Examples of Automation. X-SEL Serial Communication
|
|
|
- Naomi Reed
- 9 years ago
- Views:
Transcription
1 Examples of Automation X-SEL Serial Communication
2 Overview of Networks Examples of Automation Table of Contents DeviceNet Confectionery Sizer/Sorter Explanation of Application...5 (1) System configuration...5 (2) Explanation of operation Communication Settings...6 (1) Connect the devices...7 (2) Set the X-SEL controller...8 (3) Set the master unit (4) Perform a line test (5) Assign I/Os (6) Start the system Sample Program...15 (1) X-SEL controller sample program (2) PLC sample program CC-Link Board Solderer for Cell Production Line Explanation of Application...17 (1) System configuration (2) Explanation of operation Communication Settings...18 (1) Connect the devices... Error! Bookmark not defined. (2) Set the X-SEL controller... Error! Bookmark not defined. (3) Set the master unit... Error! Bookmark not defined. (4) Perform a line test... Error! Bookmark not defined. (5) Start the system... Error! Bookmark not defined. 3. Sample Program... Error! Bookmark not defined. (1) PLC sample program... Error! Bookmark not defined. Ethernet not defined. Work Sorter/Pick-up.. Error! Bookmark 1. Explanation of Application... Error! Bookmark not defined. (1) System configuration... Error! Bookmark not defined. (2) Explanation of operation... Error! Bookmark not defined.
3 Table of Contents 2. Communication Settings... Error! Bookmark not defined. (1) Connect the devices... Error! Bookmark not defined. (2) Set the X-SEL controller... Error! Bookmark not defined. (3) Setting the camera... Error! Bookmark not defined. (4) Perform a line test... Error! Bookmark not defined. (5) Start the system... Error! Bookmark not defined. 3. Sample Program... Error! Bookmark not defined. (1) X-SEL controller program... Error! Bookmark not defined. Protocol Communication (RS232C) Bookmark not defined. Wood Length Specifier/Cutter...Error! 1. Explanation of Application... Error! Bookmark not defined. (1) System configuration... Error! Bookmark not defined. (2) Explanation of operation... Error! Bookmark not defined. 2. Communication Settings... Error! Bookmark not defined. (1) Set the X-SEL controller... Error! Bookmark not defined. (2) Setting the touch panel... Error! Bookmark not defined. (3) Connect the devices... Error! Bookmark not defined. (4) Start the system... Error! Bookmark not defined. Free Protocol Communication (RS232C) not defined. PC Board Checker... Error! Bookmark 1. Explanation of Application... Error! Bookmark not defined. (1) System configuration... Error! Bookmark not defined. (2) Explanation of operation... Error! Bookmark not defined. 2. Communication Settings... Error! Bookmark not defined. (1) Connect the devices... Error! Bookmark not defined. (2) Set the X-SEL controller... Error! Bookmark not defined. (3) Setting the PC... Error! Bookmark not defined. (4) Perform a line test... Error! Bookmark not defined. (5) Start the system... Error! Bookmark not defined. 3. Sample Program... Error! Bookmark not defined. (1) Test program using HyperTerminal... Error! Bookmark not defined.
4
5 Overview of Networks The X-SEL controller incorporates a sequence function that allows it to operate on its own. However, in applications where the robot controlled by the X-SEL controller is assembled into a system, the X-SEL controller must be able to exchange data with the PLC (sequencer), touch panel, CCD camera or other peripherals used in the system. This document compiles representative examples of serial communication using the X-SEL controller that would provide users with tips on how to build their X-SEL controller systems. Please utilize the information provided herein when examining specifications and performing startup checks for your system. The X-SEL controller supports the serial communication modes indicated by [1] through [5] below. X-SEL serial communication [1] DeviceNet [1] DeviceNet Refer to p. 5. DeviceNet is a field network developed by Rockwell with the aim of achieving interconnection among devices manufactured by different companies. In DeviceNet communication, you can send/receive I/O signals corresponding to a maximum of 256 input points and 256 output points using only a PLC or other applicable device and one dedicated cable. Item Numbers of I/O points Communication protocol Baud rate Communication cable length Communication power supply Current consumption for communication Number of occupied nodes Specification Maximum of 256 input points and 256 output points An interface module certified under DeviceNet 2.0 is used. Group 2 only server Network-powered insulated node 500 K/250 K/125 Kbps Baud rate Maximum network length Maximum branch line length Total branch line length 500 Kbps 100 m 39 m 250 Kbps 250 m 6 m 78 m 125 Kbps 500 m 156 m Note) When a large-size DeviceNet cable is used. 24 VDC (supplied from DeviceNet) 60 ma 1 node Connector type (controller end) MSTBA2.5/5-G-5.08-AUM by Phoenix Contact (*1) * The cable-end connector uses SMSTB2.5/5-ST-5.08AU by Phoenix Contact (supplied with the controller). [2] CC-Link Refer to p. 17. CC-Link (Control & Communication Link) is a field network capable of high-speed information transfer among devices. Just like DeviceNet, CC-Link permits sending/receiving of I/O signals corresponding to a maximum of 256 input points and 256 output points using only one dedicated cable. Item Numbers of I/O points Communication protocol Baud rate Station type [2] CC-Link [3] Ethernet [4] Protocol communication (RS232C) [5] Free protocol communication (RS232C) Specification Maximum of 256 input points and 256 output points CC-Link Ver.1.10 (certified) 10 M/5 M/2.5 M/625 K/156 Kbps Remote device station Number of occupied stations 1 to 3 stations (selectable) Communication Baud rate (bps) 10 M 5 M 2.5 M 625 K 156 K cable length Cable length (m) Connector type (controller end) MSTBA2.5/5-G-5.08-AUM by Phoenix Contact (*1) * The cable-end connector uses SMSTB2.5/5-ST-5.08AU by Phoenix Contact (supplied with the controller).
6 Overview of Networks [3] Ethernet Refer to p. 27. Ethernet is a communication network most commonly used for information exchange among PCs. LAN (Local Area Network) is a representative mode of Ethernet communication. By connecting the X-SEL controller to Ethernet, you can communicate with PCs, cameras and other devices at high speed by means of exchanging messages. Item Network specification Communication protocol Baud rate Protocol Connector Cable Specification 10BASE-T/100BASE-T (auto negotiation) IEEE /100 Mbps TCP/IP message communication (IAI Protocol B/TCP, SEL program transmission) Open Modbus/TCP (remote I/Os) RJ-45 Category 5 UTP twisted cable [4] Protocol communication Refer to p. 37. This method is used to communicate with external devices via a teaching pendant or PC software connected to a teaching port. To use a teaching port, a program for communicating with external devices must be created in accordance with the communication format called protocol. Item Communication interface Baud rate Data length Stop bit length Parity RS232C 9.6/19.2/38.4 Kbps (selectable) 7 or 8 bits (selectable) 1 or 2 bits (selectable) None, Odd or Even (selectable) Specification [5] Free protocol communication Refer to p. 45. This method allows character string data to be sent and received without using a protocol. To implement free protocol communication using the X-SEL controller, install an optional SIO board in the controller and create/run a SEL program from the controller. Item Communication interface Baud rate Data length Stop bit length Parity Specification RS232C/RS422/RS485 (selectable) 9.6/19.2/38.4/57.6/76.8/115.2 Kbps (selectable) 7 or 8 bits (selectable) 1 or 2 bits (selectable) None, Odd or Even (selectable)
7 DeviceNet Confectionery Sizer/Sorter System Overview A system that uses a visual sensor to determine the size of each confectionery arriving on a conveyor, and changes the line to forward the confectionery to based on the determined size. A single-axis robot is used to change the direction of the main conveyor according to the size. Benefits Changing the connections among component devices such as the PLC, sensor and X-SEL controller from flat cables to DeviceNet reduced the wiring and also enabled early identification of open circuit and other problems. Explanation of Application (1) System configuration Conveyor A Conveyor B Conveyor C Visual sensor Terminal resistor Terminal resistor X-SEL controller PLC master unit
8 DeviceNet (2) Explanation of operation Description [1] The visual sensor measures the size of each confectionery arriving on the conveyor. [2] The PLC selects the conveyor to forward the confectionery to from among conveyors A, B and C, based on the data measured by the visual sensor. [3] The PLC instructs the X-SEL controller the position to move the sorting conveyor to. [4] The sensor on the applicable conveyor confirms passing of the confectionery, after which the system proceeds to the next cycle. Example The visual sensor measures the confectionery and determines that it is large. Conveyor C is selected. The actuator slider moves to position 3 in order to move the sorting conveyor to connect to conveyor C. A sensor signal from conveyor C confirms that the confectionery was sorted successfully. Conditions The X-SEL controller stores the program and three sets of position data (position nos. 1 to 3). Based on the size determined by the visual sensor, the program in the PLC issues an I/O signal to turn on the port assigned to the applicable position number stored in the controller. Once the confectionery has passed the sensor installed along the target conveyor, the actuator moves to the next position. The master unit adopts a free I/O assignment logic using a configurator. How to set the controller and PLC comprising this system is explained below. Communication Settings The flow of setting DeviceNet communication between the X-SEL controller and PLC is specified below. Connect the devices Connect the X-SEL controller and each DeviceNet unit using a dedicated cable. Refer to p. 7. Set the X-SEL controller Set switches and parameters on the X-SEL controller. Refer to p. 8. Set the master unit Set master unit switches on the PLC. Refer to p. 10. Perform a line test Input the power to the connected devices and perform a line test. Refer to p. 10. Assign I/Os Once the line is connected, use the configurator to assign I/Os to the connected devices. Refer to p. 11. Start the system After all I/Os have been assigned, start the PLC program to start the system. Refer to p. 15.
9 Each device connected to DeviceNet, other than the master unit, is called slave unit. Up to 63 slave units can be connected simultaneously. (Including the master unit, a maximum of 64 devices can be connected to the network.) To implement communication between each slave unit and the master unit, the following settings are required: (1) Set the node addresses and baud rate Refer to p. 8 to 10. (2) Create a scan list (to cause the master unit to recognize each slave unit) Refer to the operation manual for the applicable master unit. (3) Assign I/Os (I/O signals) for each slave unit (to the master unit) Refer to p. 11 to 14. Slave units can be assigned by fixed assignment or free assignment. Fixed assignment --- Free assignment --- The assigned areas are fixed, and node addresses are assigned sequentially from 0. This method is suitable for small networks connecting a limited number of devices. Configurator software is used to assign slaves in a desired manner. All connected devices can be monitored, which is ideal for networks connecting many devices. With both fixed assignment and free assignment, one channel consists of two bytes, and a slave having 16 I/O points occupies one channel. A slave having more than 16 I/O points occupies multiple channels. The X-SEL controller lets you freely set one to 16 occupied channels, with each channel consisting of 16 I/O points (i.e., there will be 16 input points and 16 output points if there is only one channel, or 256 input points and 256 output points when there are 16 channels). In this example, free assignment using a configurator is explained based on the settings specified below. Node address Unit type Connected unit Numbers of I/O points Number of occupied channels 0 Master unit Omron CJ series Slave unit X-SEL controller 32 input points 16 output points 2 input channels 1 output channel 2 Slave unit Sensor terminal 16 input points 1 channel 3 Intelligent slave unit Visual sensor controller 8 bytes 4 channels The setting procedure based on the above specifications is explained step by step. (1) Connect the devices Connect the dedicated DeviceNet cable to the X-SEL controller as shown below. (Black) (Blue) (Bare) (White) (Red)
10 DeviceNet (2) Set the X-SEL controller On the X-SEL controller, set [1] switches and [2] parameters. [1] Setting switches The switches that must be set are those relating to the following items: Cable connector a. Node address setting b. Baud rate setting a. Node address setting The node address is also called MAC ID. Use the six DIP switches of NA1, 2, 4, 8, 16 and 32 to set a desired address between 0 and 63 as a binary code. Since only one address is required in this system, set only NA1 to ON. DIP switches Node address setting Baud rate setting Monitor LEDs (Enlarged view of DeviceNet connection board) b. Baud rate setting Use the two DIP switches of DR1 and 0 to set a desired baud rate according to the table below. DIP switch Baud rate DR1 DR0 125 kbps OFF OFF 250 kbps OFF ON 500 kbps ON OFF This setting is prohibited ON ON Since this system communicates at 500 kbps, set only DR1 to ON. The necessary switches have been set. [2] Setting parameters The X-SEL controller provides a number of parameters for setting various aspects of operation. To connect the X-SEL controller to DeviceNet, the following I/O parameters must be set using the X-SEL PC software (model: IA-101-X-MW). (The parameters shown below apply to the X-SEL-J/K types. Some parameters are different on the X-SEL-P/Q types. For details, refer to the operation manual for your X-SEL controller.) I/O parameter no. Parameter name Description 1 I/O port assignment type (I/O type) Set whether to use fixed or automatic assignment of I/O ports ~ 9 10 ~ Standard I/O input port starting number (IO TpNo. Iprt:1) Set the port number for the first input port used in I/O communication. Standard I/O output port starting number (IO Set the port number for the first output port used in I/O TpNo. Oprt:1) communication. Extended I/O input (output) port starting number These parameters are set when an extended I/O board is used. (XIO1TpNo. Iprt (Oprt)) Standard (extended) I/O error monitor (IO (XIO) Set I/O error monitor. Sprvs) Number of network I/F card remote input ports (Prt Set the number of DeviceNet input points as a multiple of 8 (n) RmtInNetIF) (16 n 256). Number of network I/F card remote output ports Set the number of DeviceNet output points as a multiple of 8 (m) (Prt RmtOutNetIF) (16 m 256). The steps to set parameters are explained below. a) Connect the PC with the X-SEL controller using a dedicated PC connection cable, turn on the controller power, and then start the X-SEL PC software. After the software has started, click Parameter in the menu bar, and then select the Edit sub-menu.
11 b) When the parameter window opens, set I/O parameter nos. 1 to 15 as follows: No Automatic assignment No Set input ports from No. 0. No Set output ports from No Nos. 4 to Do not use (do not set). No Enable error monitoring. Nos. 11 to Do not use (do not set). No Set the number of input points to 32. No Set the number of output points to 16. c) After all parameters have been entered, click the Transfer to Controller button. d) When the message Data will be transmitted to the controller. Are you sure to continue? appears, click Yes. e) When all data has been transferred, the message Write Flash ROM? appears. Click Yes. f) When the message Restart the controller? appears, click Yes. This completes the necessary settings on the X-SEL controller side.
12 DeviceNet (3) Set the master unit On the master side, set the switches specified below. As with the X-SEL controller, the switches that must be set are those relating to the following two items: a. Node address setting b. Baud rate setting a. Node address setting Of the two rotary switches used for baud rate setting, the left switch indicates the tens digit, while the right switch indicates the ones digit. Set a desired address as a decimal number. You can set any value between 0 and 63. Switches for node address setting DIP switches for baud rate setting (Enlarged view of DeviceNet master unit) In this example, the node address is set to 0. b. Baud rate setting Set a desired baud rate using DIP switches 1 and 2 in accordance with the table below. DIP switch 1 2 Baud rate OFF OFF 125 kbps ON OFF 250 kbps OFF ON 500 kbps ON ON This setting is disabled Since this system communicates at 500 kbps, set switch 1 to OFF and switch 2 to ON. The necessary switches have been set. (4) Perform a line test The X-SEL controller and master station have been set successfully. Next, reset the controller. When the controller starts again, DeviceNet communication will be established. To check if the X-SEL controller and master station are communicating properly, check the LEDs on the master station and X-SEL controller, respectively. [1] LEDs on master station The master unit is communicating properly if the LED display on the master unit corresponds to the pattern shown to the left. : On : Off If not, review the settings. [2] LEDs on X-SEL controller The X-SEL controller is communicating properly if the LEDs on the controller correspond to the patterns shown to the left. : Steady green light : Flashing green light : Off * When I/O assignment is completed in the next section, the NS lamp will change to a steady green light. If the LEDs do not correspond to the specified patterns, write down the LED statuses and refer to the troubleshooting section in the X-SEL DeviceNet Operation Manual.
13 (5) Assign I/Os Use the configurator to assign I/Os for each slave. To set a connected device using the configurator, you need an EDS file containing information of that device. You can download an EDS file for the X-SEL controller from IAI s website. Install the file into the configurator by following the steps below. In the Configurator menu, click EDS File, and then select Install. Select the X-SEL EDS file you have downloaded, and then click Open. After the EDS file has been successfully installed, the AnyBus-S DeviceNet file is added under Vendor. Bring the configurator online. In this example, connect a communication cable to the I/F port on the PLC and connect the configurator to the network via the PLC. In the Configurator menu, click Select Interface, and then click SYSMAC CS/CJ I/F Port. In the Configurator menu, click Network, and then select Connect.
14 DeviceNet Enter the high-function unit number (number assigned to the master unit), serial port and baud rate, and then click OK. The configurator is brought online. Once the configurator is online, the applicable indicator in the status bar at the bottom of the window turns blue and the text On-line appears. Omron s EDS file is preinstalled in the configurator. In the tree view, select the model of the master unit to be used. Bring the cursor over the applicable model file, click the left mouse button, and drag the file into the right pane. After you have selected the master file, also move the X-SEL controller file into the right pane. (Repeat the step for each slave unit.) Note Node addresses may be shown in the order of #00, #01, and so on, for the files you have moved into the right pane, in the order moved. These node addresses can be changed later on. Remember that they must correspond to the node addresses selected by the switches.
15 Notes An EDS file normally contains I/O data (numbers of bytes to be occupied). The numbers of bytes occupied by the X-SEL controller vary depending on the numbers of I/O points used. Therefore, the specific I/O data must be entered to set this information. Right-click the AnyBus-S DeviceNet icon to display the pop-up menu shown to the left. In this menu, click Properties. When the window shown to the left opens, click Edit. In the OUT size and IN size fields under Poll, enter the numbers of bytes corresponding to the numbers of I/O points used. In this example, the X-SEL controller uses 16 output points and 32 input points. Accordingly, enter 4 bytes in the OUT size field and 2 bytes in the IN size field. * OUT and IN indicate the directions from the PLC side. They are reversed on the X-SEL. When the applicable settings have been entered, click OK. The numbers of bytes occupied by the X-SEL controller have been registered as Poll size information in the I/O Information tab. Confirm that the byte sizes are correct, and then click Close to close the window.
16 DeviceNet Bring the cursor over the master unit and click the right mouse button. In the pop-up menu that opens, click Parameter, and then select Edit. The device information in the files you have moved into the right pane in steps h) through i) are shown in the top pane. However, the master unit is yet to recognize these devices. Click the button at the center of the window to register the devices. * If the Automatically assign I/Os when devices are registered checkbox is selected, I/Os will be assigned automatically for devices as they are registered. (In this example, select this checkbox.) When the three devices have been registered, click OK. I/Os have been assigned for the three devices. Check the right pane and notice the icons added to the devices. These icons indicate that these devices have been registered to master #00. This completes the necessary settings on the master side.
17 (6) Start the system After confirming that the line is connected properly, start the sequencer program to start the system. Sample Program (1) X-SEL controller sample program This program selects one of positions 1 through 3 based on which of the three signals (inputs 11, 12 and 13) is sent from the PLC, and moves the actuator to the selected position. Step no. N Input condition Command Operand 1 Operand 2 Output Description 1 BTOF 304 Turn off output WTON 3 Wait for operation permission from the program 3 HOME 1 Perform home return 4 VEL 500 Set the speed to 500 mm/sec 5 TAG 1 Destination of GOTO1 6 WTOF 17 Wait for the input 17 signal (1 cycle end signal) to turn off 7 WTON 17 Wait for the input 17 signal (1 cycle end signal) to turn on 8 11 BTON 310 Turn on output 310 if input 11 is on 9 12 BTON 311 Turn on output 311 if input 12 is on BTON 312 Turn on output 312 if input 13 is on 11 N 20 GOTO 1 Return to TAG1 if input 20 is not on 12 BTOF Turn off outputs 313 to MOVP Move to position 1 if output 310 is on, and then turn on output 313 upon completion of movement MOVP Move to position 2 if output 311 is on, and then turn on output 314 upon completion of movement MOVP Move to position 3 if output 312 is on, and then turn on output 315 upon completion of movement 16 BTOF Turn off outputs 310 to BTON 304 Receive an end confirmation signal and respond to the PLC 18 GOTO 1 Return to TAG1
18 DeviceNet (2) PLC sample program Sensor 1 input Sensor 2 input Sensor 3 input Positioning complete 1 Positioning complete 2 Positioning complete 3 X-SEL program operation X-SEL input port 3 on Visual sensor signal small Auxiliary relay on Visual sensor signal medium Auxiliary relay on Visual sensor signal large Auxiliary relay on Auxiliary relay Position 1 selected Auxiliary relay Auxiliary relay Setting of position 1 complete (X-SEL output port 10 on) Setting of position 2 complete (X-SEL output port 11 on) Position 2 selected Position 3 selected Movement program started X-SEL input port 11 on X-SEL input port 12 on X-SEL input port 13 on X-SEL input port 20 on Setting of position 3 complete (X-SEL output port 12 on) Work small Movement to position 1 complete Sensor C End of 1 cycle confirmed Work medium Movement to position 2 complete Sensor B X-SEL input port 17 on Work large Movement to position 3 complete Sensor A
19 CC-Link Board Solderer for Cell Production Line System Overview This system uses cortesian 3-axis robots corresponding to individual cells to solder 10 different types of boards. Every time the board type changes, programs are switched using a sequencer connected via CC-Link. Benefits The program executed for each cell can be selected from among a group of programs and run automatically, which reduces program selection errors by the operator. Explanation of Application (1) System configuration Control panel Cell 3 master station Terminal resistor Cell 2 CC-Link cable Cell 1 X-SEL controller 3 (station number 3) Terminal resistor X-SEL controller 2 (station number 2) X-SEL controller 1 (station number 1)
20 CC-Link (2) Explanation of operation Description [1] At the start of each day, the types of works produced on that day are entered into the sequencer from the touch panel. Example Enter work 1 for cell 1. Enter work 2 for cell 2. Enter work 3 for cell 3. [2] The sequencer selects an appropriate operation program for each cell based on the entered information. [3] The sequencer selects an appropriate program via I/O for the controller corresponding to each cell. Select program 1 for work 1. Select program 2 for work 2. Select program 3 for work 3. Select program 1 for X-SEL controller 1. Select program 2 for X-SEL controller 2. Select program 3 for X-SEL controller 3. [4] Turn on the cell 1 start switch Program When a board (work) is set in each cell and the start 1 starts. switch is pressed, a selected program is started and the Turn on the cell 2 start switch Program board is soldered. 2 starts. Turn on the cell 3 start switch Program 3 starts. Conditions Operation programs for work 1 (program 1) through work 10 (program 10) are stored in the X-SEL controllers. When a work type is entered from the touch panel, the sequencer program selects the corresponding controller program via I/O as a binary code. When the operator sets a work and presses the start button, the program for each cell is started. How to set the controller and sequencer comprising this system is explained below. Communication Settings The flow of setting CC-Link communication between the X-SEL controller and sequencer is specified below. Connect the devices Connect the X-SEL controller and each CC-Link unit using a dedicated cable. Refer to p. 19. Set the X-SEL controller Set switches and parameters on the X-SEL controller. Refer to p. 20. Set the master unit Set master unit switches and parameters on the sequencer. Refer to p. 22. Perform a line test Input the power to the connected devices and perform a line test. Refer to p. 24. Start the system Once the line is connected, start the sequencer program to start the system. Refer to p. 24.
21 CC-Link (2) Set the X-SEL controller On the X-SEL controller, set [1] switches and [2] parameters. [1] Setting switches The switches that must be set are those relating to the following items: a. Station number setting b. Baud rate setting Cable connector Rotary switch for baud rate setting Rotary switch for station number setting (tens digit) Rotary switch for station number setting (ones digit) Monitor LEDs (Enlarged view of CC-Link connection board) a. Station number setting Set a desired station number using the rotary switches for station number setting (tens digit and ones digit). You can set any value between 1 and 64 (corresponding to stations 1 through 64). In this example, set the switches as follows: X-SEL controller 1 Station number 1 X-SEL controller 2 Station number 2 X-SEL controller 3 Station number 3 b. Baud rate setting One of five baud rates from 0 (156 kbps) to 4 (10 Mbps) can be set. Make sure that the baud rate set on the X-SEL controller corresponds to the baud rate set on the sequencer. Since this system communicates at 156 kbps, set the switch to 0. The necessary switches have been set. [2] Setting parameters The X-SEL controller provides a number of parameters for setting various aspects of operation. To connect the X-SEL controller to CC-Link, the following I/O parameters must be set using the X-SEL PC software (model: IA-101-X-MW). I/O parameter no. Parameter name Description 1 I/O port assignment type (I/O type) Set whether to use fixed or automatic assignment of I/O ports ~ 9 10 ~ Standard I/O input port starting number (IO TpNo. Iprt:1) Set the port number for the first input port used in I/O communication. Standard I/O output port starting number (IO Set the port number for the first output port used in I/O TpNo. Oprt:1) communication. Extended I/O input (output) port starting number These parameters are set when an extended I/O board is used. (XIO1TpNo. Iprt (Oprt)) Standard (extended) I/O error monitor (IO (XIO) Set I/O error monitor. Sprvs) Number of network I/F card remote input ports (Prt Set the number of CC-Link input points as a multiple of 16 (n) (16 RmtInNetIF) n 256). Number of network I/F card remote output ports Set the number of CC-Link output points as a multiple of 16 (m) (Prt RmtOutNetIF) (16 m 256). The steps to set parameters are explained below. * The same procedure applies to controllers 1 through 3. a) * The number of occupied stations varies depending on the numbers of points set in parameter nos. 14 and 15. For details, refer to the X-SEL CC-Link Operation Manual. Connect the PC with the X-SEL controller using a dedicated PC connection cable, turn on the controller power, and then start the X-SEL PC software. After the software has started, click Parameter in the menu bar, and then select the Edit sub-menu.
22 b) When the parameter window opens, set I/O parameter nos. 1 to 15 as follows: No Automatic assignment No Set input ports from No. 0. No Set output ports from No Nos. 4 to Do not use (do not set). No Enable error monitoring. Nos. 11 to Do not use (do not set). No Set the number of input points to 96. No Set the number of output points to 96. c) After all parameters have been entered, click the Transfer to Controller button. d) When the message Data will be transmitted to the controller. Are you sure to continue? appears, click Yes. e) When all data has been transferred, the message Write Flash ROM? appears. Click Yes. f) When the message Restart the controller? appears, click Yes. This completes the necessary settings on the X-SEL controller side.
23 CC-Link (3) Set the master unit On the master side, set the following items: [1] Switches [2] Network parameters [1] Setting switches As with the X-SEL controller, the switches that must be set are those relating to the following two items: a. Station number setting b. Baud rate setting Rotary switch for station number setting (tens digit) Rotary switch for station number setting (ones digit) Rotary switch for baud rate setting a. Station number setting Set a desired station number using the rotary switches for station number setting (tens digit and ones digit). You can set any value between 1 and 64 (corresponding to stations 1 through 64). Since the master station becomes station 0, set the station number to 0. b. Baud rate setting One of five baud rates from 0 (156 kbps) to 4 (10 Mbps) can be set. Specify the same baud rate set on the X-SEL controller. (Enlarged view of CC-Link master unit) Since this system communicates at 156 kbps, set the switch to 0. The necessary switches have been set. [2] Setting network parameters Set network parameters using GX Developer (Note 1). Among the network parameters, specify the number of devices connected to the CC-Link system, station information, and so on. Note 1) GX Developer is a programming software by Mitsubishi Electric. Double-click Network Parameters in the project data list shown in the GX Developer window. When the network parameter selection window opens, click CC-Link.
24 When the CC-Link network parameter setting window opens, set the respective parameters as specified below. * For details on each setting item, refer to the operation manual for the applicable CC-link master unit. Number of units Set the number of master unit to 1. First I/O number A0 --- Set the I/O number of the first I/O used in CC-Link communication to 00A0. Total number of Set the number of devices devices connected connected to CC-Link to 3. Remote input (RX) --- X Set the first remote input address to refresh device X100. Remote output (RY) --- Y Set the first remote output address refresh device to Y100. Remote register (RWr) --- D Set the first remote register (read) refresh device address to D100. Remote register (RWw) --- D0 --- Set the first remote register (write) refresh device address to D0. * When Station Information is clicked, the window below appears. Enter station information for the connected devices. Station number Remote device station station occupied Station number Remote device station station occupied Station number Remote device station station occupied After all parameters have been entered, click Setting Complete. Next, click the Write to PC button to open the PC write window. In the PC write window, click Parameters + Programs. The Programs and Parameters checkboxes underneath will be selected automatically. Click Write. Reset the sequencer CPU to make the new parameter effective. This completes the necessary settings on the master side.
25 CC-Link (4) Perform a line test The X-SEL controller and master station have been set successfully. Next, reset the sequencer. When the sequencer starts again, CC-Link communication will be established. To check if the X-SEL controller and master station are communicating properly, check the LEDs on the master station and X-SEL controller, respectively. [1] LEDs on master station The master unit is communicating properly if the LED display on the master unit corresponds to the pattern shown to the left. : On : Off If not, review the settings. [2] LEDs on X-SEL controller The X-SEL controller is communicating properly if the LEDs on the controller correspond to the patterns shown to the left. : Steady green light : Flashing green light : Off (red) If the LEDs do not correspond to the specified patterns, write down the LED statuses and refer to the troubleshooting section in the X-SEL CC-Link Operation Manual. (5) Start the system After confirming that the line is connected properly, start the sequencer program to start the system. Sample Program (1) PLC sample program X-SEL controller programs are selected based on I/O signals sent to the X-SEL controllers. Program numbers are specified via entry of two-digit BCD codes corresponding to port nos. 007 to 013. Specify program 1 Turn on port no. 007 Specify program 2 Turn on port no. 008 Specify program 3 Turn on port nos. 007 and 008 Specify program 4 Turn on port no. 009 Specify program 5 Turn on port nos. 007 and 009 ~ ~ Specify program 10 Turn on port nos. 008 and 010 Each work number (program number) entered from the touch panel is stored in a data register between 200 (cell 1) and 202 (cell 3). The controller input port for each cell is turned on in accordance with this number.
26 Operation details Enter a program number from the touch panel. The program number is sent to the sequencer. The sequencer stores the received value in a register and selects a controller program number corresponding to the stored value. Sequencer I/O assignments are shown below. CPU + Master Unit (An asterisk (*) indicates a system area reserved for remote device stations. These areas cannot be used as I/Os.) Slave Unit CPU register Buffer register For station number 1 Station number 1 Output Input Output Input For station number 2 Station number 2 Output Input Output Input For station number 3 Station number 3 Output Input Output Input
27 CC-Link The program below is the portion of the sample program for selecting the program for X-SEL controller 1. The program number selected on the touch panel is stored in data register 200, and the program for X-SEL controller 1 is selected based on the stored value. The programs for X-SEL controllers 2 and 3 are selected in the same manner, except that the addresses and flag numbers are different. No program Specify program 1 for controller 1 Specify program 2 for controller 1 Specify program 3 for controller 1 Specify program 4 for controller 1 Specify program 5 for controller 1 Specify program 6 for controller 1 Specify program 7 for controller 1 Specify program 8 for controller 1 Specify program 9 for controller 1 Specify program 10 for controller 1 Turn on port no. 007 (Program selection 1) Turn on port no. 008 (Program selection 2) Turn on port no. 009 (Program selection 4) Turn on port no. 010 (Program selection 8)
28 Ethernet Work Sorter/Pick-up System Overview The color and position of each molded product (work) arriving on a conveyor is measured using a camera, and the work is picked up by a SCARA robot. There are blue and red works, and works are transferred to different positions depending on their color as determined by the camera. Benefits Directly connecting the Ethernet-compatible CCD camera to the X-SEL controller eliminated the need for a PLC and thereby reduced cost. Explanation of Application (1) System configuration Sensor B Sensor A
29 Ethernet (2) Explanation of operation Description [1] The moment a work passes by sensor A, the camera measures the position and color of the work. [2] The measurement result is sent from the camera to the X-SEL controller via Ethernet. [3] The SCARA robot stands by near sensor B based on the measurement data from the camera. [4] When sensor B detects the work, the conveyor pauses momentarily. The SCARA robot picks up the work and transfers it to the pallet corresponding to the applicable color. Example The red work moves on the conveyor and passes the X coordinate: -350 position. The controller recognizes the coordinate information (-350) and color information (red) of the work via the program. The SCARA robot moves to the Y coordinate: -350 position and stands by. The SCARA robot picks up the red work and transfers it to the red pallet. Conditions The camera connected is DVT s SmartImage Sensor. The camera measures each work as soon as the work is detected by sensor A. The camera measures two items: [1] Y coordinate and [2] color (red or blue) of the work. The SCARA robot changes its standby position depending on the measurement data received from the camera, and waits for the work to arrive. The SCARA robot picks up the work as soon as the work is detected by sensor B. The SCARA robot transfers the picked-up work to the pallet corresponding to the applicable color based on the data sent from the camera. How to set the X-SEL controller and camera comprising this system is explained below. Communication Settings The flow of setting Ethernet communication between the X-SEL controller and CCD camera is specified below. Connect the devices Connect the X-SEL controller with the CCD camera using a LAN cable (RJ-45). Refer to p. 29. Set the X-SEL controller Enter X-SEL controller parameters and program. Refer to p. 30. Set the camera Set the camera and enter a program. Refer to p. 33. Perform a line test Input the power to the connected devices and perform a line test. Refer to p. 35. Start the system After confirming that the camera and X-SEL controller are connected to Ethernet, start both communication programs to establish communication between the two and start the system. Refer to p. 35.
30 About IP Address The IP address is an identification number assigned to each device communicating over Ethernet. Each address consists of four three-digit integers (0 to 255) separated by dots. The first three integers comprise an identification number used by all devices to connect to the same network, while the last integer serves as a device number. All communicating devices must have the same integers in the first three positions of their IP addresses; otherwise, they do not recognize one another as belonging to the same group. However, the last device number must be unique for each device, as duplicate device numbers disables communication. Exercise caution when setting IP addresses, because communication cannot be established if IP addresses are set incorrectly. Before establishing communication, port numbers must also be specified for communicating devices together with IP addresses. In this example, the stations are set as follows. Type Connected device IP address Server DVT camera Client X-SEL controller The setting procedure based on the above specifications is explained step by step. (1) Connect the devices Connect the X-SEL controller and each device as shown below. PC (When setting up) DVT s smart sensor Name of Each Part of Ethernet Board Cable connector DIP switches (not used) Monitor LEDs Connect a LAN cable to the cable connector. For the LAN cable, select a straight or crossed cable depending on the connection environment. Connecting controller and hub Connecting controller and controller Connecting controller and PC Straight Crossed Crossed The Ethernet connection board has DIP switches. Set all switches to OFF. The operating condition of the board and its Ethernet connection status can be checked on the monitor LEDs. (For details, refer to the X-SEL Controller Ethernet Operation Manual.) (Enlarged view of Ethernet connection board)
31 Ethernet (2) Set the X-SEL controller When the X-SEL controller is to communicate via Ethernet, one of the following three communication modes can be selected. I. [Remote I/O control using Modbus/TCP] I/Os can be turned on/off from a PLC supporting the Modbus protocol. II. [Message communication using IAI Protocol B] III. Tasks similar to those achieved in RS232C communication can be implemented via Ethernet using IAI Protocol B. [Message communication using SEL programs] You can use SEL programs to communicate easily with devices set for various protocols. In this example, the system uses communication mode III, or message communication using SEL programs. [1] Setting parameters The X-SEL controller provides a number of parameters for setting various aspects of operation. To connect the X-SEL controller to Ethernet, the following I/O parameters must be set using the X-SEL PC software (model: IA-101-X-MW). I/O parameter no. Parameter name Description 124 Network attribute 5 (Network Atrbt5) Specify the port to be used as well as its settings. 129 Network attribute 10 (Network Atrbt5) Specify the protocol type to be used. 132 Local IP address (H) (Lcl IP Adrs (H)) 133 Local IP address (HM) (Lcl IP Adrs (MH)) 134 Local IP address (ML) (Lcl IP Adrs (ML)) 135 Local IP address (L) (Lcl IP Adrs (L)) 136 Subnet mask (H) (Subnet Mask (H)) 137 Subnet mask (HM) (Subnet Mask (MH)) 138 Subnet mask (ML) (Subnet Mask (ML)) 139 Subnet mask (L) (Subnet Mask (L)) Port number for channel 31 open to user (Local Port Ch31) Port number for channel 32 open to user (Local Port Ch32) Port number for channel 33 open to user (Local Port Ch33) Port number for channel 34 open to user (Local Port Ch34) Specify the first number (192) in the IP address of the X-SEL controller. Specify the second number (168) in the IP address of the X-SEL controller. Specify the third number (0) in the IP address of the X-SEL controller. Specify the fourth number (1) in the IP address of the X-SEL controller. The subnet mask is an identification number similar to the IP address. Basically, the subnet mask is fixed to 255. The subnet mask is an identification number similar to the IP address. Basically, the subnet mask is fixed to 255. The subnet mask is an identification number similar to the IP address. Basically, the subnet mask is fixed to 255. The subnet mask is an identification number similar to the IP address. Basically, the subnet mask is fixed to 0. Specify the port number for channel 31 used for data transmission by SEL programs. Specify the port number for channel 32 used for data transmission by SEL programs. Specify the port number for channel 33 used for data transmission by SEL programs. Specify the port number for channel 34 used for data transmission by SEL programs. The steps to set parameters are explained below. a) Connect the PC with the X-SEL controller using a dedicated PC connection cable, turn on the controller power, and then start the X-SEL PC software. After the software has started, click Parameter in the menu bar, and then select the Edit sub-menu.
32 b) When the parameter window opens, set I/O parameter nos. 1 to 15 as follows: No Use channel 31. Set by the client. No Set input ports from No. 0. No IP address (H). Fixed to 192. No IP address (HM). Fixed to 168. No IP address (ML). Fixed to 0. No IP address (L). This must be a unique number. No Subnet mask (H). This number is basically fixed. No Subnet mask (HM). This number is basically fixed. No Subnet mask (ML). This number is basically fixed. No Subnet mask (L). This number is basically fixed. No Port number for channel 31 (basically fixed*). No Port number for channel 32 (basically fixed*). No Port number for channel 33 (basically fixed*). No Port number for channel 34 (basically fixed*). c) * Any value between 1025 and can be set. However, basically the default setting need not be changed. After all parameters have been entered, click the Transfer to Controller button. d) When the message Data will be transmitted to the controller. Are you sure to continue? appears, click Yes. e) When all data has been transferred, the message Write Flash ROM? appears. Click Yes. f) When the message Restart the controller? appears, click Yes. This completes the necessary settings on the X-SEL controller side. This completes the setting of necessary parameters.
33 Ethernet [2] Entering a communication program To establish communication, a communication program that declares IP addresses and port numbers, sends and receives data and performs all other necessary tasks must be entered and run. a) How to enter a program is explained below. Connect the PC with the X-SEL controller using a dedicated PC connection cable, turn on the controller power, and then start the X-SEL PC software. After the software has started, click File in the menu bar, point to the New sub-menu, and then select Program. b) When the window shown to the left opens, use the arrow keys to move the cursor to each target cell, and enter applicable data using single-byte characters. c) After all parameters have been entered, click the Transfer to Controller button. d) When the message Data will be transmitted to the controller. Are you sure to continue? appears, click Yes. e) In the next window, select a program number (1 to 64) under which to store the program in the controller. Move the cursor to a desired number, and then click Write. In this example, the program is stored under No. 3.
34 f) When all data has been transferred, the message Write Flash ROM? appears. Click Yes. The program has been entered. (3) Setting the camera To enable the camera to communicate with the X-SEL controller via Ethernet, perform the following settings using the supplied software (FRAMEWORK): [1] Specify communication settings on the PC to allow it to communicate with the camera. [2] Start FRAMEWORK installed in the PC to specify various settings for the camera. The specifics of [1] and [2] are explained below. [1] To connect the PC to Ethernet, you must set the PC s IP address and subnet mask. a) Click the Windows Start menu, point to Settings, point to Control Panel, point to Network Connections, and then select Local Area Network. b) Click Internet Protocol (TCP/IP), and then click Properties.
35 Ethernet c) Set the IP address as follows: *** * *** must be a unique number different from the numbers used in the IP addresses of the camera and X-SEL controller. Set the subnet mask as follows: When both addresses have been set, click OK to close the window. When the message box prompts you to restart the PC, click OK to restart the PC. [2] Start FRAMEWORK to set the camera. a) When FRAMEWORK is started, the PC Communications window opens first. Double-click Ethernet. Below the Ethernet folder, the IP address of the connected camera ( ***) is displayed. Click this address, and then click Connect at the bottom. b) Once the window shown to the left opens, the controller can communicate with the camera and you can perform various settings. For the procedures to set how work image is to be processed, signals are to be issued to the controller, and so on, refer to the operation manual for the applicable DVT. This completes the necessary settings for the camera.
36 (4) Perform a line test You can use the ping command to check if the camera and X-SEL controller are connected properly to Ethernet. The ping command is used to check network connection with a given host by issuing IP packets to the host and checking if the packets are correctly received and replied to by the host. From the PC desktop, click Start, point to Programs, point to Accessories, and then select Command Prompt. Type in ping, followed by the applicable IP address of the target. The target is connected properly if Reply from ***: bytes = ** time < * ms TTL = *** (* is a numerical value) is displayed, as shown to the left. Perform this for both the camera and controller. (5) Start the system After confirming that the line is connected properly, start the programs for camera and controller to start the system. Sample Program (1) X-SEL controller program The program shown on the facing page is used to communicate with the camera. The X-SEL controller receives coordinate and color information of works from the camera and assigns the received information to position data. To actually operate the system, you also need an operation program in addition to this communication program.
37 Ethernet Step no. N Input condition Command Operand 1 Operand 2 Description 1 DVT Legend series 500 communication test 2 TIMW 5 Wait for the DVT unit to start 3 BTOF Turn off controller outputs 607 to LET Set variable 300 to 0 5 SLEN 23 Set the string length to 23 bytes 6 SCPY 1 20 Copy 23 bytes from column 20 to column 1 7 DVT server IP address + port number declaration 8 LET Declare IP address H of the DVT camera 9 LET Declare IP address HM of the DVT camera 10 LET 92 0 Declare IP address ML of the DVT camera 11 LET Declare IP address L of the DVT camera 12 LET Declare the port number of the DVT system 13 DVT server IP address + port number declaration 14 IPCN Set the IP address of the DVT camera 15 SCPY 1 'RDY' Set the data to be sent 16 SPUT 4 13 Set the character string end code (13 = CR) 17 SCHA 13 Set the end code 18 OPEN 31 Open channel WRIT 31 Output the character strings spanning from column 1 to 1 CR via channel TAG 1 Destination of GOTO in step TMRD 1 22 READ 31 5 Read the response spanning from column 5 to CR 23 SCMP 5 'REQ' 24 TAG 4 25 N 608 GOTO 1 26 TAG 2 27 WTOF 607 Wait for DVT-TRRI to turn off 28 WTON 607 Wait for DVT-TRRI to turn on 29 BTOF 609 Start DVT judgment 30 SCPY 9 'GO' Set the data to be sent 31 SPUT Set the character string end code 32 WRIT 31 Output the character strings spanning from column 9 to 9 CR via channel READ Read the response spanning from column 12 to CR 34 SLEN 3 Set the number of characters to be compared 35 SCMP 12 'RED' Check for RED response 36 SCMP 12 'BLU' Check for BLUE response BTON 605 LED judgment BTOF 605 BLUE judgment 39 SLEN 7 Y-coordinate character string 40 VAL Assign the content of column 15 onward to variable LET 199 *300 Assign variable 300 to variable PPUT 2 2 Assign position 2 to axis 2 43 PPUT 2 3 Assign position 3 to axis 2 44 PPUT 2 4 Assign position 4 to axis 2 45 BTON 609 End DVT judgment 46 GOTO 2 47 EXIT
38 Protocol Communication (RS232C) Wood Length Specifier/Cutter System Overview A system that cuts wood to varying lengths. When specified dimensions are entered from the touch panel, the actuator moves to the specified position and moves the wood-length adjustment stopper. Benefits Before, the operator had to visually check the work to move the stopper and perform cutting, which led to inefficiencies stemming from incorrect scale reading and long cycle time. Introduction of the system has reduced mistakes to nearly zero because lengths can be entered numerically. The cycle time has also decreased dramatically. (Note 1) Explanation of Application (1) System configuration (Note 1) Absolute positioning accuracy is not guaranteed. Touch panel (MONITOUCH V series by Hakko Electronics) Control panel RS232C communication X-SEL controller Stopper Wood Stopper operating range
39 Ethernet [2] Entering a communication program To establish communication, a communication program that declares IP addresses and port numbers, sends and receives data and performs all other necessary tasks must be entered and run. a) How to enter a program is explained below. Connect the PC with the X-SEL controller using a dedicated PC connection cable, turn on the controller power, and then start the X-SEL PC software. After the software has started, click File in the menu bar, point to the New sub-menu, and then select Program. b) When the window shown to the left opens, use the arrow keys to move the cursor to each target cell, and enter applicable data using single-byte characters. c) After all parameters have been entered, click the Transfer to Controller button. d) When the message Data will be transmitted to the controller. Are you sure to continue? appears, click Yes. e) In the next window, select a program number (1 to 64) under which to store the program in the controller. Move the cursor to a desired number, and then click Write. In this example, the program is stored under No. 3. 3
40 f) When all data has been transferred, the message Write Flash ROM? appears. Click Yes. The program has been entered. (3) Setting the camera To enable the camera to communicate with the X-SEL controller via Ethernet, perform the following settings using the supplied software (FRAMEWORK): [1] Specify communication settings on the PC to allow it to communicate with the camera. [2] Start FRAMEWORK installed in the PC to specify various settings for the camera. The specifics of [1] and [2] are explained below. [1] To connect the PC to Ethernet, you must set the PC s IP address and subnet mask. a) Click the Windows Start menu, point to Settings, point to Control Panel, point to Network Connections, and then select Local Area Network. b) Click Internet Protocol (TCP/IP), and then click Properties. 4
41 Ethernet c) Set the IP address as follows: *** * *** must be a unique number different from the numbers used in the IP addresses of the camera and X-SEL controller. Set the subnet mask as follows: When both addresses have been set, click OK to close the window. When the message box prompts you to restart the PC, click OK to restart the PC. [2] Start FRAMEWORK to set the camera. a) When FRAMEWORK is started, the PC Communications window opens first. Double-click Ethernet. Below the Ethernet folder, the IP address of the connected camera ( ***) is displayed. Click this address, and then click Connect at the bottom. b) Once the window shown to the left opens, the controller can communicate with the camera and you can perform various settings. For the procedures to set how work image is to be processed, signals are to be issued to the controller, and so on, refer to the operation manual for the applicable DVT. This completes the necessary settings for the camera. 5
42 (4) Perform a line test You can use the ping command to check if the camera and X-SEL controller are connected properly to Ethernet. The ping command is used to check network connection with a given host by issuing IP packets to the host and checking if the packets are correctly received and replied to by the host. From the PC desktop, click Start, point to Programs, point to Accessories, and then select Command Prompt. Type in ping, followed by the applicable IP address of the target. The target is connected properly if Reply from ***: bytes = ** time < * ms TTL = *** (* is a numerical value) is displayed, as shown to the left. Perform this for both the camera and controller. (5) Start the system After confirming that the line is connected properly, start the programs for camera and controller to start the system. Sample Program (1) X-SEL controller program The program shown on the facing page is used to communicate with the camera. The X-SEL controller receives coordinate and color information of works from the camera and assigns the received information to position data. To actually operate the system, you also need an operation program in addition to this communication program. 6
43 Ethernet Step no. N Input condition Command Operand 1 Operand 2 Description 1 DVT Legend series 500 communication test 2 TIMW 5 Wait for the DVT unit to start 3 BTOF Turn off controller outputs 607 to LET Set variable 300 to 0 5 SLEN 23 Set the string length to 23 bytes 6 SCPY 1 20 Copy 23 bytes from column 20 to column 1 7 DVT server IP address + port number declaration 8 LET Declare IP address H of the DVT camera 9 LET Declare IP address HM of the DVT camera 10 LET 92 0 Declare IP address ML of the DVT camera 11 LET Declare IP address L of the DVT camera 12 LET Declare the port number of the DVT system 13 DVT server IP address + port number declaration 14 IPCN Set the IP address of the DVT camera 15 SCPY 1 'RDY' Set the data to be sent 16 SPUT 4 13 Set the character string end code (13 = CR) 17 SCHA 13 Set the end code 18 OPEN 31 Open channel WRIT 31 Output the character strings spanning from column 1 to 1 CR via channel TAG 1 Destination of GOTO in step TMRD 1 22 READ 31 5 Read the response spanning from column 5 to CR 23 SCMP 5 'REQ' 24 TAG 4 25 N 608 GOTO 1 26 TAG 2 27 WTOF 607 Wait for DVT-TRRI to turn off 28 WTON 607 Wait for DVT-TRRI to turn on 29 BTOF 609 Start DVT judgment 30 SCPY 9 'GO' Set the data to be sent 31 SPUT Set the character string end code 32 WRIT 31 Output the character strings spanning from column 9 to 9 CR via channel READ Read the response spanning from column 12 to CR 34 SLEN 3 Set the number of characters to be compared 35 SCMP 12 'RED' Check for RED response 36 SCMP 12 'BLU' Check for BLUE response BTON 605 LED judgment BTOF 605 BLUE judgment 39 SLEN 7 Y-coordinate character string 40 VAL Assign the content of column 15 onward to variable LET 199 *300 Assign variable 300 to variable PPUT 2 2 Assign position 2 to axis 2 43 PPUT 2 3 Assign position 3 to axis 2 44 PPUT 2 4 Assign position 4 to axis 2 45 BTON 609 End DVT judgment 46 GOTO 2 47 EXIT 7
44 Protocol Communication (RS232C) Wood Length Specifier/Cutter System Overview A system that cuts wood to varying lengths. When specified dimensions are entered from the touch panel, the actuator moves to the specified position and moves the wood-length adjustment stopper. Benefits Before, the operator had to visually check the work to move the stopper and perform cutting, which led to inefficiencies stemming from incorrect scale reading and long cycle time. Introduction of the system has reduced mistakes to nearly zero because lengths can be entered numerically. The cycle time has also decreased dramatically. (Note 1) Explanation of Application (1) System configuration (Note 1) Absolute positioning accuracy is not guaranteed. Touch panel (MONITOUCH V series by Hakko Electronics) Control panel RS232C communication X-SEL controller Stopper Wood Stopper operating range 8
45 Protocol Communication (RS232C) (2) Explanation of operation Description [1] Enter a wood length from the touch panel. The entered length is transferred to the controller via RS232C communication. Example Enter 800 as the length. * The value actually transferred to the controller is 500 ( mm). [2] The controller moves the slider to the specified position (coordinate). [3] The stopper attached to the slider moves, causing the target wood to be pressed against the work stopper and set in place. [4] The wood is securely held and cut. The slider moves to the coordinate position corresponding to 500 mm. (800 mm from the stopper to the cutting position) The work is cut to the overall length of 800 mm. Conditions The touch panel and X-SEL controller are connected via RS232C communication. Communication uses the communication program stored in the X-SEL controller, and the program in the touch panel is used to perform all X-SEL controller operations. (No operation program is required on the X-SEL controller side.) How to set the X-SEL controller and touch panel comprising this system is explained below. Communication Settings The flow of setting RS232C communication between the X-SEL controller and touch panel is specified below. Set the X-SEL controller Set X-SEL controller parameters. Refer to p. 39. Set the touch panel Set the touch panel parameters and create screens. Refer to p. 40. Connect the devices Connect the X-SEL controller and touch panel using a RS232C communication cable. Refer to p. 43. Start the system Start the touch panel program to start the system. Refer to p. 43. When a system uses a touch panel, a common practice is to connect the touch panel to a PLC and allow the PLC and X-SEL controller to communicate via PIOs. This is because separate communication parameters and program are needed to communicate with a touch panel. Although every manufacturer provides communication programs for their key PLC products, the user must create a communication program for connecting a touch panel with other devices. Hakko Electronics s MONITOUCH V series used in this system comes standard with a built-in communication program with the X-SEL controller. Therefore, it can communicate with the X-SEL controller directly without going through a PLC. 9
46 (1) Set the X-SEL controller If the X-SEL controller s communication protocol is used to perform communication, there is no need to create a separate program to be used by the X-SEL controller. All you need is to set the following parameters, and the communication program in the touch program will perform all control tasks. I/O parameter no. Parameter name Description 90 SIO channel 1 opened to user: Usage (Usage SIOch1) Select the communication method used for the teaching port (SEL program or IAI protocol). 91 SIO channel 1 opened to user: Station code (Address SIOch1) Set the station number to be assigned to the controller (0 to 31). 92 SIO channel 1 opened to user: Baud rate type (BaudRate SIOch1) Select the baud rate (9.6, 19.2 or 38.4 kbps). 93 SIO channel 1 opened to user: Data length (DataBits SIOch1) 94 SIO channel 1 opened to user: Stop bit length (StopBits SIOch1) 95 SIO channel 1 opened to user: Parity type (Parity SIOch1) Select the data length to be used in communication (7 or 8 bits). Select the stop bit length to be used in communication (1 or 2 bits). Select the parity to be used in communication (None, Odd or Even). a) The steps to set parameters are explained below. Connect the PC with the X-SEL controller using a dedicated PC connection cable, turn on the controller power, and then start the X-SEL PC software. After the software has started, click Parameter in the menu bar, and then select the Edit sub-menu. b) When the parameter window opens, set I/O parameter nos. 90 to 95 as follows: No Select IAI Protocol B No Set the station number to 0. No Set the baud rate to 38.4 kbps. No Set the data length to 8 (fixed). No Set the stop bit length to 1 (fixed). No Set the parity type to None (fixed). c) After all parameters have been entered, click the Transfer to Controller button. d) When the message Data will be transmitted to the controller. Are you sure to continue? appears, click Yes. e) When all data has been transferred, the message Write Flash ROM? appears. Click Yes. 10
47 Protocol Communication (RS232C) f) When the message Restart the controller? appears, click Yes. This completes the setting of necessary parameters. (2) Setting the touch panel For the touch panel, the following tasks are required: [1] Set communication parameters [2] Create screens [3] Transfer the screens and communication parameters to the touch panel [1] Setting communication parameters a) Connect the touch panel with the PC using a dedicated cable, and start the touch-panel image maker/editor software V-SFT. From the menu bar, click System Setting, point to Temp. CTRL/PLC2Way Setting, and then select Temp. CTRL/PL 2Way Comm. Setting. b) Select the Use Temp. Control Network/PLC2Way Communication checkbox. c) Leave all other settings unchanged, and click Refer to modular. The window shown to the left appears. Specify the modular jack to be connected to the X-SEL controller (modular jack 2 is used in this example) by selecting Temp./PLC2Way checkbox, and then click OK. 11
48 d) When Setting is clicked, the Type Setting window opens. Selecting Temperature control displays the names of models that can be connected. Select X-SEL Controller under IAI, and then click OK. e) When the message Will take default on Comm. Parameter. OK? appears, click Yes. f) The parameters required in communicating with the X-SEL controller are set. [2] Creating screens Use the touch-panel image maker/editor software V-SFT to create touch panel screens. For the procedures to create screens, refer to the manual for Hakko Electronics s V-SFT. 12
49 Protocol Communication (RS232C) [3] Transferring the screens and communication parameters to the touch panel a) When all necessary screens have been created, transfer the screen data and communication parameters to the touch panel. From the menu bar, click File, and then select Transfer. b) In the next window, select what you want to transfer. Select Screen Data, and then click Detail Setting. c) When the program asks you to confirm the serial port and baud rate of the PC, confirm the settings, and then click OK. * Normally, the serial port should be COM1 and baud rate should be If communication presents any problem with these settings, change the settings. d) Clicking PC -> starts data transfer. * The temperature control/plc program (Temp./PLC2) will also be sent automatically together with the screen data. 13
50 e) When the window shown to the left closes, all data has been successfully transferred. (3) Connect the devices Connect the RS232C communication cable to the X-SEL controller as shown below. Note) Turn off the power before connecting the cable. (*1) (*1) After connecting the RS232C cable, set the mode switch on the controller to MANU. MONITOUCH V series by Hakko Electronics TP port V series (MJ1/2) modular connector, 8 pins * Shielded wire (4) Start the system After connecting the X-SEL controller and touch panel using the RS232C cable, turn on the power to start communication. Press the various buttons and controls set on the touch panel to check the operations. 14
51 15 Protocol Communication (RS232C)
52 Free Protocol Communication (RS232C) PC Board Checker System Overview A board is placed on an cartesian robot assembled into a cross pattern, and a PC program is used to operate the cartesian robot to check the board with a camera. Benefits Before, an in-house XY table was controlled using a PLC positioning unit, with the PLC linked via a communication protocol to the PC for controlling the camera. Replacing the PLC and XY table with the X-SEL controller and cartesian robot enabled all control tasks to be performed using a PC program without involving any PLC ladder program. This made the overall control much easier. Explanation of Application (1) System configuration X-SEL controller PC CCD camera XY table 16
53 Free Protocol Communication (RS232C) (2) Explanation of operation Description Example [1] Enter a board type into the PC. Specify board 1. [2] The X-SEL controller moves the cartesian robot to the specified positions in accordance with the instructions from the PC. [3] Once the cartesian robot has moved to each specified position, the camera takes measurement. The robot moves to the pre-registered points (A, B and C) sequentially. Measurement is taken at positions A, B and C, respectively. Conditions This system uses a X-SEL controller of K (general-purpose) type. (Take note that the compact J type cannot accept an extended SIO board.) The X-SEL controller communicates with the PC via RS232C using the optional SIO board installed in the controller. A communication program has been created and installed in the X-SEL controller. All operations of the cartesian robot are performed using the program in the PC. How to set the X-SEL controller and PC comprising this system is explained below. Communication Settings The flow of setting RS232C communication between the X-SEL controller and PC is specified below. Connect the devices Connect the X-SEL controller with the PC using a RS232C communication cable. Refer to p. 47. Set the X-SEL controller Set X-SEL controller parameters. Refer to p. 47. Set the PC Specify communication settings on the PC. Refer to p. 49. Perform a line test Input the power to the connected devices and perform a line test. Refer to p. 50. Start the system Start the PC program to start the system. Refer to p. 54. To perform serial communication between the X-SEL controller and a peripheral, use an optional SIO board if RS422/485 communication is desired or when multiple communication channels will be used. A SIO board is installed in the extension slot of the X-SEL controller, so only the K (general-purpose) type can be used for this application. When a SIO board is used, the X-SEL controller performs free protocol communication. This means that the X-SEL controller can communicate with devices specified any protocol. (A SEL communication program is created and run in the X-SEL controller.) 17
54 (1) Connect the devices Connect the RS232C communication cable to the X-SEL controller as shown below. Crossed cable PC Controller end Model: CB-ST-232J mm Cable connection end D-sub, 9-pin connector Wiring diagram XM2D-1501 XM-2A0901 Wire Color Signal No. No. Signal Color Wire Orange with black dot SD 1 3 SD Orange with black dot Orange with black dot RD 2 2 RD Orange with black dot Light gray with black dot RS 3 7 RS Light gray with black dot Light gray with red dot CS 4 White with black dot ER CS ER Light gray with red dot White with black dot AWG24 x 7 cores White with red dot DR 6 AWG24 Yellow with black dot SG 7 x 7 cores DR SG White with red dot Yellow with black dot * The user must provide a communication cable to each external device (2) Set the X-SEL controller To perform communication using an extended SIO board, set I/O parameter nos. 100 to 110. Each extended SIO board has two ports (two channels). Up to three extended SIO boards (corresponding to two to six channels) can be installed. [1] Setting parameters Under the factory parameter settings, the channel numbers and specifications of extended SIO boards are set as follows. Channel 6 Channel 4 Channel 2 Channel 3 Default settings: Baud rate: 38.4 kbps Data length: 8 Stop bit length: 1 Parity type: None Communication mode: RS232 Channel 5 Channel 7 Channel numbers are determined by the corresponding parameter numbers. Channel 2 I/O parameter no. 100 Channel 3 I/O parameter no. 102 Channel 4 I/O parameter no. 104 Channel 5 I/O parameter no. 106 Channel 6 I/O parameter no. 108 Channel 7 I/O parameter no
55 Free Protocol Communication (RS232C) [2] Parameter settings Example) When is set in I/O parameter no. 100 The specifications of channel 2 are set as follows (the boxed portions indicate the specifications set by this parameter.) Baud rate: 0: 9.6 kbps, 1: 19.2 kbps, 2: 38.4 kbps, 3: 57.6 kbps, 4: 76.8 kbps, 5: kbps Data length: 7, 8 Stop bit length: 1, 2 Parity type: 0: None, 1: Odd, 2: Even Communication mode: 0: RS232, 1: RS422, 2: RS485 Half-duplex receive operation type (effective only in RS485 communication) 0: Enable receive after send 1: Do not enable receive after send Board channel assignment 1: Dsub upper, 2: Dsub lower (See the figure below.) Extended I/O slot assignment: 3rd from standard I/O (See the figure below.) upper lower 1st, 2nd, 3rd from the standard I/O The steps to set parameters are explained below. a) Connect the PC with the X-SEL controller using a dedicated PC connection cable, turn on the controller power, and then start the X-SEL PC software. After the software has started, click Parameter in the menu bar, and then select the Edit sub-menu. b) When the parameter window opens, set I/O parameter nos. 100 and 102 as follows: No No * Parameter no. 102 need not be set if channel 3 is not used. c) After all parameters have been entered, click the Transfer to Controller button. 19
56 d) When the message Data will be transmitted to the controller. Are you sure to continue? appears, click Yes. e) When all data has been transferred, the message Write Flash ROM? appears. Click Yes. f) When the message Restart the controller? appears, click Yes. This completes the necessary settings on the X-SEL controller side. (3) Setting the PC In this example, the setting procedure using HyperTerminal that comes with Windows is explained. a) Click the Windows Start menu, point to Programs, point to Accessories, point to Communications, and then select HyperTerminal. b) When the window shown to the left opens, enter a file name, select an appropriate icon, and then click OK. 20
57 Free Protocol Communication (RS232C) c) The port setting window appears next. Leave all settings unchanged and click OK. d) The communication parameter setting window appears next. Enter each item as shown to the left, and then click OK. This completes the necessary settings on the PC. (4) Perform a line test Use HyperTerminal to check if the PC and X-SEL controller can communicate properly. To perform a line test, enter a check program into the X-SEL controller and start the program before starting HyperTerminal. [1] Entering a X-SEL controller program a) Connect the PC with the X-SEL controller using a dedicated PC connection cable (*), turn on the controller power, and then start the X-SEL PC software. From the menu bar, click File, point to New, and then select Program. (*) Connect the teaching port (D-sub, 25-pin) on the controller with the RS232C connector (D-sub, 9-pin) on the PC. 21
58 b) When the program entry window opens, enter a desired program. * In this example, a sample line test program is entered. Refer to p. 54 for the program details. c) When the program has been entered, click the Transfer to Controller button. d) In the confirmation window, click Yes. e) The next window asks you to select a number to store the program under. Click a desired number, and then click Write. In this example, the program is stored under No. 1. f) When the program transfer is finished, the message Write Flash ROM? appears. Click Yes. The program has been successfully written to the controller. Now, you can start the program. 22
59 Free Protocol Communication (RS232C) g) From the menu bar, click Program, and then select Edit. h) When the program number selection window opens, select program No. 1 you have stored earlier, and then click Read. i) The program edit window opens next. Click the Program Start button. j) When the program is started, the background of the program window turns gray. The cursor changes to a band and moves over the lines to indicate the command currently executed. * When the band cursor is red, it means that the program is paused or waiting for entry on the applicable command. After confirming that the program has started, close the PC software and change the PC and controller connection to one using a RS232C cable. 23
60 [2] Starting HyperTerminal a) From the menu bar, click File, and then select Open. Open the file name you have entered earlier. b) When the file opens, click File from the menu bar, and then select Properties. c) The Serial Communication Properties window opens next. Click the Settings tab. Next, click ASCII Setup in the bottom right-hand corner of the window. d) Select the necessary checkboxes as shown to the left. When all selections have been made, click OK to close the window. Click OK again to close the previous window, as well. 24
61 Free Protocol Communication (RS232C) e) Enter text in the initial HyperTerminal window. If the same text appears below the one you have just entered, communication is normal. If nothing is shown, review the settings from the beginning. (5) Start the system After confirming that the line is connected properly, start the PC program to start the system. Sample Program (1) Test program using HyperTerminal This is the controller program used in the line test above. It basically returns all data sent from the PC directly back to the PC. Step no. Command Operand 1 Operand 2 Description 1 SCHA 10 Set the end code LF 2 OPEN 2 Open serial port channel 2 3 TAG 1 Destination of GOTO in step 8 4 READ 2 1 Read the data received from channel 2 to column 1 5 SLEN 99 Set the number of characters to be processed to 99 6 SCPY Copy the data in column 1 to column 301 (*) 7 WRIT 2 1 Write the data in column 1 via channel 2 8 GOTO 1 Return to TAG in step 3 * Column 301 is used for monitoring. 25
62
63 Catalog No.: CJ0086-1A (August 2005) Website: Information contained in this catalog is subject to change without notice for the purpose of product improvement.
Using the AnyBus -X Gateway to Communicate between a DVT camera and a Profibus Master
Using the AnyBus -X Gateway to Communicate between a DVT camera and a Profibus Master Page 1 of 13 Table of Contents 1 OVERVIEW... 3 2 INSTALLING AND CONFIGURING THE ANYBUS -X GENERIC GATEWAY AND ETHERNET
TCP/IP MODULE CA-ETHR-A INSTALLATION MANUAL
TCP/IP MODULE CA-ETHR-A INSTALLATION MANUAL w w w. c d v g r o u p. c o m CA-ETHR-A: TCP/IP Module Installation Manual Page Table of Contents Introduction...5 Hardware Components... 6 Technical Specifications...
USER GUIDE. Ethernet Configuration Guide (Lantronix) P/N: 2900-300321 Rev 6
KRAMER ELECTRONICS LTD. USER GUIDE Ethernet Configuration Guide (Lantronix) P/N: 2900-300321 Rev 6 Contents 1 Connecting to the Kramer Device via the Ethernet Port 1 1.1 Connecting the Ethernet Port Directly
Modbus and ION Technology
70072-0104-14 TECHNICAL 06/2009 Modbus and ION Technology Modicon Modbus is a communications protocol widely used in process control industries such as manufacturing. PowerLogic ION meters are compatible
ENET-710. ENET-710 - Ethernet Module ENET-710 JAN / 06 FOUNDATION
ENET-710 ENET-710 - Ethernet Module JAN / 06 ENET-710 FOUNDATION E N E T 7 1 0 ME smar www.smar.com Specifications and information are subject to change without notice. Up-to-date address information is
Wireless LAN 802.11g USB Adapter
Wireless LAN 802.11g USB Adapter User s Guide Version 1.0 User s Guide 0 Copyright statement No part of this publication may be reproduced, stored in a retrieval system, or transmitted in any form or by
Easy Setup Guide for the Sony Network Camera
-878-191-11 (1) Easy Setup Guide for the Sony Network Camera For setup, a computer running the Microsoft Windows Operating System is required. For monitoring camera images, Microsoft Internet Explorer
To perform Ethernet setup and communication verification, first perform RS232 setup and communication verification:
PURPOSE Verify that communication is established for the following products programming option (488.2 compliant, SCPI only): DCS - M9C & DCS M130, DLM M9E & DLM-M9G & DLM M130, DHP - M9D, P series, SG,
ACU-1000 Manual Addendum Replacement of CPM-2 with CPM-4
ACU-1000 Manual Addendum Replacement of CPM-2 with CPM-4 1 PURPOSE:... 1 2 CPM-4/CPM-2 COMPATIBILITY... 2 2.1 NETWORK CABLES... 2 2.2 FACTORY DEFAULT SETTINGS... 2 2.3 CHANGING THE RS-232 SERIAL PORT BAUD
How to setup a serial Bluetooth adapter Master Guide
How to setup a serial Bluetooth adapter Master Guide Nordfield.com Our serial Bluetooth adapters part UCBT232B and UCBT232EXA can be setup and paired using a Bluetooth management software called BlueSoleil
How to read this guide
How to read this guide The following shows the symbols used in this Quick start guide with descriptions and examples. Symbol Description Example P oint Reference Caution [ ] This symbol explains information
BASLER ACE QUICK INSTALLATION GUIDE
BASLER ACE QUICK INSTALLATION GUIDE Rev. 01 Quick installation Guide V1 1 Introduction The installation procedures in this guide assume that you want to get your camera operational and begin capturing
CCNA Discovery 4.0.3.0 Networking for Homes and Small Businesses Student Packet Tracer Lab Manual
4.0.3.0 Networking for Homes and Small Businesses Student Packet Tracer Lab Manual This document is exclusive property of Cisco Systems, Inc. Permission is granted to print and copy this document for non-commercial
1 Serial RS232 to Ethernet Adapter Installation Guide
Installation Guide 10/100 Mbps LED (amber color ) Link/Activity LED (green color ) 1. Introduction Thank you for purchasing this 1-port RS232 to Ethernet Adapter (hereinafter referred to as Adapter ).
1 Application Description... 3. 1.1 Objective... 3 1.2 Goals... 3
Contents Moxa Technical Support Team [email protected] 1 Application Description... 3 1.1 Objective... 3 1.2 Goals... 3 2 System Topology... 3 3 Hardware and Software Requirements... 4 4 Configuration...
FINS Gateway For OMRON PLCs
1 Purpose This Technical Note describes how to set up a remote collaboration. A remote collaboration consists in configuring, programming or monitoring a PLC from a remote location, without the need of
NETWORK PRINT MONITOR User Guide
NETWORK PRINT MONITOR User Guide Legal Notes Unauthorized reproduction of all or part of this guide is prohibited. The information in this guide is subject to change without notice. We cannot be held liable
About This Guide SolarEdge Configuration Tool Software Guide. About This Guide
About This Guide 3 About This Guide This user guide is intended for Photovoltaic (PV) system owners, installers, technicians, maintainers, administrators and integrators who are authorized to configure
How To Use An Easymp Network Projection Software On A Projector On A Computer Or Computer
EasyMP Network Projection Operation Guide Contents 2 Before Use Functions of EasyMP Network Projection....................... 5 Sharing the Projector....................................................
7.7 Ethernet Communication (AFPX-COM5)
7.7 Ethernet Communication (AFPX-COM5) 7.7.1 AFPX-COM5 Overview The communication cassette AFPX-COM5 has an Ethernet interface at the COM1 port and a 3-wire RS232C interface at the COM2 port. The Ethernet
Modbus and ION Technology
Modbus and ION Technology Modicon Modbus is a communications protocol widely used in process control industries such as manufacturing. ACCESS meters are compatible with Modbus networks as both slaves and
R&S AFQ100A, R&S AFQ100B I/Q Modulation Generator Supplement
I/Q Modulation Generator Supplement The following description relates to the Operating Manuals, version 03 of R&S AFQ100A, and version 01 of R&S AFQ100B. It encloses the following topics: LXI features,
R&S AFQ100A, R&S AFQ100B I/Q Modulation Generator Supplement
I/Q Modulation Generator Supplement The following description relates to the Operating Manuals, version 03 of R&S AFQ100A, and version 01 of R&S AFQ100B. It encloses the following topics: LXI features,
EasyMP Network Projection Operation Guide
EasyMP Network Projection Operation Guide Contents 2 Before Use Functions of EasyMP Network Projection... 5 Sharing the Projector... 5 Various Screen Transfer Functions... 5 Installing the Software...
MFC7840W Windows Network Connection Repair Instructions
Difficulty printing from your PC can occur for various reasons. The most common reason a networked Brother machine may stop printing, is because the connection between the computer and the Brother machine
How To Use An Easymp Network Projector On A Computer Or Network Projection On A Network Or Network On A Pc Or Mac Or Ipnet On A Laptop Or Ipro Or Ipo On A Powerbook On A Microsoft Computer On A Mini
EasyMP Network Projection Operation Guide Contents 2 Before Use Functions of EasyMP Network Projection....................... 5 Sharing the Projector....................................................
OPERATION MANUAL. MV-410RGB Layout Editor. Version 2.1- higher
OPERATION MANUAL MV-410RGB Layout Editor Version 2.1- higher Table of Contents 1. Setup... 1 1-1. Overview... 1 1-2. System Requirements... 1 1-3. Operation Flow... 1 1-4. Installing MV-410RGB Layout
Manual. IP Sensor and Watchdog IPSW2210. I P S W 2 2 1 0 M a n u a l P a g e 1. Relay Output. Power input. 12VDC adapter LED Indicators. 2 Dry.
IP Sensor and Watchdog IPSW2210 Manual Relay Output Power input 12VDC adapter LED Indicators 1 wire 2 Dry Output Green : Power Yellow: Link temperature & humidity contact inputs LED indicator sensor input
Schneider OS-Loader usage via Ethernet or USB.
LHC Gas Systems 28 th February, 2007 Schneider OS-Loader usage via Ethernet or USB. Jacques ROCHEZ - IT/CO/FE Abstract This document is a guideline on how to configure correctly a PC for the use of the
The following sections describe the Gateway configuration pages in the SBG1000 Setup Program.
Configuration Gateway > WAN Page Gateway: LAN nat config Page Gateway: LAN dhcp server config Page Gateway LOG Page Preparing the Network Preparing the Computers for TCP/IP Networking Configuring TCP/IP
FBs-CM25/CM55/CBE. Ethernet Module. User s Manual
FBs-CM25/CM55/CBE Ethernet Module User s Manual Ver. 2.1 Fatek Automation Corp. 7/1/2004 1. Preface...2 2. Specification...2 2.1 Serial Communication Connector(FBS-CM25E/CM55E only)...2 2.2 Ethernet Serial
EasyMP Network Projection Operation Guide
EasyMP Network Projection Operation Guide Contents 2 About EasyMP Network Projection Functions of EasyMP Network Projection....................... 5 Various Screen Transfer Functions.......................................
S-SupremaConfigurationGuide-DOC 7/23/2014. Suprema Biometrics Configuration Guide ACS OnSite Aparato
S-SupremaConfigurationGuide-DOC 7/23/2014 Suprema Biometrics Configuration Guide ACS OnSite Aparato Page 2 Suprema Configuration Guide ACS OnSite Aparato Table of Contents 1. SUPREMA BIOSTAR CONFIGURATION...
Legal Notes. Regarding Trademarks. 2012 KYOCERA Document Solutions Inc.
Legal Notes Unauthorized reproduction of all or part of this guide is prohibited. The information in this guide is subject to change without notice. We cannot be held liable for any problems arising from
Packet Tracer 3 Lab VLSM 2 Solution
Packet Tracer 3 Lab VLSM 2 Solution Objective Create a simulated network topology using Packet Tracer Design an IP addressing scheme using a Class B subnetwork address and VLSM Apply IP addresses to the
Adding a Modbus TCP Device to the Network. Setting Up Your Network
Page 1 of 17 Adding a Modbus TCP Device to the Network Overview This section extends the sample Unity Pro application, by describing how to: add an STB NIP 2212 Modbus TCP network interface module to your
WRE6505. User s Guide. Quick Start Guide. Wireless AC750 Range Extender. Default Login Details. Version 1.00 Edition 1, 4 2014
WRE6505 Wireless AC750 Range Extender Version 1.00 Edition 1, 4 2014 2.4G 5G Quick Start Guide User s Guide Default Login Details LAN IP Address 192.168.1.2 User Name admin www.zyxel.com Password 1234
The Wireless LAN (Local Area Network) USB adapter can be operated in one of the two following networking configurations :
SAGEM Wi-Fi 11g USB ADAPTER Quick Start Guide About this guide This Quick Start Guide describes how to install and operate your SAGEM Wi-Fi 11g USB ADAPTER. Please read this manual before you install the
1. Installing The Monitoring Software
SD7000 Digital Microphone Monitor Software manual Table of Contents 1. Installing The Monitor Software 1.1 Setting Up Receivers For Monitoring 1.2 Running The Application 1.3 Shutdown 2. The Detail Monitoring
BECKHOFF. Application Notes. www.beckhoffautomation.com. BC9000: Getting Started Guide. For additional documentation, please visit.
BECKHOFF Application Notes www.beckhoffautomation.com BC9000: Getting Started Guide BC-AppNote-002 1.0 27 August 2007 This application note is intended for the first time user of the BC9000 and TwinCAT
Computer Networks I Laboratory Exercise 1
Computer Networks I Laboratory Exercise 1 The lab is divided into two parts where the first part is a basic PC network TCP/IP configuration and connection to the Internet. The second part is building a
EZ-View Network Communications Guide www.cszindustrial.com
Network Communications Guide EzView Network Communications Guide RevB July 2013 (V2.2) Supersedes: RevA (May 2011) Cincinnati Sub-Zero Products, LLC 513-772-8810 12011 Mosteller Road Cincinnati, Ohio 45241
DTAP3000 DTSX3000 Control Visualization Software LAS2.0 Data Conversion Guide
User s Manual DTAP3000 DTSX3000 Control Visualization Software LAS2.0 Data Conversion Guide 1st Edition Blank Page < Introduction > i Introduction About this Manual Thank you for purchasing the DTSX3000
ADSL Router Quick Installation Guide Revised, edited and illustrated by Neo
ADSL Router Quick Installation Guide Revised, edited and illustrated by Neo A typical set up for a router PCs can be connected to the router via USB or Ethernet. If you wish to use a telephone with the
Procedure: You can find the problem sheet on Drive D: of the lab PCs. Part 1: Router & Switch
University of Jordan Faculty of Engineering & Technology Computer Engineering Department Computer Networks Laboratory 907528 Lab. 2 Network Devices & Packet Tracer Objectives 1. To become familiar with
How to configure DVR and computer for running Remote Viewer via IP network
How to configure DVR and computer for running Remote Viewer via IP network Follow these steps to configure a network DVR and a computer with Remote Viewer software to see live pictures via IP network.
Stand Alone Type. Digital Video Recorder USER S MANUAL. (Real time recording 8 & 16 CH DVR) Revision Date : 2010. 6. 30.
Stand Alone Type Digital Video Recorder USER S MANUAL (Real time recording 8 & 16 CH DVR) Revision Date : 2010. 6. 30. INDEX 1. Front Panel - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
Software User Guide UG-461
Software User Guide UG-461 One Technology Way P.O. Box 9106 Norwood, MA 02062-9106, U.S.A. Tel: 781.329.4700 Fax: 781.461.3113 www.analog.com ezlinx icoupler Isolated Interface Development Environment
Prestige 660R-6x Read Me First
Prestige 660R-6x Read Me First Prestige Rear Panel Connections DSL PORT CONNECTION Connect the DSL port on the Prestige to the wall jack using the included DSL cable (telephone wire). Connect the micro
WA Manager Alarming System Management Software Windows 98, NT, XP, 2000 User Guide
WA Manager Alarming System Management Software Windows 98, NT, XP, 2000 User Guide Version 2.1, 4/2010 Disclaimer While every effort has been made to ensure that the information in this guide is accurate
Setting up VPN Access for Remote Diagnostics Support
Setting up VPN Access for Remote Diagnostics Support D. R. Joseph, Inc. supports both dial-up and Internet access for remote support of 3GIBC1 and LF-Sizer control systems. This document describes how
Connecting the DG-102S VoIP Gateway to your network
Contents of Package: DG-102S VoIP Station Gateway Power adapter CD-ROM, including User s Manual Quick Install Guide Requirements: RS-232 Console Cable Two RJ-45 CAT-5 Straight-Through Cables For more information
13 Managing Devices. Your computer is an assembly of many components from different manufacturers. LESSON OBJECTIVES
LESSON 13 Managing Devices OBJECTIVES After completing this lesson, you will be able to: 1. Open System Properties. 2. Use Device Manager. 3. Understand hardware profiles. 4. Set performance options. Estimated
genie app and genie mobile app
genie app and genie mobile app User Manual 350 East Plumeria Drive San Jose, CA 95134 USA June 2012 202-10933-02 v1.0 2012 NETGEAR, Inc. All rights reserved No part of this publication may be reproduced,
Debugging Network Communications. 1 Check the Network Cabling
Debugging Network Communications Situation: you have a computer and your NetBurner device on a network, but you cannot communicate between the two. This application note provides a set of debugging steps
1 PC to WX64 direction connection with crossover cable or hub/switch
1 PC to WX64 direction connection with crossover cable or hub/switch If a network is not available, or if it is desired to keep the WX64 and PC(s) completely separated from other computers, a simple network
ModBus Server - KNX. Gateway for integration of KNX equipment into Modbus (RTU and TCP) control systems.
IntesisBox ModBus Server - KNX Gateway for integration of KNX equipment into Modbus (RTU and TCP) control systems. Integrate KNX based lighting control into your SCADA, BMS, PLC "talking" Modbus. Master
Operation Manual of EX-9132C-2. Serial to TCP/IP Converter
Operation Manual of EX-9132C-2 Serial to TCP/IP Converter Version 1.2.1 20th May 2013 Table of Contents 1. Introduction 3 Overview 4 Package Checklist 4 Block Diagram 5 Features 6 Product Specifications
General Precautions The user must operate each product according to the performance specifications described in the operation manuals.
General Precautions The user must operate each product according to the performance specifications described in the operation manuals. Before using the product under conditions which are not described
2 Setting Up the Hardware for a Wired Ethernet Network... 13. 3 Setting Up the Software for an Ethernet Network... 21
Contents 1 Networking Basics............................................... 1 Selecting a network connection........................................ 2 Wired Ethernet network...........................................
Installation and Operation Guide
www.aja.com Quick Start Guide Introduction This Quick Start Guide provides a basic overview of KUMO configuration. It is not meant as a substitute for the detailed information found in the KUMO Manual,
CS 326e F2002 Lab 1. Basic Network Setup & Ethereal Time: 2 hrs
CS 326e F2002 Lab 1. Basic Network Setup & Ethereal Time: 2 hrs Tasks: 1 (10 min) Verify that TCP/IP is installed on each of the computers 2 (10 min) Connect the computers together via a switch 3 (10 min)
Technical Note. Configuring an Omron PLC with Omron FINS Ethernet Driver. 1. Introduction
Technical Note Configuring an Omron PLC with Omron FINS Ethernet Driver 1. Introduction This document describes how to configure an Omron PLC with a FINS-enabled Ethernet module and the Omron FINS Ethernet
RcWare SoftPLC Modbus server mapping editor User manual
RcWare SoftPLC Modbus server mapping editor User manual 1 Contents 1 Contents... 2 2 Why SoftPLC as a Modbus server... 3 3 Installation and setup of the Modbus mapping editor... 4 4 Creating and editing
Operation Manual of EX9132C-RS485. Serial to TCP/IP Converter
Operation Manual of EX9132C-RS485 Serial to TCP/IP Converter Version 1.0 27th May 2014 Table of Contents 1. Introduction 3 Overview 4 Package Checklist 4 Block Diagram 5 Product Features 7 Product Specifications
1 Application Description... 2 2 System Topology... 2 3 Hardware and Software Requirements... 3
Contents Moxa Technical Support Team [email protected] 1 Application Description... 2 2 System Topology... 2 3 Hardware and Software Requirements... 3 3.1 Hardware Requirement... 3 3.2 Software Equipment...
Avaya Wireless AP Device Manager User Guide
Avaya Wireless AP Device Manager User Guide February 2003 Avaya Wireless AP Device Manager User Guide Copyright Avaya Inc. 2003 ALL RIGHTS RESERVED The products, specifications, and other technical information
32 Transferring Projects and Data
32 Transferring Projects and Data This Chapter explains how to transfer GP-Pro EX project files to the GP and how to transfer the project files stored on the GP to your PC. Please start by reading 32.1
R&S AFQ100A, R&S AFQ100B I/Q Modulation Generator Supplement
I/Q Modulation Generator Supplement The following description relates to the Operating Manuals, version 03 of R&S AFQ100A, and version 01 of R&S AFQ100B. It encloses the following topics: LXI features,
Chapter7 Setting the Receiving PC for Direct Upload. Setting the Receiving PC for Direct Upload... 148 For Windows... 148 For Macintosh...
Chapter7 Setting the Receiving PC for Direct Upload Setting the Receiving PC for Direct Upload... 148 For Windows... 148 For Macintosh... 153 Setting the Receiving PC for Direct Upload This section explains
Wireless-N. User Guide. PCI Adapter WMP300N (EU) WIRELESS. Model No.
2,4 GHz WIRELESS Wireless-N PCI Adapter User Guide Model No. WMP300N (EU) Copyright and Trademarks Specifications are subject to change without notice. Linksys is a registered trademark or trademark of
TRP-C31M MODBUS TCP to RTU/ASCII Gateway
TRP-C31M MODBUS TCP to RTU/ASCII Gateway User s Manual Printed Feb. 2007 Rev 1.0 Trycom Technology Co., Ltd 1F, No.2-11, Sihu street, Yingge Township, Taipei, Taiwan ROC Tel: 886-2-86781191, Fax: 886-2-86781172
Kurz MODBUS Client User s Guide
Kurz MODBUS Client User s Guide Introduction The Kurz MODBUS Client program can be used to demonstrate how the Kurz MFTB and MFTA Series products can be used in a MODBUS protocol network. The program is
Networking. General networking. Networking overview. Common home network configurations. Wired network example. Wireless network examples
Networking General networking Networking overview A network is a collection of devices such as computers, printers, Ethernet hubs, wireless access points, and routers connected together for communication
Ethernet Interface Manual Thermal / Label Printer. Rev. 1.01 Metapace T-1. Metapace T-2 Metapace L-1 Metapace L-2
Ethernet Interface Manual Thermal / Label Printer Rev. 1.01 Metapace T-1 Metapace T-2 Metapace L-1 Metapace L-2 Table of contents 1. Interface setting Guiding...3 2. Manual Information...4 3. Interface
BIT COMMANDER. Serial RS232 / RS485 to Ethernet Converter
BIT COMMANDER Serial RS232 / RS485 to Ethernet Converter (Part US2000A) Copyrights U.S. Converters 1 Contents Overview and Features... 3 Functions..5 TCP Server Mode... 5 Httpd Client Mode.5 TCP Auto mode....6
IP Link Device Interface Communication Sheet
This document provides additional assistance with wiring your Extron IP Link enabled product to your device. Different components may require a different wiring scheme than those listed below. For complete
MODBUS TCP to RTU/ASCII Gateway
MODBUS TCP to RTU/ASCII Gateway Users Manual Model MODport-101, MODport-102, MODport-104 July 2011 1 INTRODUCTION... 1 1.1 FEATURES... 2 1.2 PRODUCT SPECIFICATIONS... 3 1.3 DEFAULT SETTINGS... 4 2 MAKING
WUA-0605 300Mbps Wireless USB Network Adapter
WUA-0605 300Mbps Wireless USB Network Adapter User Manual V1.0 Certification FCC CE FCC Statement This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant
IP Link Device Interface Communication Sheet
This document provides additional assistance with wiring your Extron IP Link enabled product to your device. Different components may require a different wiring scheme than those listed below. For complete
Vantage RADIUS 50. Quick Start Guide Version 1.0 3/2005
Vantage RADIUS 50 Quick Start Guide Version 1.0 3/2005 1 Introducing Vantage RADIUS 50 The Vantage RADIUS (Remote Authentication Dial-In User Service) 50 (referred to in this guide as Vantage RADIUS)
Application Note Connect to a Rockwell PLC over Netbiter Remote Access
Application Note Connect to a Rockwell PLC over Netbiter Remote Access Doc: HMSI 27-239 Rev: 1.0 Connecting Devices TM HALMSTAD CHICAGO KARLSRUHE TOKYO BEIJING MILANO MULHOUSE COVENTRY PUNE COPENHAGEN
T3 Mux M13 Multiplexer
T3 Mux M13 Multiplexer User Manual [Type the abstract of the document here. The abstract is typically a short summary of the contents of the document. Type the abstract of the document here. The abstract
MicroLogix 1100 Embedded Web Server
User Manual MicroLogix 1100 Embedded Web Server Bulletin 1763 Controllers Important User Information Solid-state equipment has operational characteristics differing from those of electromechanical equipment.
3.1 Connecting to a Router and Basic Configuration
3.1 Connecting to a Router and Basic Configuration Objective This lab will focus on the ability to connect a PC to a router in order to establish a console session and observe the user interface. A console
EV-1000 Series DVR. Quick Operation Guide. Version 1.0.0
EV-1000 Series DVR Quick Operation Guide Version 1.0.0 Thank you for purchasing our product. If there is any question or request, please do not hesitate to contact dealer. This manual is applicable to
DeviceNet Bus Software Help for Programming an Allen Bradley Control System
FBP FieldBusPlug V7 DeviceNet Bus Software Help for Programming an Allen Bradley Control System DeviceNet Software Help for Programming an Allen Bradley Control System Contents Page General Purpose...
How To Use Mview On A Powerline 2.2 (Powerline) On A Pc Or Macbook 2 (Powerplst) On An Iphone Or Ipa 2 (Aldo) On Your Iphon 2 (
mview for V8.53 and Later Motion Software mview is an elevator monitoring application. Through 1 Ethernet, the computer running mview may be connected directly to a single Motion 2000 or Motion 4000 controller
IDDERO HCx-KNX TOUCH PANELS. Quick start guide. www.iddero.com 130125-02
IDDERO HCx-KNX TOUCH PANELS Quick start guide www.iddero.com 130125-02 TABLE OF CONTENTS 1 INTRODUCTION... 3 2 IDDERO CONFIGURATION SOFTWARE... 3 2.1 Installation and First Steps...3 3 TOUCH PANEL CONFIGURATION...
MODBUS TCP to RTU/ASCII Gateway. User s Manual
MODBUS TCP to RTU/ASCII Gateway User s Manual 1 INTRODUCTION... 1 1.1 FEATURES... 2 1.2 PRODUCT SPECIFICATIONS... 3 1.3 DEFAULT SETTINGS... 4 2 MAKING THE HARDWARE CONNECTIONS... 5 2.1 POWER CONNECTION...
DSL Installation Guide
DSL Installation Guide Thank you for choosing Integra Telecom s DSL service! Introduction This guide will walk you through the DSL installation process and will help you configure a computer to access
Setup and Programming of the. Master Module R72-11Z-SLSASG-028
Setup and Programming of the FX3U-16CCL-M eth1000_large.jpg FX3U CC-LINK Master Module R72-11Z-SLSASG-028 Contents Contents... i FURTHER READING REFERENCE LIST... ii Chapter 1 Introduction... 1-1 Chapter
IDDERO HOME SERVER. Quick start guide. www.iddero.com 150302-02
IDDERO HOME SERVER Quick start guide www.iddero.com 150302-02 TABLE OF CONTENTS 1 INTRODUCTION... 3 2 IDDERO CONFIGURATION SOFTWARE... 3 2.1 Installation and First Steps...3 3 IDDERO HOME SERVER CONFIGURATION...
Network Scanner Tool V3.5. User s Guide Version 3.5.01
Network Scanner Tool V3.5 User s Guide Version 3.5.01 Copyright 2000-2016 by SHARP CORPORATION. All rights reserved. Reproduction, adaptation or translation without prior written permission is prohibited,
WakeMyPC technical user guide
USER GUIDE WakeMyPC technical user guide WakeMyPC is the name for the new Wake-on-LAN (WoL) service that allows you to boot your office PC or Apple Mac from home. With this new service you no longer need
Ethernet Radio Configuration Guide
Ethernet Radio Configuration Guide for Gateway, Endpoint, and Repeater Radio Units April 20, 2015 Customer Service 1-866-294-5847 Baseline Inc. www.baselinesystems.com Phone 208-323-1634 FAX 208-323-1834
AXIS 205 Network Camera Quick Installation Guide
AXIS 205 Quick Installation Guide Page 1 of 6 AXIS 205 Network Camera Quick Installation Guide Focus Ring Status Indicator (surrounding the focus ring) Serial number Network Indicator Control Button Power
Contents. 1.2 Software Installation... 1
Software Manual Contents 1 Software Installation... 1 1.1 Overview...1 1.2 Software Installation... 1 2 Introduction To Basic Function...5 2.1 Login System... 5 2.2 CMS Operating Interface...5 2.2.1 Operating
User Guide for Windows 10
User Guide for Windows 10 System requirements E10684 First Edition July 2015 To facilitate a smoother transition from your previous operating system, read the system requirements below before upgrading
PRINTER DRIVER GUIDE (KODAK 305 Photo Printer)
PRINTER DRIVER GUIDE () Microsoft, Windows, Windows XP, Windows Vista and Windows 7 are registered trademarks of Microsoft Corporation in the United States and/or other countries. Adobe, Adobe Photoshop
