1 Installation and Service Instructions for use by heating contractor Solar Control Module for solar connections to the Vitotronic control SM1 SOLAR CONTROL MODULE Product may not be exactly as shown IMPORTANT Certified as a component part for Viessmann boilers 09/2013 Read and save these instructions for future reference. Please file in Service Binder

2 Safety Safety, Installation and Warranty Requirements Solar Control Module SM1, Installation and Service Please ensure that these instructions are read and understood before commencing installation. Failure to comply with the instructions listed below and details printed in this manual can cause product/property damage, severe personal injury, and/or loss of life. Ensure all requirements below are understood and fulfilled (including detailed information found in manual subsections). Product documentation Read all applicable documentation before commencing installation. Store documentation near boiler in a readily accessible location for reference in the future by service personnel. For a listing of applicable literature, please see section entitled Important Regulatory and Safety Requirements. Warranty Information contained in this and related product documentation must be read and followed. Failure to do so renders the warranty null and void. Licensed professional heating contractor The installation, adjustment, service and maintenance of this equipment must be performed by a licensed professional heating contractor. Please see section entitled Safety and Important Regulatory and Installation Requirements. Advice to owner Once the installation work is complete, the heating contractor must familiarize the system operator/ ultimate owner with all equipment, as well as safety precautions/requirements, shutdown procedure, and the need for professional service annually before the heating season begins. 2

3 Solar Control Module SM1, Installation and Service Table of Contents Page Safety Important Precautions General Information Installation Connections Safety, Installation and Warranty Requirements...2 Product documentation...2 Licensed professional heating contractor...2 Advice to owner...2 Warranty...2 Important Regulatory and Installation Requirements...4 Approvals...4 Codes...4 Working on the equipment...4 Power supply...4 About these Installation Instructions...5 Mounting on the Wall...6 Overview of Electrical Connections...7.System Example System Example System Example Power Supply...18 Connecting the KM Bus to the Extension Modules...19 Connection and Wiring Diagram...20 Additional Information Function Description...21 Specifications

4 Important Precautions Important Regulatory and Installation Requirements Solar Control Module SM1, Installation and Service Approvals Viessmann boilers, burners and controls are approved for sale in North America by CSA International. Codes The installation of this unit shall be in accordance with local codes. In the absence of local codes, use: - CSA C22.1 Part 1 and/or local codes in Canada - National Electrical Code ANSI/NFPA 70 in the U.S. Always use latest editions of codes. The heating contractor must comply with the Standard for Controls and Safety Devices for Automatically Fired Boilers, ANSI/ASME CSD-1 where required by the authority having jurisdiction. Working on the equipment The installation, adjustment, service, and maintenance of this product must be done by a licensed professional heating contractor who is qualified and experienced in the installation, service, and maintenance of hot water boilers. There are no user serviceable parts on the boiler, burner, or control. Power supply Install power supply in accordance with the regulations of the authorities having jurisdiction or, in absence of such requirements, in accordance with National Codes. Viessmann recommends the installation of a disconnect switch to the 120V power supply outside of the boiler room. Ensure main power supply to equipment, the heating system, and all external controls have been deactivated. Close main oil or gas supply valve. Take precautions in both instances to avoid accidental activation of power during service work. Please carefully read this manual prior to attempting installation. Any warranty is null and void if these instructions are not followed. For information regarding other Viessmann System Technology componentry, please reference documentation of the respective product. We offer frequent installation and service seminars to familiarize our partners with our products. Please inquire. The completeness and functionality of field supplied electrical controls and components must be verified by the heating contractor. These include low water cut-offs, flow switches (if used), staging controls, pumps, motorized valves, air vents, thermostats, etc. WARNING Turn off electric power supply before servicing. Contact with live electric components can cause shock or loss of life. 4

5 Solar Control Module SM1, Installation and Service About these Installation Instructions General Information Take note of all symbols and notations intended to draw attention to potential hazards or important product information. WARNING Warnings draw your attention to the presence of potential hazards or important product information. Indicates an imminently hazardous situation which, if not avoided, could result in death, serious injury or substantial product/property damage. CAUTION Cautions draw your attention to the presence of potential hazards or important product information. Indicates an imminently hazardous situation which, if not avoided, may result in minor injury or product / property damage. IMPORTANT Helpful hints for installation, operation or maintenance which pertain to the product. This symbol indicates to note additional information This symbol indicates that other instructions must be referenced. 5

6 Installation Mounting on the Wall Solar Control Module SM1, Installation and Service Extension kit for installation on a wall 1. Loosen the retaining screws from the extension kit enclosure (do not remove). 2. Remove cover and set aside. 3. Mount the extension module enclosure to the wall using the supplied hardware. 4. Install the cover. Components: H SM1 module H KM BUS plug avg H Power cord pre-wired to plug fö H Temperature sensor % H Temperature sensor & H Temperature sensor / (accessory) H Temperature sensor aö (accessory) H Pump plug ss H Pump plug sf H Speed control PWM plug 6

7 Solar Control Module SM1, Installation and Service Overview of Electrical Connections Connections A Legend A Solar control module % DHW tank temperature sensor & Collector temperature sensor / Temperature sensor (accessory) aö Temperature sensor (accessory) ss Transfer pump or 3-way diverter valve sf Solar circuit pump fö Power supply avg KM BUS to boiler control unit PWM Speed control, solar circuit pump (if circulation pump with PWM control installed) CAUTION Electronic modules can be damaged by electrostatic charges. Before commencing work, touch an grounded object, e.g. heating or water pipes to discharge static loads. Note: Apply a strain relief to all on-site cables. Close any unnecessary knock-outs with cable grommets (not cut open). 7

8 Connections System Example 1 Solar Control Module SM1, Installation and Service DHW heating with dual mode DHW tank Function description DHW heating with solar energy If the temperature differential between collector temperature sensor eq and DHW tank temperature sensor qq is greater than the start temperature differential (coding address 00), solar circuit pump ee is started and DHW tank qp is heated. Solar circuit pump ee stops if: H Actual temperature drops below stop temperature differential (coding address 01) H Maximum DHW tank temperature is exceeded (coding address 08) H The temperature selected at high limit safety cut-out qw (if installed) is reached Additional function for DHW heating The requirements for the additional function are achieved through circulation pump qt. Suppression of DHW tank reheating by the boiler Reheating suppression takes place in two stages. Required codes at the oil/gas boiler control unit Boiler installation and service instructions Reheating of DHW tank qp by boiler 1 is suppressed as soon as DHW tank qp is heated by collectors ep. For this, the set DHW tank temperature for reheating is reduced by boiler 1. After solar circuit pump ee has been switched off, suppression remains active for a certain time. In the case of uninterrupted heating by the collectors ep (> 2 h), boiler 1 will only reheat if the set DHW temperature selected at boiler control unit 2 (coding address 67 ) is not achieved. A third set DHW temperature can be specified via coding address 67 [setting range 50 to 203 F (10 to 95 C)]. This value must be below the first set DHW temperature. DHW tank qp will only be heated by boiler 1 if this set value cannot be achieved by the solar thermal system. DHW heating without solar energy The upper section of DHW tank qp is heated by boiler 1. The DHW tank thermostat with DHW tank temperature sensor qz of boiler control unit 2 regulates DHW tank heating. Function/system components Start temperature differential for solar circuit pump at connection sf Factory set condition 8 K (14.4 F) Stop temperature differential for solar circuit pump at connection sf Factory set condition 4 K (7.2 F) Solar circuit pump type: H Solar circuit pump is not speed-controlled H Solar circuit pump is speed-controlled with wave pack control H Solar circuit pump is speed-controlled with PWM control Note: Coding address 00 can be set to min. 0.9 F (0.5 K) above coding address 01. Coding address 01 can be set to max. 0.9 F (0.5 K) below coding address 00. Adjust Code in solar group 00:... 00:8 01:... 01: :1 02:2 Factory set condition 02:0 02:0 02:0 Maximum DHW tank temperature (Factory set condition 140 F) 60 C) 08:... 08:60 Additional DHW heating function: H Without additional function for DHW heating H With additional function for DHW heating -- 20:1 20:0 20:0 8

9 Solar Control Module SM1, Installation and Service System Example 1 (continued) Connections Hydraulic installation scheme Equipment required Legend 1 Wall mounted oil/gas boiler with 2 Boiler and heating circuit control unit qp Dual mode DHW tank qq DHW tank temperature sensor % (solar control module) qw High limit safety cut-out (accessory) qe DHW circulation pump (on site) (accessories may be required for connection) qr Thermostatic mixing valve (accessory) qt Circulation pump ss (transfer of heat, on site) qz DHW tank temperature sensor % (boiler) ep Solar collectors eq Collector temperature sensor & ew Solar-Divicon (accessory) with ee Solar circuit pump sf ez Solar control module, type SM1 eu Junction box (on site) 9

10 Connections System Example 1 (continued) Solar Control Module SM1, Installation and Service Electrical installation scheme Solar control module, type SM1 10

11 Solar Control Module SM1, Installation and Service System Example 2 DHW heating with two mono mode DHW tanks Function description DHW heating with solar energy If the temperature differential between collector temperature sensor eq and DHW tank temperature sensor qq is greater than the start temperature differential (coding address 00), solar circuit pump ee starts and DHW tank 1 qp is heated. Solar circuit pump ee stops if: H Actual temperature drops below stop temperature differential (coding address 01) H Maximum DHW tank temperature is exceeded (coding address 08) H The temperature selected at high limit safety cut-out qw (if installed) is reached Transfer pump qt starts if the temperature at temperature sensor qz has reached the start temperature differential of the differential temperature control 2 (code 22). The water heated in DHW tank 1 qp is supplied to DHW tank 2 qi. This means DHW tank 2 qi is also heated by solar energy. Transfer pump qt stops if the temperature at temperature sensor qz has fallen below the stop temperature differential of the differential temperature control 2 (code 23). Additional function for DHW heating Connections The requirements for the additional function are achieved through circulation pump qt. Suppression of DHW tank 2 heating by the boiler with DHW heating Reheating suppression takes place in two stages. Heating DHW tank 2 qi by boiler 1 is suppressed as soon as DHW tank 1 qp is heated by collectors ep. For this, the set DHW tank temperature for reheating is reduced by boiler 1. After solar circuit pump ee has been switched off, suppression remains active for a certain time. In the case of uninterrupted heating by the collectors ep (> 2 h), boiler 1 will only heat if the set DHW temperature selected at boiler control unit 2 (coding address 67 ) is not achieved. A third set DHW temperature can be specified via coding address 67 [setting range 50 to 203 F (10 to 95 C)]. This value must be below the first set DHW temperature. DHW tank 2 qi will only be heated by boiler 1, if this set value is not achieved by the solar thermal system. DHW heating without solar energy DHW tank 2 qi is heated by boiler 1. The DHW tank thermostat with DHW tank temperature sensor qo of boiler control unit 2 starts the internal circulation pump and changes the 3-way diverter valve to DHW heating. Required codes at the oil/gas boiler control unit Boiler installation and service instructions Function/system components Start temperature differential for solar circuit pump at connection sf. Factory set condition 8 K (14.4 F) Stop temperature differential for solar circuit pump at connection sf. Factory set condition 4 K (7.2 F) Solar circuit pump type: H Solar circuit pump is not speed-controlled H Solar circuit pump is speed-controlled with wave pack control H Solar circuit pump is speed-controlled with PWM control Adjust Code in solar group 00:... 00:8 01:... 01: :1 02:2 Factory set condition 02:0 02:0 02:0 Maximum DHW tank temperature (Factory set condition 60 C) 08:... 08:60 Start temperature differential with central heating backup. Factory set condition 8 K (14.4 F) Stop temperature differential with central heating backup. Factory set condition 4 K (7.2 F) 22:... 22:8 23:... 23:4 Note: Coding address 00 can be set to min. 0.9 F (0.5 K) above coding address 01. Coding address 01 can be set to max. 0.9 F (0.5 K) below coding address

12 Connections System Example 2 (continued) Solar Control Module SM1, Installation and Service Hydraulic installation scheme Equipment required Legend 1 Wall mounted oil/gas boiler with 2 Boiler and heating circuit control unit qp DHW tank 1, mono mode qq DHW tank temperature sensor % (solar control module) qw High limit safety cut-out (accessory) qe DHW circulation pump (on site) (accessories may be required for connection) qr Thermostatic mixing valve (accessory) qt Transfer pump (on site) qz Temperature sensor / (accessory) qu Temperature sensor aö (accessory) qi DHW tank 2, mono mode qo DHW tank temperature sensor % (boiler) ep Solar collectors eq Collector temperature sensor & ew Solar-Divicon (accessory) ee Solar circuit pump sf (standard delivery, Solar-Divicon) ez Solar control module, type SM1 eu Junction box 12

13 Solar Control Module SM1, Installation and Service System Example 2 (continued) Connections Electrical installation scheme Solar control module, type SM1 A KM BUS to boiler control unit 13

14 Connections System Example 3 Solar Control Module SM1, Installation and Service DHW heating with mono mode DHW tank and central heating backup with multi mode heating water buffer DHW tank with differential temperature control Function description DHW heating with solar energy If the temperature differential between collector temperature sensor eq and DHW tank temperature sensor rq is greater than the start temperature differential (coding address 00), solar circuit pump ee starts and heating water buffer DHW tank rp is heated. Solar circuit pump ee stops if: H Actual temperature drops below stop temperature differential (coding address 01) H Maximum DHW tank temperature is exceeded (coding address 08) H The temperature selected at high limit safety cut-out rr (if installed) is reached Entire heating water buffer DHW tank rp is heated by the solar thermal system if the insolation is adequate. If there is insufficient solar energy, the DHW is preheated by the solar energy available in heating water buffer DHW tank rp, and is brought up to the required temperature in DHW tank qp via boiler 1. The burner and circulation pump for DHW tank heating 7 are started via DHW tank temperature sensor qq of the boiler control unit. Suppression of heating water buffer DHW tank reheating by the boiler with DHW heating Reheating suppression takes place in two stages. Heating of DHW tank qp by boiler 1 is suppressed as soon as heating water buffer DHW tank rp is heated by collectors ep. For this, the set DHW tank temperature for reheating is reduced by boiler 1. After solar circuit pump ee has been switched off, suppression remains active for a certain time. In the case of uninterrupted heating by the collectors ep (> 2 h), boiler 1 will only reheat if the set DHW temperature selected at boiler control unit 2 (coding address 67 ) is not achieved. A third set DHW temperature can be specified via coding address 67 [setting range 50 to 203 F (10 to 95 C)]. This value must be below the first set DHW temperature. DHW tank qp will only be heated by boiler 1 if this set value cannot be achieved by the solar thermal system. DHW heating without solar energy DHW tank qp is heated by boiler 1. The DHW tank thermostat with DHW tank temperature sensor qq of boiler control unit 2 controls circulation pump for DHW tank heating 7. 14

15 Solar Control Module SM1, Installation and Service System Example 3 (continued) Connections Central heating with solar energy If the temperature differential between sensor rw and sensor rt is greater than the temperature differential of coding address 22, 3-way diverter valve rz is switched to direction AB-A. The heating circuit return water is routed through heating water buffer DHW tank rp and heated by solar energy. Suppression of reheating by the boiler in the case of central heating backup with solar energy If a sufficiently high temperature is available in heating water buffer DHW tank rp to heat the heating circuits, reheating by boiler 1 can be suppressed. Central heating without solar energy If the temperature differential between sensor rw and sensor rt is less than the temperature differential of coding address 23, 3-way diverter valve rz is switched to direction AB-B. The heating circuit return water is routed directly into low loss header tp and only heated by the boiler. Required codes at the oil/gas boiler control unit Boiler installation and service instructions Function/system components Start temperature differential for solar circuit pump at connection sf Factory set condition 8 K (14.4 F) Stop temperature differential for solar circuit pump at connection sf Factory set condition 4 K (7.2 F) Solar circuit pump type: H Solar circuit pump is not speed-controlled H Solar circuit pump is speed-controlled with wave pack control H Solar circuit pump is speed-controlled with PWM control Adjust Code in solar group 00:... 00:8 01:... 01: :1 02:0 Factory set condition 02:0 02:0 02:0 Maximum DHW tank temperature (Factory set condition 60 C) 08:... 08:60 Differential temperature control 2 with central heating backup 20:4 20:0 Start temperature differential with central heating backup Factory set condition 8 K (14.4 F) Stop temperature differential with central heating backup Factory set condition 4 K (7.2 F) 22:... 22:8 23:... 23:4 Note: Coding address 00 can be set to min. 0.9 F (0.5 K) above coding address 01. Coding address 01 can be set to max. 0.9 F (0.5 K) below coding address

16 Connections System Example 3 (continued) Solar Control Module SM1, Installation and Service Hydraulic installation scheme Equipment required Legend 1 Wall mounted oil/gas boiler with 2 Boiler and heating circuit control unit 7 Circulation pump for DHW tank heating (on site) (accessories may be required for connection) qp Mono mode DHW tank qq DHW tank temperature sensor % (boiler) qe DHW circulation pump (on site) (accessories may be required for connection) qr Thermostatic mixing valve (accessory) ep Solar collectors eq Collector temperature sensor & ew Solar-Divicon (accessory) ee Solar circuit pump sf (standard delivery, Solar-Divicon) ez Solar control module, type SM1 eu Junction box (on site) rp Heating water buffer DHW tank rq DHW tank temperature sensor % (solar control module) rw Temperature sensor / (flow temperature sensor in heating water buffer DHW tank, accessory) rr High limit safety cut-out (accessory) rt Temperature sensor aö (return temperature sensor in heating circuit, accessory) rz 3-way diverter valve ss (accessory) tp Low loss header (accessory) tq Flow temperature sensor, low loss header? (accessory) 16

17 Solar Control Module SM1, Installation and Service System Example 3 (continued) Connections Electrical installation scheme Solar control module, type SM1 A KM BUS to boiler control unit 17

18 Connections Power Supply Solar Control Module SM1, Installation and Service Connect accessories with a total wattage above 400 W directly to the mains power supply. WARNING Incorrectly executed electrical installations can result in injuries from electrical current and in equipment damage. Connect the power supply and implement all grounding measures (e.g. RCD circuit) in accordance with the following regulations: H In Canada all electrical wiring is to be done in accordance with the latest edition of CSA C22.1 Part 1 and/or local codes. In the U.S. use the National Electrical Code ANSI/NFPA 70. The heating contractor must also comply with both the Standard for Controls and Safety Devices for Automatically Fired Boilers, ANSI/ASME CSD-1, and the Installation Code for Hydronic Heating Systems, CSA B214-01, where required by the authority having jurisdiction. H Connection requirements specified by your local power supply utility H Protect the power cable with max. 15A WARNING The absence of component grounding in the system can lead to serious injury from electrical current if an electrical fault occurs. The equipment and the pipework must be connected to the ground bonding of the house in question. Isolators for non-grounded conductors H The main isolator (if installed) must simultaneously isolate all non-grounded conductors from the mains with a minimum contact separation of 3 mm. We additionally recommend installing an AC/DCsensitive (RCD class B ) for DC (fault) currents that can occur with energy efficient equipment. H If no main isolator is installed, all nongrounded cables must be isolated from the mains by the upstream breaker with at least 3 mm contact separation. WARNING Incorrect core termination can cause severe injuries and damage to the equipment. Never interchange cores L1 and N. 18 Legend A SM1 module CAUTION An incorrect phase sequence can cause damage to the unit. Check for phase equality with the power supply connection of the control unit.

19 Solar Control Module SM1, Installation and Service Connecting the KM BUS to the Extension Modules Connections Legend A Boiler control unit B Extension kit for heating circuit with mixing valve M2 C Extension kit for heating circuit with mixing valve M3 D Extension AM1, EA1 and/or solar control module, type SM1 19

20 Connections Connection and Wiring Diagram Solar Control Module SM1, Installation and Service Legend A1 Main PCB PWM Speed control, solar circuit pump (if circulation pump with PWM control installed) TW Maximum temperature limiter X... Electrical interfaces % DHW tank temperature sensor & Collector temperature sensor / Temperature sensor (if installed) aö Temperature sensor (if installed) ss Transfer pump or 3-way diverter valve sf Solar circuit pump fö Power supply 120V/60Hz avg KM BUS to boiler control unit 20

21 Solar Control Module SM1, Installation and Service Function Description Additional Information Note: Set or alter the functions described below in coding levels 1 and 2 (solar group) at the boiler control unit. Reduction of stagnation time If there is excess solar energy, the speed of the solar circuit pump will be reduced before the maximum DHW tank temperature is reached. This increases the difference between collector temperature and DHW tank temperature. The heat transfer to the DHW tank is reduced, which delays stagnation. Coding address 0A. Maximum collector temperature If the maximum collector temperature is exceeded, the solar circuit pump is shut down to protect the system components (emergency collector shutdown). Coding address 09. Minimum collector temperature limit If the actual temperature falls below the minimum collector temperature, the solar circuit pump is shut down. Coding address 12. Interval function Activate the interval function in systems where the collector temperature sensor is not in an ideal location to prevent a time delay in capturing the collector temperature. Coding address 07. Refer to the boiler Service Instructions Thermostat function The thermostat function can be used independently of the solar operation. Different effects can be achieved by determining the thermostat start and stop temperatures: H Start temperature < stop temperature: e.g. reheating H Start temperature > stop temperature: e.g. utilisation of excess heat Coding addresses 20, 24, 25. Speed control The speed control is disabled in the Factory set condition. It can only be enabled for relay output sf. Possible pumps: H Standard solar pumps with and without their own speed control H High efficiency pumps H Pumps with PWM input (only use solar pumps) E.g. Grundfos Solar PM Coding addresses 02 to 06. Note: We recommend operating the solar circuit pump at max. output while the solar thermal system is being vented. Heat statement When determining thermal yields, the difference between the collector and DHW tank temperature, the set throughput, the type of heat transfer medium and the operating time of the solar circuit pump are taken into account. Coding addresses 0E and 0F. Collector frost protection function Viessmann collectors are filled with Viessmann heat transfer medium. This function does not have to be enabled. Activate only when using water as heat transfer medium. With a collector temperature below 41 F (5 ºC), the solar circuit pump will be started to avoid damage to the collectors. The pump will be stopped when a temperature of 45 F (7 º C) has been reached. Coding address 0b. 21

22 Additional Information Function Description (continued) Solar Control Module SM1, Installation and Service Suppression of DHW tank reheating by the boiler Reheating suppression takes place in two stages. Reheating of the DHW tank by the boiler is suppressed as soon as the DHW tank is heated by the collectors. For this, the set DHW tank temperature for reheating is reduced by the boiler. After the solar circuit pump has been switched off, suppression remains active for a certain time. In the case of uninterrupted heating by the collectors (> 2 h), the boiler will only reheat if the set DHW tank temperature selected at the boiler control unit (coding address 67 ) is not achieved. A third set DHW temperature can be specified via coding address 67 [setting range 50 to 203 F (10 to 95 C)]. This value must be below the first set DHW temperature. The DHW tank will only be heated by the boiler, if this set value cannot be achieved by the solar thermal system. Suppression of reheating by the boiler in case of central heating backup If a sufficiently high temperature is available in the multi mode heating water buffer DHW tank to heat the heating circuits, reheating by boiler can be suppressed. Additional function for DHW heating With the additional function for DHW heating (boiler control unit function), the solar preheat stage can be heated up at the adjustable times. Boiler control unit settings: H Set DHW temperature 2 must be encoded. Coding address 58 (DHW group) H The fourth DHW phase for DHW heating must be enabled H Coding address 20 (solar group) This signal will be transmitted to the solar control module via the KM BUS, and the transfer pump will be started. External heat exchanger The DHW tank is heated via the heat exchanger. Secondary pump ss is started in parallel with solar circuit pump sf. If an additional temperature sensor / is used, secondary pump ss is switched on when solar circuit pump sf is running and the required temperature differential between % and / is available. Coding address 20. DHW tank priority control In systems with two consumers. It is possible to determine the order for heating the consumers. Coding addresses 10, 11, 26. Cyclical heating In systems with several consumers. If the consumer cannot be heated with priority, the next consumer in line will be heated for an adjustable cycle time. After this time has expired, the solar control unit checks the rise of the collector temperature during the adjustable cyclical pause. As soon as the start conditions for the consumer with priority have been met, that consumer will be heated again. Otherwise, the next-in-line consumers will continue to be heated. Coding addresses 26, 27, 28. Relay kick If the pumps and valves have been switched off for 24 h, they are started for approx. 10 sec. to prevent them seizing up. 22

23 Solar Control Module SM1, Installation and Service Specifications Additional Information Rated voltage 120 V~ Rated frequency 60 Hz Rated current 2 A Power consumption 1.5 W Protection class I IP rating IP 20 D to EN , ensure through design/ installation Permissible ambient temperature H During operation 32 to 104 F(0 to 40 C) H During storage and transport -4 to +149 F ( 20 to +65 C) Rated relay output breaking capacity H Solar circuit pump sf 1 A 120 V~ H Transfer pump ss 1 A 120 V~ Sensor curves Resistance in Temperature in Legend A Collector temperature sensor & B H DHW tank temperature sensor % H Temperature sensor / H Temperature sensor aö 23

24 Technical information subject to change without notice. Printed on environmentally friendly (recycled and recyclable) paper. Solar Control Module SM1, Installation and Service

PART 8: FIELD WIRING. n WARNING NOTICE. Boiler Manual

PART 8: FIELD WIRING. n WARNING NOTICE. Boiler Manual PART 8: FIELD WIRING A. INSTALLATION MUST COMPLY WITH: 1. National Electrical Code and any other national, state, provincial or local codes or regulations. 2. In Canada, CSA C22.1 Canadian Electrical Code

More information

VIESMANN. Installation and service instructions VITOTROL 100. for contractors

VIESMANN. Installation and service instructions VITOTROL 100. for contractors Installation and service instructions for contractors VIESMANN Vitotrol 100 Type UTDB-RF2 Room temperature controller with digital time switch and wireless receiver For applicability, see the last page

More information

Technical Information

Technical Information Technical Information Interface with DDC 6 720 642 841-00.1RS Logamatic LON-Gateway For heating contractors during project planning 6 720 643 554 (11/2010) US/CA Contents Contents 1 Explanation of symbols

More information

8 716 473 216-00.3O. Gas boiler. Gaz 6000 W WBN 6000-30-H-E-N/L-S2400. Operating instructions for the end customer. 8 716 473 217 (2014/07) en

8 716 473 216-00.3O. Gas boiler. Gaz 6000 W WBN 6000-30-H-E-N/L-S2400. Operating instructions for the end customer. 8 716 473 217 (2014/07) en 8 716 473 216-00.3O Gas boiler WBN 6000-30-H-E-N/L-S2400 Operating instructions for the end customer en 2 Contents Contents 1 Key to symbols and safety instructions................... 2 1.1 Key to symbols..................................

More information

Oil and Coolant Circulating Heating System. Model - OCSM

Oil and Coolant Circulating Heating System. Model - OCSM Oil and Coolant Circulating Heating System Model - OCSM Installation & Operation Manual 216280-000 REV 2 Identifying Your System The HOTSTART heating system is designed to heat fluids for use in marine

More information

Installation and Service Instructions. Neutralization System Part no. 7441823 Grünbeck part no. 410480

Installation and Service Instructions. Neutralization System Part no. 7441823 Grünbeck part no. 410480 Installation and Service Instructions for use by heating contractors Neutralization System Part no. 7441823 Grünbeck part no. 410480 Safety and Installation Requirements Please ensure that these instructions

More information

AE21-1319 R6 December 2013. Digital Capacity Control for Copeland Scroll Refrigeration Compressors AE21-1319 R6

AE21-1319 R6 December 2013. Digital Capacity Control for Copeland Scroll Refrigeration Compressors AE21-1319 R6 AE21-1319 R6 December 2013 Digital Capacity Control for Copeland Scroll Refrigeration Compressors TABLE OF CONTENTS Section Page Section Page Safety Safety Instructions...2 Safety Icon Explanation...2

More information

with MERCURY FREE 1 HP Relays ! WARNING Before using this product read and understand instructions.

with MERCURY FREE 1 HP Relays ! WARNING Before using this product read and understand instructions. B Installation & Maintenance Instructions MM-414 Series 150E and 157E Low Water Cut-Off/Pump Controllers For Steam Boilers and Other Level Control Applications A Typical Applications: Primary or secondary

More information

RDJ10RF/SET. Wireless room temperature controller with 24-hour time switch and LCD. Programmable, for heating systems

RDJ10RF/SET. Wireless room temperature controller with 24-hour time switch and LCD. Programmable, for heating systems 3 072 RDJ10RF RCR10/433 Wireless room temperature controller with 24-hour time switch and LCD Programmable, for heating systems RDJ10RF/SET Operating modes: Automatic, Comfort, Energy Saving, and Frost

More information

Split Controller. User Manual SM-SS-F 2009/01/04

Split Controller. User Manual SM-SS-F 2009/01/04 Split Controller SM-SS-F User Manual 2009/01/04 Table of contents 1. Parts illustration.... 1 2. Electrical technical data...... 2 3. Electrical connection...3 4. Assemble parts...4 4.1 Assemble the fixed

More information

Electric Flow Boiler

Electric Flow Boiler Electric Flow Boiler EHC offer the most comprehensive range of electric boilers in the market and with our wealth of knowledge and technical expertise we have designed the Slim Jim Electric Flow Boiler

More information

Operating instructions IV / 2007

Operating instructions IV / 2007 General Operating instructions IV / 2007 Contents General Installation Application and function Application and function... 2 Safety information... 2 Design and dimensions... 3 Wiring diagram... 3 Installation

More information

USERS GUIDE. LOGIC Combi 24, 30, 35. For installation guide see reverse of book

USERS GUIDE. LOGIC Combi 24, 30, 35. For installation guide see reverse of book USERS GUIDE LOGIC Combi 24, 30, 35 For installation guide see reverse of book When replacing any part on this appliance, use only spare parts that you can be assured conform to the safety and performance

More information

Your safety and the safety of others are very important.

Your safety and the safety of others are very important. NATURAL GAS TO PROPANE CONVERSION KIT 090 INSTALLATION INSTRUCTIONS FOR ALTITUDES 0 -,00 FT. ONLY PROPANE CONVERSION KIT SAFETY... INSTALLATION REQUIREMENTS... Tools and Parts... LP Gas Requirements...

More information

ABB Drives. User s Manual. Pulse Encoder Interface Module RTAC-01

ABB Drives. User s Manual. Pulse Encoder Interface Module RTAC-01 ABB Drives User s Manual Pulse Encoder Interface Module RTAC-0 Pulse Encoder Interface Module RTAC-0 User s Manual 3AFE 64486853 REV A EN EFFECTIVE:.5.00 00 ABB Oy. All Rights Reserved. Safety instructions

More information

For installation guide see reverse of book

For installation guide see reverse of book USERS GUIDE LOGIC Combi 24, 30, 35 For installation guide see reverse of book When replacing any part on this appliance, use only spare parts that you can be assured conform to the safety and performance

More information

PT-6000 Power Tower INSTALLATION MANUAL SPECIFICATIONS

PT-6000 Power Tower INSTALLATION MANUAL SPECIFICATIONS PT-6000 Power Tower INSTALLATION MANUAL 10.5 9.75 12 22.75 10.75 MAXIMUM SOIL HEIGHT: DO NOT ALLOW FILL TO EXCEED THIS LEVEL! 11.5 4 4 13 Optional PT-BASE for new installations or when previous 2000/6000

More information

Technical Data Manual Model Nos. and pricing: see Price List

Technical Data Manual Model Nos. and pricing: see Price List VITOCELL-V 00 Indirect-fired domestic hot water storage tank 4 to 0 / 60 to Technical Data Manual Model Nos. and pricing: see Price List Vitocell-V 00 4 to / 60 to Vitocell-V 00 0 / Vitocell-V 00 CVA Series

More information

AIR CONDITIONER INSTALLATION MANUAL

AIR CONDITIONER INSTALLATION MANUAL INSTALLATION MANUAL AIR CONDITIONER Please read this installation manual completely before installing the product. Installation work must be performed in accordance with the national wiring standards by

More information

MIC-WKT and MIC-WKT-IR

MIC-WKT and MIC-WKT-IR MIC-WKT and MIC-WKT-IR Installation Manual Bosch Security Systems EN Installation and Operation Manual MIC-WKTI and MIC-WKT-IR Installation Manual EN 2 MIC-WKT and MIC-WKT-IR Washer Pump Drive Card Kits

More information

CAT AVR V2.3. Instruction Manual. Voltage regulator for generators. March 2008

CAT AVR V2.3. Instruction Manual. Voltage regulator for generators. March 2008 CAT AVR V2.3 Voltage regulator for generators March 2008 Instruction Manual Warnings WARNING The system should not be installed, operated, serviced or modified except by qualified personnel who understand

More information

1 General information

1 General information 1 General information 1.1 About this manual This manual describes the installation, function and operation of an integrated solar control system, which is suitable for split pressurized solar heating system.

More information

User Manual THR840DUK Digital Thermostat

User Manual THR840DUK Digital Thermostat User Manual THR840DUK Digital Thermostat 50051982-001 Rev. A WARNING: This product must be correctly installed and configured to work properly (see pages 12-24). If you are not experienced in wiring electrical

More information

INSTRUCTION MANUAL HYDRAULIC GATE TRANSMISSION SYSTEM ECO240-ECO360

INSTRUCTION MANUAL HYDRAULIC GATE TRANSMISSION SYSTEM ECO240-ECO360 INSTRUCTION MANUAL HYDRAULIC GATE TRANSMISSION SYSTEM ECO240-ECO360 IMPORTANT SAFETY INSTRUCTIONS WARNING! To reduce the risk of injury or death it is important to closely follow all of the following instructions.

More information

HERZ-Thermal Actuators

HERZ-Thermal Actuators HERZ-Thermal Actuators Data Sheet 7708-7990, Issue 1011 Dimensions in mm 1 7710 00 1 7710 01 1 7711 18 1 7710 80 1 7710 81 1 7711 80 1 7711 81 1 7990 00 1 7980 00 1 7708 11 1 7708 10 1 7708 23 1 7709 01

More information

! WARNING. McDonnell & Miller Installation & Maintenance Instructions MM-217(I) Series 150S and 157S (Snap Switch, All Models except 157S-RB-P)

! WARNING. McDonnell & Miller Installation & Maintenance Instructions MM-217(I) Series 150S and 157S (Snap Switch, All Models except 157S-RB-P) Series 150S and 157S (Snap Switch, All Models except 157S-RB-P) Low Water Cut-Off/Pump Controllers For Steam Boilers and Other Level Control Applications McDonnell & Miller Installation & Maintenance Instructions

More information

RVL470. Heating Controller. Building Technologies HVAC Products. Series B

RVL470. Heating Controller. Building Technologies HVAC Products. Series B 2 522 Heating Controller Series B RVL470 Multifunctional heating controller for use in residential and non-residential buildings; suitable for weather-dependent flow temperature control of heating zones

More information

Drayton Digistat +2RF/+3RF

Drayton Digistat +2RF/+3RF /+3RF Programmable Room Thermostat Wireless Model: RF700/22090 Model: RF701/22092 Power Supply: Battery - Thermostat Mains - Digistat SCR Invensys Controls Europe Customer Service Tel: 0845 130 5522 Customer

More information

prestige Condensing Water Boiler SERVICE TECHNICIAN S TROUBLE SHOOTING GUIDE 2008-36 TSG-PRESTIGE Date revised: 12/6/10

prestige Condensing Water Boiler SERVICE TECHNICIAN S TROUBLE SHOOTING GUIDE 2008-36 TSG-PRESTIGE Date revised: 12/6/10 prestige Condensing Water Boiler SERVICE TECHNICIAN S TROUBLE SHOOTING GUIDE Date revised: 12/6/10 2008-36 TSG-PRESTIGE Table of Contents INTRODUCTION Page 1-2 SERVICING TIPS AND INSTRUCTIONS Page 3-4

More information

Heating Controller. Building Technologies HVAC Products

Heating Controller. Building Technologies HVAC Products 2 474 Heating Controller RVP300 Multifunctional heating controller for use in residential and non-residential buildings; suitable for weather-dependent flow temperature control of heating zones with or

More information

TYXIA. *2702178_Rev.1* Installation and User Guide. Wireless receiver. TYXIA RF 642-1 channel

TYXIA. *2702178_Rev.1* Installation and User Guide. Wireless receiver. TYXIA RF 642-1 channel Installation and User Guide TYXIA Wireless receiver TYXIA RF 642-1 channel DELTA DORE Bonnemain - 35270 COMBOURG - France E-mail : deltadore@deltadore.com Unit compliant with the requirements of directives:

More information

Operating Instructions. VITODENS r 200/222 Series With Vitotronic 200 HO1B Controls WARNING WARNING IMPORTANT

Operating Instructions. VITODENS r 200/222 Series With Vitotronic 200 HO1B Controls WARNING WARNING IMPORTANT Operating Instructions Vitodens 200-W, B2HA and B2HB Models 19 to 150 Wall-mounted, gas-fired condensing boiler For operation with natural gas and liquid propane gas Heating input: 12 to 530 MBH 3.5 to

More information

TIG INVERTER INSTRUCTION MANUAL

TIG INVERTER INSTRUCTION MANUAL TIG INVERTER INSTRUCTION MANUAL Contents Warning General Description Block Diagram Main Parameters Circuit Diagram Installation and Operation Caution Maintenance Spare Parts List Troubleshooting 3 4 4

More information

Max primary circuit temperature 90ºC Max primary circuit temp. 90ºC Max secondary circuit temperature 45ºC Max secondary circuit temp.

Max primary circuit temperature 90ºC Max primary circuit temp. 90ºC Max secondary circuit temperature 45ºC Max secondary circuit temp. EGLISH 1 Product description exchanger equipped with an electronic control unit and circulation pump for the primary circuit. All Aqua-Mex variants can be ordered with an interior coil of either titanium

More information

ELECTRIC CENTRAL HEATING FLOW BOILER

ELECTRIC CENTRAL HEATING FLOW BOILER ELECTRIC CENTRAL HEATING FLOW BOILER EKCO.T Used product can t be treated as general communal waste. Disassembled appliance has to be delivered to the collection point of electrical and electronic equipment

More information

IMPORTANT: BEFORE INSTALLING ANY HEATING TERMINAL UNIT TO A DOMESTIC WATER HEATER, CONSULT THE LOCAL PLUMBING CODES.

IMPORTANT: BEFORE INSTALLING ANY HEATING TERMINAL UNIT TO A DOMESTIC WATER HEATER, CONSULT THE LOCAL PLUMBING CODES. QUIET-ONE Environmental Products 2000 Kickspace Heater Series Models: KS 2004, KS 2006 KS 2008, KS 2010 INSTALLATION OPERATING MAINTENANCE Please read these instructions thoroughly before beginning your

More information

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw 4 937 DESIO Current valve for AC 24 V pulse/pause control of electrical loads up to 30 kw SEA45.1 Use The current valve is used for the control of electric heating elements in heating, ventilation and

More information

HEAVY DUTY STORAGE GAS

HEAVY DUTY STORAGE GAS Multi-Fin flue technology Flue damper saves energy Electronic controls HEAVY DUTY STORAGE GAS Dependability The Rheem heavy duty gas range is the work horse of the industry having proved itself over many

More information

HEAT INTERFACE UNITS (Modular)

HEAT INTERFACE UNITS (Modular) HEAT INTERFACE UNITS The Rhico T Fire Modular is probably the most versatile HIU available, the basic unit is a indirect heating only module incorporating a circulation pump on the secondary circuit. (A

More information

Speedflow Undersink Unvented Water Heater. Models SF10K and SF15K. Instruction Manual

Speedflow Undersink Unvented Water Heater. Models SF10K and SF15K. Instruction Manual Speedflow Undersink Unvented Water Heater Models SF10K and SF15K Instruction Manual Version 2.0 May 2009 Hyco SpeedFLOW UnVENTED WATER HEATER Models SF10K (10 Litres) and SF15K (15 Litres) 1. Introduction

More information

GeniSys 12V. Model 7556. Description / Applications. Advanced 12 Vdc Burner Control

GeniSys 12V. Model 7556. Description / Applications. Advanced 12 Vdc Burner Control PARTS & ACCESSORIES GeniSys 12V Model 7556 Advanced 12 Vdc Burner Control Description / Applications The Beckett GeniSys TM 12V Advanced Burner Control is a 12 Vdc primary safety control for oil burners

More information

- mark gas burners Cuenotherm NC.4 - NC.6 - NC.9 14.5-90kW.

- mark gas burners Cuenotherm NC.4 - NC.6 - NC.9 14.5-90kW. - mark gas burners Cuenotherm NC.4 - NC.6 - NC.9 14.5-9kW. Low NO x Comprehensive control panel Gas rack Low NOx combustion head Strong light alloy pressuremoulded housing Electronic ignition transformer

More information

ecomax Instructions for use Wall hung room sealed fan assisted condensing boilers For the user

ecomax Instructions for use Wall hung room sealed fan assisted condensing boilers For the user For the user Instructions for use ecomax Wall hung room sealed fan assisted condensing boilers ecomax 63/ E ecomax 68/ E ecomax 6/ E ecomax 635 E ecomax 84/ E ecomax 88/ E ecomax 835 E GB Table of contents

More information

INSTALLATION GUIDE 1

INSTALLATION GUIDE 1 INSTALLATION GUIDE 1 Setting information MAC-558IF-E address(mac) MAC-558IF-E serial number(id) MAC-558IF-E code(pin) Indoor unit model name Indoor unit serial number Outdoor unit model name Outdoor unit

More information

Propane Conversion Kit PROPANE CONVERSION KIT INSTALLATION MANUAL

Propane Conversion Kit PROPANE CONVERSION KIT INSTALLATION MANUAL Propane Conversion Kit Supersedes: 145.25-IOM2 (708) Form 145.25-IOM2 (908) PROPANE CONVERSION KIT INSTALLATION MANUAL "LPKIT " - PROPANE CONVERSION KIT Kits are available for field conversion from natural

More information

RRV934. Multi-controller. Synco living

RRV934. Multi-controller. Synco living s 2 709 Synco living Multi-controller RRV934 RF-based multi-controller For precontrol of up to 2 room groups For control of ventilation plant with up to 3 stages RF communication based on KNX standard

More information

Programmable Room Thermostat 7 Day (5-2 Day) Models: 22083 / 22087 Power Supply: Battery / Mains

Programmable Room Thermostat 7 Day (5-2 Day) Models: 22083 / 22087 Power Supply: Battery / Mains Drayton Programmable Room Thermostat 7 Day (5-2 Day) Models: 22083 / 22087 Power Supply: Battery / Mains Invensys Controls Europe Technical Helpline: +44 (0) 845 130 7722 www.draytoncontrols.co.uk Installation

More information

36G22, 36G23, 36G24 & 36G52 36J22, 36J23, 36J24 & 36J52 DSI and HSI Single Stage Combination Gas Valve

36G22, 36G23, 36G24 & 36G52 36J22, 36J23, 36J24 & 36J52 DSI and HSI Single Stage Combination Gas Valve Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE. DESCRIPTION

More information

Safety technique. Emergency stop module BO 5988 safemaster

Safety technique. Emergency stop module BO 5988 safemaster Safety technique Emergency stop module BO 5988 safemaster 0221562 Function diagram Pushbutton on Mains or emergencystop () K1 According to EC Directive for machines 98/37/EG According to IEC/E 60204-1

More information

VITOSOL r 200-T SP2A. VITOSOL 200-T Type SP2A

VITOSOL r 200-T SP2A. VITOSOL 200-T Type SP2A Technical Data Manual Model Nos. and pricing: see Price List Vacuum tube collector based on the heat pipe principle For the utilisation of solar energy VITOSOL r 200-T SP2A Product may not be exactly as

More information

OZW30. Central Unit SYNERGYR

OZW30. Central Unit SYNERGYR 2 841 SYNERGYR Central Unit OZW30 Collects billing data from the apartments. Generates an image of each apartment's heat consumption and makes it available for readout. Acts on room temperature control

More information

Art.S001-S002 SOLAR MODULE WITH DELIVERY AND RETURN CONNECTIONS

Art.S001-S002 SOLAR MODULE WITH DELIVERY AND RETURN CONNECTIONS Art.S001-S002 SOLAR MODULE WITH DELIVERY AND RETURN CONNECTIONS Technical Information sheet 0001/07/Rev01 ENG FUNCTION Series S001 and S002 circulation units are applied to the primary circuit of solar

More information

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit. Current Transducer HO-P series I PN = 6, 10, 25 A Ref: HO 6-P, HO 10-P, HO 25-P For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary

More information

is then retained absolutely without interruption.

is then retained absolutely without interruption. Page 1 of 11 DC UPS uninterruptible power supplies - DC UPS module 15 A Compact design, only 50 mm wide Absolutely interruption-free buffering of power failures through immediate electronic connection

More information

SF15K SF05KSS, SF10KSS

SF15K SF05KSS, SF10KSS Product Instruction Manual Speedflow SF05K, SF10K & SF15K SF05KSS, SF10KSS & SF15KSS Undersink unvented water heater V15.6/6 Version 3.2 Jan 2015 Thank you for purchasing a Hyco Speedflow unvented water

More information

DUAL SENSING DIGITAL THERMOSTAT PRODUCT INSTRUCTIONS. Construction Automotive Industry

DUAL SENSING DIGITAL THERMOSTAT PRODUCT INSTRUCTIONS.  Construction Automotive Industry DUAL SENSING DIGITAL THERMOSTAT PRODUCT INSTRUCTIONS www.rehau.com Construction Automotive Industry SCOPE This guide gives instruction regarding REHAU Programmable Digital Thermostat installation and operation.

More information

SunMaxx Solar Filling Station Operating Instructions

SunMaxx Solar Filling Station Operating Instructions SunMaxx Solar Filling Operating Instructions Content 1. Declaration of conformity... 2 2. Introduction... 2 3. Transportation and unpacking... 4 4. Mounting and commissioning... 5 5. End of operation...

More information

Operating instructions Mechatronic flow sensor. SBY33x 704465/06 03/2011

Operating instructions Mechatronic flow sensor. SBY33x 704465/06 03/2011 Operating instructions Mechatronic flow sensor SBY33x 7065/06 03/2011 Contents 1 Safety instructions...2 2 Functions and features...3 3 Installation...3 Electrical connection... 5 Switch point setting...

More information

G670 Intermittent Pilot Ignition Controls

G670 Intermittent Pilot Ignition Controls Installation Sheets Manual 121 Gas Combustion Combination Controls and Systems Section G Technical Bulletin Issue Date 0300 Intermittent Pilot Ignition Controls Figure 1: Intermittent Pilot Ignition Control

More information

Vitosoft 200 Vitodata 300 Vitocom 300 Vitocom 100

Vitosoft 200 Vitodata 300 Vitocom 300 Vitocom 100 Contents Page 1, type FA1 1.1 Function description................................................................................... 6 1.2 Pre requisites.............................................................................................

More information

REB 1 REB 3 REB 5 REB 6 REB 8 REB 10 REB 12 REB 16

REB 1 REB 3 REB 5 REB 6 REB 8 REB 10 REB 12 REB 16 REB 1 REB 3 REB 5 REB 6 REB 8 REB 10 REB 12 REB 16 Manually Operated Electronic Speed Controller Single Phase For all applications using suitably specified single-phase induction motor fans 1 GENERAL The

More information

Operating Instructions & User s Information Manual VITODENS 100-W WARNING WARNING IMPORTANT. Read and save these instructions for future reference.

Operating Instructions & User s Information Manual VITODENS 100-W WARNING WARNING IMPORTANT. Read and save these instructions for future reference. Operating Instructions & User s Information Manual Vitodens 100-W WB1B Series Wall-Mounted, gas-fired condensing boiler with optional on demand hot water CombiPLUS Kit Heating input: 37 to 118 MBH 10.8

More information

Smile. The All-In-One Heating Controller

Smile. The All-In-One Heating Controller Smile EVERYTHING UNDER CONTROL The All-In-One Heating Controller Versatile, energy-efficient heating control. The All-In-One Heating Controller Smile controllers are ideal to gain maximum efficiency from

More information

Brake module AX5021. Documentation. Please read this document carefully before installing and commissioning the brake module!

Brake module AX5021. Documentation. Please read this document carefully before installing and commissioning the brake module! Documentation Brake module AX5021 Please read this document carefully before installing and commissioning the brake module! Version : 1.2 : 2012.03.05 Date Article-no. : TDmlAX-5021-0000-0200 Page 2/8

More information

TANKLESS WATER HEATER INSTALLATION DIAGRAMS

TANKLESS WATER HEATER INSTALLATION DIAGRAMS TANKLESS WATER HEATER INSTALLATION DIAGRAMS Installation Diagrams Tankless Installation / Optional Return Small 10-15 Gallon Point-of-Use Water Single and Optional Return : One single, small capacity water

More information

RVR Hybrid System Installer Instructions - 10052012. RVR Hybrid System Controller Installation Instructions

RVR Hybrid System Installer Instructions - 10052012. RVR Hybrid System Controller Installation Instructions RVR Hybrid System Controller Installation Instructions 1 Introduction to Hybrid Systems The RVR Hybrid system uses a combination of the Immergas Audax range of heat pumps with gas or oil boilers to create

More information

Conlift1, Conlift2, Conlift2 ph+

Conlift1, Conlift2, Conlift2 ph+ GRUNDFOS DATA BOOKLET Conlift1, Conlift2, Conlift2 ph+ Small lifting stations 50 Hz CONLIFT1, CONLIFT2, CONLIFT2 ph+ Table of contents 1. Product overview 3 Conlift for condensate applications 3 Applications

More information

DLP-PU/E Instruction Manual

DLP-PU/E Instruction Manual Instruction Manual BEFORE USING THE POWER SUPPLY UNIT Pay attention to all warnings and cautions before using the unit. Incorrect usage could lead to an electrical shock, damage to the unit or a fire hazard.

More information

Addendum to the Operating Instructions

Addendum to the Operating Instructions Drive Technology \ Drive Automation \ System Integration \ Services Addendum to the Operating Instructions MOVIMOT with AS-Interface and AC Motor DT/DV Unit Replacement MOVIMOT MM..C -> MM..D with MLK3A

More information

BB800 Off-Grid Solar System

BB800 Off-Grid Solar System BB800 Off-Grid Solar System KEY PRODUCT FEATURES Control Box & Charge Controller 1000W of Solar Panels 4x200Ah of SLA Batteries in series 2KW Inverter Output Power Solar Panel & Battery Mounting Our entry

More information

12 SOLAR PHOTOVOLTAIC POWER SUPPLY SYSTEMS by John Ware. PV modules are current-limiting

12 SOLAR PHOTOVOLTAIC POWER SUPPLY SYSTEMS by John Ware. PV modules are current-limiting 12 SOLAR PHOTOVOLTAIC POWER by John Ware IT IS PLANNED for BS 7671:2008 to include a new Section 712 providing additional requirements for safety applicable to solar photovoltaic (pv) power supply systems.

More information

User Manual. Gas fired condensing wall hung boiler. G.C.N : 41-116 - 30 (12 kw) G.C.N : 41-116 - 31 (18 kw) G.C.N : 41-116 - 32 (24 kw)

User Manual. Gas fired condensing wall hung boiler. G.C.N : 41-116 - 30 (12 kw) G.C.N : 41-116 - 31 (18 kw) G.C.N : 41-116 - 32 (24 kw) User Manual Gas fired condensing wall hung boiler G.C.N : 41-116 - 30 (12 kw) G.C.N : 41-116 - 31 (18 kw) G.C.N : 41-116 - 32 (24 kw) CLAS HE R 12 CLAS HE R 18 CLAS HE R 24 Country of destination GB, IE

More information

Instruction Bulletin. MCS025 Sync-Check Module Installation Sheet

Instruction Bulletin. MCS025 Sync-Check Module Installation Sheet Instruction Bulletin 63230-216-244B1 LaVergne, TN, USA MCS025 Sync-Check Module Installation Sheet Retain for future use. DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Only qualified electrical

More information

Adjustable room thermostat for heating only or cooling only systems

Adjustable room thermostat for heating only or cooling only systems 3 003 Room hermostat RAA30 Adjustable room thermostat for heating only or cooling only systems Room thermostat with manual O/OFF switch wo-position control witching voltage AC 24 250 V Use he RAA30 room

More information

Please also see 10 golden rules for correct Saniflo installation on www.saniflo.co.uk

Please also see 10 golden rules for correct Saniflo installation on www.saniflo.co.uk 1. Description Sanicom is a lifting pump for wastewater used in commercial applications (restaurants, hairdressing salons, the catering industry etc.). The unit operates automatically, has a high performance

More information

Luna 3 Comfort Troubleshooting Guide June 2008

Luna 3 Comfort Troubleshooting Guide June 2008 Luna 3 Comfort Troubleshooting Guide June 2008 For Technical Assistance Call: (800)461-4657 WARNING! THIS DOCUMENT IS INTENDED ONLY AS AN EDUCATIONAL TOOL This Troubleshooting Guide, and the instructions

More information

Operational Overview and Controls Guide. Two or Three Pump IronHeart Lite with Variable Frequency Drives

Operational Overview and Controls Guide. Two or Three Pump IronHeart Lite with Variable Frequency Drives DOCUMENT: ECSEQ6-0 EFFECTIVE: 09/23/10 SUPERSEDES: Operational Overview and Controls Guide Two or Three Pump IronHeart Lite with Variable Frequency Drives 6700 Best Friend Road. Norcross, GA 30071. (770)

More information

BroadBand PowerShield. User Manual

BroadBand PowerShield. User Manual BroadBand PowerShield User Manual 990-0375G 12/2006 Chapter 1 General Information The PowerShield provides a power source for broadband telephony and other DC applications. Safety This Safety Guide contains

More information

Digi-Motor Installation Guide

Digi-Motor Installation Guide Digi-Motor Installation Guide Installation Video...located at marsdelivers.com Digi-Motor Installation Guide Digi-Motor For technical assistance with your Azure Digi-Motor, call the MARS technical support

More information

Instruction Manual for Operating Panel 301 and 302

Instruction Manual for Operating Panel 301 and 302 Instruction Manual for Operating Panel 301 and 30 Edition: 1/006 Edition: 1/006 Contents 1 Introduction and Overview........................ 5 1.1 Panel 301 Controls........................................

More information

Installation Instructions

Installation Instructions H5HK Series Installation Instructions 3 Phase Electric Heater Kits 7.5 and 0 TON Package A/C Systems Description Installation of 08/40V and 480V H5HK 3 Phase Heater Kits in 7.5 and 0 TON Packaged Air Conditioners.

More information

PSR The compact range Description

PSR The compact range Description Description The PSR range is the most compact of all the ABB softstarter ranges, thereby making it possible to fit many devices into the same enclosure. The system concept with Manual Motor Starters provides

More information

Battery Charger For Nickel Cadmium and Nickel-Metal Hydride Rechargeable Batteries Model PSN Series

Battery Charger For Nickel Cadmium and Nickel-Metal Hydride Rechargeable Batteries Model PSN Series Battery Charger For Nickel Cadmium and Nickel-Metal Hydride Rechargeable Batteries Model PSN Series Operating Instructions WARNING CONCERNING THE REMOVAL OF COVER: CAUTION: TO PREVENT THE RISK OF ELECTRIC

More information

Documentation for. KL2602 and KL2622. Two-channel Relay Output Terminals for 230 V AC / 30 V DC. Version: 1.4 Date: 2013-03-20

Documentation for. KL2602 and KL2622. Two-channel Relay Output Terminals for 230 V AC / 30 V DC. Version: 1.4 Date: 2013-03-20 Documentation for KL2602 and KL2622 Two-channel Relay Output Terminals for 230 V AC / 30 V DC Version: 1.4 Date: 2013-03-20 Table of contents Table of contents 1 Foreword 1 1.1 Notes on the documentation

More information

Use & Care Manual. Electric Tankless Water Heaters. With Installation Instructions for the Installer AP15447 (10/10)

Use & Care Manual. Electric Tankless Water Heaters. With Installation Instructions for the Installer AP15447 (10/10) Use & Care Manual With Installation Instructions for the Installer Electric Tankless Water Heaters The purpose of this manual is twofold: one, to provide the installer with the basic directions and recommendations

More information

The NEW Greenstar i. intuitive. innovative. improved performance. installation ease

The NEW Greenstar i. intuitive. innovative. improved performance. installation ease The NEW Greenstar i innovative intuitive improved performance installation ease A NEW look, NEW features and a NEW NAME for the UK s best selling boiler, the Greenstar i Junior 1 Introducing the new Greenstar

More information

Operating instructions

Operating instructions Operating instructions Gas condensing boilers MGK-130 MGK-170 MGK-210 MGK-250 MGK-300 Wolf GmbH Postfach 1380 D-84048 Mainburg Tel. +49 8751/74-0 Fax +49 8751/741600 Internet: www.wolf-heiztechnik.de Document

More information

FIELD TESTS OF FUEL EFFICIENCY MAGNETS J A CRABB JULY 1997 SWEEG REPORT 80

FIELD TESTS OF FUEL EFFICIENCY MAGNETS J A CRABB JULY 1997 SWEEG REPORT 80 FIELD TESTS OF FUEL EFFICIENCY MAGNETS J A CRABB JULY 1997 SWEEG REPORT 80 List of symbols T f average temperature at the flow header, C T r average temperature at the return header, C f average water

More information

Photovoltaic Solar Energy Unit EESFB

Photovoltaic Solar Energy Unit EESFB Technical Teaching Equipment Photovoltaic Solar Energy Unit EESFB Products Products range Units 5.-Energy Electronic console PROCESS DIAGRAM AND UNIT ELEMENTS ALLOCATION Worlddidac Member ISO 9000: Quality

More information

2-Stage, 3-phase controller Type 30051/1500051

2-Stage, 3-phase controller Type 30051/1500051 2-Stage, 3-phase controller Type 30051/1500051 Installation instructions Retain for future use System s for heating, cooling, ventilating ED I012/02/02/5GB Contents Correct and proper use Important information

More information

CHECKING AND TESTING ELECTRICAL INSTALLING WORK

CHECKING AND TESTING ELECTRICAL INSTALLING WORK CHECKING AND TESTING ELECTRICAL INSTALLING WORK Department of Consumer and Employment Protection Energy Safety Preface It is a requirement of the Electricity (Licensing) Regulations 1991 that all electrical

More information

WE-350 Series ¼ Turn Electric Actuator

WE-350 Series ¼ Turn Electric Actuator WE-350 Series ¼ Turn Electric Actuator Operation and Installation Manual Pg 1 (Rev. 020113) Table of Contents 1.0 General 1.1 Pre-Installation Inspection 1.2 Storage 1.3 Features & General Information

More information

Installation Guide. DEVIreg 530. Electronic Thermostat. www.devi.com

Installation Guide. DEVIreg 530. Electronic Thermostat. www.devi.com Installation Guide DEVIreg 530 Electronic Thermostat www.devi.com The English language is used for the original instructions. Other languages are a translation of the original instructions. (Directive

More information

Modular I/O System Analog and Digital Interface Modules

Modular I/O System Analog and Digital Interface Modules OPERATING INSTRUCTIONS Modular I/O System Analog and Digital Interface Modules Installation Operation Maintenance Document Information Document ID Title: Operating Instructions Modular I/O System Part

More information

TECHNICAL SUPPORT MANUAL 3 Phase Air Conditioner Component R2A3**GHR

TECHNICAL SUPPORT MANUAL 3 Phase Air Conditioner Component R2A3**GHR 3 Phase Air Conditioner Component R2A3**GHR DANGER, WARNING, CAUTION, and NOTE The signal words DANGER, WARNING, CAU- TION, and NOTE are used to identify levels of hazard seriousness. The signal word DANGER

More information

DMG 970. Gas Burner Safety Control. For 2-stage forced draught and combi oil/gas burners

DMG 970. Gas Burner Safety Control. For 2-stage forced draught and combi oil/gas burners A Honeywell Company Gas Burner Safety Control For 2-stage forced draught and combi oil/gas burners Possible flame detectors: - Ionisation probe - Infrared flicker detector 1020 - UV flame sensor UVD 971

More information

LUCCI AIRFUSION QUEST II CEILING FAN

LUCCI AIRFUSION QUEST II CEILING FAN LUCCI AIRFUSION QUEST II CEILING FAN WITH IR REMOTE INSTALLATION OPERATION MAINTENANCE WARRANTY INFORMATION CAUTION READ INSTRUCTIONS CAREFULLY FOR SAFE INSTALLATION AND FAN OPERATION. V1.0 QUEST II IR

More information

aseries A13B Mini Bullet Camera User Manual

aseries A13B Mini Bullet Camera User Manual aseries A13B Mini Bullet Camera User Manual Thank you for purchasing our product. If there are any questions, or requests, please do not hesitate to contact the dealer. This manual applies to the MicroView

More information

DMX2PWM 9 Channel Dimmer Setup Manual

DMX2PWM 9 Channel Dimmer Setup Manual DMX2PWM 9 Channel Dimmer Setup Manual www.ecue.de DMX2PWM 9ch Dimmer - Setup Manual e:cue control GmbH An OSRAM Company Rev. 1.3_01/2010 DMX2PWM 9ch Dimmer - Setup Manual Table of Contents 1. Device Overview....................................4

More information

ACS-30-EU-EMDR-10-MOD

ACS-30-EU-EMDR-10-MOD Multi-application heat tracing Control and Monitoring in commercial and residential buildings Roof & Gutter de-icing sensor module Technical Information Approvals Module IP rating Ambient operating temperature

More information