H Unit Input/Output Manual

Save this PDF as:
 WORD  PNG  TXT  JPG

Size: px
Start display at page:

Download "H Unit Input/Output Manual"

Transcription

1 H Unit Input/Output Manual 4 INPUTS 4 OUTPUTS RS485

2 Table of Contents Safety Rules...Inside Front Cover. Introduction...IFC 2. Communications...IFC 2.2 Baud Rate...IFC 2.3 Modbus Address Speed of Response Communications Failure Programming Communications Settings HUIO Configuration Setting Up the Inputs Setting Up the Outputs Input Specifications Output Specifications Power and Communications Connections Quick Setup Diagnostic Monitor INTRODUCTION The HUIO module is designed to connect to an H- panel (ONLY) and expand it s input and output capability. Each HUIO module has four (4) inputs and four (4) outputs. Up to four (4) modules can be attached to the H-panel to give a total of 6 additional inputs and 6 additional outputs. The state of the output relays can be seen on the PCB Led s -4. The additional Input/Output will appear to be a continuation of the existing Input/Output and will adopt all of it s properties such as channel naming, alarms, ILC visibility etc. The HUIO will connect to an H-panel via the simple 3-wire RS485 interface along with other peripherals such as HTS Transfer Switches, Remote Annunciators and Remote Relay panels. Because we are using RS485, the HUIO can be located up to 4000 feet away from the H-panel (depending on site and configuration). 2. COMMUNICATIONS The HUIO will connect onto the RS485 bus as a Modbus slave, along with any optional HTS units and remote annunciators/remote relay boards. 2.2 BAUD RATE The following baud rates are available , 9600, 38400, The baud rate for the RS485 port is set on the H-panel. At power up, the HUIO module will automatically search for the correct baud rate. If no good communications are received within three seconds, the HUIO will change it s baud rate on a cyclical basis. The baud rate search starts at 4800 baud. Once good communications are established, the baud rate will be held for two time-out periods even if the communications go bad. This is to prevent minor noise from causing the baud rate to cycle. Similarly outputs are disabled after one or two timeout periods depending if communications were ever established. The baud rate does not affect the speed of response (see section "Speed of Response").

3 2.3 MODBUS ADDRESS Each HUIO has base Modbus address of 230 plus a unique address which is set by two dip switches on the module (see Table ), giving a total of four possible options The H-panel has to be programmed via Genlink (NOT THE FRONT PANEL) as to which modules are connected (which addresses are in service), i.e. it is not plug and play. The reason for this is that the H-panel would need to continually search for each unit, and each unit would be adjusting it s baud rate every three seconds. With the combination of time-outs and slow loop times, the bus would become sluggish, the baud rate continually changing, and we may never achieve a connection. Input and output designation is fixed by module address: Table ADDRESS SW SW Contains inputs 2-5 and outputs Contains inputs 6-9 and outputs Contains inputs and outputs Contains inputs and outputs SPEED OF RESPONSE HUIO s are serviced cyclically with two messages (read and write) sent to each connected HUIO in turn. The message length is very small so the speed of response is not affected by the baud rate. For example four units require eight messages. Each message is separated from the next by 300ms so each HUIO requires 600ms to be serviced. This results in a response time roughly equal to: 600ms * number of HUIO s Thus the worst case response time after the auto baud rate algorithm has established a connection is: 600ms * 4 = 2.4 seconds Any time critical Input/Output should be programmed to be on the original H-panel inputs and outputs as they have an almost instantaneous response. 2.5 COMMUNICATIONS FAILURE In the event that communications to a HUIO fail, a warning will be posted on the front of the H- panel. The warning WILL NOT SHUT DOWN THE GENERATOR. The HUIO inputs will be set to a known condition (0 or OFF ) and the outputs will turn themselves off. This process will take between seconds. For example if there are four HUIO s the H-panel will only access any one at 2.4 second intervals at which time it will send both a read and a write message. The H-panel needs to see five missed messages before it confirms a failure, so it will take up to three intervals to make six message attempts, or, 7.2 seconds (3* 2.4 seconds). START Figure Communications Failure First read & write message to HUIO Second read & write message to HUIO 2.4s 2.4s 2.4s Third read & write message to HUIO 3. PROGRAMMING Genlink needs to be used to program the functions of the individual channels such as alarms, alarm properties, channel naming etc.. It is too complex to be done from the front panel. 3.2 COMMUNICATIONS SETTINGS Using Genlink, go to the communication port configuration page and set the RS485 port to be a Modbus master. Choose one of the four required baud rates (4800, 9600, 38400, 57600). If an old style remote annunciator is fitted the communications must be set at 4800 baud, no parity and two stop bits. Cycle the power to the H-panel for these settings to take effect. 3.3 HUIO CONFIGURATION The next act of programming is to tell the H-panel that a HUIO is to be connected (it s not plug and play, if a unit fails we need to know it s supposed to be there so we can post a warning if it s not). Set the dip switches on the HUIO(s) to give them a unique Modbus address (see Table ). If only one unit is to be connected we suggest leaving both switches in the OFF position to designate the unit as #. Next go to the HUIO configuration page and use the check boxes to select each of the HUIO s that are to be connected and apply the change. If the unit is not physically connected and communicating, a warning will be displayed on the front of the H-panel.

4 If a HUIO is not selected to be connected, then it s inputs and outputs will be ignored by the program EVEN IF IT IS PHYSICALLY CONNECTED. 3.4 SETTING UP THE INPUTS The new Inputs are numbered 2-27 in groups of four per HUIO module, for example, inputs 6-9 would always be on unit #2. The inputs appear on the digital input channel configuration screen just like any other input. Their status is also displayed on the input diagnostic screen in Genlink. Inputs can be given names and can be inverted, delayed, used to generate an alarm/warning and used to trigger an event. Refer to the Genlink help screen for this page if assistance is needed. A new direct output mapping method allows all of the new HUIO (only) inputs to be mapped directly to their own HUIO outputs. Alternatively, any alarm or warning generated by a HUIO input can be mapped to the HUIO output. Refer to section "Setting Up the Outputs" for examples. The new inputs are also available for use by the ILC programming tool supplied separately by the manufacturer. This allows the inputs to be logically combined just like a PLC to drive outputs or to trigger internal functions. 3.5 SETTING UP THE OUTPUTS The new Outputs are numbered 7-32 in groups of four per HUIO module, for example, outputs 2-24 would always be on unit #2. The output status appears on the digital output diagnostic screen in Genlink. The outputs are programmed by mapping them either to an output function (just like the standard outputs on the H-panel). Consult the Genlink help screen for the output function configuration page if assistance is needed. Alternatively the new HUIO outputs (ONLY) can be programmed via a new direct output mapping method. This allows any HUIO input to be either, directly mapped to it s same numbered output, or it allows an alarm/warning generated by that input to be mapped to an output. Here are some examples: HUIO #, input is directly mapped to HUIO # output. The state of the input is directly reflected by the output. However the signal can be programmed to be inverted via the input active level setting in Genlink. HUIO #2, input 3 is set as a warning and mapped to HUIO #2, output 3. When input 3 becomes active, a warning is generated. This warning activates output 3. Direct mapping is set up via radio buttons on the digital input channel configuration screen. These radio buttons only appear for HUIO inputs and not the regular inputs. The buttons are labeled as shown: Map Direct Map Alarm/Warning No Mapping The new outputs are available for use by the ILC programming tool supplied separately by the manufacturer. This allows the inputs to be logically combined just like a PLC to drive outputs or to trigger internal functions. 4. INPUT SPECIFICATIONS Each input is made active via a contact closure to ground. Two pins per input are provided for this purpose, one pin is grounded and the other is pulled up to 5V via a 4700 Ohm resistor. A volt free contact such as a relay or open collector transistor can be used to ground the input. The required current carrying capacity is in the region of ma. See Figure 2 for connection detail to J2. 5. OUTPUT SPECIFICATIONS Each output is made up of a pair of normally open relay contacts which close when the output is activated. The relay contacts are form A rated at 30 VDC and up to 5.0A each. NO AC CONNECTIONS SHOULD BE MADE TO THESE RELAYS. See Figure 2 for connection details to J5. The state of the output relays can be seen on Led s POWER AND COMMUNICATIONS CONNECTIONS Power is provided via a two-way Klippon style connector (J) which would normally be connected to the generator battery. Requirements are 6-30Vdc at 500 ma. The RS485 connection is made via a three-way Klippon style connector (J6). Wiring between units should be made using a twisted pair shielded cable such as Belden #9464. The shield should be connected AT BOTH ENDS as it acts as a common ground between the isolated ports. The RS485 network starts at the H-panel and can be daisy chained to various peripherals such as remote annunciators, remote relay panels, HTS switches and HUIO s. There should be only two terminating resistors in the whole network, one being fixed and in the H-panel. So, when fitting HUIO s the terminating jumper should be in the inactive position (on pins 2 and 3) when: 2

5 Figure 2 HUIO Outline INPUT GROUND FOR INPUT INPUT 2 GROUND FOR INPUT 2 INPUT 3 GROUND FOR INPUT 3 J3 J4 Modbus Address On 2 Jmp 2 3 J6 3 RS RS485 SCREEN RS485- INPUT 4 GROUND FOR INPUT 4 POWER + (2V) POWER - (GND) J2 J 8 2 Led Led 2 Led 3 Led 4 J5 8 OUTPUT 4 OUTPUT 4 OUTPUT 3 OUTPUT 3 OUTPUT 2 OUTPUT 2 OUTPUT OUTPUT NOTE: ) Power is nominally 2V but can be 6-30 VDC. 2) The RS485 screen should be connected at both ends. 3) JMP is the RS485 terminating resistor and should normally be fitted across Pins 2 and 3. (See manual for details.) 4) J4 is for the connection of a PC based diagnostic monitor. 5) J3 is reserved for the manufacturer s programming purposes. A. There is a remote annunciator on the network (which has a fixed terminator). B. There is an HTS on the network (which has a fixed terminator). C. There is a remote relay panel on the network which has a terminating resistor selected. The terminating jumper should be in the active position (on pins and 2) when: A. It is the only peripheral. B. It is at the far end of a bus which ONLY has other HUIO s on it. C. It is at the far end of a bus which ONLY has an un-terminated remote relay panel on it. Finally, don t worry too much about this termination business. It is unlikely to have any effect unless you are running at maximum bus length and very high speed (such as 57.6k baud). You will not damage the equipment if you terminate incorrectly. 7. QUICK SETUP. Set the Modbus address on the dip switch (e.g. off, off -for HUIO #). 2. Connect up the RS485 connection. 3. Fit the terminating jumper (jmp) in the correct position. 4. Connect up the power connection. 5. Connect to the H-panel via Genlink. 6. Set the RS485 port to be a Modbus master and choose one of the four required baud rates. If an old style remote annunciator is fitted the communications must be set at 4800 baud, no parity and two stop bits. Cycle the power to the H-panel for these settings to take effect. 7. Go to the HUIO configuration page. 8. Check the HUIO CONNECTED box for HUIO # and click apply (or whichever). 9. The unit is now connected and you can allocate the inputs and outputs as required. 3

6 8. DIAGNOSTIC MONITOR Provision has been made to fit a diagnostic PCB to the HUIO. This PCB plugs into socket J4 of the control board and also to the RS232 communication port of a PC. The controller should be power cycled AFTER plugging in the diagnostic PCB OR IT WILL NOT WORK. The unit can be interrogated either via a the manufacturer supplied custom graphical program, or by using Hyperterminal. Hyperterminal should be set for 9600 baud, eight data bits, no parity and one stop bit. The following commands are available: M* Examine memory location T* Enter production test mode S Display input/output status V Display internal voltages and hardware version C Display communication status, current baud rate and modbus address (dip switches) * These commands are reserved for the manufacturer use only and could cause mis-operation of the switch and injury or equipment damage DO NOT USE. The custom graphical program displays the screen in Figure 3. This interface will allow the HUIO outputs to be overridden for test purposes. Figure 3 Diagnostic Monitor 4

7 5

8 GENERAC POWER SYSTEMS, INC. P.O. BOX 8 WAUKESHA, WI 5387 Part No. 0G5354 Revision A (04/3/07) Printed in U.S.A.

Data Bulletin. Communications Wiring for POWERLINK G3 Systems Class 1210 ABOUT THIS BULLETIN APPLICATION INTRODUCTION.

Data Bulletin. Communications Wiring for POWERLINK G3 Systems Class 1210 ABOUT THIS BULLETIN APPLICATION INTRODUCTION. Data Bulletin 1210DB0002R3/05 03/2005 LaVergne, TN, USA Communications Wiring for POWERLINK G3 Systems Class 1210 Retain for future use. ABOUT THIS BULLETIN This data bulletin describes the proper wiring

More information

Ethernet. Customer Provided Equipment Configuring the Ethernet port.

Ethernet. Customer Provided Equipment Configuring the Ethernet port. Installing the RDSP-3000A-NIST Master Clock. Ethernet Connect the RJ-45 connector to a TCP/IP network. Equipment The following equipment comes with the clock system: RDSP-3000A-NIST Master Clock Module.

More information

8 Channel Status Input Panel model SIP-8

8 Channel Status Input Panel model SIP-8 Description The Sine Systems model SIP-8 Status Input Panel is to be used with the RFC-1/B Remote Facilities Controller. It consists of a long PC board mounted on a 1.75 inch (1U) rack panel. The SIP-8

More information

Application/Connection Examples

Application/Connection Examples This Quick Start Guide is designed to familiarize the user with the connection and configuration of the DTS-305 DIN rail mounted single / 3 phase power & energy meter with RS-485 or TCP communications.

More information

Programming and Using the Courier V.Everything Modem for Remote Operation of DDF6000

Programming and Using the Courier V.Everything Modem for Remote Operation of DDF6000 Programming and Using the Courier V.Everything Modem for Remote Operation of DDF6000 1.0 Introduction A Technical Application Note from Doppler System July 5, 1999 Version 3.x of the DDF6000, running version

More information

WinLIN Setup and Operation:

WinLIN Setup and Operation: Frequently Asked Questions about the 07551-Series Masterflex L/S Computer-Compatible drives and about the Masterflex WinLIN Linkable Instrument Control Software (07551-70) WinLIN Setup and Operation: Will

More information

EDI Distributor Control Interface Wiring and Setup Instructions

EDI Distributor Control Interface Wiring and Setup Instructions Universal I/O EDI Distributor Control Interface Wiring and Setup Instructions EDI UNIVERSAL I/O INTERFACE MODULE The only interface needed for EDI-V5 controls Network compatible with all older EDI controls

More information

ATS Communication Overview

ATS Communication Overview ATS Communication Overview Viewpoint ATS 485 Communication link IBM Compatible Slide 1 of 23 Contents 1. Introduction 2. LonWork 3. Modbus Cards 4. Modbus Factory Configuration 5. Modbus Test Software

More information

Configure Inverter output for two utility settings, (1)120V/60Hz, (2)220V/50Hz

Configure Inverter output for two utility settings, (1)120V/60Hz, (2)220V/50Hz HV Solar Inverter System GUI Overview January 2012 TMS320C2000 Systems Applications Collateral The HV Solar Inverter System GUI provides a simple interface to evaluate some of the functionalities of the

More information

CM705B - Universal Expander Module CM707B - Plug On Zone Expander Security Systems

CM705B - Universal Expander Module CM707B - Plug On Zone Expander Security Systems CM705B - Universal Expander Module CM707B - Plug On Zone Expander Security Systems EN Security System CM705B CM705B - Universal Expander Module The CM705B universal expander provides a cost effective way

More information

Bluetooth HC-06 with serial port module Easy guide

Bluetooth HC-06 with serial port module Easy guide 1 Bluetooth HC-06 with serial port module Easy guide This manual consists of 3 parts: PART 1. Overview of Bluetooth HC-06 module with serial port. PART 2. Installing Bluetooth HC-06 module with Bolt 18F2550

More information

ENET-710. ENET-710 - Ethernet Module ENET-710 JAN / 06 FOUNDATION

ENET-710. ENET-710 - Ethernet Module ENET-710 JAN / 06 FOUNDATION ENET-710 ENET-710 - Ethernet Module JAN / 06 ENET-710 FOUNDATION E N E T 7 1 0 ME smar www.smar.com Specifications and information are subject to change without notice. Up-to-date address information is

More information

Bluetooth Serial Adapter

Bluetooth Serial Adapter RN-BT-SRL-UM Bluetooth Serial Adapter 0 Roving Networks. All rights reserved. RN-BT-SRL-UM-.0 Version.0 //0 USER MANUAL RN-BT-SRL-UM-.0 OVERVIEW Roving Networks offers a variety of Bluetooth serial adapters

More information

WEA-Base. User manual for load cell transmitters. UK WEA-Base User manual for load cell transmitters Version 3.2 UK

WEA-Base. User manual for load cell transmitters. UK WEA-Base User manual for load cell transmitters Version 3.2 UK WEA-Base User manual for load cell transmitters 1 Contents 1. Technical data... 3 2. Assembly... 4 2.1 Power supply... 4 2.2 Load cells... 4 2.3 RS-485... 4 2.4 Relays... 5 2.5 Digital input... 5 2.6 Analogue

More information

Date Rev. Details Author

Date Rev. Details Author Jtech engineering ltd J - Te c h E n g i n e e ring, L t d. 11080 Bond Boulevard Delta BC V4E 1M7 Canada Tel: 604 543 6272 Fax: 604 543 6476 http://www.jtecheng.com AUTODIALER USER S MANUAL REVISION HISTORY

More information

MARS-ALE Application Note. RS-232 Computer Control Interface for LDG Electronics DTS-4/DTS-6 Desktop Coaxial Switches. Version 1.

MARS-ALE Application Note. RS-232 Computer Control Interface for LDG Electronics DTS-4/DTS-6 Desktop Coaxial Switches. Version 1. MARS-ALE Application Note RS-232 Computer Control Interface for LDG Electronics DTS-4/DTS-6 Desktop Coaxial Switches Version 1.02 08 April 2006 POC for this document is AAR2EY/NJ U.S. Army MARS aar2ey@usarmymars.us

More information

12-36-1000. Autodialler and Relay Telephone Interface 12-36-1000. I/O Telephone Interface with AutoDialer PRODUCT INFORMATION 1.

12-36-1000. Autodialler and Relay Telephone Interface 12-36-1000. I/O Telephone Interface with AutoDialer PRODUCT INFORMATION 1. 12-36-1000 Autodialler and Relay Telephone Interface 1.0 INTRODUCTION 12-36-1000 I/O Telephone Interface with AutoDialer The 12-36-1000 is a autodialer and telephone interface that can be used autonomously

More information

Develop a Dallas 1-Wire Master Using the Z8F1680 Series of MCUs

Develop a Dallas 1-Wire Master Using the Z8F1680 Series of MCUs Develop a Dallas 1-Wire Master Using the Z8F1680 Series of MCUs AN033101-0412 Abstract This describes how to interface the Dallas 1-Wire bus with Zilog s Z8F1680 Series of MCUs as master devices. The Z8F0880,

More information

Fanuc 0 M/T Model C Serial (RS232) Connection Guide

Fanuc 0 M/T Model C Serial (RS232) Connection Guide Memex Automation Inc., Burlington, Ontario Canada L7N 1 http://www.memex.ca Fanuc 0 M/T Model C Serial (RS232) Connection Guide The Fanuc 0-C control has two RS-232 interfaces. Interface number 1 (M5)

More information

Communication Setup Application Note

Communication Setup Application Note Communication Setup Application Note This Application Note describes how to install and set up communication between the inverter and the SolarEdge Monitoring Server. This document contains the following

More information

M1000 Process Alarm Monitor

M1000 Process Alarm Monitor Data Sheet Process Alarm Monitor Reliable Supervision and Control 10 inputs with LED indications Supports both NO/NC input contacts 10 open collector outputs Built-in siren relay Text label for alarm descriptions

More information

MAKING MODERN LIVING POSSIBLE. AK-SC255 On-Site Installation Guide DANFOSS ELECTRONIC CONTROLS & SENSORS

MAKING MODERN LIVING POSSIBLE. AK-SC255 On-Site Installation Guide DANFOSS ELECTRONIC CONTROLS & SENSORS MAKING MODERN LIVING POSSIBLE AK-SC255 On-Site Installation Guide DANFOSS ELECTRONIC CONTROLS & SENSORS How to Use This Guide Read this Guide completely as you install and start up your new AK-SC 255 controller.

More information

Different Ways of Connecting to. 3DLevelScanner II. A.P.M Automation Solutions LTD. www.apm-solutions.com Version 3.0

Different Ways of Connecting to. 3DLevelScanner II. A.P.M Automation Solutions LTD. www.apm-solutions.com Version 3.0 3DLevelScanner II Different Ways of Connecting to 3DLevelScanner II A.P.M Automation Solutions LTD. www.apm-solutions.com Version 3.0 2 Different Ways of Connecting to 3DLevelScanner II Version 3.0 Table

More information

MDM192 MULTI-DROPS DIGITAL MODEM FOR PRIVATE LINE. USER GUIDE Document reference : 9010709-03

MDM192 MULTI-DROPS DIGITAL MODEM FOR PRIVATE LINE. USER GUIDE Document reference : 9010709-03 MDM192 MULTI-DROPS DIGITAL MODEM FOR PRIVATE LINE USER GUIDE Document reference : 9010709-03 If you have questions about the MDM192 or desire assistance, contact ETIC TELECOMMUNICATIONS at the following

More information

LDG DTS-4/4R Desktop Coaxial Switch / Remote

LDG DTS-4/4R Desktop Coaxial Switch / Remote LDG DTS-4/4R Desktop Coaxial Switch / Remote LDG Electronics 1445 Parran Road, PO Box 48 St. Leonard MD 20685-2903 USA Phone: 410-586-2177 Fax: 410-586-8475 ldg@ldgelectronics.com www.ldgelectronics.com

More information

How to connect to a Class II router using a mobile-phone data cable specifically for Solwise & Safecom routers

How to connect to a Class II router using a mobile-phone data cable specifically for Solwise & Safecom routers USB to router s serial port How to connect to a Class II router using a mobile-phone data cable specifically for Solwise & Safecom routers by Neo at RouterTech.Org Introduction Routers based on the AR7RD/AR7WRD

More information

210E - 210ECL - 2010ECL - 2018ECL RMS Signal Monitor. Operations Manual

210E - 210ECL - 2010ECL - 2018ECL RMS Signal Monitor. Operations Manual 210E - 210ECL - 2010ECL - 2018ECL RMS Signal Monitor Operations Manual THIS MANUAL CONTAINS TECHNICAL INFORMATION FOR THE FOLLOWING SERIES OF MODEL 210/2010/2018 SIGNAL MONITORS: 210E, 210ECL, 2010, 2010ECL,

More information

PM1122 INT DIGITAL INTERFACE REMOTE

PM1122 INT DIGITAL INTERFACE REMOTE PM1122 INT DIGITAL INTERFACE REMOTE PM1122 INT front panel description: 1. Clear wireless remotes knob: push this button for more than 2 seconds to clear the list of all assigned wireless remote settings

More information

Connecting UniOP to Telemecanique PLC s

Connecting UniOP to Telemecanique PLC s Connecting UniOP to Telemecanique PLC s Contents 1. Introduction... 2 2. Uni-Telway Driver... 2 2.1 Uni-Telway Addresses... 2 2.2 Designer Controller Setup... 4 2.3 Point To Point Connection Addressing...

More information

Remote control circuitry via mobile phones and SMS

Remote control circuitry via mobile phones and SMS Remote control circuitry via mobile phones and SMS Gunther Zielosko 1. Introduction In application note No. 56 ( BASIC-Tiger sends text messages, in which we described a BASIC-Tiger sending text messages

More information

Mobile Device Power Monitor Battery Connection Quick Start Guide

Mobile Device Power Monitor Battery Connection Quick Start Guide Mobile Device Power Monitor Battery Connection Quick Start Guide Distributed By: Monsoon Solutions, Inc. www.msoon.com Introduction The Power Tool software and the Mobile Device Power Monitor hardware

More information

ImproX IXP20 Controller INSTALLATION MANUAL

ImproX IXP20 Controller INSTALLATION MANUAL MODEL NUMBER: ISC910-1-0-GB-XX ISC911-5-0-GB-XX IXP20 CONTROLLER SPECIFICATIONS Working Environment Plastic Housing... Power ImproX IXP20 Controller INSTALLATION MANUAL Designed to work in an indoor (dry)

More information

STANDALONE PCI INTERFACE PACKAGE

STANDALONE PCI INTERFACE PACKAGE PACKAGE USER S MANUAL DOC-039 Rev. 1.1 Copyright 2009 All Rights Reserved MED Associates, Inc. P.O. Box 319 St. Albans, Vermont 05478 www.med-associates.com - ii - TABLE OF CONTENTS Chapter 1... 1 Introduction...1

More information

Contents. Document information

Contents. Document information User Manual Contents Document information... 2 Introduction... 3 Warnings... 3 Manufacturer... 3 Description... Installation... Configuration... Troubleshooting...11 Technical data...12 Device Scope: PCB

More information

Modbus Communications for PanelView Terminals

Modbus Communications for PanelView Terminals User Guide Modbus Communications for PanelView Terminals Introduction This document describes how to connect and configure communications for the Modbus versions of the PanelView terminals. This document

More information

Technical Manual. For use with Caller ID signaling types: Belcore 202, British Telecom, & ETSI

Technical Manual. For use with Caller ID signaling types: Belcore 202, British Telecom, & ETSI Technical Manual For use with Caller ID signaling types: Belcore 202, British Telecom, & ETSI Caller ID.com WHOZZ CALLING? POS 2 Caller ID Monitoring Unit Technical Manual For use with Caller ID signaling

More information

HSG Engineering Tech Bulletin

HSG Engineering Tech Bulletin Specifications subject to change OCT 2013; Rev. 1.3 HSG Engineering Tech Bulletin Recommended RS-485 Wiring for NetAXS-4/NetAXS-123 Loops Overview This document provides the recommended RS-485 wiring for

More information

Network Operation and Troubleshooting

Network Operation and Troubleshooting and Troubleshooting 7 2 and Troubleshooting Starting the Network PLC as Master Networks If you re using a PLC as the master station, you must put the CPU in Run mode before the communications program can

More information

Contact Center CC-165 INSTALLATION & USER'S GUIDE

Contact Center CC-165 INSTALLATION & USER'S GUIDE Contact Center CC-165 INSTALLATION & USER'S GUIDE Table of Contents Introduction... 2 Specifications... 2 J4 Host Communications... 2 J5 and J12 (upper board)... 3 J6, J13, and 14 Input Connections...

More information

M68EVB908QL4 Development Board for Motorola MC68HC908QL4

M68EVB908QL4 Development Board for Motorola MC68HC908QL4 M68EVB908QL4 Development Board for Motorola MC68HC908QL4! Axiom Manufacturing 2813 Industrial Lane Garland, TX 75041 Email: Sales@axman.com Web: http://www.axman.com! CONTENTS CAUTIONARY NOTES...3 TERMINOLOGY...3

More information

Keep it Simple Timing

Keep it Simple Timing Keep it Simple Timing Support... 1 Introduction... 2 Turn On and Go... 3 Start Clock for Orienteering... 3 Pre Start Clock for Orienteering... 3 Real Time / Finish Clock... 3 Timer Clock... 4 Configuring

More information

RS232 Programming and Troubleshooting Guide for Turbo Controls

RS232 Programming and Troubleshooting Guide for Turbo Controls RS232 Programming and Troubleshooting Guide for Turbo Controls This Troubleshooting guide is intended for the set up and troubleshooting of the control panels onboard RS232 output. Refer to the Installation

More information

Orbit PCI Mk 2 Network Card. User Manual. Part No. 502566 Issue 4

Orbit PCI Mk 2 Network Card. User Manual. Part No. 502566 Issue 4 Orbit PCI Mk 2 Network Card User Manual Part No. 502566 Issue 4 Information in this document is subject to change without notice. Companies, names and data used in examples herein are fictitious unless

More information

EVAL-UFDC-1/UFDC-1M-16

EVAL-UFDC-1/UFDC-1M-16 Evaluation Board for Universal Frequency-to- Digital Converters UFDC-1 and UFDC-1M-16 EVAL-UFDC-1/UFDC-1M-16 FEATURES Full-Featured Evaluation Board for the Universal Frequency-to-Digital Converters UFDC-1

More information

mdm-mp3 minidirector with MP3 Player

mdm-mp3 minidirector with MP3 Player minidirector with MP3 Player User Manual December 15, 2014 V1.02 Copyright Light O Rama, Inc. 2007, 2008 Table of Contents Introduction... 4 What s in the Box... 4 Hardware Utility Version... 5 Important

More information

BATTERY MANAGEMENT SYSTEM

BATTERY MANAGEMENT SYSTEM BATTERY MANAGEMENT SYSTEM User s manual Revision 1 In this user s manual you will find a list of characteristics, setup and installation steps and recommendations for the EMUS Battery Management System.

More information

In regard to calculating system power requirements, refer to DBK Basics located near the front of this manual.

In regard to calculating system power requirements, refer to DBK Basics located near the front of this manual. DBK42 16-Slot 5B Signal Conditioning Module Overview 1 Hardware Setup 2 DBK42 Connection 2 DBK42 Configuration 2 5B Module Connection 2 Power Considerations 2 Terminal Block Connections 3 DaqBoard/2000

More information

INTERFACING SECURITY SYSTEMS TO HOMEVISION

INTERFACING SECURITY SYSTEMS TO HOMEVISION INTERFACING SECURITY SYSTEMS TO HOMEVISION We receive a lot of requests about interfacing HomeVision to a security system. This article discusses the options in detail. OVERVIEW There are three main ways

More information

DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS

DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS Features: INSTALLATION Install in accordance with NFPA 70. DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS Up to 1.95 Amps Load Capacity Class 2 Rated Outputs Overload, Over Voltage, and Short

More information

Single channel data transceiver module WIZ2-434

Single channel data transceiver module WIZ2-434 Single channel data transceiver module WIZ2-434 Available models: WIZ2-434-RS: data input by RS232 (±12V) logic, 9-15V supply WIZ2-434-RSB: same as above, but in a plastic shell. The WIZ2-434-x modules

More information

MODEL 5010 DUAL CHANNEL SMOKE/FIRE DETECTION MODULE

MODEL 5010 DUAL CHANNEL SMOKE/FIRE DETECTION MODULE DESCRIPTION MODEL 5010 DUAL CHANNEL SMOKE/FIRE DETECTION MODULE DESCRIPTION The SST Model 5010 Two Channel Smoke/Fire Detection Module provides two independent detection input channels for the NOVA-5000

More information

Series Six Plus Programmable Controller

Series Six Plus Programmable Controller Series Six Plus Programmable Controller Gl?K-0147B June 1989 Central Processor Unit 8-Slot Rack 1l-Slot Rack General Description The Central Processor Unit (CPU) for the Series Six Plus Programmable Logic

More information

LocoNet, the Digitrax Difference

LocoNet, the Digitrax Difference LocoNet, the Digitrax Difference LocoNet is Digitrax's method of communication between LocoNet compatible devices on a model railroad layout. LocoNet Compatible devices are designed to work together on

More information

ADA COMPLIANT BOX STYLE TELEPHONE INSTALLATION, PROGRAMMING AND OPERATING INSTRUCTIONS FOR MODEL PBX

ADA COMPLIANT BOX STYLE TELEPHONE INSTALLATION, PROGRAMMING AND OPERATING INSTRUCTIONS FOR MODEL PBX ADA COMPLIANT BOX STYLE TELEPHONE INSTALLATION, PROGRAMMING AND OPERATING INSTRUCTIONS FOR MODEL PBX INSTALLATION INSTRUCTIONS Step 1. Determine the position for the Hands-free phone in the elevator phone

More information

TPM Product Type 107-D162-NNT 48-channel digital input and 16-channel digital output module with pluggable terminal

TPM Product Type 107-D162-NNT 48-channel digital input and 16-channel digital output module with pluggable terminal Product Type 107-D162-NNT 48-channel digital input and 16-channel digital output module with pluggable terminal Specifications Size: (L122 x W123 x H104 mm) Series Interface: Half duplex RS-485 with transformer

More information

OWNERS MANUAL. Status Monitor. for Windows 95, 98, ME, NT 4, 2000 & XP. SIGNALCRAFTERS TECH, INC. www.signalcrafters.com

OWNERS MANUAL. Status Monitor. for Windows 95, 98, ME, NT 4, 2000 & XP. SIGNALCRAFTERS TECH, INC. www.signalcrafters.com OWNERS MANUAL Status Monitor for Windows 95, 98, ME, NT 4, 2000 & XP SIGNALCRAFTERS TECH, INC. www.signalcrafters.com 57 Eagle Rock Avenue, East Hanover, NJ 07936 Tel: 973-781-0880 or 800-523-5815 Fax:

More information

CM6700 Matrix Switcher/Controller

CM6700 Matrix Switcher/Controller CM6700 Matrix Switcher/Controller Installation/ Operation Manual C523M-H (6/05) Pelco 3500 Pelco Way Clovis, CA 93612-5699 USA www.pelco.com In North America and Canada: Tel (800) 289-9100 FAX (800) 289-9150

More information

ALARMS-xx. Remote Alarm Unit Setup Guide 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 RESET ALL

ALARMS-xx. Remote Alarm Unit Setup Guide 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 RESET ALL Remote Alarm Unit Setup Guide 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 RESET ALL User s Guide Version 1.0 07/01/2009 Michael Stevens & Partners Ltd. has made

More information

LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA. General Specification

LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA. General Specification 08/17/12 Rev2 LTR Series General Specification 700 VA to 2.1 KVA 1.0 General LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA General Specification This specification describes the features and

More information

Instruction Manual RCI-800-XXX. Remote Control Signal Interface

Instruction Manual RCI-800-XXX. Remote Control Signal Interface Manufacturers of Process Controls and Instrumentation Instruction Manual Model: Function: Communication: Input: Output: Power: RCI-800-XXX Remote Control Signal Interface XXX=SER: RS-232/485 XXX=MDM Modem

More information

Current Loop Application Note 1495

Current Loop Application Note 1495 Current Loop Application Note Document No. CLAN1495 International Headquarter B&B Electronics Mfg. Co. Inc. 707 Dayton Road -- P.O. Box 1040 -- Ottawa, IL 61350 USA Phone (815) 433-5100 -- General Fax

More information

Application Note - Connecting an Electricity Meter to SolarEdge Devices (Europe and APAC)

Application Note - Connecting an Electricity Meter to SolarEdge Devices (Europe and APAC) February 2015 February 2015 Application Note - Connecting an Electricity Meter to SolarEdge Devices (Europe and APAC) This document describes how to connect an electricity meter to a SolarEdge device (inverters,

More information

WEB log. Device connection plans

WEB log. Device connection plans WEB log LIGHT+ 20 BASIC 100 PRO unlimited Device connection plans Version 20151210* Copyright Copyright for this manual remains with the manufacturer. No part of this manual may be reproduced or edited,

More information

HCS-3300/3302/3304 USB Remote Programmable Laboratory Grade Switching Mode Power Supply

HCS-3300/3302/3304 USB Remote Programmable Laboratory Grade Switching Mode Power Supply 1. INTRODUCTION HCS-3300/3302/3304 USB Remote Programmable Laboratory Grade Switching Mode Power Supply User Manual This family of efficient, upgraded SMPS with small form factor, auto cross over CV CC,

More information

Mobile Satellite Solutions. A WiWorld Partner SATELLITE TV ANTENNA CONTROLLER RFM-1000/1100 TECHNICAL MANUAL STOW SEARCH

Mobile Satellite Solutions. A WiWorld Partner SATELLITE TV ANTENNA CONTROLLER RFM-1000/1100 TECHNICAL MANUAL STOW SEARCH Mobile Satellite Solutions A WiWorld Partner SATELLITE TV ANTENNA CONTROLLER RFM-1000/1100 TECHNICAL MANUAL SEARCH STOW Ver. 1 June 2012 WARNING Make all electrical and coax connections from the controller

More information

To perform Ethernet setup and communication verification, first perform RS232 setup and communication verification:

To perform Ethernet setup and communication verification, first perform RS232 setup and communication verification: PURPOSE Verify that communication is established for the following products programming option (488.2 compliant, SCPI only): DCS - M9C & DCS M130, DLM M9E & DLM-M9G & DLM M130, DHP - M9D, P series, SG,

More information

Introduction: Implementation of the MVI56-MCM module for modbus communications:

Introduction: Implementation of the MVI56-MCM module for modbus communications: Introduction: Implementation of the MVI56-MCM module for modbus communications: Initial configuration of the module should be done using the sample ladder file for the mvi56mcm module. This can be obtained

More information

User manual Compact Web PLC WP240 series IEC-line

User manual Compact Web PLC WP240 series IEC-line User manual Compact Web PLC WP240 series IEC-line update: 09-01-2014 IEC-line by OVERDIGIT overdigit.com 1. General description The WP240 device is a PLC, programmable in IEC61131-3 language using CoDeSys

More information

FOSTCDR. Industrial Serial to Multimode Fiber Optic Converter PRODUCT INFORMATION B&B ELECTRONICS. Specifications Serial Technology

FOSTCDR. Industrial Serial to Multimode Fiber Optic Converter PRODUCT INFORMATION B&B ELECTRONICS. Specifications Serial Technology FOSTCDR pn 8684R1 FOSTCDR-0812ds page 1/5 Industrial Serial to Multimode Fiber Optic Converter Data Rates up to 115.2 kbps 2.5 Mile (4 km) Range 10 to 30 VDC Input Voltage Wide Operating Temperature 2000V

More information

EQUIPMENT SPECIFICATIONS

EQUIPMENT SPECIFICATIONS EQUIPMENT SPECIFICATIONS IC-1600 Intelligent Controller The IC-1600 Intelligent Controller is a fully intelligent panel that has a complete database on board. It operates in conjunction with the Access

More information

DIN Rail Mounted Leased Line Modem Users Manual 366-101 Rev. 2

DIN Rail Mounted Leased Line Modem Users Manual 366-101 Rev. 2 DIN Rail Mounted Leased Line Modem Users Manual 366-101 Rev. 2 Copyright 2008 Miille Applied Research Co., Inc. Houston, Texas This page is left blank intentionally Page i TABLE OF CONTENTS LIST OF FIGURES...

More information

Communication with BushingGard using computer USB port

Communication with BushingGard using computer USB port Communication with BushingGard using computer USB port There are two ways of communication with BushingGard through computer USB port: Direct communication between computer USB port and BushingGard USB

More information

1.Eastron SDM220Modbus Smart Meter Modbus Protocol Implementation V1.0

1.Eastron SDM220Modbus Smart Meter Modbus Protocol Implementation V1.0 1.Eastron SDM220Modbus Smart Meter Modbus Protocol Implementation V1.0 1.1 Modbus Protocol Overview This section provides basic information for interfacing the Eastron Smart meter to a Modbus Protocol

More information

NETWORK ENABLED EQUIPMENT MONITOR

NETWORK ENABLED EQUIPMENT MONITOR NETWORK ENABLED EQUIPMENT MONITOR Remotely Monitor Sensors over the Internet Connect Sensors to the Web to Remotely Monitor Equipment, Processes or Other Applications A Complete, Easy to Deploy, Stand-Alone

More information

Installation instructions for Series NRX INCOM communications adapter module

Installation instructions for Series NRX INCOM communications adapter module 4000 NRX RF DRAWOUT SUBTITLE IMAGE (12/15/2010) Effective July 2015 Supersedes October 2010 IL01301033EH04 Installation instructions for Series NRX INCOM communications adapter module Instructions apply

More information

SHDSL LAN EXTENDER H301A. User Manual

SHDSL LAN EXTENDER H301A. User Manual SHDSL LAN EXTENDER H301A User Manual Rev. 1.0 Yoda Communications, Inc. Yoda Communications, Inc. Address 2F, No. 3-1, Industry East Road IX, Science Based Industrial Park, HsinChu, Taiwan Tel 886-3-5632323

More information

SMART SENSOR COLLECTION

SMART SENSOR COLLECTION TEMPERATURE SENSOR This sensor measures temperature in degrees Celsius or Fahrenheit. It works with all SensorHawk base units (SensorHawk-2, SensorHawk-8 and SensorHawk8/20) as well as the SecurityHawk-8

More information

MSL1000 Monitored Serial Link Interface Manual V1.01

MSL1000 Monitored Serial Link Interface Manual V1.01 Audix Systems, Station Road, Wenden, Saffron Walden, Essex, CB11 4LG. Telephone: +44(0)1799 540888 Facsimile: +44(0)1799 541618 www.tycosafetyproducts-europe.com www.audixsystems.co.uk MSL1000 Monitored

More information

Fire Fighter Phone System Installation Instructions

Fire Fighter Phone System Installation Instructions Fire Fighter Phone System Installation Instructions Introduction This publication describes the installation procedure for the Fire Fighter s Phone on a 4100U or a 4100ES Fire Alarm Control Panel (FACP).

More information

CMC-PD01 PROFIBUS DP Slave Communication Card Operation Manual

CMC-PD01 PROFIBUS DP Slave Communication Card Operation Manual CMC-PD01 PROFIBUS DP Slave Communication Card Operation Manual CMC-0205820-01 Table of Content 1 Introduction to CMC-PD01... 2 1.1 Product Introduction... 2 1.2 Features... 2 2 Product Profile and Outline...

More information

Pressure transmitter (2 wire) / switch for continuous or On/Off Control

Pressure transmitter (2 wire) / switch for continuous or On/Off Control transmitter (2 wire) / switch for continuous or On/Off Control Indication, monitoring, transmitting and continuous or On/Off control in one device Output signal 4...20 ma, 2-wire for continuous control

More information

MANUAL FOR RX700 LR and NR

MANUAL FOR RX700 LR and NR MANUAL FOR RX700 LR and NR 2013, November 11 Revision/ updates Date, updates, and person Revision 1.2 03-12-2013, By Patrick M Affected pages, ETC ALL Content Revision/ updates... 1 Preface... 2 Technical

More information

DK40 Datasheet & Hardware manual Version 2

DK40 Datasheet & Hardware manual Version 2 DK40 Datasheet & Hardware manual Version 2 IPC@CHIP DK40 Evaluation module Beck IPC GmbH http://www.bcl.de page 1 of 11 Table of contents Table of contents... 2 Basic description... 3 Characteristics...

More information

Model CFA-24 Transparent Cable Farm Automation Switch

Model CFA-24 Transparent Cable Farm Automation Switch Model CFA-24 Transparent Cable Farm Automation Switch Ideal for Broadband Forum s ID-337 G.fast Certification and TR-249 VDSL2 Vectoring Testing High performance transparent solution designed to automate

More information

MIDNITE SOLAR AND SOLAR WASHINGTON

MIDNITE SOLAR AND SOLAR WASHINGTON MIDNITE SOLAR AND SOLAR WASHINGTON CHARGE CONTROLLERS 30 amp MPPT with load control for small systems, boats and RV s THE KID THE KID LED MODES The KID has a three LED bar graph plus four status LEDs that

More information

IMS ALARM 3 PORT RS485 EXPANSION BOX

IMS ALARM 3 PORT RS485 EXPANSION BOX Price $.00 IMS ALARM 3 PORT EXPANSION BOX OPERATING INSTRUTIONS READ THOROUGHLY BEFORE INSTALLING EQUIPMENT 920147.fm TABLE OF ONTENTS GENERAL SPEIFIATIONS... 3 INTRODUTION... 4 RS232 ONNETION... 4 OMPATIBILITY...

More information

User and installation manual

User and installation manual User and installation manual aquaero 5 The information contained in this manual is subject to change without prior notice. All rights reserved. Current as of April 2011 ENGLISH: PAGE 1 DEUTSCH: SEITE 13

More information

BACnet Wiring Guidelines. For Price Controls MANUAL INSTALLATION

BACnet Wiring Guidelines. For Price Controls MANUAL INSTALLATION MANUAL INSTALLATION BACnet Wiring Guidelines For Price Controls Revision #: 01 Issue Date: 01/22/14 2014 Price Industries Limited. All rights reserved. TABLE OF CONTENTS Product Overview Overview...1 Power

More information

By: John W. Raffensperger, Jr. Revision: 0.1 Date: March 14, 2008

By: John W. Raffensperger, Jr. Revision: 0.1 Date: March 14, 2008 Introduction Page 1 of 13 So, you got your AX-12+ servos, you got your USB2Dynamixel, you connected things up, fire up the software, and wala! Nothing happens. Welcome to the club! There are at least four

More information

DSX Master Communications

DSX Master Communications DSX Access Systems, Inc. PC to Master Controller - Direct Connect Communications DSX Master Communications Communications between the Comm Server PC and the Master Controller can take several forms which

More information

Switch board datasheet EB007-00-1

Switch board datasheet EB007-00-1 Switch board datasheet EB007-00-1 Contents 1. About this document... 2 2. General information... 3 3. Board layout... 4 4. Testing this product... 5 5. Circuit description... 6 Appendix 1 Circuit diagram

More information

LEN s.r.l. Via S. Andrea di Rovereto 33 c.s. 16043 CHIAVARI (GE) Tel. +39 0185 318444 - Fax +39 0185 472835 mailto: len@len.it url: http//www.len.

LEN s.r.l. Via S. Andrea di Rovereto 33 c.s. 16043 CHIAVARI (GE) Tel. +39 0185 318444 - Fax +39 0185 472835 mailto: len@len.it url: http//www.len. MA511 General Index 1 INTRODUCTION... 3 1.1 HARDWARE FEATURES:... 4 2 INTERFACE... 5 2.1 KEYBOARD... 6 2.2 POWER ON... 7 2.3 POWER OFF... 7 2.4 DETECTOR CONNECTION... 7 2.5 DETECTOR SUBSTITUTION...7 3

More information

TAC I/NETTM MR-VAV-AX. Application Specific MicroRegulator TM

TAC I/NETTM MR-VAV-AX. Application Specific MicroRegulator TM TAC I/NETTM TM TAC s TM has an extensive range ofpre-engineered VAV control sequences, which combined with a fully integrated actuator and airflow transducer, makes it a low Total Installed Cost solution

More information

Combi B Alarm box. Mounting instructions

Combi B Alarm box. Mounting instructions Combi B Alarm box Mounting instructions EN Mounting instructions Alarm box Combi B VdS, G113064, G113065, G113066 Table of Contents 1 Description... 3 2 System overview... 3 3 Structure... 3 3.1 Power

More information

SMS Alarm Messenger. Setup Software Guide. SMSPro_Setup. Revision 090210 [Version 2.2]

SMS Alarm Messenger. Setup Software Guide. SMSPro_Setup. Revision 090210 [Version 2.2] SMS Alarm Messenger SMSPro_Setup Revision 090210 [Version 2.2] ~ 1 ~ Contents 1. How to setup SMS Alarm Messenger?... 3 2. Install the SMSPro_Setup software... 5 3. Connection Type... 6 4. Connection Port

More information

LTM-1338B. Plus Communications Manual

LTM-1338B. Plus Communications Manual LTM-1338B Plus Communications Manual 2000. Best Power, Necedah, Wisconsin All rights reserved. Best Power The System Setup option from the Main Menu on the front panel is passwordprotected. The default

More information

Firmware version: 1.10 Issue: 7 AUTODIALER GD30.2. Instruction Manual

Firmware version: 1.10 Issue: 7 AUTODIALER GD30.2. Instruction Manual Firmware version: 1.10 Issue: 7 AUTODIALER GD30.2 Instruction Manual Firmware version: 2.0.1 Issue: 0.6 Version of the GPRS transmitters configurator: 1.3.6.3 Date of issue: 07.03.2012 TABLE OF CONTENTS

More information

Managed Switch Quick Start Guide

Managed Switch Quick Start Guide Managed Switch Quick Start Guide Note: The purpose of this guide is to help you get your Hirschmann managed switch up & running as quickly as possible and recommend switch settings that are suitable for

More information

OPERATING INSTRUCTIONS Model ST-888 DTMF ANI/ENI Display Decoder

OPERATING INSTRUCTIONS Model ST-888 DTMF ANI/ENI Display Decoder P R O D U C T G R O U P OPERATING INSTRUCTIONS Model ST-888 DTMF ANI/ENI Display Decoder Manual # 600-0901 November 30, 1999 Rev. D - 99068 DESCRIPTION The ST-888 Mobilecall Display Decoder is a desktop

More information

Daker DK 1, 2, 3 kva. Manuel d installation Installation manual. Part. LE05334AC-07/13-01 GF

Daker DK 1, 2, 3 kva. Manuel d installation Installation manual. Part. LE05334AC-07/13-01 GF Daker DK 1, 2, 3 kva Manuel d installation Installation manual Part. LE05334AC-07/13-01 GF Daker DK 1, 2, 3 kva Index 1 Introduction 24 2 Conditions of use 24 3 LCD Panel 25 4 Installation 28 5 UPS communicator

More information