Variable Speed AC Motor Drives SM-Basic Installation and Operation Manual
|
|
|
- Bartholomew Mills
- 9 years ago
- Views:
Transcription
1 ELECTRIC MOTORS, GEARMOTORS AND DRIVES Variable Speed AC Motor Drives SM-Basic Installation and Operation Manual
2 We, EC Declaration of Conformity In accordance with EN45014:1998 Leeson Electric Corporation 2100 Washington Street Grafton, Wisconsin USA declare under sole responsibility that the following equipment to which this declaration relates, meets the essential health and safety requirements and is in conformity with the relevant sections of the applicable EC standards and other normative documents. If changes are made to the product that is covered by this declaration of conformity, the declaration of conformity is no longer valid. Equipment Type: AC Variable Frequency Motor Drives: EC Directives: By virtue of this conformity, the products are deemed to comply with the provisions of the Council of European Communities Directives listed, provided installations are carried out in accordance with the manufacturer s instructions. 1) Low Voltage Directive 73/23/EEC as amended 93/68/EEC 2) Electromagnetic Compatibility Directive 89/336/EEC as amended 92/31/EEC Harmonized Standards Used: EN *: Electromagnetic Compatibility Generic Emission Standard; Part 2: Industrial Environment EN *: Electromagnetic Compatibility Generic Emission Standard; Part 2: Industrial Environment EN50178; 1998 Electronic Equipment for use in Power Installations * with suitable filters that are properly installed Authorized Representative: Ms. Elisa Basso Leeson Electric International Phone: (+39) Via Caduti Di Sabbiuno 11/D-E Fax: (+39) Anzola Emilia Bologna Italy Dated this 2 st day of May Peter F. Hennig Senior Design Engineer Revision: 00, 5/02/2000
3 Manual Number: IMSN01 TABLE OF CONTENTS 1.0 GENERAL SM-Basic DIMENSIONS SM-Basic MODEL DESIGNATION CODE SM-Basic SPECIFICATIONS SM-Basic RATINGS INSTALLATION INPUT AC POWER REQUIREMENTS POWER WIRING SM-Basic POWER WIRING DIAGRAM CONTROL WIRING SM-Basic CONTROL WIRING DIAGRAMS INITIAL POWER UP AND MOTOR ROTATION PROGRAMMING THE SM Basic DRIVE PARAMETER MENU DESCRIPTION OF PARAMETERS TROUBLESHOOTING SM-Basic DISPLAY MESSAGES USER SETTING RECORD... 41
4 THE SM-Basic SUB-MICRO DRIVE INPUT POWER TERMINALS GROUND LUG ELECTRONIC PROGRAMMING MODULE (EPM) 2-DIGIT LED DISPLAY PROGRAMMING BUTTONS CONTROL TERMINAL STRIP OUTPUT (MOTOR) TERMINALS
5 1.0 GENERAL 1.1 PRODUCTS COVERED IN THIS MANUAL This manual covers the Leeson Electric Corporation SM-Basic Series Variable Frequency Drive. 1.2 PRODUCT CHANGES Leeson Electric Corporation reserves the right to discontinue or make modifications to the design of its products without prior notice, and holds no obligation to make modifications to products sold previously. Leeson Electric Corporation also holds no liability for losses of any kind which may result from this action. 1.3 WARRANTY Leeson Electric Corporation warrants the SM-Basic AC motor control to be free of defects in material and workmanship for a period of twelve months from the date of sale to the user, or eighteen months from the date of shipment, which ever occurs first. If an SM-Basic motor control, under normal use, becomes defective within the stated warranty time period, contact Leeson Electric's Service Department for instructions on obtaining a warranty replacement unit. Leeson Electric Corporation reserves the right to make the final determination as to the validity of a warranty claim, and sole obligation is to repair or replace only components which have been rendered defective due to faulty material or workmanship. No warranty claim will be accepted for components which have been damaged due to mishandling, improper installation, unauthorized repair and/or alteration of the product, operation in excess of design specifications or other misuse, or improper maintenance. Leeson Electric Corporation makes no warranty that its products are compatible with any other equipment, or to any specific application, to which they may be applied and shall not be held liable for any other consequential damage or injury arising from the use of its products. This warranty is in lieu of all other warranties, expressed or implied. No other person, firm or corporation is authorized to assume, for Leeson Electric Corporation, any other liability in connection with the demonstration or sale of its products. 1.4 RECEIVING Inspect all cartons for damage which may have occurred during shipping. Carefully unpack equipment and inspect thoroughly for damage or shortage. Report any damage to carrier and/or shortages to supplier. All major components and connections should be examined for damage and tightness, with special attention given to PC boards, plugs, knobs and switches. 1.5 CUSTOMER MODIFICATION Leeson Electric Corporation, its sales representatives and distributors, welcome the opportunity to assist our customers in applying our products. Many customizing options are available to aid in this function. Leeson Electric Corporation cannot assume responsibility for any modifications not authorized by its engineering department. 1
6 2.0 SM-Basic DIMENSIONS 0.38" H R W 0.38" 0.18" D 0.69" P 0.19" Dia. Slot Mounting Tab Detail HP INPUT VOLTAGE MODEL H W D P R /208/ / /208/ / / /208/ / / /208/ / / / / / /
7 3.0 SM-Basic MODEL DESIGNATION CODE 4.0 SM-Basic SPECIFICATIONS Storage Temperature -20 to 70 C Ambient Operating Temperature 0 to 50 C (up to 6 khz carrier, derate above 6 khz) Ambient Humidity < 95% (non-condensing) Altitude 3300 ft (1000 m) above sea level (without derating) Input Line Voltages 120/208/240 Vac single phase, 208/240 Vac three phase Input Voltage Tolerance +10%, -15% Input Frequency Tolerance 48 to 62 Hz Output Wave Form Sine Coded PWM Output Frequency 0-99 Hz Carrier Frequency 4 khz to 10 khz Service Factor 1.00 (up to 6 khz carrier, derate above 6 khz) Efficiency Up to 98% Power Factor (displacement) 0.96 or better Overload Current Capacity 150% for 60 seconds, 180% for 30 seconds Speed Reference Follower Speed Potentiometer, 0-10 VDC (must be isolated) 1 Power Supply for Auxiliary Relay 50 ma at 12 VDC Digital Output Circuit rated 50 ma and 30 VDC max (to drive auxiliary relay) 1 1 WARNING: Control terminals are not isolated from line voltage! Do not touch! 3
8 5.0 SM-Basic RATINGS MODEL NUMBER INPUT OUTPUT MODEL (120/208/240 Vac, Hz) (0-200/230 Vac) HEAT LOSS FOR MOTORS RATED HP kw INPUT PHASE CURRENT (AMPS) (NOTE 1) POWER (kva) CURRENT (AMPS) (NOTE 1) WATTS (NOTE 3) /3.5/ /1.6/ /5.3/ /2.5/ /9.1/ /4.6/ /12.3/ /6.2/ NOTE 1: The first current rating listed is for 120 Vac input, the second current rating is for 208 Vac input, and the third current rating is for 240 Vac input. 120 Vac input yields 230 Vac output. MODEL NUMBER INPUT OUTPUT MODEL (208/240 Vac, Hz) (0-200/230 Vac) HEAT LOSS FOR MOTORS RATED HP kw INPUT PHASE CURRENT (AMPS) (NOTE 1) POWER (kva) CURRENT (AMPS) (NOTE 1) WATTS (NOTE 3) / / / / / / / / / / / / / / / / / NOTE 1: Models are rated for use with single and three phase input. NOTE 2: The higher current rating is for 208 Vac input and the lower current rating is for 240 Vac input. NOTE 3: Values are worst-case (not typical) for 6 khz carrier frequency at full speed and full load. 4
9 6.0 INSTALLATION NOTE! SM-Basic drives are intended for inclusion within other equipment, by professional electrical installers. They are not intended for stand-alone operation. WARNING! DRIVES MUST NOT BE INSTALLED WHERE SUBJECTED TO ADVERSE ENVIRONMENTAL CONDITIONS SUCH AS: COMBUSTIBLE, OILY, OR HAZARDOUS VAPORS OR DUST; EXCESSIVE MOISTURE OR DIRT; VIBRATION; EXCESSIVE AMBIENT TEMPERATURES. CONSULT AC TECHNOLOGY FOR MORE INFORMATION ON THE SUITABILITY OF A DRIVE TO A PARTICULAR ENVIRONMENT. WARNING! Hazard of electrical shock! The SM-Basic control terminals are not isolated from line voltage! Line voltage is present between the control terminals and ground. Do not touch! Disconnect input power and wait three minutes before making connections to the control terminals. Devices (such as switches, pushbuttons, potentiometers, relays, etc) and wiring connected to the control terminals are hot to ground and must have an insulation rating of at least 240 Vac or a dielectric rating of at least 1500 volts to prevent damage to equipment and/or injury to personnel. SM-Basic models are suitable for UL pollution degree 2 environment only, and MUST be installed in an electrical enclosure which will provide complete mechanical protection and will maintain the internal temperature within the drive s ambient operating temperature rating. All drive models MUST be mounted in a vertical position for proper heatsink cooling. Maintain a minimum spacing around the drive of at least one inch on each side and two inches on the top and bottom. Allow more spacing if the drive is mounted next to other heat-producing equipment. Do not mount drives above other drives or heat producing equipment. Fans or blowers should be used to insure proper cooling in tight quarters. In order to properly size an enclosure, the heat generated by the drive(s) must be known. Refer to the HEAT LOSS column in Section SM-Basic RATINGS. An enclosure manufacturer can then determine the required enclosure size based on the total heat generated inside the enclosure (from the drive(s) and other heat sources), the maximum allowable temperature inside the enclosure, the maximum ambient temperature outside the enclosure, and the enclosure properties. The SM-Basic Series is UL approved for solid state motor overload protection. Therefore, a separate thermal overload relay is not required for single motor applications. 5
10 6.1 INSTALLATION AFTER A LONG PERIOD OF STORAGE WARNING! Severe damage to the drive can result if it is operated after a long period of storage or inactivity without reforming the DC bus capacitors! If input power has not been applied to the drive for a period of time exceeding three years (due to storage, etc), the electrolytic DC bus capacitors within the drive can change internally, resulting in excessive leakage current. This can result in premature failure of the capacitors if the drive is operated after such a long period of inactivity or storage. In order to reform the capacitors and prepare the drive for operation after a long period of inactivity, apply input power to the drive for 8 hours prior to actually operating the motor. 6.2 EXPLOSION PROOF APPLICATIONS Explosion proof motors that are not rated for inverter use lose their certification when used for variable speed. Due to the many areas of liability that may be encountered when dealing with these applications, the following statement of policy applies: Leeson Electric Corporation inverter products are sold with no warranty of fitness for a particular purpose or warranty of suitability for use with explosion proof motors. Leeson Electric Corporation accepts no responsibility for any direct, incidental or consequential loss, cost, or damage that may arise through the use of its AC inverter products in these applications. The purchaser expressly agrees to assume all risk of any loss, cost, or damage that may arise from such application. Leeson Electric Corporation or Leeson Electric Corporation s engineering department will not knowingly approve applications involving explosion proof motors. 6
11 7.0 INPUT AC POWER REQUIREMENTS WARNING! Hazard of electrical shock! Capacitors retain charge after power is removed. Disconnect incoming power and wait until the voltage between terminals B+ and B- is 0 VDC before servicing the drive. The input voltage must match the nameplate voltage rating of the drive. Voltage fluctuation must not vary by greater than 10% overvoltage or 15% undervoltage. NOTE: Drives with dual input voltage ratings must be programmed for the proper supply voltage (refer to Parameter 01 - LINE VOLTAGE SELECTION in Section DESCRIPTION OF PARAMETERS). The drive is suitable for use on a circuit capable of delivering not more than 5,000 RMS symmetrical amperes at the drive s rated voltage. Three phase voltage imbalance must be less than 2.0% phase to phase. Excessive phase to phase imbalance can cause severe damage to the drive. Motor voltage should match line voltage in normal applications. The drive s maximum output voltage will equal the input voltage. Use extreme caution when using a motor with a voltage rating which is different from the input line voltage. 7.1 INPUT VOLTAGE RATINGS SM-Basic Series drives are rated for 120/208/240 Vac, single phase, Hz input. The drive will function with input voltage of 120 Vac (+10%, -15%), at 48 to 60 Hz, or with input voltage of 208 to 240 Vac (+ 10%, - 15%), at 48 to 62 Hz. SM-Basic Series drives are rated for 208/240 Vac, single phase, Hz input. The drive will function with input voltages of 208 to 240 Vac (+10%, -15%), at 48 to 62 Hz. SM-Basic Series drives are rated for 208/240 Vac, three phase, Hz input. The drive will function with input voltages of 208 to 240 Vac (+ 10%, - 15%), at 48 to 62 Hz. NOTE: Parameter 01 - LINE VOLTAGE SELECTION must be programmed according to the applied input voltage. See Section DESCRIPTION OF PARAMETERS. 7.2 INPUT FUSING AND DISCONNECT REQUIREMENTS A circuit breaker or a disconnect switch with fuses must be provided in accordance with the National Electric Code (NEC) and all local codes. The SM-Basic drive is capable of withstanding up to 150% current overload for 60 seconds. Select a fuse or magnetic trip circuit breaker rated at 1.5 times the input current rating of the drive (the minimum fuse size should be 10 amps, regardless of input current rating). Refer to Section SM-Basic RATINGS. 7
12 Minimum voltage rating of the protection device should be 250 Vac for 120/208/240 Vac and 208/ 240 Vac rated drives. UL Class CC fast-acting, current limiting type fuses should be used when input fusing is required. Select fuses with low I 2 T values, rated at 200,000 AIC. Recommended fuses are Bussman KTK-R. Similar fuses with equivalent ratings by other manufacturers may also be acceptable. 8.0 POWER WIRING WARNING! Hazard of electrical shock! Capacitors retain charge after power is removed. Disconnect incoming power and wait until the voltage between terminals B+ and B- is 0 VDC before servicing the drive. Note drive input and output current ratings and check applicable electrical codes for required wire type and size, grounding requirements, over-current protection, and incoming power disconnect, before wiring the drive. Size conservatively to minimize voltage drop. Strip off 0.20 to 0.25 inches of insulation for input power, output power, and DC Bus wiring. The input power, output power, and DC Bus terminals must be tightened to a torque of 4.0 to 4.5 lb-in. Input fusing and a power disconnect switch or contactor MUST be wired in series with terminals L1, L2, and L3 for three phase input models. For 208/240 Vac single phase input models, use terminals L1 and L2. For 120 Vac single phase input models, use terminals L1 and N. This disconnect must be used to power down the drive when servicing, or when the drive is not to be operated for a long period of time, but should not be used to start and stop the motor. Repetitive cycling of a disconnect or input contactor (more than once every two minutes) may cause damage to the drive. 8.1 WIRING FOR SINGLE PHASE OR THREE PHASE INPUT If the drive is rated for 120/208/240 Vac single phase input, wire the input to terminals L1 and N for 120 Vac voltage, or wire to terminals L1 and L2 (do not wire to N) for 208/240 Vac input voltage. Refer to Section SM-Basic POWER WIRING DIAGRAM. If the drive is rated for 208/240 Vac single phase input, wire the input to terminals L1 and L2. If the drive is rated for three phase input, wire the input to terminals L1, L2, and L3. All three power output wires, from terminals T1, T2, and T3 to the motor, must be kept tightly bundled and run in a separate conduit away from all other power and control wiring. Do not install contactors or disconnects between the drive and motor without consulting Leeson Electric Corporation for more information. 8
13 9.0 SM-Basic POWER WIRING DIAGRAM THREE PHASE INPUT (where applicable) 120 Vac SINGLE PHASE INPUT (where applicable) L1 L2 L3 L1 L2 N 208/240 Vac SINGLE PHASE INPUT (where applicable) OUTPUT (ALL) T1 T2 T3 B- B+ L1 L2 L3* 3 PHASE AC MOTOR + DC BUS VOLTAGE WARNING! Do not connect incoming AC power to output terminals T1, T2, or T3. Severe damage to the drive will result. NOTES: 1. WIRE AND GROUND IN ACCORDANCE WITH NEC OR CEC, AND ALL APPLICABLE LOCAL CODES. 2. Motor wires MUST be run in a separate steel conduit away from control wiring and incoming AC power wiring. 3. Do not install contactors between the drive and the motor without consulting Leeson Electric Corporation for more information. Failure to do so may result in drive damage. 4. Use only UL and CSA listed and approved wire. 5. Minimum wire voltage ratings: 300 V for 120, 208 and 240 Vac systems. 6. Wire gauge must be based on a minimum of 125% of the rated input/output current of the drive, and a minimum 75 C insulation rating. Use copper wire only. 7. Strip off 0.20 to 0.25 inches of insulation for input power, output power, and DC Bus wiring. 9
14 10.0 CONTROL WIRING WARNING! Hazard of electrical shock! The SM-Basic control terminals are not isolated from line voltage! Line voltage is present between the control terminals and ground. Do not touch! Disconnect input power and wait three minutes before making connections to the control terminals. Devices (such as switches, pushbuttons, potentiometers, relays, etc) and wiring connected to the control terminals are hot to ground and must have an insulation rating of at least 240 Vac or a dielectric rating of at least 1500 volts to prevent damage to equipment and/or injury to personnel CONTROL WIRING VS. POWER WIRING External control wiring MUST be run in a separate conduit away from all other input and output power wiring. If control wiring is not kept separate from power wiring, electrical noise may be generated on the control wiring that will cause erratic drive behavior. Use twisted wires or shielded cable rated for 300 VDC minimum (do not ground the shield) SURGE SUPPRESION ON RELAYS Current and voltage surges and spikes in the coils of contactors, relays, and solenoids, near or connected to the drive, can cause erratic drive operation. Snubbers should be used on any coils associated with the drive. For AC loads, snubbers should consist of a resistor and a capacitor in series across the coil. For DC loads, a free-wheeling or flyback diode should be placed across the coil START/STOP CONTROL There are various control schemes that allow for 2-wire and 3-wire Start/Stop circuits. Refer to the wiring diagrams in Section SM-Basic CONTROL WIRING DIAGRAMS SPEED REFERENCE SIGNALS SPEED POT Connect the wiper to terminal TB-5, and connect the high and low end leads to terminals TB-6 and TB-3, respectively. The speed pot can be 5kΩ up to 10kΩ VDC Wire the positive to terminal TB-5 and the negative to terminal TB-3. The 0-10 VDC signal must be isolated, as the control terminals are at line voltage potential. DO NOT connect the low side of the speed pot or 0-10 VDC signal to ground. 10
15 10.5 SPEED REFERENCE SELECTION If a speed pot is to be used to control the drive speed, terminal TB-13A, 13B, or 13C (Parameter 10, 11, or 12) may be programmed as the input select for the speed pot. When that TB-13 terminal is then closed to TB-11, the drive will follow the speed pot input. If the speed pot is not selected on the terminal strip using TB-13A, 13B, or 13C, speed control will default to STANDARD mode, which is governed by the setting of Parameter 05 - STANDARD SPEED SOURCE. The STANDARD SPEED SOURCE can be the s and t buttons on the front of the drive, PRESET SPEED #1 (Parameter 31), or a speed pot. PRESET SPEEDS TB-13A can be programmed to select PRESET SPEED #1, TB-13B to select PRESET SPEED #2, and TB-13C to select PRESET SPEED #3. There are a total of seven preset speeds, which are activated by different combinations of contact closures between TB-13A, 13B, 13C and TB-11. Refer to Parameters in Section DESCRIPTION OF PARAMETERS. JOG TB-13B can be programmed to select either JOG FORWARD or JOG REVERSE. The Jog speed is set by PRESET SPEED #2. Close TB-13B to TB-11 to JOG, and open the contact to STOP. WARNING! When operating in JOG mode, the STOP signal and the AUXILIARY STOP function (see Parameters 10-12) WILL NOT stop the drive. To stop the drive, remove the JOG command. JOG REVERSE will operate the drive in reverse rotation even if ROTATION DIRECTION (Parameter 17) is set to FORWARD ONLY. NOTE: If the drive is commanded to JOG while running, the drive will enter JOG mode and run at PRESET SPEED #2. When the JOG command is removed, the drive will STOP. MOTOR OPERATED POT (MOP) / FLOATING POINT CONTROL TB-13B and TB-13C are required for this function, which controls the drive speed using normally open contacts wired to the terminal strip. Program TB-13B for DECREASE FREQ, and program TB-13C for INCREASE FREQ. Closing the contacts between the TB-13 terminals and TB-11 will cause the speed setpoint to increase or decrease until the contact is opened. The INCREASE FREQ function will only operate while the drive is running. NOTE: If TB-13A, TB-13B, and TB-13C are all programmed to select speed references, and two or three of the terminals are closed to TB-11, the higher terminal has priority and will override the others. For example, if TB-13A is programmed to select a speed pot, and TB-13C is programmed to select PRESET SPEED #3, closing both terminals to TB-11 will cause the drive to respond to PRESET SPEED #3, because TB-13C overrides TB-13A. 11
16 10.7 DRIVE STATUS DIGITAL OUTPUTS There is one open-collector output at terminal TB-14. The open-collector circuit is a current-sinking type rated at 30 VDC and 50 ma maximum. The open-collector output can be programmed to indicate any one of the following: RUN, FAULT, INVERSE FAULT, FAULT LOCKOUT, AT SPEED, ABOVE PRESET SPEED #3, CURRENT LIMIT, AUTO SPEED MODE, and REVERSE. Refer to Parameter 06 in Section DESCRIPTION OF PARAMETERS. DIODE SNUBBER (RECOMMENDED) SCN TERMINAL STRIP TB-11 TB-14 RELAY COIL WARNING! Hazard of electrical shock! The SCN control terminals are not isolated from line voltage! Line voltage is present between the control terminals and ground. Do not touch! Only use relays with an insulation rating of at least 240 Vac or a dielectric rating of at least 1500 volts to prevent damage to equipment and/or injury to personnel. NOTE: When the optional remote keypad is used, TB-14 is wired to the remote keypad and cannot be used for status indication. 12
17 11.0 SM-Basic CONTROL WIRING DIAGRAMS 11.1 TWO-WIRE START/STOP CONTROL WARNING! Hazard of electrical shock! The SM-Basic control terminals are not isolated from line voltage! Line voltage is present between the control terminals and ground. Do not touch! Disconnect input power and wait three minutes before making connections to the control terminals. Devices (such as switches, pushbuttons, potentiometers, relays, etc) and wiring connected to the control terminals are hot to ground and must have an insulation rating of at least 240 Vac or a dielectric rating of at least 1500 volts to prevent damage to equipment and/or injury to personnel A 13B 13C 14 RUN SPEED POT COMMON SPEED POT INPUT SPEED POT POWER SUPPLY DIGITAL INPUT REFERENCE TB-13A FUNCTION SELECT (RUN REVERSE) TB-13B FUNCTION SELECT TB-13C FUNCTION SELECT OPEN-COLLECTOR OUTPUT SPEED POT NOTES: MAINTAINED RUN/STOP CONTACT (FORWARD) MAINTAINED RUN/STOP CONTACT (REVERSE) 1. Close TB-1 to TB-11 to RUN, and open to STOP. TB-1 functions as a RUN input for two-wire start/stop circuits, and a STOP input for three-wire start/stop circuits. Refer to Section If reverse direction is required, set ROTATION (Parameter 17) to FORWARD AND REVERSE (02), and program TB-13A (Parameter 10) to RUN REVERSE (05). Close TB-13A to TB-11 to RUN in the reverse direction, and open to STOP. 3. For speed pot control, set STANDARD SPEED SOURCE (Parameter 05) to SPEED POT (03). 13
18 11.2 THREE-WIRE START/STOP CONTROL WARNING! Hazard of electrical shock! The SM-Basic control terminals are not isolated from line voltage! Line voltage is present between the control terminals and ground. Do not touch! Disconnect input power and wait three minutes before making connections to the control terminals. Devices (such as switches, pushbuttons, potentiometers, relays, etc) and wiring connected to the control terminals are hot to ground and must have an insulation rating of at least 240 Vac or a dielectric rating of at least 1500 volts to prevent damage to equipment and/or injury to personnel A 13B 13C 14 STOP SPEED POT COMMON SPEED POT INPUT SPEED POT POWER SUPPLY DIGITAL INPUT REFERENCE TB-13A FUNCTION SELECT (START REVERSE) TB-13B FUNCTION SELECT TB-13C FUNCTION SELECT (START FORWARD) OPEN-COLLECTOR OUTPUT SPEED POT REV FWD MOMENTARY STOP CONTACT MOMENTARY START CONTACT NOTES: 1. Program TB-13C (Parameter 12) for START FORWARD (05). 2. If reverse direction is required, set ROTATION (Parameter 17) to FORWARD AND REVERSE (02), and program TB-13A (Parameter 10) for START REVERSE (06). 3. Momentarily close TB-13C to TB-11 to START in the forward direction, or close TB-13A to TB-11 to START in the reverse direction. Momentarily open TB-1 to TB-11 to STOP the drive. 4. For speed pot control, set STANDARD SPEED SOURCE (Parameter 05) to SPEED POT (03). 14
19 11.3 PRESET SPEEDS (WITH TWO-WIRE START/STOP CONTROL) WARNING! Hazard of electrical shock! The SM-Basic control terminals are not isolated from line voltage! Line voltage is present between the control terminals and ground. Do not touch! Disconnect input power and wait three minutes before making connections to the control terminals. Devices (such as switches, pushbuttons, potentiometers, relays, etc) and wiring connected to the control terminals are hot to ground and must have an insulation rating of at least 240 Vac or a dielectric rating of at least 1500 volts to prevent damage to equipment and/or injury to personnel A 13B 13C 14 RUN SPEED POT COMMON SPEED POT INPUT SPEED POT POWER SUPPLY DIGITAL INPUT REFERENCE TB-13A FUNCTION SELECT (PRESET SPEED #1) TB-13B FUNCTION SELECT (PRESET SPEED #2) TB-13C FUNCTION SELECT (PRESET SPEED #3) OPEN-COLLECTOR OUTPUT SPEED POT MAINTAINED RUN/STOP CONTACT NOTES: 1. For preset speed control, all or some of the TB-13 terminals must be programmed as preset speed selects. If only two or three preset speeds are required, only two of the TB-13 terminals must be used. Refer to the table in the description of Parameters in Section Program the PRESET SPEEDS (Parameters 31-37) to the desired values. 3. If speed pot control is desired when none of the preset speeds are selected (all preset speed selects are open to TB-11), set STANDARD SPEED SOURCE (Parameter 05) to SPEED POT (03). 15
20 12.0 INITIAL POWER UP AND MOTOR ROTATION WARNING! DO NOT connect incoming AC power to output terminals T1, T2, and T3! Severe damage to the drive will result. Do not continuously cycle input power to the drive more than once every two minutes. Damage to the drive will result. WARNING! Hazard of electrical shock! The SM-Basic control terminals are not isolated from line voltage! Line voltage is present between the control terminals and ground. Do not touch! Capacitors retain charge after power is removed. Disconnect input power and wait until the voltage between terminals B+ and B- is 0 VDC before making control connections or servicing the drive. WARNING! Severe damage to the drive can result if it is operated after a long period of storage or inactivity without reforming the DC bus capacitors! If input power has not been applied to the drive for a period of time exceeding three years (due to storage, etc), the electrolytic DC bus capacitors within the drive can change internally, resulting in excessive leakage current. This can result in premature failure of the capacitors if the drive is operated after such a long period of inactivity or storage. In order to reform the capacitors and prepare the drive for operation after a long period of inactivity, apply input power to the drive for 8 hours prior to actually operating the motor. Before attempting to operate the drive, motor, and driven equipment, be sure all procedures pertaining to installation and wiring have been properly followed. If possible, disconnect the driven load from the motor. Verify that the drive input terminals (L1, L2, and L3 or N) are wired to the proper input voltage per the nameplate rating of the drive. Energize the incoming power line. The LED display will flash a two-digit number (15 in the example below) that identifies the parameter version contained in the drive ("15" actually means parameter version 315). The display should then read - -", which indicates that the drive is in a STOP condition. This is shown below: Apply input power Display flashes parameter version (00-99) Display then reads "- -" 16
21 Follow the procedure below to check the motor rotation. This procedure assumes that the drive has been powered up for the first time, and that none of the parameters have been changed. 1. Use the t button to decrease the speed setpoint to 0 Hz. The left decimal point will illuminate as the speed setpoint is decreased. Once 0 Hz is reached, the display will toggle between 00 and - -, which indicates that the drive is in a STOP condition with a speed setpoint of 0 Hz. 2. Give the drive a START command. This can be done using one of several wiring methods described in Section SM-Basic CONTROL WIRING DIAGRAMS. Once the START command is issued, the display will read 00, indicating that the drive is in a RUN condition with a speed setpoint of 0 Hz. 3. Use the s button to increase the speed setpoint until the motor starts to rotate. The left decimal point will light as the speed setpoint is increased. 4. If the motor is rotating in the wrong direction, give the drive a STOP command and remove power from the drive. Wait three minutes for the bus capacitors to discharge, and swap any two of the motor wires connected to T1, T2, and T3. NOTE: The drive is phase insensitive with respect to incoming line voltage. This means that the drive will operate with any phase sequence of the incoming three phase voltage. Therefore, to change the motor rotation, the phases must be swapped at the drive output terminals or at the motor. 17
22 13.0 PROGRAMMING THE SM-Basic DRIVE The drive may be programmed by one of two methods: using the three buttons and 2-digit LED display on the front of the drive, or programming the Electronic Programming Module (EPM) using the optional EPM Programmer. This section describes programming the drive using the buttons and display, which are shown below: BUTTONS DISPLAY Mode To enter the PROGRAM mode to access the parameters, press the Mode button. This will activate the PASSWORD prompt (if the password has not been disabled). The display will read 00 and the upper right-hand decimal point will be blinking, as shown below: Press Mode Display reads "00" Right decimal point blinks Use the s and t buttons to scroll to the password value (the factory default password is 25 ) and press the Mode button. Once the correct password value is entered, the display will read "01", which indicates that the PROGRAM mode has been accessed at the beginning of the parameter menu (01 is the first parameter), and the upper right decimal point will turn on solid. This is shown below: Use s and t to scroll to the password value Press Mode to enter password Parameter menu is accessed at the first parameter Upper right decimal point turns on solid. 18
23 NOTE: If the display flashes Er, the password was incorrect, and the process to enter the password must be repeated. Use the s and t buttons to scroll to the desired parameter number. In the example below, Parameter 19 is being displayed, which is the ACCELERATION TIME of the drive: Use s and t to scroll to the desired parameter number Once the desired parameter number is found, press the Mode button to display the present parameter setting. The upper right-hand decimal point will begin blinking, indicating that the present parameter setting is being displayed, and that it can be changed by using the s and t buttons. Press Mode to display present parameter setting (present example setting is 15) Right decimal point blinks Use s and t to change setting (example setting changed to 30) Press Mode to store new setting Pressing the Mode will store the new setting and also exit the PROGRAM mode. To change another parameter, press the Mode key again to re-enter the PROGRAM mode (the parameter menu will be accessed at the parameter that was last viewed or changed before exiting). If the Mode key is pressed within two minutes of exiting the PROGRAM mode, the password is not required access the parameters. After two minutes, the password must be entered in order to access the parameters again. 19
24 13.2 ELECTRONIC PROGRAMMING MODULE (EPM) Every SM-Basic Series drive has an Electronic Programming Module (EPM) installed on the main control board. The EPM stores the user s parameter settings and special OEM default settings (if programmed). The EPM is removable, allowing it to be installed in another drive for quick set-up. For example, if a drive is being replaced with a new one, the EPM can be taken out of the first drive and installed in the new drive. Downtime is minimized because the new drive does not require programming - it is ready to run when the EPM is installed. The SM-Basic Series drive contains two or three sets of parameter values, depending on whether the drive has been programmed with optional OEM default settings. The first set of values is the factory default settings, which are permanently stored on the main control board and cannot be changed. The second set of values is the user settings, which are stored in the EPM. When the drive leaves the factory, the user settings are the same as the factory default settings, but the user settings can be changed to configure the drive for a particular application. The optional third set of values is the OEM default settings, which are also stored in the EPM. OEM default settings are typically used in cases where many drives are used for the same application, which requires that all of the drives have the same parameter settings. The OEM default settings cannot be changed without the optional EPM Programmer. The drive can be programmed to operate according to the user settings or the OEM default settings (see Parameter 48 in Section 15.0). NOTE: The drive will not operate without the EPM installed. The drive will display F1 if the EPM is missing or damaged. WARNING! Do not remove the EPM while power is applied to the drive. Damage to the EPM and/or drive may result. An EPM Programmer is available as an option from SM-Basic, which has the ability to quickly and easily program many SM-Basic drives for the same configuration. Once a master EPM is programmed with the desired parameter settings, the EPM Programmer can copy those settings to other EPMs, allowing many drives to be configured very quickly. Please consult the EPM Programmer Instruction Manual or contact the factory for more information. If the OEM settings in the EPM become corrupted, the drive will operate normally, until an attempt is made to perform a RESET OEM using Parameter 48 - PROGRAM SELECTION. The drive will then flash GF to indicate that the OEM settings are no longer valid. This will require that the EPM be re-programmed using the optional EPM Programmer. If the OEM settings and the user settings are both corrupted, the drive will display GF immediately and the drive will require a RESET 60 or RESET 50 using Parameter 48 - PROGRAM SELECTION. Once the RESET is performed, the parameters can then be programmed individually to match the OEM default settings. This will allow the drive to operate as if it were in OEM mode, even though it is actually operating in USER mode. Refer to Parameter 48 in Section DESCRIPTION OF PARAMETERS. NOTE: The drive will also display GF if a RESET OEM or OPERATE WITH OEM SETTINGS is attempted when the drive is not equipped with the OEM default option. 20
25 14.0 PARAMETER MENU FACTORY NO. PARAMETER NAME RANGE OF ADJUSTMENT DEFAULT (NOTE 1) 01 LINE VOLTAGE HIGH (01), LOW (02) HIGH (01) 02 CARRIER FREQUENCY 4kHz (01), 6 khz (02), 8 khz (03), 10 khz (04) 6 khz (02) 03 START METHOD NORMAL (01), START ON POWER UP (02), NORMAL (01) START WITH DC BRAKE (03), AUTO RESTART WITH DC BRAKE (04), FLYING RESTART 1 (05), FLYING RESTART 2 (06), FLYING RESTART 3 (07) 04 STOP METHOD COAST (01), COAST WITH DC BRAKE (02), COAST (01) RAMP (03), RAMP WITH DC BRAKE (04) 05 STANDARD SPEED KEYPAD (01), PRESET #1 (02), KEYPAD (01) SOURCE SPEED POT (03) 06 TB-14 OUTPUT NONE (01), RUN (02), FAULT (03), NONE (01) INVERSE FAULT (04), FAULT LOCKOUT (05), AT SET SPEED (06), ABOVE PRESET #3 (07), CURRENT LIMIT (08), AUTO SPEED (09), REVERSE (10), DB BRAKE (11) 10 TB-13A FUNCTION NONE (01), SPEED POT (02), NONE (01) SELECT PRESET SPEED #1 (03), START FORWARD (04), RUN REVERSE (05), START REVERSE (06), EXTERNAL FAULT (07), DB FAULT (08), AUXILIARY STOP (09), ACCEL/DECEL #2 (10) 11 TB-13B FUNCTION NONE (01), SPEED POT (02), NONE (01) SELECT PRESET SPEED #2 (03), DECREASE FREQ (04), JOG FORWARD (05), JOG REVERSE (06), EXTERNAL FAULT (07), DB FAULT (08), AUXILIARY STOP (09), ACCEL/DECEL #2 (10) 12 TB-13C FUNCTION NONE (01), SPEED POT (02), NONE (01) SELECT PRESET SPEED #3 (03), INCREASE FREQ (04), START FORWARD (05), EXTERNAL FAULT (06), DB FAULT (07), AUXILIARY STOP (08), ACCEL/DECEL #2 (09) NOTE 1: Factory defaults are shown for a 60 Hz base frequency. See Parameter 48 for 50 Hz base frequency. 21
26 FACTORY NO. PARAMETER NAME RANGE OF ADUSTMENT DEFAULT (NOTE 1) 14 CONTROL TERMINAL STRIP ONLY (01), TERMINAL STRIP REMOTE KEYPAD ONLY (02) ONLY (01) 17 ROTATION FORWARD ONLY (01), FORWARD FORWARD AND REVERSE (02) ONLY (01) 18 TIME RANGE SELECT x0.1 (01), x1.0 (02), x10.0 (03) x1.0 (02) 19 ACCELERATION TIME SEC 20 SEC 20 DECELERATION TIME SEC 20 SEC 21 DC BRAKE TIME SEC 0 SEC 22 DC BRAKE VOLTAGE 0-30 % 0 % 23 MINIMUM FREQUENCY 0 - MAXIMUM FREQUENCY 0 Hz 24 MAXIMUM FREQUENCY MINIMUM FREQUENCY - 99 Hz 60 Hz 25 CURRENT LIMIT % (NOTE 2) 180 % 26 MOTOR OVERLOAD % 100 % 27 BASE FREQUENCY Hz 60 Hz 28 FIXED BOOST 0-30 % 1 % 29 ACCEL BOOST 0-20 % 0 % 30 SLIP COMPENSATION % 0 % PRESET SPEEDS 0 - MAXIMUM FREQUENCY 0 Hz 38 SKIP BANDWIDTH 0-10 Hz 0 Hz 42 ACCEL / DECEL # SEC 20 SEC 44 PASSWORD CLEAR HISTORY MAINTAIN (01), CLEAR (02) MAINTAIN (01) 48 PROGRAM USER SETTINGS (01), OEM SETTINGS (02), USER SELECTION RESET OEM (03), RESET 60 (04), SETTINGS (01) RESET 50 (05), TRANSLATE (06) 50 FAULT HISTORY (VIEW-ONLY) (N/A) 51 SOFTWARE CODE (VIEW-ONLY) (N/A) 52 DC BUS VOLTAGE (VIEW-ONLY) (N/A) 53 MOTOR VOLTAGE (VIEW-ONLY) (N/A) 54 LOAD (VIEW-ONLY) (N/A) 55 SPEED POT INPUT (VIEW-ONLY) (N/A) 57 TB STRIP STATUS (VIEW-ONLY) (N/A) 58 KEYPAD STATUS (VIEW-ONLY) (N/A) NOTE 1: Factory defaults are shown for a 60 Hz base frequency. See Parameter 48 for 50 Hz base frequency. NOTE 2: If LINE VOLTAGE is set to LOW, maximum setting is 150%. 22
27 15.0 DESCRIPTION OF PARAMETERS 01 LINE VOLTAGE SELECTION This calibrates the drive for the actual applied input voltage, and can be set to HIGH (01) or LOW (02). Refer to the table below for the proper setting depending on the input voltage. RATED INPUT INPUT APPLIED PLIED INPUT PARAMETERR MODEL VOLTAGE PHASE VOLTAGE SETTING SN100S 120 / 208 / 240 Vac Vac or Vac HIGH (01) Vac LOW (02) N 0S 208 / 240 Vac 1 or Vac HIGH (01) 1 or Vac LOW (02) SN / 240 Vac Vac HIGH (01) Vac LOW (02) NOTE: If this parameter is changed while the drive is running, the new value will not take effect until the drive is stopped. 02 CARRIER FREQUENCY This sets the switching rate of the output IGBT s. Increasing the carrier frequency will result in less audible motor noise. Available settings are: 4 khz, 6 khz, 8 khz, and 10 khz. PARAMETER CARRIER MAXIMUM OUTPUT AMBIENT OR OUTPUT SETTING FREQUENCY FREQUENCY DERATE (NOTE 2) 01 4 khz 99 Hz 50 C or 100% 02 6 khz 99 Hz 50 C or 100% 03 8 khz 99 Hz 43 C or 92% khz 99 Hz 35 C or 82% NOTE 1: The SM-Basic drive is fully rated up to 6 khz carrier frequency. If the 8 khz or 10 khz carrier frequency is selected, the drive s ambient temperature rating OR output current rating must be de-rated to the value shown in the table above. NOTE 2: If this parameter is changed while the drive is running, the change will not take effect until the drive is stopped. 23
28 03 START METHOD WARNING! Automatic starting of equipment may cause damage to equipment and/or injury to personnel! Automatic start should only be used on equipment that is inaccessible to personnel. 01 NORMAL: The drive will start when the appropriate contact is closed on the terminal strip. See Section 11 for possible control configurations. 02 START ON POWER UP: The drive will automatically start upon application of input power. 03 START WITH DC BRAKE: When a START command is given, the drive will apply DC BRAKE VOLTAGE (Parameter 22) for the duration of DC BRAKE TIME (Parameter 21) prior to starting the motor to ensure that the motor is not turning. 04 AUTO RESTART WITH DC BRAKING: Upon a START command, after a fault, or upon application of power, the drive will apply DC BRAKE VOLTAGE (Parameter 22) for the duration of DC BRAKE TIME (Parameter 21) prior to starting (or restarting) the motor. 05 FLYING RESTART 1: LOW performance. Slowest synchronization and lowest current level. This setting results in the smoothest synchronization. 06 FLYING RESTART 2: MEDIUM performance. Faster synchronization and higher current level. This setting allows faster synchronization while retaining smoothness. 07 FLYING RESTART 3: HIGH performance. Fastest synchronization and highest current level. This setting allows the fastest synchronization, but sacrifices smoothness. When programmed for auto-restart (settings 04-07), the drive will attempt three restarts after a fault. The interval between restart attempts is 15 seconds for setting 04, and 2 seconds for settings 05, 06 and 07. During the interval between restart attempts, the display will read SP to indicate Start Pending. If all three restart attempts fail, the drive will trip into FAULT LOCKOUT (displayed LC ) and require a manual reset. Refer to Section TROUBLESHOOTING. The FLYING RESTART 1-3 settings allow the drive to start into a spinning load after a fault or upon application of input power. They differ in the time required to find the motor and the amount of current required to synchronize with it. The faster the drive attempts to find the motor, the more current is required. The first two restart attempts will try to start into the spinning load, but the third restart attempt will act like AUTO RESTART WITH DC BRAKING. NOTE: Settings 02 and require a two-wire start/stop circuit to operate. The RUN contact must remain closed for the power-up start and auto-restart functions to operate. 24
29 04 STOP METHOD 01 COAST TO STOP: When a STOP command is given, the drive shuts off the output to the motor, allowing it to coast freely to a stop. 02 COAST WITH DC BRAKE: When a stop command is given, the drive will activate DC braking (after a delay of up to 2 seconds, depending on frequency) to help decelerate the load. Refer to Parameters: 21 - DC BRAKE TIME, and 22 - DC BRAKE VOLTAGE. 03 RAMP TO STOP: When a stop command is given, the drive will decelerate the motor to a stop at the rate determined by Parameter 20 - DECELERATION TIME. 04 RAMP WITH DC BRAKE: When a stop command is given, the drive will decelerate the motor down to 0.2 Hz (at the rate set by Parameter 20 - DECELERATION TIME) and then activate DC braking according to the settings of Parameters 21 - DC BRAKE TIME and 22 - DC BRAKE VOLTAGE. This is used to bring the load to a final stop, as the motor may still be turning slightly after the drive stops. 05 STANDARD SPEED SOURCE This selects the speed reference source when the drive is in STANDARD speed mode. The following speed references can be selected: 01 KEYPAD: Use the s and t buttons to scroll to the desired speed. 02 PRESET SPEED #1: The drive will operate at the frequency set into Parameter SPEED POT: The drive will respond to a speed pot. Refer to Section 11.0 for speed pot wiring. 06 TB-14 OPEN COLLECTOR OUTPUT This selects the status indication for the open-collector output at TB-14. The terms open and close refer to the state of the internal transistor that activates the circuit. When the transistor is closed, TB-14 is at the same potential as TB-2, allowing current to flow. 01 NONE: Disables the open-collector output. 02 RUN: Closes upon a START command. Opens if the drive is in a STOP state, the drive faults, or input power is removed. DC braking is considered a STOP state. 03 FAULT: Closes if there is no fault condition. Opens if the drive faults, or input power is removed. 04 INVERSE FAULT: Closes if the drive faults. Opens if there is no fault condition. 05 FAULT LOCKOUT: Closes when input power is applied. Opens if three restart attempts are unsuccessful, or if input power is removed. 25
30 06 AT SET SPEED: Closes if the drive is within Hz of the speed setpoint. 07 ABOVE PRESET SPEED #3: Closes if the output frequency exceeds PRESET SPEED #3 (Parameter 33). Opens if the output frequency is equal to or less than PRESET SPEED #3. 08 CURRENT LIMIT: Closes if the output current exceeds the CURRENT LIMIT setting. Opens if the output current is equal to or less than CURRENT LIMIT (see Parameter 25). 09 AUTOMATIC SPEED MODE: Closes if an AUTOMATIC (terminal strip) speed reference is active. Opens if a STANDARD (Parameter 5) speed reference is active. 10 REVERSE: Closes when reverse rotation is active. Opens when forward rotation is active (see Parameter 17 - ROTATION DIRECTION). 11 DB BRAKE: TB-14 becomes the "trigger" that activates the optional external Dynamic Braking module. Refer to the instructions included with the Dynamic Braking option. NOTE: If the optional remote keypad is used, TB-14 is wired to the remote keypad and cannot be used for any of the above listed functions. In this case, this parameter should be set to NONE (01). 10 TB-13A FUNCTION SELECT This selects the function of terminal TB-13A. Closing TB-13A to TB-11 (or opening in the case of settings 07 and 09) activates the selected function. The following functions can be selected: 01 NONE: Disables the TB-13A function. 02 SPEED POT: Selects a speed pot as the speed reference input. Refer to Section 11.0 for speed pot wiring. 03 PRESET SPEED #1: Selects PRESET SPEED #1 as the speed reference. The drive will operate at the frequency programmed into Parameter START FORWARD: Sets up the drive for a 3-wire start/stop circuit. Momentarily close TB- 13A to TB-11 to start the drive, and momentarily open TB-1 to TB-11 to stop. 05 RUN REVERSE: Close TB-13A to TB-11 to run in the reverse direction, and open to stop. Close TB-1 to TB-11 to run in the forward direction and open to stop. 06 START REVERSE: Momentarily close TB-13A to TB-11 to start the drive in the reverse direction, and momentarily open TB-1 to TB-11 to stop. Parameter 17 - ROTATION must be set to FORWARD AND REVERSE (02), and TB-13C must be used for START FORWARD. 07 EXTERNAL FAULT: Sets TB-13A as a normally closed external fault input. Open TB-13A to TB-11 to trip the drive. 26
31 08 DB FAULT: Sets TB-13A as a dynamic braking fault input when used with the optional dynamic braking module. When this input is activated by the dynamic braking module, the drive will trip into a "df" fault and the motor will coast to a stop. Refer to the instructions included with the Dynamic Braking option. 09 AUXILIARY STOP: When TB-13A is opened with respect to TB-11, the drive will decelerate to a STOP (even if STOP METHOD is set to COAST) at the rate set into ACCEL/DECEL #2 (Parameter 42). 10 ACCEL/DECEL #2: Selects the acceleration and deceleration time programmed into ACCEL/ DECEL #2 (Parameter 42). NOTE: If the optional remote keypad is used, functions 02, 04, 05, and 06 are disabled. Therefore, if this terminal is not being used for any of the other functions, it should be set to NONE (01). 11 TB-13B FUNCTION SELECT This selects the function of terminal TB-13B. Closing TB-13B to TB-11 (or opening in the case of settings 07 and 09) activates the selected function. The following functions can be selected: 01 NONE: Disables the TB-13B function. 02 SPEED POT: Selects a speed pot as the speed reference input. Refer to Section 11.0 for speed pot wiring. 03 PRESET SPEED #2: Selects PRESET SPEED #2 as the speed reference. The drive will operate at the frequency programmed into Parameter DECREASE FREQ: Closing TB-13B to TB-11 will decrease the speed setpoint until the contact is opened. TB-13C must be programmed for INCREASE FREQ. 05 JOG FORWARD: Close TB-13B to TB-11 to JOG in the forward direction. The drive will run at PRESET SPEED #2 (Parameter 32) when in JOG mode. 06 JOG REVERSE: Close TB-13B to TB-11 to JOG in the reverse direction. The drive will run at PRESET SPEED #2 (Parameter 32) when in JOG mode. WARNING! When operating in JOG mode, the STOP signal and the AUXILIARY STOP function (see Parameters 10-12) WILL NOT stop the drive. To stop the drive, remove the JOG command. JOG REVERSE will operate the drive in reverse rotation even if ROTATION DIRECTION (Parameter 17) is set to FORWARD ONLY. 07 EXTERNAL FAULT: Sets TB-13B as a normally closed external fault input. Open TB-13B to TB-11 to trip the drive. 27
32 08 DB FAULT: Used with the optional dynamic braking module. When this input is activated by the dynamic braking module, the drive will trip into a "df" fault and the motor will coast to a stop. Refer to the instructions included with the Dynamic Braking option. 09 AUXILIARY STOP: When TB-13B is opened with respect to TB-11, the drive will decelerate to a STOP (even if STOP METHOD is set to COAST) at the rate set into ACCEL/DECEL #2 (Parameter 42). 10 ACCEL/DECEL #2: Selects the acceleration and deceleration time programmed into Parameter 42 - ACCEL/DECEL #2. NOTE 1: If the drive is commanded to JOG while running, the drive will enter JOG mode and run at PRESET SPEED #2 (Parameter 32). When the JOG command is removed, the drive will STOP. NOTE 2: If the optional remote keypad is used, functions 02 and 08 are disabled. Therefore, if this terminal is not being used for any of the other functions, it should be set to NONE (01). 12 TB-13C FUNCTION SELECT This selects the function of terminal TB-13C. Closing TB-13C to TB-11 (or opening in the case of settings 06 and 08) activates the selected function. The following functions can be selected: 01 NONE: Disables the TB-13C function. 02 SPEED POT: Selects a speed pot as the speed reference input. Refer to Section 11.0 for speed pot wiring. 03 PRESET SPEED #3: Selects PRESET SPEED #3 as the speed reference. The drive will operate at the frequency programmed into Parameter INCREASE FREQ: Closing TB-13C to TB-11 will increase the speed setpoint until the contact is opened. INCREASE FREQ will only work when the drive is running. TB-13B must be programmed for DECREASE FREQ. 05 START FORWARD: Sets up the drive for a 3-wire start/stop circuit. Momentarily close TB- 13C to TB-11 to start the drive, and momentarily open TB-1 to TB-11 to stop. 06 EXTERNAL FAULT: Sets TB-13C as a normally closed external fault input. Open TB-13C to TB-11 to trip the drive. 07 DB FAULT: Used with the optional dynamic braking module. When this input is activated by the dynamic braking module, the drive will trip into a "df" fault and the motor will coast to a stop. Refer to the instructions included with the Dynamic Braking option. 08 AUXILIARY STOP: When TB-13C is opened with respect to TB-11, the drive will decelerate to a STOP (even if STOP METHOD is set to COAST) at the rate set into ACCEL/DECEL #2 (Parameter 42). 28
33 09 ACCEL/DECEL #2: Selects the acceleration and deceleration time programmed into ACCEL/ DECEL #2 (Parameter 42). NOTE: If the optional remote keypad is used, functions 02, 05, and 07 are disabled. Therefore, if this terminal is not being used for any of the other functions, it should be set to NONE (01). 14 CONTROL 01 TERMINAL STRIP ONLY: The drive will only respond to START and direction commands from the terminal strip. 02 REMOTE KEYPAD ONLY: The drive will only respond to START and direction commands from the optional remote keypad. NOTE: When the optional remote keypad is used, TB-5 and TB-14 are wired to the remote keypad. Therefore, a speed pot cannot be used for speed control, and TB-14 cannot be used for status indication. Also, some of the functions on TB-13A, 13B, and 13C are disabled, and the Dynamic Braking option cannot be used. 17 ROTATION DIRECTION 01 FORWARD ONLY: The drive will only allow rotation in the forward direction. However, JOG REVERSE (see Parameter 11) will still operate even if FORWARD ONLY is selected. 02 FORWARD AND REVERSE: The drive will allow rotation in both directions. 18 TIME RANGE SELECT This parameter is used as a time multiplier for Parameters 19, 20, 21, and 42. The values entered into those parameters are multiplied by the selected factor in this parameter. 01 x0.1 (Multiplies time by a factor of 0.1) 02 x1.0 (Multiplies time by a factor of 1.0) 03 x10.0 (Multiplies time by a factor of 10.0) Example: If an acceleration time of 5.5 seconds is desired, set this parameter to 01 (x0.1 factor), and set ACCELERATION TIME (Parameter 19) to 55. NOTE: When a new time multiplier is selected, the displays for Parameters 19, 20, 21, and/or 42 will change to maintain the same time value. For example, if the multiplier is x1.0, and ACCELERATION TIME is set to 30, the time value is 30 seconds. If the multiplier is then changed to x10.0, the ACCELERATION TIME display will change to 3 to maintain the time value of 30 seconds. If the display required to maintain the time value is out of the possible range (less than 1, higher than 99, or a decimal), the display will blink to indicate that it is not accurate. 29
34 19 ACCELERATION TIME This sets the acceleration rate for all of the speed reference sources (keypad, speed pot, jog, MOP, and preset speeds). This setting is the time to accelerate from 0 Hz to the BASE FREQUENCY (Parameter 27). This parameter is affected by the setting of TIME RANGE SELECT (Parameter 18). 20 DECELERATION TIME This sets the deceleration rate for all of the speed reference sources (keypad, speed pot, jog, MOP, and preset speeds). This setting is the time to decelerate from BASE FREQUENCY to 0 Hz. If the drive is set for COAST TO STOP (setting 01 or 02 in Parameter 04), this parameter will have no effect when a STOP command is given. This parameter is affected by the setting of TIME RANGE SELECT (Parameter 18). 21 DC BRAKE TIME This sets the length of time that the DC braking voltage is applied to the motor. The DC BRAKE TIME should be set to the lowest value that provides satisfactory operation in order to minimize motor heating. This parameter is affected by the setting of TIME RANGE SELECT (Parameter 18). 22 DC BRAKE VOLTAGE This sets the magnitude of the DC braking voltage, in percentage of the line voltage. The point at which the DC braking is activated depends on the selected STOP METHOD (Parameter 04): If COAST WITH DC BRAKE is selected, braking is activated after a time delay of up to 2 seconds, depending on the output frequency at the time of the STOP command. In this case, the DC braking is the only force acting to decelerate the load. If RAMP WITH DC BRAKE is selected, braking is activated when the output frequency reaches 0.2 Hz. In this case, the drive decelerates the load to a near stop and then DC braking is used to bring the load to a final stop. 23 MINIMUM FREQUENCY This sets the minimum output frequency of the drive for all speed reference sources except the PRESET SPEEDS (Parameters 31-37). When using a speed pot reference, this parameter also sets the drive speed that corresponds to the minimum analog input (0 VDC). NOTE: If this parameter is changed while the drive is running, the new value will not take effect until the drive is stopped. 24 MAXIMUM FREQUENCY This sets the maximum output frequency of the drive for all speed reference sources, and is used with MINIMUM FREQUENCY (Parameter 23) to define the operating range of the drive. 30
35 When using a speed pot reference, this parameter also sets the drive speed that corresponds to the maximum analog input (10 VDC). NOTE: If this parameter is changed while the drive is running, the new value will not take effect until the drive is stopped. 25 CURRENT LIMIT This sets the maximum allowable output current of the drive. The maximum setting is either 180% or 150%, depending on whether LINE VOLTAGE SELECTION (Parameter 01) is set to HIGH or LOW. If the load demands more current than the CURRENT LIMIT setting, the drive will reduce the output frequency in an attempt to reduce the output current. When the overcurrent condition passes, the drive will accelerate the motor back up to the speed setpoint. To set this parameter, divide the desired setting by 10 and enter that value. For example, if the desired setting is 150%, set this parameter to MOTOR OVERLOAD The SM-Basic Series is UL approved for solid state motor overload protection, and therefore does not require a separate thermal overload relay for single motor applications. The drive contains an adjustable thermal overload circuit that protects the motor from excessive overcurrent. This circuit allows the drive to deliver up to 150% current for one minute. If the overload circuit times out, the drive will trip into an OVERLOAD fault (displayed as "PF"). To set this parameter, subtract 1 from the desired setting and enter that value. For example, if the desired setting is 75%, set this parameter to 74. MOTOR OVERLOAD should be set to the ratio (in percent) of the motor current rating to the drive current rating in order to properly protect the motor. Example: A 2 HP, 230 Vac drive with a 6.8 Amp rating is operating a 1 HP motor with a current rating of 4.0 Amps. Dividing the motor current rating by the drive current rating yields 59% (4.0 / 6.8 = 0.59 = 59%), so this parameter should be set to 58 ( = 59%). 27 BASE FREQUENCY The BASE FREQUENCY determines the V/Hz ratio by setting the output frequency at which the drive will output full voltage to the motor. In most cases, the BASE FREQUENCY should be set to match the motor s rated frequency. Example: A 230 Vac, 60 Hz motor requires a V/Hz ratio of 3.83 (230 V / 60 Hz = 3.83 V/Hz) to produce full torque. Setting the BASE FREQUENCY to 60 Hz causes the drive to output full voltage (230 Vac) at 60 Hz, which yields the required 3.83 V/Hz. Output voltage is proportional to output frequency, so the 3.83 V/Hz ratio is maintained from 0-60 Hz, allowing the motor to produce full torque from about 2 Hz (below 2 Hz there is less torque due to slip) up to 60 Hz. NOTE: If this parameter is changed while the drive is running, the new value will not take effect until the drive is stopped. 31
36 2 8 FIXED BOOST FIXED BOOST increases starting torque by increasing the output voltage when operating below half of the base frequency, which increases the V/Hz ratio. For better out-of-the-box performance, SCN Series drives are shipped with a setting that is different from the factory default of 1%. Units rated 0.25 to 1 HP are set to 5.3%, units rated 1.5 to 2 HP are set to 4.4%, and 3 HP units are set to 3.6%. 29 ACCELERATION BOOST ACCELERATION BOOST helps accelerate high-inertia loads. During acceleration, the output voltage is increased to increase motor torque. Once the motor reaches the new speed setpoint, the boost is turned off and the output voltage returns to the normal value. 30 SLIP COMPENSATION SLIP COMPENSATION is used to counteract changes in motor speed (slip) caused by changes in load. In a standard AC induction motor, the shaft speed decreases as load increases, and increases as load decreases. By increasing or decreasing the output frequency in response to an increasing or decreasing load, the slip is counteracted and speed is maintained. Most standard NEMA B motors have a 3% slip rating. To set this parameter, multiply the desired setting by 10 and enter that value. For example, if a setting of 2.5% is desired, enter 25 into this parameter PRESET SPEED #1 - #7 Preset speeds are activated by contact closures between TB-11 and TB-13A, 13B, and 13C. The TB- 13 terminals must be programmed as preset speed selects using Parameters NOTE 1: Preset speeds can operate below the frequency defined by the minimum frequency parameter (Parameter 23). Refer to the table below for activation of the preset speeds using the TB-13 terminals. SPEED # TB - 13A TB - 13B TB - 13C 1 CLOSED OPEN OPEN 2 OPEN CLOSED OPEN 3 OPEN OPEN CLOSED 4 CLOSED CLOSED OPEN 5 CLOSED OPEN CLOSED 6 OPEN CLOSED CLOSED 7 CLOSED CLOSED CLOSED 32
37 NOTE 2: When a TB-13 terminal is programmed for a function other than a preset speed select, it is considered OPEN for the table above. Preset Speed #6 and #7 can also be used as skip frequencies to restrict the drive from operating at frequencies that cause vibration in the system. See Parameter 38 below. 38 SKIP BANDWIDTH The SM-Basic drive has two skip frequencies that can be used to lock out critical frequencies that cause mechanical resonance in the system. Once SKIP BANDWIDTH is set to a value other than 0 Hz, the skip frequencies are enabled. When the skip frequency function is enabled, PRESET SPEED #6 and #7 are used as the skip frequencies. SKIP BANDWIDTH sets the range above the skip frequencies that the drive will not operate within. Example: The critical frequency is 23 Hz, and it is desired to skip a frequency range of 3 Hz above and below the critical frequency (therefore the skip range is 20 to 26 Hz). PRESET SPEED #6 or #7 would be set to 20 Hz, and the SKIP BANDWIDTH would be set to 6 Hz. If the drive is running at a speed below the skip range, and it is given a speed command that is within the skip range, the drive will accelerate to the start of the skip range (20 Hz in the example) and run at that speed until the speed command is greater than or equal to the "top" of the skip range. The drive will then accelerate through the skip range to the new speed. Likewise, if the drive is running at a speed above the skip range, and it is given a speed command that is within the skip range, the drive will decelerate to the "top" of the skip range (26 Hz in the example) and run at that speed until the speed command is less than or equal to the "bottom" of the skip range. The drive will then decelerate through the skip range to the new speed. NOTE: PRESET SPEEDS #6 and #7 can still be used as preset speeds even if they are also being used as skip frequencies. 42 ACCEL / DECEL #2 This parameter sets the second acceleration and deceleration rate of the drive, which can be activated using terminals TB-13A, 13B, or 13C (Parameter 10, 11, or 12). This parameter is affected by the setting of TIME RANGE SELECT (Parameter 18). 44 PASSWORD This allows the PASSWORD to be changed to any number between 00 and 99. Setting PASSWORD to 00 disables the password function. NOTE: The factory default password is CLEAR FAULT HISTORY 01 MAINTAIN: Maintains the FAULT HISTORY (Parameter 50) entries for troubleshooting. 02 CLEAR: Erases the FAULT HISTORY (Parameter 50) entries. 33
38 4 8 PROGRAM SELECTION This is used to select whether the drive will operate according to the user settings or the optional OEM default settings, and to reset the parameters to default settings. Refer to Section OPERATE WITH USER SETTINGS: The drive will operate according to the user settings. Operation in USER mode allows the parameter values to be changed to suit any application. 02 OPERATE WITH OEM DEFAULTS: The drive will operate according to the optional OEM default settings, which configure the drive for a specific application. When operating in OEM mode, the parameter values can be viewed, but not changed. If an attempt is made to change a parameter setting, the display will flash GE. If the drive is not programmed with OEM default settings, the display will flash GF if this option is selected. 03 RESET OEM: Resets the user parameters to the OEM default settings. If the drive is not programmed with OEM default settings, the display will flash GF if this option is selected. 04 RESET 60: Resets the user parameters to the factory defaults for a 60 Hz base frequency. 05 RESET 50: Resets the user parameters to the factory defaults for a 50 Hz base frequency. Parameters 24 and 27 will reset to 50.0 Hz. 06 TRANSLATE: If an EPM from a drive with a previous parameter version is installed in a new drive, the new drive will function like the previous version drive, but none of the parameter settings can be changed ("ce" will be displayed if this is attempted). The TRANSLATE function converts the EPM to the new parameter version so that the parameters can be changed, but it also retains the old parameter settings so the new drive will operate like the old drive without having to re-program all of the parameters. NOTE 1: If the user parameters are reset to the OEM defaults (using the RESET OEM option), and then OPERATE WITH USER SETTINGS is selected, the USER settings will be the same as the OEM default settings. This allows the drive to operate as if it was in OEM mode, but the parameter values can be changed. This is useful if some of the OEM default settings need to be fine-tuned for proper operation. The new parameter values are not actually stored as new OEM default settings however; they are simply stored as new USER settings. Therefore, if the parameters are reset to the OEM defaults again, the parameters that were changed will be reset to their old value. The optional EPM Programmer is required to change OEM default settings. Refer to Section NOTE 2: Only the TRANSLATE (06) function can be performed while the drive is running. The display will flash "Er" if an attempt is made to select any other function while the drive is running. 34
39 5 0 FAULT HISTORY The FAULT HISTORY stores the last eight faults that tripped the drive. Refer to Section TROUBLESHOOTING for a list of the faults and possible causes. Use the s and t buttons to scroll through the fault entries. The faults are stored from newest to oldest, with the first fault shown being the most recent. The display will read if the FAULT HISTORY does not contain any fault messages. 51 SOFTWARE VERSION This displays the software version number for the control board software. This information is useful when contacting the factory for programming or troubleshooting assistance. The software version is displayed in two parts which alternate. The first part is the software version, and the second part is the revision number. For example, if the display flashes "72" and "02", this indicates that the drive contains the second revision of version 72 software. 52 DC BUS VOLTAGE This displays the DC bus voltage in percent of nominal. Nominal DC bus voltage is determined by multiplying the drive s nameplate input voltage rating by MOTOR VOLTAGE This displays the output voltage in percent of the drive s nameplate output voltage rating. 54 MOTOR LOAD This displays the motor load in percent of the drive s output current rating. 55 SPEED POT INPUT This displays the level of the speed pot input signal at TB-5. A reading of 100% indicates that the maximum speed pot signal is present at TB-5. NOTE: Paramaters can display values greater than 99. If the value is greater than 99, the display will alternate between "1 -" or "2 -" (for one hundred or two hundred) and the rest of the value. For example, if MOTOR LOAD is 137%, the display will alternate between "1 -" and "37". 35
40 5 7 TERMINAL STRIP STATUS This indicate the status of several terminals using the vertical segments of the LED display. An illuminated segment indicates that the particular terminal is closed to TB-2. TB-1 TB-13A TB-13C TB-13B TB-14 FACTORY RESERVED 58 KEYPAD AND PROTECTION STATUS This indicate the status of the buttons on the keypad, and the status of the protective circuitry in the drive, using the horizontal segments of the LED display. An illuminated segment indicates that the particular button is pressed, or the protective circuit is active. s t FCLIM Mode OUTPUT FAULT NOTE: FCLIM is an abbreviation for Fast Current Limit. 36
41 16.0 TROUBLESHOOTING To aid in troubleshooting, Parameters 50 through 58 can be accessed without entering the PASSWORD. Simply press the Mode button twice to skip over the PASSWORD prompt, and 50 will be displayed to indicate that the parameter menu has been entered and Parameter 50 (FAULT HISTORY) can be viewed. The s and t buttons can then be used to scroll from Parameter 50 to Parameter 58. Once the desired parameter is found, press the Mode button to view its contents. When finished, press Mode to exit the parameter menu. An example is shown below: Press Mode once Display reads "00" Upper right decimal point blinks Press Mode again Display reads "50" (FAULT HISTORY) Use s and t to scroll to the desired parameter number (In this example Parameter 54 has been selected, which is MOTOR LOAD) Press Mode to view parameter contents (77 = 77% LOAD) Upper right decimal point blinks Press Mode again to exit In the example above, Parameter 54 - MOTOR LOAD is being viewed. The 77 in the example indicates that the load on the motor is 77% of the output current rating of the drive. 37
42 The table below lists the fault conditions that will cause the drive to shut down, as well as some possible causes. Please contact the factory for more information on troubleshooting faults. FAULT MESSAGES FAULT AF CF cf df EF GF HF JF LF OF PF SF UF F1 F2 - F9, Fo DESCRIPTION & POSSIBLE CAUSES High Temperature Fault: Ambient temperature is too high; Cooling fan has failed (if equipped). Control Fault: A blank EPM, or an EPM with corrupted data has been installed. Perform a factory reset using Parameter 48 - PROGRAM SELECTION. Incompatibility Fault: An EPM with an incompatible parameter version has been installed. Either remove the EPM or perform a factory reset (Parameter 48) to change the parameter version of the EPM to match the parameter version of the drive. Dynamic Braking Fault: The drive has sensed that the dynamic braking resistors are overheating and shuts down to protect the resistors. External Fault: One of the TB-13 terminals is set as an External Fault input and that terminal is open with respect to TB-11. Refer to Parameters 10, 11 and 12. Data Fault: User data and OEM defaults in the EPM are corrupted. High DC Bus Voltage Fault: Line voltage is too high; Deceleration rate is too fast; Overhauling load. For fast deceleration or overhauling loads, dynamic braking may be required. Remote Keypad Fault: The communication between the SCN drive and the optional Remote Keypad has been lost. Check for proper wiring and/or noise. Low DC Bus Voltage Fault: Line voltage is too low. Output Transistor Fault: Phase to phase or phase to ground short circuit on the output; Boost settings are too high; Acceleration rate is too fast; Failed output transistor. Current Overload Fault: VFD is undersized for the application; Mechanical problem with the driven equipment. Single-phase Fault: Single-phase input power has been applied to a three-phase drive. Start Fault: Start command was present when the drive was powered up. Must wait 2 seconds after power-up to apply Start command if START METHOD is set to NORMAL. EPM Fault: The EPM is missing or damaged. Internal Faults: The control board has sensed a problem - consult factory. To clear a fault, issue a STOP command on the terminal strip. The fault will only clear if the condition that caused the fault has passed. For example, if the drive trips on a LOW DC BUS VOLTAGE FAULT (LF) due to low input voltage, the fault cannot be cleared until the input voltage returns to a normal level. If the drive is programmed to automatically restart after a fault (see Parameter 03), the drive will attempt to restart three times after a fault (the drive will not restart after CF, cf, GF, F1, F2-F9, or Fo faults). If all three restart attempts are unsuccessful, the drive will trip into FAULT LOCKOUT (LC), which requires a manual reset as described above. 38
43 17.0 SM-Basic DISPLAY MESSAGES The following describes the various displays and messages that can appear on the SCN drive SPEED DISPLAY If the drive is in a STOP state (indicated by "- -" on the display), and the keypad speed command is changed, the display will show the commanded speed, and the upper left decimal point will turn on solid. About five seconds after a change is made, the display will begin to alternate between the commanded speed value and the "- -" display. If the Mode button is pressed, the display will stop alternating and show the "- -" display only. When the drive is given a START command, the displayed speed will start increasing as the drive accelerates up to the commanded speed. If the keypad speed command is changed while the drive is running, the display will show the commanded speed rather than the actual speed, until the actual speed reaches the commanded speed. If the keypad speed command is changed faster than the drive can accelerate or decelerate, the upper left decimal point will blink to indicate that the the drive is accelerating or decelerating to the new speed. Once the actual speed reaches the commanded speed, the upper left decimal point will turn on solid for 5 seconds and then turn off to indicate that the commanded speed has been reached, and that the display is now showing the actual speed CHANGING THE SPEED REFERENCE SOURCE When the speed source is changed while the drive is running, the display will flash the message for the new speed source to indicate that the new speed source is active. Also, if the drive is being controlled from a speed source other than the s and t buttons (speed pot, preset speed, etc), and one of the s or t buttons is pressed, the display will flash the present speed source message to indicate that the s and t buttons are invalid. Example 1: The drive is running and the present speed source is the keypad. TB-13A is programmed to select a speed pot signal as the speed source. When TB-13A is closed to TB-11, the display will flash EU to indicate that the speed source has changed to the speed pot signal. If the contact between TB-13A and TB-11 is opened, the display will flash CP to indicate that the speed source has changed back to the s and t buttons. Example 2: The speed source is a speed pot. If the s or t button is pushed, the display will flash EU to indicate that the present speed source is the speed pot and that the s and t buttons are invalid. Refer to the table below for the possible speed reference source displays: 39
44 DISPLAY SPEED SOURCE DISPLAYS DESCRIPTION CP CONTROL PAD: Speed is set using the and buttons on the front of the drive. EU EXTERNAL VOLTAGE: Speed is controlled by a speed pot. JG JOG: The drive is in Jog mode, and the speed is set by Preset Speed #2 (Parameter 32). OP MOP (Motor Operated Pot): Contacts wired to two of the TB-13 terminals are used to increase and decrease the drive speed. See Parameters 10, 11, and 12. P1 - P7 PRESET SPEEDS #1-7: Speed is set by the indicated Preset Speed (Parameters 31-37). NOTE: The speed source displays will flash when the speed reference source is changed while the drive is running to indicate that the new speed reference source is active STATUS AND WARNING MESSAGES STATUS AND WARNING MESSAGES DISPLAY DESCRIPTION br DC BRAKING: The DC braking circuit is activated. ce COMPATIBLE EPM: An EPM with a previous parameter version has been installed, and an attempt was made to change the programming. The drive will operate with the EPM installed, but the parameters cannot be changed. Refer to setting 06 (TRANSLATE) in Parameter 48. CL CURRENT LIMIT: The output current has exceeded the CURRENT LIMIT setting (Parameter 25) and the drive is reducing the output frequency to reduce the output current. If the drive remains in CURRENT LIMIT for too long, it can trip into a CURRENT OVERLOAD fault (PF). Er ERROR: Invalid data has been entered or an invalid command was attempted. GE "GE" will be displayed if an attempt is made to change the OEM default settings when the drive is operating in the OEM mode (see Parameter 48). GF If "GF" is displayed when a RESET OEM is attempted, it indicates that the OEM defaults in the EPM are corrupted. If "GF" is displayed upon power-up, it indicates that the OEM defaults and the user settings in the EPM are corrupted. Refer to Section LC FAULT LOCKOUT: The drive has failed three restart attempts and now requires a manual reset. SP START PENDING: "SP" blinks during the interval between restart attempts. DECEL OVERRIDE (both upper decimal points blinking): The drive has stopped decelerating to avoid tripping into an HF fault due to regenerative energy from the motor. 40
45 18.0 USER SETTING RECORD NO. PARAMETER NAME FACTORY DEFAULT USER SETTING 01 LINE VOLTAGE HIGH (01) 02 CARRIER FREQUENCY 6 khz (02) 03 START METHOD NORMAL (01) 04 STOP METHOD COAST (01) 05 STANDARD SPEED SOURCE KEYPAD (01) 06 TB-14 OUTPUT NONE (01) 10 TB-13A FUNCTION SELECT NONE (01) 11 TB-13B FUNCTION SELECT NONE (01) 12 TB-13C FUNCTION SELECT NONE (01) 14 CONTROL TERMINAL STRIP ONLY (01) 17 ROTATION FORWARD ONLY (01) 18 TIME RANGE SELECT x1.0 (02) 19 ACCELERATION TIME 20 SEC 20 DECELERATION TIME 20 SEC 21 DC BRAKE TIME 0 SEC 22 DC BRAKE VOLTAGE 0 % 23 MINIMUM FREQUENCY 0 Hz 24 MAXIMUM FREQUENCY 60 Hz 41
46 NO. PARAMETER NAME FACTORY DEFAULT USER SETTING 25 CURRENT LIMIT 180% 26 MOTOR OVERLOAD 100% 27 BASE FREQUENCY 60 Hz 28 FIXED BOOST 1% 29 ACCEL BOOST 0% 30 SLIP COMPENSATION 0% PRESET SPEEDS 0 Hz 38 SKIP BANDWIDTH 0 Hz 42 ACCEL / DECEL #2 20 SEC 44 PASSWORD CLEAR HISTORY MAINTAIN (01) 48 PROGRAM SELECTION USER SETTINGS (01) 50 FAULT HISTORY (N/A) 51 SOFTWARE CODE (N/A) 52 DC BUS VOLTAGE (N/A) 53 MOTOR VOLTAGE (N/A) 54 LOAD (N/A) 55 SPEED POT INPUT (N/A) 57 TB STRIP STATUS (N/A) 58 KEYPAD STATUS (N/A) 42
47 4/00 Service Dept. FAX (262)
REGAL-BELOIT. Installation and Operation Manual. Variable Speed AC Motor Drives. Micro and PowerWash Series
REGAL-BELOIT Variable Speed AC Motor Drives Micro and PowerWash Series Installation and Operation Manual Manual Number: SB184 TABLE OF CONTENTS 1.0 GENERAL................................................1
MC1000 Series Installation and Operation Manual
MC1000 Series Installation and Operation Manual NOTE! The manual covers software version M108314 and above. Refer to parameter 63 for the software version of the drive you are working with. If you are
SPEEDMASTER MICRO SERIES COMPACT INVERTERS
SPEEDMASTER MICRO SERIES COMPACT INVERTERS Installation and Operation Manual EC Declaration of Conformity TABLE OF CONTENTS 1.0 GENERAL....................................................... 2 PRODUCT
GPD 506/P5 Start-up Procedure and Checklist
GPD 506/P5 Start-up Procedure and Checklist Preparation for GPD506/P5 Drive Start-Up...2 HVAC Start-Up Procedure for GPD 506/P5 WITH Bypass Option:...4 HVAC Start-Up Procedure for GPD 506/P5 WITHOUT Bypass
A1000 Cheat Sheet (Open Loop Vector)
A1000 Cheat Sheet (Open Loop Vector) The following procedure is a supplement to supplied with this equipment and will guide the user in properly wiring the A1000 and. It will also show the user how to
Bulletin 150 Smart Motor Controllers SMC-3 Smart Motor Controller
Overview/Modes of Operation Bulletin 150 Smart Motor Controller The SMC-3 is a compact, simple to use, solid-state motor controller designed to operate 3-phase motors. It features a built-in overload relay
GENERATOR START CONTROL MODULE - MINI (2 Wire to 3 Wire)
FEATURES & APPLICATIONS Inexpensive 2 wire to 3 wire start controller for electric start high speed gas generators. Optimized for use with Outback Invertors. Supports three types of 3 wire generator control
NX Series Inverters. HVAC Pocket Programming Guide
NX Series Inverters HVAC Pocket Programming Guide HVAC Pocket Programming Guide HVAC Pocket Programming Guide / Contents This guide provides a single reference document for the user of NXL HVAC (product
Single Phase Soft Starter
Single Phase Soft Starter Installation & Operating Manual 6/02 Table of Contents Section 1 General Information................................................... 1 1 General Description................................................
SAFETY INSTRUCTIONS WARNING
Important User Information Thank you for purchasing LS Variable Frequency Drives! SAFETY INSTRUCTIONS Always follow safety instructions to prevent accidents and potential hazards from occurring. In this
CONSTRUCTION STANDARDS DIVISION 23 HEATING VENTILATING AND AIR CONDITIONING
PART 1-GENERAL 1.01 DESCRIPTION A. This specification is to cover a complete Variable Frequency motor Drive (VFD) consisting of a pulse width modulated (PWM) inverter designed for use on a standard NEMA
MTE SERIES RLW. World REACTORS USER MANUAL PART NO. INSTR 030 REL. 090930. 2009 MTE Corporation
MTE SERIES RLW World REACTORS USER MANUAL PART NO. INSTR 030 REL. 090930 2009 MTE Corporation IMPORTANT USER INFORMATION NOTICE MTE Series RLW reactors are components designed to improve the reliability
Bulletin 150 SMC Flex Smart Motor Controller Specifications
Specifications Specifications Standard Features Optional Features Installation Setup Communications Power Wiring Control Wiring Keypad Software Starting and Stopping Modes Protection and Diagnostics Metering
MC Series Drives. Flexible, simple, rugged, robust! Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.actechdrives.com - Email: info@actechdrives.
Drives Flexible, simple, rugged, robust! Our promise Commitment to Price Leadership Price leadership is serious business. It takes continuous life cycle management to make price leadership a sustainable
AC ADJUSTABLE SPEED DRIVES MICRO SERIES INVERTERS
MICRO SERIES INVERTERS MICRO SERIES INVERTER DRIVES Full feature, ultra-friendly operation. Programs and reads-out in plain English. Intelligent Power Module-IGBT s with a 16 bit Intel microprocessor.
543-0032-00, 943-0032-00. User s Manual
543-0032-00, 943-0032-00 User s Manual 1 Comfort Alert Diagnostics Faster Service And Improved Accuracy The Comfort Alert diagnostics module is a breakthrough innovation for troubleshooting heat pump and
ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL
RANCO INSTALLATION INSTRUCTIONS ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL Relay Electrical Ratings PRODUCT DESCRIPTION The Ranco ETC is a microprocessor-based family of electronic temperature controls,
..OR How To Protect your 3-Phase Equipment Investment with 3-Phase Monitors from Time Mark...
..OR How To Protect your 3-Phase Equipment Investment with 3-Phase Monitors from Time Mark... TIME MARK CORPORATION 11440 EAST PINE STREET TULSA, OK 74116 USA tel 918 438-1220 fax 918 437-7584 www.time-mark.com
Specifying a Variable Frequency Drive s
Specifying a Variable Frequency Drive s Put on by Bruce Reeves and Jeremy Gonzales Dykman Electrical Covering the Western US For all of your VFD and Soft Start and Motor Needs How To Specify a Variable
LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA. General Specification
08/17/12 Rev2 LTR Series General Specification 700 VA to 2.1 KVA 1.0 General LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA General Specification This specification describes the features and
Oil and Coolant Circulating Heating System. Model - OCSM
Oil and Coolant Circulating Heating System Model - OCSM Installation & Operation Manual 216280-000 REV 2 Identifying Your System The HOTSTART heating system is designed to heat fluids for use in marine
Advantium 2 Plus Alarm
ADI 9510-B Advantium 2 Plus Alarm INSTALLATION AND OPERATING INSTRUCTIONS Carefully Read These Instructions Before Operating Carefully Read These Controls Corporation of America 1501 Harpers Road Virginia
SAFETY INSTRUCTIONS WARNING
Thank you for purchasing LG Variable Frequency Drives! SAFETY INSTRUCTIONS Always follow safety instructions to prevent accidents and potential hazards from occurring. In this manual, safety messages are
KBIC Solid State SCR DC Motor Speed Controls See table 2 page 4 for KBIC models covered by this manual
KBIC Solid State SCR DC Motor Speed Controls See table 2 page 4 for KBIC models covered by this manual Patented Ultra Fast CL Circuit Prevents Demagnetization in PM Motors Installation and Operating Instructions
Match. GE Digital Energy. Uninterruptible Power Supply 500-1500 VA. Technology for the Digital World. Match UPS. GE Digital Energy.
Match Uninterruptible Power Supply 500-1500 VA Manufactured by: General Electric Company Telephone +41 (0)91 / 850 51 51 CH 6595 Riazzino (Locarno) Fax +41 (0)91 / 850 51 44 Switzerland Website www.gedigitalenergy.com
BroadBand PowerShield. User Manual
BroadBand PowerShield User Manual 990-0375G 12/2006 Chapter 1 General Information The PowerShield provides a power source for broadband telephony and other DC applications. Safety This Safety Guide contains
BT300 HVAC Drives Conventional Bypass (C-Bypass) Options
BT300 HVAC Drives Conventional Bypass (C-Bypass) Options Description The BT300 Conventional Bypass is a companion package for the family of BT300 HVAC Drives. For information on the family of BT300 HVAC
VLT Series 3500 Adjustable Frequency Drive Instruction Manual
Adjustable Frequency Drive Instruction Manual VLT Series 3500 Instruction Manual 175R5237 - Document Version 5.00 This manual applies to all VLT Series 3502-3800 Adjustable Frequency Drives with software
VLT 6000 HVAC. Contents
Contents Introduction Safety...3 Safety Guidelines...3 Warnings Against Unintended Start...3 Introduction...4 About this manual...4 Assumptions...4 References...4 Trademarks...5 Programming the VLT 6000
SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS
SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS TABLE OF CONTENTS 1. Warnings...2 2. Accessibility Of Appliance...3 3. Unit Dimensions And Specifications...3 4. Unit Specifications
AGS. Owner's Manual. Xantrex Automatic Generator Start Control System
AGS Owner's Manual Xantrex Automatic Generator Start Control System TABLE OF CONTENTS INTRODUCTION...3 Main Features...3 Safety Summary...3 THINGS YOU SHOULD KNOW...4 THEORY OF OPERATION...5 System...5
LS1024B / LS2024B/ LS3024B. Solar Charge Controller USER MANUAL
EPSOLAR LS1024B / LS2024B/ LS3024B Solar Charge Controller USER MANUAL Thank you very much for selecting our product! This manual offers important information and suggestions with respect to installation,
32VFD Variable Frequency Drives for Centrifugal Chillers
32VFD 32VFD Variable Frequency Drives for Centrifugal Chillers ENERGY-SAVING CONTROL FOR CENTRIFUGAL CHILLERS Reduce energy consumption in your existing centrifugal chiller Your chiller was specified to
Installation and Operating Manual
DC DRIVE BC138 BC139 DC CONTROL Installation and Operating Manual 7/2001 MN708 TABLE OF CONTENTS Section Page i. Simplified Operating Instructions.......................................... 1 ii. Safety
T7560A,B,C Digital Wall Module
T7560A,B,C Digital Wall Module HONEYWELL EXCEL 5000 OPEN SYSTEM BEFORE INSTALLATION All wiring must comply with local electrical codes and ordinances or as specified on installation wiring diagrams. Digital
RI-215A Operator s Manual. Part Number: 71-0045RK Revision 0 Released: 10/3/05
RI-215A Operator s Manual Part Number: 71-0045RK Revision 0 Released: 10/3/05 Warranty RKI Instruments, Inc., warrants gas alarm equipment sold by us to be free from defects in materials and workmanship,
EnVisioneering. www.danfossdrives.com
EnVisioneering As a world leader in components and solutions, Danfoss meets our customers challenges through EnVisioneering. This approach expresses our views on engineering innovation, energy efficiency,
Industrial-Grade UPS System Heavy-duty power protection for harsh industrial environments
Industrial-Grade UPS System Heavy-duty power protection for harsh industrial environments Model #: SM2000RMX Heavy-duty, industrial-grade metal housings Shock and vibration rated to MIL-STD-810D 19 inch
BLWR23MDA Series. 24V, 15A Brushless Controller / Motor. User s Guide. 910 East Orangefair Lane, Anaheim, CA 92801 e-mail: info@anaheimautomation.
BLWR23MDA Series 24V, 15A Brushless Controller / Motor User s Guide A N A H E I M A U T O M A T I O N 910 East Orangefair Lane, Anaheim, CA 92801 e-mail: [email protected] (714) 992-6990 fax:
AMFA-27 AMFA-29. Operator s Manual & Installation Instructions. Rev. 2.5
AMFA-27 AMFA-29 Operator s Manual & Installation Instructions Rev. 2.5 Date: 17 July, 2010 Permanently-connected, utility Interactive, single-phase, inverters Model AMFA-27 WIND TURBINE INVERTER (240 VAC
Installation & Operation Manual for Energenics Air-Flow Optimizer
1470 Don Street Naples, Florida 34104 Telephone: (239) 643-1711 Fax: (239) 643-6081 Customer Service: (800) 944-1711 Installation & Operation Manual for Energenics Air-Flow Optimizer Table of Contents
SECTION 26 29 23 VARIABLE FREQUENCY DRIVES
SECTION 26 29 23 VARIABLE FREQUENCY DRIVES PART 1 GENERAL 1.01 SCOPE A. Furnish and install individual freestanding variable frequency AC drives (VFD) as shown on the Drawings and specified herein. 1.02
Back-UPS 650 VA 120 V with AVR (BX650CI-LM)
Back-UPS 650 VA 120 V with AVR (BX650CI-LM) Overview Do not install the unit in direct sunlight, in areas of excessive heat or humidity, or in contact with fluids ON/OFF button Battery connector Circuit
User Manual THR840DUK Digital Thermostat
User Manual THR840DUK Digital Thermostat 50051982-001 Rev. A WARNING: This product must be correctly installed and configured to work properly (see pages 12-24). If you are not experienced in wiring electrical
Master Time Clock MTC-200 MTC-400 MTC-600. Users Manual
Master Time Clock MTC-200 MTC-400 MTC-600 Users Manual Toll Free (888)713-0373 Phone (972)987-4408 FAX (877)720-9291 www.midwest-time.com [email protected] TABLE OF CONTENTS TOPIC PAGE GENERAL DESCRIPTION
INSTALLER S & OWNER S MANUAL
INSTALLER S & OWNER S MANUAL HVAC INSTALLER: PLEASE LEAVE MANUAL FOR HOMEOWNER DEH 3000 DEH 3000 Part No. 4028539 Dehumidifier & Ventilation System Controller P.O. Box 8680 Madison, WI 53708 TOLL-FREE
REB 1 REB 3 REB 5 REB 6 REB 8 REB 10 REB 12 REB 16
REB 1 REB 3 REB 5 REB 6 REB 8 REB 10 REB 12 REB 16 Manually Operated Electronic Speed Controller Single Phase For all applications using suitably specified single-phase induction motor fans 1 GENERAL The
SAFETY INSTRUCTIONS. Always follow safety instructions to prevent accidents and potential hazards from occurring.
Thank you for purchasing LS Variable Frequency Drives! SAFETY INSTRUCTIONS Always follow safety instructions to prevent accidents and potential hazards from occurring. In this manual, safety messages are
Installation, Operation and Maintenance Manual
Installation, Operation and Maintenance Manual VLT 6000 Series Adjustable Frequency Drive 12/01 23-6108-00 Revision K Rotating shafts and electrical equipment can be hazardous. Therefore, it is strongly
Installing the Tracer ZN517 Unitary Controller Ordering number: 4950 0496, 4950 0596
Installing the Tracer ZN517 Unitary Controller Ordering number: 4950 0496, 4950 0596 Product overview The Tracer ZN517 controller is a field-installed, application-specific controller that provides directdigital
DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS
Features: INSTALLATION Install in accordance with NFPA 70. DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS Up to 1.95 Amps Load Capacity Class 2 Rated Outputs Overload, Over Voltage, and Short
VARIABLE FREQUENCY DRIVES Revised 4/30/2015 23 81 07-1 Mechanical Systems
SECTION 23 81 07 - VARIABLE FREQUENCY DRIVES PART 1 - GENERAL 1.1 SUMMARY A. This section includes all variable frequency drives. All standard and optional features shall be included within the VFD panel
CQM1-SF200/CS1W-SF200
Safety Relay Unit ( I/O Unit Type) CQM1-SF200/CS1W-SF200 CSM_CQM1-SF200_CS1W-SF200_DS_E_2_1 A Safety Relay Unit That Functions as a I/O Unit. Less Installation Space and Wiring Required. Safety Relay Unit
Installation & Operation Manual Dial-A-Flow Adjustable Frequency Drives
GM 04-13 Installation & Operation Manual Dial-A-Flow Adjustable Frequency Drives for 1/8 HP thru 1HP 3-Phase AC Motors rated 208 230 VAC, 50 & 60 Hz NEMA-1 / IP-40 Operates from 115 and 208/230 Volt 50/60
VSD Series Drives. November 2009 Supersedes September 2006. Powered by Eaton Technology. User Manual
Powered by Eaton Technology VSD Series Drives User Manual Supersedes September 2006 LIT-1201828 For more information visit: www.johnsoncontrols.com Powered by Eaton Technology VSD Series Drives User Manual
Digital echo-charge. Owner s Manual. Xantrex Digital echo-charge Battery Charger
Digital echo-charge Owner s Manual Xantrex Digital echo-charge Battery Charger Thank you for purchasing a Xantrex Digital echo-charge. Xantrex Technology Inc. takes pride in manufacturing quality products
Analog Servo Drive 25A8
Description Power Range NOTE: This product has been replaced by the AxCent family of servo drives. Please visit our website at www.a-m-c.com or contact us for replacement model information and retrofit
TECHNICAL SPECIFICATIONS FOR 1.5 KVA ONLINE UPS
Capacity Technology Inverter Technology Noise Level Operating Temperature Humidity Harmonic Distortion Total DC bus voltage Battery recharge time (After Complete discharge) to 100% charge Crest Factor
Operating Manual. Los Angeles Abrasion Machine HM-70A & HM-70AF
Operating Manual Los Angeles Abrasion Machine HM-70A & HM-70AF Rev: 07/19/2012 PHONE: 800-444-1508 P.O. Box 200, Lewis Center, Ohio 43035-0200 FAX: 800-255-5314 740-548-7298 E-mail: [email protected]
MODEL 2202IQ (1991-MSRP $549.00)
F O R T H E L O V E O F M U S I C F O R T H E L O V E O F M U S I C MODEL 2202IQ (1991-MSRP $549.00) OWNER'S MANUAL AND INSTALLATION GUIDE INTRODUCTION Congratulations on your decision to purchase a LINEAR
MDC151-024031 Series
MDC151-024031 Series 24V, 3A Brushless DC Controller User s Guide A N A H E I M A U T O M A T I O N 910 East Orangefair Lane, Anaheim, CA 92801 e-mail: [email protected] (714) 992-6990 fax: (714)
PowerFlex Dynamic Braking Resistor Calculator
Application Technique PowerFlex Dynamic Braking Resistor Calculator Catalog Numbers 20A, 20B, 20F, 20G, 22A, 22B Important User Information Solid-state equipment has operational characteristics differing
FlexPak 3000 Digital DC Drive Software Reference Manual Version 4.3
FlexPak 3000 Digital DC Drive Software Reference Manual Version 4.3 Instruction Manual D2-3405-2 The information in this manual is subject to change without notice. Throughout this manual, the following
USER MANUAL WARNING! CONTENTS MODEL 1 SPECIFICATIONS READ ALL INSTRUCTIONS BEFORE PROCEEDING. Non-Programmable Single Stage Heat/Cool Thermostat
Builder MODEL 1010 Series Non-Programmable Single Stage Heat/Cool Thermostat USER MANUAL Compatible with low voltage single stage gas, oil or electric heating or cooling systems, including single stage
VCM Installation and Operations Manual. Table of Contents
Table of Contents VCM Installation and Operations Manual 1.0 Introduction... 1 2.0 Product Inspection... 2 2.1 Nameplate Layout... 2 3.0 Operating Precautions... 3 3.1 Before Power up... 3 3.2 During Power
SMVector - Frequency Inverter
SMVector - Frequency Inverter Operating Instructions Contents 1 Safety Information...3 2 Technical Data...5 2.1 Standards and Application Conditions...5 2.2 Ratings...6 2.2.1 NEMA 1 (IP 31) Ratings...6
SmartOnline 200-240V 5kVA 4.5kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 4U Rack/Tower, USB, DB9 Serial
SmartOnline 200-240V 5kVA 4.5kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 4U Rack/Tower, USB, DB9 Serial MODEL NUMBER: SU5000RT4UHV Description Tripp Lite SU5000RT4UHV 5000VA / 5kVA /
2011 Industrial Catalog. DRIVES, PAC, PLCs. Industrial Catalog 2011. www.toshiba.com/ind
www.toshiba.com/ind 2011 Toshiba International Corporation Rev. 110504 Industrial Catalog 2011 13131 W. Little York Road Houston, TX 77041 Tel: 713-466-0277 Fax: 713-466-8773 US: 800-231-1412 Canada: 800-872-2792
26 3213.13 Diesel Engine Driven Generators Page 1 of 6
Last Update: December 8, 2014 A. Description of System Consultant s Handbook Page 1 of 6 1. Provide a diesel engine driven electric generating unit, factory assembled, tested and certified to operate at
SmartPro 120V 2.2kVA 1.92kW Line-Interactive Sine Wave UPS, SNMP, Webcard option, 2U Rack/Tower, LCD, USB, DB9 Serial
SmartPro 120V 2.2kVA 1.92kW Line-Interactive Sine Wave UPS, SNMP, Webcard option, 2U Rack/Tower, LCD, USB, DB9 Serial MODEL NUMBER: SMART2200RM2U Highlights 2.2kVA / 2200VA / 1920W line interactive 2U
User s Manual AURORA 1.2K/2.2K
User s Manual AURORA 1.2K/2.2K Uninterruptible Power System Safety CAUTION This UPS utilizes voltages that may be hazardous. Do not attempt to disassemble the unit. The unit contains no user serviceable
Name of Equipment Silver King Model SKMCD1P/C1. This equipment chapter is to be inserted in the appropriate section of the Equipment Manual.
Name of Equipment Silver King Model SKMCD1P/C1 This equipment chapter is to be inserted in the appropriate section of the Equipment Manual. Manufactured exclusively for McDonald s By Silver King Refrigeration,
VARI-DRIVE NEMA1 / IP20 SCR Variable Speed DC Motor Controls
TM TM INSTALLATION AND OPERATING INSTRUCTIONS VARI-DRIVE NEMA1 / IP20 SCR Variable Speed DC Motor Controls Model KBWM-120 rated 1/100-1/3 HP (90 Volts DC) @ 115 Volts AC, 50/60 Hz Model KBWM-240 rated
Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact
Data sheet Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact The CT-AHD.12 is an electronic time relay with OFF-delay. It is from the CT-D range. With their MDRC profile and a width of only
SUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original
SUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original A motor starter is a combination of devices to allow an induction motor to start, run and stop according
Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000
Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000 Description Firetrol FTA1000 Full Voltage Fire Pump Controllers are intended for use with electric motor driven fi re pumps
Transfer Equipment Controls
Control Types Manual Transfer Switches Nonautomatic Transfer Switches Automatic Transfer Switches The type of control system for the transfer switch will vary depending on the type of switching equipment
ATS Overhead Table Shelf System INSTRUCTION MANUAL
ATS Overhead Table Shelf System INSTRUCTION MANUAL ATS Overhead Table Shelf System Instruction Manual Warranty Newport Corporation warrants this product to be free of defects in material and workmanship
User's Guide. Integrating Sound Level Datalogger. Model 407780. Introduction
User's Guide 99 Washington Street Melrose, MA 02176 Phone 781-665-1400 Toll Free 1-800-517-8431 Visit us at www.testequipmentdepot.com Back to the Extech 407780 Product Page Integrating Sound Level Datalogger
CPCI-3U-AC-300W-R. Rugged 300W AC Input 3U CompactPCI Power Supply. Electrical Specification for: Telkoor Part Number: 900-4602-0000
Electrical Specification for: CPCI-3U-AC-300W-R Rugged 300W AC Input 3U CompactPCI Power Supply Telkoor Part Number: 900-4602-0000 GENERAL SCALE RELEASE DATE 12/9/06 SHEET 1 OF 6 REVISION HISTORY Rev Level
Installation and Operation Manual Back-UPS BX800CI-AS/BX1100CI-AS
+ Installation and Operation Manual Back-UPS BX800CI-AS/BX1100CI-AS Inventory Safety and General Information bu001c This unit is intended for indoor use only. Do not operate this unit in direct sunlight,
EPM3. Phase Sequence and Motor Rotation Tester. Users Manual
EPM3 Phase Sequence and Motor Rotation Tester Users Manual 1 L1 L2 L3 2 3 A B C CAT 600V 3-PHASE TESTER 5 TEST M1 M2 BATT M3 EPM3 MOTOR ROTATION TESTER EPM3 MOTOR ROTATION DETERMINED WHILE FACING MOTOR
SmartOnline 200-240V 6kVA 4.2kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 6U Rack/Tower, DB9 Serial, Hardwire
SmartOnline 200-240V 6kVA 4.2kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 6U Rack/Tower, DB9 Serial, Hardwire MODEL NUMBER: SU6000RT3UHV Highlights 6000VA / 6kVA / 4200W on-line double-conversion
MCR1900 Media Converter 19-Slot Chassis
MCR1900 Media Converter 19-Slot Chassis Installation Guide Part #5500304-11 Copyright Statement This document must not be reproduced in any way whatsoever, either printed or electronically, without the
TABLE OF CONTENTS. Fig. 1 EV Pictorial Wiring Diagram 5. Section 2 Inverter Option Modules 6
TABLE OF CONTENTS Introduction.. 3 Section 1 Safety Precautions.. 3 1.1 Preface.. 3 1.2 Receiving and Inspection... 3 1.3 Installation and Pre-operation 4 1.4 During Power ON. 4 Fig. 1 EV Pictorial Wiring
0150506194 C Limited 2nd through 5th Year Functional Parts Warranty During the 2nd through 5th year,haier will provide functional parts which prove to be defective due to workmanship
MOVFR ELECTRICAL ADJUSTMENTS. G.A.L. MFG. CORP. NEW YORK CITY U.S.A. http://www.gal.com
MOVFR ELECTRICAL ADJUSTMENTS G.A.L. MFG. CORP. NEW YORK CITY U.S.A. http://www.gal.com 1 ELECTRICAL ADJUSTMENTS ADJUSTING INSTRUCTIONS FOR THE G.A.L. VARIABLE FREQUENCY CLOSED LOOP DOOR OPERATOR TYPE MOVFR
Panel Mounted Air Conditioners by Dantherm, Inc.
Panel Mounted Air Conditioners by Dantherm, Inc. CS020020A/B with USACG-6 Control PRODUCT INFORMATION MANUAL AC-2 CS020020 USACG-6 Manual Rev H Page 1 of 17 Dantherm, Inc. 110 Corporate Drive, Suite K
Water Leak Detection System
Water Leak Detection System Installation and Operating Manual 505-334-5865 ph 505-334-5867 fax www.rodisystems.com email:[email protected] 936 Highway 516 Aztec, NM 87410-2828 Manual Revisions and Copyright
INSTRUCTION MANUAL PHOENIX DX 3 TO 3500 HP SENSORLESS VECTOR AC DRIVE
INSTRUCTION MANUAL PHOENIX DX 3 TO 3500 HP SENSORLESS VECTOR AC DRIVE Thank You We at US Drives would like to say thank you for purchasing our product. We believe the Phoenix AC Drive Series is the most
AUTOMATIC TRANSFER SWITCH CONTROL UNIT OPERATOR S MANUAL
ATS-220 AUTOMATIC TRANSFER SWITCH CONTROL UNIT OPERATOR S MANUAL For Use in 208 to 240 Volts Single and 3 Phase ATS Systems With 110Volt AC or DC Control Motors and selenoids 4501 NW 27 ave Miami FL 33142
HCS-3300/3302/3304 USB Remote Programmable Laboratory Grade Switching Mode Power Supply
1. INTRODUCTION HCS-3300/3302/3304 USB Remote Programmable Laboratory Grade Switching Mode Power Supply User Manual This family of efficient, upgraded SMPS with small form factor, auto cross over CV CC,
Specification Requirements DBL 700MX and 1000MX Series UPS
Specification Requirements DBL 700MX and 1000MX Series UPS Theory of Operation Upon loss of utility power, the UPS inverter shall continue to provide seamless pure sine-wave AC from the batteries without
XC120 XC180. Owner's Guide Conforms to / Conforme à UL std. 458, Toll Free 1 866 295 6775. www.powerbright.com
WARNING: This Unit employs Components that tend to produce arcs or sparks To prevent fire or explosion, do not install in compartments containing batteries or flammable materials - SHOCK HAZARD. DO NOT
Addendum to the Operating Instructions
Drive Technology \ Drive Automation \ System Integration \ Services Addendum to the Operating Instructions MOVIMOT with AS-Interface and AC Motor DT/DV Unit Replacement MOVIMOT MM..C -> MM..D with MLK3A
BLY17MDA Series. 24V, 10A Brushless Controller/Motor. User s Guide. 910 East Orangefair Lane, Anaheim, CA 92801 e-mail: info@anaheimautomation.
BLY17MDA Series 24V, 1A Brushless Controller/Motor User s Guide A N A H E I M A U T O M A T I O N 91 East Orangefair Lane, Anaheim, CA 9281 e-mail: [email protected] (714) 992-699 fax: (714) 992-471
Daker DK 1, 2, 3 kva. Manuel d installation Installation manual. Part. LE05334AC-07/13-01 GF
Daker DK 1, 2, 3 kva Manuel d installation Installation manual Part. LE05334AC-07/13-01 GF Daker DK 1, 2, 3 kva Index 1 Introduction 24 2 Conditions of use 24 3 LCD Panel 25 4 Installation 28 5 UPS communicator
Instructions & Safety Information Models A220-20D and A220-20L Version 2
Quick 220 Voltage Converting Power Supply Instructions & Safety Information Models A220-20D and A220-20L Version 2 Quick 220 Systems LLC PO Box 47489 Phoenix, Arizona 85068-7489 800-347-0394 602-938-6057
LDO03C/LDO06C/LDO10C
NEW LDO03C/LDO06C/LDO10C A p p l i c a t i o n N o t e 1 8 6 1. Introduction 2 2. Models Features 2 3. General Description Electrical Description 2 Physical Construction 2 4. Features and Functions Wide