REQUEST FOR BIDS Hillside Terrace Attic Air Sealing & Insulating Project
|
|
- Hilary Bates
- 7 years ago
- Views:
Transcription
1 March 2013 REQUEST FOR BIDS Hillside Terrace Attic Air Sealing & Insulating Project The Burlington Housing Authority (BHA) is inviting Contractors to submit Bids for the Attic Air Sealing and Insulating at Hillside Terrace, Burlington, VT. Hillside Terrace is comprised of 13 Duplex apartment Buildings totaling 26 apartments. Abbreviated Written Summary: Briefly and without force and effect upon the contract documents, the work of the Contract can be summarized as follows: Contractor shall provide all labor and materials to perform all work listed below: A. Air seal, insulate, repair gypsum board and remediate mold in 26 attic spaces as follows: REPLACEMENT LIGHTING: Provide a $13,000 allowance for the following Replacement Lighting Work: Replace 2 nd floor recessed closet lights with new surface mounted energy star rated light. Contractor shall remove existing recessed light, install new single gang box in ceiling and patch ceiling gypsum board around box, add texture and paint to match existing. New light will be chosen by BHA and wired and installed by contractor. Approx. Two (2) lights per apartment totaling Fifty Two (52) site wide. AIR SEALING: All air bypasses into the attic shall be sealed air tight. Attic air sealing must address all penetrations or wiring, plumbing vent stacks, attic hatches, surface mounted ceiling fixtures, recessed lighting fixtures, exhaust fan assemblies, chimney/flue chases, partition walls, exterior walls, merger walls between adjoining building sections, and all other miscellaneous penetrations. This shall be done be removing/pulling back existing insulation around all penetrations and treating each with an air sealing foam spray product. A single component low expansion polyurethane foam or a expanding, 2-part polyurethane foam is acceptable for sealing most penetrations. The foam shall be a Class 1 fire retardant, meeting ASTM E84 Surface Burning Characteristics. The foam shall be installed per manufacturer specifications. Seal with (Touch n Seal Quick Cure or (Touch n Seal FR Two Component Class 1 Fire Retardant Spray Foam. The exterior wall tops shall be sealed using an expanding, 2-part polyurethane foam,
2 sprayed on both outer and inner top plates. This includes both gable and eave edges of the building. The foam shall be a Class 1 fire retardant, meeting ASTM E84 Surface Burning Characteristics. The foam shall be installed per manufacturer specifications. Seal with (Touch n Seal FR Two Component Class 1 Fire Retardant Spray Foam. DAMS: A durable wooden plywood (5/8 thick min.) insulation dam shall be installed around all attic hatch openings. The dam must extend at least 2 higher than the settled insulation depth at the completion of the weatherization project. On the front of the buildings where the eaves extend beyond the top plates a durable wooden insulation dam shall be installed beyond the top plate to prevent insulation from getting into the eaves. ATTIC HATCH: Install 3-2 layers of XPS Rigid Foam Insulation (Extruded polystyrene) to the top of existing attic hatch panels and to each other with Loctite PL 300 VOC Foam Board Adhesive. Tape all edges of foam board with aluminum tape to cover all seams. Install a rubber compression gasket to the under side of the attic hatch to form an air seal when hatch is dropped into position. VENT EXTENSIONS: Install all new foam baffle vents. Each baffle must be installed in a manner that will protect the attic insulation from both intrusion and wind washing. This can be achieved by securely fastening the baffle to the underside of the roof and then either placing a piece of rigid foam board or rolled fiberglass beyond the exterior top plate. The foam board would be sealed in place at the edges with foam, and the fiberglass batt would be sprayed and covered with the 2-part foam while spraying the top plates. This will prevent wind wash and insulation from getting into the eaves. The perimeter top plates must still be sealed with a 2-part, closed cell foam. Vents must extend at least 2 higher than the settled insulation depth at the completion of the weatherization project. PERIMETER PULL: Any preexisting fiberglass batting shall be removed from within 4 feet of the perimeter of the attic. This insulation can be used to roll up and block soffits, or can be added on top of existing insulation in the center of the attic. Once the perimeter is cleared of fiberglass and all attic air sealing measures are complete and verified to be effective, blown-in insulation must be installed around the attic perimeter and over the fiberglass batting throughout the rest of the attic. INSULATION:
3 The minimum effective R-value at project completion shall be R-60. If roof clearance does not allow for an R-60, insulation must be added up to the roofline. All air sealing measures must be complete before installing new insulation. Existing conditions in buildings are 6-10 of various insulation (cellulose, fiberglass battings with cellulose, blown fiberglass). Install an average of 14 additional cellulose over existing insulation. PARTY WALLS: The party walls shall be drilled to accept an insulation blowing tube. Dense pack all party wall cavities with cellulose to a density of 3.5 pounds per cubic foot. This will provide insulation and reduce air infiltration within the cavity. Repair holes in gypsum board. CLOSET SLANTS: Each of the closets above the front entry way has a slanted ceiling. This slant is insulated with fiberglass batting. A rigid insulation blowing tube shall be pushed down the slant over the fiberglass batting to dense pack each cavity with cellulose. If vent baffles are existing in cavities, it is acceptable to block the airflow when dense packing with cellulose. BUMPOUTS: Front bump outs are open and accessible for work. Air seal any penetrations as normal. Dense pack accessible wall cavities. Once general air sealing and dense packing of walls is complete, cover cavity over bump out with a building wrap or 6 mil poly sheeting sealed at the edges with foam. The cover can be held in place by strapping. Dense pack the cavity through a hole in the cover, and seal hole with foam. Side bump outs will need to be accessed from either through the exterior siding or through the interior. These should dense packed with cellulose. Contractor has the option to perform this work from the interior or exterior. Interior or exterior building components damaged due to this work shall be restored to the exiting condition. Back bump outs are accessible from the attic, but with very little space due to the slope of the roof. As much effort to air seal using foam should be made. The best option here would be to dense pack the cavity from the attic.
4 MOLD REMEDIATION: Spray all visible mold located on roof decking and framing with Moldstat plus mold killer product per manufacturer s instructions. Black mold is visible in several attic areas with approx. square footage as follows: Apt #34 10 sq ft Apt #47 50 sq ft Apt #49 24 sq ft Apt # sq ft Apt #72 60 sq ft Apt #73 20 sq ft Apt #81 15 sq ft Apt # sq ft Apt #83 10 sq ft DRYWALL REPAIR: Patch all holes in attic party wall gypsum board created for the installation of blown cellulose in wall cavity. Re-tape (Fire Tape) all seams in attic party wall gypsum board that are failing. Approx. 48 linear ft. per apartment. Patch holes in gypsum board ceilings/walls in 2 nd floor closets due to the replacement of closet lighting. See Replacement Lighting above. Base Bid: Furnish all material, labor and equipment to perform all work in apartment attics as described above. Base Bid to include $13,000 lighting allowance. General Conditions Contractor is responsible to obtain and pay for all required Building Permits & Inspections. Note: Thirteen (13) separate Building Permits may be required for this project. Contractor is responsible to ensure areas under construction are controlled to ensure the safety of the residents. Contractor is responsible for the proper protection of all BHA/Tenant property. Any and all damage to said property shall be replaced at Contactors expense. All contractors will be required to supply proof of Workman s Comp and Employer s Liability Insurance. All Debris must be removed from premises at the end of each day. Working hours for this project shall be between 8am-4:30pm Monday thru Friday. Contractor shall submit a project schedule prior to beginning the project and work with BHA to coordinate access to apartments. Coordinate 48 Hours notice to access Apartments with BHA Staff. Contractor shall provide all electrical power required for the project utilizing generators. Contractor shall provide temporary toilet facilities.
5 Attention is called to: Attached HUD General Conditions for small construction/development contracts Attention is called to: Attached Section 3, Women & Minority Business Concern. Attention is called to: Attached Davis-Bacon Labor Standards and Wage Provisions. Contractor will be required to submit attached form: DOL WH 347-Payroll information. Additional forms may be required based on HUD Guidelines. Bids will be received at the offices of the BURLINGTON HOUSING AUTHORITY at 65 Main Street, Burlington, Vermont until March 26 th, A Pre-Bid Meeting will be held at 10am on Tuesday March 19th, 2013 at Hillside Terrace, Burlington, Vermont. BHA will meet contractors at the parking lot near the playground at which time bidders are invited to inspect some of the apartments and attic spaces. The BURLINGTON HOUSING AUTHORITY reserves the right to accept or reject any or all Proposals, or to waive informalities or minor irregularities in the bids received and to seek clarification of bid documents and pricing. Award of contract shall be made to the responsible bidder whose bid will be most advantageous to the Authority. The successful bidder will be required to provide an assurance of completion. No Proposal shall be withdrawn for a period of Thirty (30) days subsequent to the opening of bids without consent of the BURLINGTON HOUSING AUTHORITY. The successful bidder shall be prepared to start the work as soon as possible after the Notice to Proceed and complete the entire installation within 60 days. Inspection of the property may be arranged by appointment. Please contact John MacDonald at (802) , ext. 224 to schedule a date and time for a site visit and to study the Project requirements or John at jmacdonald@burlingtonhousing.org. Questions concerning this project shall be directed to the Burlington Housing Authority office at 65 Main Street, Burlington, Vermont. BURLINGTON HOUSING AUTHORITY Paul Dettman, Executive Director March 11, 2013
6
Envelope INSULATION BATT (2) Avoid Using Batt Insulation With Metal Framing. Pressure or Friction Fit
R-H-DI1 INSULATION BATT NR-E-IB1 Avoid Using Batt Insulation With Metal Framing Batt insulation should not be used with metal framing systems. Although it is common to see fiberglass batt insulation installed
More informationHome Energy Evaluation Report for Fritz Kreiss and Catherine McQueen
Home Energy Evaluation Report for Fritz Kreiss and Catherine McQueen May 2008 Wisconsin Area PO BOX 115 Lake Geneva, WI 53147 CELL (414) 550-4765 Home Performance with ENERGY STAR Evaluation Report Customer
More informationPreventing Ice Dams on Roofs
Preventing Ice Dams on Roofs Facility Manager November/December 2005 When a roof leaks, facility managers inevitably receive complaints from building occupants. If it is winter, ice dams are often the
More informationROOFS, SNOW AND ICE DAMS
ROOFS, SNOW AND ICE DAMS The Problem Ice dams are a common roof performance problem in cold climate buildings. Simply put, they are ridges of ice and icicles caused by melt water from further up the roof
More informationSigns of insulation problems In the winter. In the summer. conditioning system
about your house CE 19 While previous generations may have been content to live in drafty houses, most people now want comfortable warm houses. A healthy house today is well sealed, well insulated and
More informationAttic condensation during winter can
Housing Fact Sheet Causes and Cures of Attic Condensation and Roof Ice Damming Problems Attic condensation during winter can decrease the effectiveness of insulation and over time can cause significant
More informationThis sample quote was created using the JobFLEX Mobile App Learn More at www.job-flex.com
The Best Products The Best Price The Best Service...We Guarantee It! Prepared For: ABC Company 125 Maple St Rockford, MI 49341 Phone: 555.223.1245 Fax: 555.555.1234 Billing Address Phone: 566.563.5866
More informationWhitley Manufacturing Co., Inc. 201 W. First Street S. Whitley, IN 46787 Phone (260) 723-5131 Sales Fax (260) 723-6396 whitley@whitleyman.
Building Type Building Code Whitley Classroom Buildings BOCA, UBC, SBCCI, NEC, ADA Structural Support Outrigger construction standard, Whitley model classrooms. Main support beams to be 12 11.8# per lineal
More informationAdditions and Alterations
Additions and Alterations Addition and alteration construction is a miscellaneous grouping of home improvement and renovation projects that are generally geared toward the enhancement of an existing principal
More informationAll bidders shall indicate in their bid/proposal that this Addendum has been received and considered in their bid proposal.
Addendum #1 Fire Damage Repairs 4316 City View Terrace, Units A and B City View Terrace, OH5-13C, AMP 4 IFB #14-03 October 23, 2014 Greater Dayton Premier Management 400 Wayne Ave. Dayton, Ohio 45410 This
More informationRehab Inspection Report Page 1
Rehab Inspection Report Page 1 Home Address: Construction Style: Number of bedrooms Square footage: Value of offer: Estimated rehab cost: Value of resale: Orientation of house: N S E W Note: orientation
More informationThis handout is a guide only and does not contain all of the requirements of the Minnesota State Building Code or city ordinances.
Basement Finishing Guide Community Development Department Building Inspections Division 5200 85 th Avenue North / Brooklyn Park, MN 55443 Phone: (763) 488-6379 / Fax: (763) 493-8171 6/15 www.brooklynpark.org
More informationInsulation R-Value Comparisons
Insulation R-Value Comparisons American Ingenuity s component panels for the 22 48 domes contains seven inch thick rigid Expanded Polystyrene (E.P.S.) insulation which has an R value of 28. American Ingenuity
More informationSeptember 3, 2009. Ric Boyd, Public Works Director Ketchikan Gateway Borough 344 Front St. Ketchikan, AK 99901
September 3, 2009 Ric Boyd, Public Works Director Ketchikan Gateway Borough 344 Front St. Ketchikan, AK 99901 RE: Ketchikan Gateway Borough Gateway Recreation Center Roof Observations and Intrusive Inspections
More informationBest Basement Water Management Practices
Best Basement Water Management Practices Guide written by Patrick Sluss Sluss Construction (330) 224 5394 When a home owner is faced with a leaking basement there is a way to correct the problem and a
More informationsolutions & tips six Wise Energy Guide Building envelope solutions and simple tips AIR SEALING
Wise Energy Guide solutions & tips 32 AIR SEALING Is your house leaking money? six Building envelope solutions and simple tips If your home is like most, the greatest amount of heat loss is from air leakage;
More informationSTAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM
STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM Installed in Pre-engineered Steel Buildings Provides Lowest Cost Construction Method for CORROSIVE AND WET Environments PREFERRED SOLUTIONS, INC.
More informationRESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000
RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000 SECTION R905 REQUIREMENTS FOR ROOF COVERINGS R905.1 Roof covering application. Roof coverings
More informationRetrofitting an Insulated Cold Roof
Retrofitting an Insulated Cold Roof As a metal-roofing contractor in the Upper Peninsula of Michigan, I am frequently asked to fix roof leaks that have less to do with roofing than with the way poorly
More informationEcoTouch Insulation with PureFiber Technology
PROJECT ENGINEER RESPONSIBILITY: This is a general specification guide, intended to be used by experienced construction professionals, in conjunction with good construction practice and professional judgment.
More informationDEFAULT HEAT LOSS COEFFICIENTS
DEFAULT HEAT LOSS COEFFICIENTS SECTION A101 GENERAL REQUIREMENTS A101.1 Scope. The following defaults shall apply to Chapter 4 of both the (RE) and (CE) sections of the IECC. This chapter includes tables
More informationHVAC INSTALLATION. Success with 2015 IECC Northeast & Mid-Atlantic. Checklist for Builders & Trades
Success with 2015 IECC Northeast & Mid-Atlantic Checklist for Builders & Trades COPYRIGHT 2015 ADVANCED ENERGY. ALL RIGHTS RESERVED TEMPLATE 2015.1.0 PAGE 1 CHECKLIST: JOB READY 1. 2. 3. 4. 5. 6. 7. 8.
More informationManaging Trade Contractors for High Performance Homes. Carl Seville
Managing Trade Contractors for High Performance Homes Carl Seville Overview Implementing Management Systems Why How Steps Troubleshooting Successes High Performance Buildings Attention to detail Management
More informationATTIC BYPASSES HOME ENERGY GUIDE
HOME ENERGY GUIDE TECHNIQUES TACTICS & TIPS How to locate attic bypasses Common bypasses and how to fix them Attic bypasses are hidden air passageways that lead from the heated space into the attic. Because
More informationfirst look at GigaCrete s revolutionary new New Construction GigaHouse GigaHouse Utilizing GigaPanel
first look at GigaCrete s revolutionary new New Construction GigaHouse GigaHouse Utilizing GigaPanel What is GigaCrete GigaCrete is a family of products based on low carbon footprint Green ceramic binders
More informationMinimizing Water Intrusion Through Roof Vents in High-Wind Regions
Minimizing Water Intrusion Through Roof Vents in High-Wind Regions http://www.fema.gov HURRICANE IKE RECOVERY ADVISORY Purpose: To recommend practices for minimizing water intrusion through roof vent systems
More informationabout your house Attic Venting, Attic Moisture, and Ice Dams Figure 1 Typical attic floor insulations
about your house CE 13 Attic Venting, Attic Moisture, and Ice Dams It is rare for Canadians to visit their attics. For many years building codes have required high levels of attic insulation, making attics
More informationPANELIZED HOME INSTALLATION GUIDELINE
PANELIZED HOME INSTALLATION GUIDELINE A typical home package will be constructed of Snap-N-Lock Insulated Panels clad with steel skins. 4" panels will be used for the walls, and 6" panels for the roof.
More informationAir Conditioner Duct Construction & Repair
PROPER ROOF AIR CONDITIONER MOUNTING At Newmar, there are two different models of air conditioners available on all towable and motorized units. The different models are the Dometic Brisk and Penguin models,
More informationENERGY STAR Qualified New Homes Thermal Enclosure Checklist. Water Management Checklist. Eli Caudill
ENERGY STAR Qualified New Homes Thermal Enclosure Checklist & Water Management Checklist Eli Caudill ENERGY STAR Version 3 Tighter Standards Whole Home Approach Better, More Sustainable Construction Surpasses
More informationAsphalt Shingle Application Requirements
Alberta Allied Roofing Association Asphalt Shingle Application Requirements Section 1 Roof Decks 1.1 General Asphalt Shingles are not permitted to be installed directly over rigid insulation. When Asphalt
More informationA D D E N D U M # 3 QUESTIONS FROM BIDDERS: DATE: November 5, 2012. All Bidders. Jenne dos Santos, CBI Consulting Inc. City of Chelsea, MA
Page 1 of 10, Addendum No. 3 Temporary Garage Structure City of Chelsea, MA November 5, 2012 CBI Job No.: 12055-A A D D E N D U M # 3 DATE: November 5, 2012 TO: FROM: PROJECT: All Bidders Jenne dos Santos,
More informationNRDCA 400 GUIDELINE FOR FIELD APPLICATION of LIGHTWEIGHT INSULATING CONCRETE REROOFING/RECOVER SYSTEMS
NRDCA 400 GUIDELINE FOR FIELD APPLICATION of LIGHTWEIGHT INSULATING CONCRETE REROOFING/RECOVER SYSTEMS The (NRDCA) has prepared this document to provide customers and installers information that the industry
More informationATTIC AIR LEAKS & ICE DAMS
HOME ENERGY GUIDE TECHNIQUES TACTICS & TIPS How to locate attic air leaks Common air leaks and how to fix them ATTIC AIR LEAKS & ICE DAMS Minnesota Department of Commerce Energy Information Center Ice
More informationHVAC INSTALLATION SUCCESS WITH 2012 IECC DELAWARE. for Builders & Trades. Recommended Practices for Optimized Energy Savings
SUCCESS WITH 2012 IECC DELAWARE Recommended Practices for Optimized Energy Savings for Builders & Trades COPYRIGHT 2015 ADVANCED ENERGY. ALL RIGHTS RESERVED VERSION 2015.1.0 CHECKLIST: JOB READY 1. 2.
More informationCITY OF WHITE BEAR LAKE BUILDING INSPECTION DEPARTMENT 4701 Highway 61 White Bear Lake, MN 55110 Fax: 651-429-8503. Re-Roofing: Asphalt Shingles
CITY OF WHITE BEAR LAKE BUILDING INSPECTION DEPARTMENT 4701 Highway 61 White Bear Lake, MN 55110 Fax: 651-429-8503 Re-Roofing: Asphalt Shingles This is a summary of the standard requirements based on the
More informationFiberglas, Exterior Wall Thermal Insulation
PROJECT ENGINEER RESPONSIBILITY: This is a general specification guide, intended to be used by experienced construction professionals, in conjunction with good construction practice and professional judgment.
More informationFinal inspections are completed by site visit only. Access to fenced yards shall be planned.
ROOFING RESIDENTIAL BUILDING INSPECTIONS DEPARTMENT www.ci.blaine.mn.us This handout is intended only as a guide and is based in part on the 2015 Minnesota State Building Code, Blaine City ordinances,
More informationRenovating Your Basement
building science.com 2006 Building Science Press All rights of reproduction in any form reserved. Renovating Your Building America Report - 0309 2003 (revised 2007) Building Science Corporation Abstract:
More informationHow To Repair A House
Assessing Structural Damages Please note-this presentation is only intended to be used as a basic educational tool and is by no means all encompassing. Each property should be treated on a case by case
More informationColorado State University. Durrell Center Roof Repair
Colorado State University Durrell Center Roof Repair SPECIFICATION: POLYURETHANE FOAM ROOFING l.0 GENERAL REQUIREMENTS The successful application of a polyurethane foam roofing system is dependent upon
More informationHow to Estimate the Cost of Interior Building Finishes from Schematic Drawings. CPE Candidate No. 0714108. December 2014
How to Estimate the Cost of Interior Building Finishes from Schematic Drawings CPE Candidate No. 0714108 December 2014 1 How to Estimate the Cost of Interior Building Finishes from Schematic Drawings Table
More informationHousing Fact Sheets. Insulation Check-Up
Insulation Check-Up Housing Fact Sheets Introduction Heating and cooling account for the majority of energy costs in homes throughout the United States. Although current energy prices are relatively low,
More informationGeorgia State University. Urban Life Building Roof Replacement
ENGINEERING AND ENVIRONMENTAL 140 DECATUR STREET SE, ATLANTA, GA 30303 GEORGIA STATE UNIVERSITY - FACILITIES DESIGN & CONSTRUCTION 34 BROAD STREET, SUITE 100 ATLANTA, GA 30303 DRAWING INDEX A-0 PROJECT
More informationIMPROVEMENT COST ESTIMATE powered by HomeFixers
IMPROVEMENT COST ESTIMATE powered by HomeFixers 123 Main St, Anytown, USA 12345 2000 SF $ 45,041.06 100.0% $22.52 per sq. ft. Stage 1: Pre-Construction $ 1,461.00 3.2% 1 House Secured $ 106.00 0.2% Lockbox
More informationCONSTRUCTION DETAILS & LOAD DESIGN CHARTS
Office and Production 126 New Pace Rd., PO Box 279 Newcomerstown, OH 43832 1-800-446-2188, Fax: 740-498-4184 www.buildwithsips.com CONSTRUCTION DETAILS & LOAD DESIGN CHARTS Table of Contents Description
More informationGramercy Place Condo Association, Inc.
Gramercy Place Condo Association, Inc. UNIT MODIFICATION REQUEST Date of Application: Name of Owner (s): Telephone: (Home) (Cell) E-Mail: Anticipated start date: Anticipated ending date: Permission is
More informationVA25014B0516 VA CINCINNATI PROJECT NO. 539-328 INPATIENT BED TOWER ADDITION (4 TH AND 5 TH FLOORS) SECTION 09 29 00 GYPSUM BOARD
SECTION 09 29 00 GYPSUM BOARD PART 1 - GENERAL 1.1 DESCRIPTION This section specifies installation and finishing of gypsum board, vapor retarder and air and moisture barrrier. 1.2 RELATED WORK A. Installation
More informationCity of St. Charles Basement Finish or Remodel
City of St. Charles Basement Finish or Remodel Building & Code Enforcement Division 2 East Main Street St. Charles IL 60174 630.377.4406 (Office) 630.443.4638 (Fax) http://www.stcharlesil.gov Please direct
More informationUPDATE October 8, 2012 Chicago Roofing Contractors Association CHICAGOLAND S ROOFING, INSULATION, AIR-BARRIER REQUIREMENTS
UPDATE October 8, 2012 Chicago Roofing Contractors Association CHICAGOLAND S ROOFING, INSULATION, AIR-BARRIER REQUIREMENTS Executive Summary: There is a proposal at the Joint Committee on Administrative
More informationMarch 14, 2007. Installation of Bay, Bow and Garden Windows
March 14, 2007 Re: Installation of Bay, Bow and Garden Windows Attached are the Atrium Companies, Inc recommendation for the installation of bay, bow and garden windows. These instructions were developed
More informationAMERICAN GOTHIC PLAYHOUSE
AMERICAN GOTHIC PLAYHOUSE Project Plan #856 Sheet 1 of 5 Pick a spot and get started with the beautiful that your kids will love. The design of the playhouse includes 35 square feet of interior space plus
More informationSingle Family Residential Basement Finish
How to Use This Guide Building Guide Pottawattamie County Planning & Development Department Building & Safety Division Single Family Residential Basement Finish Provide two (2) sets of plans and complete
More informationnecessary for years of satisfactory service. SmartBlock insulating form concrete walls share the
Chapter 7 PLUMBING AND ELECTRICAL 7.1 Introduction to Plumbing and Electrical Consideration of support services such as plumbing and electrical systems from the preliminary schematics phase through final
More informationAPPLICANT: ORANGE COUNTY, NEW YORK
Figure 1 Div 1 3 rd Flr Leakage in County Executives Office Figure 2 Div 1 3 rd Flr Location 067 approximately 2 SF of visible mold growth above entrance to Room 341 Figure 3 Div 1 3 rd Flr Location 067
More informationSkirt 1 / 4. The Skirt. The skirt patterns were downloaded from Mark's site but they need expanding before they can be used.
Skirt 1 / 4 The Patterns The Skirt The skirt patterns were downloaded from Mark's site but they need expanding before they can be used. I used Corel Draw's real world dimensions to expand the patterns
More informationGreenGuard Housewrap Installation Guide
000768PACBPHW_Flashing Bro 5/23/03 2:52 PM Page 1 For the most current product information, go to www.green-guard.com. Pactiv Building Products believes the information and recommendations herein to be
More information07 21 19 Guide Specification STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM
07 21 19 STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM 7819 Broadview Road Cleveland, OH 44131 800-522-4522 February, 2011 SPEC NOTE: This guide specification is intended for use when specifying
More informationEASY$ TIP SHEETS. Energy Advice Saving Yukoners Money
EASY$ TIP SHEETS Energy Advice Saving Yukoners Money Quick Links How to check for leaks Draftproofing products Sealants Draft proofing your home Draftproofing can be a cost-effective measure you take to
More informationCITY OF SELMA, TEXAS Inspection Checklist: Commercial
Rev Y71004 The Permits and Inspections Department welcomes you to the City of Selma. The following information is provided to you as guidance through the inspection process. The City of Selma provides
More informationHigh R-Value Does Not Always Mean High Performance
High R-Value Does Not Always Mean High Performance By Charlie Gohman, Building Science and Efficiency Manager, Energy Office, Arizona Department of Commerce Ever since the energy crisis of the 70s we have
More informationBasement & Foundation Damage
Basement & Foundation Damage Please note-this presentation is only intended to be used as a basic educational tool and is by no means all encompassing. Each property should be treated on a case by case
More informationGHS Flood Final Report CTA Architects Engineers March 31, 2011
GHS Flood Final Report CTA Architects Engineers March 31, 2011 INTRODUCTION: Glacier High School underwent extensive flooding due to a broken frozen fire sprinkler joint of the ceiling in the Small Conference
More informationPreparation for 2015 Residential Code Changes Discussion with Local Builders and Designers
City of Duluth Preparation for 2015 Residential Code Changes Discussion with Local Builders and Designers Thank you for taking the time to join us today. We know you are busy and your time is valuable.
More informationresearch highlight Highly Energy Efficient Building Envelope Retrofits for Houses
research highlight June 2012 Technical Series 12-103 Highly Energy Efficient Building Envelope Retrofits for Houses introduction In Canada approximately 30% of all energy is consumed in buildings, with
More information2015 1322) SIGNIFICANT CHANGES INCLUDING CODE COMMENTARY
MINNESOTA ENERGY CODE COMPLIANCE COLLABORATIVE 2015 Minnesota Residential Energy Code (MR 1322) SIGNIFICANT CHANGES INCLUDING CODE COMMENTARY (July 15, 2015 Update) Note: The following information contains
More information*Trademark of The Dow Chemical Company A business unit of The Dow Chemical Company and its subsidiaries Copyright 2003 The Dow Chemical Company.
Dow Chemical is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned on completion of this program will be reported to CES Records for AIA members.
More informationHow To Repair A Boat Landing Deck With A Boat Bed
RESIDENTIAL INSULATED SHEATHING INSTALLATION GUIDE Residential Insulated Sheathing Installation Guide ROXUL COMFORTBOARD IS Table of Contents Slab-on-grade-to Above Grade Wall...1 Foundation Wall at Footing
More informationCHAPTER 7: Building Systems ROOFING SYSTEMS
ROOFING SYSTEMS Purpose Examples 1. Shingle roof system 2. Metal roof with blanket insulation 3. Metal roof with rigid insulation 4. Built-up asphalt roof system 5. Single-ply roof system 6. Modified Bitumen
More informationINSTALLATION OF A BAY WINDOW
INSTALLATION OF A BAY WINDOW Installation of a Bay Window These instructions relate to the replacement of an existing bay window or replacement of a straight window with a new bay window, in an opening
More informationHome Performance with ENERGY STAR. Evaluation Report
Home Performance with ENERGY STAR Customer Information Evaluation Report Customer Name: Sample Report 2 Address of Building: 123 Johnson Street Mailing Address: Same City: Madison State: WI Zip: 53704
More informationFlood-Damage Resistive Residential Envelope Systems. Ed Laatsch,, FEMA Robert Wendt, ORNL
Flood-Damage Resistive Residential Envelope Systems Ed Laatsch,, FEMA Robert Wendt, ORNL Floods have been a way of life in the U.S. (FEMA News Photo) They strike throughout the country - CA to FL, ND to
More informationAvoiding Air Barrier Pitfalls
Avoiding Air Barrier Pitfalls Design & Durability November 2013 Air barriers, when correctly installed, help buildings achieve high levels of energy efficiency by decreasing heat loss. For example, great
More informationCLOSED CRAWLSPACES. Have you ever been in your crawlspace? If not, have you ever even
CLOSED CRAWLSPACES What s In the Crawlspace? Wet Sagging Fiberglass Improper Drainage Have you ever been in your crawlspace? If not, have you ever even opened the door to look inside and see what it looked
More informationMUNICIPALITY OF THAMES CENTRE COMMUNITY SERVICES AND DEVELOPMENT RECREATION
REPORT NO. PR-019-15 MUNICIPALITY OF THAMES CENTRE COMMUNITY SERVICES AND DEVELOPMENT RECREATION TO: Mayor and Members of Council FROM: Liz Murray Recreation and Facilities Manager DATE: July 13, 2015
More informationLarry Haight's Residential Roofing Co, Inc 15203 NE 95th Street Redmond, Washington Phone: (425) 881-9771 Fax: (425) 869-1010
Larry Haight's Residential Roofing Co, Inc 15203 NE 95th Street Redmond, Washington Phone: (425) 881-9771 Fax: (425) 869-1010 Custom bid generated for: Job site address: Lake Villas Condominium Attention:
More informationPDmB, Inc. Definitions
Page 1 of 11 Definitions S Satisfactory Meets industry standards for proper material and installation NP Not Present Condition or item was not present at time of inspection NI Not Inspected Condition or
More informationROOF CONDENSATION: A COSTLY PROBLEM
ROOF CONDENSATION: A COSTLY PROBLEM CONTENTS 1. What is it? 2. How does it form? 3. What to look for 4. Repair options 5. Owner responsibilities and proactive measures 1. WHAT IS IT? Roof condensation
More informationThe Butler MR-24 Standing Seam Roof Difference. A comparison between metal roof systems
The Butler MR-24 Standing Seam Roof Difference A comparison between metal roof systems Roof Systems Necessities Weathertight (don t leak!) Low maintenance Weathertightness Roof clips, seams, panel alignment
More informationC. Remove all existing asphalt shingles, underlayment and any loose debris into contractor provided dumpsters.
SCOPE OF WORK Project Title: Replace Deteriorated Roof Singles at Cape Lookout National Seashore Maintenance Shop PMIS # 159350 Prepared By: Mike Baker Cape Lookout National Seashore 131Charles St Harkers
More informationIf you are a web registered user of ArlingontPermits.com you may also request an inspection at:
TECHNICAL BULLETIN Community Development & Planning, Building Inspections TOPIC: Permits & Inspections for Roofing Replacement Effective November 1, 2011 Revised This Technical Bulletin will provide contractors
More informationJagger Enterprises, Inc. dba Buckeye Home Inspections 17204 Dorchester Drive Cleveland OH 44119-1302 (216) 486-4663 Fax (216) 486-9922
Jagger Enterprises, Inc. dba Buckeye Home Inspections 17204 Dorchester Drive Cleveland OH 44119-1302 (216) 486-4663 Fax (216) 486-9922 November 09, 2002 Name deleted, Esq. address deleted Your client:
More informationFoundation. Foundation
Moisture Aside from structural concerns, the most important consideration for foundation design is moisture. No client wants a wet basement. No client wants a damp basement. No client wants mold in their
More informationCHAPTER 5: INSULATION: MATERIALS AND TECHNIQUES
Chapter 5: Insulation: Materials and Techniques 59 CHAPTER 5: INSULATION: MATERIALS AND TECHNIQUES An energy efficient building envelope contains both a thermal barrier and an air barrier. The key to an
More informationBASEMENT FINISH PERMIT AND BUILDING CODE REQUIREMENTS (REVISED 3/20/2009)
BASEMENT FINISH PERMIT AND BUILDING CODE REQUIREMENTS (REVISED 3/20/2009) PERMIT SUBMITAL CHECKLIST: Signed and completed Building Permit application form. 2 Copies of plans showing proposed layout and
More informationSECTION 08 41 1 ALUMINUM FRAMED ENTRANCES and STOREFRONTS. System 402 Flush-Glazed Screw Spline Storefront
PART 1 GENERAL 1.01 Work Included SECTION 08 41 1 ALUMINUM FRAMED ENTRANCES and STOREFRONTS System 402 Flush-Glazed Screw Spline Storefront A. Furnish and install aluminum architectural storefront system
More informationHow To Make A House Safe
1 RESIDENTIAL Screen Enclosures Orange County Residential Code Compliance Alternative design method for screen enclosures R301.2.1.1.3 PLAN REVIEW Engineered plans must state that the Alternative Design
More informationDIVISION: 07 00 00 THERMAL AND MOISTURE PROTECTION SECTION: 07 21 00 THERMAL INSULATION REPORT HOLDER: ICYNENE, INC.
0 ICC-ES Report ICC-ES (800) 423-6587 (562) 699-0543 www.icc-es.org 000 Most Widely Accepted and Trusted ESR-1826 Reissued 02/2016 This report is subject to renewal 02/2018. DIVISION: 07 00 00 THERMAL
More information1. Adhered KEE membrane roofing system. 2. Mechanically fastened KEE membrane roofing system.
SECTION 075416 - PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Adhered KEE membrane roofing system. 2. Mechanically fastened KEE membrane roofing system. 1.2 PERFORMANCE REQUIREMENTS A. Solar Reflectance
More informationSECTION 07 61 13 STANDING SEAM METAL ROOFING
SECTION 07 61 13 STANDING SEAM METAL ROOFING PART 1 GENERAL 1.01 SCOPE OF WORK A. The Work shall include all labor, materials, equipment and supervision required to complete the work of the above referenced
More informationTEXAS A&M CENTRAL ACADEMIC BUILDIING & PATRIOT S CASA SUBMITTAL. 23 21 13.19 Pre-Insulated Piping 4-8-13
TEXAS A&M CENTRAL ACADEMIC BUILDIING & PATRIOT S CASA SUBMITTAL 23 21 13.19 Pre-Insulated Piping 4-8-13 MATERIAL SUBMITTAL JOB NAME: TEXAS A&M SAN ANTONIO CENTRAL ACADEMIC BUILDING & PATRIOTS CASA CONTRACTOR:
More informationBuilding Condition Assessment Report
C2 - Nurses Resident (aka Administration) Building Condition Assessment Report Asset Address Address Construction Year Size (Gross Floor Area) Asset Type Floors Above Ground Inspection Date C2 - Nurses
More informationICC-ES Evaluation Report. ESR-3493 Reissued September 2014 This report is subject to renewal September 2015.
ICC-ES Evaluation Report www.icc-es.org (800) 423-6587 (562) 699-0543 ESR-3493 Reissued September 2014 This report is subject to renewal September 2015. A Subsidiary of the International Code Council DIVISION:
More informationSTANDARD REQUIREMENTS FOR BONDING OR MECHANICAL ATTACHMENT OF INSULATION PANELS AND MECHANICAL ATTACHMENT OF ANCHOR AND/OR BASE SHEETS TO SUBSTRATES
ROOFING APPLICATION STANDARD (RAS) No. 117 STANDARD REQUIREMENTS FOR BONDING OR MECHANICAL ATTACHMENT OF INSULATION PANELS AND MECHANICAL ATTACHMENT OF ANCHOR AND/OR BASE SHEETS TO SUBSTRATES Scope 1.1.
More informationINSTALLATION INSTRUCTIONS for Vinyl Windows with Integral Nailing Fin (JII001)
Thank you for selecting JELD-WEN products. Attached are JELD-WEN s recommended installation instructions for Vinyl windows with an integral nailing fin. While the use of these installation instructions
More informationGarden Window. Montecito Series Vinyl Garden Window Architectural Manual
Montecito Series Vinyl The offers the outstanding insulating properties, low maintenance, and contemporary aesthetic appeal only vinyl can provide. Available in White and Tan homogenous window frames,
More informationbout your apartment SOLVING ODOUR TRANSFER PROBLEMS IN YOUR APARTMENT Understanding Air Movement in Your Building
A bout your apartment SOLVING ODOUR TRANSFER PROBLEMS IN YOUR APARTMENT AE 1 One of the most common problems experienced by the occupants of apartment buildings is the transfer of objectionable odours
More informationThe compliance of a roof to part of a new house at 28D Rata Street, Oxford, Waimakariri
Determination 2009/103 The compliance of a roof to part of a new house at 28D Rata Street, Oxford, Waimakariri 1. The matters to be determined 1.1 This is a determination under Part 3 Subpart 1 of the
More informationInspection Item COMMENTS
APPENDIX 9 AFFORDABLE HOUSING PROGRAM INSPECTION CHECKLIST Participating Jurisdiction: Homeowner Name: Assisted Property Address: Date of Physical Inspection of Property: Total Square Footage of Property:
More informationINSTALLATION RECOMMENDATIONS. Outdoor Rubber Tiles
INSTALLATION RECOMMENDATIONS Outdoor Rubber Tiles Prior to Installation: The Outdoor Rubber Tiles and accessory transition pieces intended for this installation have been shipped to you via a freight carrier
More information