Flame Conductivity VS Flame Rectification Systems

Size: px
Start display at page:

Download "Flame Conductivity VS Flame Rectification Systems"

Transcription

1 Flame Conductivity VS Flame Rectification Systems There are two basic principles in flame rod detection systems-flame conductivity and flame rectification. Conductivity systems are, for the most part no longer used. Either type of system depends on the ability of the flame to conduct current when a voltage is applied across 2 electrodes in the flame. Heat from the flame causes molecules between the electrodes to collide with each other so forcibly as to knock some electrons out of the atoms, producing ions. This is called flame ionization. Positively charged ions flow to the negatively charged electrode; negatively charged electrons flow to the positively charged electrode. In a 60 Hz system, it changes its direction (polarity) 120 times a second. At one instant, one of the electrodes is positive, and 1/120 of a second later it is negative. As the voltage changes polarity, the flame current (ion flow) will change direction. For a conductivity system, the areas of the 2 electrodes (called flame and ground electrodes) are equal and the flame current between them is the same in both directions. This is the principle of a conductivity system. When an ac voltage is applied across the flame electrode and the ground electrode, alternating current proportional to the applied voltage flows through the flame. Because the flame current in a conductivity system is ac, this system cannot differentiate between a leakage current and an actual flame current. It is possible for the system to falsely indicate the presence of a flame (with possibly dangerous results) if the flame electrode is shorted to ground through a leakage circuit with about the same resistance as the impedance of a flame. A carbon deposit on the base of the flame electrode could form a very effective leakage path and cause a false flame indication. (A direct short of low impedance would, of course, make the system inoperative.)

2 The flame rectification system also uses 2 electrodes, but with 1 important difference-the ground electrode is always designed to be much larger than the flame electrode (flame rod). For effective operation, the area of the ground electrode must be at least 4 times that of the flame rod. Usually, the ground electrode will be the burner bead. Because of the difference in electrode size, more current flows in one direction than in the other.

3

4 With the current in one direction so much larger than the current in the other direction, the resultant current is, effectively, a pulsating direct current which operates the electronic network. The flame relay pulls in, indicating the presence of a flame and allowing the burner sequence to continue. The larger the ratio of ground area to flame electrode area, the greater the flow of current in the proper direction-in other words, a rectified current. Only the ionized path through a flame and the different sized electrodes can provide the rectified current required for the operation of the electronic network in a rectification system. Should a high resistance leakage to ground occur in the flame circuit, it sends an ac signal into the network, and the system shuts down safely. The rectification system does recognize the difference between a high resistance leakage to ground and the presence of a flame. The flame current is measured in microamps. Normal microamps would be 2 to 10. Viessmann Vitodens 200 W, WB2B Lamda-Pro System The same principle that is applied to flame rectification is used with Lamda-Pro. The ionization of the atmosphere in and around the flame is used to create a microamp signal for the microprocessor to process and determine it is safe to allow the main gas valve to open allowing gas to flow and burners to light safely. The Ionization Rod inserted into the Matrix burner flame sends a microamp signal (flame signal) similar to the standard signal used for electric ignition gas systems. The Vitodens by establishing a Lamda relationship between the air and gas mixture it can in a fully automatic way control/manage the gas and air ratio. The Lambda-Pro System allows control of gas and air independently of each other to ensure optimum combustion with varying operating conditions and also fuel qualities. The Flame Ionization Electrode is used as the Lambda sensor (no other components required). The air (30% excess air) and the gas flow rates are independently controlled by the Electronic Boiler Control Unit.

5 The ionization sensing rod needs to be kept clean as is always the case. The microamp signal is used to electronically control the firing rate of the gas valve. This again ensures optimum performance at all times. The fuel flow is checked against the optimum flame signal and correct Lambda setting is determined for each current burner cycle. There is no derating required at higher altitudes. You would however have to have the correct coding card installed. The Vitotronic Control provides flame safety function plus the Lambda- Pro it is also the Main Programmable Temperature Controller. As an example of what might happen is the uncontaminated fresh air for combustion was somehow contaminated. An example with the coaxial venting arrangement a cross contamination of products of combustion getting into the air side of the co-axial vent. This would cause a poor reading on the ionization rod and would trigger an immediate reaction because you are beyond the parameters set within the control and the boiler would go off and you would have an E9 code. This is burner in fault. The troubleshooting for an E9 fault code states that the ionization current lies outside the permissible range during calibration. The corrective action is to check the rod and the cable. It also states to check for venting system leaks. In the initial start up steps it is required to check at the vent pipe adapter which has two measuring ports, one for combustion air-intake and one for flue gas measurement. CO2 level allowed in the air intake is no higher than 0.2% and O2 no lower than 20.6% (20.9% is normal O2 content in air).

6

7

Fossil fuel heating equipment

Fossil fuel heating equipment Fossil fuel heating equipment principles and troubleshooting techniques Application Note This application note was written to provide you with an understanding of the basic principles of fossil fuel heating

More information

G670 Intermittent Pilot Ignition Controls

G670 Intermittent Pilot Ignition Controls Installation Sheets Manual 121 Gas Combustion Combination Controls and Systems Section G Technical Bulletin Issue Date 0300 Intermittent Pilot Ignition Controls Figure 1: Intermittent Pilot Ignition Control

More information

Vitodens 200, B2HA / B2HB - Product Introduction

Vitodens 200, B2HA / B2HB - Product Introduction - Product Introduction Foil 2, 10/2015 Viessmann Manufacturing Wall Mounted, Gas-Fired Condensing Boiler Foil 3, 10/2015 Viessmann Manufacturing A member of the Viessmann family of heating products Condensing

More information

1/11 CO2 DOSAGE SYSTEMS. CO2 dosage system consists of following parts;

1/11 CO2 DOSAGE SYSTEMS. CO2 dosage system consists of following parts; 1/11 CO2 DOSAGE SYSTEMS CO2 dosage system consists of following parts; 1 - O2 trim system with micro processing burner (automatic combustion monitoring), 2 - Other components of O2 trim system, 3 - CO2

More information

TECHNICAL SERVICE DEPARTMENT Technical Service Bulletin 1-800-432-8373. 2 Inch PowerVent LED Indicator Explanations & Troubleshooting Table

TECHNICAL SERVICE DEPARTMENT Technical Service Bulletin 1-800-432-8373. 2 Inch PowerVent LED Indicator Explanations & Troubleshooting Table New Robertshaw control valve was introduced in May 2008 as a replacement part. See last page for troubleshooting this replacement part. All voltage inputs are 120V. All electrical connectors are Molex

More information

E - THEORY/OPERATION

E - THEORY/OPERATION E - THEORY/OPERATION 1995 Volvo 850 1995 ENGINE PERFORMANCE Volvo - Theory & Operation 850 INTRODUCTION This article covers basic description and operation of engine performance-related systems and components.

More information

http://waterheatertimer.org/how-to-troubleshoot-gas-water-heater.html

http://waterheatertimer.org/how-to-troubleshoot-gas-water-heater.html http://waterheatertimer.org/how-to-troubleshoot-gas-water-heater.html TECHNICAL SERVICE DEPARTMENT Effective October 2007, we transitioned to the White Rodgers (Intelli-Vent TM )Thermostat Control for

More information

LMS The modular management system for condensing boilers. Control Products & Systems OEM. Answers for infrastructure.

LMS The modular management system for condensing boilers. Control Products & Systems OEM. Answers for infrastructure. LMS The modular management system for condensing boilers Control Products & Systems OEM Answers for infrastructure. LMS advanced electronics and proven software At times of dwindling resources, rising

More information

TOBY DVR5 OIL CONTROL & SAFETY VALVE

TOBY DVR5 OIL CONTROL & SAFETY VALVE TOBY DVR5 OIL CONTROL & SAFETY VALVE TECHNICAL HANDBOOK Principle of Operation The Toby DVR5 Oil Control Valve is a multi function unit for maintaining a constant oil level, regulating the oil flow and

More information

http://waterheatertimer.org/how-to-troubleshoot-gas-water-heater.html

http://waterheatertimer.org/how-to-troubleshoot-gas-water-heater.html http://waterheatertimer.org/how-to-troubleshoot-gas-water-heater.html APPLY POWER TO APPLIANCE FIELD WIRING CORRECT? DPLAY ERROR CODE 1 OR 2 Intelli-Vent TM Sequence of Operation REQUEST FOR HEAT PRESENT?

More information

Automotive Sensor Simulator. Automotive sensor simulator. Operating manual. AutoSim

Automotive Sensor Simulator. Automotive sensor simulator. Operating manual. AutoSim Automotive sensor simulator Operating manual AutoSim Contents Introduction.. page 3 Technical specifications.... page 4 Typical application of AutoSim simulator..... page 4 Device appearance... page 5

More information

PART 11: START-UP PROCEDURES FOR THE INSTALLER

PART 11: START-UP PROCEDURES FOR THE INSTALLER PART 11: START-UP PROCEDURES FOR THE INSTALLER NOTICE It is important to note that the user can adjust the heat curve down by adjusting the central heating temperature to a lower setting. 212 CENTRAL HEATING

More information

SIMPLE ELECTRONIC IGNITION WIRE DIAGRAM THERMOSTAT (3) PV PILOT BURNER/IGNITOR - SENSOR Q345A (9) SPARK (4) GND (BURNER) CHASSIS GND

SIMPLE ELECTRONIC IGNITION WIRE DIAGRAM THERMOSTAT (3) PV PILOT BURNER/IGNITOR - SENSOR Q345A (9) SPARK (4) GND (BURNER) CHASSIS GND Honeywell Electronic Ignition Troubleshooting Tech Tip April 2007 The Honeywell S8610H Intermittent Pilot Module provides the ignition sequencing, pilot spark, pilot flame monitoring, Pilot Valve (PV)

More information

Factory owners must ensure the boiler is:

Factory owners must ensure the boiler is: Factory owners must ensure the boiler is: * Registered with the Boilers and Pressure Vessels Division, Labour Department * Examined by an appointed examiner and has a valid certificate of fitness * Supervised

More information

Continuous Monitoring of Flue and Combustible or Hazardous Gases and Vapors

Continuous Monitoring of Flue and Combustible or Hazardous Gases and Vapors Continuous Monitoring of Flue and Combustible or Hazardous Gases and Vapors www.static-control.in 1 Introduction The detection or monitoring of flue gases and or hazardous gases has been a complex subject

More information

prestige Condensing Water Boiler SERVICE TECHNICIAN S TROUBLE SHOOTING GUIDE 2008-36 TSG-PRESTIGE Date revised: 12/6/10

prestige Condensing Water Boiler SERVICE TECHNICIAN S TROUBLE SHOOTING GUIDE 2008-36 TSG-PRESTIGE Date revised: 12/6/10 prestige Condensing Water Boiler SERVICE TECHNICIAN S TROUBLE SHOOTING GUIDE Date revised: 12/6/10 2008-36 TSG-PRESTIGE Table of Contents INTRODUCTION Page 1-2 SERVICING TIPS AND INSTRUCTIONS Page 3-4

More information

Operating instructions

Operating instructions 6300 9681 02/2006 GB For the user Operating instructions Logano GE315 Boiler for oil-/gas-fired pressure jet burners Please read thoroughly before use. Operating instructions Logano GE315 Dear Customer,

More information

8 716 473 216-00.3O. Gas boiler. Gaz 6000 W WBN 6000-30-H-E-N/L-S2400. Operating instructions for the end customer. 8 716 473 217 (2014/07) en

8 716 473 216-00.3O. Gas boiler. Gaz 6000 W WBN 6000-30-H-E-N/L-S2400. Operating instructions for the end customer. 8 716 473 217 (2014/07) en 8 716 473 216-00.3O Gas boiler WBN 6000-30-H-E-N/L-S2400 Operating instructions for the end customer en 2 Contents Contents 1 Key to symbols and safety instructions................... 2 1.1 Key to symbols..................................

More information

DTC P0125 Insufficient Coolant Temperature for Closed Loop Fuel Control

DTC P0125 Insufficient Coolant Temperature for Closed Loop Fuel Control EINE (5VZFE) DI195 DI8YY02 DTC P0125 Insufficient Coolant Temperature for Closed Loop Fuel Control CIRCUIT DESCRIPTION To obtain a high purification rate of the CO, HC and x components of the exhaust gas,

More information

Trouble Shooting. Pump

Trouble Shooting. Pump Trouble Shooting Pump Trouble Possible Cause Remedy Oil leaking in the area of water pump crankshaft Worn crankshaft seal, bad bearing, grooved shaft, or failure of retainer o-ring. Excessive play on crankshaft

More information

Energy Efficient Operations and Maintenance Strategies for Boilers

Energy Efficient Operations and Maintenance Strategies for Boilers Energy Efficient Operations and Maintenance Strategies for Boilers Large, complex and widely used, industrial boilers are major consumers of fuel. Proper operations and maintenance (O&M) procedures must

More information

Control Device Requirements Charts For Oil and Gas Handling and Production Facilities

Control Device Requirements Charts For Oil and Gas Handling and Production Facilities Device Charts For Oil and Gas Handling and Production Facilities Purpose/Scope: The purpose of this document is to provide standardized guidance for use by the regulated community and air permit reviewers,

More information

December Newsletter by Vincent Dunn Backdraft and flashover, what is the difference?

December Newsletter by Vincent Dunn Backdraft and flashover, what is the difference? Photo By: Steve Spak December Newsletter by Vincent Dunn Backdraft and flashover, what is the difference? What is a backdraft explosion and how does differ from a flashover? Explosions kill and injure

More information

For installation guide see reverse of book

For installation guide see reverse of book USERS GUIDE LOGIC Combi 24, 30, 35 For installation guide see reverse of book When replacing any part on this appliance, use only spare parts that you can be assured conform to the safety and performance

More information

The Concept of Condensing Boilers

The Concept of Condensing Boilers The Concept of Condensing Boilers ENERGY SAVINGS AND ENVIRONMENTAL COMMITMENT Energy conservation is becoming a global necessity in the face of depleting natural resources. As a result, the technology

More information

TB-A028-06 - A. O. SMITH - FVIR INTELLI-VENT TROUBLESHOOTING CHART # LED STATUS PROBLEM SOLUTION

TB-A028-06 - A. O. SMITH - FVIR INTELLI-VENT TROUBLESHOOTING CHART # LED STATUS PROBLEM SOLUTION 1 2 3 4 5 Inadequate or no earth ground sensed by the Intelli-Vent control. Power supply to Intelli-Vent control has reversed polarity. Pressure switch circuit remaining closed for more than 5 seconds

More information

Model 7586. Description / Applications. Intermittent Pilot Gas Ignition Control

Model 7586. Description / Applications. Intermittent Pilot Gas Ignition Control PARTS & ACCESSORIES Model 7586 Intermittent Pilot Gas Ignition Control Description / Applications The Beckett GeniSys Intermittent Pilot Gas Ignition Control is a 24 Vac gas ignition and safety control.

More information

How Sensors Work. How Oxygen, Electrochemical Toxic, and Metal Oxide Semiconductor Sensors Work *

How Sensors Work. How Oxygen, Electrochemical Toxic, and Metal Oxide Semiconductor Sensors Work * How Oxygen, Electrochemical Toxic, and Metal Oxide Semiconductor Sensors Work * 1. Oxygen sensor detection principle Most portable or survey instruments used for workplace evaluation of oxygen concentrations

More information

Munchkin Heat Exchanger Maintenance

Munchkin Heat Exchanger Maintenance Munchkin Heat Exchanger Maintenance By: Mike Granahan *Refer to the appropriate boiler manual for your specific model number. Adjustment procedures will vary. Boiler shown below is an HTP Munchkin 80M

More information

Luna 3 Comfort Troubleshooting Guide June 2008

Luna 3 Comfort Troubleshooting Guide June 2008 Luna 3 Comfort Troubleshooting Guide June 2008 For Technical Assistance Call: (800)461-4657 WARNING! THIS DOCUMENT IS INTENDED ONLY AS AN EDUCATIONAL TOOL This Troubleshooting Guide, and the instructions

More information

80UHG. Service Literature

80UHG. Service Literature Service Literature Corp. 9728 L12 Revised 01 2002 80UHG 80UHG series units are mid efficiency gas furnaces used for upflow or horizontal applications only, manufactured with tubular heat exchangers formed

More information

Alarm and Detection/Suppression

Alarm and Detection/Suppression Alarm and Detection/Suppression Fire Safety American Fire Technologies To provide special hazard services world wide to the industrial market through the integration of components and services Clean Agent

More information

Diesel: Troubleshooting

Diesel: Troubleshooting Diesel: Troubleshooting Probable Cause Engine not starting Hard to start engine Runs rough at lower RPM Lack of power Diesel knock / pinking Black White Blue Low compression X X X Low fuel pressure X X

More information

USERS GUIDE. LOGIC Heat 12, 15, 18, 24, 30. For installation guide see reverse of book

USERS GUIDE. LOGIC Heat 12, 15, 18, 24, 30. For installation guide see reverse of book USERS GUIDE LOGIC Heat 12, 15, 18, 24, 30 For installation guide see reverse of book When replacing any part on this appliance, use only spare parts that you can be assured conform to the safety and performance

More information

Fault codes DM1. Industrial engines DC09, DC13, DC16. Marine engines DI09, DI13, DI16 INSTALLATION MANUAL. 03:10 Issue 5.0 en-gb 1

Fault codes DM1. Industrial engines DC09, DC13, DC16. Marine engines DI09, DI13, DI16 INSTALLATION MANUAL. 03:10 Issue 5.0 en-gb 1 Fault codes DM1 Industrial engines DC09, DC13, DC16 Marine engines DI09, DI13, DI16 03:10 Issue 5.0 en-gb 1 DM1...3 Abbreviations...3 Fault type identifier...3...4 03:10 Issue 5.0 en-gb 2 DM1 DM1 Fault

More information

Safe Method: Gas Safety in Catering Establishments

Safe Method: Gas Safety in Catering Establishments Safe Method: Gas Safety in Catering Establishments Safety Point Why? What do you do? Gas equipment and services must only be installed, maintained and repaired by a Gas Safe registered installer. Check

More information

GenTech Practice Questions

GenTech Practice Questions GenTech Practice Questions Basic Electronics Test: This test will assess your knowledge of and ability to apply the principles of Basic Electronics. This test is comprised of 90 questions in the following

More information

OPERATING INSTRUCTIONS

OPERATING INSTRUCTIONS PIPELINE INSPECTION COMPANY LTD. OPERATING INSTRUCTIONS Wet Sponge Holiday Detectors 670,673, and MSRB Wet Sponge Holiday Detectors Portable and In-Plant Detectors Table of Contents General Information.......................3

More information

Continuous flow direct water heating for potable hot water

Continuous flow direct water heating for potable hot water Continuous flow direct water heating for potable hot water An independently produced White Paper for Rinnai UK 2013 www.rinnaiuk.com In the 35 years since direct hot water systems entered the UK commercial

More information

Modern Gas Heating. The Vitodens 200 gas-fired condensing boiler is prepared for the use of conditioned biogas.

Modern Gas Heating. The Vitodens 200 gas-fired condensing boiler is prepared for the use of conditioned biogas. Heating with Gas Modern Gas Heating With fluctuating energy prices and a growing concern for the environment, it pays to modernize your outdated gas-fired boiler. You will save money, and the environment

More information

800-292-3279 916 638-0828

800-292-3279 916 638-0828 800-292-3279 916 638-0828 http://easycleansystems.com/heaters/heater-parts.html VAL6 KBE5S and KBE5L Service manual KBE5S 1 2 Specifications Type VAL6 KBE5S Heat Output 111,000BTU/h Fuel Kerosene, Diesel

More information

OBSERVING BOILER SAFETY RULES

OBSERVING BOILER SAFETY RULES OBSERVING BOILER SAFETY RULES The rules that follow are brief reminders of the possible consequences in a boiler plant of inappropriate operator response or questionable action in maintaining the boiler

More information

Operating instructions

Operating instructions 6302 6959 02/2006 GB For the user Operating instructions Logano G215 WS Oil and gas-fired boilers Please read thoroughly before use. Overview Regulations and directives Installation: 90/396/EEC gas appliance

More information

Gas Oven Repair Guide

Gas Oven Repair Guide - /6 - Gas Oven Repair Guide [ FX70*, FX50*] Ver. Aug-0 Ignition Failure Cooktop ignition Oven ignition Heating defect Oven Cooktop Abnormal Flame Button, Motors Lamp Others Smell, Smoke, Noise No Display,

More information

Tips for burner modulation, air/fuel cross-limiting, excess-air regulation, oxygen trim and total heat control

Tips for burner modulation, air/fuel cross-limiting, excess-air regulation, oxygen trim and total heat control Boiler control Tips for burner modulation, air/fuel cross-limiting, excess-air regulation, oxygen trim and total heat control Boilers are often the principal steam or hot-water generators in industrial

More information

User Manual for CH-PFC76810

User Manual for CH-PFC76810 AA Portable Power Corp www.batteryspace.com, Email: Sales@batteryspace.com User Manual for CH-PFC76810 1. Overview The CH-PFC76810 charger is suitable for charging lithium ion battery packs such as those

More information

Biomass Boiler House Best Practices. Irene Coyle & Fernando Preto CanmetENERGY

Biomass Boiler House Best Practices. Irene Coyle & Fernando Preto CanmetENERGY Biomass Boiler House Best Practices Irene Coyle & Fernando Preto CanmetENERGY Growing the Margins London, Ontario March 2010 The Biomass & Renewables Group of Industrial Innovation Group (IIG) of CanmetENERGY

More information

USERS GUIDE. LOGIC Combi 24, 30, 35. For installation guide see reverse of book

USERS GUIDE. LOGIC Combi 24, 30, 35. For installation guide see reverse of book USERS GUIDE LOGIC Combi 24, 30, 35 For installation guide see reverse of book When replacing any part on this appliance, use only spare parts that you can be assured conform to the safety and performance

More information

1 DESCRIPTION OF THE APPLIANCE

1 DESCRIPTION OF THE APPLIANCE 1 DESCRIPTION OF THE APPLIANCE 1.1 INTRODUCTION The cast iron SF boilers are a valid solution for the present energetic problems, since they can run with solid fuels: wood and coal. These series of boilers

More information

Boiler and Burner Cleaning and Servicing Specifications

Boiler and Burner Cleaning and Servicing Specifications Boiler and Burner Cleaning and Servicing Specifications The Town of Groton of Public Works Department is requesting bids to provide manufacturers recommended maintenance, repairs and emergency service

More information

36G22, 36G23, 36G24 & 36G52 36J22, 36J23, 36J24 & 36J52 DSI and HSI Single Stage Combination Gas Valve

36G22, 36G23, 36G24 & 36G52 36J22, 36J23, 36J24 & 36J52 DSI and HSI Single Stage Combination Gas Valve Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE. DESCRIPTION

More information

For the owner. Instructions for use. ecotec. Wall hung room sealed fan assisted condensing boilers

For the owner. Instructions for use. ecotec. Wall hung room sealed fan assisted condensing boilers For the owner Instructions for use ecotec Wall hung room sealed fan assisted condensing boilers GB Contents Specified use Notes on these instructions Specified use... Notes on these instructions.... Storage

More information

Baxi Combi Instant 80e & 105e. User s Operating Instructions. Gas Fired Wall Mounted Combination Boiler

Baxi Combi Instant 80e & 105e. User s Operating Instructions. Gas Fired Wall Mounted Combination Boiler User s Operating Instructions Baxi Combi Instant 8e & 15e Gas Fired Wall Mounted Combination Boiler Please keep these instructions safe. Should you move house, please hand them over to the next occupier.

More information

Service Manual Models: 150-800

Service Manual Models: 150-800 AW-SER Rev H Service Manual Models: 150-800 WARNING This manual must only be used by a qualified heating installer / service technician. Read all instructions, including this manual and the Armor Water

More information

Vehicle Engine Management Systems

Vehicle Engine Management Systems Unit 11: Vehicle Engine Management Systems NQF level 3: Guided learning hours: 60 BTEC National Unit abstract Modern motor vehicles continue to make use of the rapid advances in electronics technology

More information

01-3 0000-00 6810-20 AIR CONDITIONING SYSTEM 1. FFH SPECIFICATION AIR CONDITIONING SYSTEM RODIUS 2004.09

01-3 0000-00 6810-20 AIR CONDITIONING SYSTEM 1. FFH SPECIFICATION AIR CONDITIONING SYSTEM RODIUS 2004.09 0000-00 01-3 6810-20 1. FFH SPECIFICATION 01-4 0000-00 2. SYSTEM LAYOUT AND COMPONENTS 0000-00 01-5 01-6 0000-00 3. FFH GENERAL INFORMATION The system is to increase the coolant temperature quickly by

More information

Service Manual Models: 150-500

Service Manual Models: 150-500 Models: 150-500 WARNING This manual must only be used by a qualified heating installer / service technician. Read all instructions, including this manual and the Armor Water Heater Installation and Operation

More information

23 The Thermal Conductivity Detector

23 The Thermal Conductivity Detector 23 The Thermal Conductivity Detector General Information TCD pneumatics Conditions that prevent the detector from operating Filament passivation Carrier, reference, and makeup gas Negative polarity Analyzing

More information

EZ OUTDOOR TANKLESS WATER HEATER. EZtankless.com SPECIFICATIONS. Model EZ OUTDOOR. Rated heat input (kw) 32

EZ OUTDOOR TANKLESS WATER HEATER. EZtankless.com SPECIFICATIONS. Model EZ OUTDOOR. Rated heat input (kw) 32 EZ OUTDOOR TANKLESS WATER HEATER EZtankless.com SPECIFICATIONS Model EZ OUTDOOR Rated heat input (kw) 32 Hot water supply (for 60 F tem. rise) (GPM) 5.5 External dimensions 23.7" x 15.5" x 5.5" Water pressure

More information

SERVICE SERVICE COMPACT MANUAL. Mod. 3000 92X Mod. 3000 93X Mod. 3000 94X. Part 2

SERVICE SERVICE COMPACT MANUAL. Mod. 3000 92X Mod. 3000 93X Mod. 3000 94X. Part 2 SERVICE COMPACT SERVICE 000 MANUAL Mod. 000 9X Mod. 000 9X Mod. 000 94X Part Forward This Service Handbook is intended to assist with servicing and fault-finding in Caravans and Motor Caravans equipped

More information

Service Manual Models: 80-285

Service Manual Models: 80-285 KB-SER-08 Service Manual Models: 80-285 Starting Serial #H07H10040039 WARNING This manual must only be used by a qualified heating installer / service technician. Read all instructions, including this

More information

1 General information

1 General information 1 General information 1.1 About this manual This manual describes the installation, function and operation of an integrated solar control system, which is suitable for split pressurized solar heating system.

More information

ecomax Instructions for use Wall hung room sealed fan assisted condensing boilers For the user

ecomax Instructions for use Wall hung room sealed fan assisted condensing boilers For the user For the user Instructions for use ecomax Wall hung room sealed fan assisted condensing boilers ecomax 63/ E ecomax 68/ E ecomax 6/ E ecomax 635 E ecomax 84/ E ecomax 88/ E ecomax 835 E GB Table of contents

More information

Consortiwm Awdurdodau Lleol Cymru Consortium Local Authorities Wales

Consortiwm Awdurdodau Lleol Cymru Consortium Local Authorities Wales Consortiwm Awdurdodau Lleol Cymru Consortium Local Authorities Wales SPECIFICATION FOR BOILER SERVICING MAINTENANCE Maintenance Module 11 March 2012 issue This document has been compiled by the Engineering

More information

Signature and ISX CM870 Electronics

Signature and ISX CM870 Electronics Signature and ISX CM870 Electronics Cummins West Training Center System Description General Information The Signature and ISX CM870 engine control system is an electronically operated fuel control system

More information

PROCEDURES PREVENTION OF ACCIDENTAL IGNITION

PROCEDURES PREVENTION OF ACCIDENTAL IGNITION Page No: 1 of 7 6.0 PURPOSE (192.751) All possible precautions shall be exercised to prevent the accidental escape and ignition of gas. Whenever possible, potential sources of ignition should be eliminated

More information

Tankless Gas Water Heaters Second Generation Indoor, Outdoor and Direct Vent Up to 199,000 BTU

Tankless Gas Water Heaters Second Generation Indoor, Outdoor and Direct Vent Up to 199,000 BTU http://waterheatertimer.org/troubleshoot-rheem-tankless-water-heater.html Tankless Gas Water Heaters Second Generation Indoor, Outdoor and Direct Vent Up to 199,000 BTU Includes RTG2-42, RTG53, RTG66 and

More information

TYPE 65UV5-1004 CEX Integrated Flame Scanner with Internal Flame Relay and Analog Output

TYPE 65UV5-1004 CEX Integrated Flame Scanner with Internal Flame Relay and Analog Output 133-683 JUNE 28, 2006 TYPE 65UV5-1004 CEX Integrated Flame Scanner with Internal Flame Relay and Analog Output DESCRIPTION APPLICATION The Fireye 65UV5-1004 flame scanner is a microprocessor based flame

More information

Propane Conversion Kit PROPANE CONVERSION KIT INSTALLATION MANUAL

Propane Conversion Kit PROPANE CONVERSION KIT INSTALLATION MANUAL Propane Conversion Kit Supersedes: 145.25-IOM2 (708) Form 145.25-IOM2 (908) PROPANE CONVERSION KIT INSTALLATION MANUAL "LPKIT " - PROPANE CONVERSION KIT Kits are available for field conversion from natural

More information

FUEL-16, Troubleshooting Fuel Supply Problems

FUEL-16, Troubleshooting Fuel Supply Problems FUEL-16, Troubleshooting Fuel Supply Problems Introduction This procedure is used to troubleshooting fuel supply problems including failure of the fuel pump to start during engine cranking. Fuel Pump Not

More information

PART 1 - INTRODUCTION...

PART 1 - INTRODUCTION... Table of Contents PART 1 - INTRODUCTION... 3 1.1 General... 3 1.2 Sensor Features... 3 1.3 Sensor Specifications (CDE-45P)... 4 Figure 1-1 CDE-45P Sensor Dimensions (standard, convertible style)... 4 PART

More information

Application Note. So You Need to Measure Some Inductors?

Application Note. So You Need to Measure Some Inductors? So You Need to Measure Some nductors? Take a look at the 1910 nductance Analyzer. Although specifically designed for production testing of inductors and coils, in addition to measuring inductance (L),

More information

SERVICE TIPS. Dometic REFRIGERATORS. Models. OS1927 4/96 Copyright 1996 The Dometic Corporation

SERVICE TIPS. Dometic REFRIGERATORS. Models. OS1927 4/96 Copyright 1996 The Dometic Corporation SERVICE TIPS Dometic REFRIGERATORS Models RM2612 RM2652 RM2812 RM2852 OS1927 4/96 Copyright 1996 The Dometic Corporation THE MOST COMMON SYSTEM PROBLEMS ASSOCIATED WITH THE RM2612, RM2812, RM2652, RM2852

More information

METHOD 511.4 EXPLOSIVE ATMOSPHERE

METHOD 511.4 EXPLOSIVE ATMOSPHERE EXPLOSIVE ATMOSPHERE NOTE: Tailoring is essential. Select methods, procedures, and parameter levels based on the tailoring process described in Part One, paragraph 4.2.2, and Appendix C. Apply the general

More information

CABINET. A Clean Burn Heat Exchanger provides approximately 200% more surface area for capturing combustion heat. You get more heat from less oil.

CABINET. A Clean Burn Heat Exchanger provides approximately 200% more surface area for capturing combustion heat. You get more heat from less oil. Lanair Clean Burn CABINET Lanair's lightweight heat exchanger provides very little travel for the heat to be picked-up and ultimately be transferred to your shop. It uses a 2-pass design made up of 12

More information

Rinnai Tankless. Water Heater. Troubleshooting Manual

Rinnai Tankless. Water Heater. Troubleshooting Manual Rinnai Tankless Water Heater Troubleshooting Manual WARNING There are a number of live tests that are required when fault finding this product. Extreme care should be used at all times to avoid contact

More information

Vitosoft 200 Vitodata 300 Vitocom 300 Vitocom 100

Vitosoft 200 Vitodata 300 Vitocom 300 Vitocom 100 Contents Page 1, type FA1 1.1 Function description................................................................................... 6 1.2 Pre requisites.............................................................................................

More information

Electronic Diesel Control EDC 16

Electronic Diesel Control EDC 16 Service. Self-Study Programme 304 Electronic Diesel Control EDC 16 Design and Function The new EDC 16 engine management system from Bosch has its debut in the V10-TDI- and R5-TDI-engines. Increasing demands

More information

7800 SERIES EC7895A,C; RM7895A,B,C,D and RM7896A,B,C,D Relay Modules

7800 SERIES EC7895A,C; RM7895A,B,C,D and RM7896A,B,C,D Relay Modules 7800 SERIES EC7895A,C; RM7895A,B,C,D and RM7896A,B,C,D Relay Modules SPECIFICATION DATA FEATURES APPLICATION The Honeywell EC7895/RM7895/RM7896 is a microprocessor based integrated burner control for automatically

More information

C. Burner management system to follow requirements of Industrial Risk Insurers (IRI).

C. Burner management system to follow requirements of Industrial Risk Insurers (IRI). SECTION 23 52 30 PART 1 - GENERAL 1.01 RELATED WORK A. Section 23 05 00: Common Work Results for HVAC B. Section 23 25 00: Chemical Water Treatment C. Section 23 51 23: Flue Piping 1.02 QUALITY ASSURANCE

More information

Your safety and the safety of others are very important.

Your safety and the safety of others are very important. NATURAL GAS TO PROPANE CONVERSION KIT 090 INSTALLATION INSTRUCTIONS FOR ALTITUDES 0 -,00 FT. ONLY PROPANE CONVERSION KIT SAFETY... INSTALLATION REQUIREMENTS... Tools and Parts... LP Gas Requirements...

More information

Version: 1.0 Last Edited: 2005-10-27. Guideline

Version: 1.0 Last Edited: 2005-10-27. Guideline Process hazard and risk Comments on this report are gratefully received by Johan Hedberg at SP Swedish National Testing and Research Institute mailto:johan.hedberg@sp.se -1- Summary This report will try

More information

Boiler Tune-up Guide

Boiler Tune-up Guide Boiler Tune-up Guide National Emission Standards for Hazardous Air Pollutants for Area Sources: Industrial, Commercial, and Institutional Boilers What is a boiler tune-up? 40 CFR Part 63 Subpart JJJJJJ

More information

R&D on Oil-Burning, Environment-Friendly, High-Efficiency Boiler

R&D on Oil-Burning, Environment-Friendly, High-Efficiency Boiler [N.2.1.1] R&D on Oil-Burning, Environment-Friendly, High-Efficiency Boiler (Environment-Friendly, High-Efficiency Boiler Group) Takashi Murakawa, Yasuhiro Kotani, Kazuhiro Kamijo, Koichi Tsujimoto, Hiroshi

More information

HOW MUCH FUEL DOES A GAS STOVE CONSUME AND HOW MUCH DOES IT COST TO OPERATE?

HOW MUCH FUEL DOES A GAS STOVE CONSUME AND HOW MUCH DOES IT COST TO OPERATE? WHAT IS A BTU? The standard energy measurement is the BTU (British Thermal Unit). Each BTU unit is determined by the amount of thermal energy required to raise the temperature of one pound of water by

More information

Throttle Body Fuel Injection

Throttle Body Fuel Injection Throttle Body Fuel Injection Initial Calibration of the TBI Disclaimer The author of this presentation assumes NO responsibility for information provided causing the owner to modify or alter their motorhome

More information

Section 6 Fire Detection and Alarm Systems Russell Porteous Chief Executive Officer Firewize Services

Section 6 Fire Detection and Alarm Systems Russell Porteous Chief Executive Officer Firewize Services Section 6 Fire Detection and Alarm Systems Russell Porteous Chief Executive Officer Firewize Services General Information Section 6 of AS1851-2012 covers: Fire Detection and Alarms Systems Electrical Detection

More information

Grounding of Electrical Systems NEW CODE: Grounding and Bonding

Grounding of Electrical Systems NEW CODE: Grounding and Bonding Grounding of Electrical Systems NEW CODE: Grounding and Bonding Presented By Scott Peele PE Grounding of Electrical Systems Outline Defining the Terms Why should I Ground? Types of Grounding Systems Separately

More information

OPERATION MANUAL VALVE CHECKER G040-123

OPERATION MANUAL VALVE CHECKER G040-123 OPERATION MANUAL VALVE CHECKER AUSTRALIA PTY. LTD. L:\DWG_NO\DOCUMENT\MANUALS\Word File\A OPERATION MANUAL CN 20.4.99 VALVE CHECKER 1 of 20 CONTENTS Chapter Title Page 1. Description 3 2. Specification

More information

Operator: Save these instructions for future use!

Operator: Save these instructions for future use! WHITE-RODGERS 36C01 Combination Gas Valves (24 Volt and 120 Volt Models) INSTALLATI INSTRUCTIS FAILURE TO READ AND FOLLOW ALL INSTRUCTIS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CTROL COULD CAUSE

More information

Tankless. Water Heater. Troubleshooting Manual

Tankless. Water Heater. Troubleshooting Manual Tankless Water Heater Troubleshooting Manual WARNING There are a number of live tests that are required when fault finding this product. Extreme care should be used at all times to avoid contact with energized

More information

Oil - kerosene burners

Oil - kerosene burners Installation, use and maintenance instructions Oil - kerosene burners One stage operation CODE MODEL TYPE 3747469 G0 474T5 90 (0) - 05/008 TECHNICAL FEATURES Thermal power output 95 3 kw 8 8 kg/h Fuel

More information

Tankless Water Heater

Tankless Water Heater Tankless Water Heater USER S INFORMATION MANUAL Models WGRTNG199 / WGRTLP199 WGRTCNG199 / WGRTCLP199 NOTICE: Westinghouse reserves the right to make product changes or updates without notice and will not

More information

PACKAGED FIRE TUBE BOILER

PACKAGED FIRE TUBE BOILER SAMPLE PREVENTIVE MAINTENANCE MANUAL PACKAGED FIRE TUBE BOILER 1 CONTENTS Introduction 1 Intention 2 Organisational setup 3 Boiler Fault reporting & Repair progression 4 Preventive Maintenance Schedules

More information

ANALOG AND DIGITAL METERS ANALOG VS. DIGITAL METERS VOLTMETERS ANALOG AND DIGITAL

ANALOG AND DIGITAL METERS ANALOG VS. DIGITAL METERS VOLTMETERS ANALOG AND DIGITAL ANALOG VS. DIGITAL METERS Ultimately, your diagnosis of vehicle electrical system problems will come down to using a voltmeter, ammeter, or ohmmeter to pinpoint the exact location of the problem. There

More information

SERVICE INSTRUCTIONS

SERVICE INSTRUCTIONS SERVICE INSTRUCTIONS 18, 20,24, 26L Integrity Electronic Gas Continuous Flow Water Heater TM031 Reevvi issi ion:: B Publissheed:: Feebrruaarryy 0088 871018 871020 871024 871024-B 871024-C 871026 871026-B

More information

Improving Steam Methane Reformer Performance with the ZoloSCAN-SMR

Improving Steam Methane Reformer Performance with the ZoloSCAN-SMR Improving Steam Methane Reformer Performance with the SCAN-SMR The global demand for hydrogen continues to increase as heavier crudes are processed and stricter governmental mandates require reductions

More information

Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading. Ramandeep Kaur Aujla S.NO 250447392

Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading. Ramandeep Kaur Aujla S.NO 250447392 1 Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading By Ramandeep Kaur Aujla S.NO 250447392 ES 586b: Theory and applications of protective relays Department of

More information

SELECTION, APPLICATION AND MAINTENANCE

SELECTION, APPLICATION AND MAINTENANCE DIESEL PROTECTION SYSTEMS Automatic Diesel Engine Shut Down System for Safe Area Applications SELECTION, APPLICATION AND MAINTENANCE Series 300 Series 310 SYSTEM DESCRIPTION Suitable for attended engine

More information