General Purpose PT100 Temperature Sensors

Similar documents
Errors Related to Cable Resistance Imbalance in Three Wire RTDs

Product data sheet. JUMO MIDAS Pressure Transmitter. Sales No. Order code JUMO AS /

RTD Temperature Probe for the Food/Pharmaceutical Industry

Temperature sensor with integrated transmitter for industrial applications, MBT 3560

A99B Series Temperature Sensors

Improving Temperature Measurement to Optimize Inventory Control and Custody Transfer Systems

Test equipment for temperature and its reduction

ATL Fuel Level Sender Probes

Basic RTD Measurements. Basics of Resistance Temperature Detectors

How To Read A Pipe From A Sensor

Technical Data. Dimensions

OEM Pressure Transmitters for heavy-duty applications, Type MBS 1200 and MBS 1250

Digital display DA 48

Thermometer in stainless steel with capillary and switch contacts

Digital inductive conductivity transmitter

Turbine Flow Sensor Series VTR

BM SERIES WAVE COMPACT 6.3 GHZ CW SERIES PULSE RADAR LEVEL INSTRUMENTS (6.3 GHz)

DiwiTherm, Resistance Thermometers Model TR75, with digital Display Battery or Solar Powered

The Do s and Don ts of Pressure Transducers

Electronic Flow Switches

Pressure transmitter For general industrial applications Model A-10

Plastic tube flowmeters Series PT/PS

SITRANS F flowmeters SITRANS F M

Online data sheet PET-1CB010N10SVMC PET PRESSURE SENSORS

Temp-485-Pt100. A temperature sensor (Pt100 or Pt1000) communicating over the RS-485 bus with a simple communication protocol

Rosemount DIN-Style Temperature Sensors and Thermowells (Metric)

Inductive sensor NI10-M18-Y1X-H1141

Typical Aluminum GFM Mass Flow Meter

Instructions Manual. Electromagnetic sensor Series FLOMID FX. instrumentation for fluids. R-MI-FlomidFX Rev.: 0 English version

DMP 331. Industrial Pressure Transmitter for Low Pressure. Stainless Steel Sensor

MTI10 Insertion and MTL10 In-line Thermal Mass Flowmeter and Temperature Transmitter

Portable digital microprocessor thermometers with interchangeable probes

Pressure monitoring equipment for oil-sf 6. bushings, type GOEK

Vehicle Brake System Monitoring 2-wire, 4-20 ma option; Intrinsic Safety Approval to E Exia IIC T4 (Tamb=60 C) BASEEFA, CENELEC EN50-020

CALIBRATION OF A THERMISTOR THERMOMETER (version = fall 2001)

Temperature Calibration; Depths of Immersion

Electro-Magnetic Flowmeters COPA-XT 2-Wire DT43

Givare NC-SRS 280 och 880

Festoon 715 P PUR cable for flexible application in festoon systems

Features. Picture. Specifications

The Unique Accelabar Flow Meter

PMP 4000 Series. Druck Amplified Output Pressure Transducers. GE Sensing. Applications. Features

Introduction to Fiber Optic Cables. Photoelectric Sensors. 2Photoelectric Sensors, Standard Sensors, Fiber optic cables. Please Note!

DSD 70 Dual Channel Hall Effect Speed Sensor for Railway Applications, compliant with EN 50155

Models SFP33 & SFP32 Pressure Transmitters

In-Line Electronic Flow Switches

Thermocouples & Thermoresistances

Sanitary Type Electronic Flow Switches

Relative and absolute pressure switch type 529

Certified according to DIN EN ISO 9001 Technical Datasheet C-Flow Coriolis Mass Flow Meter

Position Transducers with Restoring Spring 10, 25, 50, 75, 100 mm TR, TRS Series

psens Pressure Measurement

Electronic pressure switch with display Model PSD-30, standard version Model PSD-31, with flush diaphragm

Data Sheet PS1B Pressure Switch

MGO Insulated Thermocouples Index

Technical Data. General specifications Switching element function Rated operating distance s n 5 mm

Thermal flow sensors TA10-ZG8c and TA10-ZG9c for exact and stable, long-term measuring of lower flow velocities (Laminar Flow)

Level Switch LBFS. Technical Data. ATEX data Internal inductivity Li < 10 μh Internal capacity Ci < 43 nf Barrier data. Sensor

Evaluation copy. Build a Temperature Sensor. Project PROJECT DESIGN REQUIREMENTS

F ox W hi t e Paper. Reduce Energy Costs and Enhance Emissions Monitoring Systems

crm+25/d/tc/e Extract from our online catalogue: Current to:

Subminiature Load Cell Model 8417

Flow switches Series AD/VH

How To Make An Ultrasonic Sensor

ENAiKOON ultrasonic fuel-level sensor

Relative pressure transmitter type 520

RHE12. Hazardous Area Coriolis Mass Flow Transmitter. Features. Applications. Benefits

Technical Data. Dimensions

key- precision Tecum cuil Ludere ipsae. Possem Precision level detection When space and price matter Pointek CLS 100

HEAT MONITORING AND CONTROL INSTRUMENTS FOR TRANSFORMERS MB 103 TEMPERATURE CONTROL UNIT PT 100 TEMPERATURE SENSOR

ALARMLINE ANALOGUE Linear Heat Detection System

Installation Guidelines: Resistance Thermometers and Temptran Thermometers for Building Automation Systems

Temperature, hygrometry, CO and CO 2. probes for class 310 transmitters

Series 510 Submersible Level Transmitters

THE STRAIN GAGE PRESSURE TRANSDUCER

Heat Tracing is the use of an externally applied heat source to a pipeline to compensate for heat losses through the thermal insulation.

PD30ETB20xxIS. Photoelectrics, Background Suppression reflective with IR light. Main features. Description

HARAX circular connector

Certified according to DIN EN ISO 9001 Technical Datasheet KVO Series Vortex Flow Meter

Pipe Temperature Sensors

THERMAL ANEMOMETRY ELECTRONICS, SOFTWARE AND ACCESSORIES

How To Control A Power Supply With A Mini Transmitter And Switch (Power Supply)

Clear Glass Sensor. Ordering Information E3S-CR67/62. Optimum Sensor for Detecting Transparent Glass and Plastic Bottles

APPLICATION NOTES OF SIGNAL ISOLATORS

Capteur température et humidité pour HVAC

Electromagnetic Flow Meter

Of all the physical properties, it is temperature, which is being measured most often.

K Standard Grade Ni-Cr vs Ni-Al (Chromel vs Alumel)

MEITRACK Fuel Sensor User Guide. Applicable Model: MVT600/T1/MVT800/T333

4 Posiflow Proportional Solenoid Valves

Safety at a high level!

APG. PT-400 Heavy Duty, Amplified Output Pressure Transducer

Cables. Accessories. For Force, Torque and Strain Sensors

How To Use A Ds340 (Dsp)

Liquid Leakage Sensor Amplifier

PRODUCT PROFILE FEATURES

PART 1 - INTRODUCTION...

Microcontroller to Sensor Interfacing Techniques

Transcription:

General Purpose PT100 Temperature Sensors These general purpose sensors can be used in most liquid and air applications. Compression fittings are also available for installation. These probes can be used as stand-alone sensors, or they can be configured with a variety of termination options, and combined with controllers, indicators, or precision thermometers to create complete measurement systems. Accessories Specification Material Body : Stainless steel AISI 316L (1.4404) Sensing Elements: PT100 Platinum Elements per IEC751 (alpha = 0.00385 Ω/Ω/ C) Accuracy : ±0.03ºC to ±0.3ºC depending upon class selection Operating Temperature: from -200 to + 650ºC selection dependant Output: Pt100 Cable Type: Selection PFA-Silicone-PVC-Fibreglass Protection: IP65 Enclosures 4/20mA Transmitters Fittings Controllers

RTM13 Model Maximum Opertaing Temperature 250C 650C Number of Wires 3 wire = 3W 4 wire = 4W Element/Tolerance S = Single D = Duplex B = Class B A = Class A 10 = Class 1/10th Sheath Diameter 3 =3mm, 6 = 6mm, 8 = 8mm, 10= 10mm Sheath Length in mm Cable Length in meters Cable Type PVC, PTFE, Silcone Rubber = SR, Fibreglass with Braid = FGSSOB Stainless Steel Flexible Conduit = SSFC Process Fitting 0 = None, 14= 1/4", 12 =1/2", 34 = 3/4", UN = Union, DF=Duct Flange

Sensor Configuration/Assembly Termination Heads PVC -10C to 105C Good general purpose insulation for medium temperature environments. Waterproof and very flexible. PTFE -260C to +260C Resistant to oils, acids, other adverse agents and fluids. Good mechanical strength and flexibility. Silicone Rubber -50 to +200 Offers excellent dielectric strength and flexibility. Operation over a wide temperature range and ease of silastic bonding are other outstanding characteristics of silicone rubber cable. Glass fibre (Varnished) -60C to 350C Good temperature range but will not prevent ingress of fluids. Fairly flexible but does not provide good mechanical protection. Stainless Steel Flexible Conduit withstands high temperatures Durable crush-proof construction Corrosion and rust resistant

Sensor Configuration/Assembly Fittings Type: UN Type: DF Type: FT

Wiring Configuration. Two Wire When accuracy is not critical, a two-wire RTD is the least expensive; offering. Using lead wires to place any distance between a two wire RTD and a receiving device will further compromise its accuracy. The potential for poor accuracy from a two-wire RTD stems from its inability to compensate for lead length, resistance that changes the ohm value of the original signal. A two-wire RTD should be used only in applications where the receiving device connects directly to the sensor Three Wire RTD Three-wire RTD's compensate for resistance resulting from length differences by adding a third lead to the RTD. To accomplish this requires that the wires match exactly. Any difference in resistance between the lead wires will cause an imbalance, which will compromise the accuracy of the RTD. Lead length variance, work hardening or corrosion, and manufacturing irregularities are errors to avoid. Quality manufacturing is critical to insure balance of all three leads. Four Wire RTD Errors caused by resistance imbalance between leads are cancelled out in a fourwire RTD circuit. Four-wire RTD's are used where superior accuracy is critical or if the sensor is installed far from the receiving device. In a four-wire RTD one pair of wires carries the current through the RTD the other pair senses the voltage across the RTD. 2- and three-wire RTD's require heavier lead wire because thicker wire, by creating less resistance to the measured signal, reduces measurement distortion. Therefore lighter gauge wire, less expensive, may be used in four-wire RTD applications. RTD's are limited to temperatures of 1200 F and because of the construction of the sensing element, RTD's do not do well in high-vibration and severe mechanical shock environments. When selecting a temperature sensor for an application you should consult your temperature sensor manufacturer for recommendations.

Accuracy, Stability, and Repeatability. Tolerance/Accuracy is calculated as: Class B change in t=+/- (0.3+0.005 t ) Class A change in t=+/- (0.15+0.002 t ) 1/3 Class B change in t=+/- 1/3 x (0.3+0.005 t ) 1/5 Class B change in t=+/- 1/5 x (0.3+0.005 t ) 1/10 Class B change in t=+/- 1/10 x (0.3+0.005 t ) t = absolute temperature in C. Where elements have a resistance of n x 100 Ohms then the basic values and tolerances also have to be multiplied by n These three terms are often confused, but it is important to understand the difference. Accuracy. IEC standard 751 sets two tolerance classes for the accuracy of RTDs: Class A and Class B: Class A: Δt = ±(0.15 + 0.002 t ) Class B: Δt = ±(0.30 + 0.005 t ) where: t = absolute value of temperature in C Class A applies to temperatures from 200 C to 650 C, and only for RTDs with three- or four-wire configurations. Class B covers the entire range from 200 C to 850 C. Stability. This is the sensor's ability to maintain a consistent output when a constant input is applied. Physical or chemical changes can cause calibration drift. The material that the platinum is Figure 3. Lead wires have resistance that is a function of the material used, wire size, and lead length. This resistance can add to the measured RTD resistance, and improper wire compensation can result in significant errors. The common configurations of RTDs are two (A), three (B), or four wires (C). adhered to, whether wound on a mandrel or on a substrate, can expand and contract, straining the wire. Drift rates conservatively specified by manufacturers are typically 0.05 C/yr. Repeatability. Repeatability is the sensor's ability to give the same output or reading under repeated identical conditions. Absolute accuracy is not necessary in most applications. The focus should be on the stability and repeatability of the sensor. If an RTD in a 100.00 C bath consistently reads 100.06 C, the electronics can easily compensate for this error. The stability of RTDs is exceptional, with most experiencing drift rates of 0.05 C over a five-year period. Response Time. Response time varies according to the application. It is the sensor's ability to react to a change in temperature, and depends on the sensor's thermal mass and proximity to the material being tested. For instance, an RTD sensor in a thermowell will react more slowly than the same sensor immersed directly into a process. RTD specifications will list the sensor's time constant, which is the time it takes for an RTD to respond to a step change in temperature and come to 63% of its final equilibrium value. Response times are calculated in water flowing at 0.2 m/s and in air flowing at 1 m/s. This gives a useful comparison of RTD sensor configurations.

RTD accuracy Class A, Class B, 1/3 DIN, 1/10 DIN ACTUAL RTD ACCURACY +/- C PT100 Ω ALPHA 0.003850 to DIN 43760 IEC751 DIN EN 60 751 B GRADE A GRADE BAND 3 (1/3 DIN) BAND 5 (1/10 DIN) -200 C 1.30 C 0.55 C 0.39 C 0.38 C -150 C 1.05 C 0.45 C 0.23 C 0.21 C -100 C 0.80 C 0.35 C 0.15 C 0.12 C -90 C 0.75 C 0.33 C 0.14 C 0.10 C -80 C 0.70 C 0.31 C 0.13 C 0.09 C -70 C 0.65 C 0.29 C 0.12 C 0.08 C -60 C 0.60 C 0.27 C 0.11 C 0.07 C -50 C 0.55 C 0.25 C 0.10 C 0.06 C -40 C 0.50 C 0.23 C 0.10 C 0.06 C -30 C 0.45 C 0.21 C 0.09 C 0.05 C -20 C 0.40 C 0.19 C 0.09 C 0.04 C -10 C 0.37 C 0.17 C 0.08 C 0.03 C 0 C 0.30 C 0.15 C 0.08 C 0.03 C 10 C 0.35 C 0.17 C 0.09 C 0.04 C 20 C 0.40 C 0.19 C 0.10 C 0.04 C 30 C 0.45 C 0.21 C 0.11 C 0.05 C 40 C 0.50 C 0.23 C 0.12 C 0.06 C 50 C 0.55 C 0.25 C 0.13 C 0.07 C 60 C 0.60 C 0.27 C 0.14 C 0.08 C 70 C 0.65 C 0.29 C 0.16 C 0.09 C 80 C 0.70 C 0.31 C 0.17 C 0.10 C 90 C 0.75 C 0.33 C 0.18 C 0.11 C 100 C 0.80 C 0.35 C 0.19 C 0.12 C 110 C 0.85 C 0.37 C 0.20 C 0.13 C 120 C 0.90 C 0.39 C 0.21 C 0.14 C 130 C 0.95 C 0.41 C 0.22 C 0.15 C 140 C 1.00 C 0.43 C 0.24 C 0.15 C 150 C 1.05 C 0.45 C 0.25 C 0.16 C 160 C 1.10 C 0.47 C 0.26 C 0.17 C 170 C 1.15 C 0.49 C 0.27 C 0.18 C 180 C 1.20 C 0.51 C 0.29 C 0.19 C 190 C 1.25 C 0.53 C 0.30 C 0.21 C 200 C 1.30 C 0.55 C 0.31 C 0.22 C Saved as 1393