SF 6 -insulated, extensible block module bus sectionaliser / bus riser panel

Similar documents
NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems. Safe energy distribution that meets the highest industrial requirements

Voltage Rated operating voltage [kv] Rated power frequency withstand voltage [kv] Rated lightning impulse withstand voltage [kv]

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV

ELEKTROTEHNI KO PODJETJE Leskoπkova cesta 12, 1000 Ljubljana, SLOVENIA

Our brand POWER DYNAMIC PASSION COMMITMENT CREATIVITY. A strong brand for strong products: 8PU Premium. MV Energy

3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & Instructions For Installation, Operation & Maintenance

Medium Voltage Products. ZN1 12 kv arc-proof air-insulated switchgear for primary distribution

Siemens AG Power Transmission and Distribution Medium Voltage Division Mozartstr. 31c Erlangen Germany.

METAL-CLAD AND METAL-ENCLOSED SWITCHGEAR 3.6KV~40.5KV. tgood.com. Energy. Fast.

e 2 ALPHA Medium Voltage Switchgear Data Sheet K EN

High-Voltage Compact Switchgear 3AP1 DTC for 145 kv and 245 kv

ALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU

PPS-PPQ-BT-PIAS RESIN INSULATORS FOR OIL INSULATED ELECTRICAL MACHINES

MNS is Switchgear System Technical Overview

Pressure monitoring equipment for oil-sf 6. bushings, type GOEK

Low Voltage Switchboards The Best Technical Solution for Your Ship

INTERNATIONAL POWER DISTRIBUTION CONGRESS CIDEL ARGENTINA 2002

Technical catalogue TK 503/01 E. ZX0.2 Gas-insulated medium voltage switchgear

ELEKTROTECHNISCHE WERKE FRITZ DRIESCHER & SÖHNE GMBH D MOOSBURG TEL FAX

KOLMA and IHDA Indoor type Cable Current Transformers Catalogue ABB Power Distribution ABB Transmit 1 KKOLMA 1 GB

Unified requirements for systems with voltages above 1 kv up to 15 kv

How To Build A Low Voltage Capacitor Lvcp

UniGear ZS1. Medium voltage, arc proof, air insulated switchgear for primary distribution

UFES Active protection for switchgear

Modular Systems, PPMV, 2014 UniPack-G Glass Fiber Reinforced Polyester Compact Secondary Substation

SURGE PROTECTIVE DEVICES

FAQs-Main switchboard design criteria

2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV a. Section INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.

Low Voltage Products. Switches Automatic Transfer Switches

HERZ-Thermal Actuators

Type-Tested Power Distribution Board 8PT with Rear Busbars. sivacon

The power distribution board that sets new standards

Safe and secure distribution of medium voltage with AX1

Technical data UNIBLOCK UBSF

Linear Luminaire with LED Series EXLUX 6402/2

Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components

CAS 36 Ring Main Unit

3/2-way Solenoid Valve, direct-acting, NC or NO

Terminal Boxes Series 8146

Advantages of Fixed Circuit Breaker Switchgear

R.C.C.B. s two-pole LEXIC

MEDIUM VOLTAGE SWITCHGEAR CATALOGUE. Code: P2490_xx

DF-DT (G) MEDIUM VOLTAGE SWITCHGEAR THE MODULAR CONCEPT. User Manual. SGC - SwitchGear Company nv - Moorstraat 24 - B-9850 Nevele - Belgium

Linear Luminaire for Fluorescent Lamps Series EXLUX 6001

AutoLink Three-Phase Sectionalizer Specifications. Scope. General. Applicable Standards. Operating principle

Series 8146/5-V37 and Series 8150/5-V37

MEDIUM VOLTAGE SWITCHGEAR. DI-2, a modular concept combining all mediumvoltage

1ZSE en, Rev. 8. Transformer bushings, type GOE and GOE(2) Technical guide

EVC40 EMERGENCY VOICE COMMUNICATION SYSTEM

TriLine ASSEMBLY System PowerModules

Masterclad Medium Voltage Passive Arc-Resistant Switchgear

Voltage Regulator SPAU 341 C. Product Guide

The Intelligent AX1 Switchgear for Medium Voltage

Application Switchgear for industrial and commercial applications. U e V AC 230/ (per pole)

Switchgear and Metal-Enclosed Bus

AUTOMATIC TRANSFER SWITCH. Changeover Type from 250A to 2500A

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

Safety technique. Emergency stop module BO 5988 safemaster

Medium-voltage transformers

Electronic timer CT-VBS OFF-delayed without auxiliary voltage, for DC contactors Data sheet

The complete range of consumer switchboards and switchgear

Transformer Bushings for GIS

Pluggable interface relays CR-P Pcb relays

SF 6 Gas Insulated Switchgear Type SDF for 170 kv

PSU-U-24V/AC-6A/10/FTA-TR-MC PSAC 0624

MEDIUM AND HIGH VOLTAGE CAPACITORS, CAPACITOR BANKS AND SYSTEMS

Installation, Operation and Maintenance Instructions. Uniflex ABB PTMV

Comparative study for cables and busbars

2. INDUCTIVE VOLTAGE TRANSFORMERS Oil-paper insulation Gas insulation

Lightning Arresters P KVA P KVA. Description & Installation

1ZSC AAC en, Rev. 7. Resin impregnated paper bushing, oil to air, type GSB Technical guide

Dead Tank Circuit Breaker 72PM40-C Proven reliability through common platforms

DIGITUS Network & Server Cabinets. UNIQUE Series

SIVACON The Versatile Low-Voltage Switchboard

Vario-Series Accessories

DS 600. A contact free flux gate based current measurement sensor 600A rms

LV MCC LOW VOLTAGE SWITCHGEAR MOTOR CONTROL CENTRE PRODUCT GUIDE

Medium voltage products UniSec for Smart Grid Air-insulated medium-voltage secondary distribution switchgear

Secondary Unit Substations

EDITION 2012 CABLE SYSTEMS

VD4. Vacuum circuit-breaker

C I R E D 21 st International Conference on Electricity Distribution Frankfurt, 6-9 June 2011

Thyristor-controlled power supplies and battery chargers

PSDC PSDC 12V/8A/8x1A Power supply for up to 8 analog cameras PTC/TOPIC.

BLADE S-MAX Cabinet for Blade Server

Automation Products. Low Voltage Switchgear MNS System Overview

Services Enclosures and Protected Shafts - Maintaining Compartmentation

SIRCOVER. Manual changeover switches from 125 to 3200 A. Changeover switches. Function. Advantages. The solution for.

Medium Voltage Switchgear

RISH CON - Hz. Salient Features : Application : Product Features: FREQUENCY TRANSDUCER

ENERGY. TECWATER S1BN8-F 0,6/1 kv. Cable for Water Application

REVIEWED BY CAPITAL PROJECTS MANAGER (DAN REDDY) GENERAL MANAGER EQUIPMENT ENGINEERING & ASSET MANAGEMENT (HAMILTON NXUMALO)

Type: DILM115(RAC240) Article No.: Sales text Contactor,55kW/400V,AC operated. Ordering information

Laser diffuse reflection light scanner with background suppression. Dimensioned drawing

Control and Distribution Boxes made of Stainless Steel Series 8150

Permissible ambient temperature Operation Storage, transport

Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous

Selector Switch Type 08

Metal Enclosed Switchgears Metal Clad Switchgears Gas Insulated RMU's

OUTDOOR DISCONNECTORS A division of ACTOM (Pty) Ltd

Transcription:

SF 6 -insulated, extensible block module bus sectionaliser / bus riser panel Type GAE630-1KG/4/ 1H1-/4/ for accessible switchgear rooms for rated voltages of up to 24 kv

2 These operating instructions must only be used as a supplement to the operating instructions SF 6 -insulated, extensible ring-cable panel, Type GAE630-1K-/3/ (No. 12244745). All information and safety relevant instructions and regulations must also be observed when installing, operating and servicing the block module type GAE630-1KG/4/ 1H1-/4/! The block module consists of the bus sectionaliser load-break switch panel GAE630-1KG/4/ and the bus riser panel GAE630 1H1-/4/ and is factory pre-assembled. Both panels are bolted together with an intermediate frame. The outer and inner construction of the bus riser panel GAE630 1H1-/4/ complies with the cable panel. The job specification for the bus riser panel does not require any circuitry. Therefore the panel is equipped without switching drive. In combination with a bus sectionaliser load-break switch panel GAE630-1KG/4/ the bus riser panel is used for separation of the busbar running through the entire switching system into defined sections. The internally routed phase separated busbar (main current path) is guided to the cast resin bushings between bus sectionaliser panel and busbar riser panel. Both panels are joined by means of uncontrolled busbars through the side walls of the connection compartment. Separation of the internal busbar is accomplished by switching of the bus sectionaliser panel. The connection area of the bus riser panel is designed with a transparent PETG-screen against unauthorized access as standard, which is tightly bolted to the connection compartment behind the front panel. As a measure against the removal of the front panel during operation the fastener on the front panel can be optionally fitted with a lock.

3 Planning of installation floor fastening measurements GAE630-1KG/4/ GAE630 1H1-/4/ Fastening bores Ø 12 Floor contact area Floor opening * In the case of the installation of LSF panels, a minimum distance of 200 mm is necessary. Fig. 1 Floor fastening measurements (all dimensions are nominal dimensions [mm]) GAE630-1KG/4/ 1H1-/4/ with pressure relief into cable trench / raised floor GAE630-1KG/4/ GAE630 1H1-/4/ Fastening bores Ø 12 Floor contact area Earthing busbar Ø 70 Earthing standard Ø 30 Fig. 2 Floor fastening measurements (all dimensions are nominal dimensions [mm]) GAE630-1KG/4/ 1H1-/4/ with pressure relief via rear pressure absorber channel

4 Planning of installation dimensions Pressure absorber channel (optional) with minimum relay cabinet height 600 mm Note: Relay cabinet (300/600/900 mm) optional in case of switchgear without pressure absorber channel Fig. 3 Block module GAE630-1KG/4/ 1H1-/4/ (all dimensions are nominal dimensions [mm])

5 Planning of installation installation possibilities Installation possibilities for block modules in accessible switchgear rooms. Attention! During installation make sure not to damage the burst protection in the bottom of the gas tank. This diaphragm opens in case of an internal arc fault. The gases emerging must be discharged as shown in Fig. 4. The cable trench must have a defined minimum cross-section. For the optional pressure relief of the cable trench the following rule of thumb must be applied: up to 3 panels: one metal cooling stretch arrangement (400 x 600 mm) from 4 panels: a second metal cooling stretch arrangement of the same size. The metal cooling stretch arrangement must be arranged on site in a way that the cable trench is evenly divided. Metal cooling stretch arrangement (optional) Metal absorber In order to enhance the stability the back plate of the transformer outgoing panel can be fastened with two steel angles (not included in the scope of delivery). For this purpose use the screws from the transport device. Please ask for our assistance in the planning and installation of the station. The construction of the building and the switchgear room must withstand the expected mechanical loads and the internal pressure caused by a shortcircuit arc. Appropriate calculations for these purposes are recommended. Switchgear related pressure calculations can be requested as part of the services provided by the sales department at Ormazabal GmbH. Fig. 4 Cable trench/ Raised floor Panel base open Pressure relief into cable trench / raised floor Metal cooling stretch arrangement (optional) to cool down hot gases generated in case of an internal arc fault Panel base closed Pressure relief via metal absorber and rear pressure absorber channel into the switchgear room

6 Technical data General data Rated filling pressure of insulating gas at 20 C and 101.3 kpa 130 kpa (30 kpa overpressure) Insulating gas SF 6 SF 6 - filling weight at 20 C and 101,3 kpa 0.7 kg (each gas tank) Rated density of the insulating gas 7.9 kg/m 3 Ambient temperature without secondary equipment 25 to +40 C ( 40 to + 40 C on request) with secondary installations 1) 5 to +40 C ( 25 to + 40 C on request) with reduced rated currents above +40 C Relative humidity max. 95% (indoor conditions) Enclosure of the HV compartment sealed pressure system acc. to IEC, IP 65/IP4X Enclosure of the drive housing IP44 Enclosure of the connection compartment IP44 Arc-fault qualification according to VDE 0671 part 200 or IEC 62271-200 respectively Coloration of equipment Loss of service continuity category Partition class Weight block module GAE630-1KG/4/ 1H1-/4/ Table 1 IAC AFL 20 ka 1 s for HV compartment and connection compartment RAL 7035 (light grey) LSC 2A PM approx. 290 kg (approx. 470 kg with pressure absorber channels) 1) dependent on the secondary technology used Rated values bus sectionaliser load-break switch panel GAE630-1KG/4/ Switch Earthing switch Rated frequency f r 50/60 Hz 50/60 Hz Rated voltage U r 12/24 kv 12/24 kv Rated normal current I r 630 A - Rated short-duration power-frequency withstand voltage U d 50 kv 50 kv 1 min Rated lightning impulse withstand voltage U w 125 kv 125 kv Rated lightening impulse withstand voltage of the isolating U p 145 kv - gap Rated mainly active load-breaking current I 1 630 A - Rated cable-charging breaking current I 4a 50 A - Rated earth fault breaking current I 6a 160 A - Rated cable- and line-charging breaking current under earth I 6b 100 A - fault conditions Rated peak withstand current I p 50 ka 50 ka Rated short-time withstand current 1 s, optionally 3 s I K 20 ka 20 ka Rated short-circuit making current I ma 50 ka 50 ka Number of switching operations under n 100 - rated mainly active load-breaking current Number of switching operations under n 5 5 rated short-circuit making current Number of mechanical switching operations n 1000 1000 Class - E3 M1 E2 Table 2

7 Rated values bus riser panel GAE630 1H1-/4/ Rated frequency f r 50/60 Hz Rated voltage U r 12/24 kv Rated current I r 630 A Rated short-duration power-frequency withstand voltage 1 min U d 50 kv Rated lightning impulse withstand voltage U w 125 kv Rated lightning impulse withstand voltage of the air gap U p 145 kv Rated peak withstand current I p 50 ka Rated short-time current I K 20 ka Table 3

Ormazabal Anlagentechnik GmbH Am Neuerhof 31 D-47804 Krefeld, Germany Tel.: +49 2151 7151-0 Fax: +49 2151 7151-75 E-mail: anlagentechnik@ormazabal.de Internet: www.ormazabal.de Printed in the Federal Republic of Germany Subject to change without notice