 449TZ 5100 North IH 35 Round Rock, Texas 78681 Phone: 800-451-8798 512-255-4141 Fax: 512-244-5512 RECEIVING 1. Check
Direct Current Motors
Direct Current Motors DC MOTORS The DC machine can operate as a generator and as a motor. Chap 5. Electrical Machines by Wildi, 6 e Lecturer: R. Alba-Flores Alfred State College Spring 2008 When a DC machine
AND8008/D. Solid State Control Solutions for Three Phase 1 HP Motor APPLICATION NOTE
Solid State Control Solutions for Three Phase 1 HP Motor APPLICATION NOTE INTRODUCTION In all kinds of manufacturing, it is very common to have equipment that has three phase motors for doing different
BRUSHHOLDERS AND THE PERFORMANCE OF CARBON BRUSHES
Tech Note No. 22 TECH NOTE NO. 22 Brushholders and the Performance of Carbon Brushes Reliable Solutions Today! EA SA ELECTRICAL SERVICE APPARATUS ASSOCIATION BRUSHHOLDERS AND THE PERFORMANCE OF CARBON
SYNCHRONOUS MACHINES
SYNCHRONOUS MACHINES The geometry of a synchronous machine is quite similar to that of the induction machine. The stator core and windings of a three-phase synchronous machine are practically identical
IA Renewal Seminar 2014
IA Renewal Seminar 2014 Introductions Introductions Scott Durham President, Co-Owner Overview of FAA / EASA Certified Repair Station Instrument & Accessory Overhaul Location: McClellan CA (Sacramento)
Specifying a Variable Frequency Drive s
Specifying a Variable Frequency Drive s Put on by Bruce Reeves and Jeremy Gonzales Dykman Electrical Covering the Western US For all of your VFD and Soft Start and Motor Needs How To Specify a Variable
SALVAGING FLOOD DAMAGED ELECTRICAL EQUIPMENT
SALVAGING FLOOD DAMAGED ELECTRICAL EQUIPMENT Overview In all drying out of electrical windings, the regulation of temperature should be controlled carefully. Maximum drying temperatures on windings should
The Charging System. Section 5. Charging System. Charging System. The charging system has two essential functions:
The Charging System Charging System The charging system has two essential functions: Generate electrical power to run the vehicle s electrical systems Generate current to recharge the vehicle s battery
Lab 14: 3-phase alternator.
Lab 14: 3-phase alternator. Objective: to obtain the no-load saturation curve of the alternator; to determine the voltage regulation characteristic of the alternator with resistive, capacitive, and inductive
UNIT 3 AUTOMOBILE ELECTRICAL SYSTEMS
UNIT 3 AUTOMOBILE ELECTRICAL SYSTEMS Automobile Electrical Structure 3.1 Introduction Objectives 3.2 Ignition System 3.3 Requirement of an Ignition System 3.4 Types of Ignition 3.4.1 Battery or Coil Ignition
4 DEDICATED SINGLE PHASE LIMA MAC GENERATOR LIGHT TOWER DUTY MODELS 250MSL1278 AND 250MSL1299 SERVICE PROCEDURE ELECTRICAL COMPONENT TESTING
HI POTENTIAL TESTS 4 DEDICATED SINGLE PHASE LIMA MAC GENERATOR LIGHT TOWER DUTY MODELS 250MSL1278 AND 250MSL1299 SERVICE PROCEDURE ELECTRICAL COMPONENT TESTING None of the windings, either rotating or
Chapter 22: Electric motors and electromagnetic induction
Chapter 22: Electric motors and electromagnetic induction The motor effect movement from electricity When a current is passed through a wire placed in a magnetic field a force is produced which acts on
Principles of Adjustable Frequency Drives
What is an Adjustable Frequency Drive? An adjustable frequency drive is a system for controlling the speed of an AC motor by controlling the frequency of the power supplied to the motor. A basic adjustable
ABB ! CAUTION. Type COQ Negative Sequence Generator Relay. (50/60 Hertz) 41-161J. Instruction Leaflet
ABB Instruction Leaflet 41-161J Effective: May 1997 Supersedes I.L. 41-161H Dated July 1984 ( ) Denotes Change Since Previous Issue Type COQ Negative Sequence Generator Relay (50/60 Hertz)! CAUTION Before
AC generator theory. Resources and methods for learning about these subjects (list a few here, in preparation for your research):
AC generator theory This worksheet and all related files are licensed under the Creative Commons Attribution License, version 1.0. To view a copy of this license, visit http://creativecommons.org/licenses/by/1.0/,
13 ELECTRIC MOTORS. 13.1 Basic Relations
13 ELECTRIC MOTORS Modern underwater vehicles and surface vessels are making increased use of electrical actuators, for all range of tasks including weaponry, control surfaces, and main propulsion. This
ELECTRICAL ENGINEERING Vol. III - Induction Motor and Self-Excited Induction Generator - Tze-Fun Chan
INDUCTION MOTOR AND SELFEXCITED INDUCTION GENERATOR TzeFun Chan The Hong Kong Polytechnic University, Hung Hom, Kowloon, Hong Kong, China Keywords: threephase induction motor, singlephase induction motor,
Basics of Electricity
Basics of Electricity Generator Theory PJM State & Member Training Dept. PJM 2014 8/6/2013 Objectives The student will be able to: Describe the process of electromagnetic induction Identify the major components
WHITE PAPER. DC Motors Explained. DC Motors Explained: White Paper, Title Page
DC Motors Explained: White Paper, Title Page DC Motors Explained By Joe Kimbrell, Product Manager, Drives, Motors & Motion, AutomationDirect DC Motors Explained: White Paper, pg. 2 How many types of DC
ST Style Generator. Owners/Operators Manual
ST Style Generator Owners/Operators Manual LLC 216 Airport Rd NE Milledgeville, GA 31061 478-453-9358-Office 478-457-5524- Tom Cell 478-251-2914- Chris Cell Table of Contents Page 2. Table of Contents
Understanding Insulation Resistance Testing
Understanding Insulation Resistance Testing Why have an insulation testing program? A regular program of testing insulation resistance is strongly recommended to prevent electrical shocks, assure safety
Service and Maintenance. SEW-EURODRIVE Driving the world
SEW Brakes Service and Maintenance 2 Objectives Upon completion of this session, you will be able to do the following: - Identify the components of an SEW brakemotor - Explain the operation of the SEW
Equipment: Power Supply, DAI, Wound rotor induction motor (8231), Electrodynamometer (8960), timing belt.
Lab 13: Wound rotor induction motor. Objective: to examine the construction of a 3-phase wound rotor induction motor; to understand exciting current, synchronous speed and slip in this motor; to determine
DC Motor control Reversing
January 2013 DC Motor control Reversing and a "Rotor" which is the rotating part. Basically there are three types of DC Motor available: - Brushed Motor - Brushless Motor - Stepper Motor DC motors Electrical
AC Electric Motors best practice
If you want to learn more about best practice machinery maintenance, or world class mechanical equipment maintenance and installation practices, follow the link to our Online Store and see the Training
DC generator theory. Resources and methods for learning about these subjects (list a few here, in preparation for your research):
DC generator theory This worksheet and all related files are licensed under the Creative Commons Attribution License, version 1.0. To view a copy of this license, visit http://creativecommons.org/licenses/by/1.0/,
Equipment: Power Supply, DAI, Universal motor (8254), Electrodynamometer (8960), timing belt.
Lab 12: The universal motor. Objective: to examine the construction of the universal motor; to determine its no-load and full-load characteristics while operating on AC; to determine its no-load and full-load
CHAPTER 4 DESIGN OF INTEGRAL SLOT AND FRACTIONAL SLOT BRUSHLESS DC MOTOR
47 CHAPTER 4 DESIGN OF INTEGRAL SLOT AND FRACTIONAL SLOT BRUSHLESS DC MOTOR 4.1 INTRODUCTION This chapter deals with the design of 24 slots 8 poles, 48 slots 16 poles and 60 slots 16 poles brushless dc
Simple Analysis for Brushless DC Motors Case Study: Razor Scooter Wheel Motor
Simple Analysis for Brushless DC Motors Case Study: Razor Scooter Wheel Motor At first glance, a brushless direct-current (BLDC) motor might seem more complicated than a permanent magnet brushed DC motor,
Rutland 913 Windcharger Fault Finding Guide
Rutland 913 Windcharger Fault Finding Guide Document No. SM-133 Issue A LOW VOLTAGE CHARGE CURRENT? TE 4 REGULATOR TE 5 REG RETURN REG TO MANUFACTURER CHARGE CURRENT INTERMITTENT CHARGE CURRENT SUFFICIENT
Solving VFD-sourced Bearing Current Problems in AC Motors.
Solving VFD-sourced Bearing Current Problems in AC Motors. The 2 main sources of motor shaft voltage are: 1. Asymmetric Motor construction The stator and rotor magnetic circuits within the motor itself
SHIP SERVICE GENERATORS (AC)
CHAPTER 14 SHIP SERVICE GENERATORS (AC) INTRODUCTION All generators change mechanical energy into electrical energy. This is the easiest way to transfer power over distances. Fuel is used to operate the
WINDING RESISTANCE TESTING
WINDING RESISTANCE TESTING WINDING RESISTANCE TEST SET, MODEL WRT-100 ADWEL INTERNATIONAL LTD. 60 Ironside Crescent, Unit 9 Scarborough, Ontario, Canada M1X 1G4 Telephone: (416) 321-1988 Fax: (416) 321-1991
Rotating Machinery Diagnostics & Instrumentation Solutions for Maintenance That Matters www.mbesi.com
13 Aberdeen Way Elgin, SC 29045 Cell (803) 427-0791 VFD Fundamentals & Troubleshooting 19-Feb-2010 By: Timothy S. Irwin, P.E. Sr. Engineer [email protected] Rotating Machinery Diagnostics & Instrumentation
Federal Wage System Job Grading Standard for Electrical Equipment Repairing, 2854. Table of Contents
Federal Wage System Job Grading Standard for Electrical Equipment Repairing, 2854 Table of Contents WORK COVERED... 2 WORK NOT COVERED... 2 TITLES... 3 GRADE LEVELS... 3 HELPER AND INTERMEDIATE JOBS...
EVANS ENTErprises, Inc.
EVANS ENTErprises, Inc. Since 1954 THE LEADER IN ELECTRO-MECHANICAL SALES, SERVICE AND INTERGRATION Our Mission Our purpose at Evans Enterprises is to serve customers by providing increased value of product
26 3213.13 Diesel Engine Driven Generators Page 1 of 6
Last Update: December 8, 2014 A. Description of System Consultant s Handbook Page 1 of 6 1. Provide a diesel engine driven electric generating unit, factory assembled, tested and certified to operate at
13 common causes of motor failure
13 common causes of motor failure Application Note What to look for and how to improve asset uptime Motors are used everywhere in industrial environments and they are becoming increasingly complex and
Line Reactors and AC Drives
Line Reactors and AC Drives Rockwell Automation Mequon Wisconsin Quite often, line and load reactors are installed on AC drives without a solid understanding of why or what the positive and negative consequences
How to Turn an AC Induction Motor Into a DC Motor (A Matter of Perspective) Steve Bowling Application Segments Engineer Microchip Technology, Inc.
1 How to Turn an AC Induction Motor Into a DC Motor (A Matter of Perspective) Steve Bowling Application Segments Engineer Microchip Technology, Inc. The territory of high-performance motor control has
Digital Energy ITI. Instrument Transformer Basic Technical Information and Application
g Digital Energy ITI Instrument Transformer Basic Technical Information and Application Table of Contents DEFINITIONS AND FUNCTIONS CONSTRUCTION FEATURES MAGNETIC CIRCUITS RATING AND RATIO CURRENT TRANSFORMER
Chapter 5. Components, Symbols, and Circuitry of Air-Conditioning Wiring Diagrams
Chapter 5 Components, Symbols, and Circuitry of Air-Conditioning Wiring Diagrams Objectives Upon completion of this course, you will be able to: Explain what electrical loads are and their general purpose
BRUSHLESS DC MOTORS. BLDC 22mm. BLDC Gearmotor Size 9. nuvodisc 32BF. BLDC Gearmotor Size 5
BRUSHLESS DC MOTORS BLDC Gearmotor Size 9 BLDC 22mm nuvodisc 32BF BLDC Gearmotor Size 5 Portescap Brushless DC motors are extremely reliable and built to deliver the best performances. Their high power
Speed Control Methods of Various Types of Speed Control Motors. Kazuya SHIRAHATA
Speed Control Methods of Various Types of Speed Control Motors Kazuya SHIRAHATA Oriental Motor Co., Ltd. offers a wide variety of speed control motors. Our speed control motor packages include the motor,
Unit 33 Three-Phase Motors
Unit 33 Three-Phase Motors Objectives: Discuss the operation of wound rotor motors. Discuss the operation of selsyn motors. Discuss the operation of synchronous motors. Determine the direction of rotation
t... - GENERATORS - / SWITCHABLE VOLTAGE TRAILER MOUNTED GENERATOR W b 0 WER PLANTS-Over OPERATION and MAINTENANCE INSTRUCTIONS 45 Years of Leadership
- GENERATORS SWITCHABLE VOLTAGE TRAILER MOUNTED GENERATOR OPERATION and MAINTENANCE INSTRUCTIONS Attention: Read all instructions in this manual before attempting to operate or service your WlNCO generator.
Shaft grounding. Carbon brushes for shaft grounding are used in turbo-generators, in distinct AC- and DC motors and as a special application in Ships.
"Modern AC-Motors don't need carbon brushes and are maintenance free " Until some years ago this thrilling statement could be heard from motor OEM's. Nowadays SCHUNK supplies carbon brushes and brush holders
PM734F - Technical Data Sheet Winding 28
- Technical Data Sheet Winding 28 SPECIFICATIONS & OPTIONS STANDARDS STAMFORD AC generators are designed to meet the performance requirements of IEC EN 60034-1. Other international standards, including
8 Speed control of Induction Machines
8 Speed control of Induction Machines We have seen the speed torque characteristic of the machine. In the stable region of operation in the motoring mode, the curve is rather steep and goes from zero torque
C Standard AC Motors
C Standard AC Standard AC C-1 Overview, Product Series... C-2 Constant... C-9 C-21 C-113 Reversible C-147 Overview, Product Series Constant Reversible Electromagnetic Brake C-155 Electromagnetic Brake
GOVERNMENT COLLEGE OF ENGINEERING, BARGUR
UNIT NAME NO OF QNS 1A DC GENERATORS 124 1B DC MOTORS 123 2 TRANSFORMERS 135 THREE PHASE INDUCTION 3A MOTORS 101 SINGLE PHASE INDUCTION 3B MOTORS 110 4 SYNCHRONOUS MOTORS 124 TRANSMISSION AND DISTRIBUTION
*ADVANCED ELECTRIC GENERATOR & CONTROL FOR HIGH SPEED MICRO/MINI TURBINE BASED POWER SYSTEMS
*ADVANCED ELECTRIC GENERATOR & CONTROL FOR HIGH SPEED MICRO/MINI TURBINE BASED POWER SYSTEMS Jay Vaidya, President Electrodynamics Associates, Inc. 409 Eastbridge Drive, Oviedo, FL 32765 and Earl Gregory,
Predictive Maintenance
PART ONE of a predictive maintenance series Predictive Maintenance Overview Predictive maintenance programs come in all shapes and sizes, depending on a facility s size, equipment, regulations, and productivity
3.0 CHARACTERISTICS. AR Auxiliary Relay High Speed, High Threshold 41-759.3C
41-759.3C the magnetic core upon energizing of the switch. When the switch closes, the moving contacts bridge two stationary contacts, completing the trip circuit. Also during this operation two fingers
CONTINUOUS AUTOMATED FLUX MONITORING FOR TURBINE GENERATOR ROTOR CONDITION ASSESSMENT
CONTINUOUS AUTOMATED FLUX MONITORING FOR TURBINE GENERATOR ROTOR CONDITION ASSESSMENT Abstract J. Kapler, S. Campbell, M. Credland Iris Power Engineering Inc. Toronto, Canada Flux monitoring via permanently
INSTRUMENTATION AND CONTROL TUTORIAL 2 ELECTRIC ACTUATORS
INSTRUMENTATION AND CONTROL TUTORIAL 2 ELECTRIC ACTUATORS This is a stand alone tutorial on electric motors and actuators. The tutorial is of interest to any student studying control systems and in particular
R E C O M M E N D E D P R A C T I C E FOR THE REPAIR OF ROTATING ELECTRICAL APPARATUS
Recognized as an American National Standard (ANSI) A N S I / E A S A A R 10 0-2 0 10 EASA Standard AR100-2010 R E C O M M E N D E D P R A C T I C E FOR THE REPAIR OF ROTATING ELECTRICAL APPARATUS ELECTRICAL
Power-factor testing of rotating machinery is another valuable test
Feature Power-Factor Testing of Stator Winding Insulation: Understanding the Test Technique and Interpretation of Results Power-factor testing of rotating machinery is another valuable test technique providing
ECM Motors Manufactured By Regal Beloit. Products and Applications- What s an ECM? GEXPRO Regal Beloit s distribution arm for all ECM motor products
ECM Motors Manufactured By Regal Beloit Products and Applications- What s an ECM? ECM 2.3 series ECM 142 Arktic ECM 58mm Arktic ECM 59 Arktic SSC2 Arktic 51 GEXPRO Regal Beloit s distribution arm for all
The Starting System. Section 4. Starting System Overview. Starter. The starting system:
The Starting System Starter The starter motor drives the engine through a pinion gear that engages the ring gear on the flywheel. Fig. 4-01 TL623f401c Starting System Overview The starting system: Uses
PI734D - Technical Data Sheet
PI734D - Technical Data Sheet PI734D SPECIFICATIONS & OPTIONS STANDARDS Newage Stamford industrial generators meet the requirements of BS EN 60034 and the relevant sections of other national and international
AC Generators and Motors
AC Generators and Motors Course No: E03-008 Credit: 3 PDH A. Bhatia Continuing Education and Development, Inc. 9 Greyridge Farm Court Stony Point, NY 10980 P: (877) 322-5800 F: (877) 322-4774 [email protected]
PI734B - Technical Data Sheet
PI734B - Technical Data Sheet PI734B SPECIFICATIONS & OPTIONS STANDARDS Newage Stamford industrial generators meet the requirements of BS EN 60034 and the relevant sections of other national and international
Section 9.5 Electric Motors
Power connection Brush Commutator Bearing Electromagnet Armature haft Bearing Cooling fan ection 9.5 Electric Motors Electric motors spin the parts of many household machines. ometimes this rotary motion
This slide is hidden. It will not show up during presentation.
This material has been created and distributed for the purpose of education and to encourage best practices of the HVAC industry. The integrity of the industry we share is the responsibility of every one
DHANALAKSHMI COLLEGE OF ENGINEERING DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING EE2302 - ELECTRICAL MACHINES II UNIT-I SYNCHRONOUS GENERATOR
1 DHANALAKSHMI COLLEGE OF ENGINEERING DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING Constructional details Types of rotors EE2302 - ELECTRICAL MACHINES II UNIT-I SYNCHRONOUS GENERATOR PART A 1.
GenTech Practice Questions
GenTech Practice Questions Basic Electronics Test: This test will assess your knowledge of and ability to apply the principles of Basic Electronics. This test is comprised of 90 questions in the following
Understanding Generator Ripple Waveforms
Understanding Generator Ripple Waveforms 2 Understanding Generator Ripple Waveforms Chapter Page Preliminary Information and Setup 3 Generator Theory 6 Generator Ripple Theory 15 Factors that Influence
COMPUTER AIDED ELECTRICAL DRAWING (CAED) 10EE65
COMPUTER AIDED ELECTRICAL DRAWING (CAED) EE Winding Diagrams: (i) DC Winding diagrams (ii) AC Winding Diagrams Terminologies used in winding diagrams: Conductor: An individual piece of wire placed in the
Verification of Short Circuit Test Results of Salient Poles Synchronous Generator
Verification of Short Circuit Test Results of Salient Poles Synchronous Generator Abdul Jabbar Khan 1, Amjadullah Khattak 2 1 PG Student, University of Engineering and Technology, Peshawar, Department
17. APTA PR-IM-S-017-02 Standard for Third Rail Current Collection Equipment Periodic Inspection and Maintenance
17. APTA PR-IM-S-017-02 Standard for Third Rail Current Collection Equipment Periodic Inspection and Maintenance Approved October 30, 2002 APTA Passenger Rail Equipment Safety Standards Task Force Authorized
Inductance. Motors. Generators
Inductance Motors Generators Self-inductance Self-inductance occurs when the changing flux through a circuit arises from the circuit itself. As the current increases, the magnetic flux through a loop due