2015 Performance Spec Guidelines

Size: px
Start display at page:

Download "2015 Performance Spec Guidelines"

Transcription

1 Commercial, Medical and Military Grade Copper Silver Ionization for: Facility Potable Water Legionella Prevention or Remediation 2015 Performance Spec Guidelines Industry Guidelines for Medical, Commercial or Military Type Copper Silver Ion Generator Technology Specified for Legionella Prevention Code Compliance in Design Stage Facility Potable Water Network Projects (Healthcare, Nursing Homes, VA Hospitals, Hotels & Resorts, Large Residential Facilities, Schools, Sports Centers, Military Structures) PART 1 - GENERAL 1.1 SUMMARY A. A medical, commercial/hotel, military grade copper silver ionisation system is sought for: Legionella prevention within: DHW loop(s) only (or) 100% Potable Water excluding any cooling tower. B. Each water areas include: (Zone A), (Zone B), (Zone C), (Zone D) Patient Care Beds / Rooms / H2O Usage (GPD-DHW) / H2O Flow 100% C. Multi-Zone: When multiple DHW loops are in a common mechanical room, the manufacturer can provide Multi-Zone controller(s): Mech. Room 1 = DHW-Loop(s) Mech. Room 2 = DHW-Loop(s) Mech. Room 3 = DHW-Loop(s) Mech. Room 4 = DHW-Loop(s) C-1: Each Multi-Zone area(s) include: (R1), (R2), (R3), (R4) Patient Care Beds / Rooms / H2O Usage (DHW) / H2O Flow (100%) 1.2 DEFINITIONS: A. VDC: Volts of Direct Current. / VAC: Volts of Alternate Current. B. TCP/IP: Transmission Control Protocol (TCP) supporting the Internet Protocol (IP) Suite. C. DHW: Potable Domestic Hot Water Loop D. PLC: Programmable Logic Controller / HMI: Human Machine Interface E. IPS: Iron Pipe Size / CTS: Copper Tube Size 1.3 SUBMITTALS A. Equipment Data: Attached "Equipment Data / Cut Sheet must be included. B. Shop Drawings: Include plans, sections, details, and connections to piping systems. C. Operation and Maintenance Data: Include operation and maintenance manuals. D. Warranty: Include all warranties. E. Maintenance: Include maintenance service agreement if available Performance Specifications for Copper Silver Ionisation Water Treatment Technology Page 1 of 7

2 F. Data Logs & Reporting: Include Internet address where data logging & reporting will be accessed by the end user. Temporary username and password must be provided to verify application claims. G. Past Installations: Document synopsis report to include a list of no less than 10 comparable installations in the last 5 years with: Project ID, geographical location, synopsis, model number, date commissioned, technology parameters, capacity, installation pictures. H. The technology manufacturer must provide a US-EPA registration number when applicable to the installation s geographical location. I. The manufacturing company will included a letter to certify that the proposed copper silver ionisation technology has been manufactured either in Canada, the USA or the UK. J. The manufacturing company will maintain at its expense Comprehensive General Liability Insurance. Commercial General Liability Insurance policy limits shall be not less than a Combined Single Limit for Bodily Injury, Property Damage, and Personal Injury Liability of $4,000,000 (USD) or $5,000,000 (CAN) per occurrence valid both in Canada and/or the USA. K. The manufacturing company will provide a post commissioning report example unique to their business. L. The manufacturing company will provide an on-site training agenda with topic descriptions and required class time. M. Letter of compliance to these performance specifications including original corporate ink stamp and signature. 1.4 QUALITY ASSURANCE A. Product Options: Include any drawings indicating size, profiles, and dimensional requirements of copper silver ion generators based on the specific system/configuration indicated. 1.5 COORDINATION A. Coordinate size and location of copper silver ion generators and controller(s). 1.6 WARRANTY A. 2 to 10 Years limited warranty on controller and 1 year pro-rated warranty for each individual ionisation chamber cell. The manufacturer will include standard form in which manufacturer agrees to repair or replace components of copper silver system that fail in materials or workmanship within specified warranty period. 1. Type of Failure: Include type of failures. 2. Warranty Period by component: From date of Substantial Completion: a. Ion Chamber Cell(s) (1 Year) b. Controller(s) (2 to 10 years) Performance Specifications for Copper Silver Ionisation Water Treatment Technology Page 2 of 7

3 PART 2 - PRODUCTS 2.1 ACCEPTED MANUFACTURERS / BRANDS a. AquaLyse / CSI Defender (Canada) by: ProCare Water Treatment Inc. WEB: Toll Free: +1 (888) FAX: support@portal-hub.com b. (USA) Available upon request by sending to: support@portal-hub.com c. (USA) Available upon request by sending to: support@portal-hub.com d. (UK) Available upon request by sending to: support@portal-hub.com 2.2 INDUSTRIAL SIZED COPPER SILVER ION GENERATORS SYSTEMS A. DESCRIPTION: ION CHAMBER CELL(S) 1. The ionisation chamber cell will be constructed of Schedule 40 stainless steel (or) powder coated aluminum to meet fire building codes and international plumbing codes when applicable. CPVC Schedule 80 Chamber cells will be allowed when building fire codes do not apply to said facility potable water distribution network.: (Mandatory) 2. Internal electrode protection engineering feature to prevent premature physical water related erosion when installed within a domestic hot water loop with continuous water circulation. Internal water turbulence prevention feature to prevent sedimentation and more frequent preventative maintenance cleaning: (Preferred) 3. The use of either Victaulic couplings or flange type connections: (Mandatory) 4. When multiple chamber cells are required, such ion chamber cells must be installed in parallel to each other and not end to end as to prevent ionic re-deposition: (Mandatory) 5. Ion Chamber Cells should be installed vertical position & at less than 6M / 18 from the controller when possible: (Preferred) 6. Safety activation flow switch or flow meter as proposed by the manufacturer s recommendation and application process. (Mandatory) 7. For 100% Facility Potable Water Applications: When installed for 100% facility potable water treatment applications: (No facility water storage), the manufacturer will include a properly sized commercial grade flow meter connected to the facility incoming water supply. The flow meter will provide a 4-20ma output signal to the automated ion controller for variable ionisation process. (Optional when manufacturer provides alternate monitoring & application methods) 8. For 100% Facility Potable Water Applications: When installed for 100% facility potable water treatment applications: (With facility water storage), and constant water flow rate, the provider will include either: A) a commercial grade flow meter connected to the facility water supply that will include a 4-20ma output signal connected to the ion controller for variable water flow ionisation control or B) a commercial grade activation flow switch connected to the facility water supply and calibration of the copper silver ion controller. (Mandatory for single or multiple tank parameters) Performance Specifications for Copper Silver Ionisation Water Treatment Technology Page 3 of 7

4 9. The system will include integrated dielectric ion chamber cell isolators (Optional) Revised: January 26, Must Identify type of waterproof engineering and pressure tolerance levels. Must also include the storage shelf life of the ionisation chamber cells. (Mandatory) 11. Minimum operational water pressures of between 40PSI to 200 PSI in any liquid water temperature or 33 F / 1 C up to 176 F / 80 C for a period of no less than 12 consecutive hours. (Mandatory) 12. Having a water flow capacity of up to 45 GPM each ion chamber cell (Mandatory) 13. Only one (1) ion chamber cell per automated amps / VDC drive or amps / VDC output: (Mandatory) 14. Electrode MSDS composition demonstrating alloy purity and trace elements present in the electrodes. Report must be by an independent 3 rd party. (Mandatory) 15. Provide NSF61 documentation on all wetted components. (Mandatory) 16. Usage lifespan (warranty) of the ionisation chamber cells must be associated to one (1) ion chamber cell only. Each chamber cell must be capable of treating no less than 20,000 US-GPD per day & last for a period of no less than 9 months. (Mandatory) 17. Replacement chamber cells Spare cells that extend the perceived warranty lifespan of an originally installed chamber cell will not be allowed. (Mandatory) 18. The internal electrodes will be composed of % pure copper (Cu) and 99.99% silver (Ag). (Mandatory) 19. The Cu and Ag alloy ratio will be no less than 90% Cu / 10% Ag and no more than 60% Cu / 40% Ag. The provider will indicate the composition of the proposed alloy. (Mandatory) 20. A 3 rd party laboratory alloy report will be supplied by the manufacturer at all times as to demonstrate both the alloy purity and impurity presence within the alloy. (Mandatory) 21. The solution will have less than 5 PSI drop in water pressure post treatment. (Mandatory) B. DESCRIPTION: FULLY AUTOMATED PID (COMPUTER & SOFTWARE) ION CONTROLLER 1. Required is a fully automated industrial grade (PID) copper silver ion generator capable of treating the required amount of daily potable water usage within the intended facility location: See project parameters for details (Mandatory) 2. Facility power source requirement will be (100 to 240 VAC) (Mandatory) 15 amps 25 amps 35 amps 45 amps 2x30 amps 2x40 amps 3. Output PLC/ software controller set-point capacity of 1 to 10 amps constant current for each individual ion chamber cell with a total controller capacity output of: (Mandatory) 10 amps 20 amps 30 amps 40 amps 60 amps 80 amps 4. The copper silver ionisation controller (s) must be able to generate via amperage set points between ppm Cu and ppm Ag within the DHW loop over existing pre-startup Cu and Ag values without going over the maximum acceptable limits of 1.0 ppm Cu (Canada) and 1.3 ppm Cu (USA). (Mandatory) Performance Specifications for Copper Silver Ionisation Water Treatment Technology Page 4 of 7

5 5. Upon startup, the ionisation controller must be calibrated in order to provide ionic the required CuAg saturation concentrations within 30 minutes or less. (Preferred) 6. The system will include 0 to 100 VDC or 0 to 180 VDC fully automated constant current set point variable power output drives for each ionisation chamber cell to maintain ion controller amperage set point(s) in any potable water conditions including high or low conductivity environments required: (Mandatory) 7. The system will include variable power drive(s) that are individually controlled and monitored by the Ion Controller and for each ion chamber cell(s). If multiple ion chamber cells are required, each cell will have its own individually controlled variable power drive that will all be controlled from either multiple controllers or one (1) common Ion Controller having independent ionisation cell control features: NOT ALLOWED: Multiple (twinning or tripling) ion chamber cells connected to one (1) common variable output DC drive is not permitted at any time. Ion chamber cells must have their own independent automated VDC drive controlled by one PLC. PLC controllers can be connected to multiple VDC power drives yet demonstrate independent control. (Mandatory) 8. Nema 4 or 12 Enclosure: (Mandatory) 9. Panel mounted electrical circuit breakers to each chamber cell: No fuses (Preferred) 10. User & administrative password protected features: (Preferred) 11. Front mounted UL/CSA listed load bearing PLC electrical breakers (electrical fuses not permitted): (Preferred) 12. Front mounted UL/CSA listed load bearing ion chamber cell electrical breakers (electrical fuses not permitted): (Preferred) 13. M20 water proof industrial access port: (1 to 8 based on requirements) (Preferred) 14. UL listed 10 amp / 600 V capacity electrical connectors: (Preferred) 15. Reverse Polarity Ionisation feature: (Optional) 16. PLC with touch screen or membrane type HMI interface: (Preferred) 17. PLC/HMI display of ionisation process variables in real time: (Mandatory) 18. Operational status LED Safety Light (Green/Yellow/Red/Flashing Red): (Preferred) 19. Operational alarm status to BMS / volt free contact, normally closed: (Mandatory) 20. Proper labeling of all front panel controller parts: (Mandatory) 21. External Safety power interruption: (Mandatory) 22. Provide a Windows based (or other), computer software for remote HMI login and management. (Preferred) 23. Remote PLC monitoring & management via TCP/IP connection: (Mandatory) 24. System must be UL 508 and CSA certified based on geographical installation location. (Mandatory) 25. Must be CE certified based on geographical installation location. (Mandatory) 26. Must include no less that 5 year warranty or more on controller(s) from date of commissioning / startup: (Mandatory) Performance Specifications for Copper Silver Ionisation Water Treatment Technology Page 5 of 7

6 27. Must be capable of providing additional analogue & digital I/O ports. (Optional) Revised: January 26, 2015 C. FLOW METRE (S) (OPTIONAL) 1. The proposed copper silver ionisation unit will have the option to include or omit the use of any PID flow meter device (AKA: Proportional Control) as a means to control the ionisation process based in technology engineering requirements and application protocols. (Optional) 2. In the event that a flow meter is utilized, said flow meter will be of either a: turbine type, or b: pallet type or c: magnetic / non-intrusive type. (Optional) 3. Should a flow meter be utilized, said flow meter will provide a 4-20 ma analogue signal to the copper silver ionisation controller. (Optional) 4. Should a flow meter be utilized, said flow meter will be calibrated in relation to both low and high water flow velocities in relation to a 4-20 ma signal. (Optional) D. FIELD COPPER TESTING KIT (MANDATORY) 1. Provide a LaMotte 1200 Colorimeter Copper test kit (or) Hach Pocket Colorimeter II digital display water testing colorimeter for copper with testing procedure instructions. PART 3 - QUALITY CONTROL & DATA LOGGING / REPORTING 3.1 QUALITY CONTROL (Mandatory) A. Provide a post-commissioning report signed by the manufacturing company. 3.2 WATER DATA LOGGING & REPORTING (PREFERRED) A. Provide on-line access to input / output (reporting) water sample data logging accessible by registered end users and/or a group of authorized users via a secured internet SSL connection. All data input variables will be identified by input date and data submission origin (username). Water data collection and reporting variable will include: locations, times, multiple copper values, water temperatures, comment area, and any other necessary type of variable associated to the technology used. 3.3 PREVENTATIVE MAINTENANCE DATA LOGGING & REPORTING (PREFERRED) A. Provide on-line access to input / output (reporting) and scheduled preventative maintenance data logging accessible by registered end users and/or a group of authorized users via a secured internet SSL connection. All data input variables will be identified by input date and data submission origin (username) and will include data entry items required such as: type of maintenance, location, site name, technology model number, mechanical room location, service tech name, and any other necessary type of variable associated to the technology used. PART 4 - EXECUTION 4.1 IMPLEMENTATION (MANDATORY) A. Describe implementation process. 4.2 CONNECTIONS (MANDATORY) A. Piping installation requirements: Include digital shop drawings to indicate general arrangement of piping, fittings, and specialties if any Performance Specifications for Copper Silver Ionisation Water Treatment Technology Page 6 of 7

7 B. Install piping adjacent to equipment to allow service and maintenance. 4.3 FIELD QUALITY CONTROL (MANDATORY) A. Manufacturer's Field Service: Engage a factory certified service representative to inspect, test, and adjust field-assembled components and equipment installation, including connections, and to assist in field-testing. Report results in writing via commissioning report within 15 days after commissioning. B. Perform the following field tests and inspections and prepare test reports: 1. Leak Test: After installation, charge system and test for leaks. Repair leaks and retest until no leaks exist. 2. Operational Test: After electrical circuitry has been energized, start units to confirm proper unit operation. 3. Test and adjust controls and safeties. Replace damaged and malfunctioning controls and equipment. C. Remove and replace malfunctioning copper silver ion generators that do not pass tests and inspections and retest as specified above. 4.4 STARTUP SERVICE (MANDATORY) A. Engage a factory certified service representative to perform startup service. Complete installation and startup checks according to manufacturer's written instructions. B. Commissioning. C. Prepare post-commissioning report for sign off by Owner or Owner representative. 4.5 ON-SITE TRAINING & DEMONSTRATION A. On-Site training by a manufacturer-authorized service representative for facility engineers on the operations, maintenance and on-going documentation requirements associated to the technology. Owner's maintenance personnel will be capable of: troubleshooting operational issues, proceed with water test for copper values, adjusting, operate, and maintain the copper silver ion generator(s), consult the manufacturing company at all times by or by phone without any charges imposed to the technology owners. B. The training seminar will be scheduled within the same startup & commissioning period. C. Attendance of the training seminar is mandatory by key facility engineers or maintenance personnel involved with the technology and attendance will be documented. **END** Performance Specifications for Copper Silver Ionisation Water Treatment Technology Page 7 of 7

TABLE 1. Rugged cast aluminum alloy casing,celcon waterways with nichrome parts White (unless stainless steel housing)

TABLE 1. Rugged cast aluminum alloy casing,celcon waterways with nichrome parts White (unless stainless steel housing) CHRONOMITE INSTANT-FLOW MICRO WATER HEATER INSTALLATION AND OPERATION INSTRUCTIONS - (LOW FLOW MODELS) (Before installation, compare electrical needed for the model of heater selected) TABLE 1 Model No.

More information

FTA1100-J DIESEL ENGINE FIRE PUMP CONTROLLERS STANDARD SUBMITTAL PACKAGE

FTA1100-J DIESEL ENGINE FIRE PUMP CONTROLLERS STANDARD SUBMITTAL PACKAGE FTA1100-J DIESEL ENGINE FIRE PUMP CONTROLLERS STANDARD SUBMITTAL PACKAGE SBP1100J FTA1100J Diesel Engine Fire Pump Controllers Product Description Description Firetrol combined automatic and manual Mark

More information

INSTALLATION AND OPERATION INSTRUCTIONS - (LOW FLOW MODELS) (Before installation, compare electrical needed for the model of heater selected)

INSTALLATION AND OPERATION INSTRUCTIONS - (LOW FLOW MODELS) (Before installation, compare electrical needed for the model of heater selected) CHRONOMITE INSTANT-FLOW WATER HEATER INSTALLATION AND OPERATION INSTRUCTIONS - (LOW FLOW MODELS) (Before installation, compare electrical needed for the model of heater selected) TABLE 1 Model No. Wattage

More information

E-Version SECTION 15318 - CHLORINATION SYSTEM PART 1 - GENERAL PART 2 - PRODUCT

E-Version SECTION 15318 - CHLORINATION SYSTEM PART 1 - GENERAL PART 2 - PRODUCT SECTION 15318 - CHLORINATION SYSTEM PART 1 - GENERAL 1.1. SCOPE OF WORK A. Under this item the Contractor shall furnish and install a sodium hypochlorite solution metering system complete with all accessories

More information

Oil and Coolant Circulating Heating System. Model - OCSM

Oil and Coolant Circulating Heating System. Model - OCSM Oil and Coolant Circulating Heating System Model - OCSM Installation & Operation Manual 216280-000 REV 2 Identifying Your System The HOTSTART heating system is designed to heat fluids for use in marine

More information

Sanitary Type Electronic Flow Switches

Sanitary Type Electronic Flow Switches Industries Pharmaceutical Sanitary Type Electronic Flow Switches Food and Beverage Biotechnology Semiconductor Water Treatment S Series Ameritrol, Inc. Instruments and Controls Features No Moving Parts

More information

! WARNING. Before using product, read and understand instructions.

! WARNING. Before using product, read and understand instructions. McDonnell & Miller Installation & Maintenance Instructions MM-600G) Series FS8-W General Purpose Liquid Flow Switch OPERATION This control is an independently mounted water flow sensing device that makes

More information

For Multi-Parameter Meters see mvx

For Multi-Parameter Meters see mvx BULLETIN BULLETIN EM20607 VORTEX IN-LINE FLOW METERS Design Features For Multi-Parameter Meters see m Principles of Operation n No moving parts to wear or fail. n Electronics can be remotely mounted up

More information

The Breather Box. High Performance Grade-D Breathing Air Filtration system. BB50-cO

The Breather Box. High Performance Grade-D Breathing Air Filtration system. BB50-cO The Breather Box High Performance Grade-D Breathing Air Filtration system Specifications Filter change Indicators Incoming Air Plug 1/2 Industrial Interchange 2 Automatic Drains with Discharge tubes 3

More information

Electronic Flow Switches

Electronic Flow Switches Industries Electronic Flow Switches Petrochemical Refining Oil Production Water Treatment Pharmaceutical Food and Beverage Pulp and Paper Power Production Gas Processing Mining Biotechnology Semiconductor

More information

POOL SUNSHINE IONIZER MODELS SPD, SPD2 AND SPS INSTALLATION INSTRUCTIONS

POOL SUNSHINE IONIZER MODELS SPD, SPD2 AND SPS INSTALLATION INSTRUCTIONS Sunshine Pool Products, LLC Manufacturer of Quality Pool & Spa Products 902 W 2010 S, Syracuse, Utah 84075 USA Voice: 801-825-4523 Website: www.sunshinepool.com Email: info@sunshinepool.com POOL SUNSHINE

More information

SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches

SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches PART 1 GENERAL 1.01 Scope Optional Standby Power Generator Systems A. Furnish and install automatic transfer switches

More information

In-Line Electronic Flow Switches

In-Line Electronic Flow Switches In-Line Electronic Flow Switches Industries Petrochemical Refining Oil Production Water Treatment Pharmaceutical Food and Beverage Pulp and Paper Power Production Gas Processing Mining Biotechnology Semiconductor

More information

Bussmann. All-In-One Module. Bussmann Power Module Switch. How to configure Part Numbers: Step 1: Select Switch Amperage 1

Bussmann. All-In-One Module. Bussmann Power Module Switch. How to configure Part Numbers: Step 1: Select Switch Amperage 1 How to configure Part Numbers: Step : Select Switch Amperage Power Module Switch Rating (Amps) Power Module Switch Catalog No. 30 3 60 6 00 200 2 400 4 Step 2: Select Options Needed 5 Bussmann Power Module

More information

Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000

Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000 Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000 Description Firetrol FTA1000 Full Voltage Fire Pump Controllers are intended for use with electric motor driven fi re pumps

More information

Recommended Product Specifications Fuel Day Tank System Tramont UTRS Fuel Day Tank

Recommended Product Specifications Fuel Day Tank System Tramont UTRS Fuel Day Tank Recommended Product Specifications Fuel Day Tank System Tramont UTRS Fuel Day Tank This specification describes requirements for a Diesel Fuel Day Tank System consisting of one or more fuel tanks, an Electronic

More information

PRODUCT PROFILE FEATURES

PRODUCT PROFILE FEATURES PRODUCT PROFILE Pressure Transmitters & Pneumatic Transducer Airflow Transmitter, Differential Air Pressure Transmitter and Differential & Gauge Liquid/Gas Pressure Transmitter FEATURES AIRFLOW TRANSMITTER

More information

Medical Air Systems: Scroll

Medical Air Systems: Scroll GENERAL The Chemetron skid mount scroll medical air system is designed to provide medical breathing air for hospital and medical institutions. This system meets NFPA 99 requirements for Level 1 breathing

More information

OPL BASIC. Dosing System for Professional Laundry machines. Contents

OPL BASIC. Dosing System for Professional Laundry machines. Contents OPL BASIC Dosing System for Professional Laundry machines Contents 1 Getting Started. Page 2 2 Installation. Page 4 3 Set Up & Operation. Page 8 4 Maintenance & Accessories. Page 10 5 Troubleshooting Page

More information

ASME Packaged Indirect Fired Water Heater

ASME Packaged Indirect Fired Water Heater Utilizes Or HTHW To Heat Domestic Water, Semi-Instantaneous or Storage Type Model BW Features Reliable Only high grade materials used in construction to ensure long operating life Hydrastone cement lining

More information

Residential/Commercial Gas Condensing High Efficiency Tankless Water Heaters

Residential/Commercial Gas Condensing High Efficiency Tankless Water Heaters Residential/Commercial Gas Condensing High Efficiency Tankless Water Heaters FEATURES ULTRA-LOW NOx CONDENSING TECHNOLOGY PROVIDES UNPRECEDENTED 0.95 ENERGY FACTOR DURABLE HEAT EXCHANGER Primary Heat Exchanger

More information

SOLARCARE SERIES PRODUCT AND APPLICATION GUIDE

SOLARCARE SERIES PRODUCT AND APPLICATION GUIDE SOLARCARE SERIES PRODUCT AND APPLICATION GUIDE for solar energy management LEATEC Delivering Solutions for Energy Management SOLAR ENERGY DATA CENTER BUILDING 4 to8 String Monitoring with 0.% Accuracy

More information

SECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL

SECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL SECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL 1.1 SUMMARY A. This section describes the requirements for the installation of Power Monitors and associated

More information

CalMod Design-Build Electrification Services

CalMod Design-Build Electrification Services SECTION 28 16 00 INTRUSION DETECTION SYSTEM PART 1 - GENERAL 1.1 DESCRIPTION A. This section describes the detailed technical requirements for the Intrusion Detection System (IDS), where the Contractor

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS LIGHTING CONTROL PANELS 4 AND 8 RELAYS INSTALLATION INSTRUCTIONS INSTALLATION OVERVIEW The installation instructions contained in this document are provided as a guide for proper and reliable installation.

More information

SECTION 26 29 23 VARIABLE FREQUENCY DRIVES

SECTION 26 29 23 VARIABLE FREQUENCY DRIVES SECTION 26 29 23 VARIABLE FREQUENCY DRIVES PART 1 GENERAL 1.01 SCOPE A. Furnish and install individual freestanding variable frequency AC drives (VFD) as shown on the Drawings and specified herein. 1.02

More information

PIEZOMETER AIRFLOW MEASURING RING

PIEZOMETER AIRFLOW MEASURING RING PIEZOMETER AIRFLOW MEASURING RING M.K. Plastics is pleased to introduce The Piezometer Airflow Measuring Ring, now available as an accessory for our steel Axijet fans. The system consists of a Piezometer

More information

SECTION 26 09 26 LOW VOLTAGE LIGHTING CONTROLS

SECTION 26 09 26 LOW VOLTAGE LIGHTING CONTROLS SECTION 26 09 26 LOW VOLTAGE LIGHTING CONTROLS PART 1 - GENERAL 1.01 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section

More information

A. Accessible Fixture: Emergency plumbing fixture that can be approached, entered, and used by people with disabilities.

A. Accessible Fixture: Emergency plumbing fixture that can be approached, entered, and used by people with disabilities. SECTION 224500 - EMERGENCY PLUMBING FIXTURES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

OWNER S MANUAL FORCE 10 MARINE COMPANY 23080 HAMILTON ROAD RICHMOND, BC CANADA V6V 1C9 TEL: (604) 522-0233 FAX: (604) 522-9608

OWNER S MANUAL FORCE 10 MARINE COMPANY 23080 HAMILTON ROAD RICHMOND, BC CANADA V6V 1C9 TEL: (604) 522-0233 FAX: (604) 522-9608 Electric Water Heater OWNER S MANUAL FORCE 10 MARINE COMPANY 23080 HAMILTON ROAD RICHMOND, BC CANADA V6V 1C9 TEL: (604) 522-0233 FAX: (604) 522-9608 If your water Heater is Damaged or you have questions

More information

Product Description Primary Resistance Starting Electric Fire Pump Controllers FTA1500

Product Description Primary Resistance Starting Electric Fire Pump Controllers FTA1500 Product Description Primary Resistance Starting Electric Fire Pump Controllers FTA1500 Description Firetrol FTA1500 Primary Resistance Fire Pump Controllers use resistors in the line to reduce line voltage

More information

Water Leak Detection System

Water Leak Detection System Water Leak Detection System Installation and Operating Manual 505-334-5865 ph 505-334-5867 fax www.rodisystems.com email:info@rodisystems.com 936 Highway 516 Aztec, NM 87410-2828 Manual Revisions and Copyright

More information

Pump_PT580. Optional. Optional. Modbus. Remote Reset Local Display PLC/DCS PT580-CFG PCM370 DTM96. Buffered Output. Dual Relay Output.

Pump_PT580. Optional. Optional. Modbus. Remote Reset Local Display PLC/DCS PT580-CFG PCM370 DTM96. Buffered Output. Dual Relay Output. Pump_PT580 Optional PT580-CFG PCM370 Optional DTM96 Buffered Dual Relay Remote Reset Local Display Condition Monitoring System PLC/DCS PT580 Digital Vibration Switch Introduction The PT580 Digital Vibration

More information

HL Series - Commercial Heaters Tankless Water Heating Solutions

HL Series - Commercial Heaters Tankless Water Heating Solutions HL Series - Commercial Heaters 5-18 kw (17,000-61,400 BTUs) Low flow activation options at.15 and.25 GPM (0.6 and 0.9 L-Min) Certified Lead-Free Design Variable Temp Heat Exchanger Pressure Drop Advantage

More information

key- precision Tecum cuil Ludere ipsae. Possem Precision level detection When space and price matter Pointek CLS 100

key- precision Tecum cuil Ludere ipsae. Possem Precision level detection When space and price matter Pointek CLS 100 Pointek CLS 100 Compact design and short insertion length. Ideal for constricted spaces and for small vessels or pipes up to 100 mm (4 ). Tecum cuil Ludere ipsae. Possem Precision level detection When

More information

SERVICE MANUAL RESIDENTIAL ELECTRIC AND LIGHT DUTY COMMERCIAL ELECTRIC WATER HEATERS. Troubleshooting Guide and Instructions for Service

SERVICE MANUAL RESIDENTIAL ELECTRIC AND LIGHT DUTY COMMERCIAL ELECTRIC WATER HEATERS. Troubleshooting Guide and Instructions for Service RESIDENTIAL ELECTRIC AND LIGHT DUTY COMMERCIAL ELECTRIC WATER HEATERS SERVICE MANUAL Troubleshooting Guide and Instructions for Service (To be performed ONLY by qualified service providers) Models Covered

More information

A Practical Guide to Free Energy Devices

A Practical Guide to Free Energy Devices A Practical Guide to Free Energy Devices Part PatE17: Last updated: 24th November 2006 Author: Patrick J. Kelly This is a patent application from Stephen Meyer, brother of the late Stan Meyer. While this

More information

A. Accessible Fixture: Emergency plumbing fixture that can be approached, entered, and used by people with disabilities.

A. Accessible Fixture: Emergency plumbing fixture that can be approached, entered, and used by people with disabilities. SECTION 224500 - EMERGENCY PLUMBING FIXTURES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

SECTION 13XXX DISPERSAL PUMP STATION (4x4 DiPS)

SECTION 13XXX DISPERSAL PUMP STATION (4x4 DiPS) SECTION 13XXX DISPERSAL PUMP STATION (4x4 DiPS) PART 1: GENERAL 1.01 SCOPE OF WORK A. Under this section of the specifications, the contractor shall furnish and install a shop-fabricated 4X4 Dispersal

More information

Domestic Hot Water Systems and Plumbing Products

Domestic Hot Water Systems and Plumbing Products Domestic Hot Systems and Plumbing Products Taco Catalog #100-117 Effective Date: 09/02/15 Supersedes: 06/22/15 Printed in USA Domestic Hot Recirculation Taco Domestic Hot Plumbing Products Since 1920 Taco

More information

Commercial Semi-Instantaneous Water Heaters

Commercial Semi-Instantaneous Water Heaters FEATURES HWI Models A. O. Smith s HWI models are available for operation with steam or boiler water as the energy source. They are factory assembled with components sized, piped and checked at the factory

More information

MR221-MR222 Heavy Duty Geared Limit Switches, CE Approved

MR221-MR222 Heavy Duty Geared Limit Switches, CE Approved MR221-MR222 Heavy Duty Geared Limit Switches, CE Approved MICRONOR automation components Product MICRONOR MR221 and MR222 series Heavy Duty Geared Limit Switches are for use in the most demanding industrial

More information

LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA. General Specification

LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA. General Specification 08/17/12 Rev2 LTR Series General Specification 700 VA to 2.1 KVA 1.0 General LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA General Specification This specification describes the features and

More information

MTI10 Insertion and MTL10 In-line Thermal Mass Flowmeter and Temperature Transmitter

MTI10 Insertion and MTL10 In-line Thermal Mass Flowmeter and Temperature Transmitter Thermal Mass meter and Temperature Transmitter Description The MTI10 insertion thermal mass flowmeter and the MTL10 in-line thermal mass flowmeter provide accurate mass flow measurement of clean, dry gases

More information

Electrodeionization (EDI)

Electrodeionization (EDI) Electrodeionization (EDI) Fact Sheet Cal Water Industrial Water Purification (800) CAL-WATER EDI is a continuous electro-chemical process of water purification where ion specific membranes, mixed bed resin,

More information

Case Study - University at Buffalo State University of New York. Lower Energy Usage Costs with Real Time Monitoring, Campus-wide

Case Study - University at Buffalo State University of New York. Lower Energy Usage Costs with Real Time Monitoring, Campus-wide Case Study - University at Buffalo State University of New York Lower Energy Usage Costs with Real Time Monitoring, Campus-wide Reduce Energy Consumption through Awareness of Energy Use Analyze Power Quality

More information

SECTION 23 81 43 HEAT PUMPS

SECTION 23 81 43 HEAT PUMPS SECTION 23 81 43 HEAT PUMPS PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop heat pumps. 1.2 REFERENCES A. American Society of Heating, Refrigerating and Air-Conditioning Engineers:

More information

InHome Water Leak Detection Package

InHome Water Leak Detection Package InHome Water Leak Detection Package For Model Numbers ILD10A-L and ILD10A-B Installation Guide / Wiring Diagram For Creating Water Leak Detection-based Events with Line-Powered or Battery-Powered Sensors

More information

User Manual for CH-PFC76810

User Manual for CH-PFC76810 AA Portable Power Corp www.batteryspace.com, Email: Sales@batteryspace.com User Manual for CH-PFC76810 1. Overview The CH-PFC76810 charger is suitable for charging lithium ion battery packs such as those

More information

NRG. Intelligent Engine Start Battery Charger. The Smart Choice for Mission-Critical Engine Starting

NRG. Intelligent Engine Start Battery Charger. The Smart Choice for Mission-Critical Engine Starting NRG Intelligent Engine Start Battery Charger The Smart Choice for Mission-Critical Engine Starting Fast, accurate, mission-critical charging gives best starting reliability 4-rate, temperature-compensated

More information

VARIABLE FREQUENCY DRIVES Revised 4/30/2015 23 81 07-1 Mechanical Systems

VARIABLE FREQUENCY DRIVES Revised 4/30/2015 23 81 07-1 Mechanical Systems SECTION 23 81 07 - VARIABLE FREQUENCY DRIVES PART 1 - GENERAL 1.1 SUMMARY A. This section includes all variable frequency drives. All standard and optional features shall be included within the VFD panel

More information

CONTROL PANEL INSTALLATION INSTRUCTIONS. Single Phase Simplex Page 2-7. 3-Phase Simplex Page 8-13

CONTROL PANEL INSTALLATION INSTRUCTIONS. Single Phase Simplex Page 2-7. 3-Phase Simplex Page 8-13 CONTROL PANEL INSTALLATION INSTRUCTIONS Single Phase Simplex Page 2-7 3-Phase Simplex Page 8-13 Single Phase Simplex SXL21=3, SXL24=3, SXH21=3, and SXH24=3 Manufactured by SJE-Rhombus Installation Instructions

More information

O C M III. Open Channel Flow Monitor

O C M III. Open Channel Flow Monitor O C M III Open Channel Flow Monitor Part 1. General 1.1 Scope A. This section describes the requirements for an ultrasonic flow transmitter with sensor and temperature compensation probe. B. Under this

More information

Cathodic Protection Use On Tank Bottoms & Underground Piping In Power Generation Plants

Cathodic Protection Use On Tank Bottoms & Underground Piping In Power Generation Plants Cathodic Protection Use On Tank Bottoms & Underground Piping In Power Generation Plants PG&E Office San Francisco January 18, 2007 Craig K. Meier Corrosion Control Incorporated Corrosion process for tanks

More information

Utility Distribution Systems

Utility Distribution Systems Utility Distribution Systems 6/2012 A0011037 1 WARRANTY This equipment is warranted to be free from defects in materials and workmanship, under normal use and service, for a period of 12 months from date

More information

prestige Condensing Water Boiler SERVICE TECHNICIAN S TROUBLE SHOOTING GUIDE 2008-36 TSG-PRESTIGE Date revised: 12/6/10

prestige Condensing Water Boiler SERVICE TECHNICIAN S TROUBLE SHOOTING GUIDE 2008-36 TSG-PRESTIGE Date revised: 12/6/10 prestige Condensing Water Boiler SERVICE TECHNICIAN S TROUBLE SHOOTING GUIDE Date revised: 12/6/10 2008-36 TSG-PRESTIGE Table of Contents INTRODUCTION Page 1-2 SERVICING TIPS AND INSTRUCTIONS Page 3-4

More information

All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.

All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations. DIVISION 16 ELECTRICAL SECTION 16100 - ELECTRICAL PART 1 - GENERAL SCOPE All electrical work as shown on the drawings and as necessary to provide a complete electrical system. Include primary service,

More information

D Youville College July 31, 2008 New Academic Building Cannon Design Project No. 002935.00

D Youville College July 31, 2008 New Academic Building Cannon Design Project No. 002935.00 SECTION 22 6119 - COMPRESSED-AIR EQUIPMENT FOR LABORATORY AND HEALTHCARE PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged, oilless scroll air compressors. 1.2 DEFINITIONS A. Actual Air: Air

More information

SPECIFICATION DIVISION 22 SECTION DESCRIPTION DIVISION 22 PLUMBING SECTION 220519 - THERMOMETERS, PRESSURE GAUGES, AND ACCESSORIES

SPECIFICATION DIVISION 22 SECTION DESCRIPTION DIVISION 22 PLUMBING SECTION 220519 - THERMOMETERS, PRESSURE GAUGES, AND ACCESSORIES ARCHITECTURE, ENGINEERING AND CONSTRUCTION P00000000 0000 DOCUMENTS ARCHITECTURE & ENGINEERING 326 East Hoover, Mail Stop B Ann Arbor, MI 48109-1002 Phone: 734-764-3414 Fax: 734-936-3334 SPECIFICATION

More information

Pump Specifications 250 Series Submersible Sump / Effluent Pump 2 Solids handling

Pump Specifications 250 Series Submersible Sump / Effluent Pump 2 Solids handling Pump Specifications 250 Series Submersible Sump / Effluent Pump 2 Solids handling 250_P1 R10/7/2015 Copyright 2015 Liberty Pumps Inc. All rights reserved. Specifications subject to change without notice.

More information

Commercial Electric Water Heater

Commercial Electric Water Heater MODEL SE Commercial Electric Water Heater 6-120 Gallon Capacity, up to 58 KW in all Three Phase Voltages, Over 6 KW in all Single Phase Voltages Features Heavy Duty Construction Hydrastone cement lining

More information

FFI. Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars. Presented By: Greg Pelster & Robert Schmid

FFI. Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars. Presented By: Greg Pelster & Robert Schmid Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars Presented By: Greg Pelster & Robert Schmid FFI Ferrie, Franzmann Industries LOW VOLTAGE SWITCHGEAR & LOW VOLTAGE

More information

Series 510 Submersible Level Transmitters

Series 510 Submersible Level Transmitters Series 510 Submersible Level Transmitters The Series 510 Submersible Level Transmitters are solid state instruments designed for direct submergence into many types of liquid for quick, accurate and reliable

More information

PART 8: FIELD WIRING. n WARNING NOTICE. Boiler Manual

PART 8: FIELD WIRING. n WARNING NOTICE. Boiler Manual PART 8: FIELD WIRING A. INSTALLATION MUST COMPLY WITH: 1. National Electrical Code and any other national, state, provincial or local codes or regulations. 2. In Canada, CSA C22.1 Canadian Electrical Code

More information

ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL

ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL RANCO INSTALLATION INSTRUCTIONS ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL Relay Electrical Ratings PRODUCT DESCRIPTION The Ranco ETC is a microprocessor-based family of electronic temperature controls,

More information

SERIES 12-600 VOLT ELECTRIC INSTANTANEOUS WATER HEATER FOR EMERGENCY SAFTEY EQUIPMENT INSTALLATION AND OWNERS MANUAL REQUIRED MANTENANCE

SERIES 12-600 VOLT ELECTRIC INSTANTANEOUS WATER HEATER FOR EMERGENCY SAFTEY EQUIPMENT INSTALLATION AND OWNERS MANUAL REQUIRED MANTENANCE Eemax Inc., 353 Christian Street, Oxford, CT 06478 1 E ema X SERIES 12-600 VOLT ELECTRIC INSTANTANEOUS WATER HEATER FOR EMERGENCY SAFTEY EQUIPMENT INSTALLATION AND OWNERS MANUAL REQUIRED MANTENANCE WARNING

More information

Specification Requirements DBL 700MX and 1000MX Series UPS

Specification Requirements DBL 700MX and 1000MX Series UPS Specification Requirements DBL 700MX and 1000MX Series UPS Theory of Operation Upon loss of utility power, the UPS inverter shall continue to provide seamless pure sine-wave AC from the batteries without

More information

EDD-600 FLOW TOTALIZER RATE INDICATOR OPERATION MANUAL. P.O. Box 12128 Odessa, Texas 79768 USA. E-mail rkw@eddevices.com.

EDD-600 FLOW TOTALIZER RATE INDICATOR OPERATION MANUAL. P.O. Box 12128 Odessa, Texas 79768 USA. E-mail rkw@eddevices.com. OPERATION MANUAL EDD-600 FLOW TOTALIZER RATE INDICATOR Phone 432-366-8699 Fax 432-366-1106 P.O. Box 12128 Odessa, Texas 79768 USA E-mail rkw@eddevices.com Website www.eddevices.com 3 EDD-600 Digital Battery

More information

Nordic Heat Pump Product Guide

Nordic Heat Pump Product Guide Nordic Heat Pump Product Guide About Maritime Geothermal Maritime Geothermal is a privately owned, Canadian based manufacturer of geothermal heat pumps. We began manufacturing the Nordic line of heat pumps

More information

NC State University Design and Construction Guidelines Division 26 Fire Alarm Systems

NC State University Design and Construction Guidelines Division 26 Fire Alarm Systems NC State University Design and Construction Guidelines Division 26 Fire Alarm Systems 1.0 Purpose A. The following guideline provides the minimum standards and requirements for fire alarm systems. 2.0

More information

Brooks Models SLA5850, SLA5851, SLA5853 Mass Flow Controllers and Models SLA5860, SLA5861, SLA5863 Mass Flow Meters

Brooks Models SLA5850, SLA5851, SLA5853 Mass Flow Controllers and Models SLA5860, SLA5861, SLA5863 Mass Flow Meters Data Sheet Brooks Digital MFC's & MFM's Brooks Models SLA5850, SLA5851, SLA5853 Mass Flow Controllers and Models SLA5860, SLA5861, SLA5863 Mass Flow Meters GENERAL FEATURES Wide FS flow range for measurement

More information

Electronics Ltd. Presenting. Power, Intelligence... with a sense of feeling

Electronics Ltd. Presenting. Power, Intelligence... with a sense of feeling Electronics Ltd Presenting Power, Intelligence... with a sense of feeling By Appointment to Her Majesty The Queen Supplier of Fire Detection Equipment Kentec Electronics Ltd. Dartford Plug in slots K772

More information

98371000 REV. REL 1302 WEST BEARDSLEY AVENUE P.O. BOX 1127 ELKHART IN 46515 (574) 295-8330 FAX (574) 293-9914 2011 ELKHART BRASS MFG. CO., INC.

98371000 REV. REL 1302 WEST BEARDSLEY AVENUE P.O. BOX 1127 ELKHART IN 46515 (574) 295-8330 FAX (574) 293-9914 2011 ELKHART BRASS MFG. CO., INC. 81471067 Electric Monitor Motor Control Panel For use with Model 8394059 SPIT-FIRE Monitor Installation, Operation, and Maintenance Instructions FOR ATEX APPLICATIONS 1302 WEST BEARDSLEY AVENUE P.O. BOX

More information

FCI M180 Series: Custom Engineered Flow and Level Sensors for OEM Applications

FCI M180 Series: Custom Engineered Flow and Level Sensors for OEM Applications FCI M180 Series: Custom Engineered Flow and Level Sensors for OEM Applications Flow Measurement Flow Switches Level Switches Level Interface Switches FCI OEM SERIES Industrial Machinery Chemical Injection

More information

Operational Overview and Controls Guide. Two or Three Pump IronHeart Lite with Variable Frequency Drives

Operational Overview and Controls Guide. Two or Three Pump IronHeart Lite with Variable Frequency Drives DOCUMENT: ECSEQ6-0 EFFECTIVE: 09/23/10 SUPERSEDES: Operational Overview and Controls Guide Two or Three Pump IronHeart Lite with Variable Frequency Drives 6700 Best Friend Road. Norcross, GA 30071. (770)

More information

PowerCommand Paralleling System Digital MasterControl

PowerCommand Paralleling System Digital MasterControl PowerCommand Paralleling System Digital MasterControl Description The PowerCommand Digital MasterControl is a systemlevel controller designed to interface directly with Cummins Power Generation PowerCommand

More information

D. Infrared scanning reports with pictures printed in a final report with any deficiencies and actions taken to rectify.

D. Infrared scanning reports with pictures printed in a final report with any deficiencies and actions taken to rectify. SECTION 263354 STATIC UPS TESTING AND COMMISSIONING PART 1 - GENERAL 1.1 SUMMARY A. Section Includes 1. System start-up services. 2. Battery charging. 3. Load bank testing. 4. Battery load testing. 5.

More information

Design & Construction Standards, Revised January 2013 5.21.30-1

Design & Construction Standards, Revised January 2013 5.21.30-1 PART 1 GENERAL 1.01 Scope of Standard A. This standard provides general requirements of The University of Texas at Austin for fire pumps. This document is not intended to serve as a guide specification.

More information

User s Manual Before using the inverter, you need to read and save the safety instructions.

User s Manual Before using the inverter, you need to read and save the safety instructions. User s Manual Before using the inverter, you need to read and save the safety instructions. STI SERIES (STI200, STI300, STI500, STI700, STI1000) Power Frequency Pure Sine Wave Inverter The information

More information

RESIDENTIAL HEATING OIL SERVICE CONTRACT ANNUAL COST $276.00

RESIDENTIAL HEATING OIL SERVICE CONTRACT ANNUAL COST $276.00 RESIDENTIAL HEATING OIL SERVICE CONTRACT This service contract covers all routine service and maintenance of your residential oil fired furnace or boiler. In addition this contract covers all service calls

More information

Installation and Operation Guide for PD4000 Series Power Control Center

Installation and Operation Guide for PD4000 Series Power Control Center Extended warranties are available for purchase at www.progressivedyn.com Installation and Operation Guide for PD4000 Series Power Control Center Member Thank you for selecting Progressive Dynamics as your

More information

4-Wire Air Duct Smoke Detector. Protection Systems. A UTC Fire & Security Company. Models DH-60 FEATURES APPLICATION DESCRIPTION SAMPLING TUBES

4-Wire Air Duct Smoke Detector. Protection Systems. A UTC Fire & Security Company. Models DH-60 FEATURES APPLICATION DESCRIPTION SAMPLING TUBES 4-Wire Air Duct Smoke Detector Models DH-60 F-70.05 FEATURES Approvals/Listing UL 268A Listed File S1064 Factory Mutual Approved CSFM Listed #3240-1076:121 NYC MEA Listed #134-95-E City of Los Angeles

More information

Comfort Control Relay Panel (CCRP)

Comfort Control Relay Panel (CCRP) CCRP9 "Commitment to Innovation" OPERATION & INSTALLATION GUIDE FOR Comfort Control Panel (CCRP) Off-Peak System Control 9 Pole CCRP 4 Pole CCRP (Applicable to Software Version 14.0-14.9) "Manufactured

More information

D. Open hydronic systems, including [condenser] [fluid-cooler spray] water, shall have the following water qualities:

D. Open hydronic systems, including [condenser] [fluid-cooler spray] water, shall have the following water qualities: SECTION 232500 - PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following HVAC water-treatment systems: 1. Open Loop Chemical Treatment Systems. 2. Closed Loop Chemical Treatment Systems. 3.

More information

OASIS-PLUS 120V READ ALL INSTRUCTIONS BEFORE OPERATING READ ALL INSTRUCTIONS BEFORE OPERATING OZONE IS A POWERFUL OXIDIZER AND MUST BE USED WITH CARE

OASIS-PLUS 120V READ ALL INSTRUCTIONS BEFORE OPERATING READ ALL INSTRUCTIONS BEFORE OPERATING OZONE IS A POWERFUL OXIDIZER AND MUST BE USED WITH CARE OASIS-PLUS 120V INFORMATION & OPERATING INSTRUCTIONS READ ALL INSTRUCTIONS BEFORE OPERATING READ ALL INSTRUCTIONS BEFORE OPERATING OZONE IS A POWERFUL OXIDIZER AND MUST BE USED WITH CARE 56041852 WARNING:

More information

Centro-Matic Automatic Lubrication Systems System Controls

Centro-Matic Automatic Lubrication Systems System Controls Selecting the right controls for your automated lubrication system is one of the last steps in the design process. Several different models may be chosen to control power-operated pumps, depending on the

More information

RI-215A Operator s Manual. Part Number: 71-0045RK Revision 0 Released: 10/3/05

RI-215A Operator s Manual. Part Number: 71-0045RK Revision 0 Released: 10/3/05 RI-215A Operator s Manual Part Number: 71-0045RK Revision 0 Released: 10/3/05 Warranty RKI Instruments, Inc., warrants gas alarm equipment sold by us to be free from defects in materials and workmanship,

More information

OPERATING INSTRUCTIONS

OPERATING INSTRUCTIONS PIPELINE INSPECTION COMPANY LTD. OPERATING INSTRUCTIONS Wet Sponge Holiday Detectors 670,673, and MSRB Wet Sponge Holiday Detectors Portable and In-Plant Detectors Table of Contents General Information.......................3

More information

Installation Instructions for Solar Pumps USER MANUAL FOR SPS, SPC, SPSC SPQB, SPGJ SERIES SOLAR PUMPS AND PUMP CONTROLLERS

Installation Instructions for Solar Pumps USER MANUAL FOR SPS, SPC, SPSC SPQB, SPGJ SERIES SOLAR PUMPS AND PUMP CONTROLLERS Installation Instructions for Solar Pumps USER MANUAL FOR SPS, SPC, SPSC SPQB, SPGJ SERIES SOLAR PUMPS AND PUMP CONTROLLERS PO Box 80, Tuakau 2342 ph 0800 14 48 65 e-mail: hunkin-garden@xnet.co.nz www.hunkin.co.nz

More information

Digital I/O: OUTPUT: Basic, Count, Count+, Smart+

Digital I/O: OUTPUT: Basic, Count, Count+, Smart+ Digital I/O: OUTPUT: Basic, Count, Count+, Smart+ The digital I/O option port in the 4-Series provides us with 4 optically isolated inputs and 4 optically isolated outputs. All power is supplied externally.

More information

SECTION 16999 ELECTRICAL ACCEPTANCE TESTS

SECTION 16999 ELECTRICAL ACCEPTANCE TESTS SECTION 16999 ELECTRICAL ACCEPTANCE TESTS PART 1 2. AND 3. COMBINED 1.1 SUMMARY A. Description of Systems 1. Furnish all labor, materials, test equipment, and technical supervision to perform and record

More information

Medical Vacuum Systems-PXMI

Medical Vacuum Systems-PXMI Medical Vacuum Systems-PXMI Please read and save these instructions. Read carefully before attempting to assemble, install, operate or maintain the product described. Protect yourself and others by observing

More information

G4 Digital DC Output Modules. G4 Digital DC Output Modules. Features. Description. Part Numbers

G4 Digital DC Output Modules. G4 Digital DC Output Modules. Features. Description. Part Numbers Features volts opticalisolation (transient) Built-in LED status indicator Logic levels of 5, 5, and 4 VDC Removable fuse Ability to withstand one-second surge of 5 amps Operating temperature: -0 C to 70

More information

DTW Works Master Specification Version 2006

DTW Works Master Specification Version 2006 Issued 2006/08/01 Section 13852 Multiplex Fire Alarm System Page 1 of 10 PART 1 GENERAL 1.1 RELATED WORK.1 Section 01330 Submittal Procedures..2 Section 01780 Closeout Procedures..3 Section 01810 Commissioning..4

More information

Scraper Passage Indicator. Electrical Indicator. Features

Scraper Passage Indicator. Electrical Indicator. Features IV Scraper Passage Indicator Bulletin No: 5110.001.03 Date: June 2008 Cross Indexing No: n/a Supersedes: 5110.001.02 (1/06) Flag Indicator Electrical Indicator Options Description TDW s IV Scraper Passage

More information

Installation and Operating Instructions Installation Instructions for SS EPE-316L Series

Installation and Operating Instructions Installation Instructions for SS EPE-316L Series INSTR3010 0406 Installation and Operating Instructions Installation Instructions for SS EPE-316L Series Congratulations on your purchase of this Aqua-Pure high flow, single housing filtration system. This

More information

Energy Depot GmbH PRODUCT AND APPLICATION GUIDE. Total Monitoring Solution for PV. Delivering Solutions for Energy Management

Energy Depot GmbH PRODUCT AND APPLICATION GUIDE. Total Monitoring Solution for PV. Delivering Solutions for Energy Management Energy Depot GmbH Delivering Solutions for Energy Management PRODUCT AND APPLICATION GUIDE Total Monitoring Solution for PV SOLAR LOGGER & ANALYSIS DC STRING MONITORING Residential Comprehensive Solar

More information

The table below lists the symbols used on the Clamp and/or in this manual. Important Information. See manual.

The table below lists the symbols used on the Clamp and/or in this manual. Important Information. See manual. i800 AC Current Clamp Instruction Sheet Introduction The i800 AC Current Clamp, the Clamp, has been designed for use with multimeters, recorders, power analyzers, safety testers, etc., for accurate non-intrusive

More information

SECTION 13XXX CONTROL DESCRIPTION (DICP Models 02-412NC, 412, 622, 826, 1030)

SECTION 13XXX CONTROL DESCRIPTION (DICP Models 02-412NC, 412, 622, 826, 1030) PART 1 - GENERAL SECTION 13XXX CONTROL DESCRIPTION (DICP Models 02-412NC, 412, 622, 826, 1030) 1.01 SUMMARY This section describes the operation and control of a drip irrigation system. The major components

More information

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Metering and Monitoring. Basis of Design

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Metering and Monitoring. Basis of Design Basis of Design This section applies to the design, installation and integration of metering and monitoring equipment, including: hardware installed in the electrical service and distribution equipment,

More information