Cabling Standards and Guidelines Commonwealth of Massachusetts
|
|
|
- Jeremy Alexander
- 10 years ago
- Views:
Transcription
1 Cabling Standards and Guidelines Commonwealth of Massachusetts Information Technology Division Cabling Standards and Guidelines Version 2.2 August 2002 Document History Date Version Number Summary 1995 Version 1.0 Developed by the Network standards subcommittee of the Governor s Advisory Council on Information Technology (GACIT), chaired by James Herman and comprised of personnel from various Commonwealth agencies. Version 2.0 Revisions drafted by ITD s Strategic Planning Bureau with input from other ITD staff and the wiring blanket contract vendors. July 1998 Version 2.1 Revisions drafted by ITD's Strategic Planning Bureau with the assistance of GTE Internetworking. August Version 2.2 Revisions drafted by the Wiring Standards and Guidelines 2002 Group chaired by Joseph Hickey, ITD Telecommunications System Manager
2 Date Version Number Summary Table of Contents: Foreword 1.0 Introduction 2.0 Industry Standards and Practices 3.0 System Overview 4.0 System and Cabling Topology 5.0 Specification of Cable and Work Area Outlet 6.0 Specification of Telecommunications Rooms (TR) 7.0 Administrative and Management Requirements Appendix A: Guidelines for Telecommunications Rooms Appendix B: Guidelines for Equipment Rooms Appendix C: Specifications for System Cabling and Components I. General System Specifications II. III. IV. Voice Twisted Pair Station Cable Data Twisted Pair Station Cable Communications Outlet Specifications V. Voice Riser/Distribution Cables VI. VII. VIII. IX. Voice Riser/Distribution Cable Terminations Data Riser/Distribution Cables Data Riser/Distribution Cable Terminations Fiber Riser and Distribution System X. Cable Documentation Appendix D: Wireless System Cabling and Components
3 Document Authors Foreword A well designed and implemented generic cabling system within Commonwealth buildings can save agencies significant dollars and can make it much easier for the Commonwealth to implement new Information Technology systems. As an analogy - one does not worry when moving from one office to another whether there will be power in the new office, or whether they will be able to plug in and use their favorite desk lamp; a generic cabling system can provide the same level of functionality and ubiquity for telecommunications and office computer systems. This revision of the Cabling Standards and Guidelines has been drafted by the Wiring Standards and Guidelines group chaired by Joseph Hickey and comprised of personnel from various Commonwealth agencies and industry professionals. For a list of group participants please, see the Document Authors section at the end of this document. This revision of the Cabling Standards and Guidelines document updates requirements to conform to the latest industry standards and practices. The design of non-proprietary cabling standards is a very active area of work within the industry, and the Commonwealth. This document takes advantage of the Commonwealth's experience and the relevant body of work by referring to current industry standards and practices from the ANSI, TIA/EIA, IEEE, and BICSI whenever possible. In the same vein however, industry practice will continue to change, and therefore there will be a continued need to update this document accordingly. Please contact the Information Technology Division at with your comments, suggestions, and questions. 1.0 Introduction The purpose of a cabling system within a building or group of buildings is to provide interconnection between communication devices. These devices can be telephones, computer terminals, personal computers, faxes, and the devices such as servers, bridges, and routers that make up a Local Area Network (LAN) and Wide Area Networks (WAN). In a small office with only a few computers, it is a fairly straightforward exercise to interconnect the devices as needed. However, once there are more than a handful of machines, it is necessary to use a structured cabling system to
4 interconnect them. This cabling system shall be a generic structured cabling system, which can support both your current and future communication systems. A generic structured cabling system based on unshielded twisted pair cable, which is what this document addresses and provides the following benefits for the Commonwealth: Support for multi-vendor equipment and services Improved management of building space resources Reduced costs for cabling installation, support, and management Reduced training requirements for personnel Consistency of cabling at different locations improved troubleshooting and fault isolation Improved ability to manage system moves, adds, and changes System based on proven ANSI, TIA/EIA, IEEE and BICSI industry standards Given all of these benefits, there is virtually no reason today to establish a proprietary cabling scheme for the type of office environments used by Commonwealth agencies and departments. 2.0 Industry Standards and Practices This document is based on industry standards and we often refer to them rather than repeating sections from them in this document. The most relevant standards are noted below. These standards and related documents are available for viewing at ITD. EIA/TIA-568-B1, B.2, B.3 Commercial Building Telecommunications Cabling Standard and its appendix, and addendums as issued. ANSI/TIA/EIA-569-A569-ACommercial Building Standard for Telecommunications Pathways and Spaces EIA/TIA-570 -A Residential and Light Commercial Telecommunications Cabling Standard
5 EIA/TIA-606 Administrative Standard for the Telecommunications Infrastructure of Commercial Building ANSI/TIA/EIA-607 Commercial Building grounding and bonding requirements for telecommunications. ANSI/TIA/EIA-758 Customer owned outside plant telecommunications standards. BICSI Telecommunications Distribution Methods Manual FCC Docket and related rules regarding inside wire and demarcation points. IEEE Specifications and associated sections The National Electrical Code (NEC) NFPA-70 National Electrical Safety Code NESC The Electronics Industry Alliance (EIA) and Telecommunications Industry Association (TIA) American National Standards Institute (ANSI) are large industry trade groups with memberships drawn from all facets of the telecommunications industry. Technical committees draft ANSI/ EIA/TIA standards and these standards are reviewed every five years. The cabling standards noted above detail the architecture, engineering, cable specification and management of cabling systems. BICSI stands for Building Industry Consulting Service International, Inc. and it is an industry organization that provides training and certification in this area The BICSI manual provides a detailed description of cabling layout and installation. The IEEE is a professional engineering society. IEEE standards specify LAN architecture and engineering. ANSI is the American National Standards Institute responsible for issuing of documents. FCC is the Federal Communication Commission. NFPA is the National Fire Protection Association and is responsible for NFPA 70 National Electric Code (NEC). 3.0 System Overview A cabling system can be divided into several different types of building blocks, which include specific subsystems and cabling components. Since the interconnection of these building blocks is a classic system-engineering problem, it is helpful to study each subsystem individually, and then describe how they interconnect. This is the approach we take in this document.
6 The major subsystems below are referenced from ANSI/TIA/EIA 568B.1 for a cabling system include the following: Horizontal cabling (clause 4); Backbone cabling (clause 5); Work area (WA OUTLET) (clause 6); Telecommunications rooms (TR) (clause 7); Equipment rooms (ER) (clause 8); Entrance facilities (EF) (clause 9); Administration Combined Fiber and Copper Backbone The following figure illustrates a typical backbone arrangement for an installation requiring both voice and data services at the user stations.
7 Example of combined copper/fiber backbone supporting voice and data traffic Figure -1 The relationship between these subsystems can be seen schematically in Figure 1. The horizontal cabling distribution system is used to connect each user's telephone and computer equipment to the required communications systems on that floor. The backbone cabling distribution system provides the means of inter-connection of data and voice communications between telecommunication rooms including inter/and intra building cabling. The cables that are used for this include both copper and fiber optic cables. There may be more than one backbone cabling distribution system within a building since it is often practical from an implementation standpoint to logically subdivide the building. This is also done for disaster backup and redundancy.
8 The work area components extend from the telecommunications outlet/connector end of the horizontal cabling system to the workstation equipment. The workstation equipment can be any of a number of devices including but not limited to telephones, data terminals, and computers. A Telecommunications room (TR) is an enclosed spaced for housing telecommunications equipment, cable terminations, and cross-connects. The room is the recognized cross-connect between the backbone cable and horizontal cabling. Equipment rooms (ERs) a centralized space for telecommunications equipment that serves the occupants of a building. Equipment housed therein is considered distinct from a telecommunications room because of its nature or complexity. The entrance facility (EF) is an entrance to a building for both public and private network service cables (including antennae) including the entrance point at the building Wall and continuing to the entrance room or space. The components in this space consist of the cables, connecting hard Ware, protection devices, and other equipment needed to connect the outside plant facilities to the premises cabling. These components may be used for regulated access providers (e.g. local telephone companies); private network customer premises services, or both. The demarcation point between the regulated access providers and the customer premises cabling may be part of the entrance facility. Basic administration information is covered in various locations throughout this Standard. Detailed information regarding administration referred to ANSI/TIA/EIA System and Cabling Topology
9 Figure-2 The Commonwealth s standard for cabling topology is the star configuration. Star topology is a topology which telecommunications cables are distributed from a central point. The use of this star topology means that cables should not be run directly between adjacent floors to interconnect equipment. For example, assume that it was necessary to connect a terminal on the 12th floor to a computer system on the 14th floor in a building, which has a MC, located on the 10th floor. In this case, a cable should not be run between these two floors. Rather, cables from the TR on each floor, which connect to the MC, should be used, and the connection made via patch panels located in the MC. This is the case for both fiber and copper connections. 5.0 Specification of Cable and Communications Outlet
10 This standard specifies only two types of media for use within Commonwealth buildings: unshielded twisted pair (UTP) and multimode fiber (62.5/125 or 50/125) fiber optic cable. The use of other media such as shielded twisted pair (STP) and coax should be avoided since they provide no advantage and are more expensive and difficult to install and maintain. A minimum three ports per WA Outlet, one voice, two data, unless otherwise specified by agency. Category 6 UTP is required for both voice and data communications. For voice, horizontal station cable to all locations will consist of one (1) unshielded, 4 pair, 24 gauge copper, solid conductor, twisted pair category 6 cable enclosed by a thermoplastic jacket. For data, horizontal station cable to all locations will consist of two (2) unshielded, 4 pair, 24 gauge copper, solid conductor, twisted pair, and category 6 or higher rated cable as amendments are made to industry standards and enclosed by a thermoplastic jacket. As the industry and emerging technologies allow amendments to this document will be included to satisfy user needs. Cable jackets may be of different materials to meet different UL ratings, but are generally rated for either normal in-wall installation or plenum installation. Commercial buildings usually use plenum-rated wire because at least some of their runs are through air plenums (such as the space above suspended ceilings) associated with heating and cooling systems (HVAC). Building code usually requires plenum-rated wire to ensure a fire is less likely to cause burning insulation to contaminate the air system. In addition to the category printed on the cable jacket, cables have a fire rating with codes like MPP (Multi-Purpose Plenum), CMP (Communications Plenum), and CMR (Communications Riser). Cables to be run within plenums should have a fire rating code of CMP or MPP. Plenum-rated communications cables shall be third party NRTL listed in accordance with article , through 53. Plenum-rated fiber optic cables shall be third party NRTL listed in accordance with NEC sections through 53. CMP, (Plenum Cable) for use in plenum areas (air ducts) must pass UL 910 test for smoke and flame spread). ALL CABLE MUST MEET THE REQUIREMENTS OF THE NATIONAL ELECTRICAL CODE (NEC) EXCEPT WHERE OTHER AUTHORITIES OR CODES IMPOSE A MORE STRINGENT REQUIREMENT OR PRACTICE. PARTICULAR DILIGENCE TO THESE CODES MUST BE USED IF CABLE IS TO BE RUN WITHIN AIR PLENUMS. The technical specifications of category 6 UTP are currently defined in TIA/EIA 568-B.2.1. Category 6 cable is characterized for operation up to 250 MHz and it
11 is intended for data applications that operate up to 1000 Mbps. This means that category 6 cable can easily support 10BASE-T Ethernet at 10 Mbps, 100 Mbps Ethernet or 1000 Mbps Ethernet. It can also support several standard ATM transmission options. This document requires the use of this cable for voice and data so that once the cable is installed; it has the greatest breadth of applications. (Note however that if category 3 cable has already been installed for data, it does not necessarily need to be replaced. Replacement will be dictated by the speed requirements of the data application.) The general layout for floor cabling is shown in Figure 6. The maximum length of the horizontal subsystem for data applications should be 90 meters (295 feet) independent of media type. This is the actual cable length, not the walking distance, from the termination in the TR to the device in the work area outlet (Wall). The length of the data patch cords in the cross-connect facilities, including voice horizontal cross connect, and the data patch cords that connect horizontal cabling with equipment or back bone cabling shall not exceed 5 meters in length. Telecommunications Cable shall not be run near any source of EMI. Required clearances for electromagnetic isolation shall be a minimum of 6 inches, in accordance of the guidelines in ANSI TIA/EIA 569-A and Article 800 of ANSI/NFPA 70. The termination of the voice and data cable within the workspace is done at the WA Outlet. The WA Outlet is the modular interface used to connect the horizontal cabling to the user's equipment. Each WA Outlet shall have a minimum of three separate RJ45 modular connectors - one for voice and two for data. Each modular connector will terminate the UTP cable in an eight-position modular jack, which meets the requirements of EIA/TIA-568-B.2.1. All four pairs shall terminate at both ends. One end of each horizontal cable shall terminate in an 8-position, eight conductor category 6 modular jack. Splices and bridge taps are not allowed. The termination cabling shall be T568B
12 configuration. Figure-3 The modular connectors should be flush mounted in a WA Outlet, or by other secure means if WA Outlet mounting is not possible. Each workspace or work area shall have a minimum of one WA Outlet regardless of the size of the area. Private offices of approximately 100 square feet should have two WA Outlets and offices larger than 150 square feet should have 3 WA Outlets. Conference rooms and reception areas should have at least one WA Outlet. The number of WA Outlets in areas, which are used for printers, FAX machines, copy machines, etc., should be determined based on the anticipated use.
13 Both copper and fiber optic cable will be used within the Backbone cabling system (riser backbone system). All cable will be run in the star topology between the MC the building ER and each TR as previously described. Backbone cable for voice shall terminate four copper pairs per voice station with a minimum of 25% growth available to the next highest 100 pair. This voice cable will be a minimum 100 pair 24 gauges with overall jacket. All riser cable must meet NEC and fire codes. Riser cable for data shall be optical fiber. (Note however that if copper has already been installed as riser cable, it does not need to be replaced until the usage or application requires the installation of fiber.) There should be at least 24 strands of fiber optics installed between the MC/ER and each TR. If more than one TR is located on a floor, the need for distribution cable (fiber optic or UTP cable) between them should be determined as part of the system cabling design. Additional requirements for these cabling components are summarized in an appendix to this document. 6.0 Specification of Telecommunications Rooms (TR) There are three different types of TRs and they each support critical functions as part of the building cabling system. In general, each room must be large enough to accommodate the cabling and equipment, which will be located within them, plus additional space allocated for growth. The general environmental requirements include sufficient power and HVAC, plus they must be secure, and they must meet all applicable building and safety codes. Telecommunications room (TR) is an enclosed space for housing telecommunications equipment, cable terminations, and cross-connects. The room is the recognized cross-connect between the backbone cable and horizontal cabling. There may be one or more TRs depending on the size and layout of a floor. The TRs should be centrally located to accommodate cable routing to each location served by that TR without having to penetrate or pass around architectural barriers. The TR may serve as the center of the star topology for cabling and cable distribution for that floor or portion of the floor. Cabling from the TR is distributed to each work space served by that TR; this cabling can be distributed via a number of methods depending upon building and electrical codes, fire safety codes, etc. The most common methods are conduit, cable raceway systems, cable suspension (above a dropped ceiling) and various under floor systems. The cable distance between the TR and any workspace must be no more than 90 meters. The equipment in the TR may include cabling cross connects and patch panels, punch down blocks, fiber patching equipment, etc. The TR may also contain communications equipment such as cabling hubs, terminal servers, and Ethernet bridges. This equipment is modular, available from multiple vendors, and is generically known as a smart hub. The Logical Network Architecture Guidelines
14 defines the combination of this communications equipment as the Group Hub (GH). LNA guidelines can be found at the following website. TR should be large enough (with sufficient power and HVAC) to contain both the mechanical cabling systems and the communications equipment. If this is not possible, the communications equipment should be located in the ER, or a space on the floor with the correct HVAC and support systems. It is imperative that the placement of equipment in the TR meets all applicable building, fire and safety codes. Building Entrance Facility (BEF) is the point of demarcation between the communication facilities provided by a telephone company (access provider, which could be an Incumbent Local Exchange Carrier, Competitive Local Exchange Carrier, or a Competitive Access Provider) and the building's communication facilities. The actual physical point of interconnection to the carrier provided telephone services is typically a standard Telco company jack, or other means as specified in the applicable tariffs. In single tenant buildings, the demarcation point BEF is generally located within 50 feet of exiting the entrance facility conduit of the telephone company lightning or surge protectors. These are safety devices, which the telephone company places on their lines at the location where they enter the building. In multi-tenant buildings, a telephone company may designate a single room in the basement as the demarcation point, (BEF) or they may designate multiple demarcation points at various locations in the building. Note that with the emergence of Competitive Access Providers and Competitive Local Exchange Carriers, a given building may receive service from more than one Telephone Company. In such cases, there may be a need for separate Building Demarcation Points for each carrier, preferably using separate rooms and possibly separate entrance conduits. In many cases, a CLEC or CAP will deliver service directly over fiber optics. Such installations have fewer physical pairs and may lack the lightning protection characteristic of copper, but will require electrical service to a fiber optic terminal and/or multiplexor, as well as associated lighting and ventilation. It is important to note that the BEF may be located somewhere other than within the ER, and in these circumstances, sufficient cable conduit must be installed between these locations. It is not unusual for the demarcation point to be located in the basement and the ER to be located on a higher floor. Regardless of the location of the carrier's demarcation point, the MC should serve as the main communications room. Equipment Room (ER) is a centralized space for telecommunications equipment that serves the occupants of a building. Equipment housed therein is considered distinct from a telecommunications room because of its nature or
15 complexity. The Main Cross connect (MC) is normally located in the main equipment room for cross connection and interconnection of entrance cable, first level backbone cable and equipment cables. This room may also serve as the BEF. The MC is used to distribute communication services to all of the Telecommunication Room (TR) within the building and as such, it can be viewed as the center of the star for cabling and cable distribution. The room contains the necessary cabling cross connects, punch down blocks, fiber patching equipment, etc. to connect to each TR within the building. The MC may also contain the shared communications equipment for the building. For voice, the room contains the PBX, or other telecommunications equipment, and for data, the MC contains the shared data communications equipment such as routers, hubs, switches which will all collapse to the wide area network backbone. The Logical Network Architecture Guidelines defines the combination of this communications equipment as the Core Hub (CH) for the building. Every building should have one MC centrally located in order to minimize the cable distances within the building. In a high-rise building, this means the MC should be located on a middle floor even though the BEF might be located on the first floor or in the basement. If a number of Commonwealth agencies lease multiple floors within a commercial building, there might be a MC built for their exclusive use. There may be two or more MCs within a very large building. The technical and architectural requirements for a MC can be found in the ANSI/TIA/EIA-569-A standard and the BICSI Telecommunications Distribution Methods Manual (TDMM). General room requirements are summarized in an appendix to this document, but it is important to note that the MC must be a secure room and that disaster backup plans must be in place for this facility. Note that if GH equipment must be located in the TR, then the data functions of the TR are subsumed by the MC, as the standard fiber optic data risers are designed to end at the GH. The total distance from the CO to the GH must still not exceed 100 meters. The technical and architectural requirements for a TR can be found in the ANSI/TIA/EIA-569-A standard and the BICSI Telecommunications Distribution Methods Manual (TDMM). General room requirements are summarized in an appendix to this document, but it is important to note that the TR must be a secure room and that disaster backup plans must be in place for users served from this room. 7.0 Administrative and Management Requirements The administration of the telecommunication infrastructure within a building requires that documentation of the building's cabling be created and then maintained on an ongoing basis. Administration also includes setting policies on the installation and upgrading of the system, access to the building and TRs and planning for disaster recovery. All of these issues and details are described at
16 length in the ANSI/TIA/EIA-606 standard. The most important point however is that a single organization should be responsible for the management and administration of the physical cabling infrastructure within a building. This approach is an integral part of this policy. Appendix A: Guidelines for Telecommunications Rooms The following are the basic guidelines that should be adhered to in the construction and renovation of Telecommunication Rooms (TR). These rooms, which are also known as wiring closets or Intermediate Distribution Frames (IDF), are to be set aside on each floor for the exclusive purpose of housing the communications equipment and related cabling that serves the specific area of the building. These are minimal requirements only; a detailed design is required for each such room within a building. These guidelines should reflect the most current ANSI/TIA/EIA and BICSI standards, before a final design is approved. Rooms in current buildings that are being renovated should try to meet these guidelines if possible. It is imperative that the TR and equipment placed within the TR meet all applicable building, fire and safety codes. The basic guidelines for TR ("rooms") include the following: a: Rooms should serve one floor only and rooms should be physically located on the floor. Rooms which serve an area of approximately 10,000 square feet should be 10' x 11' in dimension. Rooms which serve an area of 5,000 square feet should be 10' x 7' in dimension. b: All interior walls in closets should be covered, floor to ceiling with 3/4" plywood that is raised away from the wall a minimum 1&3/4". c: All interior walls in rooms should be fire rated or treated on both sides with 2 coats of white fire retardant paint, which meets applicable fire codes. d: There should be, at a minimum, two (2) duplex convenience outlets on each wall of the room at a minimum at 6ft intervals around perimeter of room. Dedicated service should be provided as required for the communications equipment. All outlets should be backed up via the building UPS if available. e: Rooms should not have a false or drop ceiling. f: Flooring should be tile or other finished surface to keep dust at a minimum. g: No building water or steam carrying pipes shall run through or above the room, except for sprinkler systems if required. If sprinkler heads are required they shall be of high temp rating and caged.
17 h: Lighting should be maintained at 50-foot candles, measured at 3 foot above floor level. i: Lighting should be able to be turned on/off via a Wall switch located immediately inside the door. j: Door should be minimally three feet (3') wide and should swing open out of the room. k: Doors should lock from outside access; exiting from closets must always be permissible. l: Floor loading must be a minimum of 100 lb. per square feet. m: HVAC should be included in the design of the room in order to maintain a room temperature of degrees Fahrenheit with the full complement of equipment in the room. n: Relative humidity should be maintained between 30% and 50%. o: Riser cable access into TR(s) shall be via four-inch (4") conduit or sleeved cores. Exact amounts of conduit required on a per closet basis must be determined based upon the amount of fiber and copper cable that must be supported in each TR (see ANSI/TIA/EIA-569-A for guidelines). A minimum of two (2) additional cores/conduits must be provided in each room for future growth. p: All conduits/coring should be kept six inches (6") or less from walls whenever construction permits. All cores should be in single row. All cores should be kept in same relative proximity in stacked TRs. q: All penetrations must be sealed with a fire stop, which meets applicable code. r: Rooms that are not equipped with raised flooring should have 12" ladder rack installed along each plywood wall with an additional 12 ladder rack above each equipment rack or cabinet. Ladder rack must be securely installed and must provide a minimum clearance of 9'-0" above the floor. s: Station cable access, when not via raised floor, should be via 4" sleeves located above door level, and cable should run directly onto ladder rack within room. t: Pull strings must be installed in all conduits and sleeves. Appendix B: Guidelines for Equipment Room
18 The following are basic guidelines that should be adhered to in the construction and renovation of Equipment Rooms (ER). These rooms, which are also known as the Building Entrance Facility (BEF), Main Distribution Frame (MDF). Equipment Rooms are the primary communications room for a building or facility. These are minimal requirements only; a detailed design is required for this room. These guidelines should reflect the most current ANSI/TIA/EIA and BICSI standards before a final design is approved. Rooms in current buildings that are being renovated should try to meet these guidelines, if at all possible. It is imperative that the Equipment Rooms and equipment placed within the rooms, meet all applicable building, fire and safety codes. The basic guidelines for (ER s) include the following: a: (ER) should be sized to meet the requirements of the current and planned communications equipment. When requirements are not known, the ANSI/TIA/EIA 569-A standard recommends that there be a minimum of 0.75 square feet of space for every 100 square feet of workspace. (A minimum of 150 square feet is recommended.) b: All interior walls in closets should be covered, floor to ceiling, with 3/4" plywood that is raised away from the Wall a minimum 1&3/4". c: All interior walls in rooms should be fire rated or treated on both sides with 2 coats of white fire retardant paint, which meets applicable fire codes. d: There should be, at a minimum, two (2) duplex convenience outlets on each wall of the room at a minimum of 6ft intervals around perimeter of room. Dedicated service should be provided as required for the communications equipment. All outlets should be backed up via the building UPS if available e: Dedicated electrical service should be provided as required for the installed communications equipment and should be backed up via the building UPS. f: Rooms should not have a false or drop ceiling. g: Flooring should be tile or other finished surface to keep dust at a minimum. Anti-static protection should be used as required by equipment. h: No building water or steam carrying pipes shall run through or above the room, except for sprinkler systems if required. If sprinkler heads are required, they shall be of high temp rating and caged. i: Lighting should be maintained at 50-foot candles, measured at 3 foot above floor level. Lighting should be able to be turned on/off via a Wall switch located immediately inside door.
19 j: Doors should be minimally three feet (3') wide and should swing open out of the room. Doors should lock from the outside; exiting from the room must always be possible. k: Floor loading must be a minimum of 250 lb. per square foot, or as required by equipment. l: HVAC should be included in the design of the room in order to maintain a room temperature of degrees Fahrenheit with the full complement of equipment in the room. Relative humidity should be maintained between 30% and 50%. m: Riser and distribution cables leaving the room to building TRs and agency computer and communication room spaces should be via four-inch (4") conduits or sleeved cores. The exact number of conduits required should be determined based upon the amount of fiber and copper cable that must be supported in each closet, and each agency computer or communications room. Additional conduits or sleeved cores must be included in the design to provide for future growth. n: If the Building Entrance Facility (BEF) is not located within the room, sufficient conduit must be run between these two locations. A minimum of four (4) additional four-inch (4 ) cores/conduits must be provided for future growth. o: If the Building Entrance Facility (BEF) is located within the room, a minimum of fifteen feet of Wall space with backboards must be provided for terminations and related equipment. p: If a second Building Entrance Facility (BEF) is provided to allow for second provider s entrance facilities, additional cores/conduits must be provided to that location. If more than one provider's BEF needs to be in the ER, their respective wall space and backboards must be kept separate and clearly distinguishable. q: All conduits/coring should be kept six inches (6") or less from walls whenever construction permits. r: All penetrations must be sealed with a fire stop, which meets applicable code. s: Rooms should be installed with raised floors. Rooms that are not equipped with raised floors should have 12" ladder rack installed in a configuration, which supports the proposed equipment layout. t: Pull strings must be installed in all conduits and sleeves. Appendix C: Specifications for System Cabling and Components
20 The following are the basic specifications for system cabling and components. These are minimal requirements only; a detailed system specification and design is required for each installation. These specifications should reflect the most current ANSI/TIA/EIA and BICSI standards, before a final cabling design is approved. All cabling systems that are being updated shall meet these guidelines. It is imperative that all cabling system components used within Commonwealth buildings meet all applicable building, electrical, fire and safety codes. This appendix is divided into ten sections. I. General System Specifications 1.1 All voice and data cabling should be neatly installed without using any electrical conduits, plumbing, heating, or air conditioning structures for support. Cabling must be routed so that it does not interfere with access to panels, switches, valves, or other maintenance systems. 1.2 All cables must be installed at least one foot from any fluorescent lighting unless contained in separate conduit, and four feet from other sources of electrical interference such as motors and generators. 1.3 All above-ceiling cable must be installed in cable trays or installed using a comparable method of support so that the cable does not lie loosely on the top of the false or drop ceiling. 1.4 All twisted pair cable must be tested by the installer to the latest industry standards to be compliant with category 6 specifications, (as appropriate). All fiber optic cable must be tested to the latest industry standards (ANSI/TIA/EIA 568 B.3). All test results must be included in the installation documentation. II. Voice Twisted Pair Station Cable 2.1 Voice station cable must consist of one (1) unshielded, 4-pair, 24-gauge copper, solid conductor category 6, twisted cable. Hybrid cable, which meets the same category 6 technical specifications, is also acceptable. 2.2 All cable must be labeled clearly and legibly at both ends. 2.3 Station locations must be labeled on connection blocks and or patch panels in all TR and ER Separate connection blocks or patch panels must be provided for station cables and riser/ horizontal cables.
21 2.5 At the IDF end of the voice station cable: 1. Cables must be terminated onto 110 type blocks or patch panels, (per agency specifications). 2. Cables must be cut down in numerical order. 3. Cables must include ten (10) feet of additional length, looped in the room to allow for future adjustment of blocks. 2.6 Cables must include ten (10) feet of additional length, looped, and secured above the ceiling or below the floor at the station outlet end to allow for future room rearrangements. 2.7 At the station and/or communications outlet end, cable must be connected to modular jacks per 568 B wiring scheme. III. Data Twisted Pair Station Cable 3.1 Data station cable must consist of one (1) unshielded, 4-pair, 24-gauge copper, solid conductor twisted pair, category 6, cable at a minimum. To all cabled locations. Hybrid cable, which meets the same category 6 technical specifications, is also acceptable. 3.2 All cable must be labeled clearly and legibly at both ends. 3.3 Station locations must be labeled on patch panels at all TR and ER. 3.4 At the TR/ER end of the cable: 1. Cables must be terminated directly onto patch panels 2. Cables must be terminated in numerical order. 3. Cables must include ten (10) feet of additional slack, in the closet to allow for future adjustment of patch panels. 3.5 At the station and/or communications outlet end, the cable must be terminated in an 8 position, 8 conductor modular connector. (568 B Wiring Scheme). 3.6 Cables must include ten (10) feet of additional slack, secured above the ceiling at the station outlet end to allow for future room rearrangements. 3.7 Patch cables shall meet or exceed horizontal cabling category specifications at the TR.
22 IV. Communications Outlet Specifications 4.1 At the station and/or communications outlet end, voice cable must be connected to an 8 position, 8-pin conductor modular RJ-45 jack. 4.2 At the station and/or communications outlet end, data cable must be connected to, 8 position, 8 conductor modular RJ-45 jack. 4.3 Communication outlets located in building walls should be flush mounted in single gang electrical boxes with appropriately labeled faceplates. 4.4 Communication outlets located in movable and demountable partitions must be mounted in an integral raceway system. The use of adhesive backed surface mount boxes is specifically prohibited. 4.5 All outlets must be clearly identified with labels as to station type (voice and data) and terminating TR location. V. Voice Riser/Distribution Cables 5.1 Conventional voice distribution cables must be 100-pair category 3, #24 gauge at a minimum. All riser cable must meet all applicable fire and safety codes. 5.2 If there is more than one TR located on a floor, distribution cable between these rooms must be included as part of the system cabling design. 5.3 All 100-pair cable must contain four (4) 25-pair binders. 5.4 Color code of each 25-pair binder must be as follows: PAIR COLOR CODE COMBINATION 1 White/Blue Blue/White 2 White/Orange Orange/White 3 White/Green Green/White 4 White/Brown Brown/White 5 White/Slate Slate/White 6 Red/Blue Blue/Red 7 Red/Orange Orange/Red 8 Red/Green Green/Red 9 Red/Brown Brown/Red
23 10 Red/Slate Slate/Red 11 Black/Blue Blue/Black 12 Black/Orange Orange/Black 13 Black/Green Green/Black 14 Black/Brown Brown/Black 15 Black/Slate Slate/Black 16 Yellow/Blue Blue/Yellow 17 Yellow/Orange Orange/Yellow 18 Yellow/Green Green/Yellow 19 Yellow/Brown Brown/Yellow 20 Yellow/Slate Slate/Yellow 21 Violet/Blue Blue/Violet 22 Violet/Orange Orange/Violet 23 Violet/Green Green/Violet 24 Violet/Brown Brown/Violet 25 Violet/Slate Slate/Violet VI. Voice Riser/Distribution Cable Terminations 6.1 Voice riser/distribution cable must be run from the ER directly to each of the building's TR. All distribution cables must be terminated on 110 type blocks, or patch panels at floor TR and at the ER. 6.2 All termination blocks at the TR must be securely mounted and must not exceed 900 pair within a group with the bottom block at least 18" above the finished floor. 6.3 The first block must be a minimum of 6" in from the end of the backboard. Adjacent rows shall be 2.5" apart. Minor adjustments in row spacing are allowed to provide clearance of the mounting studs behind the backboards. 6.4 All blocks at TR must be mounted on fire retardant plywood backboards. 6.5 Riser distribution cable must include two pair per voice station with a minimum of 25% growth per TR, in multiples of 100 pair cables. VII. Copper Data Riser/Distribution Cables 7.1 Data distribution cables must be 25-pair category 6 or greater, unless specific requirements dictate otherwise, #24 gauge. All riser cable must meet all safety and fire codes and must have a different jacket color than that cable supplied for voice riser.
24 7.2 If there is more than one TR located on a floor, distribution cable between these rooms must be included as part of the system cabling design. 7.3 All 100-pair cable must contain four (4) 25-pair binders. 7.4 Color code of each 25-pair binder must be as follows: PAIR COLOR CODE COMBINATION 1 White/Blue Blue/White 2 White/Orange Orange/White 3 White/Green Green/White 4 White/Brown Brown/White 5 White/Slate Slate/White 6 Red/Blue Blue/Red 7 Red/Orange Orange/Red 8 Red/Green Green/Red 9 Red/Brown Brown/Red 10 Red/Slate Slate/Red 11 Black/Blue Blue/Black 12 Black/Orange Orange/Black 13 Black/Green Green/Black 14 Black/Brown Brown/Black 15 Black/Slate Slate/Black 16 Yellow/Blue Blue/Yellow 17 Yellow/Orange Orange/Yellow 18 Yellow/Green Green/Yellow 19 Yellow/Brown Brown/Yellow 20 Yellow/Slate Slate/Yellow 21 Violet/Blue Blue/Violet 22 Violet/Orange Orange/Violet 23 Violet/Green Green/Violet 24 Violet/Brown Brown/Violet 25 Violet/Slate Slate/Violet VIII. Data Riser/Distribution Cable Terminations 8.1 Data riser/distribution cable must be run from the ER directly to each of the building's TRs and must be terminated on patch panels. 8.2 All patch panels at TR shall be wall or rack mounted. All patch panels shall be in increments of 24 ports and be category 6 or higher.
25 8.3 The size of the riser distribution cables must be determined during system design. IX. Fiber Riser and Distribution System 9.1 At a minimum, one (1) twelve (12)-strand fiber optic cable shall be distributed to each TR in the building from the ER. Fiber strands may be single mode (8.3/125 micron) or multi-mode (62.5/125 or 50/125 microns) or a combination thereof. This is a minimum; additional fiber cables should be installed as needed for current and future requirements. Consult your cabling vendor for a design to suit your requirements. 9.2 Fiber optic cable at each TR and or ER must be terminated in a wall or rack mounted enclosure that must accommodate at least twelve (12) patch cord terminations. 9.3 If there is more than one TR located on a floor, the installation of fiber cable between the rooms should be considered only if special circumstances exist. 9.4 All fiber strands must be terminated with SC or small form factor connectors. ST type connectors are acceptable to match existing connectors. 9.5 All fiber must be run through inner duct or conduit. The pathway must be clearly labeled as "FIBER OPTIC CABLE" and must be labeled with information on the fiber's termination point and the fiber's owner. 9.6 All fiber strands shall be terminated, labeled and tested. All unused connectors shall have dust covers installed. X. Cable Documentation 10.1 The cable installer must provide clean and legible as-built cable drawings and records in both hard and soft copy as part of system installation. These drawings must, at a minimum, show the location and type of all communication rooms, communication closets, all distributing cable runs, and all outlets. Cable records must, at a minimum, include station location number, horizontal and riser distribution cable numbers, and all other information necessary to correlate cable runs and terminating locations. Cable records should also include the cable lengths; pair count/fiber counts for all distribution and outside plant cable (by segment) and the locations of any splices All cables must be labeled using a permanent marking system. Handwritten labels are not acceptable. All conduits carrying fiber cable and all voice and data riser or distribution cables must be labeled at ten-foot intervals on long runs, but not less than twice within a room. At a conduit end point, the label must
26 include information indicating distant end point (i.e. Fiber Optic Cable to Floor 1, Closet "A") Labeling methods should be consistent throughout the system and should meet the reporting requirements of ANSI/EIA/TIA/ Installers of fiber cable must test the Loss Ratio of each fiber and provide the results to the agency(s)in hard and soft copies as part of the cable documentation. Appendix D: Wireless System Cabling and Components The following are the basic specifications for wireless system cabling and components. These are minimal requirements only; a detailed system specification and design is required for each installation. These specifications should reflect the most current ANSI/TIA/EIA, IEEE b specifications and BICSI standards, before a final cabling design is approved. Wireless systems and applications will need to meet enterprise standards currently under development by the Wireless Technology Planning Group chaired by the Information Technology Division. Document Authors Wiring Standards and Guidelines Group Lead: Joseph Hickey, ITD Telecommunications Systems Manager Members: Greg Niemiera, Mohawk Cable Corp Jim Salvo, Mohawk Cable Corp Phil Milan, LanTel c/o Bisci Rep Mike Duda, Panduit Corp. Ed Dowling, JCI/ Netversant Leanne Maio, Trial Courts Ann Roper Quinn, City of Boston Bob McCann, RDK Consulting Pam Goodwin, DCAM Cindi Ettinger, ITD
Part No. P0943133 02. Business Communications Manager 2.5. BIX Box Wiring Guide
Part No. P0943133 02 Business Communications Manager 2.5 BIX Box Wiring Guide 2 Copyright 2001 Nortel Networks All rights reserved. May, 2001. The information in this document is subject to change without
Presenters Brett Weiss, Gabe Martinez, Brian Kroeger.
1 Presenters Brett Weiss, Gabe Martinez, Brian Kroeger. Topics to be covered: Cable identification Purpose of the various cable types Installation techniques Building Infrastructure Overview of networking
Network Design. Yiannos Mylonas
Network Design Yiannos Mylonas Physical Topologies There are two parts to the topology definition: the physical topology, which is the actual layout of the wire (media), and the logical topology, which
DIVISION 27 COMMUNICATIONS. A. System design shall be completed by a Registered Communications Distribution Designer (RCDD).
DIVISION 27 COMMUNICATIONS 27 00 00 COMMUNICATIONS A. System design shall be completed by a Registered Communications Distribution Designer (RCDD). B. Comply with American National Standards Institute
ANSI/TIA/EIA - 568-A, Commercial Building Telecommunications Cabling Standard.
WIRING STANDARD INTRODUCTION This standard defines a telecommunications wiring system for North Dakota State Agencies, offices or buildings that will support a multi-product environment. The purpose of
Installing the Loop Start Line Board with Centrex Message Waiting and Caller ID
Installing the Line Board with Centrex Message Waiting and Defining the Centrex Line Board The FXCMW-08 and FXCMW-16 line boards provide eight and sixteen lines respectively, with support for caller ID
1. Furnish and install faceplate and modular jacks at each single gang outlet as described below:
Washington University in St. Louis Building: Communication Specification: Research Voice/Network/Typical 1. Furnish and install faceplate and modular jacks at each single gang outlet as described below:
Structured Cabling Statement of Work
Structured Cabling Statement of Work Multiple Locations June 15, 2010 Page 1 A. GENERAL a. San Joaquin County (referred to as Owner ) is requesting proposals for a new structured cabling infrastructure
SECTION 25110 TELECOMMUNICATION ROOMS
PART 1 - GENERAL 1.1 SUMMARY A. SCOPE SECTION 25110 TELECOMMUNICATION ROOMS 1. This section includes the minimum installation requirements for equipment and cabling infrastructure in Telecommunication
TIA 569 Standards Update Pathways & Spaces. Ignacio Diaz, RCDD April 25, 2012
TIA 569 Standards Update Pathways & Spaces Ignacio Diaz, RCDD April 25, 2012 The purpose of this Standard is to standardize specific pathway and space design and construction practices in support of telecommunications
Building Telecommunications Infrastructure Requirements
Building Telecommunications Infrastructure Requirements This page identifies specific requirements for the design of telecommunications infrastructure for buildings at Clemson University. (Revised October,
DESIGN GUIDELINES. Local Area Network
DESIGN GUIDELINES Local Area Network The total oversight and management responsibilities for information assurance (IA) and protection of DoDEA s critical infrastructure fall under the purview of the DoDEA
DEPARTMENTAL REGULATION
U.S. DEPARTMENT OF AGRICULTURE WASHINGTON, D.C. 20250 DEPARTMENTAL REGULATION SUBJECT: Service Center Technology Modernization Project (SCTMP) Wiring/Cabling Specifications for Service Center Agencies
ANSI/TIA/EIA-570. 570-A A Revisited. Residential Telecommunications Cabling Standard (Draft 6/22/99) Larry L. Hamlin, RCDD
BICS I CABLING INSTALLATION PROGRAM ANSI/TIA/EIA-570 Residential Telecommunications Cabling Standard (Draft 6/22/99) Larry L. Hamlin, RCDD Copyright BICSI, October 1999 -A Revisited 1.1 Purpose standardize
TCTC Cabling Specifications
TCTC Cabling Specifications Purpose: To provide a standard specification that will be used for all Tri County Technical College (TCTC) facilities requiring structured cabling installation. Product specifications,
ANSI/TIA-942 Telecommunications Infrastructure Standard for Data Centers
ANSI/TIA-942 Telecommunications Infrastructure Standard for Data Centers Jonathan Jew [email protected] J&M Consultants, Inc Co-chair TIA TR-42.1.1 data center working group Co-chair BICSI data centers standards
Structured and Point to Point Network Cabling for Industrial Automation
Structured and Point to Point Network Cabling for Industrial Automation Introduction Industrial automation systems are undergoing dramatic transformations that require businesses to adopt new strategies
UT Southwestern Medical Center Information Resources Cable Installation Standard
UT Southwestern Medical Center Information Resources Cable Installation Standard PART 1- GENERAL 1.01 SUMMARY A. Furnish and install wire, cable, devices, equipment, and accessories for a complete system
SYSTIMAX SCS PowerSum and GigaSPEED XL Cabling Installation Guidelines
SYSTIMAX SCS PowerSum and GigaSPEED XL Cabling Installation Guidelines This document contains critical information regarding the installation of a certified SYSTIMAX SCS that meets or exceeds performance
Specifications for Communication Cabling Distribution Systems
Washington University in St. Louis Specifications for Communication Cabling Distribution Systems General Overview Listed below are the separate sub-systems of Washington University s structured cabling
Cable Installation Project
Cable Installation Project 1. Intent. It is the intent of the U.S. Court of Appeals to install Category 6 (CAT6) data cabling in the Robert F. Peckham Federal Building and United States Courthouse, 280
ANSI/TIA-942 Telecommunications Infrastructure Standards for Data Centers
ANSI/TIA-942 Telecommunications Infrastructure Standards for Data Centers Jonathan Jew jew@j-and and-m.com J&M Consultants, Inc Co-chair TIA TR-42.1.1 data center committee Co-chair BICSI data centers
Telecommunications Infrastructure Standard for Data Centers. 802.3 Tutorial
Telecommunications Infrastructure Standard for Data Centers 802.3 Tutorial Prepared by: Jonathan Jew - J&M Consultants and Chris DiMinico - MC Communications - Co-chairs TR42.1.1 TR42: Data Center Standard
Implementing Fast Ethernet
Implementing Fast Ethernet R The Next Generation of Ethernet Fast Ethernet (also known as IEEE 802.3u or 100BASE-T) is quickly becoming the successor to Ethernet as the network topology of choice. Fast
UNIFIED FACILITIES GUIDE SPECIFICATIONS
USACE / NAVFAC / AFCEC / NASA UFGS-27 05 14.00 10 (April 2006) -------------------------------- Preparing Activity: USACE Superseding UFGS-27 05 14.00 10 (April 2004) UNIFIED FACILITIES GUIDE SPECIFICATIONS
Cabling and Building Infrastructure for Technology
Cabling and Building Infrastructure for Technology by: Ernest J. Schirmer, Director Information Technology Infrastructure Design CUH2A Architecture Engineering Planning 211 Carnegie Center Princeton, NJ
DIVISION 26 - ELECTRICAL SECTION 26 05 20 CABLES FOR INSTRUMENTATION
DIVISION 26 - ELECTRICAL PART 1 - GENERAL 1.01 SUMMARY A. Section Includes 1. Instrumentation Cables 1.02 SUBMITTALS A. Submit in accordance with requirements of Section 01 33 00. B. Product Data: Submit
TELECOMMUNICATIONS STRUCTURED CABLING GUIDELINES AND SPECIFICATIONS. University of Chicago IT Services Infrastructure Services October 2011
TELECOMMUNICATIONS STRUCTURED CABLING GUIDELINES AND SPECIFICATIONS IT Services Infrastructure Services October 2011 Table of Contents 1 Introduction... 4 1.1 Planning and Design... 4 1.2.1 Roles and Responsibilities...
Telecommunications Systems Narrative Page 1 The Engineering Enterprise
I. TELECOMMUNICATIONS GENERAL REQUIREMENTS A. The project consists of a renovation to the historic Clinical Sciences building, originally built in 1933. The existing building has a total area of 105,000
HOUSTON COMMUNITY COLLEGE HCC ALIEF CAMPUS MAIN BUILDING, FIRST, SECOND & FOURTH FLOORS RENOVATION ISSUE DATE: 10.17.12
SECTION 27 05 26 - GROUNDING AND BONDING FOR COMMUNICATIONS SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes grounding and bonding products, design requirements and installation for communications
Standards. www.nordx.com 5 ANSI/TIA/EIA-569-A (CSA T530)
The primary focus of this standard is to provide design specifications and guidance for all building facilities relating to telecommunications cabling systems and components. This standard identifies and
TELECOMMUNICATIONS NETWORK STANDARDS AND GUIDELINES FOR THE NEW ADMINISTRATION BULDING
TELECOMMUNICATIONS NETWORK STANDARDS AND GUIDELINES FOR THE NEW ADMINISTRATION BULDING October 1998 Table of Contents SECTION I: New Construction Programming 1.0 New Construction 1.1 Design Elements..................................
B. Cross-Connect: A facility enabling the termination of cable elements and their interconnection or cross-connection.
DIVISION 16 ELECTRICAL Section 16740 Telephone System PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division
Minimum Standards for Data/Voice Infrastructure in New Building Construction
UNIVERSITY OF WATERLOO Minimum Standards for Data/Voice Infrastructure in New Building Construction 12/17/2012 Offices 1. Two Work Area Outlets (WAO) on opposite walls, each with 2 jacks 2. Each WAO shall
Cabling Requirements for the District of Columbia on behalf of the Criminal Justice Coordinating Council
Cabling Requirements for the District of Columbia on behalf of the Criminal Justice Coordinating Council Date: 6/19/2013 Version: 1.0 Prepared by: Gregory Cotten Department of General Services District
1.1 SYSTEM DESCRIPTION.1 Data system includes data outlets and wiring for office and school applications.
Issued 2005/06/01 Section 16743 Data System Page 1 of 7 PART 1 GENERAL 1.1 SYSTEM DESCRIPTION.1 Data system includes data outlets and wiring for office and school applications..2 Data system equipment
Specifying an IT Cabling System
Specifying an IT Cabling System This guide will help you produce a specification for an IT cabling system that meets your organisation s needs and gives you value for money. You will be able to give your
Installing a Physical Network. Chapter 8
Installing a Physical Network Chapter 8 Contents Recognize and describe the function of basic components in a structured cabling system Explain the process of installing structured cable Install a network
Chapter 4 Connecting to the Internet through an ISP
Chapter 4 Connecting to the Internet through an ISP 1. According to Cisco what two things are essential to gaining access to the internet? a. ISPs are essential to gaining access to the Internet. b. No
TIA-942 Data Centre Standards Overview WHITE PAPER
TIA-942 Data Centre Standards Overview WHITE PAPER TIA-942 Data Centre Standards Overview For the past 20 years, cabling standards have been the cornerstone of ensuring proper design, installation, and
1 Campus Cabling Systems Introduction
1 Campus Cabling Systems Introduction This document represents the campus cable and infrastructure standards adopted and supported by the XXXX. All new construction and renovation should conform to these
Data Center Design Considerations
Data Center Design Considerations Chris DiMinico MC Communications [email protected] Contributors: Jonathan Jew, President, J&M Consultants (Telecommunication Engineering Firm) Co-chair TR42.1.1, Data
HIGH SPEED COMMUNICATIONS PLENUM CABLE CATEGORY 5e CMP FEP JACKETED, PVC-FREE UNSHIELDED TWISTED PAIR (UTP)
Cable Specification Category 5e CMP HIGH SPEED COMMUNICATIONS PLENUM CABLE CATEGORY 5e CMP FEP JACKETED, PVC-FREE UNSHIELDED TWISTED PAIR (UTP) This cable specification complies with the electrical transmission
Design Guide. Universal Connectivity Grid. SYSTIMAX Solutions from CommScope
Design Guide Universal Connectivity Grid SYSTIMAX Solutions from CommScope CONTENTS Introduction 3 Commercial building network overview 4 Zone cabling 5 Universal Connectivity Grid 6 UCG cell size 7 Integrating
Networks. The two main network types are: Peer networks
Networks Networking is all about sharing information and resources. Computers connected to a network can avail of many facilities not available to standalone computers: Share a printer or a plotter among
SECTION 16750 VOICE AND DATA COMMUNICATION CABLING
SECTION 16750 VOICE AND DATA COMMUNICATION CABLING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Store drawing set and general provisions of the Contract, including General and Supplementary Conditions and
Structured Wiring Specifications ERAU Daytona Beach Campus (Dec 14 2011)
Structured Wiring Specifications ERAU Daytona Beach Campus (Dec 14 2011) A. Objectives The Information Technology (IT) Department of Embry-Riddle Aeronautical University (ERAU) seeks to establish a standards-based
How To Write An Infrastructural Standard For Data Center Infrastructure
Infrastructure Standard for Data Centers ANSI/CSA/EIA/TIA-942 (PN-3-0092) Introduction When approved, the standard will be: ANSI/CSA/EIA/TIA-942 Telecommunications Infrastructure Standard for Data Centers
Designing A Communications Cabling System for the Colocation Data Center Larry Smith President, ABR Consulting Group, Inc.
Designing A Communications Cabling System for the Colocation Data Center Larry Smith President, ABR Consulting Group, Inc. It is often said that the communications cabling system is the conduit over which
ATTACHMENT F 050R6800016 - CABLE AND WIRING SERVICES FUNCTIONAL AREA I PRICE PROPOSAL FORM Amendment 6
050R6800016 CABLE AND WIRING SERVICES (Column A) (Column B) (Column C) (Column D) (Column E) (Column F) (Column G) (B+C+D+E)*F= G Item Description PER 100' RUN PER 150' RUN PER 200' RUN PER 300' RUN QUANTITY
ANSI/TIA/EIA-606. Administration Standard for the Telecommunications Infrastructure of Commercial Buildings
ANSI/TIA/EIA-606 Administration Standard for the Telecommunications Infrastructure of Commercial Buildings Distributed by NDS INFORMATION- TELECOM SYSTEM --------------------------------------------- Head
SECTION 16750. TELECOMMUNICATIONS SYSTEM (Cat 6)
SECTION 16750 TELECOMMUNICATIONS SYSTEM (Cat 6) PART 1 - GENERAL 1.01 REQUIREMENTS A. The general provisions of the Contract, including General and Supplementary Conditions and General Requirements, apply
Data and Voice Network Infrastructure
Data and Voice Network Infrastructure Denis Levesque Mike Milne Sponsored By Data and Voice Network Infrastructure Page 1 Copyright APPA 2015 Published by APPA: APPA is the association of choice serving
CommScope Intelligent Building Infrastructure Solutions (IBIS)
SYSTIMAX Solutions CommScope Intelligent Building Infrastructure Solutions (IBIS) Questions & Answers Q. What is an Intelligent Building? A. An intelligent building can be defined as one which provides
Nathan Dayton ADNET. ADNET SYSTEMS, Inc. [email protected]. Slide Number 1
Nathan Dayton SYSTEMS, Inc. [email protected] Slide Number 1 NETWORK DESIGN Slide Number 2 Previously there have been two phases in the design of a network Department Design Interconnect Design
Data Center. Pre-terminated. Patch Panel System. Cabling Systems Simplified. Patch Panels. 10G + Gigabit. Patch Cords. Plug & Play Installation
Data Center Pre-terminated Patch Panel System Patch Panels Plug & Play Installation 10G + Gigabit Patch Cords Bundled + Labeled Cabling Systems Simplified Our Mission At Cablesys, our mission is to simplify
Purpose of the ANSI/TIA/EIA-569-A Standard
For more information, see anixter.com/standards Purpose of the ANSI/TIA/EIA-569-A Standard As the complexity of voice and data telecommunications has increased, standards have been established to ensure
DIIT Voice/Data Cable Infrastructure Specifications
DIIT Voice/Data Cable Infrastructure Specifications Version 7.3.5 (8-22-13) Table of Contents About this Revision...3 Voice/Data Cable Infrastructure Specifications...5 1. Overview...5 2. Cabling Infrastructure
BCM50 Hardware & Installation
BCM Rls 6.0 BCM50 Hardware & Installation Task Based Guide Copyright 2010 Avaya Inc. All Rights Reserved. Notices While reasonable efforts have been made to ensure that the information in this document
SPACE TYPE: AUTOMATED DATA PROCESSING CENTER (ADP) (MAINFRAME)
SPACE TYPE: AUTOMATED DATA PROCESSING CENTER (ADP) (MAINFRAME) Construction Criteria The unit costs for ADP Mainframe space types are based on the construction quality and design features in the following
SECTION 28 05 00 COMMON WORK RESULTS FOR ELECTRONIC SAFETY AND SECURITY
SECTION 28 05 00 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specifications Sections, apply
Request for Proposal DESIGN AND INSTALLATION OF STRUCTURED COMMUNICATIONS CABLE SYSTEMS. Kalispell Public Schools
Request for Proposal DESIGN AND INSTALLATION OF STRUCTURED COMMUNICATIONS CABLE SYSTEMS For Kalispell Public Schools 2015 TABLE OF CONTENTS I. PROJECT DESCRIPTION / GENERAL SCOPE OF WORK...3 II. PROJECT
800 Communications Circuits
ARTICLE 800 Communications Circuits INTRODUCTION TO ARTICLE 800 COMMUNICATIONS CIRCUITS This article has its roots in telephone technology. Consequently, it addresses telephone and related systems that
SECTION 27 13 24 COMMUNICATIONS OPTICAL FIBER OSP CABLING
SECTION 27 13 24 COMMUNICATIONS OPTICAL FIBER OSP CABLING PART 1 GENERAL 1.01 DESCRIPTION A. The work covered by this section of the Specifications includes all labor necessary to perform and complete
March 2007. 27 08 00 Commissioning of Communications. See Appendix E3. 27 08 00-1
March 2007 27 08 00 Commissioning of Communications See Appendix E3. 27 08 00-1 27 11 00 Communications Equipment Room Fittings 1.0 General TELEPHONE RISERS: A. All copper telephone riser cables must be
Innovation. Volition Network Solutions. Leading the way in Network Migration through Innovative Connectivity Solutions. 3M Telecommunications
3M Telecommunications Solutions for Networks Volition Network Solutions Leading the way in Network Migration through Innovative Connectivity Solutions Innovation The Broadband Migration Path 3M TM Volition
Data Center Standards Making Progress on Many Fronts. Jonathan Jew J&M Consultants, Inc [email protected]
Data Center Standards Making Progress on Many Fronts Jonathan Jew J&M Consultants, Inc [email protected] J&M Consultants - 2008 Speaker Jonathan Jew Co-chair TIA TR-42.1.1 Data Center working group ANSI/TIA-942
InstaPATCH Cu Cabling Solutions for Data Centers
SYSTIMAX Solutions InstaPATCH Cu Cabling Solutions for Data Centers Design Guidelines August 2008 www.commscope.com Contents Overview 1 Instapatch Cu Solution Specification 2 Harness Assembly Design 3
Digital Telephone System System Manual
Digital Telephone System System Manual For The Impact DSU This publication is applicable to the following equipment: G0408, with software I0408, revision 18A and later G0816, with software I0816, revision
BIX Cross-Connect System Distribution Connectors, Multiplying Connectors and Modular Jack Connectors
C O M M E R C I A L N E T W O R K I N G C O P P E R 15.13 Distribution Connectors, Multiplying Connectors and Modular Jack Connectors A0393146 QCBIX1A4 Connector BIX Distribution Connector The BIX Distribution
Organizing and Managing Equipment Rooms
Organizing and Managing Equipment Rooms How you organize and maintain your equipment room can be just as important as maintaining the operating systems on the boxes themselves. Although many companies
AMP NETCONNECT CABLING SYSTEMS FOR DATA CENTERS & STORAGE AREA NETWORKS (SANS) High-density, High Speed Optical Fiber and Copper Solutions
AMP NETCONNECT CABLING SYSTEMS FOR DATA CENTERS & STORAGE AREA NETWORKS (SANS) High-density, High Speed Optical Fiber and Copper Solutions TABLE OF CONTENTS TABLE OF CONTENTS... 2 INTRODUCTION... 3 CABLING
Intelligent Cable Management Systems
Intelligent Cable Management Systems Bringing Practical Application Karen Pearson - Leviton Why Cable Management Matters Performance Cooling and air-handling Maintenance ANSI/TIA 569* Telecommunication
Ethernet Patch Cord Wiring
Ethernet Patch Cord Wiring C ONTENTS Ethernet Patch Cords & RJ-45 Connectors... 2 Ethernet Patch Cords and UTP Cabling... 3 What s all the twisting about?... 4 Ethernet Applications... 5 568A & 568B Wiring
Networking 101 (Networking Basics) Presentation to UCHUG - 1/03/07 G. Skalka
Networking 101 (Networking Basics) Presentation to UCHUG - 1/03/07 G. Skalka What is a network? A computer network is two or more computers connected together using a telecommunication system for the purpose
Terminating 25-Pair Cable and 4-Pair Cross Connects
Terminating 25-Pair Cable and 4-Pair Cross Connects Estimated Time: 90 minutes Number of Teams: 2 Number of Team Members: one to four This Lab has four major parts that will be addressed separately. 1.
VIDEO SURVEILLANCE OVER UTP WHITE PAPER INTRODUCING VIPER VIDEO SURVEILLANCE
VIDEO SURVEILLANCE OVER UTP WHITE PAPER INTRODUCING VIPER VIDEO SURVEILLANCE 1 C O N T E N T S Security Systems can be integrated into any IT Network The Network Manager s New Responsibility The Problem
Standards and Guidelines for Telecommunications Wiring Design and Installation Montana State University-Bozeman
Standards and Guidelines for Telecommunications Wiring Design and Installation Montana State University-Bozeman This document defines the standards used for voice and data wiring in buildings used by MSU
270526-TC Grounding and Bonding for Telecommunications Systems
270526-TC Grounding and Bonding for Telecommunications Systems Part 1 - General Related Documents The following related sections of the OT standards shall also be applicable to this section. OT Engineer
B. PART 1 - GENERAL of SECTION 271300 BACKBONE COMMUNICATIONS CABLING shall also apply to this section.
SECTION 271500 - HORIZONTAL UTP CABLING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
ELECTRICAL CONTRACTORS THE UNIVERSITY OF TENNESSEE KNOXVILLE, TENNESSEE SECTION 16050 PAGE 1
KNOXVILLE, TENNESSEE SECTION 16050 PAGE 1 PART 1 - GENERAL 1.01 RELATED DOCUMENTS: SECTION 16050 A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division-1
Request for Proposal (RFP) IP Cameras/Door Access Control
WAHPETON PUBLIC SCHOOLS Information Technology Department Request for Proposal (RFP) IP Cameras/Door Access Control Inquiries and requests regarding this RFP should be directed to: Jason Pfahl, Director
ADC s Data Center Optical Distribution Frame: The Data Center s Main Cross-Connect WHITE PAPER
ADC s Data Center Optical Distribution Frame: The Data Center s Main Cross-Connect WHITE PAPER ADC s Data Center Optical Distribution Frame: The Data Center s Main Cross-Connect Introduction The primary
The Evolution of Copper Cabling Systems from Cat5 to Cat5e to Cat6 Copper Cabling Standards and Technical Aspects
The Evolution of Copper Cabling Systems from Cat5 to Cat5e to Cat6 Copper Cabling Standards and Technical Aspects White Paper /7/0 Executive Summary Now that the TIA/EIA-568-B.- Category 6 Copper Cabling
Wired and Wireless Network Request for Proposal New Washington County High School Facility
Washington County Board Of Education P.O. Box 716 501 Industrial Drive Sandersville, GA 31082 (478) 552-3981 FAX (478) 552-3128 Description Wired and Wireless Network Request for Proposal New Washington
BRIDGEWATER COLLEGE HERITAGE HALL RENOVATIONS 12057.00
SECTION 271500 COMMUNICATIONS HORIZONTAL CABLING PART 1 - GENERAL 1.1 OVERVIEW A. This section provides the necessary guidelines to install service entrance cables to buildings and information for the
TELUS Residential Service Conduit Requirements for Stand Alone Homes and Duplexes in Fibre Only Communities
1 TELUS Residential Service Conduit Requirements for Stand Alone Homes and Duplexes in Fibre Only Communities Beginning in January 2010 TELUS began designing new subdivisions within the Top 48 population
INDOOR PHONE INSTALLATION (CONCEALED) TECHNICAL SPECIFICATION
TÜRK TELEKOMÜNİKASYON KASYON A.Ş. DIRECTORSHIP OF OPERATION AND MAINTENANCE Operation Directorate of Access Networks INDOOR PHONE INSTALLATION (CONCEALED) TECHNICAL SPECIFICATION ANKARA 2008 CONTENTS 1.
FITNESS FACILITY WIRING SPECIFICATIONS. NETPULSE Inc. 2331 3rd Street San Francisco, CA 94107 Phone: 415.643.0223
FITNESS FACILITY WIRING SPECIFICATIONS NETPULSE Inc. 2331 3rd Street San Francisco, CA 94107 Phone: 415.643.0223 CONTENTS: - Scope of work Summary - Equipment list - Technical specifications - Map of data
The Telecommunications Closet and Building Services
APPENDIX G Telecommunications Building & Network Standards 1. Expectations...2 2. Definitions...2 3. Contractor Requirements...2 4. Design Elements...3 4.1. Spaces...3 4.1.1. Building Service Entrance...3