ACCESSORY KIT INSTALLATION INSTRUCTIONS

Similar documents
Digi-Motor Installation Guide

G670 Intermittent Pilot Ignition Controls

HP 5 Microprocessor Control for Mammoth Water Source Heat Pumps

INSTALLATION INSTRUCTIONS COMMERCIAL ROOM VENTILATORS WITH EXHAUST

PART 8: FIELD WIRING. n WARNING NOTICE. Boiler Manual

Your safety and the safety of others are very important.

Fan Coil EC Motor Control

SERVICE MANUAL FOR 12 VDC WALL THERMOSTAT AIR CONDITIONING SYSTEMS ROOF TOP UNITS ONLY

SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS

Roof Top Air Conditioner INSTALLATION AND OPERATING INSTRUCTIONS

SERVICE MANUAL 12VDC WALL THERMOSTAT AIR CONDITIONING SYSTEMS ROOFTOP UNITS ONLY

WON0502-B INSTALLATION INSTRUCTIONS FOR ELECTRIC FURNACES. Bulletin / March 2013

Fossil fuel heating equipment

E2 Series Electric Furnaces

T7079A,B Solid State Remote Temperature Controllers

R22. K Control. Indoor Unit. Nomenclature. Compatibility PL H 3 G K H B. Unit style Heat Pump Horse Power

TECHNICAL GUIDE 95.5% SINGLE STAGE GAS-FIRED RESIDENTIAL MULTI-POSITION GAS FURNACES MODELS: TG9S DESCRIPTION FEATURES

*.ppt 11/2/ :48 PM 1

IMPORTANT: BEFORE INSTALLING ANY HEATING TERMINAL UNIT TO A DOMESTIC WATER HEATER, CONSULT THE LOCAL PLUMBING CODES.

Thermostatic Wiring Principles by Bob Scaringe Ph.D., P.E.


Manual for Fire Suppression & Methane Detection System

IPX AUTOMATIC IP NETWORK LOSS BACKUP A/B SWITCH INSTRUCTION BOOK IB

Commercial Refrigeration Temperature and Defrost Controls

USER MANUAL WARNING! CONTENTS MODEL 1 SPECIFICATIONS READ ALL INSTRUCTIONS BEFORE PROCEEDING. Non-Programmable Single Stage Heat/Cool Thermostat

, User s Manual

The Ultimate Truck Stock Motor

Oil and Coolant Circulating Heating System. Model - OCSM

LG Air Conditioning Multi F(DX) Fault Codes Sheet. Multi Split Units

ECM. Service Guide.

CONTROLS KITS AND ACCESSORIES /2014 Supersedes10/2014

USER S, MAINTENANCE and SERVICE INFORMATION MANUAL

HEAT SIPHON ANSWERBOOK

INSTALLATION & SERVICE MANUAL. Display Panel

GENERATOR START CONTROL MODULE - MINI (2 Wire to 3 Wire)

DIESEL-FUELED, BLOWN AIR, DUCTABLE HEATERS

Installation Instructions

Circuit breaker panel. Power supply for condensing unit. Power supply for furnace. Air handler (Furnace)

ELECTRIC POSITION for electric heat, then confirm with Fan Test below.

ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL

QT Residential Blower Metal Residential Blower

INSTALLER S & OWNER S MANUAL

Downflow Furnace Models *FD14DCLFR000D *FD17DCLFR000D *FD21DCLFR000D *FD24DCLFR000D


Installation Guide. VisionPRO. TH8000 Series. Need Help? This manual covers the following models. System Types

Thermo Top - Troubleshooting Tree

T7560A,B,C Digital Wall Module

G26 Corp L11 Revised LENNOXOEMPARTS.COM. Service Literature G26 SERIES UNITS

prestige Condensing Water Boiler SERVICE TECHNICIAN S TROUBLE SHOOTING GUIDE TSG-PRESTIGE Date revised: 12/6/10

Chapter 5. Components, Symbols, and Circuitry of Air-Conditioning Wiring Diagrams

M7RL Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. High Efficiency / Direct Vent Condensing Downflow Gas Furnace

Commercial Gas Furnace Upflow

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM

Zoning Reference Guide

Water Leak Detector BA/LDT Accessories Termination and Troubleshooting

Service manual. Website: CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL.

PRODUCT PRODUCT CODE TECHNICAL INSTRUCTIONS PAGE

AIR CONDITIONER & HEAT PUMP DIGITAL CONTROL FOR DUCTED SYSTEM INSTALLATION AND OPERATING INSTRUCTIONS

Installation Guide. LR-HWLV-HVAC TouchPRO Wireless. System Types

INSTALL INSTRUCTIONS KK-C-HVAC-1 HVAC UNIT CHEVROLET/GMC VANS FOR

INSTALLATION INSTRUCTIONS MC95HAE-1 MASTER CONTROLLER

tidesmarine Smart Seal Temperature Alarm System Generation II Installation Instructions Starboard side cable

Introduction. Motor Types

Install Guide CT100. Caution. Caution ENGLISH. disconnect the power supply before beginning work.

its ELECTRIC POSITION for electric heat, or set the units fan control appropriately to ELECTRIC or another appropriate setting.

12. Inspection and Maintenance

Service Facts. WARNING: HAZARDOUS VOLTAGE - DISCONNECT POWER and DISCHARGE 4TTM3-SF-1. Split System Cooling 4TTM3018-4TTM3060

INSTALLATION INSTRUCTIONS AIRCOMMAND IBIS ROOFTOP AIRCONDITIONER

Heating, Ventilation, Air Conditioning and Refrigeration (HVACR)

ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013

SUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original

Chromalox. Installation, Operation. Portable Industrial Unit Blower Air Heater Type DRA RENEWAL PARTS IDENTIFICATION

PUSH BUTTON START INSTALLATION MANUAL

Why and How we Use Capacity Control


OASIS SERVICE & TROUBLESHOOTING MANUAL (WITH DM10 OR DM12)

MicroTech III Unit Controller for Water Source Heat Pump Units

Water Leak Detection System

BC & BCH SERIES INDOOR / OUTDOOR INSTALLATION

Communicating Wall Control Installation Manual TSTAT0101SC

Install Guide CT101. Caution. Caution

ELECTRONIC THERMOSTAT AND THERMOMETER With SPEED CONTROL

PRODUCT DESIGN. 5. Furnace awaits call from thermostat.

USER S MANUAL HSC-24A

WHOLESALE DIRECT INC WEST 65TH STREET

ACS-30-EU-EMDR-10-MOD

Failure code manual. content

Instruction Bulletin. MCS025 Sync-Check Module Installation Sheet

Operating Instructions. UL325 Compliant Non-monitored

General Information. Do programmable thermostats really save energy?

ModPac II 1 to 5-Ton Vertical Wall Mount Air Conditioners Models AVPA

Solid State Timers Type F

ECM Blower Motor Replacement Controls Programming Process

36G22, 36G23, 36G24 & 36G52 36J22, 36J23, 36J24 & 36J52 DSI and HSI Single Stage Combination Gas Valve

HEAT HEAT COOL HEAT PUMP COOL

Installation Instructions

SERVICE MANUAL RESIDENTIAL ELECTRIC AND LIGHT DUTY COMMERCIAL ELECTRIC WATER HEATERS. Troubleshooting Guide and Instructions for Service

Thermwire. Selection Guide. Freeze Protection Heating Cable. Thermwire -Wrap. Pre-Assembled. Thermwire-Comp. Thermwire-Melt.

PANASONIC TROUBLE SHOOTING GUIDE

HVAC-32A. Operation Manual. Specifications. Digital Multistage Air Conditioning Controller with inbuilt Outside Air Economy function

Transcription:

ACCESSORY KIT INSTALLATION INSTRUCTIONS 2TC03700124 FURNACE TWINNING CONTROL 035-14572-000 REV. A (800) For use with the following furnace models: ALL SINGLE STAGE DIRECT DRIVE BLOWER MODEL GAS FURNACES ALL DIRECT DRIVE BLOWER MODEL OIL FURNACES TWO BELT DRIVE MODEL GAS FURNACES MAY BE TWINNED WITH THE ADDITION OF ACCESSORY MODEL 2TS03700106 GENERAL This twinning control accessory allows proper operation of two furnaces when the units are installed on a common duct system in a commercial application. This allows a greater system cfm and heating capacity to be attained than would be available from a single furnace. The control, shown in Figure 1, supports both single and dual stage heating/cooling thermostats. Fan sensors continuously monitor the fan motors for proper system operation. The system shuts down if either fails to operate. thermostats may be applied with this twinning control, as it has no special requirements. The blower sensors will properly function with any direct drive PSC or multi-speed blower motor. NOTE: This kit should not be applied with two stage furnaces. OPERATIONAL SEQUENCE The following describes the operation of a twinned furnace system using this control. Both single stage and two stage sequences are shown. SINGLE STAGE THERMOSTAT OPERATION Before installing this control, disconnect electrical power to both furnaces. Failure to cut power could result in electric shock or equipment damage. FAN ONLY - When the fan switch on the room thermostat is in the "ON" position, both furnaces will receive the "G" signal, and both blowers will operate. This will allow constant airflow and will reduce air stratification within the conditioned space. Constant airflow is recommended in most commercial applications during the occupied mode. This control must not be installed in any location where it could be exposed to water. If the control has been exposed to water in any way, it must not be used. DESCRIPTION This accessory includes the twinning control and 2 blower sensor assemblies with 15 ft. wiring harnesses. The control uses only 24 volt field wiring connections. Most electro-mechanical or electronic type room Delay-on timer kit part no. 373-21144-001 is required on furnaces with 1 hp or greater blower motors. Premature motor failure can occur if this kit is not used. HEATING - When the room thermostat heating circuit closes, the control will first energize the "G" circuits in both furnaces to start the blowers. One second later, the control will energize the "W" circuits in both furnaces. This will provide total heating capacity under control of the single stage room thermostat. Unitary Products Group

FIGURE 1: TWINNING CONTROL heating capacity. When first stage of the room thermostat is satisfied, the "W" circuit to the active furnace will be de-energized. FLASH 1 = FURNACE 1 FAULT FLASH 2 = FURNACE 2 SIGNAL FLASH 3 = BOTH FAN/LED SENSOR F U R A C (COM) N R (24V) FURNACE C T'STAT E W (HEAT) Y (COOL) 2 G (FAN) G (FAN) F Y(COOL) FURNACE U W (HEAT) T'STAT R R (24V) A N C (COM) C FAN/LED E SENSOR 1 (+) REMOTE FAULT (-) SEE INSTRUCTIONS FOR ELECTRICAL SPECIFICATIONS OF REMOTE DEVICE 2TC03700124 TWINNING CONTROL THERMOSTAT CONNECTIONS (1ST STAGEHEAT) W1 (2ND STAGE HEAT W2 (1ST STAGE COOL) Y1 (2ND STAGE COOL) Y2 (FAN) G (SUPPLY) R (COMMON) C FOR SINGLE STAGE OPERATION: HEATING: JUMPER W1-W2 COOLING: JUMPER Y1-Y2 INPUT: 24VAC, 50-/60 HZ (FROM FURNACE 1 XFMR) OUTPUTS: 2 A MAX. (EACH FUNCT.) T'STAT ANTICIPATOR SETTING: 0.16A The furnace blowers will continue to operate for for the standard blower offf delay (BOD) set at the time of installation. If the standard BOD is set for 60 seconds, the twinning control will energize the blowers for an additional 5 seconds. On the next heating cycle, the previously inactive furnace will be utilized as first stage. This will provide equal run time on both units. SIGNAL OUTPUT FIGURE 2: TYPICAL TWINNED FURNACE APPLICATION When the room thermostat is satisfied, the "W" circuits to both furnaces will be de-energized. The furnace blowers will continue to operate for the standard blower off delay (BOD) set at the time of installation. If the standard BOD is set for 60 seconds, the twinning control will energize the blowers for an additional 5 seconds. COOLING - When the room thermostat cooling circuit closes, the control will first energize the "G" circuits in both furnaces to start the blowers. One second later, the control will energize the "Y" circuit(s) to the condensing units (either 1 or 2). This will provide total cooling capacity under control of the single stage room thermostat. If only one fan is sensed "ON" while a thermostat signal is present, relays in the twinning control close both fan (R-G) circuits. COMMON SUPPLY PLENUM SUPPLY AIR 1 OR 2 COILS SEPARATE GAS & ELECTRICAL SUPPLIES RETURN AIR When the room thermostat is satisfied, the "Y" circuits to both condensing units will be de-energized. The furnace blowers will continue to operate for 65 seconds, then the "G" circuits will be de-energized. TWO STAGE THERMOSTAT OPERATION FAN ONLY - When the fan switch on the room thermostat is in the "ON" position, both furnaces will receive the "G" signal, and both blowers will operate. This will allow constant airflow and will reduce air stratification within the conditioned space. Constant airflow is recommended in most commercial applications during the occupied mode. HEATING, STAGE ONE - When the room thermostat heating circuit "W1" closes, the control will first energize the "G" circuits in both furnaces to start the blowers. One second later, the control will energize the "W" circuit in one of the furnaces. This will provide 50% COMMON RETURN PLENUM HEATING, STAGE TWO - With the system operating on first stage, as detailed above, when the second stage thermostat heating circuit "W2" is energized, the twinning control will energize the "W" circuit in the second furnace. This will provide 100% heating capacity. When second stage of the room thermostat is satisfied, the "W" circuit to the second stage furnace will be deenergized. this will allow the system heating capacity to again fall to 50%. The system will cycle off as detailed in stage one above. The second stage furnace usage 2 Unitary Products Group

will also alternate along with the first stage unit as detailed in Stage One above. COOLING, STAGE ONE - When the room thermostat cooling circuit "Y1" closes, the control will first energize the "G" circuits in both furnaces to start the blowers. One second later, the control will energize the "Y" circuit to condensing unit number two. This will provide 50% cooling capacity. When first stage of the room thermostat is satisfied, the "Y" circuit to condensing unit number two will be de-energized. The furnace blowers will continue to operate for 65 seconds, then the "G" circuits will be de-energized. On the next cooling cycle, condensing unit number one will be utilized as first stage. This will provide equal run time on both units. COOLING, STAGE TWO - With the system operating on first stage, as detailed above, when the second stage cooling circuit "Y2" is energized, the control will energize the "Y" circuit to the second condensing unit. This will provide 100% cooling capacity. When second stage of the room thermostat is satisfied, the "Y" circuit to the second stage condensing unit will be deenergized. This will allow the system cooling capacity to fall to 50%. The system will cycle off as detailed in stage one above. The second stage condensing unit usage will also alternate along with the first stage unit. BLOWER FAILURE LOCKOUT The twinning control fan sensors continuously monitor the fan motors for proper system operation. The system shuts down if either fails to operate. If, during a call for heat, cooling or fan, only one furnace blower is sensed to be "on", the system will shut down. No heating or cooling will take place unless both blowers operate. The LED on the twinning control will blink a fault code indicating which furnace blower did not operate. The LED can blink, one, two, or three times, with a twosecond off interval between fault code sequences. These codes indicate the problem to be in #1, #2, or both furnaces. Following a lockout condition, the control must be reset by removing all inputs from the room thermostat. APPLICATION DUCT SYSTEM Twinned furnaces must only be applied on a common duct system. A single air supply plenum must be used for both furnaces and coil(s). Separate plenums and supply ducts systems cannot be utilized. A single return air plenum, common to both furnaces must be used. It is suggested that a return platform be utilized, with bottom air entrance into each furnace. If a side entrance return system is used, the common return duct must be divided equally so as to supply each furnace with an equal amount of return air. Both furnaces must be identical models in both heating capacity and CFM capacity. Both furnaces must be operated on the same motor speed tap. The cooling speed connection is used for all heating, cooling, and fan only operation. See typical application, Figure 2. NOTE: When two furnaces are twinned, typical system total airflow will be approximately 85% of additive individual furnaces, i.e., two 2000 cfm units will yield a total 3400 cfm. If a return duct is connected to only one furnace (with a connection between the two furnaces) an imbalance in the air flow will occur and the furnace furthest from the return plenum will overheat. GAS PIPING Furnace gas supplies must be provided as specified with the basic furnace instruction. Since the furnaces are side, by side, with no space between, gas supplies must enter on the right and left respectively. Follow the details in the basic furnace instruction for proper connection. NOTE: All gas piping must be in accordance with both the National Fuel Gas Code, ANSI Z223.1, latest edition, and/or all local code or utility requirements. FURNACE VENTING Vent furnaces as detailed in the individual furnace installation instructions. All vents must be in accordance with the National Fuel Gas Code, ANSI Unitary Products Group 3

Z223.1 latest edition, and/or all local code or utility requirements. INSTALLATION - ALL MODELS POWER WIRING CONNECTION Furnace power supplies must be provided as specified in the basic furnace instruction. Since the furnaces are side by side, with no space between, power supplies must enter on the right and left respectively. Follow the details in the basic furnace instruction to move any power connection points. The twinning control does not require a 120 volt power supply. Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. NOTE: All wiring must be in accordance with both the National Electric Code, latest edition, and all local electrical codes. MOUNTING THE CONTROL The control should be mounted at a location convenient to both furnaces. The location must be near enough to the furnaces that the 15 ft. blower sensor cables will reach. Mount with #6 screws through the corner locations. The control must be mounted in a location where temperature ranges do not exceed -40 F to 120 F. If control is mounted on a furnace panel, be sure that the screws do not interfere with any wires, components, or safe working conditions within the furnace. CONTROL WIRING CONNECTION The twinning control uses all low voltage wiring between both furnaces and the room thermostat. Use adequate wire size for all control circuit loads just as you would with any thermostat, 18 AWG minimum. Connect the room thermostat to the twinning control. Connect the twinning control to each furnace. All control wiring must be connected as shown in Figure 7. Each furnace should be identified with a number in order to eliminate confusion. The furnace connected to the twinning kit terminals identified as "Furnace #1", will provide the 24 volt power required to power the control. FIGURE 3: JUMPE TERMINALS WIRE MUST BE POSITIONED BETWEEN CLAMP AND TERMINAL BLOCK SINGLE STAGE OPERATION If single stage heat operation is used, the "W1" and "W2" terminals must be jumpered at the twinning control as shown in Figure 3. If single stage cooling is desired, the "Y1" and "Y2" terminals must be jumpered. 4 Unitary Products Group

FIGURE 4: TYPICAL FAN/LED SENSOR CONNECTIONS HEAT ANTICIPATOR SETTING Set the heat anticipator in the room thermostat at.16 amps on single stage installations. This is when both furnaces are always operated together. For two stage systems, set the first stage anticipator at.16 amps and set the second stage anticipator at minimum (lowest setting available). Some electronic thermostats will not have a heat anticipator adjustment. MOUNTING THE FAN / LED SENSORS Included with the control are two, 1-in. black cubes with 12 in., wire leads and a 15 ft. cable. These are the fan/ LED sensors and one must be used on each furnace. Taking into account the wiring connections, choose a convenient mounting location for the sensor. It may be mounted on any clean, flat surface using the attached adhesive foam tape. Refer to the correct furnace type section on connecting the sensors before mounting. SECTION 1 - WIRING FAN / LED SENSORS ON ALL DIRECT DRIVE MODELS Locate any two motor speed wires in the control box area. The motor wires may be used (connected) or unused (taped) Do not use the common (white) wire. Connect the black blower sensor wires to any two of the motor speed wires as shown in Figures 4 & 6. If not used, the fault signal wires must be individually isolated and taped to prevent shorting to ground. SECTION 2 - WIRING FAN / LED SENSORS ON 230 VOLT BELT DRIVE UNITS Accessory sensor Model 2TS03700106 must be used or the twinning control will be damaged. Locate the two black blower motor wires that are connected to the contactor. Remove the strain relief Unitary Products Group 5

through which these wires pass into the control enclosure. Remove one of these wires from the contactor. It does not matter which one is chosen. FIGURE 5: FAN SENSOR/CURRENT TRANSFORMER CONNECTIONS ON BELT DRIVE UNITS ONLY Wrap this wire around the unused core of the current transformer three times as shown in Figure 5. Cut the existing wire ties if more usable wire length is needed. 1R-1 BLOWER MOTOR 1R-2 Pull this wire so that it wraps tightly around the core (See Figure 5). Secure wire tightly in place using a wire tie. Reconnect the black motor wire onto the contactor. It must connect to the same terminal from which it was removed. Reconnect the strain relief and re-secure the fan motor wires (as they were originally) with the remaining wire ties. The current transformer has two short leads with 1/4" male spade terminals. Connect these leads to the two black leads of the fan/led sensor. See Figure 6. CONNECT THESE WIRES TO THE BLACK LEADS ON THE FAN/LED SENSOR FAN/LED SENSOR` 2TS03700106 CURRENT TRANSFORMER LED SENSOR` WIRES NOT USED (TAPE) TO FAN CONTACTOR TIE WIRE FAN MOTOR WIRE SENSOR WIRES TO TWINNING CONTROL 6 Unitary Products Group

Unitary Products Group 7 COOL HEAT PARK (w/terminals) Fan/LED Sensor (without terminals) Note: LED sensor wires not used (tape) FURNACE #2 G Y W R C COOL HEAT PARK (w/terminals) G Y W R C FURNACE #1 Fan/LED Sensor (without terminals) Note: LED sensor wires not used (tape) FAULT SIGNAL C (COM) R (24V) W (HEAT) Y (COOL) G (FAN) G (FAN) Y(COOL) W (HEAT) R (24V) C (COM) (+) (-) FLASH 1 = FURNACE 1 FLASH 2 = FURNACE 2 FLASH 3 = BOTH FAN/LED SENSOR FURNACE T'STAT FURNACE T'STAT FAN/LED SENSOR F U R A N C E 2 F U R A N C E 1 REMOTE FAULT SIGNAL OUTPUT SEE INSTRUCTIONS FOR ELECTRICAL SPECIFICATIONS OF REMOTE DEVICE 2TC03700124 TWINNING CONTROL THERMOSTAT CONNECTIONS (1ST STAGEHEAT) W1 (2ND STAGE HEAT W2 (1ST STAGE COOL) Y1 (2ND STAGE COOL) Y2 (FAN) G (SUPPLY) R (COMMON) C FOR SINGLE STAGE OPERATION: HEATING: JUMPER W1-W2 COOLING: JUMPER Y1-Y2 INPUT: 24VAC, 50-/60 HZ (FROM FURNACE 1 XFMR) OUTPUTS: 2 A MAX. (EACH FUNCT.) T'STAT ANTICIPATOR SETTING: 0.16A Y88FA-1 JOHNSON CONTROLS O PATENTS PENDING ROOM THERMOSTAT W1 W2 Y1 Y2 G R C X1 X2 FIGURE 6: FURNACE CONTROL WIRING 035-14572-000 REV. A (800)

NOTES Subject to change without notice. Printed in U.S.A. 035-14572-000 REV. A (800) Copyright by Unitary Products Group 2000. All rights reserved. Supersedes: 650.69-N2.7V (899) Unitary 5005 York Norman Product Drive OK Group North 73069