REQUEST FOR BIDS Hillside Terrace Attic Air Sealing & Insulating Project

Size: px
Start display at page:

Download "REQUEST FOR BIDS Hillside Terrace Attic Air Sealing & Insulating Project"

Transcription

1 March 2013 REQUEST FOR BIDS Hillside Terrace Attic Air Sealing & Insulating Project The Burlington Housing Authority (BHA) is inviting Contractors to submit Bids for the Attic Air Sealing and Insulating at Hillside Terrace, Burlington, VT. Hillside Terrace is comprised of 13 Duplex apartment Buildings totaling 26 apartments. Abbreviated Written Summary: Briefly and without force and effect upon the contract documents, the work of the Contract can be summarized as follows: Contractor shall provide all labor and materials to perform all work listed below: A. Air seal, insulate, repair gypsum board and remediate mold in 26 attic spaces as follows: REPLACEMENT LIGHTING: Provide a $13,000 allowance for the following Replacement Lighting Work: Replace 2 nd floor recessed closet lights with new surface mounted energy star rated light. Contractor shall remove existing recessed light, install new single gang box in ceiling and patch ceiling gypsum board around box, add texture and paint to match existing. New light will be chosen by BHA and wired and installed by contractor. Approx. Two (2) lights per apartment totaling Fifty Two (52) site wide. AIR SEALING: All air bypasses into the attic shall be sealed air tight. Attic air sealing must address all penetrations or wiring, plumbing vent stacks, attic hatches, surface mounted ceiling fixtures, recessed lighting fixtures, exhaust fan assemblies, chimney/flue chases, partition walls, exterior walls, merger walls between adjoining building sections, and all other miscellaneous penetrations. This shall be done be removing/pulling back existing insulation around all penetrations and treating each with an air sealing foam spray product. A single component low expansion polyurethane foam or a expanding, 2-part polyurethane foam is acceptable for sealing most penetrations. The foam shall be a Class 1 fire retardant, meeting ASTM E84 Surface Burning Characteristics. The foam shall be installed per manufacturer specifications. Seal with (Touch n Seal Quick Cure or (Touch n Seal FR Two Component Class 1 Fire Retardant Spray Foam. The exterior wall tops shall be sealed using an expanding, 2-part polyurethane foam,

2 sprayed on both outer and inner top plates. This includes both gable and eave edges of the building. The foam shall be a Class 1 fire retardant, meeting ASTM E84 Surface Burning Characteristics. The foam shall be installed per manufacturer specifications. Seal with (Touch n Seal FR Two Component Class 1 Fire Retardant Spray Foam. DAMS: A durable wooden plywood (5/8 thick min.) insulation dam shall be installed around all attic hatch openings. The dam must extend at least 2 higher than the settled insulation depth at the completion of the weatherization project. On the front of the buildings where the eaves extend beyond the top plates a durable wooden insulation dam shall be installed beyond the top plate to prevent insulation from getting into the eaves. ATTIC HATCH: Install 3-2 layers of XPS Rigid Foam Insulation (Extruded polystyrene) to the top of existing attic hatch panels and to each other with Loctite PL 300 VOC Foam Board Adhesive. Tape all edges of foam board with aluminum tape to cover all seams. Install a rubber compression gasket to the under side of the attic hatch to form an air seal when hatch is dropped into position. VENT EXTENSIONS: Install all new foam baffle vents. Each baffle must be installed in a manner that will protect the attic insulation from both intrusion and wind washing. This can be achieved by securely fastening the baffle to the underside of the roof and then either placing a piece of rigid foam board or rolled fiberglass beyond the exterior top plate. The foam board would be sealed in place at the edges with foam, and the fiberglass batt would be sprayed and covered with the 2-part foam while spraying the top plates. This will prevent wind wash and insulation from getting into the eaves. The perimeter top plates must still be sealed with a 2-part, closed cell foam. Vents must extend at least 2 higher than the settled insulation depth at the completion of the weatherization project. PERIMETER PULL: Any preexisting fiberglass batting shall be removed from within 4 feet of the perimeter of the attic. This insulation can be used to roll up and block soffits, or can be added on top of existing insulation in the center of the attic. Once the perimeter is cleared of fiberglass and all attic air sealing measures are complete and verified to be effective, blown-in insulation must be installed around the attic perimeter and over the fiberglass batting throughout the rest of the attic. INSULATION:

3 The minimum effective R-value at project completion shall be R-60. If roof clearance does not allow for an R-60, insulation must be added up to the roofline. All air sealing measures must be complete before installing new insulation. Existing conditions in buildings are 6-10 of various insulation (cellulose, fiberglass battings with cellulose, blown fiberglass). Install an average of 14 additional cellulose over existing insulation. PARTY WALLS: The party walls shall be drilled to accept an insulation blowing tube. Dense pack all party wall cavities with cellulose to a density of 3.5 pounds per cubic foot. This will provide insulation and reduce air infiltration within the cavity. Repair holes in gypsum board. CLOSET SLANTS: Each of the closets above the front entry way has a slanted ceiling. This slant is insulated with fiberglass batting. A rigid insulation blowing tube shall be pushed down the slant over the fiberglass batting to dense pack each cavity with cellulose. If vent baffles are existing in cavities, it is acceptable to block the airflow when dense packing with cellulose. BUMPOUTS: Front bump outs are open and accessible for work. Air seal any penetrations as normal. Dense pack accessible wall cavities. Once general air sealing and dense packing of walls is complete, cover cavity over bump out with a building wrap or 6 mil poly sheeting sealed at the edges with foam. The cover can be held in place by strapping. Dense pack the cavity through a hole in the cover, and seal hole with foam. Side bump outs will need to be accessed from either through the exterior siding or through the interior. These should dense packed with cellulose. Contractor has the option to perform this work from the interior or exterior. Interior or exterior building components damaged due to this work shall be restored to the exiting condition. Back bump outs are accessible from the attic, but with very little space due to the slope of the roof. As much effort to air seal using foam should be made. The best option here would be to dense pack the cavity from the attic.

4 MOLD REMEDIATION: Spray all visible mold located on roof decking and framing with Moldstat plus mold killer product per manufacturer s instructions. Black mold is visible in several attic areas with approx. square footage as follows: Apt #34 10 sq ft Apt #47 50 sq ft Apt #49 24 sq ft Apt # sq ft Apt #72 60 sq ft Apt #73 20 sq ft Apt #81 15 sq ft Apt # sq ft Apt #83 10 sq ft DRYWALL REPAIR: Patch all holes in attic party wall gypsum board created for the installation of blown cellulose in wall cavity. Re-tape (Fire Tape) all seams in attic party wall gypsum board that are failing. Approx. 48 linear ft. per apartment. Patch holes in gypsum board ceilings/walls in 2 nd floor closets due to the replacement of closet lighting. See Replacement Lighting above. Base Bid: Furnish all material, labor and equipment to perform all work in apartment attics as described above. Base Bid to include $13,000 lighting allowance. General Conditions Contractor is responsible to obtain and pay for all required Building Permits & Inspections. Note: Thirteen (13) separate Building Permits may be required for this project. Contractor is responsible to ensure areas under construction are controlled to ensure the safety of the residents. Contractor is responsible for the proper protection of all BHA/Tenant property. Any and all damage to said property shall be replaced at Contactors expense. All contractors will be required to supply proof of Workman s Comp and Employer s Liability Insurance. All Debris must be removed from premises at the end of each day. Working hours for this project shall be between 8am-4:30pm Monday thru Friday. Contractor shall submit a project schedule prior to beginning the project and work with BHA to coordinate access to apartments. Coordinate 48 Hours notice to access Apartments with BHA Staff. Contractor shall provide all electrical power required for the project utilizing generators. Contractor shall provide temporary toilet facilities.

5 Attention is called to: Attached HUD General Conditions for small construction/development contracts Attention is called to: Attached Section 3, Women & Minority Business Concern. Attention is called to: Attached Davis-Bacon Labor Standards and Wage Provisions. Contractor will be required to submit attached form: DOL WH 347-Payroll information. Additional forms may be required based on HUD Guidelines. Bids will be received at the offices of the BURLINGTON HOUSING AUTHORITY at 65 Main Street, Burlington, Vermont until March 26 th, A Pre-Bid Meeting will be held at 10am on Tuesday March 19th, 2013 at Hillside Terrace, Burlington, Vermont. BHA will meet contractors at the parking lot near the playground at which time bidders are invited to inspect some of the apartments and attic spaces. The BURLINGTON HOUSING AUTHORITY reserves the right to accept or reject any or all Proposals, or to waive informalities or minor irregularities in the bids received and to seek clarification of bid documents and pricing. Award of contract shall be made to the responsible bidder whose bid will be most advantageous to the Authority. The successful bidder will be required to provide an assurance of completion. No Proposal shall be withdrawn for a period of Thirty (30) days subsequent to the opening of bids without consent of the BURLINGTON HOUSING AUTHORITY. The successful bidder shall be prepared to start the work as soon as possible after the Notice to Proceed and complete the entire installation within 60 days. Inspection of the property may be arranged by appointment. Please contact John MacDonald at (802) , ext. 224 to schedule a date and time for a site visit and to study the Project requirements or John at jmacdonald@burlingtonhousing.org. Questions concerning this project shall be directed to the Burlington Housing Authority office at 65 Main Street, Burlington, Vermont. BURLINGTON HOUSING AUTHORITY Paul Dettman, Executive Director March 11, 2013

6

Envelope INSULATION BATT (2) Avoid Using Batt Insulation With Metal Framing. Pressure or Friction Fit

Envelope INSULATION BATT (2) Avoid Using Batt Insulation With Metal Framing. Pressure or Friction Fit R-H-DI1 INSULATION BATT NR-E-IB1 Avoid Using Batt Insulation With Metal Framing Batt insulation should not be used with metal framing systems. Although it is common to see fiberglass batt insulation installed

More information

Home Energy Evaluation Report for Fritz Kreiss and Catherine McQueen

Home Energy Evaluation Report for Fritz Kreiss and Catherine McQueen Home Energy Evaluation Report for Fritz Kreiss and Catherine McQueen May 2008 Wisconsin Area PO BOX 115 Lake Geneva, WI 53147 CELL (414) 550-4765 Home Performance with ENERGY STAR Evaluation Report Customer

More information

Preventing Ice Dams on Roofs

Preventing Ice Dams on Roofs Preventing Ice Dams on Roofs Facility Manager November/December 2005 When a roof leaks, facility managers inevitably receive complaints from building occupants. If it is winter, ice dams are often the

More information

ROOFS, SNOW AND ICE DAMS

ROOFS, SNOW AND ICE DAMS ROOFS, SNOW AND ICE DAMS The Problem Ice dams are a common roof performance problem in cold climate buildings. Simply put, they are ridges of ice and icicles caused by melt water from further up the roof

More information

Signs of insulation problems In the winter. In the summer. conditioning system

Signs of insulation problems In the winter. In the summer. conditioning system about your house CE 19 While previous generations may have been content to live in drafty houses, most people now want comfortable warm houses. A healthy house today is well sealed, well insulated and

More information

Attic condensation during winter can

Attic condensation during winter can Housing Fact Sheet Causes and Cures of Attic Condensation and Roof Ice Damming Problems Attic condensation during winter can decrease the effectiveness of insulation and over time can cause significant

More information

This sample quote was created using the JobFLEX Mobile App Learn More at www.job-flex.com

This sample quote was created using the JobFLEX Mobile App Learn More at www.job-flex.com The Best Products The Best Price The Best Service...We Guarantee It! Prepared For: ABC Company 125 Maple St Rockford, MI 49341 Phone: 555.223.1245 Fax: 555.555.1234 Billing Address Phone: 566.563.5866

More information

Whitley Manufacturing Co., Inc. 201 W. First Street S. Whitley, IN 46787 Phone (260) 723-5131 Sales Fax (260) 723-6396 whitley@whitleyman.

Whitley Manufacturing Co., Inc. 201 W. First Street S. Whitley, IN 46787 Phone (260) 723-5131 Sales Fax (260) 723-6396 whitley@whitleyman. Building Type Building Code Whitley Classroom Buildings BOCA, UBC, SBCCI, NEC, ADA Structural Support Outrigger construction standard, Whitley model classrooms. Main support beams to be 12 11.8# per lineal

More information

Additions and Alterations

Additions and Alterations Additions and Alterations Addition and alteration construction is a miscellaneous grouping of home improvement and renovation projects that are generally geared toward the enhancement of an existing principal

More information

All bidders shall indicate in their bid/proposal that this Addendum has been received and considered in their bid proposal.

All bidders shall indicate in their bid/proposal that this Addendum has been received and considered in their bid proposal. Addendum #1 Fire Damage Repairs 4316 City View Terrace, Units A and B City View Terrace, OH5-13C, AMP 4 IFB #14-03 October 23, 2014 Greater Dayton Premier Management 400 Wayne Ave. Dayton, Ohio 45410 This

More information

Rehab Inspection Report Page 1

Rehab Inspection Report Page 1 Rehab Inspection Report Page 1 Home Address: Construction Style: Number of bedrooms Square footage: Value of offer: Estimated rehab cost: Value of resale: Orientation of house: N S E W Note: orientation

More information

This handout is a guide only and does not contain all of the requirements of the Minnesota State Building Code or city ordinances.

This handout is a guide only and does not contain all of the requirements of the Minnesota State Building Code or city ordinances. Basement Finishing Guide Community Development Department Building Inspections Division 5200 85 th Avenue North / Brooklyn Park, MN 55443 Phone: (763) 488-6379 / Fax: (763) 493-8171 6/15 www.brooklynpark.org

More information

Insulation R-Value Comparisons

Insulation R-Value Comparisons Insulation R-Value Comparisons American Ingenuity s component panels for the 22 48 domes contains seven inch thick rigid Expanded Polystyrene (E.P.S.) insulation which has an R value of 28. American Ingenuity

More information

September 3, 2009. Ric Boyd, Public Works Director Ketchikan Gateway Borough 344 Front St. Ketchikan, AK 99901

September 3, 2009. Ric Boyd, Public Works Director Ketchikan Gateway Borough 344 Front St. Ketchikan, AK 99901 September 3, 2009 Ric Boyd, Public Works Director Ketchikan Gateway Borough 344 Front St. Ketchikan, AK 99901 RE: Ketchikan Gateway Borough Gateway Recreation Center Roof Observations and Intrusive Inspections

More information

Best Basement Water Management Practices

Best Basement Water Management Practices Best Basement Water Management Practices Guide written by Patrick Sluss Sluss Construction (330) 224 5394 When a home owner is faced with a leaking basement there is a way to correct the problem and a

More information

solutions & tips six Wise Energy Guide Building envelope solutions and simple tips AIR SEALING

solutions & tips six Wise Energy Guide Building envelope solutions and simple tips AIR SEALING Wise Energy Guide solutions & tips 32 AIR SEALING Is your house leaking money? six Building envelope solutions and simple tips If your home is like most, the greatest amount of heat loss is from air leakage;

More information

STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM

STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM Installed in Pre-engineered Steel Buildings Provides Lowest Cost Construction Method for CORROSIVE AND WET Environments PREFERRED SOLUTIONS, INC.

More information

RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000

RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000 RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000 SECTION R905 REQUIREMENTS FOR ROOF COVERINGS R905.1 Roof covering application. Roof coverings

More information

Retrofitting an Insulated Cold Roof

Retrofitting an Insulated Cold Roof Retrofitting an Insulated Cold Roof As a metal-roofing contractor in the Upper Peninsula of Michigan, I am frequently asked to fix roof leaks that have less to do with roofing than with the way poorly

More information

EcoTouch Insulation with PureFiber Technology

EcoTouch Insulation with PureFiber Technology PROJECT ENGINEER RESPONSIBILITY: This is a general specification guide, intended to be used by experienced construction professionals, in conjunction with good construction practice and professional judgment.

More information

DEFAULT HEAT LOSS COEFFICIENTS

DEFAULT HEAT LOSS COEFFICIENTS DEFAULT HEAT LOSS COEFFICIENTS SECTION A101 GENERAL REQUIREMENTS A101.1 Scope. The following defaults shall apply to Chapter 4 of both the (RE) and (CE) sections of the IECC. This chapter includes tables

More information

HVAC INSTALLATION. Success with 2015 IECC Northeast & Mid-Atlantic. Checklist for Builders & Trades

HVAC INSTALLATION. Success with 2015 IECC Northeast & Mid-Atlantic. Checklist for Builders & Trades Success with 2015 IECC Northeast & Mid-Atlantic Checklist for Builders & Trades COPYRIGHT 2015 ADVANCED ENERGY. ALL RIGHTS RESERVED TEMPLATE 2015.1.0 PAGE 1 CHECKLIST: JOB READY 1. 2. 3. 4. 5. 6. 7. 8.

More information

Managing Trade Contractors for High Performance Homes. Carl Seville

Managing Trade Contractors for High Performance Homes. Carl Seville Managing Trade Contractors for High Performance Homes Carl Seville Overview Implementing Management Systems Why How Steps Troubleshooting Successes High Performance Buildings Attention to detail Management

More information

ATTIC BYPASSES HOME ENERGY GUIDE

ATTIC BYPASSES HOME ENERGY GUIDE HOME ENERGY GUIDE TECHNIQUES TACTICS & TIPS How to locate attic bypasses Common bypasses and how to fix them Attic bypasses are hidden air passageways that lead from the heated space into the attic. Because

More information

first look at GigaCrete s revolutionary new New Construction GigaHouse GigaHouse Utilizing GigaPanel

first look at GigaCrete s revolutionary new New Construction GigaHouse GigaHouse Utilizing GigaPanel first look at GigaCrete s revolutionary new New Construction GigaHouse GigaHouse Utilizing GigaPanel What is GigaCrete GigaCrete is a family of products based on low carbon footprint Green ceramic binders

More information

Minimizing Water Intrusion Through Roof Vents in High-Wind Regions

Minimizing Water Intrusion Through Roof Vents in High-Wind Regions Minimizing Water Intrusion Through Roof Vents in High-Wind Regions http://www.fema.gov HURRICANE IKE RECOVERY ADVISORY Purpose: To recommend practices for minimizing water intrusion through roof vent systems

More information

about your house Attic Venting, Attic Moisture, and Ice Dams Figure 1 Typical attic floor insulations

about your house Attic Venting, Attic Moisture, and Ice Dams Figure 1 Typical attic floor insulations about your house CE 13 Attic Venting, Attic Moisture, and Ice Dams It is rare for Canadians to visit their attics. For many years building codes have required high levels of attic insulation, making attics

More information

PANELIZED HOME INSTALLATION GUIDELINE

PANELIZED HOME INSTALLATION GUIDELINE PANELIZED HOME INSTALLATION GUIDELINE A typical home package will be constructed of Snap-N-Lock Insulated Panels clad with steel skins. 4" panels will be used for the walls, and 6" panels for the roof.

More information

Air Conditioner Duct Construction & Repair

Air Conditioner Duct Construction & Repair PROPER ROOF AIR CONDITIONER MOUNTING At Newmar, there are two different models of air conditioners available on all towable and motorized units. The different models are the Dometic Brisk and Penguin models,

More information

ENERGY STAR Qualified New Homes Thermal Enclosure Checklist. Water Management Checklist. Eli Caudill

ENERGY STAR Qualified New Homes Thermal Enclosure Checklist. Water Management Checklist. Eli Caudill ENERGY STAR Qualified New Homes Thermal Enclosure Checklist & Water Management Checklist Eli Caudill ENERGY STAR Version 3 Tighter Standards Whole Home Approach Better, More Sustainable Construction Surpasses

More information

Asphalt Shingle Application Requirements

Asphalt Shingle Application Requirements Alberta Allied Roofing Association Asphalt Shingle Application Requirements Section 1 Roof Decks 1.1 General Asphalt Shingles are not permitted to be installed directly over rigid insulation. When Asphalt

More information

A D D E N D U M # 3 QUESTIONS FROM BIDDERS: DATE: November 5, 2012. All Bidders. Jenne dos Santos, CBI Consulting Inc. City of Chelsea, MA

A D D E N D U M # 3 QUESTIONS FROM BIDDERS: DATE: November 5, 2012. All Bidders. Jenne dos Santos, CBI Consulting Inc. City of Chelsea, MA Page 1 of 10, Addendum No. 3 Temporary Garage Structure City of Chelsea, MA November 5, 2012 CBI Job No.: 12055-A A D D E N D U M # 3 DATE: November 5, 2012 TO: FROM: PROJECT: All Bidders Jenne dos Santos,

More information

NRDCA 400 GUIDELINE FOR FIELD APPLICATION of LIGHTWEIGHT INSULATING CONCRETE REROOFING/RECOVER SYSTEMS

NRDCA 400 GUIDELINE FOR FIELD APPLICATION of LIGHTWEIGHT INSULATING CONCRETE REROOFING/RECOVER SYSTEMS NRDCA 400 GUIDELINE FOR FIELD APPLICATION of LIGHTWEIGHT INSULATING CONCRETE REROOFING/RECOVER SYSTEMS The (NRDCA) has prepared this document to provide customers and installers information that the industry

More information

ATTIC AIR LEAKS & ICE DAMS

ATTIC AIR LEAKS & ICE DAMS HOME ENERGY GUIDE TECHNIQUES TACTICS & TIPS How to locate attic air leaks Common air leaks and how to fix them ATTIC AIR LEAKS & ICE DAMS Minnesota Department of Commerce Energy Information Center Ice

More information

HVAC INSTALLATION SUCCESS WITH 2012 IECC DELAWARE. for Builders & Trades. Recommended Practices for Optimized Energy Savings

HVAC INSTALLATION SUCCESS WITH 2012 IECC DELAWARE. for Builders & Trades. Recommended Practices for Optimized Energy Savings SUCCESS WITH 2012 IECC DELAWARE Recommended Practices for Optimized Energy Savings for Builders & Trades COPYRIGHT 2015 ADVANCED ENERGY. ALL RIGHTS RESERVED VERSION 2015.1.0 CHECKLIST: JOB READY 1. 2.

More information

CITY OF WHITE BEAR LAKE BUILDING INSPECTION DEPARTMENT 4701 Highway 61 White Bear Lake, MN 55110 Fax: 651-429-8503. Re-Roofing: Asphalt Shingles

CITY OF WHITE BEAR LAKE BUILDING INSPECTION DEPARTMENT 4701 Highway 61 White Bear Lake, MN 55110 Fax: 651-429-8503. Re-Roofing: Asphalt Shingles CITY OF WHITE BEAR LAKE BUILDING INSPECTION DEPARTMENT 4701 Highway 61 White Bear Lake, MN 55110 Fax: 651-429-8503 Re-Roofing: Asphalt Shingles This is a summary of the standard requirements based on the

More information

Fiberglas, Exterior Wall Thermal Insulation

Fiberglas, Exterior Wall Thermal Insulation PROJECT ENGINEER RESPONSIBILITY: This is a general specification guide, intended to be used by experienced construction professionals, in conjunction with good construction practice and professional judgment.

More information

Final inspections are completed by site visit only. Access to fenced yards shall be planned.

Final inspections are completed by site visit only. Access to fenced yards shall be planned. ROOFING RESIDENTIAL BUILDING INSPECTIONS DEPARTMENT www.ci.blaine.mn.us This handout is intended only as a guide and is based in part on the 2015 Minnesota State Building Code, Blaine City ordinances,

More information

Renovating Your Basement

Renovating Your Basement building science.com 2006 Building Science Press All rights of reproduction in any form reserved. Renovating Your Building America Report - 0309 2003 (revised 2007) Building Science Corporation Abstract:

More information

How To Repair A House

How To Repair A House Assessing Structural Damages Please note-this presentation is only intended to be used as a basic educational tool and is by no means all encompassing. Each property should be treated on a case by case

More information

Colorado State University. Durrell Center Roof Repair

Colorado State University. Durrell Center Roof Repair Colorado State University Durrell Center Roof Repair SPECIFICATION: POLYURETHANE FOAM ROOFING l.0 GENERAL REQUIREMENTS The successful application of a polyurethane foam roofing system is dependent upon

More information

How to Estimate the Cost of Interior Building Finishes from Schematic Drawings. CPE Candidate No. 0714108. December 2014

How to Estimate the Cost of Interior Building Finishes from Schematic Drawings. CPE Candidate No. 0714108. December 2014 How to Estimate the Cost of Interior Building Finishes from Schematic Drawings CPE Candidate No. 0714108 December 2014 1 How to Estimate the Cost of Interior Building Finishes from Schematic Drawings Table

More information

Housing Fact Sheets. Insulation Check-Up

Housing Fact Sheets. Insulation Check-Up Insulation Check-Up Housing Fact Sheets Introduction Heating and cooling account for the majority of energy costs in homes throughout the United States. Although current energy prices are relatively low,

More information

Georgia State University. Urban Life Building Roof Replacement

Georgia State University. Urban Life Building Roof Replacement ENGINEERING AND ENVIRONMENTAL 140 DECATUR STREET SE, ATLANTA, GA 30303 GEORGIA STATE UNIVERSITY - FACILITIES DESIGN & CONSTRUCTION 34 BROAD STREET, SUITE 100 ATLANTA, GA 30303 DRAWING INDEX A-0 PROJECT

More information

IMPROVEMENT COST ESTIMATE powered by HomeFixers

IMPROVEMENT COST ESTIMATE powered by HomeFixers IMPROVEMENT COST ESTIMATE powered by HomeFixers 123 Main St, Anytown, USA 12345 2000 SF $ 45,041.06 100.0% $22.52 per sq. ft. Stage 1: Pre-Construction $ 1,461.00 3.2% 1 House Secured $ 106.00 0.2% Lockbox

More information

CONSTRUCTION DETAILS & LOAD DESIGN CHARTS

CONSTRUCTION DETAILS & LOAD DESIGN CHARTS Office and Production 126 New Pace Rd., PO Box 279 Newcomerstown, OH 43832 1-800-446-2188, Fax: 740-498-4184 www.buildwithsips.com CONSTRUCTION DETAILS & LOAD DESIGN CHARTS Table of Contents Description

More information

Gramercy Place Condo Association, Inc.

Gramercy Place Condo Association, Inc. Gramercy Place Condo Association, Inc. UNIT MODIFICATION REQUEST Date of Application: Name of Owner (s): Telephone: (Home) (Cell) E-Mail: Anticipated start date: Anticipated ending date: Permission is

More information

VA25014B0516 VA CINCINNATI PROJECT NO. 539-328 INPATIENT BED TOWER ADDITION (4 TH AND 5 TH FLOORS) SECTION 09 29 00 GYPSUM BOARD

VA25014B0516 VA CINCINNATI PROJECT NO. 539-328 INPATIENT BED TOWER ADDITION (4 TH AND 5 TH FLOORS) SECTION 09 29 00 GYPSUM BOARD SECTION 09 29 00 GYPSUM BOARD PART 1 - GENERAL 1.1 DESCRIPTION This section specifies installation and finishing of gypsum board, vapor retarder and air and moisture barrrier. 1.2 RELATED WORK A. Installation

More information

City of St. Charles Basement Finish or Remodel

City of St. Charles Basement Finish or Remodel City of St. Charles Basement Finish or Remodel Building & Code Enforcement Division 2 East Main Street St. Charles IL 60174 630.377.4406 (Office) 630.443.4638 (Fax) http://www.stcharlesil.gov Please direct

More information

UPDATE October 8, 2012 Chicago Roofing Contractors Association CHICAGOLAND S ROOFING, INSULATION, AIR-BARRIER REQUIREMENTS

UPDATE October 8, 2012 Chicago Roofing Contractors Association CHICAGOLAND S ROOFING, INSULATION, AIR-BARRIER REQUIREMENTS UPDATE October 8, 2012 Chicago Roofing Contractors Association CHICAGOLAND S ROOFING, INSULATION, AIR-BARRIER REQUIREMENTS Executive Summary: There is a proposal at the Joint Committee on Administrative

More information

March 14, 2007. Installation of Bay, Bow and Garden Windows

March 14, 2007. Installation of Bay, Bow and Garden Windows March 14, 2007 Re: Installation of Bay, Bow and Garden Windows Attached are the Atrium Companies, Inc recommendation for the installation of bay, bow and garden windows. These instructions were developed

More information

AMERICAN GOTHIC PLAYHOUSE

AMERICAN GOTHIC PLAYHOUSE AMERICAN GOTHIC PLAYHOUSE Project Plan #856 Sheet 1 of 5 Pick a spot and get started with the beautiful that your kids will love. The design of the playhouse includes 35 square feet of interior space plus

More information

Single Family Residential Basement Finish

Single Family Residential Basement Finish How to Use This Guide Building Guide Pottawattamie County Planning & Development Department Building & Safety Division Single Family Residential Basement Finish Provide two (2) sets of plans and complete

More information

necessary for years of satisfactory service. SmartBlock insulating form concrete walls share the

necessary for years of satisfactory service. SmartBlock insulating form concrete walls share the Chapter 7 PLUMBING AND ELECTRICAL 7.1 Introduction to Plumbing and Electrical Consideration of support services such as plumbing and electrical systems from the preliminary schematics phase through final

More information

APPLICANT: ORANGE COUNTY, NEW YORK

APPLICANT: ORANGE COUNTY, NEW YORK Figure 1 Div 1 3 rd Flr Leakage in County Executives Office Figure 2 Div 1 3 rd Flr Location 067 approximately 2 SF of visible mold growth above entrance to Room 341 Figure 3 Div 1 3 rd Flr Location 067

More information

Skirt 1 / 4. The Skirt. The skirt patterns were downloaded from Mark's site but they need expanding before they can be used.

Skirt 1 / 4. The Skirt. The skirt patterns were downloaded from Mark's site but they need expanding before they can be used. Skirt 1 / 4 The Patterns The Skirt The skirt patterns were downloaded from Mark's site but they need expanding before they can be used. I used Corel Draw's real world dimensions to expand the patterns

More information

GreenGuard Housewrap Installation Guide

GreenGuard Housewrap Installation Guide 000768PACBPHW_Flashing Bro 5/23/03 2:52 PM Page 1 For the most current product information, go to www.green-guard.com. Pactiv Building Products believes the information and recommendations herein to be

More information

07 21 19 Guide Specification STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM

07 21 19 Guide Specification STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM 07 21 19 STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM 7819 Broadview Road Cleveland, OH 44131 800-522-4522 February, 2011 SPEC NOTE: This guide specification is intended for use when specifying

More information

EASY$ TIP SHEETS. Energy Advice Saving Yukoners Money

EASY$ TIP SHEETS. Energy Advice Saving Yukoners Money EASY$ TIP SHEETS Energy Advice Saving Yukoners Money Quick Links How to check for leaks Draftproofing products Sealants Draft proofing your home Draftproofing can be a cost-effective measure you take to

More information

CITY OF SELMA, TEXAS Inspection Checklist: Commercial

CITY OF SELMA, TEXAS Inspection Checklist: Commercial Rev Y71004 The Permits and Inspections Department welcomes you to the City of Selma. The following information is provided to you as guidance through the inspection process. The City of Selma provides

More information

High R-Value Does Not Always Mean High Performance

High R-Value Does Not Always Mean High Performance High R-Value Does Not Always Mean High Performance By Charlie Gohman, Building Science and Efficiency Manager, Energy Office, Arizona Department of Commerce Ever since the energy crisis of the 70s we have

More information

Basement & Foundation Damage

Basement & Foundation Damage Basement & Foundation Damage Please note-this presentation is only intended to be used as a basic educational tool and is by no means all encompassing. Each property should be treated on a case by case

More information

GHS Flood Final Report CTA Architects Engineers March 31, 2011

GHS Flood Final Report CTA Architects Engineers March 31, 2011 GHS Flood Final Report CTA Architects Engineers March 31, 2011 INTRODUCTION: Glacier High School underwent extensive flooding due to a broken frozen fire sprinkler joint of the ceiling in the Small Conference

More information

Preparation for 2015 Residential Code Changes Discussion with Local Builders and Designers

Preparation for 2015 Residential Code Changes Discussion with Local Builders and Designers City of Duluth Preparation for 2015 Residential Code Changes Discussion with Local Builders and Designers Thank you for taking the time to join us today. We know you are busy and your time is valuable.

More information

research highlight Highly Energy Efficient Building Envelope Retrofits for Houses

research highlight Highly Energy Efficient Building Envelope Retrofits for Houses research highlight June 2012 Technical Series 12-103 Highly Energy Efficient Building Envelope Retrofits for Houses introduction In Canada approximately 30% of all energy is consumed in buildings, with

More information

2015 1322) SIGNIFICANT CHANGES INCLUDING CODE COMMENTARY

2015 1322) SIGNIFICANT CHANGES INCLUDING CODE COMMENTARY MINNESOTA ENERGY CODE COMPLIANCE COLLABORATIVE 2015 Minnesota Residential Energy Code (MR 1322) SIGNIFICANT CHANGES INCLUDING CODE COMMENTARY (July 15, 2015 Update) Note: The following information contains

More information

*Trademark of The Dow Chemical Company A business unit of The Dow Chemical Company and its subsidiaries Copyright 2003 The Dow Chemical Company.

*Trademark of The Dow Chemical Company A business unit of The Dow Chemical Company and its subsidiaries Copyright 2003 The Dow Chemical Company. Dow Chemical is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned on completion of this program will be reported to CES Records for AIA members.

More information

How To Repair A Boat Landing Deck With A Boat Bed

How To Repair A Boat Landing Deck With A Boat Bed RESIDENTIAL INSULATED SHEATHING INSTALLATION GUIDE Residential Insulated Sheathing Installation Guide ROXUL COMFORTBOARD IS Table of Contents Slab-on-grade-to Above Grade Wall...1 Foundation Wall at Footing

More information

CHAPTER 7: Building Systems ROOFING SYSTEMS

CHAPTER 7: Building Systems ROOFING SYSTEMS ROOFING SYSTEMS Purpose Examples 1. Shingle roof system 2. Metal roof with blanket insulation 3. Metal roof with rigid insulation 4. Built-up asphalt roof system 5. Single-ply roof system 6. Modified Bitumen

More information

INSTALLATION OF A BAY WINDOW

INSTALLATION OF A BAY WINDOW INSTALLATION OF A BAY WINDOW Installation of a Bay Window These instructions relate to the replacement of an existing bay window or replacement of a straight window with a new bay window, in an opening

More information

Home Performance with ENERGY STAR. Evaluation Report

Home Performance with ENERGY STAR. Evaluation Report Home Performance with ENERGY STAR Customer Information Evaluation Report Customer Name: Sample Report 2 Address of Building: 123 Johnson Street Mailing Address: Same City: Madison State: WI Zip: 53704

More information

Flood-Damage Resistive Residential Envelope Systems. Ed Laatsch,, FEMA Robert Wendt, ORNL

Flood-Damage Resistive Residential Envelope Systems. Ed Laatsch,, FEMA Robert Wendt, ORNL Flood-Damage Resistive Residential Envelope Systems Ed Laatsch,, FEMA Robert Wendt, ORNL Floods have been a way of life in the U.S. (FEMA News Photo) They strike throughout the country - CA to FL, ND to

More information

Avoiding Air Barrier Pitfalls

Avoiding Air Barrier Pitfalls Avoiding Air Barrier Pitfalls Design & Durability November 2013 Air barriers, when correctly installed, help buildings achieve high levels of energy efficiency by decreasing heat loss. For example, great

More information

CLOSED CRAWLSPACES. Have you ever been in your crawlspace? If not, have you ever even

CLOSED CRAWLSPACES. Have you ever been in your crawlspace? If not, have you ever even CLOSED CRAWLSPACES What s In the Crawlspace? Wet Sagging Fiberglass Improper Drainage Have you ever been in your crawlspace? If not, have you ever even opened the door to look inside and see what it looked

More information

MUNICIPALITY OF THAMES CENTRE COMMUNITY SERVICES AND DEVELOPMENT RECREATION

MUNICIPALITY OF THAMES CENTRE COMMUNITY SERVICES AND DEVELOPMENT RECREATION REPORT NO. PR-019-15 MUNICIPALITY OF THAMES CENTRE COMMUNITY SERVICES AND DEVELOPMENT RECREATION TO: Mayor and Members of Council FROM: Liz Murray Recreation and Facilities Manager DATE: July 13, 2015

More information

Larry Haight's Residential Roofing Co, Inc 15203 NE 95th Street Redmond, Washington Phone: (425) 881-9771 Fax: (425) 869-1010

Larry Haight's Residential Roofing Co, Inc 15203 NE 95th Street Redmond, Washington Phone: (425) 881-9771 Fax: (425) 869-1010 Larry Haight's Residential Roofing Co, Inc 15203 NE 95th Street Redmond, Washington Phone: (425) 881-9771 Fax: (425) 869-1010 Custom bid generated for: Job site address: Lake Villas Condominium Attention:

More information

PDmB, Inc. Definitions

PDmB, Inc. Definitions Page 1 of 11 Definitions S Satisfactory Meets industry standards for proper material and installation NP Not Present Condition or item was not present at time of inspection NI Not Inspected Condition or

More information

ROOF CONDENSATION: A COSTLY PROBLEM

ROOF CONDENSATION: A COSTLY PROBLEM ROOF CONDENSATION: A COSTLY PROBLEM CONTENTS 1. What is it? 2. How does it form? 3. What to look for 4. Repair options 5. Owner responsibilities and proactive measures 1. WHAT IS IT? Roof condensation

More information

The Butler MR-24 Standing Seam Roof Difference. A comparison between metal roof systems

The Butler MR-24 Standing Seam Roof Difference. A comparison between metal roof systems The Butler MR-24 Standing Seam Roof Difference A comparison between metal roof systems Roof Systems Necessities Weathertight (don t leak!) Low maintenance Weathertightness Roof clips, seams, panel alignment

More information

C. Remove all existing asphalt shingles, underlayment and any loose debris into contractor provided dumpsters.

C. Remove all existing asphalt shingles, underlayment and any loose debris into contractor provided dumpsters. SCOPE OF WORK Project Title: Replace Deteriorated Roof Singles at Cape Lookout National Seashore Maintenance Shop PMIS # 159350 Prepared By: Mike Baker Cape Lookout National Seashore 131Charles St Harkers

More information

If you are a web registered user of ArlingontPermits.com you may also request an inspection at:

If you are a web registered user of ArlingontPermits.com you may also request an inspection at: TECHNICAL BULLETIN Community Development & Planning, Building Inspections TOPIC: Permits & Inspections for Roofing Replacement Effective November 1, 2011 Revised This Technical Bulletin will provide contractors

More information

Jagger Enterprises, Inc. dba Buckeye Home Inspections 17204 Dorchester Drive Cleveland OH 44119-1302 (216) 486-4663 Fax (216) 486-9922

Jagger Enterprises, Inc. dba Buckeye Home Inspections 17204 Dorchester Drive Cleveland OH 44119-1302 (216) 486-4663 Fax (216) 486-9922 Jagger Enterprises, Inc. dba Buckeye Home Inspections 17204 Dorchester Drive Cleveland OH 44119-1302 (216) 486-4663 Fax (216) 486-9922 November 09, 2002 Name deleted, Esq. address deleted Your client:

More information

Foundation. Foundation

Foundation. Foundation Moisture Aside from structural concerns, the most important consideration for foundation design is moisture. No client wants a wet basement. No client wants a damp basement. No client wants mold in their

More information

CHAPTER 5: INSULATION: MATERIALS AND TECHNIQUES

CHAPTER 5: INSULATION: MATERIALS AND TECHNIQUES Chapter 5: Insulation: Materials and Techniques 59 CHAPTER 5: INSULATION: MATERIALS AND TECHNIQUES An energy efficient building envelope contains both a thermal barrier and an air barrier. The key to an

More information

BASEMENT FINISH PERMIT AND BUILDING CODE REQUIREMENTS (REVISED 3/20/2009)

BASEMENT FINISH PERMIT AND BUILDING CODE REQUIREMENTS (REVISED 3/20/2009) BASEMENT FINISH PERMIT AND BUILDING CODE REQUIREMENTS (REVISED 3/20/2009) PERMIT SUBMITAL CHECKLIST: Signed and completed Building Permit application form. 2 Copies of plans showing proposed layout and

More information

SECTION 08 41 1 ALUMINUM FRAMED ENTRANCES and STOREFRONTS. System 402 Flush-Glazed Screw Spline Storefront

SECTION 08 41 1 ALUMINUM FRAMED ENTRANCES and STOREFRONTS. System 402 Flush-Glazed Screw Spline Storefront PART 1 GENERAL 1.01 Work Included SECTION 08 41 1 ALUMINUM FRAMED ENTRANCES and STOREFRONTS System 402 Flush-Glazed Screw Spline Storefront A. Furnish and install aluminum architectural storefront system

More information

How To Make A House Safe

How To Make A House Safe 1 RESIDENTIAL Screen Enclosures Orange County Residential Code Compliance Alternative design method for screen enclosures R301.2.1.1.3 PLAN REVIEW Engineered plans must state that the Alternative Design

More information

DIVISION: 07 00 00 THERMAL AND MOISTURE PROTECTION SECTION: 07 21 00 THERMAL INSULATION REPORT HOLDER: ICYNENE, INC.

DIVISION: 07 00 00 THERMAL AND MOISTURE PROTECTION SECTION: 07 21 00 THERMAL INSULATION REPORT HOLDER: ICYNENE, INC. 0 ICC-ES Report ICC-ES (800) 423-6587 (562) 699-0543 www.icc-es.org 000 Most Widely Accepted and Trusted ESR-1826 Reissued 02/2016 This report is subject to renewal 02/2018. DIVISION: 07 00 00 THERMAL

More information

1. Adhered KEE membrane roofing system. 2. Mechanically fastened KEE membrane roofing system.

1. Adhered KEE membrane roofing system. 2. Mechanically fastened KEE membrane roofing system. SECTION 075416 - PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Adhered KEE membrane roofing system. 2. Mechanically fastened KEE membrane roofing system. 1.2 PERFORMANCE REQUIREMENTS A. Solar Reflectance

More information

SECTION 07 61 13 STANDING SEAM METAL ROOFING

SECTION 07 61 13 STANDING SEAM METAL ROOFING SECTION 07 61 13 STANDING SEAM METAL ROOFING PART 1 GENERAL 1.01 SCOPE OF WORK A. The Work shall include all labor, materials, equipment and supervision required to complete the work of the above referenced

More information

TEXAS A&M CENTRAL ACADEMIC BUILDIING & PATRIOT S CASA SUBMITTAL. 23 21 13.19 Pre-Insulated Piping 4-8-13

TEXAS A&M CENTRAL ACADEMIC BUILDIING & PATRIOT S CASA SUBMITTAL. 23 21 13.19 Pre-Insulated Piping 4-8-13 TEXAS A&M CENTRAL ACADEMIC BUILDIING & PATRIOT S CASA SUBMITTAL 23 21 13.19 Pre-Insulated Piping 4-8-13 MATERIAL SUBMITTAL JOB NAME: TEXAS A&M SAN ANTONIO CENTRAL ACADEMIC BUILDING & PATRIOTS CASA CONTRACTOR:

More information

Building Condition Assessment Report

Building Condition Assessment Report C2 - Nurses Resident (aka Administration) Building Condition Assessment Report Asset Address Address Construction Year Size (Gross Floor Area) Asset Type Floors Above Ground Inspection Date C2 - Nurses

More information

ICC-ES Evaluation Report. ESR-3493 Reissued September 2014 This report is subject to renewal September 2015.

ICC-ES Evaluation Report. ESR-3493 Reissued September 2014 This report is subject to renewal September 2015. ICC-ES Evaluation Report www.icc-es.org (800) 423-6587 (562) 699-0543 ESR-3493 Reissued September 2014 This report is subject to renewal September 2015. A Subsidiary of the International Code Council DIVISION:

More information

STANDARD REQUIREMENTS FOR BONDING OR MECHANICAL ATTACHMENT OF INSULATION PANELS AND MECHANICAL ATTACHMENT OF ANCHOR AND/OR BASE SHEETS TO SUBSTRATES

STANDARD REQUIREMENTS FOR BONDING OR MECHANICAL ATTACHMENT OF INSULATION PANELS AND MECHANICAL ATTACHMENT OF ANCHOR AND/OR BASE SHEETS TO SUBSTRATES ROOFING APPLICATION STANDARD (RAS) No. 117 STANDARD REQUIREMENTS FOR BONDING OR MECHANICAL ATTACHMENT OF INSULATION PANELS AND MECHANICAL ATTACHMENT OF ANCHOR AND/OR BASE SHEETS TO SUBSTRATES Scope 1.1.

More information

INSTALLATION INSTRUCTIONS for Vinyl Windows with Integral Nailing Fin (JII001)

INSTALLATION INSTRUCTIONS for Vinyl Windows with Integral Nailing Fin (JII001) Thank you for selecting JELD-WEN products. Attached are JELD-WEN s recommended installation instructions for Vinyl windows with an integral nailing fin. While the use of these installation instructions

More information

Garden Window. Montecito Series Vinyl Garden Window Architectural Manual

Garden Window. Montecito Series Vinyl Garden Window Architectural Manual Montecito Series Vinyl The offers the outstanding insulating properties, low maintenance, and contemporary aesthetic appeal only vinyl can provide. Available in White and Tan homogenous window frames,

More information

bout your apartment SOLVING ODOUR TRANSFER PROBLEMS IN YOUR APARTMENT Understanding Air Movement in Your Building

bout your apartment SOLVING ODOUR TRANSFER PROBLEMS IN YOUR APARTMENT Understanding Air Movement in Your Building A bout your apartment SOLVING ODOUR TRANSFER PROBLEMS IN YOUR APARTMENT AE 1 One of the most common problems experienced by the occupants of apartment buildings is the transfer of objectionable odours

More information

The compliance of a roof to part of a new house at 28D Rata Street, Oxford, Waimakariri

The compliance of a roof to part of a new house at 28D Rata Street, Oxford, Waimakariri Determination 2009/103 The compliance of a roof to part of a new house at 28D Rata Street, Oxford, Waimakariri 1. The matters to be determined 1.1 This is a determination under Part 3 Subpart 1 of the

More information

Inspection Item COMMENTS

Inspection Item COMMENTS APPENDIX 9 AFFORDABLE HOUSING PROGRAM INSPECTION CHECKLIST Participating Jurisdiction: Homeowner Name: Assisted Property Address: Date of Physical Inspection of Property: Total Square Footage of Property:

More information

INSTALLATION RECOMMENDATIONS. Outdoor Rubber Tiles

INSTALLATION RECOMMENDATIONS. Outdoor Rubber Tiles INSTALLATION RECOMMENDATIONS Outdoor Rubber Tiles Prior to Installation: The Outdoor Rubber Tiles and accessory transition pieces intended for this installation have been shipped to you via a freight carrier

More information