Causes of Noise Generation & its Mitigation in Transformer

Similar documents
Active noise control in practice: transformer station

DIRECT CURRENT GENERATORS

DC GENERATOR THEORY. LIST the three conditions necessary to induce a voltage into a conductor.

Line Reactors and AC Drives

How to Optimize Performance and Minimize Size in High Speed Applications High Performance Brushless DC Motors

Transformer Design & Design Parameters

Basics of Electricity

Theory of Heating by Induction

Variable Frequency Drives - a Comparison of VSI versus LCI Systems

Understanding the Alternator

Understanding Transformer Noise

1. The diagram below represents magnetic lines of force within a region of space.

Iron Powder Cores for Switchmode Power Supply Inductors. by: Jim Cox

Selecting IHLP Composite Inductors for Non-Isolated Converters Utilizing Vishay s Application Sheet

UNDERSTANDING AND CONTROLLING COMMON-MODE EMISSIONS IN HIGH-POWER ELECTRONICS

Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading. Ramandeep Kaur Aujla S.NO

AC Induction Motor Slip What It Is And How To Minimize It

Once you know the volume of air and the static pressure of the system to be cooled, you can determine the fan specifications for your product.

MEMBRANE VACUUM MINI PUMPS

FREQUENCY CONTROLLED AC MOTOR DRIVE

2. Permanent Magnet (De-) Magnetization 2.1 Methodology

32:(5#5$7,1* 4833#USP283#+] 4;33#USP293#+] 3ULPH 113 kva, 90 kw 124 kva, 99 kw 6WDQGE\ 114 kva, 91 kw 125 kva, 100 kw

Product Data Bulletin

Digital Energy ITI. Instrument Transformer Basic Technical Information and Application

2. A conductor of length 2m moves at 4m/s at 30 to a uniform magnetic field of 0.1T. Which one of the following gives the e.m.f. generated?

General Thoughts on Generator Set - Acoustic Solutions & Noise Control

1150 hp motor design, electromagnetic and thermal analysis

CHAPTER 4 DESIGN OF INTEGRAL SLOT AND FRACTIONAL SLOT BRUSHLESS DC MOTOR

THIS paper reports some results of a research, which aims to investigate the

Application Note. So You Need to Measure Some Inductors?

Transformer Calculations

OVERCURRENT & EARTH FAULT RELAYS. To study the protection of equipment and system by relays in conjunction with switchgear.

Noise associated with the ground water systems serving residential geothermal heat pumps

Current Probes. User Manual

Rotating Machinery Diagnostics & Instrumentation Solutions for Maintenance That Matters

Principles of Adjustable Frequency Drives

Fan Basics and Selection Criteria (How to Use)

8 Speed control of Induction Machines

Build Green Schools. Click on this link for more information.

An equivalent circuit of a loop antenna.

Specifying a Variable Frequency Drive s

Iron core Material-Somaloy Unique magnetic properties High purity iron powder Electrically insulated surface. Result in.

Mathematical Modelling of PMSM Vector Control System Based on SVPWM with PI Controller Using MATLAB

EMC STANDARDS STANDARDS AND STANDARD MAKING BODIES. International. International Electrotechnical Commission (IEC)

Motor Fundamentals. DC Motor

AC generator theory. Resources and methods for learning about these subjects (list a few here, in preparation for your research):

We will discuss common industrial applications with guides for the proper use of electric motors on these.

DC MOTOR ANALYSIS & TROUBLESHOOTING

SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS

SUNON SPECIFICATION FOR APPROVAL DESCRIPTION : DC BRUSHLESS FAN. DIMENSIONS : 60X60X15 mm M O D E L : KD0506PHS2

understanding medium frequency induction melting furnace and its components


A METHOD OF CALIBRATING HELMHOLTZ COILS FOR THE MEASUREMENT OF PERMANENT MAGNETS

Equipment: Power Supply, DAI, Universal motor (8254), Electrodynamometer (8960), timing belt.

TOP 10 NOISE CONTROL TECHNIQUES

Lesson 3 DIRECT AND ALTERNATING CURRENTS. Task. The skills and knowledge taught in this lesson are common to all missile repairer tasks.

Unit 6 Transformers. Lead-in. Basic principles. Task 1. Task 2. What applications of transformers do you know?

d di Flux (B) Current (H)

3) What is the difference between "Insulating", "Isolating", and "Shielded Winding" transformers?

Lab 8: DC generators: shunt, series, and compounded.

Paralleling Power Sources Which Share a Common Neutral

How To Reduce Noise From A Test Screen

Chen. Vibration Motor. Application note

Direction of current flow through conductor. Fig. 1 Magnetic field generated by current flow

Components. Transformers

Acoustic Terms, Definitions and General Information

Single-Phase AC Synchronous Generator

Chapter 22: Electric motors and electromagnetic induction

EMI in Electric Vehicles

MAGNETICS: FERRITES, BEADS and BALUNS

Drive circuit basics + V. τ e. Industrial Circuits Application Note. Winding resistance and inductance

Constructing a precision SWR meter and antenna analyzer. Mike Brink HNF, Design Technologist.

High Voltage Power Supplies for Analytical Instrumentation

USE OF ARNO CONVERTER AND MOTOR-GENERATOR SET TO CONVERT A SINGLE-PHASE AC SUPPLY TO A THREE-PHASE AC FOR CONTROLLING THE SPEED OF A THREE-PHASE INDUCTION MOTOR BY USING A THREE-PHASE TO THREE-PHASE CYCLOCONVERTER

Chapter 11 SERVO VALVES. Fluid Power Circuits and Controls, John S.Cundiff, 2001

GenTech Practice Questions

E. K. A. ADVANCED PHYSICS LABORATORY PHYSICS 3081, 4051 NUCLEAR MAGNETIC RESONANCE

A Practical Guide to Free Energy Devices

Diesel Engine Driven Generators Page 1 of 6

The Emergence of Brushless DC Motors Within Medical Applications

EMI and t Layout Fundamentals for Switched-Mode Circuits

Analysis of Space Vector Pulse Width Modulation VSI Induction Motor on various conditions

Generators TEM. for small hydroelectric power stations. Electric Machines

WIND TURBINE TECHNOLOGY

AC Electric Motors best practice

EFFECT OF OBSTRUCTION NEAR FAN INLET ON FAN HEAT SINK PERFORMANCE

AC Motor Speed. n s = synchronous speed (in RPM), f = frequency (in Hz), and p = the number of poles

Sigma Frequency Control

Single and Three Phase Transformer Testing Using Static Motor Circuit Analysis Techniques

NUCLEAR MAGNETIC RESONANCE. Advanced Laboratory, Physics 407, University of Wisconsin Madison, Wisconsin 53706

SUNON SPECIFICATION FOR APPROVAL

Subject: Glenair MIL-PRF Conduit Surface Transfer Impedance Test

The DC Motor/Generator Commutation Mystery. Commutation and Brushes. DC Machine Basics

Linear DC Motors Magnetic Flux Permanent Bar Magnets

Candidate Number. General Certificate of Education Advanced Level Examination June 2014

Introduction. Harmonics and IEEE 519 Page 1 of 19

2 Ohm Nominal Coaxial Speaker OWNER S MANUAL

Documenting Results to Validate Energy Savings Projects: Case Study of Direct Drive Cooling Tower Installations: Before and After

Survey of Harmonics Measurements in Electrical Distribution System of a Technical Institution

Annex-A TECHNICAL SPECIFICATION

Transcription:

Causes of Noise Generation & its Mitigation in Transformer Ruchi Negi 1, Prateek Singh 2, Gaurav Kr. Shah 3 Third year Student, Dept. of Electrical and Electronics Engineering, MIT, Moradabad, India 1 Final year Student, Dept. of Electrical and Electronics Engineering, MIT, Moradabad, India 2 Third year Student, Dept. of Electrical Engineering, MIT, Moradabad, India 3 Abstract: This paper presents causes of noise generation in transformers and its mitigation. The ministry of environment has specified noise level for different areas i.e. industrial, commercial and residential. In this paper there are three causes of noise generation in transformer i.e. core sound, load sound and sound by cooling fans & pumps. Various methods are suggested in this paper in order to mitigate the sound in transformer. Keywords: Magnetostriction, Magnetic Forces, Magnetic Hysteresis. I. INTRODUCTION Transformer in operation emits a noise, the magnitude of noise increases with increase in its capacity. It is common to see an electrical transformer near your locality. While passing by your street near to the transformers, you might have heard a continuous vibration like noise near the transformers which seems like hum. Though it seems, nothing is moving inside it unlike electric motors and generators. Actually, inside the transformer there is no rotating part as in motors and generators, but still they produce the sound because of Magnetostriction Effect which occurs inside the transformer, Magnetostriction effect is one of the important property of ferromagnetic materials. Due to this property, whenever a ferromagnetic material comes in contact of varying magnetic field, it changes its dimensions. Inside a transformer is nothing but magnetic core wound by a number of turns of wires on two sides. In one side, AC voltage is applied and on another side stepped up or stepped down voltage is received. Well we might be aware that AC alternates its direction after every half cycle. Due to this variation in applied voltage, Varying magnetic field is produced and these varying magnetic fields changes dimensions of the ferromagnetic material used as the transformer component and it appears as vibrations. These vibrations are the source of the noise or hmmm... like sound in the transformers. Earlier the sound produced by transformer had been of secondary importance. It has now become a matter of concern due to growing public concern about the environmental noise pollution. In INDIA and many other countries, the Ministry of Environment and Forest Notification specifies the acceptable limits of sound level in db as shown in Table-1 below. Table 1: Ambient Air Quality Standards in respect of Noise S.No. Category of Area/Zone Limits in db(a) Day Time Night Time (A) Industrial area 75 70 (B) Commercial area 65 55 (C) Residential area 55 45 (D) Silence Zone 50 40 Note:- 1. Day time shall mean from 6.00 a.m. to 10.00 p.m. 2. Night time shall mean from 10.00 p.m. to 6.00 a.m. 3. Silence zone is defined as an area comprising not less than 100 meters around hospitals,educational institutions and courts. The silence zones are zones, which are declared as such by the competent authority. Copyright to IJAREEIE www.ijareeie.com 1732

II. SOURCES OF SOUND GENERATION IN TRANSFORMER There are three basic sources 5of sound generation in power transformer as shown in Figure-1. Figure 1: Transformer Sound 1. Core Noise: Transformer Noise is caused by a phenomenon called Magnetostriction, which occurs inside the transformers. Magnetostriction is a phenomenon by which a metallic objects experiences a distortion in its shape when it is placed inside a magnetic field. The objects can experience a change in the dimensions, expansion or contraction. Inside a transformer, the core, which is made in the form of laminated sheets, also undergoes expansion and contraction due to the changing magnetic flux. This expansion and contraction occurs twice in an ac cycle. The fundamental frequency of the noise or vibration is double that of the frequency of the power supply. Thus, a supply with a frequency of 50 Hz will cause noise or vibration whose fundamental frequency is 100 Hz. Figure 2: Magnetostriction 2. Load Noise: Load noise is caused by vibrations in tank walls, magnetic shields, and transformer windings due to the electromagnetic forces resulting from leakage fields produced by load currents. These electromagnetic forces are proportional to the square of the load currents. The load noise is predominantly produced by axial and radial vibration of transformer windings. However, marginally designed magnetic shielding can also be a significant source of sound in transformers. A rigid design Copyright to IJAREEIE www.ijareeie.com 1733

for laminated magnetic shields with firm anchoring to the tank walls can greatly reduce their influence on the overall load sound levels. The frequency of load noise is usually twice the power frequency. An appropriate mechanical design for laminated magnetic shields can be helpful in avoiding resonance in the tank walls. The design of the magnetic shields should take into account the effects of overloads to avoid saturation, which would cause higher sound levels during such operating conditions. The presence of harmonics in load current and voltage, most especially in rectifier transformers, can produce vibrations at twice the harmonic frequencies and thus a sizeable increase in the overall sound level of a transformer. Through several decades, the contribution of the load noise to the total transformer noise has remained moderate. However, in transformers designed with low induction levels and improved core designs for complying with low sound-level specifications, the load-dependent winding noise of electromagnetic origin can become a significant contributor to the overall sound level of the transformer. 3. Fan and Pump Sound: Power transformers generate considerable heat because of the losses in the core, coils, and other metallic structural components of the transformer. Fans that blow air over radiators or coolers remove this heat. Noise produced by the cooling fans is usually broadband in nature. Cooling fans usually contribute more to the total noise for transformers of smaller ratings and for transformers that are operated at lower levels of core induction. III. MITIGATION OF TRANSFORMER SOUND The various methods are used for mitigation of transformer sound are as follows: (a).no-load sound mitigation: Flux density: No-load sound level of core mainly depends on Magnetostriction and magnetic forces. The magnitude of Magnetostriction could be reduced by lowering flux density. Flux density is inversely proportional to the core weight. Therefore, that if we reduce the flux density in order to reduce the sound, core weight increases which in turn increases the cost. Choice of CRGO material: CRGO material, which is used for making the core, should have properties such as low loss, high permeability and low noise generation from core. Figure 3: B-H Curve for magnetic materials (b)magnetic Hysteresis Loops For Soft And Hard Materials: Magnetic Hysteresis results in the dissipation of wasted energy in the form of heat with the energy wasted being in proportion to the area of the magnetic hysteresis loop. Hysteresis losses will always be a problem in AC transformers where the current is constantly changing direction and thus the magnetic poles in the core will cause losses because they constantly reverse direction. Copyright to IJAREEIE www.ijareeie.com 1734

Figure 4: Magnetic Hysteresis Loops Rotating coils in DC machines will also incur hysteresis losses as they are alternately passing north the south magnetic poles. The shape of the hysteresis loop depends upon the nature of the iron or steel used and in the case of iron which is subjected to massive reversals of magnetism, for example transformer cores, it is important that the B-H hysteresis loop is as small as possible. (c) Cooling fans & oil pumps sound mitigation: Standard size of fan used are 18 & 24 inch with speed of 900-950 rpm and their sound level is in the range of 64-65dB. The fan noise is a function of speed and circumfential velocity. If the size of fans will be reduced number of fans increases. Therefore, it is better to increase number radiators. Therefore, ONAN cooling is preferred than ONAF cooling. Figure 5: Noise Spectrum IV. CONCLUSION Transformer cores can make acoustical noise like humming and rattling. The mechanisms that cause this noise inside the core have been explained. Proper transformer design, wiring, and, above all, grounding, are the only effective means of reducing the three types of noise problems. Grounding should be controlled and use the lowest impedance path possible (i.e., bonding) to the central reference ground system to insure maximum attenuation of noise sources. To achieve the maximum protection from a transformer, not only must it be applied properly, but also the transformer should be one specially designed for isolation usage. Since this process can t be stopped so the question arises is how to reduce this kind of noise. There are many ways to achieve that, one of the ways include sound insulation which can be done by: 1. We can use cushion padding and oil barriers which can help in insulating the sound of vibration and hence it will reduce the noise appearing to the users. 2. Insulation of sound from Ground and Air near to the transformers. 3. Using proper innovation designs and materials like stiffeners while constructing the walls of the transformer tanks. Some of the other ways that can be used are proper fixing and clamping of the laminations and frames of the transformers. If further reduction in audible noise is desired for a given transformer construction, the designer can reduce the peak flux density. Copyright to IJAREEIE www.ijareeie.com 1735

REFERENCES [1]. Ministry of Environment & Forest Notification Govt. Rule, New Delhi, Feb 14th 2000. [2]. J.G. Charles, The effect of the level of Magnetostriction upon noise & vibration of model Single-phase transformer. Electrical Research Association (ERA), January-1967. [3]. Jeewan Puri, Causes and Effects of Transformer Sound Levels. [4]. S. V. Kulkarni, S. A. Khaparde, Transformer engineering design and practice, 2004. [5]. H. V. Paghadar, Mitigation of Audible Sound in Transformer Trafotech-2010. [6]. T. Yanada, M. Matsuda, 0. Ichinokura and T. Jiiizenji. "Performance and Noise Attenuation Mechanism of Noise Reduction Trai1sforme.r." IEEE Trans. Magn., vol. 30, pp. 4860-4862. 1994. [7]. Ji Shengchang, Cheng Jin, Li Yanming, "Research on Vibration Characteristics of Windings and Core of Oil filled Transformer", Journal of Xi'an Jiaotong University,Vol.39, No.6, pp. 616~619, 2005. Copyright to IJAREEIE www.ijareeie.com 1736