BUILDING CODE COMMISSION

Size: px
Start display at page:

Download "BUILDING CODE COMMISSION"

Transcription

1 Ruling No Application No BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF Article of Regulation 403, as amended, (the Building Code). AND IN THE MATTER OF an application by John McIntyre, Maple Reinders Constructors Ltd., for resolution of a dispute with Shelly Switzer, Chief Building Official, Town of Oakville, to determine whether the size and positioning of openings in the as-constructed firewalls provide sufficiency of compliance with Article of the Building Code at the Clearview Christian Reformed Church, 2300 Sheridan Garden Drive, Oakville, Ontario. APPLICANT RESPONDENT PANEL PLACE John McIntyre Maple Reinders Constructors Ltd. Shelly Switzer Chief Building Official Town of Oakville Tony Chow, Chair Donald Pratt Michael Steele Toronto, Ontario DATE OF HEARING January 13, 2005 DATE OF RULING January 19, 2005 APPEARANCES Walter Miller, Consulting Engineer Arencon Inc. Agent for the Applicant Shelly Switzer, Chief Building Official Town of Oakville The Respondent

2 - 2 - RULING 1. Particulars of Dispute The Applicant has received a building permit under the Building Code Act, 1992, and has constructed an assembly occupancy building referred to as the Clearview Christian Reformed Church at 2300 Sheridan Garden Drive, Oakville, Ontario. The subject structure is a 1 storey, Group A, Division 2 major occupancy building, comprised of combustible construction. The structure has been subdivided into three separate buildings by firewalls having a 2 hour fire resistance rating. Buildings A (the sanctuary), B (offices) and C (fellowship hall) have areas of 1,483.4 m 2, m 2 and m 2 respectively. The entire facility is equipped with a fire alarm system. The construction in dispute involves the openings that penetrate the two firewalls that subdivide the structure. The subject firewalls are penetrated by several openings including doors, ducts and a pass-through window. Each opening in the firewall is protected with a 90 minute rated closure (door, shutter or fire damper). Where mechanical ducts penetrate the firewalls they are positioned directly above an opening for a door or pass-through window separated from the larger openings below by a 2 hour masonry panel. Further, the duct openings do not surpass the vertical extension of the width of the opening above which they are located. According to the Applicant, the total width of all door and pass-through window openings does not exceed 25% of the lineal length of either firewall. This calculation for percentage openings, however, does not include separate consideration for the width of the mechanical openings. The issue for consideration is whether placing the duct openings directly above the door and window openings will provide sufficiency of compliance with the provisions of Article of the Building Code. 2. Provisions of the Building Code in Dispute Maximum Openings (1) Openings in a firewall shall conform to the size limits described in Article and the aggregate width of openings shall be not more than 25% of the entire length of the firewall. 3. Applicant s Position The Agent for the Applicant provided the Commission with an overview of the issue at dispute. He submitted several exhibits depicting the as-constructed firewall openings and offered a comparison between what is proposed and what would be permitted by the Code if the door and window openings were vertically extended to incorporate the area where the duct penetrations are positioned. The hypothetical scenario, he submitted, would encompass a greater cumulative area than the current proposal, and yet would still not exceed 25% of the entire length of the firewall. The Agent submitted that, generally, he agreed that each opening should be measured independently. However, in this instance, greater life safety is provided where openings are positioned directly above one another. He noted further, that the City has now agreed, in principal, to the Applicant s reasoning but, because of the technical opinion provided by the Building and Development Branch of the Ministry of Municipal Affairs and Housing, the Town is

3 - 3 - still requiring that this matter be resolved by the Building Code Commission. In summation, the Agent reiterated that, following the example depicted in Scenario 2 presented in Exhibit 7, significantly larger openings would be permitted than what is proposed in this building. He noted that the walls were constructed in accordance with Article and comply with the requirements of He suggested that the proposed configuration of openings offers better protection than what would be permitted by the Code. 4. Respondent s Position The Respondent submitted that, in his opinion, the Applicant has achieved sufficiency of compliance with Sentence of the Code. He requested that the Commission, however, still rule on this matter since the Ministry s Building and Development Branch has provided a contrary opinion suggesting that the as-built configuration does not comply with the Code requirements. He noted that the technical background information report prepared in connection with this dispute states that combining openings in this manner is not an option permitted by the Code. In response to questioning, the Respondent submitted that he did not believe that the structural integrity of the wall system was at issue in respect to the aggregate length of openings. Instead, he suggested, that the issue is related to fire safety and protection (i.e. closures). He stated that the Town would satisfy itself as to the structural integrity of the firewalls and compliance with other relevant provisions of the Building Code. He asked, however, that the Commission rule as to the sufficiency of compliance of the proposal with Sentence Commission Ruling It is the decision of the Building Code Commission that the size and positioning of openings in the as-constructed firewalls will provide sufficiency of compliance with Article of the Building Code at the Clearview Christian Reformed Church, 2300 Sheridan Garden Drive, Oakville, Ontario, on condition that: 1. The Chief Building Official is satisfied that: a) The as-constructed firewalls will meet the definition of firewall as set out in Article of the Code in respect to the structural stability of the wall under fire conditions; b) The as-constructed firewalls will comply with Sentences (1) and (2) of the Building Code; c) The as-constructed firewalls have been designed to meet the requirements of Article of the Building Code; and d) Fire dampers and mechanical duct openings in the firewalls will comply with the requirements of (4). of the Code. 2. The mechanical duct openings in the firewalls are to be positioned such that the width of the mechanical opening is entirely within the vertical extension of the width of the door or shutter opening located directly below it. 3. Those portions of the masonry firewalls situated between the door/shutter openings and the mechanical duct openings will remain structurally stable under fire conditions as required by Article of the Building Code.

4 Reasons i) The mechanical duct openings are positioned directly above the openings for a door or shutter. ii) The horizontal projection of the individual mechanical duct openings will be within the width of the corresponding door or shutter opening above which the mechanical openings are situated. iii) The aggregate width of all door and shutter openings in each firewall does not exceed 25% of the entire length of the firewall.

5 - 5 - Dated at Toronto this 19 th day in the month of January in the year 2005 for application number Tony Chow, Chair Donald Pratt Michael Steele

BUILDING CODE COMMISSION

BUILDING CODE COMMISSION Ruling No. 02-25-880 Application No. 2002-21 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF Article 9.30.1.2 of

More information

Excerpts from the Canadian National Building Code (NBC)

Excerpts from the Canadian National Building Code (NBC) Excerpts from the Canadian National Building Code (NBC) Reproduced here with Permission of the Copyright Owner, the National Research Council of Canada, Institute for Research in Construction. For more

More information

How To Build A Two Hour Firewall In Calgary

How To Build A Two Hour Firewall In Calgary BUILDING CODE INTERPRETATION February 2008 06-BCI-005-R1 Page 1 of 6 TWO-HOUR FIREWALLS BACKGROUND Historically, firewalls used to subdivide buildings into smaller units have been built using one of two

More information

Overview of Hotel Fire Safety Requirements

Overview of Hotel Fire Safety Requirements Overview of Hotel Fire Safety Requirements in the Fire Code Susan Clarke, P.Eng. Office of the Fire Marshal - January 10, 2012 1 Agenda Regulation History - Hotels Fire Code Overview (Parts 1 to 8) Defined

More information

Small Business Permit Service

Small Business Permit Service Small Business Permit Service Building Permit Requirements For a Unit Finish or Interior Alteration Industrial, Commercial or Institutional Occupancies Building Permit Application The following documents

More information

Executive Summary Inclusion of Current Firewall Requirements in NBCC

Executive Summary Inclusion of Current Firewall Requirements in NBCC Executive Summary Inclusion of Current Firewall Requirements in NBCC This background paper has been prepared on behalf of the Gypsum Manufacturers of Canada by Standing Committee on Fire Safety & Occupancy

More information

New Ontario Building Code Requirements for Mid-rise Wood Frame Buildings

New Ontario Building Code Requirements for Mid-rise Wood Frame Buildings New Ontario Building Code Requirements for Mid-rise Wood Frame Buildings Note: This information addresses complex issues in a summary fashion. Consideration should be given to the official version of the

More information

INTERNATIONAL ASSOCIATION OF CLASSIFICATION SOCIETIES. Interpretations of the FTP

INTERNATIONAL ASSOCIATION OF CLASSIFICATION SOCIETIES. Interpretations of the FTP INTERNATIONAL ASSOCIATION OF CLASSIFICATION SOCIETIES Interpretations of the FTP CONTENTS FTP1 Adhesives used in A or B class divisions (FTP Code 3.1, Res A.754 para. 3.2.3) June 2000 FTP2 Pipe and duct

More information

MULTI-FAMILY, COMMERCIAL, INDUSTRIAL, AS GOVERNED BY THE BC BUILDING CODE PART 3

MULTI-FAMILY, COMMERCIAL, INDUSTRIAL, AS GOVERNED BY THE BC BUILDING CODE PART 3 TOWN OF SIDNEY Multi-Family, Commercial, Industrial and Institutional Building Permit Guide The information provided is intended as a guide only and does not replace current bylaws and regulations. Complete

More information

LPCB Red Book Listed Products and Passive Fire Protection Installer Schemes Answering the needs of the market

LPCB Red Book Listed Products and Passive Fire Protection Installer Schemes Answering the needs of the market LPCB Red Book Listed Products and Passive Fire Protection Installer Schemes Answering the needs of the market Ian Stewart Passive installer scheme manager September 2011 Introduction to BRE Global Research,

More information

The Florida Building Code

The Florida Building Code Setting New Standards for Safety The Florida Building Code Florida Building Commission Florida Department of Community Affairs The Florida Building Code System The Florida Building Commission Florida Building

More information

We hope these Frequently Asked Questions will be of use both to municipal officials and fire inspectors.

We hope these Frequently Asked Questions will be of use both to municipal officials and fire inspectors. September 14, 2012 Dear AMM Member: Please see the attached Fire Code Frequently Asked Questions. This document was compiled by the Office of the Fire Commissioner at the AMM s request to help clarify

More information

POLICY ON COMPLAINTS HANDLING PROCEDURES. 1. Complaints Handling Effectiveness, Efficiency and Accountability

POLICY ON COMPLAINTS HANDLING PROCEDURES. 1. Complaints Handling Effectiveness, Efficiency and Accountability POLICY ON COMPLAINTS HANDLING PROCEDURES 1. Complaints Handling Effectiveness, Efficiency and Accountability This Policy sets out the procedures that apply to FCT Insurance Company Ltd., First American

More information

2012 Ontario Building Code Requirements for New Construction. Bradford West Gwillimbury Building Division March 5, 2012

2012 Ontario Building Code Requirements for New Construction. Bradford West Gwillimbury Building Division March 5, 2012 2012 Ontario Building Code Requirements for New Construction Bradford West Gwillimbury Building Division March 5, 2012 1 Ontario Building Code changes Applicable to permits applied for after December 31,

More information

Ministry of the Environment Decree. on housing design

Ministry of the Environment Decree. on housing design G1 THE NATIONAL BUILDING CODE OF FINLAND Housing Design Regulations and Guidelines 2005 Ministry of the Environment Decree on housing design adopted in Helsinki on the 1 st of October 2004 In accordance

More information

3.In making the following determination, the Secretary of State has not considered whether the plans conform to any other relevant requirements.

3.In making the following determination, the Secretary of State has not considered whether the plans conform to any other relevant requirements. Date: 06/09/99 Ref: 45/1/166 Note: The following letter was issued by our former department, the Department for Environment, Transport and the Regions (DETR). DETR is now Communities and Local Government

More information

Decree of the Ministry of the Environment on fire safety of ventilation systems

Decree of the Ministry of the Environment on fire safety of ventilation systems THE NATIONAL BUILDING CODE OF FINLAND MINISTRY OF THE ENVIRONMENT Housing and Building Department Decree of the Ministry of the Environment on fire safety of ventilation systems Adopted in Helsinki, 18

More information

Ontario s 2012 Building Code Division B, Part 9 (Ontario Regulation 332/12)

Ontario s 2012 Building Code Division B, Part 9 (Ontario Regulation 332/12) Ontario s 2012 Building Code Division B, Part 9 (Ontario Regulation 332/12) Notice: This e-learning module is intended for general information purposes only. It only highlights certain provisions of the

More information

OFM-TG-01-2004. Office of the Fire Marshal F M FIRE DRILLS GUIDELINE

OFM-TG-01-2004. Office of the Fire Marshal F M FIRE DRILLS GUIDELINE O FIRE DRILLS F M October 2004 GUIDELINE TABLE OF CONTENTS SECTION PAGE Abstract... 3 1.0 INTRODUCTION... 4 2.0 DEFINITIONS... 4 3.0 LEGAL OBLIGATIONS... 5 4.0 FIRE DRILL OBJECTIVES... 5 5.0 FIRE DRILL

More information

- 5 - Table1. Maximum Compartment Volumes

- 5 - Table1. Maximum Compartment Volumes - 5 - Part II - SPECIFIC REQUIREMENTS 5. Compartmentation 5.1 Every building should be divided into compartments by walls and floors to inhibit the spread of fire. 5.2 Compartment walls, compartment floors,

More information

FIRE RATED WIRING. What the FT4! Paul Latreille, C.E.T. Ottawa Branch Manager

FIRE RATED WIRING. What the FT4! Paul Latreille, C.E.T. Ottawa Branch Manager FIRE RATED WIRING What the FT4! Paul Latreille, C.E.T. Ottawa Branch Manager INTRODUCTION OBC requirements for emergency power OBC requirements for emergency power for fire alarm systems and other building

More information

GENERAL + MEANS OF ESCAPE (Part One) By Mdm Eng Yew Hoon (SIA)

GENERAL + MEANS OF ESCAPE (Part One) By Mdm Eng Yew Hoon (SIA) GENERAL + MEANS OF ESCAPE (Part One) By Mdm Eng Yew Hoon (SIA) Chapter 1 : Definitions clause 1.2.10 : circulation space OLD CLAUSE A space mainly used as means of access between a room or protected shaft

More information

FIRE AND SMOKE PROTECTION FEATURES

FIRE AND SMOKE PROTECTION FEATURES CHAPTER 7 FIRE AND SMOKE PROTECTION FEATURES SECTION 70 GENERAL 70. Scope. The provisions of this chapter shall govern the materials, systems and assemblies used for structural fire resistance and fire-resistance-rated

More information

Building Code Clarifications - 7. Fire Resistance

Building Code Clarifications - 7. Fire Resistance Building Code Clarifications - 7. Fire Resistance 7.1 (15-12-030) Use of combustibles in Type III construction roof assemblies Code Section (15-12-030) Use of Combustibles was revised on May 17, 2000,

More information

FIRE-RESISTANCE-RATED CONSTRUCTION

FIRE-RESISTANCE-RATED CONSTRUCTION CHAPTER 7 FIRE-RESISTANCE-RATED CONSTRUCTION SECTION 70 GENERAL 70. Scope. The provisions of this chapter shall govern the materials and assemblies used for structural fire resistance and fire-resistance-rated

More information

FIRE-RESISTANCE-RATED CONSTRUCTION

FIRE-RESISTANCE-RATED CONSTRUCTION CHAPTER 7 FIRE-RESISTANCE-RATED CONSTRUCTION SECTION 70 GENERAL 70. Scope. The provisions of this chapter shall govern the materials and assemblies used for structural fire resistance and fire-resistance-rated

More information

HCD DSA OSHPD 1 2 1/AC AC SS SS/CC 1 2 3 4 2013 CALIFORNIA BUILDING CODE 199

HCD DSA OSHPD 1 2 1/AC AC SS SS/CC 1 2 3 4 2013 CALIFORNIA BUILDING CODE 199 CALIFORNIA BUILDING CODE MATRIX ADOPTION TABLE CHAPTER 7 FIRE AND SMOKE PROTECTION FEATURES (Matrix Adoption Tables are non-regulatory, intended only as an aid to the user. See Chapter for state agency

More information

FIRE AND SMOKE PROTECTION FEATURES

FIRE AND SMOKE PROTECTION FEATURES CHAPTER 7 FIRE AND SMOKE PROTECTION FEATURES SECTION 70 GENERAL 70. Scope. The provisions of this chapter shall govern the materials, systems and assemblies used for structural fire resistance and fire-resistance-rated

More information

RULING OF THE MINISTER OF MUNICIPAL AFFAIRS AND HOUSING

RULING OF THE MINISTER OF MUNICIPAL AFFAIRS AND HOUSING BUILDING CODEACT, 1992 RULING OF THE MINISTER OF MUNICIPAL AFFAIRS AND HOUSING Pursuant to clause 29(l)(b) of the Building Code Act, 1992. as amended, the Director of the Building and Development Branch

More information

February 2014 Alberta Fire Code 4.2.6.3. Page 1 of 5. Fire Safety and Hand Hygiene in Healthcare Facilities

February 2014 Alberta Fire Code 4.2.6.3. Page 1 of 5. Fire Safety and Hand Hygiene in Healthcare Facilities FIRE CODE VARIANCE February 2014 Alberta Fire Code 4.2.6.3. Page 1 of 5 ISSUE: Fire Safety and Hand Hygiene in Healthcare Facilities This Variance covers alcohol based hand hygiene products used in healthcare

More information

By-law to Regulate Vacant Buildings

By-law to Regulate Vacant Buildings By-law to Regulate Vacant Buildings A-35 Enacted November 23, 2009 This by-law is printed under and by authority of the Council of the City of London, Ontario, Canada Disclaimer: The following consolidation

More information

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT FIRE SAFETY INSPECTION REPORT M.I.T APPARELS LTD PATHANTULY, GODNAIL, SHIDDIRGONJ, NARAYANGONJ OTHER FACTORIES: NONE June 4, 2014 Page 2 SUMMARY was surveyed for fire safety on 6/4/2014 by Hughes Associates,

More information

Schedule B to By-law 33-2009

Schedule B to By-law 33-2009 Amended by By-law 8-2016 Note: This consolidation is prepared for convenience only. For accurate reference the original by-laws should be reviewed. Floor Area Calculation Floor area shall: Schedule B to

More information

Indiana Building Rehabilitation Standard

Indiana Building Rehabilitation Standard Rule 8. Indiana Building Rehabilitation Standard 675 IAC 12-8-1 Definitions Sec. 1. The following definitions apply throughout this rule: (1) "Building code" means the Indiana Building Code under 675 IAC

More information

How To Install A Carbon Monoxide Detector

How To Install A Carbon Monoxide Detector NASSAU COUNTY FIRE COMMISSION OFFICE OF THE FIRE MARSHAL Nassau County Public Safety Center 1194 Prospect Avenue Westbury, New York 11590 (516) 573-9900 / nassaucountyny.gov Chief Fire Marshal Scott D.

More information

Number of Sides Required to Have a Handrail

Number of Sides Required to Have a Handrail Excerpt from 2012 B.C. Building Code HANDRAILS & GUARDS 9.8.7. Handrails 9.8.7.1. Required Handrails 1) Except as provided in Sentences (2) to (4), handrails shall be installed on stairs and ramps in accordance

More information

Building Codes Update: The 2009 International Fire Code and the Apartment Industry

Building Codes Update: The 2009 International Fire Code and the Apartment Industry ! Building Codes Update: The 2009 International Fire Code and the Apartment Industry Apartment operators and developers should be aware of organizational changes in the 2009 edition of the International

More information

Services Enclosures and Protected Shafts - Maintaining Compartmentation

Services Enclosures and Protected Shafts - Maintaining Compartmentation Introduction When a fire resisting element is used to provide fire compartmentation, every opening that allows services to pass through the element must be adequately protected by sealing, or fire stopping

More information

Certification: Building Plans Examiner. Exam ID: B3

Certification: Building Plans Examiner. Exam ID: B3 Certification: Building Plans Examiner Exam ID: B3 Scope: A Building Plans Examiner will be responsible for reviewing submitted plans to determine if they meet the requirements of the various Building

More information

Important Ontario Fire Code Information for Building Owners in the City of Windsor

Important Ontario Fire Code Information for Building Owners in the City of Windsor Important Ontario Fire Code Information for Building Owners in the City of Windsor This information is intended to be used a reference only. For a complete listing consult the Ontario Fire Code or contact

More information

I.S. 3218 :2013 Fire Detection & Alarm Systems

I.S. 3218 :2013 Fire Detection & Alarm Systems I.S. 3218 :2013 Fire Detection & Alarm Systems Overview of significant changes 26 th March 2014 FPS Ltd Today s Programme Commencement Transition Competence & Qualifications System Certification System

More information

HOW METAL BUILDING INSURANCE COSTS COMPARE TO OTHER BUILDING TYPES

HOW METAL BUILDING INSURANCE COSTS COMPARE TO OTHER BUILDING TYPES MBMA INSURANCE BULLETIN no. 15 HOW METAL BUILDING INSURANCE COSTS COMPARE TO OTHER BUILDING TYPES Contractors who build with other products will compete with metal buildings based on an assumption that

More information

Queen's University Environmental Health and Safety

Queen's University Environmental Health and Safety April, 2009 1 SOP-Chem-08 1.0 Introduction This document is intended as a guide to the Queen s University requirements for handling and storing flammable and combustible material in non-laboratories areas.

More information

Chapter 492 GREEN ROOFS

Chapter 492 GREEN ROOFS Chapter 492 GREEN ROOFS ARTICLE I General 492-1. Definitions. ARTICLE II Requirement for Green Roofs 492-2. Green roofs required. 492-3. Maintenance of green roofs and health of vegetation. 492-4. Permit

More information

NRC Canadian Codes Centre. Codes Update. Nedjma Belrechid October 2012

NRC Canadian Codes Centre. Codes Update. Nedjma Belrechid October 2012 NRC Canadian Codes Centre Codes Update Nedjma Belrechid October 2012 Codes Update Outline Activities of CCBFC, PTPACC, NRC-IRC Code Development Public Reviews Active/Inactive SC Tasks Detailed: Step Dimensions

More information

H:\forms\handouts\bldg049 1 of 11 Revised Mar 2/15/dh

H:\forms\handouts\bldg049 1 of 11 Revised Mar 2/15/dh Accessory Apartment Construction Guide For Single Detached Dwelling and Semi-Detached Dwellings that have been in existence for at least five (5) years Notes: Buildings that are less than five (5) years

More information

New Ontario Building Code Highlights

New Ontario Building Code Highlights New Ontario Building Code Highlights Part 9 This summary highlights items that are believed to be significant changes to the 2012 OBC and is not intended to include all changes made within this or other

More information

4 Installation Requirements

4 Installation Requirements 4 Installation Requirements 9 4.1 Code Reference The authority having jurisdiction should be referenced to determine what law, ordinance or code shall apply in the use of flexible duct. Ducts conforming

More information

Composite Panel Firewall Systems

Composite Panel Firewall Systems Composite Panel Firewall Systems part of the Protecting more than your business Insulated mineral fibre panels have excellent thermal and acoustic properties, ideal for factory and office partition walls.

More information

Fire Safety In High Rise Building

Fire Safety In High Rise Building Fire Safety In High Rise Building CLASSIFICATION OF BUILDINGS AS PER NATIONAL BUILDING CODE 1. GROUPING. Group A - Residential : Lodgings, Dwellings, Dormitories, Flats, Hotels. Group B Group C - Educational

More information

Loss Prevention Standard

Loss Prevention Standard Loss Prevention Standard : ISSUE 3.0 Requirements for the LPCB Approval and Listing of Companies Undertaking the Maintenance and Repair of Doorsets, Shutters, and Active Smoke/Fire Barriers This standard

More information

I.S. 3218 :2013 Fire Detection & Alarm Systems

I.S. 3218 :2013 Fire Detection & Alarm Systems I.S. 3218 :2013 Fire Detection & Alarm Systems Overview of significant changes 26 th March 2014 FPS Ltd Today s Programme Commencement Transition Competence & Qualifications System Certification System

More information

Required Certification Documentation. Contractor's installation certification for range hood fire suppression systems.

Required Certification Documentation. Contractor's installation certification for range hood fire suppression systems. OFFICE OF UNIVERSIT BUILDING OFFICIAL PROJECT/CONSTRUCTION MAGER: Sample Manager Required Aboveground only Required Certification Documentation Contractor s material and test certifications for both above

More information

780 CMR: MASSACHUSETTS AMENDMENTS TO THE INTERNATIONAL EXISTING BUILDING CODE 2009

780 CMR: MASSACHUSETTS AMENDMENTS TO THE INTERNATIONAL EXISTING BUILDING CODE 2009 780 CMR: MASSACHUSETTS AMENDMENTS TO THE INTERNATIONAL EXISTING BUILDING CODE 2009 CHAPTER 34: EXISTING STRUCTURES 3401.1 Replace as follows: 3401.1 Scope. Chapter 34 of the International Building Code

More information

The risk assessment of fire damper installations

The risk assessment of fire damper installations The risk assessment of fire damper installations June 2010 Paul White OVERVIEW OVERVIEW The purpose of this presentation is to highlight that fire dampers form a key part of the passive fire protection

More information

Requirements to Obtain a Building Permit for a NEW HOME. 1. Completed application form. (Boxes A, B, C, D & E if applicable F and I)

Requirements to Obtain a Building Permit for a NEW HOME. 1. Completed application form. (Boxes A, B, C, D & E if applicable F and I) Requirements to Obtain a Building Permit for a NEW HOME 1. Completed application form. (Boxes A, B, C, D & E if applicable F and I) 2. Proof of Ownership (New Development Only, Copy of Deed or Tax Bill)

More information

A ROAD MAP FOR YOUR CODE, SMOKE BARRIER & SMOKE PARTITION REQUIREMENTS

A ROAD MAP FOR YOUR CODE, SMOKE BARRIER & SMOKE PARTITION REQUIREMENTS A ROAD MAP FOR YOUR CODE, SMOKE BARRIER & SMOKE PARTITION REQUIREMENTS International Code Council National Fire Protection Association Underwriters Laboratories Inc. 5203 Leesburg Pike, Suite 600 1 Batterymarch

More information

Ontario Fire Code SECTION 5.13 DIP TANKS. Illustrated Commentary. Office of the Ontario Fire Marshal

Ontario Fire Code SECTION 5.13 DIP TANKS. Illustrated Commentary. Office of the Ontario Fire Marshal Ontario Fire Code SECTION 5.13 DIP TANKS Illustrated Commentary Office of the Ontario Fire Marshal Dip Tanks Illustrated Commentary 1 5.13.1. Location 5.13.1.1. Dip tank operations involving flammable

More information

Miami Beach Building Department

Miami Beach Building Department Miami Beach Building Department Documents Required To Be Signed and Sealed By A Design Professional (FLORIDA BUILDING CODE) GENERAL CONTRACTOR: If the plans are prepared by a design professional that is

More information

Building Control Guidance Note

Building Control Guidance Note Issued 01/10/10 Rev Page 1 A new updated version of Approved Document B comes into force from the 6 th April 2007. This revised guidance is split into two separate documents:- Volume 1 Dwelling Houses

More information

Exterior Elevated Elements Inspection Guidelines

Exterior Elevated Elements Inspection Guidelines Exterior Elevated Elements Inspection Guidelines Planning and Development 1. Guideline Purpose These guidelines are intended to assist practicing professionals in complying with Berkeley Municipal Code

More information

Summary of Preliminary Assessment on Structural, Fire and Electrical Safety

Summary of Preliminary Assessment on Structural, Fire and Electrical Safety Name of the Factory Address of the Factory Present Status of the Factory Structural Assessment Conducted by : Galaxy Stitch Ltd. : BSCIC Industrial Estate, Plot no. A102, Tongi Gazipur Bangladesh : Under

More information

Supplementary Report: 2015 Heads and Beds Levy on Institutions

Supplementary Report: 2015 Heads and Beds Levy on Institutions STAFF REPORT INFORMATION ONLY Supplementary Report: 2015 Heads and Beds Levy on Institutions Date: July 6, 2015 To: From: Wards: Reference Number: City Council Acting Treasurer All P:\2015\Internal Services\rev\cc15017rev

More information

April 2, 2007 TO: BUILDING CODE USERS

April 2, 2007 TO: BUILDING CODE USERS Ministry of MinistPre des Municipal Affairs Affaires municipales and Housing et du Logement Building and Development Branch Direction du bâtiment et de l'aménagement 777 Bay Street, 2 nd Floor 777, rue

More information

Please read carefully before filling in this certificate of insurance (COI):

Please read carefully before filling in this certificate of insurance (COI): Certificate of Insurance Errors and Omissions or Professional Liability for Design Firms Seeking Registration, Renewal or Reinstatement in Accordance With the Building Code Ontario Ministry of Municipal

More information

Name Of Occupancy Date. Yes No Describe

Name Of Occupancy Date. Yes No Describe FIRE PREVENTION INSPECTION CHECKLIST For Class A Occupancy (For Assembly Buildings, Bars, Restaurants, Gyms, Churches, Arenas, Theatres or wherever people gather) Name Of Occupancy Date Physical Address

More information

Understanding Firewall Basics

Understanding Firewall Basics PDHonline Course G125 (1 PDH) Understanding Firewall Basics Instructor: D. Matthew Stuart, P.E., S.E., F.ASCE, F.SEI, SECB, MgtEng 2013 PDH Online PDH Center 5272 Meadow Estates Drive Fairfax, VA 22030-6658

More information

This handout is a guide only and does not contain all of the requirements of the Minnesota State Building Code or city ordinances.

This handout is a guide only and does not contain all of the requirements of the Minnesota State Building Code or city ordinances. Basement Finishing Guide Community Development Department Building Inspections Division 5200 85 th Avenue North / Brooklyn Park, MN 55443 Phone: (763) 488-6379 / Fax: (763) 493-8171 6/15 www.brooklynpark.org

More information

Ch. 58 DIVISION D-O 34 CHAPTER 58. DIVISION D-O ORDINARY COMMERCIAL, INDUSTRIAL, OFFICE OCCUPANCY GROUP CONSTRUCTION TYPE MAXIMUM STORY HEIGHT

Ch. 58 DIVISION D-O 34 CHAPTER 58. DIVISION D-O ORDINARY COMMERCIAL, INDUSTRIAL, OFFICE OCCUPANCY GROUP CONSTRUCTION TYPE MAXIMUM STORY HEIGHT Ch. 58 DIVISION D-O 34 CHAPTER 58. DIVISION D-O ORDINARY COMMERCIAL, INDUSTRIAL, OFFICE Sec. 58.1. Division D-O occupancies. 58.2. Separation and mixed occupancy. OCCUPANCY GROUP CONSTRUCTION TYPE MAXIMUM

More information

Area of Rescue Assistance Communication System ADA Code Applicable excerpts:

Area of Rescue Assistance Communication System ADA Code Applicable excerpts: Area of Rescue Assistance Communication System ADA Code Applicable excerpts: CONTENTS (Guidelines and Definitions) Page 1 Area of Rescue Assistance Requirements Page 2 Emergency Communication Equipment

More information

Vestibule Case Study. Vestibule Requirement Intent [2003 IECC, 2006 IECC, 2003 IBC, 2006 IBC, 90.1-2001, 90.1-2004]

Vestibule Case Study. Vestibule Requirement Intent [2003 IECC, 2006 IECC, 2003 IBC, 2006 IBC, 90.1-2001, 90.1-2004] Vestibule Case Study [2003 IECC, 2006 IECC, 2003 IBC, 2006 IBC, 90.1-2001, 90.1-2004] Vestibule Requirement Intent Page 1 of 14 The primary intent behind the requirement for a vestibule is to reduce infiltration

More information

SARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS

SARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS SARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS I. APPLICATION AND DEFINITIONS 1.01 Authorization for Standards 1.02 Application of Standards 1.03 Definitions

More information

1997 Uniform Administrative Code Amendment for Earthen Material and Straw Bale Structures Tucson/Pima County, Arizona

1997 Uniform Administrative Code Amendment for Earthen Material and Straw Bale Structures Tucson/Pima County, Arizona for Earthen Material and Straw Bale Structures SECTION 70 - GENERAL "APPENDIX CHAPTER 7 - EARTHEN MATERIAL STRUCTURES 70. Purpose. The purpose of this chapter is to establish minimum standards of safety

More information

Decree of the Ministry of the Environment on fire safety of buildings

Decree of the Ministry of the Environment on fire safety of buildings E1 THE NATIONAL BUILDING CODE OF FINLAND 1 Fire safety of buildings Regulations and guidelines 2002 Decree of the Ministry of the Environment on fire safety of buildings Adopted in Helsinki, 12 March 2002

More information

General Fire Code Requirements Within Commercial Tenant Spaces

General Fire Code Requirements Within Commercial Tenant Spaces FIRE DEPARTMENT in cooperation with Scope: General Fire Code Requirements Within Commercial Tenant Spaces This handout is designed to assist owners, architects, contractors and others in understanding

More information

NFPA 101 SAF-FIR PUBLIC COMMENTS

NFPA 101 SAF-FIR PUBLIC COMMENTS Page 50 of 195 8.2.3.1.2 ] Public Comment No. 82-NFPA 101-2013 [ New Section after 8.2.3.1.3* The fire resistance rating of an element or assembly determined by tests conducted in accordance with NFPA

More information

SUPPLEMENTAL TERMS AND CONDITIONS TO STATE FORM SC-5.1TC ARCHITECT/ENGINEER AGREEMENT TERMS AND CONDITIONS DESIGN/BID/BUILD

SUPPLEMENTAL TERMS AND CONDITIONS TO STATE FORM SC-5.1TC ARCHITECT/ENGINEER AGREEMENT TERMS AND CONDITIONS DESIGN/BID/BUILD ATTACHMENT 2 UNIVERSITY OF COLORADO BOULDER SUPPLEMENTAL TERMS AND CONDITIONS TO STATE FORM SC-5.1TC ARCHITECT/ENGINEER AGREEMENT TERMS AND CONDITIONS DESIGN/BID/BUILD Table of Contents, Exhibits Delete

More information

Introduction. CE marked construction products

Introduction. CE marked construction products Introduction This Technical Booklet has been prepared by the Department of Finance and Personnel and provides for certain methods and standards of building which, if followed, will satisfy the requirements

More information

Chapter 5 The creation of the corporation

Chapter 5 The creation of the corporation Chapter 5 The creation of the corporation 1. Introduction This chapter is intended to provide a basic overview of the major issues facing solicitors retained to incorporate a business. The focus will be

More information

Ontario Association of Fire Chiefs Position Paper Residential Fire Sprinklers

Ontario Association of Fire Chiefs Position Paper Residential Fire Sprinklers Ontario Association of Fire Chiefs Position Paper Residential Fire Sprinklers The Ontario Association of Fire Chiefs (OAFC) supports changes to the Ontario Building Code to require that all new residential

More information

Town House 11265 Center Highway North Huntingdon, PA 15642

Town House 11265 Center Highway North Huntingdon, PA 15642 APPENDIX C SPECIFICATIONS FOR THE CONSTRUCTION OF BUILDING LATERAL SANITARY SEWERS DECEMBER 2004, INCLUDING AMENDMENTS ADOPTED ON FEBRUARY 6, 2008 AND APRIL 2, 2008; EFFECTIVE ON MAY 1, 2008 Town House

More information

FSD35, FSD36 AND FSD37 COMBINATION FIRE and SMOKE DAMPERS

FSD35, FSD36 AND FSD37 COMBINATION FIRE and SMOKE DAMPERS 3900 Dr. Greaves Rd. Kansas City, MO 64030 (816) 761-7476 FAX (816) 765-8955 INSTALLATION INSTRUCTIONS FSD35, FSD36 AND FSD37 COMBINATION FIRE and SMOKE DAMPERS 11/2 HOUR UL555 RATED UL555S LEAKAGE RATED

More information

527 CMR: BOARD OF FIRE PREVENTION REGULATIONS

527 CMR: BOARD OF FIRE PREVENTION REGULATIONS 527 CMR 31.00: CARBON MONOXIDE ALARMS Section 31.01: Purpose and Scope 31.02: Definitions 31.03: General Installation Provisions 31.04: Specific Installation Provisions 31.05: Carbon Monoxide Protection:

More information

13 PROPOSED REGION OF YORK EMERGENCY MANAGEMENT BY-LAW

13 PROPOSED REGION OF YORK EMERGENCY MANAGEMENT BY-LAW 13 PROPOSED REGION OF YORK EMERGENCY MANAGEMENT BY-LAW The Finance and Administration Committee recommends the adoption of the recommendations contained in the following report, November 23, 2004, from

More information

REASONS FOR DECISION OF THE TORONTO LICENSING TRIBUNAL

REASONS FOR DECISION OF THE TORONTO LICENSING TRIBUNAL REASONS FOR DECISION OF THE TORONTO LICENSING TRIBUNAL Date of Hearing: Panel: Re: David Peacock, Chair; Ken Chan and Diane Hall, Members 2254367 Ontario Inc. O/A Toronto Wide Waterproofing Michael Patrick

More information

How To Make A House Safe

How To Make A House Safe 1 RESIDENTIAL Screen Enclosures Orange County Residential Code Compliance Alternative design method for screen enclosures R301.2.1.1.3 PLAN REVIEW Engineered plans must state that the Alternative Design

More information

TORONTO MUNICIPAL CODE CHAPTER 470, FIRE SAFETY BOXES. Chapter 470 FIRE SAFETY BOXES

TORONTO MUNICIPAL CODE CHAPTER 470, FIRE SAFETY BOXES. Chapter 470 FIRE SAFETY BOXES Chapter 470 FIRE SAFETY BOXES 470-1. Interpretation. 470-2. Administration. 470-3. Fire safety box and lock box. 470-4. One fire safety box and one lock box. 470-5. Location. 470-6. Contents. 470-7. Service

More information

SMOKE ALARM PROGRAM AND HOME ESCAPE PROGRAM

SMOKE ALARM PROGRAM AND HOME ESCAPE PROGRAM CORPORATION OF THE TOWNSHIP OF HOWICK SCHEDULE A BY-LAW NO. 38-2007 SMOKE ALARM PROGRAM AND HOME ESCAPE PROGRAM The Township of Howick Smoke Alarm and Home Escape Planning Program SECTION INDEX 1. Introduction

More information

Building Permit Application

Building Permit Application Building Permit Application CBO: Don Reed / Inspector: Scott Richardson -All applications must be filled out in full -Residential applications will be issued or denied within 10 working days -Multi-residential

More information

Class Environmental Assessment Process Guide

Class Environmental Assessment Process Guide Class Environmental Assessment Process Guide The Environmental Assessment (EA) process is a planning tool used to identify the possible adverse effects of proposed infrastructure projects on the environment.

More information

Australian/New Zealand Standard

Australian/New Zealand Standard Australian/New Zealand Standard The use of ventilation and air conditioning in buildings - Part 1: Fire and smoke control in buildings UPDATED AS/NZS 1668.1:2015 What is the scope of this Standard? The

More information

DuPont Tyvek Commercial Air Barrier Assemblies Exceed Air Barrier Association of America, ASHRAE 90.1

DuPont Tyvek Commercial Air Barrier Assemblies Exceed Air Barrier Association of America, ASHRAE 90.1 Building Science Bulletin DuPont Tyvek Commercial Air Barrier Assemblies Exceed Air Barrier Association of America, ASHRAE 90.1 and IECC Air Leakage Requirements When Tested in Accordance with ASTM E2357

More information

DESIGN AND INSTALLATION OF RESIDENTIAL FLEXIBLE DUCTWORK SYSTEMS

DESIGN AND INSTALLATION OF RESIDENTIAL FLEXIBLE DUCTWORK SYSTEMS DESIGN AND INSTALLATION OF RESIDENTIAL FLEXIBLE DUCTWORK SYSTEMS A. SCOPE 1. This information is intended to assist contractors, installers and code officials in the proper design and installation of flexible

More information

CITY CLERK. Other Items Considered by the Community Council

CITY CLERK. Other Items Considered by the Community Council CITY CLERK Consolidated Clause in Report 4, which was received, for information, by City Council on May 23, 24 and 25, 2006. 23 Other Items Considered by the Community Council (The Community Council is

More information

Fire Safety Requirements for Child Care Centre

Fire Safety Requirements for Child Care Centre Fire Safety Requirements for Child Care Centre A. Restrictions on Location Child care centre shall not be located : - (a) (b) in any premises designed for residential use; in any industrial building, warehouses,

More information

Act on the Supervision of Financial Institutions etc. (Financial Supervision Act)

Act on the Supervision of Financial Institutions etc. (Financial Supervision Act) FINANSTILSYNET Norway Translation update January 2013 This translation is for information purposes only. Legal authenticity remains with the official Norwegian version as published in Norsk Lovtidend.

More information

Arapahoe County Residential Water Heater Installation and Inspection Guide

Arapahoe County Residential Water Heater Installation and Inspection Guide Arapahoe County Residential Water Heater Installation and Inspection Guide The attached handout is designed to be a general permit submittal and inspection guide covering most installation instances, however

More information

Conrex Steel Ltd. ite468 Rideau Street. Kingston, Ontario K7K 3B1. 468 Rideau Street

Conrex Steel Ltd. ite468 Rideau Street. Kingston, Ontario K7K 3B1. 468 Rideau Street Ministry of the Environment and Climate Change Ministère de l Environnement et de l Action en matière de changement climatique ENVIRONMENTAL COMPLIANCE APPROVAL NUMBER 9418-A9CSB9 Issue Date: May 17, 2016

More information

NOTIFICATION AND FEDERAL EMPLOYEE ANTIDISCRIMINATION AND RETALIATION ACT OF 2002

NOTIFICATION AND FEDERAL EMPLOYEE ANTIDISCRIMINATION AND RETALIATION ACT OF 2002 NOTIFICATION AND FEDERAL EMPLOYEE ANTIDISCRIMINATION AND RETALIATION ACT OF 2002 VerDate 11-MAY-2000 09:01 May 20, 2002 Jkt 099139 PO 00174 Frm 00001 Fmt 6579 Sfmt 6579 E:\PUBLAW\PUBL174.107 APPS10 PsN:

More information

Law No. (9) of 2012 Amending some provisions of Law No. (13) of 1997 Concerning the Civil Defense

Law No. (9) of 2012 Amending some provisions of Law No. (13) of 1997 Concerning the Civil Defense Law No. (9) of 2012 Amending some provisions of Law No. (13) of 1997 Concerning the Civil Defense We, Hamad Bin Khalifa Al-Thani, Emir of the State of Qatar Having pursued the Constitution, And the Law

More information