Operating Manual A-ISOMETER IR1575PG1
|
|
|
- Dale Fields
- 9 years ago
- Views:
Transcription
1 Operating Manual A-ISOMETER IR1575PG1 Insulation monitoring device for IT AC and DC systems with integrated test current generator for insulation fault location Power in electrical safety TGH1380en/
2 Dipl.-Ing. W. Bender GmbH & Co.KG Londorfer Str Grünberg Germany Postfach Grünberg Germany Tel.: +49 (0) Fax: +49 (0) Web server: BENDER Germany All rights reserved. Reprinting only with permission of the publisher. Subject to change!
3 Table of Contents 1. Safety information Use for the intended purpose Warranty and liability Personnel About the operating manual Hazards when handling the A-ISOMETER IR1575PG Inspection, transport and storage Note Explanations of symbols and warnings Directions for installation Function IR1575PG1 characteristics Product description Function Commissioning flow chart Commissioning of the A-ISOMETER functionality Commissioning of the insulation fault location function (EDS) (1) Connection Wiring Operation and setting Operating elements and displays IR1575PG Display in the standard mode Display in the Menu mode TGH1380en/
4 Table of Contents Display in the EDS mode Function keys Menu structure Diagram menu structure ISO SETUP menu: A-ISOMETER default settings Response values Alarm1 and Alarm Operating principle of the alarm relays Diagram ISO SETUP Memory setting (on/off) EDS SETUP menu: default settings for fault location EDS on / auto / 1cycle / off maxpuls: 10 / 25 ma Diagram EDS-SETUP PASSWORD menu Password activation and setting Diagram PASSWORD LANGUAGE menu Language setting Diagram Language SERVICE menu INFO menu Diagram INFO Operation with EDS device EDS Technical data IR1575PG Data in tabular form Standards and approvals Characteristic curves Dimension diagram enclosure IR1575PG Ordering details Standard version Label for modified versions TGH1380en/
5 1. Safety information 1.1 Use for the intended purpose The A-ISOMETER is intended for: monitoring the insulation resistance of IT systems localisation of insulation faults using EDS insulation fault evaluators Any other use, or any use which goes beyond the foregoing, is deemed to be used other than for the intended purpose. The BENDER companies shall not be liable for any losses or damage arising therefrom. Use for the intended purpose also includes compliance with all information in the operating instructions and compliance with test intervals. As a basic principle, our "General conditions of Sale and Delivery" shall apply. At the latest, these shall be available to the operator when the contract is concluded. 1.2 Warranty and liability Warranty and liability claims in cases of damage to persons and property shall be excluded if they are attributable to one or more of the following causes: Use of the A-ISOMETER other than for the intended purpose Incorrect assembly or installation, commissioning, operation and maintenance of the A-ISOMETER Failure to comply with the information in the operating instructions regarding transport, commissioning, operation and maintenance of the A-ISOMETER Unauthorized structural modifications to the A-ISOMETER Failure to comply with the technical data Improperly executed repairs, and the use of spare parts or accessories which are not recommended by the manufacturer Cases of disaster and force majeure Assembly and installation with device combinations not recommended TGH1380en/
6 Safety information This operating manual, especially the safety information, must be observed above all by personnel who work on the A-ISOMETER. In addition, the rules and regulations that apply for accident prevention at the place of use must be observed Personnel Only appropriately qualified staff may work on the A-ISOMETER. Qualified means familiar with the installation, commissioning and operation of the product and with training appropriate to the work. Personnel must have read and understood the safety section and warning information in this operating manual About the operating manual This operating manual has been compiled with the greatest possible care. Nevertheless, errors and mistakes cannot be entirely ruled out. The BENDER companies assume no liability whatsoever for any injury to persons or damage to property which may be sustained as a result of faults or errors in this operating manual Hazards when handling the A-ISOMETER IR1575PG1 The A-ISOMETER IR1575PG1 is constructed according to the state-of-the-art and recognized technical safety rules. Nevertheless, when it is being used, hazards may occur to the life and limb of the user or third parties, or there may be adverse effects on the A-ISOMETER or on other valuable property. The A-ISOMETER must only be used: for the purpose for which it is intended and when it is in perfect technical condition as far as safety is concerned. Any faults which may impair safety must be eliminated immediately. Impermissible modifications and the use of spare parts and additional devices which are not sold or recommended by the manufacturer of the devices may cause fires, electric shocks and injuries. Unauthorized persons must not have access to or contact with the A-ISOMETER. Warning signs must always be easily legible. Damaged or illegible signs must be replaced immediately. 6 TGH1380en/
7 Safety information Inspection, transport and storage Inspect the dispatch packaging and equipment packaging for damage, and compare the contents of the package with the delivery documents. In the event of damage in transit, please inform the BENDER company immediately. The devices must only be stored in areas protected from dust, damp and spray or dripping water, and in which the specified storage temperatures are maintained Note Make sure that the operating voltage is correct! Prior to insulation and voltage tests, the A-ISOMETER must be disconnected from the power system for the duration of these tests. In order to check the proper connection of the device, it is recommended to carry out a functional test. Make sure that the basic settings meet the requirements of the system. Children and unauthorized persons must not have access to or contact with the A-ISOMETER. 1.3 Explanations of symbols and warnings The following symbols are used in BENDER documentation to draw attention to important information and to make it easier to find certain text passages. The following examples explain the meaning of the symbols: The "Attention" symbol is used to draw attention to information warning employees of hazardous situations. Information you should know for correct handling of the product is marked with the "Info" symbol. TGH1380en/
8 Safety information 1.4 Directions for installation Only one insulation monitoring device may be used in each interconnected IT system. When insulation or voltage tests are to be carried out, the device shall be isolated from the system for the test period. The terminals and KE shall be connected by a separate wire to the protective conductor (PE). If the terminals L1, L2, L3 of the device are connected to a system under operation, the terminals and KE must not be disconnected from the protective conductor (PE). In order to check the proper connection of the device, it is recommended to carry out a functional test using a insulation fault against earth, e.g. via a suitable resistance, before starting the A-ISOMETER. The devices will be delivered with the following factory settings: ISO SETUP: Alarm 1 / Alarm 2 = 40 kω / 10 kω ISO SETUP: Operating principle K1/K2 ISO SETUP: Memory = off EDS SETUP: EDS = auto EDS SETUP: MaxPuls = 25 ma = N.O. test (N/O operation with relay test) Please check if the basic setting of the A-ISOMETER fulfils the requirements of the system to be monitored. When an AC system includes galvanically connected DC circuits, the following shall be considered: Insulation faults in DC circuits can only be monitored correctly when the rectifiers carry a continuous load of ma. 8 TGH1380en/
9 2. Function 2.1 IR1575PG1 characteristics A-ISOMETER for IT AC systems with galvanically connected rectifiers and for IT DC systems U n up to 480 V (IT = unearthed electrical systems) Automatic adaptation to the existing system leakage capacitance C e up to 60 μf AMP measuring principle (European Patent: EP B1) Generation of the test current necessary for selective insulation fault location Two separately adjustable ranges of response value of 2 kω... 1 MΩ each (Alarm1, Alarm2) Two-line LC display Connection monitoring of the measuring leads to the IT system and to earth Automatic device self test Option W : This option provides: improved shock and vibration resistance for use in ships, on rolling stock and in seismic environment. 2.2 Product description The A-ISOMETER Typ IR1575PG1 monitors the insulation resistance of 3(N)AC/AC and DC IT systems. AC systems monitored by the IR1575PG1 may include extensive DC supplied loads (such as converters). The device automatically adapts itself to the existing system leakage capacitance. 2.3 Function The A-ISOMETER IR1575PG1 is connected between the unearthed system and the protective conductor (PE). The response values and other function parameters are set via the function keys. The parameters are indicated on the LC display and are stored in a nonvolatile memory (EEPROM) after the setting is completed. The IR1575PG1 superimposes a microprocessor-controlled pulsating meas- TGH1380en/
10 Function uring voltage on the system being monitored using the AMP measuring principle. The "adaptive measuring pulse" is a patent developed and patented by BENDER (European Patent:EP B1). The measuring pulse consists of positive and negative pulses of the same amplitude. The period depends on the respective system leakage capacitances and the insulation resistances of the system being monitored. An insulation fault between system and earth closes the measuring circuit. After detecting the measuring values, the evaluation circuit calculates the insulation resistance which is indicated on the LC display after the measuring time. The measuring time is determined by the system leakage capacitances, the insulation resistance, and the system-related interferences. System leakage capacitances do not influence the measuring accuracy. If the reading is below the selected response values Alarm1/Alarm2, the associated alarm relays respond and the alarm LEDs Alarm1/2 light up and the measuring value is indicated on the display (in the event of DC insulation faults, the faulty supply line is indicated). If the terminals R1/R2 are bridged (external RESET button [NC contact] or wire bridge), the fault message will be stored. Pressing the RESET button or opening the connection R1/R2, resets the fault message, provided that the currently displayed insulation resistance is at least 25% above the actual response value. The fault memory behaviour can also be set in the "ISO SETUP" menu, under "Memory: on/off". In this case the terminals R1/R2 remain unused. By pressing the TEST button, the function of the A-ISOMETER IR1575PG1 can be tested. In this way, all essential measuring functions as well as connections to the system and to earth are checked. This self test can automatically be carried out every 24 hours. Normally, the self test is carried out after switching the supply voltage on. Self test In order to ensure high measuring reliability, the A-ISOMETER IR1575PG1 provides comprehensive self test functions. After switching the supply voltage on, all internal measuring functions, the components of the process control such as data and parameter storage as well as the connections L1 and L3 to the system and to earth are checked using the self test functions (L2 will not be monitored). The progress of the self test is shown on the display by 10 TGH1380en/
11 Function a bar graph. Depending on the system conditions, the self test is running for approximately s, then the message "Test ok" appears on the LC display for approximately 2 s. Then the device returns to normal measuring mode and the currently measured value is displayed after the expiry of the measuring time. When a device error or connection fault is detected, the message "Error" will appear on the display, the system fault LED (Alarm LED2) lights, the relay K2 ( ) switches and the respective alarm message (see table) is indicated. When such a system fault occurs, a self test will be started after approximately one minute. When no more malfunction is detected, the alarm message is deleted automatically, and the system fault LED extinguishes. During operation, the self test function can be started by pressing the TEST button (internal or external). The alarm relays Alarm1/2 only switch after starting the self test function by pressing the TEST button. Insulation fault location Another function of the IR1575PG1 is the generation of the test current for selective insulation fault location. When the value of the insulation resistance falls below the set response values Alarm1 and Alarm2, the IR1575PG1 generates the respective test current. In combination with an EDS insulation fault evaluator and the associated measuring current transformers connected to it, the insulation fault can be selectively detected. If no test current > 5 ma can be generated, the alarm message "No EDS funct." will be indicated. This may be caused by a device defect, loss of voltage or overtemperature in the device. Another cause may be a response value selected too high resulting in an increased insulation resistance too high to generate a sufficient test current. TGH1380en/
12 Function Alarm messages and corrective actions: Alarm message Description Corrective actions System connection? Connection PE? Device error x Insulation fault No EDS Funct. No low-resistance connection of the terminals L1, L3 to the system No low-resistance connection between terminal and KE to earth (PE) Internal device error The insulation resistance value has fallen below the set response value A test current cannot be generated 1. Check the wiring of the terminals L1, L3 to the system 2. Press the TEST button 3. Switch the supply voltage on and off 4. Check the fuse 1. Check wiring of terminal and KE to earth (PE) 2. Press the TEST button 3. Switch the supply voltage on and off 1. Press the TEST button 2. Switch the supply voltage on and off 3. Contact Bender 1. Reduce the response value 2. Locate and clear insulation fault (EDS470-12) 1. Check response value 2. Check supply voltage 12 TGH1380en/
13 Function Reset sequence control If the on/off switching of the supply voltage is not possible for technical reasons, a RESET of the sequence control is to be carried out by pressing the buttons "RESET", "MENU" and "TEST" in succession. Proceed as follows: 1. Press and hold down the RESET button 2. Press and hold down the MENU button 3. Press the TEST button for at least 2 s After executing the steps described above, the sequence control including the self test are restarted again. TGH1380en/
14 Function 14 TGH1380en/
15 3. Commissioning flow chart 3.1 Commissioning of the A-ISOMETER functionality The encircled figures in the three pages of the flow charts correspond to the figures in the legend to wiring diagram (see page 25). Commissioning of the A-ISOMETER (1) Is the system to be monitored an unearthed system (IT system)? no The IR1575PG1 is not suitable for this application (contact Bender). Is the voltage to be monitored Un AC 480 V? or Un DC 480 V? no The IR1575PG1 is not suitable for this application (contact Bender). Deenergize the installation before connecting the device! yes Device connection Recommended wire cross section of connecting cable single wire mm2 flexible mm2 yes Optional device connectionl Connect the two PE connections and KE separately to the equipotential bonding 6 External TEST button (NO contact) to the terminals T1 and T2 7 Connect the terminals L1, L2 and L3 according to the wiring diagram to the system to be monitored Un. Connect the supply voltage Us to the terminals A0(-) and A1(+) or A0 and A2 (AC 400 V). Consider the indications on the nameplate External RESET button (NC contact) to the terminals R1 and R2 Output contacts of the alarm relays 9 Alarm1 ( ) Alarm2 ( ) 10 8 TGH1380en/
16 Commissioning flow chart Commissioning of the A-ISOMETER (2) Connect the supply voltage Connect the voltage of the system to be monitored The A-ISOMETER carries out a self test. The insulation value is being displayed after completion of the measuring process. Shall the default setting be changed? Alarm1 = 40 kohm Alarm2 = 10 kohm K1/K2 = N/O operation Memory = off no yes Select ISO SETUP (see chapter operation and setting) Does one of the alarm LEDs light? no yes The insulation value of the system being monitored is below the set respone value. Change the response value or improve the insulation state of the system. 16 TGH1380en/
17 Commissioning flow chart Commissioning of the A-ISOMETER (3) In order to check the proper connection, a functional test is to be carried out using a suitable resistance: Size of the resistance: 50% of the preset response value Alarm2. Do both alarm LEDs light? Did the alarm relays switch? yes no Check the connecting leads! Is system voltage Un available across the terminals L1/L2/L3? Check the voltages with a voltmeter. Do both alarm LEDs light? Did the alarm relays switch? Remove the resistor! yes Alarm LEDs extinguished? Did the alarm relays change their position? no yes The IR1575PG1 is correctly connected and functions reliably! TGH1380en/
18 Commissioning flow chart 3.2 Commissioning of the insulation fault location function (EDS) (1) Disconnect the electrical installation before connecting the device! Install the components of the insulation fault location system EDS470 including the associated measuring current transformers TGH1282 TGH1243 Turn the supply voltage on Turn the system voltage on The IR1575PG1 carries out a self test EDS470 is being applied Set the max. test current (maxpuls) to 25 ma (10 ma) in the EDS-SETUP menu Set the EDS to Master mode TGH TGH1380en/
19 Commissioning flow chart Commissioning of the function insulation fault location (EDS) (2) Carry out a functional test between system and earth using a resistance of 50% of the lowest response value downstream a CT. Alarm LEDs 1 and 2 light Alarm relays switch Display: -EDS:on-auto-- no Make sure that EDS-auto is activated in the EDS-SETUP menu Scanning of the CTs by EDS470-12? yes Is the faulty subcircuit being recognized correctly? yes Shall any other connected CT be checked? no no yes Set the EDS to Master mode (DIP switch) To check another CT, remove the resistance and select another location for the insulation fault upstream a CT. Remove resistance Do the alarm LEDs extinguish? Alarm relays switched over? no Delete alarm messages using the RESET button at EDS The EDS470 is correctly connected and functions reliably TGH1380en/
20 Commissioning flow chart 20 TGH1380en/
21 4. Connection 4.1 Wiring IR1575PG1 has plug-in terminals. Connect the terminals A0/A1 respectively A0/A2 to the supply voltage U s in accordance with IEC The connections to the supply voltage shall be provided with protective devices to afford protection in the event of a short circuit (a 6 A fuse is recommended). Devices for protection against short circuit in conformity with IEC for the IT system coupling L1/L2/L3 can be omitted if the wiring is carried out in such a manner as to reduce the risk of a short-circuit to a minimum. (a short-circuit-proof and insulation-fault-proof wiring is recommended) Only one A-ISOMETER may be connected to an external TEST or RESET button. A galvanic parallel connection of several TEST and RESET inputs for collective testing of A-ISOMETER s is not permitted. TGH1380en/
22 Connection IR1575PG K2 K1 T1 T2 R1 R A0 A1 A2 L1 L2 L3 KE 1 -/~ +/~ ~ Un PE 6 Us AC/DC 0V AC/DC 230V AC 400V 2 3 AC system L1 Un L2 L3 L1 L2 L3 AC system Un L1 L2 L3 L1 L2 5 L1 L2 L3 DC system Un L+ L TGH1380en/
23 Connection Legend to wiring diagram: 1 Supply voltage Us (see nameplate, Technical Data on page 43 or the ordering details ) via 6 A fuse: 2 Connection of the 3AC system to be monitored: connect the terminals L1, L2, L3 to the conductors L1, L2, L3 4 Connection of the DC system to be monitored: connect L1 to conductor L+, terminal L2, L3 to conductor L- 5 Connection of the AC system to be monitored: connect terminal L1 to conductor L1, terminals L2, L3 to conductor L2 6 Separate connection of and KE to PE 7 External TEST button (NO contact) 8 External RESET button (NC contact or wire jumper), when the terminals are open, the alarm message will not be stored, Factory setting: Memory off! 9 Alarm relay: Alarm2 10 Alarm relay: Alarm1 IR1575PG1-434 A0 A1 A2 1 -/~ +/~ Us AC/DC 0V AC V / DC 10,2..84 V TGH1380en/
24 Connection 24 TGH1380en/
25 5. Operation and setting 5.1 Operating elements and displays IR1575PG1 1 ***IT-SYSTEM**** R >5.0MW TEST RESET MENU Two-line display for standard and menu mode 2 TEST button: to activate the self test/ Up key: parameter change, moving up in the menu 3 RESET button: to delete insulation fault alarms/ Down key: parameter change, moving down in the menu 4 MENU key: activating the menu system / Enter key: confirmation parameter change 5 Alarm LED 1 lights: insulation fault, first warning level reached 6 Alarm LED 2 lights: insulation fault, second warning level reached, or system fault message TGH1380en/
26 Operation and setting Display in the standard mode Insulation Rs=011kW fault Indication of the insulation resistance in kω 2 Additional information about the insulation resistance: + = insulation fault at L+ = insulation fault at L s = new measurement is running 3 = Polarity of the measuring pulse (AMP) 4 Messages: - Insulation fault - Connection system? - Connection PE? - Device error x - No EDS function Display in the Menu mode 1. EXIT 2. ISO SETUP Parameter change is allowed Parameter change is blocked,, enabling by a password 26 TGH1380en/
27 Operation and setting Display in the EDS mode Insulation fault -EDS:on-auto Indication of an insulation fault 2 EDS operating modes: - EDS:on EDS:on-auto-- - EDS:on-1cycle-- = Polarity of the test current TGH1380en/
28 Operation and setting Function keys Two functions are assigned to each function key. In addition to the encircled basic functions, all keys allow navigation within the menu. TEST RESET Pressing the TEST key starts the A-ISOMETER self test. Pressing the RESET button resets insulation fault alarm messages stored in the A-ISOMETER. This function is only available after activating the fault memory in the ISO-Setup menu or after bridging R1/ R2. Furthermore, the A-ISOMETER can only be reset when the currently measured insulation value is 25% above the set response value. Pressing the MENU key opens the menu system. MENU The UP/DOWN keys and the ENTER key are used for menu system control: TEST Up key: Moving up in the menu, increasing parameters. RESET Down key: Moving down in the menu, reducing a parameter. MENU ENTER key Selecting a menu item or sub menu item, confirming or storing a parameter change and going back to the associated sub menu item or going to the next input area. If the menu is not closed, the device changes to the display mode after approximately 5 minutes. 28 TGH1380en/
29 Operation and setting For the sake of clarity, only the following symbols are used to represent the functions ENTER and UP/DOWN: TGH1380en/
30 Operation and setting 5.2 Menu structure Switchover to the menu mode After pressing the MENU key, you can change from the standard mode to the menu mode. From the menu mode you can link to the different sub menus. Navigation within the menu Select the desired menu item using the UP/DOWN keys. The selected menu item is indicated by a flashing cursor. Press the ENTER key to open the associated sub menu. Use the UP/DOWN keys again to select the desired parameters. Move the cursor to the edit field by pressing the ENTER key. If you have reached the end of the main menu list, it will be indicated by the "Arrow UP" symbol. Changing the parameters When password protection is activated, indicated by the symbol "padlock closed", the first thing to enter is the correct password before the parameters can be changed using the UP/DOWN keys. Entering the correct password once allows all parameters to be changed as long as you do not leave the menu. Changing the parameter usually has an immediate effect on the measuring and alarm functions. The changed parameter is stored in a volatile memory by pressing the ENTER key after returning to the sub menu (flashing cursor in column 1). During menu operations, all measuring and alarm functions carry on working as usual in the background. Changing from the menu mode to the standard mode Select the menu item "EXIT" and press the ENTER key to leave the respective menu and to move to the next higher level. This is either the main menu or the standard mode. If you stay in the main menu or a sub menu longer than five minutes, the device will automatically switchover from the menu to the standard mode. 30 TGH1380en/
31 Operation and setting Diagram menu structure *** IT-SYSTEM *** R >5.0 MW MENU 1. EXIT 2. ISO SETUP 3. EDS SETUP 4. PASSWORD 5. LANGUAGE 6. SERVICE 7. INFO ISO SETUP EDS SETUP PASSWORD LANGUAGE SERVICE INFO 1. Exit 2. EDS: auto 3. MaxPuls: 25mA 1. Exit 2. Text: Deutsch 1. Exit BENDER GRUENBERG IR1575PG1 ---FIRMWARE--- V1.0 D Exit 2. Alarm1 040 kw 3. Alarm2 010 kw 4. K1 : N.O 5. K2 : N.O 6. Memory: off 1. Exit 2. Password: XXX 3. Status: off Insert Service Password: XXX TGH1380en/
32 Operation and setting 5.3 ISO SETUP menu: A-ISOMETER default settings The alarm functions Alarm1 and Alarm2 (prewarning and main alarm), the operating principle of the alarm relays K1 and K2 (N.O = N/O operation, N.C = N/C operation), and fault memory behaviour can be set in this menu Response values Alarm1 and Alarm2 The alarm values Alarm1 und Alarm2 are set using the UP/DOWN keys and saved pressing the ENTER key Operating principle of the alarm relays By default K1/K2 is set to N.O Test, that means N/O operation. The supplement "Test" points out that the setting of the alarm relays changes during a manual self test. If, for any reason, the alarm relays are to be prevented from switching during a manual self test, select N.C or N.O. K1: N.C Test = N/C operation contacts , including relay test (the alarm relay is energized during normal operation) K1: N.O Test = N/O operation contacts , including relay test (the alarm relay is deenergized during normal operation) K1: N.C = N/C operation contacts , without relay test (the alarm relay is energized during normal operation) K1: N.O = N/C operation contacts , without relay test (the alarm relay is deenergized during normal operation) K1: Flash = Blinking function contacts (The alarm relay and the LED flash (0.5 Hz) when an alarm message occurs) K2: N.C Test = N/C operation contacts , including relay test (the alarm relay is energized during normal operation) K2: N.O Test = N/O operation contacts , including relay test (the alarm relay is deenergized during normal operation) K2 : N.C = N/C operation contacts , without relay test K2 : N.O (the alarm relay is energized during normal operation) = N/O operation contacts , without relay test (the alarm relay is deenergized during normal operation) K2 : Flash = Flashing function contacts (the alarm relay and the LED flash (0.5 Hz) when an alarm message occurs 32 TGH1380en/
33 Operation and setting Diagram ISO SETUP *** IT-SYSTEM *** R >5.0 MW 1. EXIT 2. ISO SETUP 3. EDS SETUP 4. PASSWORD 5. LANGUAGE 6. SERVICE 7. INFO 1. Exit 2. Alarm1: 40 KW 3. Alarm2: 10 KW 4. K1 : N.O Test 5. K2 : N.O Test 6. Memory: off Alarm2 : 10 KW Alarm1 : 40 KW 2 KW... 1 MW K1: N.O Test K2: N.O Test K1: N.O Test K1: N.C Test K1: Flash K1: N.O K1: N.C Memory: off Memory: on Memory: off TGH1380en/
34 Operation and setting During the 24 h self test, the relays are not switched over. On the occurrence of a system fault, the Alarm LED 2 lights and relay K2 will be automatically activated as a system fault relay Memory setting (on/off) Memory: on = Fault memory os activated. Reset the device using the RESET button after clearing the fault. Memory: off = Fault memory deactivated (factory setting) 34 TGH1380en/
35 Operation and setting 5.4 EDS SETUP menu: default settings for fault location All appropriate settings for insulation fault location systems (EDS) can be set in this menu EDS on / auto / 1cycle / off The following start and stop conditions for the EDS system can be selected here: on The EDS system is activated and continuously operating, regardless of the insulation value and the alarm messages of the A-ISOMETER. This setting is particularly suitable for fault location using a portable insulation fault location system such as EDS3060, for example. auto The EDS system will automatically be activated as soon as the level of Alarm 1 and Alarm 2 goes above or below the normal level and remains active as long as the test current is above 5 ma. To measure the insulation fault value using the A-ISOMETER, insulation fault location is cyclically interrrupted for approximately 5 minutes (factory setting). 1cycle The EDS system will automatically be activated when the level of the response value falls below the response values Alarm 1 and Alarm 2. It remains active until every EDS has measured all channels once and when the test current is above 5 ma during the measurement. off The EDS system is constantly switched off maxpuls: 10 / 25 ma The maximum test current can be set here. 10 ma and 25 ma for EDS470 systems, preferably 25 ma. 10 ma are recommended to be set when sensitive electrical equipment such as control relays are supplied by the system. (factory setting 25mA) TGH1380en/
36 Operation and setting Diagram EDS-SETUP *** IT-SYSTEM *** R >5.0 MW 1. EXIT 2. ISO SETUP 3. EDS SETUP 4. PASSWORD 5. LANGUAGE 6. SERVICE 7. INFO 1. Exit 2. EDS: auto 3. MaxPuls: 25mA EDS : auto on auto 1cycle off MaxPuls: 25mA 10 ma 25 ma 36 TGH1380en/
37 Operation and setting 5.5 PASSWORD menu Password activation and setting A "password" query can be activated in this menu to protect the A-ISOMETER against unauthorized settings and modifications. Use the arrow keys to select the desired password (menu item 2. Password: xxx) and confirm with ENTER. For password activation, select menu item "3. Status: on" using the ENTER key. By default the password is deactivated 3. Status: off Diagram PASSWORD *** IT-SYSTEM *** R >5.0 MW 1. EXIT 2. ISO SETUP 3. EDS SETUP 4. PASSWORD 5. LANGUAGE 6. SERVICE 7. INFO 1. Exit 2. Password: XXX 3. Status: off Password: XXX Password: XXX Password: 000 Password:... Password: 999 Status: off Status: off Status: on TGH1380en/
38 Operation and setting 5.6 LANGUAGE menu Language setting This menu item offers a selection of two languages for the indication of fault messages. Choose between English and German language. The device menu is indicated in English language and cannot be changed by the language setting Diagram Language *** IT-SYSTEM *** R >5.0 MW 1. EXIT 2. ISO SETUP 3. EDS SETUP 4. PASSWORD 5. LANGUAGE 6. SERVICE 7. INFO 1. Exit 2. Text: Deutsch 2. Text: Deutsch 2. Text: Deutsch 2. Text: English 38 TGH1380en/
39 Operation and setting 5.7 SERVICE menu This menu item is intended for BENDER service staff and is secured by a password against erroneous settings. It is intended to provide fast fault clearance by qualified experts. 5.8 INFO menu This menu allows to query the type of the device addressed. In addition, the display indicates the software version applied Diagram INFO *** IT-SYSTEM *** R >5.0 MW 1. EXIT 2. ISO SETUP 3. EDS SETUP 4. PASSWORD 5. LANGUAGE 6. SERVICE 7. INFO 1. Exit BENDER GRUENBERG IR1575PG1 ----FIRMWARE---- V1.0 D205 TGH1380en/
40 Operation and setting 40 TGH1380en/
41 6. Operation with EDS device EDS The illustration below shows an IR1575PG1 in combination with EDS without bus capability and the associated measuring current transformers for insulation fault location. In many cases, the device can be operated using the default settings. When an EDS is used, it must operate in the Master mode. For details about the test current setting MaxPuls in the EDS SETUP menu, refer to "chapter maxpuls: 10 / 25 ma". For further use of the IR1575PG1 in combination with EDS systems, the following technical manuals are available: TGH1243 for EDS470, TGH1282 for configuration of EDS470 systems. 3 AC / 3 (N) AC / AC V L1 L2 L3 N PE Us see nameplate Measuring current transformers to the loads F 6A F 6A A0 A1 A2 L1 L2 L3 A1 A2 k1 k2 IR1575PG1 EDS KE l max. 25 cm PE TGH1380en/
42 Operation with EDS device EDS TGH1380en/
43 7. Technical data IR1575PG1 7.1 Data in tabular form Insulation coordination acc. to IEC Rated voltage...ac 500 V Rated impulse voltage/pollution degree... 4 kv / 3 Voltage ranges IR1575PG1...: Nominal voltage range U n... AC / 3 AC V Nominal frequency f n Hz Nominal voltage range U n... DC V IR1575PG1-435: Supply voltage U s at A0/A1 (see nameplate)... AC V Frequency range of U s Hz Supply voltage U s at A0/A2 (see nameplate)... AC V Frequency range of U s Hz Supply voltage U s at A0/A1 (see nameplate)... DC V IR1575PG1-434: Supply voltage U s at A0/A1 (see nameplate)... AC V Frequency range of U s Hz Supply voltage U s at A0/A1 (see nameplate)... DC 10, V IR1575PG1...: Power consumption... 5 VA Response values Response value R an1 (Alarm1)... 2 kω...1 MΩ Response value R an2 (Alarm2)... 2 kω...1 MΩ Specified response value (2 kω...10 kω) kω Specified response value (10 kω...1 MΩ)... 0 % % Response time t an at R F = 0.5 x R an and C e = 1 µf... 5 s Measuring time... see characteristic curves Hysteresis (2 kω...10 kω) kω Hysteresis (10 kω...1 MΩ) % Measuring circuit for insulation measurement Measuring voltage U m V TGH1380en/
44 Technical data IR1575PG1 Measuring current I m (at R F = 0 Ω) µa Internal DC resistance R i kω Internal impedance Zi, at 50 Hz kω Permissible extraneous DC voltage U fg... DC 680 V Permissible system leakage capacitance C e µf Measuring circuit for insulation fault location (EDS) Test current Ip DC...10 / 25 ma Test pulse / break... 2s / 4s Displays Display, illuminated...two-line display Number of characters... 2 x 16 Display range measuring value... 1 kω... 5 MΩ Absolute error (1 kω...10 kω)... ± 1 kω Relative percentage error (10 kω...5 MΩ)... ± 10 % Outputs/inputs TEST/ RESET button... internal/external Switching components Switching components... 2 changeover contacts Operating principle... N/O or N/C operation Factory setting (Alarm1/Alarm2)...N/O operation Admissible number of operations/h cycles Contact class... IIB (IEC ) Rated contact voltage... AC 250 V / DC 300 V Making capacity... UC 5 A Breaking capacity... 2 A, AC 230 V, cos ϕ = A, DC 220 V, L/R = 0.04 s Minimum contact current at DC 24 V... 2 ma (50 mw) General data EMC immunity... acc. to EN EMC emission... acc. to EN Shock resistance acc. to IEC (during operation) g / 11 ms Bumping acc. to IEC (during transport) g / 6 ms Vibration resistance acc. to IEC (during operation)... 1 g / Hz Vibration resistance acc. to IEC (during transport)... 2 g / Hz Ambient temperature (during operation) C C Storage temperature range C C 44 TGH1380en/
45 Technical data IR1575PG1 Climatic class acc. to IEC K5 Operating mode... continuous operation Position... depending on the display position Connection... plug-in terminals Wire cross section of connecting cable, rigid/flexible mm 2 / mm 2 Connection, flexible with ferrules, without/with plastic collar, mm 2 Conductor sizes (AWG) Degree of protection, internal components (DIN EN 60529)... IP30 Degree of protection, terminals (DIN EN 60529)... IP20 Enclosure... for panel mounting 96 x 96 mm Flammability class... UL94 V-2 Weight... ca. 480 g Option W Shock resistance acc. to IEC (during operation) g / 11 ms Bumping acc. to IEC (during transport) g / 6 ms Vibration resistance acc. to IEC mm / Hz... 4 g / Hz Ambient temperature (during operation C C Storage temperature range C C 7.2 Standards and approvals The A-ISOMETER was designed in consideration of the following standards: - DIN EN (VDE ): EN : IEC : IEC : IEC : EN DIN EN (VDE ): DIN EN (VDE ): ASTM F1669M-96(2002) - ASTM F1207M-96(2002) TGH1380en/
46 Technical data IR1575PG1 7.3 Characteristic curves A-ISOMETER reponse times in relation to system leakage capacitances: C e = µf, U n = V / 50 Hz IR t an [s] R 1 MW f 10 R ³ 0 kw f C e [µf] 46 TGH1380en/
47 Technical data IR1575PG1 Max. AC voltage between the IT system and earth in the frequency range < 50 Hz U n [V] f n [Hz] TGH1380en/
48 Technical data IR1575PG1 Response values for the insulation fault location system EDS470 R F (k ) AC 3AC DC Curve 1a: Response values in relation to the system voltage to be monitored for a maximum system leakage capacitance C e as illustrated in curve 2a. In order to start automatic insulation fault location, the resistance values to be selected for the alarm values 1 and 2 must be sufficiently low at a given nominal voltage. Otherwise, the EDS current is not sufficient to locate the insulation fault. Determine the suitable values using the characteristic curves above. U n (V) R F 100 (k ) U n (V) Curve 1b: Response values in relation to the system voltage to be monitored for a maximum system leakage capacitance C e as illustrated in curve 2b. AC 3AC DC 48 TGH1380en/
49 Technical data IR1575PG1 Maximum system leakage capacitances for the insulation fault location system EDS470 C e (μf) AC 3AC DC 10 0 U n (V) Curve 2a: Maximum allowable system leakage capacitance in relation to the system voltage to be monitored. Up to this limiting value of the system leakage capacitance, the EDS470 system has the sensitivity illustrated in curve 1a. C e (μf) AC 3AC DC U n (V) Curve 2b: Maximum allowable system leakage capacitance in relation to the system voltage to be monitored. Up to this limiting value of the system leakage capacitance, the EDS470 system has the sensitivity illustrated in curve 1b. TGH1380en/
50 Technical data IR1575PG1 120 R F max (%) ,1 0,3 0,5 0,7 1,1 1,5 2,2 2, x C e max Curve 3. A reduction of the response sensitivity at system leakage capacitances greater than the maximum permissible value of C e (curves 2a and 2b). Considering these curves, note that the sum of the precapacitances upstream of the individual measuring current transformer must be at least 50 % of the maximum total capacitance. Otherwise wrong alarm messages may occur. A value of μfv/400 V = 50 μf is taken as the maximum system leakage capacitance. Exceeding this limiting value may result in false trippings. 50 TGH1380en/
51 Technical data IR1575PG1 7.4 Dimension diagram enclosure IR1575PG mm approx. 120 mm suitable for panel mounting, the illustration below shows the necessary cutout: 92 mm + 0,8 / mm + 0,8 / - 0 TGH1380en/
52 Technical data IR1575PG1 7.5 Ordering details Standard version Type Nominal voltage. Supply voltage Art. No. U n U s IR1575PG /(N)/ AC V AC V B AC V AC V DC V IR1575PG1W-435 3/(N)/ AC V AC V B W AC V AC V DC V IR1575PG /(N)/ AC V AC V B AC V DC 10, V Devices with ending "W" provide improved shock and vibration resistance. A special varnish of the electronics provides higher resistance against mechanical stress and moisture. This makes the devices suitable for use in ships, on rolling stock and in seismic environment Label for modified versions There will only be a label in this field when the A-ISOMETER differs from the standard version. 52 TGH1380en/
53 INDEX A AC systems with galvanically connected DC circuits 8 Adaptive measuring pulse 10 Alarm LED 1 25 Alarm LED 2 25 Alarm message 12 Allowable response values for EDS C Characteristic curves 46 Commissioning flow chart 15 Current transformer 41 D Device type query 39 Dimension diagram, enclosure 51 Directions for installation 8 Display - in EDS mode 27 - in menu mode 26 - in standard mode 26 E EDS - Block diagram 41 - Operating mode, setting 35 - Test current setting 35 Explanations of symbols and warnings 7 External RESET button 23 External TEST button 23 F Factory settings 8 Fault memory, setting 34 Function 9 Function keys 28 I Inspection, transport and storage 7 Insulation fault location 18 IR1575PG1 characteristics 9 L Language of fault messages setting 38 M Menu - EDS SETUP 35 - INFO 39 - ISO SETUP 32 - LANGUAGE 38 - Navigation 30 - PASSWORD 37 - SERVICE 39 - structure 31 N Navigation within the menu 30 O Operating elements and displays 25 Operating principle of the alarm relays, setting 32 TGH1380en/
54 INDEX Operation with EDS Option "W" 9 Ordering details 52 P Parameters, changing 30 Password 37 Product description 9 R RESET button 10, 25 Response times 46 Response values, Alarm1/2, setting 32 S Self test 10, 25 Sequence control, reset 13 Software version query 39 Standards and approvals 45 System fault relay 34 T Technical data 43 TEST button 25 Test current, setting 35 W Wiring diagram TGH1380en/
55
56 Dipl.-Ing. W. Bender GmbH & Co.KG Londorfer Str Grünberg Germany Postfach Grünberg Germany Tel.: +49 (0) Fax: +49 (0) Internet:
ISOMETER IRDH275. Insulation monitoring device for unearthed AC, AC/DC and DC systems (IT systems) Vorläufiges Datenblatt
Insulation monitoring device for unearthed AC, AC/DC and DC systems (IT systems) Vorläufiges Datenblatt TDB106015en/05.2013 Insulation monitoring device for unearthed AC, AC/DC and DC systems (IT systems)
Manual ISOMETER IRDH575
EN Manual ISOMETER IRDH575 Insulation monitoring device for IT AC and DC systems with integrated test generator and controller for EDS46..., EDS47... and EDS49... systems IRDH575_D00089_00_M_XXEN/06.2014
ISOM ALD590. Operating manual
Operating manual ISOM ALD590 Insulation Fault Rs=011kW.H --- DLD: on---auto-- ADR: 02 k: 03 12 ma ISOM ALD590 Insulation monitoring device for IT AC and DC systems with integrated test generator and controller
LINETRAXX VMD460-NA. Network and system protection (NS protection) for monitoring the power feed-in of power generation systems
LIETRAXX -A etwork and system protection (S protection) for monitoring the power feed-in of power generation systems TDB301021en/06.2013 LIETRAXX -A etwork and system protection (S protection) for monitoring
Modular I/O System Analog and Digital Interface Modules
OPERATING INSTRUCTIONS Modular I/O System Analog and Digital Interface Modules Installation Operation Maintenance Document Information Document ID Title: Operating Instructions Modular I/O System Part
UM-X Field display for continous level sensors
Technical Documentation Field display for continous level sensors 10/2007 Edition: 1 Item No.: 207120 FAFNIR GmbH Bahrenfelder Str. 19 D-22765 Hamburg Telephone: +49 (0)40-39 82 07-0 Fax: +49 (0)40-3 90
Operating Manual EDS3090. Portable insulation fault location system for energised and deenergised systems Software version: D316 V1.
Operating Manual EDS3090 Portable insulation fault location system for energised and deenergised systems Software version: D316 V1.0 TGH1420en/12.2011 Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str.
Safety technique. Emergency stop module BO 5988 safemaster
Safety technique Emergency stop module BO 5988 safemaster 0221562 Function diagram Pushbutton on Mains or emergencystop () K1 According to EC Directive for machines 98/37/EG According to IEC/E 60204-1
Your Advantages For safety application up to PL e / Cat. 4 e.g. SIL 3 Manual or automatic start 0225592. * see variants. Applications.
Safety Technique SAFEMASTER Emergency Stop Module BG 5924, IP 5924 Your Advantages For safety application up to PL e / Cat. 4 e.g. SIL 3 Manual or automatic start 0225592 BG 5924 IP 5924 Product Description
Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages
Data sheet Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages The CM-ESS.2 is an electronic voltage monitoring relay that provides reliable monitoring of voltages as well as detection of
Type: EASY719 DC RC Article No.: 274119. Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC. Description
Type: EASY719 DC RC Article.: 274119 Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC Description 12 digital inputs (4 inputs available as analog inputs) 6 relay outputs LCD display
RM17TE 183...528 V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC
Characteristics multifunction control relay RM17-TE - range 183..528 V AC Complementary Reset time Maximum switching voltage Minimum switching current Maximum switching current [Us] rated supply voltage
Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages
Data sheet Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages The CM-ESS.2 is an electronic voltage monitoring relay that provides reliable monitoring of voltages as well as detection of
ABB 1 NEW. Three-phase monitoring relay for grid feeding CM-UFS.1. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories
2CDC 251 014 F0t09 Features Monitoring of three-phase mains for grid feeding Type-tested in accordance with DIN V VDE V 0126-1-1: February 2006 Neutral conductor connection configurable Can also be used
Temperature monitoring relays CM-TCS Monitoring relays for monitoring temperatures with a PT100 sensor (2- or 3-wire connection)
Data sheet Temperature monitoring relays CM-TCS Monitoring relays for monitoring temperatures with a PT100 sensor (2- or 3-wire connection) The temperature monitoring relays CM-TCS monitor overtemperature,
is then retained absolutely without interruption.
Page 1 of 11 DC UPS uninterruptible power supplies - DC UPS module 15 A Compact design, only 50 mm wide Absolutely interruption-free buffering of power failures through immediate electronic connection
VEO. V4PF480Y/277VSYTK02 Art.Nr.: 2104200. V4PF480Y/277VSYTK02P Art.Nr.: 2104210 TECHNICAL DATA
Monitoring of phase sequence and phase loss Monitoring of asymmetry Temperature monitoring (PTC) Supply voltage 208-480 V AC Supply circuit = measuring circuit 2 change-over contacts Width 45 mm Control
RM35UA13MW. range 15..600 V. Main. Product or component type. Relay monitored parameters
Characteristics multifunction voltage control relay RM35-U - range 15..600 V Complementary Reset time Maximum switching voltage [Us] rated supply voltage Supply voltage limits Power consumption in W Main
Digital input modules
8 172 TX-I/O Digital input modules TXM1.8D TXM1.16D Two fully compatible versions: TXM1.8D: 8 inputs, each with a three-color LED (green, yellow or red) TXM1.16D: As TXM1.8X, but 16 inputs, each with a
ABB 1. Three-phase monitoring relay CM-PFS. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories. Application.
1SR 430 824 F9300 Features Monitoring of three-phase mains for phase sequence and failure Powered by the measuring circuit 2 c/o (SPDT) contacts 1 LED for status indication Approvals R: yellow LED - relay
mecotron Safety relay ESTOP-2 For emergency stop monitoring
E0006 000824 Safety relay E-2 For emergency stop monitoring Description The safety module E-2 for emergency stop monitoring is used for safety breaking one or more circuits and is designed to be incorporated
Thermistor motor protection
Thermistor motor protection CM-E Range Thermistor motor protection Thermistor motor protection relays Benefits and advantages Selection table Operating principle and fields of application for thermistor
Operating Manual for the Electronic Built-in Interval Timer. Micro II (Countdown Timer)
Operating Manual for the Electronic Built-in Interval Timer Micro II (Countdown Timer) Note: This document has been designed for our OEM customers. They can use it as supporting material when creating
MONITORING RELAYS. w VOLTAGE MONITORING RELAY UR5U1011. w SCHRACK-INFO. w TECHNICAL DATA
w VOLTAGE MONITORING RELAY UR5U1011 w SCHRACK-INFO AC/DC voltage monitoring in 1-phase mains Undervoltage monitoring 1 change over contact Width 17.5 mm Installation design w TECHNICAL DATA 502 1. Functions
User s Manual Before using the inverter, you need to read and save the safety instructions.
User s Manual Before using the inverter, you need to read and save the safety instructions. STI SERIES (STI200, STI300, STI500, STI700, STI1000) Power Frequency Pure Sine Wave Inverter The information
Electronic timer CT-VBS.17+18 OFF-delayed without auxiliary voltage, for DC contactors Data sheet
Characteristics Single-function OFF-delay timer for DC contactors, without auxiliary voltage Width.5 mm CDC 5 6 F3 Approvals A culus E CCC CT-VBS a Circuit diagram b Marker label Marks a CE b C-Tick Order
Documentation for. KL2602 and KL2622. Two-channel Relay Output Terminals for 230 V AC / 30 V DC. Version: 1.4 Date: 2013-03-20
Documentation for KL2602 and KL2622 Two-channel Relay Output Terminals for 230 V AC / 30 V DC Version: 1.4 Date: 2013-03-20 Table of contents Table of contents 1 Foreword 1 1.1 Notes on the documentation
Power Supply Unit, Primary Switched, Narrow Design MINI-PS-12-24DC/24DC/1
Power Supply Unit, Primary Switched, Narrow Design MINI POWER provides: Extra narrow design with widths of 22.5 mm, 45 mm, and 67.5 mm (0.886, 1.772, and 2.657 in.) Global use due to a wide-range input
Voltage Regulator SPAU 341 C. Product Guide
Issued: July 1998 Status: Updated Version: D/25.04.2006 Data subject to change without notice Features Comprehensive voltage regulation for power transformers with on-load tapchangers in distribution substations
Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous
Safety relay for monitoring E-STOP pushbuttons. Approvals Unit features Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous 1 auxiliary contact (N/C), instantaneous Safe separation of
Redundancy Module QUINT-DIODE/40
Redundancy Module QUT DIODE provides: 00% decoupling of power supplies connected in parallel Can be installed in potentially explosive areas Load currents up to 60 A supported Easy assembly by snapping
Preset Counter signo 721
Most simple handling Impressive, clearly readable display in 48x48 mm Input frequency up to 60 khz Easy installation due to pluggable terminals TECHNICAL DATA GENERAL Display Height of digits Supply voltage
Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact
Data sheet Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact The CT-AHD.12 is an electronic time relay with OFF-delay. It is from the CT-D range. With their MDRC profile and a width of only
Process modules Digital input PMI for 24 V DC inputs for 120 V AC inputs
E031026 000823 Process modules Digital input PMI for inputs for 120 V AC inputs PMI Input E4, E5, GND L- PMI 120 V AC Input E4, E5, Common C E6, E7, GND L- E6, E7, Common C LEDs for the inputs operation
Three-phase monitoring relay CM-PFE
Data sheet Three-phase monitoring relay CM-PFE The CM-PFE is a three-phase monitoring relay that monitors the phase parameter phase sequence and phase failure in three-phase mains. 2CDC 251 005 S0012 Characteristics
GAE953 Electrical Alarm Unit 19" with Indicator
Master Instruction 08.95 MI EIO2211 A-(en) GAE953 Electrical Alarm Unit 19" with Indicator The electrical alarm unit GAE953 gives a signal when one or two set alarm values have been exceeded. Input signals
Electronic overload relay EF19 and EF45
Data sheet Electronic overload relay EF19 and EF45 Electronic overload relays offer reliable protection in case of overload and phase-failure. They are the alternative to thermal overload relays. Motor
Quick Connect. quick - simple - efficient. www.g-mw.de
Quick Connect quick - simple - efficient www.g-mw.de Phone: +49 9103 7129-0 Fax: +49 9103 7129-207 Innovative connection technology to plug three single-phase current transformers to multifunctional power
38 SERIES. Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A. EMR Electromechanical Relays. Common features. SSR Solid State Relays. 6.
38 Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A 38 Common features Instant ejection of relay by plastic retaining clip Integral coil indication and protection circuit 6.2 mm wide EMR - DC, AC or AC/DC
Voltage monitoring relays CM-ESS.M For single-phase AC/DC voltages
Data sheet Voltage monitoring relays CM-ESS.M For single-phase AC/DC voltages The CM-ESS.M is an electronic voltage monitoring relay that provides reliable monitoring of voltages as well as detection of
ABB Drives. User s Manual. Pulse Encoder Interface Module RTAC-01
ABB Drives User s Manual Pulse Encoder Interface Module RTAC-0 Pulse Encoder Interface Module RTAC-0 User s Manual 3AFE 64486853 REV A EN EFFECTIVE:.5.00 00 ABB Oy. All Rights Reserved. Safety instructions
Electronic overload relay EF65, EF96 and EF146
Data sheet Electronic overload relay EF65, EF96 and EF146 Electronic overload relays offer reliable protection in case of overload and phase-failure. They are the alternative to thermal overload relays.
MILLENIUM INSTALLATION MANUAL NTR 735 A. Simple Automation Control Module (MAS)
MILLENIUM Table of contents 1. INTRODUCTION 1 2. HARDWARE DESCRIPTION 2 3. INSTALLATION 5 4. CONNECTION 6 5. USER SAFETY AND PROTECTION OF EQUIPMENT 8 1. Introduction The MILLENIUM series has been designed
Thermistor motor protection relays CM-MSS.22 and CM-MSS.23
Data sheet Thermistor motor protection relays CM-MSS.22 and CM-MSS.23 The thermistor motor protection relays CM-MSS.22 and CM-MSS.23 monitor the winding temperature of motors and protect them from overheating,
ALARM ANNUNCIATOR ME - 3010 INSTRUCTION MANUAL
ALARM ANNUNCIATOR ME - 3010 INSTRUCTION MANUAL INTRODUCTION... 2.. TECHNICAL DATA... 3 ACCESSORIES... 5. INSTALLATION... 7 OPERATION... 12. TECHNICAL INFORMATION... 13 MAINTENANCE... 14. CONFIGURATIONS...
CAT AVR V2.3. Instruction Manual. Voltage regulator for generators. March 2008
CAT AVR V2.3 Voltage regulator for generators March 2008 Instruction Manual Warnings WARNING The system should not be installed, operated, serviced or modified except by qualified personnel who understand
Digital Pressure Measuring Instrument MDR480
Description The digital panel instrument MDR480 is designed to measure, display, and monitor pressures in industrial applications. The instrument is panel mounted with a front frame dimension of 96 mm
Power Supply and Indicator Unit Type 5024-1. Fig. 1 Type 5024-1. Mounting and Operating Instructions EB 9539 EN
Power Supply and Indicator Unit Type 5024-1 Fig. 1 Type 5024-1 Mounting and Operating Instructions EB 9539 EN Edition October 2003 Application 1 Application The Type 5024-1 Power Supply and Indicator Unit
Advantium 2 Plus Alarm
ADI 9510-B Advantium 2 Plus Alarm INSTALLATION AND OPERATING INSTRUCTIONS Carefully Read These Instructions Before Operating Carefully Read These Controls Corporation of America 1501 Harpers Road Virginia
Insulation resistance
The insulation resistance is particularly important for the prevention of damage and injury, and for the reliability of electrical systems and equipment. On the one hand it is basis for the protection
48 SERIES Relay interface modules 10 A
48 Relay interface modules 10 A 1 CO relay interface modules, mm wide Ideal interface for PLC and electronic systems Type 48.P3 1 CO 10 A s Type 48.31 1 CO 10 A s AC coils or DC sensitive coils Supply
Control Devices Catalogue. Control Devices. Preferred and Standard Products
Control Devices Catalogue Control Devices Preferred and Standard Products KOP.J Timer Electronic 22.5 mm Characteristics Mounting KOP.J 22.5 mm mono or multifunction high immunity to interference surface
Automation System TROVIS 6400 TROVIS 6493 Compact Controller
Automation System TROVIS 6400 TROVIS 6493 Compact Controller For panel mounting (front frame 48 x 96 mm/1.89 x 3.78 inch) Application Digital controller to automate industrial and process plants for general
Duct Humidity Transmitter
SDC-H Duct Humidity Transmitter Features Replaceable sensor element Humidity measurement for air ducts Minimum and maximum value memory 0 0V, 0 0mA or 0V, 4 0mA measuring signals selectable with jumpers
HERZ-Thermal Actuators
HERZ-Thermal Actuators Data Sheet 7708-7990, Issue 1011 Dimensions in mm 1 7710 00 1 7710 01 1 7711 18 1 7710 80 1 7710 81 1 7711 80 1 7711 81 1 7990 00 1 7980 00 1 7708 11 1 7708 10 1 7708 23 1 7709 01
Product and functional description
Product and functional description The KNX / DALI gateway N 141/02 is a 4 MU wide, DINrail mounted KNX device with one DALI interface to which up to 64 DALI actuators (e.g. DALI ballasts) can be connected
SKR - industry relay
SKR - industry relay the universal relay SKR the time module STM the socket The strengths of the SKR industry relay lie in the mature and thoughtout construction. Over-average contact safety and life time,
MCR-VDC-UI-B-DC. Voltage Transducer for DC Voltages. INTERFACE Data Sheet 100260_en_01. 1 Description
Voltage Transducer for DC Voltages TERFACE Data Sheet 000_en_0 PHOENIX CONTACT - /00 Description The MCR voltage transducer measures DC voltages in several signal ranges from 0... ±0 V DC to 0... ±0 V
MINI MCR-SL-R-UI(-SP)
Resistance/potiposition transducer INTERFACE Data Sheet 0807_en_05 Description PHOENIX CONTACT - 0/008 Features The slim MINI MCR-SL-R-UI... potiposition transducer has a width of only 6. mm and converts
RISH EM 3490 DS Dual Source Energy Meter RISH EM 3490 DS. Application : Product Features:
Application : RISH Master 3490 DS measures important electrical parameters of Utility (in normal mode) & Generators (in Power back up) in three phase and single phase Network & replaces the multiple analog
User's Guide. Integrating Sound Level Datalogger. Model 407780. Introduction
User's Guide 99 Washington Street Melrose, MA 02176 Phone 781-665-1400 Toll Free 1-800-517-8431 Visit us at www.testequipmentdepot.com Back to the Extech 407780 Product Page Integrating Sound Level Datalogger
Three-phase monitoring relays CM-PSS CM-PSS.31 and CM-PSS.41
Data sheet Three-phase monitoring relays CM-PSS CM-PSS.31 and CM-PSS.41 The three-phase monitoring relays CM-PSS.x1 monitor the phase parameters phase sequence, phase failure as well as over- and undervoltage.
TC-9102 Series Surface Mount Temperature Controllers
TC-9102 Series Surface Mount Temperature Controllers General Description & Applications The TC-9102 Series Temperature Controller offers a versatile solution for a wide variety of applications that may
RM4TG20 three-phase network control relay RM4-T - range 200..500 V
Characteristics three-phase network control relay RM4-T - range 200..500 V Complementary [Us] rated supply voltage Output contacts Setting accuracy of time delay Delay at power up Measuring cycle Marking
Pluggable interface relays CR-P Pcb relays
2CDC 293 034 F0004 1 2 4 3 Features 9 different supply s: DC versions: 12 V, 24 V, 48 V, 110 V AC versions: 24 V, 48 V, 110 V, 120 V, 230 V Output contacts: 1 c/o (16 A) or 2 c/o (8 A) Cadmium-free contact
FLOW CALCULATOR INSTRUCTION MANUAL MESURES BAMOPHOX 759 26-06-2007 759 M1 02 E MES FLOW CALCULATOR 759-02/1
BAMOPHOX 759 E - M FLOW CALCULATOR INSTRUCTION MANUAL MESURES 22, Rue de la Voie des Bans - Z.I. de la Gare - 95100 ARGENTEUIL Tél : (33) 01 30 25 83 20 - Web : www.bamo.fr Fax : (33) 01 34 10 16 05 -
CQM1-SF200/CS1W-SF200
Safety Relay Unit ( I/O Unit Type) CQM1-SF200/CS1W-SF200 CSM_CQM1-SF200_CS1W-SF200_DS_E_2_1 A Safety Relay Unit That Functions as a I/O Unit. Less Installation Space and Wiring Required. Safety Relay Unit
Safety Relays ESM/ESM-F
Safety Relays ESM/ESM-F More than safety. Safety More than safety. Emil Euchner, the company s founder and inventor of the multiple limit switch, circa 1928. Around the world the Swabian specialists in
Multifunctional three-phase monitoring relays CM-MPS CM-MPS.43
Data sheet Multifunctional three-phase monitoring relays CM-MPS CM-MPS.43 The three-phase monitoring relay CM-MPS.43 monitors the phase parameters phase sequence, phase failure, over- and undervoltage
Type: DILM115(RAC240) Article No.: 239548 Sales text Contactor,55kW/400V,AC operated. Ordering information
Type: DILM115(RAC240) Article No.: 239548 Sales text Contactor,55kW/400V,AC operated Ordering information Connection technique Description Description Rated operational current Screw terminals 3 pole AC
Installation manual. Generator Paralleling Controller GPC multi-line 2 4189340225C
Installation manual Generator Paralleling Controller GPC multi-line 2 Software ver. 1.3X Compact system in one unit - dynamic synchronisation - load sharing - generator protection DEIF A/S 3-phase AC RMS
Inductive Sensors Single or Dual Loop Detectors Type LD with teach-in
Inductive Sensors Single or Dual Loop Detectors Type LD with teach-in Single or Dual loop detector Automatically adjustment of detection level Manual sensitivity for compensations of variations Easy installation
E-STOP relays, safety gate monitors
Unit features Safety features Gertebild ][Bildunterschrift_NOT_Sch.tuer_Licht Safety relay for monitoring E-STOP pushbuttons, safety gates and light beam devices Approvals Gertemerkmale Positive-guided
Example of use: Fuse for a solenoid valve. If the fuse is defective, no information is sent to the electronic component.
Overview Switch and button modules The dimensions of the switch and button modules are adapted to the electronic components in the integral housing. The modules are equipped with the universal clip-on
Ground Resistance Clamp On Tester
USER MANUAL Ground Resistance Clamp On Tester MODEL 382357 Introduction Congratulations on your purchase of Extech s 382357 Ground Resistance Tester. This Clamp on device allows the user to measure ground
Auto-ranging Digital Multimeter 52-0052-2 INSTRUCTION MANUAL
Auto-ranging Digital Multimeter 52-0052-2 INSTRUCTION MANUAL WARNING: READ AND UNDERSTAND THIS MANUAL BEFORE USING YOUR MULTIMETER. FAILURE TO UNDERSTAND AND COMPLY WITH WARNINGS AND OPERATING INSTRUCTIONS
For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.
Current Transducer HO-P series I PN = 6, 10, 25 A Ref: HO 6-P, HO 10-P, HO 25-P For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary
Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw
4 937 DESIO Current valve for AC 24 V pulse/pause control of electrical loads up to 30 kw SEA45.1 Use The current valve is used for the control of electric heating elements in heating, ventilation and
Technote. Frese OPTIMA Compact actuators DN10-DN32. Application. Features thermic actuators. Features motoric actuators. Approval. www.frese.
Page 1 of 6 Application Proportional 0-10V or 3-position modulating or On/ Off control of Frese OPTIMA Compact valves in heating, ventilating and air conditioning systems. The actuator can be mounted on
38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A
38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A 38 SERIES Common features Instant ejection of relay by plastic retaining clip Integral coil indication and protection circuit EMR Electromechanical
Instructions for Safe Use
Instructions for Safe Use (Certification N:o VTT 08 ATEX 029) Thank you for choosing Slam Trans portable transformer for your job site. Purpose of this manual is to provide you all the necessary safety
H/L = Power supply. FN = Nominal Frequency. RN = Rated value of output burden. UN = Nominal input voltage. IN = Nominal input current.
Application : The transducer RISH CON - CA/CV (Fig.1) converts a sinusoidal AC Current or AC Voltage into a load independent DC Current or a load independent DC Voltage proportional to the measured value.
Technical Data. Dimensions
0102 Model Number Features Comfort series 5 mm flush Usable up to SIL 2 acc. to IEC 61508 Accessories BF 18 Mounting flange, 18 mm EXG-18 Quick mounting bracket with dead stop Technical Data specifications
R4D0-FB-IA* FieldBarrier. Features. Assembly. Function. Connection IN + - S OUT ... ... Spur 2. Spur 1. Zone 1. Zone 0
FieldBarrier Features Assembly 8... 12 outputs Ex ia IIC, FISCO and Entity Advanced fault isolation and diagnostics at the spur FieldBarrier in Zone 1/Div. 2 Instruments in Zone 0...1/Div. 1 For FOUNDATION
Safety Manual BT50(T) Safety relay / Expansion relay
Safety Manual BT50(T) Safety relay / Expansion relay ABB Jokab Safety Varlabergsvägen 11, SE-434 39, Sweden www.abb.com/jokabsafety Read and understand this document Please read and understand this document
DUAL%CHANNEL BROADBAND%LINEAR%AMPLIFIER Model&A800D
ELECTRONICS AB DUAL%CHANNEL BROADBAND%LINEAR%AMPLIFIER Model&A800D & HIGH&VOLTAGE& FIXED&GAIN& BROADBAND & 800Vpp&60mA& 100x& DC&to&ca&200&kHz & LOW&OUTPUT&IMPEDANCE& HIGH&SLEW&RATE &
Technical data. General specifications. Indicators/operating means. 30 Hz Multiplex operation 30 Hz / n, n = number of sensors, n 5
Model Number Single head system Features Parameterization interface for the application-specific adjustment of the sensor setting via the service program ULTRA 000 programmable switch outputs Hysteresis
TIG INVERTER INSTRUCTION MANUAL
TIG INVERTER INSTRUCTION MANUAL Contents Warning General Description Block Diagram Main Parameters Circuit Diagram Installation and Operation Caution Maintenance Spare Parts List Troubleshooting 3 4 4
MasterINTERFACE 39 Series - Relay interface modules
MasterINTERFACE 39 Series - Relay interface modules Common features Space saving 6.2 mm wide Connections for 16-way jumper link Integral coil indication and protection circuit Secure retention and easy
Type: DILM50(230V50HZ,240V60HZ) Article No.: 277830
Type: DILM50(230V50HZ,240V60HZ) Article No.: 277830 Ordering information Rated operational current AC 3 400 V I e A 50 Max. rating for three phase motors, 50 60 Hz AC 3 230 V Max. rating for three phase
instabus KNX / EIB System System E F G H
Product name: Uninterruptible power supply (USV) 640 ma Design: REG (rail-mounted device) Article-no.: 1079 00 ETS search path: Gira Giersiepen / system components / power supply / power supply 640mA DRA
HSP GmbH Zum Handwerkerhof 2 90530 Wendelstein Tel. 09129 / 2852-0 Fax: 09129 / 2852-11 Web: www.hsshsp.de EMAIL: [email protected] NTG-3000.
NTG-3000 Transducer Data Sheet Document Version 2.8 Page 1 of 10 Versions / Revisions: Document Creation Author Description version date 2.0 2012-07-25 P. Compensis First official version 2.1 2012-08-24
AC3200 INTELLIGENT BROADBAND AMPLIFIER
Kari Mäki 9.4.2013 1(7) AC3200 INTELLIGENT BROADBAND AMPLIFIER AC3200 is the latest leading-edge addition to AC family with extended frequency and gain ranges and integrated electrical controls in both
Drayton Digistat +2RF/+3RF
/+3RF Programmable Room Thermostat Wireless Model: RF700/22090 Model: RF701/22092 Power Supply: Battery - Thermostat Mains - Digistat SCR Invensys Controls Europe Customer Service Tel: 0845 130 5522 Customer
RISH CON - Hz. Salient Features : Application : Product Features: FREQUENCY TRANSDUCER
Application : The RISH CON - Hz transducer is used for frequency measurement. The output signal is proportional to measured frequency and is either load independent DC Current or load independent DC Voltage.
Type: DILM32 10(24V50HZ) Article No.: 277247
Type: DILM32 10(24V50HZ) Article No.: 277247 Ordering information Rated operational current AC 3 400 V I e A 32 Max. rating for three phase motors, 50 60 Hz AC 3 230 V Max. rating for three phase motors,
Short information Parameters are programmed via front-side membrane keypad
Digital remote display for Flow Meter DM /DE Universal meter UZ Indication of the quantity consumed in m³ Features LED-Display 14.2mm red Indicating range -99999... 999999 0... 3 Decimal points programmable
Handheld portable appliance testers
PAT100 SERIES Handheld portable appliance testers PAT100 SERIES Handheld portable appliance testers Simple Tick/Cross, pass/fail indication plus measurement Battery powered with rechargeable options Includes
Inductive sensor NI10-M18-Y1X-H1141
ATEX category II 1 G, Ex zone 0 ATEX category II 1 D, Ex zone 20 SIL2 as per IEC 61508 Threaded barrel, M18 x 1 Chrome-plated brass DC 2-wire, nom. 8.2 VDC Output acc. to DIN EN 60947-5-6 (NA- MUR) M12
Technical data. General specifications. Signal voltage 15... 30 V DC Signal duration. 1 s Input 2. Signal voltage. 1 s Analog output.
Model Number Features Very small housing High climatic resistance 4 Bit multiturn Analog output Surge and reverse polarity protection Description This absolute rotary encoder with internal magnetic sampling