GAINESVILLE REGIONAL UTILITIES Water & Wastewater Engineering SUBMITTAL REVIEW COMMENTS DATE: 11/17/14 PROJECT: GRU Dewatering SUBMITTAL NO.: 04230-001 PROJECT NUMBER: 461318.02.20.10 SUBMITTAL TITLE: Concrete Unit Masonry REVIEWER(S): Clement Anson, Tim Dodge CONTRACTOR: Ortega Industrial Contractors TO BE COMPLETED BY PRIMARY REVIEWER: ACTION SUBMITTAL: DEFERRED NON-DEFERRED APPROVED REVISE AND RESUBMIT APPROVED AS NOTED The Engineer requested additional information from the Contractor to address this submittal. This additional information is attached to the submittal. NOT SUBJECT TO REVIEW PARTIAL APPROVAL ( RESUBMIT AS NOTED) ACTION SUBMITTAL OPERATIONS AND MAINTENANCE MANUALS: APPROVED REJECTED INFORMATION SUBMITTAL: DEFERRED NON-DEFERRED Meets Project Criteria Meets Project Criteria As Noted Does Not Meet Project Criteria; Resubmit The Engineer s review and approval of this submittal are expressly limited as provided in the Contract Documents and are only to determine conformance with information given in the Contract Documents and compatibility with the design concept for the completed project as a functioning whole as indicated in the Contract Documents. The Contractor is responsible for all matters relating to fabrication, shipping, handling, storage, assembly, installation, testing, startup, all aspects related to safety and coordination of subcontractors. 1
NO. COMMENT 1. 04230-001. Aggregate for mortar shall meet ASTM C144 and aggregate for grout shall meet ASTM C404. Mix design denotes ASTM C33 for both. Agros submitted a letter dated 10/30/14 confirming these requirements. Approved as Noted. 2. 04230-001. Mortar shall be type S. Data for type N submitted. Agros submitted a letter dated 10/30/14 confirming these requirements. Approved as Noted. 3. 04230-001. Submittal includes data for material that is not called for in the Concrete Unit Masonry specification. Remove such items in the next submittal. Data submitted appears to be conflicting, it notes ASTM C404 in one sheet while noting ASTM C33 in another sheet. Agros submitted a letter dated 10/30/14 confirming these requirements. Approved as Noted. 4 04230-001. The color selection for the digester electrical building shall be CABANA. RELATED SPEC PAR./ DRAWING REVIEWER INITIALS 2.03, C CA 2.05, A CA - CA TD End of Comments 2
From: To: Subject: Date: Attachments: Ptak, Tim/GNV Henley, Donna/GNV Tim OK FW: GRU Dewatering - 04230-001 Concrete Unit Masonry Monday, November 17, 2014 6:46:03 AM image001.png image002.jpg GRU Dewatering Masonry Submittal revised 10.30.14.pdf 04230-001 Concrete Unit Masonry.doc Donna, I put this submittal on hold till we received the necessary information. The e-mail below and one of the attachments is the required information. Attached is the Approved as Noted comment form. I saved this in the project directory. Tim Ptak CH2M HILL 352.384.7159 (office direct) 3011 SW Williston Rd. Gainesville, FL 3260 From: John Kaschak [mailto:jkaschak@ortegaindustrial.com] Sent: Monday, November 03, 2014 2:56 PM To: Ptak, Tim/GNV Cc: Vielka Garcia Subject: FW: GRU Dewatering - 04230-001 Concrete Unit Masonry Tim..Attached and below is the response from Argos pertaining to your comments (e-mailed on 1023-14) related to the Concrete Unit Masonry submittal. Please let me know if you have any further concerns. Thanks, JOHN M. KASCHAK Vice President Field Operations Ortega Industrial Contractors 6415 Greenland Road Jacksonville, Florida 32258 Office...904-268-2181 x204 Fax...904-260-5181 Cell...904-545-0456 E-Mail...jkaschak@ortegaindustrial.com From: Dewayne Stidham [mailto:dstidham@argos-us.com] Sent: Friday, October 31, 2014 3:19 PM To: John Kaschak Subject: RE: GRU Dewatering - 04230-001 Concrete Unit Masonry John, Here s the revised submittal.
On November 3 rd, 2014 we are switching to ARGOS Command Batch System so our mix numbers are changing. In the attachment above, Page one is our CAB mix number submittal. Page 2 is the new cover letter for the COMMAND Submittal for the concrete mixes. Page 3 is the cross reference CAB to the COMMAND mix numbers cross reference submittal (it identifies the old mix number and shows the new mix number). Response to Engineers concerns: No#1: Mix # FC65GD & J2059 are cell fill mixes (fine & course cell fill) not mortar and mortar grout mixes which was identified in the description on our Submittal Cover Letter. That is why ASTM C33 Standard Specifications for Concrete Aggregate was referenced for the concrete sand and 3/8 limestone and not ASTM C144 Specifications for Aggregate for Masonry Mortar & ASTMC 404 Specifications for Aggregates for Masonry Grout.. No#2: Type N Color Mortar Certification has been removed and a Type S Color Mortar Certification has been added. No#3: Note # 1 might have cleared this concern up. No#4: CMU Color Cabana noted. If there s any questions, please give me a call. Thank you, Dewayne Stidham Sales Representative 352-376-6491 ext. 224 office 352-494-2813 cell dstidham@argos-us.com From: John Kaschak [mailto:jkaschak@ortegaindustrial.com] Sent: Thursday, October 23, 2014 3:05 PM To: Dewayne Stidham Cc: Vielka Garcia Subject: FW: GRU Dewatering - 04230-001 Concrete Unit Masonry Dewayne..Can you please review the comments from the engineer pertaining to the masonry materials submitted for the Kanapaha project and provide the requested information ASAP! Thanks,
JOHN M. KASCHAK Vice President Field Operations Ortega Industrial Contractors 6415 Greenland Road Jacksonville, Florida 32258 Office...904-268-2181 x204 Fax...904-260-5181 Cell...904-545-0456 E-Mail...jkaschak@ortegaindustrial.com From: Tim.Ptak@CH2M.com [mailto:tim.ptak@ch2m.com] Sent: Thursday, October 23, 2014 10:43 AM To: jkaschak@ortegaindustrial.com Cc: Donna.Henley@CH2M.com; vgarcia@ortegaindustrial.com Subject: GRU Dewatering - 04230-001 Concrete Unit Masonry John K., In an effort to save a resubmittal, can you have you block supplier, Argos, respond to the 3 comments on the attached form. The were some relatively simple inconsistencies that are holding up approval. If they can send us the 3 revised sheets for the attached PDF file that will be great. Comment 4 is the color selection CABANA. Tim Ptak CH2M HILL 352.384.7159 (office direct) 3011 SW Williston Rd. Gainesville, FL 32608 This message (including all attachments ) may contain information that is private, confidential, and privileged. If you are not the named addressee, please notify the sender immediately, delete this communication from all data storage devices, and destroy all copies. Any use, disclosure, distribution, copy, retention or recording of this message and any attachments, in whole or in part, by anyone other than the intended recipient(s) is strictly prohibited. ++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++ El contenido de este mensaje (incluyendo los documentos adjuntos) puede contener información privada, confidencial y privilegiada. Si usted no es el destinatario real del mismo, por favor informe de ello inmediatamente a quien lo envía, elimine esta comunicación de cualquier sistema o servidor y destruya todas las copias que tenga de ella. Cualquier uso, divulgación, distribución, copia, retención o grabación de este mensaje y de cualquiera de sus anexos, en todo o en parte, por cualquier persona distinta a su destinatario real, está estrictamente prohibida. El contenido de este mensaje puede ser informacion privilegiada y confidencial. Si usted no es el destinatario real del mismo, por favor informe de ello a quien lo envia y destruyalo en forma inmediata. Esta prohibida su retencion, grabacion, utilizacion o divulgacion con cualquier proposito. Este mensaje ha sido verificado con software antivirus; en consecuencia, el remitente de este no se hace responsable por la presencia en el o en sus anexos de algun virus que pueda generar daños en los equipos o programas del destinatario. Las opiniones contenidas en este mensaje y sus adjuntos no necesariamente coinciden con las posiciones institucionales. ++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++ This communication ( including all attachments ) may contain information that is private, confidential and privileged. If you have received this communication in error; please notify the sender inmediately, delete this communication from all data storage devices and destroy all hard copies. Any use, dissemination, distribution, copying or disclosure of this message and any attachments, in whole or in part, by anyone other than the intended recipient(s) is strictly prohibited. This message has been checked with an antivirus software; accordingly, the sender in not liable for the presence of any virus in attachments that causes or may cause damage to the recipient s equipment or software. The views expressed in this message and its attachments do not necessarily coincide with the institutional positions.