Pier Design Fundamentals Igloo Observatory Hampshire, IL USA Dec 5, 2005 Revision 3 Copyright 2005 Dennis Persyk

Similar documents
Residential Deck Safety, Construction, and Repair

The minimum reinforcement for the stem wall is the placement of:

Chapter 3 Pre-Installation, Foundations and Piers

Bolting: Attachment Of The Mudsill To The Foundation

Report on. Wind Resistance of Signs supported by. Glass Fiber Reinforced Concrete (GFRC) Pillars

New construction Repairing failed or old foundations Retrofit foundations Permanent battered piers Machinery/equipment foundations

TYPES OF PIERS USED IN NORTH AND EAST TEXAS RESIDENTIAL FOUNDATION REPAIR

1997 Uniform Administrative Code Amendment for Earthen Material and Straw Bale Structures Tucson/Pima County, Arizona

Attachment G-1: Pit Latrine Diagram. Fig E.1a: Pit Latrine. Fig E.1b: Plan View of Twin Pits

Foundation Experts, LLC Specializes in Foundation Repair and Waterproofing

The Stabilizer TM. Benefits. Supplemental support system for sagging beams and floor joists within a crawl space

Stability. Security. Integrity.

High Capacity Helical Piles Limited Access Projects

GMC 2013: Piping Misalignment and Vibration Related Fatigue Failures

SECTION 1 GENERAL REQUIREMENTS

ATLAS RESISTANCE Pier Foundation Systems

SUPPLEMENTAL TECHNICAL SPECIFICATIONS BI-DIRECTIONAL STATIC LOAD TESTING OF DRILLED SHAFTS

RESIDENTIAL FOUNDATION GUIDELINE Johnson County, KS

State of Illinois Department Of Transportation CONSTRUCTION INSPECTOR S CHECKLIST FOR STORM SEWERS

STRUCTURES Excavation and backfill for structures should conform to the topic EXCAVATION AND BACKFILL.

Table 1 Mechanical Properties of Pipe Table 2 Section Properties of Pipe and Reinforcing Dowel The Fitting with the Rib

load on the soil. For this article s examples, load bearing values given by the following table will be assumed.

METHOD A10 (a) THE DETERMINATION OF THE IN-PLACE DRY DENSITY OF SOIL OR GRAVEL BY THE SAND REPLACEMENT METHOD

Seven. Easy Steps. Your Own Walkway, Without Mortar. or Concrete. to Installing. Driveway and Patio

PVC PIPE PERFORMANCE FACTORS

System. Stability. Security. Integrity. 150 Helical Anchor

CH. 2 LOADS ON BUILDINGS

High Strain Dynamic Load Testing of Drilled Shafts

PILE FOUNDATIONS FM 5-134

SMarT_Foundation [Simple Modular Technology] Assembly and Installation Instructions (U.S. Patent Pending)

Structural Failures Cost Lives and Time

GLOSSARY OF TERMINOLOGY

ALLOWABLE LOADS ON A SINGLE PILE

TECHNICAL NOTE Culvert Sliplining and Lining of Casings with HPPipe

Weight Measurement Technology

Activity 2.3b Engineering Problem Solving Answer Key

SAMPLE GUIDE SPECIFICATIONS FOR OSTERBERG CELL LOAD TESTING OF DEEP FOUNDATIONS

Fiberstars Mini Lighted Laminar Flow Fountains

NCMA TEK CONCRETE MASONRY FOUNDATION WALL DETAILS. TEK 5-3A Details (2003)

Design of reinforced concrete columns. Type of columns. Failure of reinforced concrete columns. Short column. Long column

Introduction to Solid Modeling Using SolidWorks 2012 SolidWorks Simulation Tutorial Page 1

MCE380: Measurements and Instrumentation Lab. Chapter 9: Force, Torque and Strain Measurements

Depend-O-Lok FxE Expansion Coupling. System No. Submitted By Spec Sect Para Location Date Approved Date. DEPEND-O-LOK FxE EXPANSION COUPLING

Sonotube Instructions for PreFab Sheds

LEGACY REPORT ER ICC Evaluation Service, Inc. Reissued November 1, Legacy report on the 1997 Uniform Building Code

Removable Aluminium posts

INSITU TESTS! Shear Vanes! Shear Vanes! Shear Vane Test! Sensitive Soils! Insitu testing is used for two reasons:!

POST AND FRAME STRUCTURES (Pole Barns)

CEEN Geotechnical Engineering Laboratory Session 7 - Direct Shear and Unconfined Compression Tests

Guide for SOLID CONCRETE BLOCK SEALS

Technical Assignment 2 TABLE OF CONTENTS

Section SEWER PIPE INSTALLATION AND TESTING

Baton Rouge Foundation Repair

Embedded Parts Introduction - Anchors

LAYING BLOCK AND BRICK

Safe & Sound Bridge Terminology

Hardened Concrete. Lecture No. 14

DIVISION 2 - SEWERAGE AND DRAINAGE SECTION STORM DRAIN SYSTEMS PART 1 - GENERAL

METHOD OF STATEMENT FOR STATIC LOADING TEST

Designed and Engineered to Perform

Transmission Foundations. helical piles and guy anchors for transmission structures.

American National, Unified Screw Threads

PERFORMANCE TEST REPORT. Rendered to: FORMTECH ENTERPRISES, INC. SERIES/MODEL: Truline PRODUCT TYPE: PVC Seawall

Design of Steel Structures Prof. S.R.Satish Kumar and Prof. A.R.Santha Kumar. Fig some of the trusses that are used in steel bridges

Residential Foundations and Basements

Up-Down Construction Utilizing Steel Sheet Piles and Drilled Shaft Foundations

STANDARD OPEN PATIO COVER

Engineered, Time-Tested Foundation Repairs for Settlement in Residential and Light Commercial Structures. The Leading Edge.

Lighthouse Engineering, L.L.C.

APPENDIX A PRESSUREMETER TEST INTERPRETATION

Chapter 3 FOUNDATIONS AND FOUNDATION WALLS

Sports and High Mast Lighting Poles Phone: (866) Fax: (817)

The Verdura Wall check with your local building department

Problem Set 1 Solutions to ME problems Fall 2013

PowerLine Magnetic-Laser Sheave Alignment System Instructions

T-14 Tilt-Up Wall Braces

Technical Report Example (1) Chartered (CEng) Membership

Aluminium systems profile selection

Pro-Lift Steel Pile Foundation Repair

Envelope INSULATION BATT (2) Avoid Using Batt Insulation With Metal Framing. Pressure or Friction Fit

Lab for Deflection and Moment of Inertia

SECTION 36 - CAST-IN-PLACE CONCRETE PIPE (CIPCP) TABLE OF CONTENTS

SECTION 55 PIPE FOR STORM DRAINS AND CULVERTS (FAA D-701)

Best Practices: Machinery Alignment Shimming by Alan Luedeking

PUMP JACK SYSTEM AND ACCESSORIES

Mechanics. Determining the gravitational constant with the gravitation torsion balance after Cavendish. LD Physics Leaflets P

ITEM # OSTERBERG CELL LOAD TESTING OF DRILLED SHAFT

Proposed Minimum Subterranean Termite Treatment Standards

Section 2100-Trenching and Tunneling

ENCE 4610 Foundation Analysis and Design

Program COLANY Stone Columns Settlement Analysis. User Manual

product manual HS-4210 HS-4210_MAN_09.08 Digital Static Cone Penetrometer

Soils, Foundations & Moisture Control

CHAIN-LINK FENCES BID SPECIFICATIONS DESCRIPTION

Materials. Estimating Steel. Players. Materials. Shop Drawings. Detailing Process. Standard shapes. Fabricated members, Built-up sections

EZ-48-3AB Weather Station Mounting Tripod and Mast

4. ANCHOR BOLTS AND STRAPS a. ½" anchor bolts shall be embedded 7" into concrete a maximum of 6' on center and 12" from corners and ends of plates.

Advanced Structural Analysis. Prof. Devdas Menon. Department of Civil Engineering. Indian Institute of Technology, Madras. Module

FY11 Sanitary Sewer Main Rehab and Point Repair Bid Tabulation

Rock Bolt Condition Monitoring Using Ultrasonic Guided Waves

Transcription:

Pier Design Fundamentals Igloo Observatory Hampshire, IL USA Dec 5, 2005 Revision 3 Copyright 2005 Dennis Persyk Abstract: Telescope piers can be designed and built to meet predetermined specifications. This paper treats the specification of pier deflection. The importance of a large diameter to afford maximum rigidity is emphasized. A table of pier heights and diameters accompanies the paper to aid the astronomer in designing his pier using concrete and steel pipe. Introduction: Most serious observers and imagers eventually turn to a permanent pier to mount their scope. This allows one to quickly begin observing without any tedious and timeconsuming setup time. Most commercially available piers are designed to bolt to an existing surface and therefore do not solve the problem of choosing the appropriate concrete base. I will describe the process of specifying the concrete base and embedded pier column. I will also discuss the bolt-on pier column. You can decide if you want to tackle the job yourself or hire a contractor. Either way, you will have the benefit of specifications to help you build a solid pier. Specifying the Pier: How big do I need? Commercially available piers are generally specified in terms of their weight capacity. This is, unfortunately, a frankly useless specification. Almost any pier will support a massive weight. What we want to know is how much the pier moves with our mount and scope attached. Pier movement is predominantly sway. The pier acts like an inverted pendulum, hinged at the base, and sways from side to side. The engineering term is a cantilevered beam. It is constrained at one end with the other end free to sway in the breeze. Some astronomers concern themselves with vibrations, damping time and ringing. If you design your pier using my guidelines you can forget about these considerations completely. You will not worry about the period of oscillation (damping time) because your pier will not deflect enough to disturb imaging or observing, whatever the fundamental frequency may be. Similarly, your steel pier will ring with a crisp high C bell tone if you strike it forcefully with a hammer. Just don t do that while you are imaging or observing and the ringing will be of no consequence. There are no natural forces that can excite the ringing mode as long as you keep your hammer away. The singular most important specification is pier deflection. We can specify it in terms of movement in thousands of an inch displacement from vertical at the top when we push on the pier. But this is too coarse a specification! We can t tolerate even a thousandth of an inch. So we specify pier deflection in terms of angular deflection arc seconds. This is a term we are all familiar with. We have split double stars that are a few arc seconds apart

and have a feel for what a deflection of a few arc seconds would do to our imaging or observing. I recommend a 0.5 arc second displacement for a 5 pound-force push exerted at the top of the pier. If a star is centered in your scope s FOV and you push on the pier (not the scope) with a 5-pound force, the star will move 0.5 arc second. This will meet the needs of 90% of the amateur astronomer community. It is a realistic specification accounting for wind loading on a large scope. Wind is a factor even in roll-off and dome observatories. If you will be imaging DSOs at 4000 mm focal length from Pickering 8 skies you may want to tighten the spec. If you will never do any serious, long focal length imaging and are purely a visual observer, you can loosen the spec. But please note that it costs very little more build the pier to 0.5 arc second deflection than to 5.0 arc second deflection. The possible exception is a second-story installation with a ten-foot or higher pier. Such a pier is beyond the scope of this paper, although the specification methodology can still be applied. Pier Deflection Specification: The pier shall deflect less than 0.5 arc second when a lateral force of 5 pounds is applied to the top of the pier. Pier Design: Diameter is your Friend! The equation for angular pier deflection (given in the appendix) yields a very important relationship regarding the diameter of the pier. The angular deflection is proportional to the inverse (one-over) forth power of the diameter, that is, 1/(D^4). Let s put that into practical table of numbers. Below we consider a pier that is 6 inches in OD. This purely imaginary pier is constructed of material like PVC pipe it is not the steel which I recommend. Let s assume that it deflects 10 arc seconds for our 5 pound push not a very good pier! What happens if we increase the diameter of the steel pipe while maintaining nearly constant wall thickness? Deflection arc Diameter seconds 6 10.0 8 3.2 10 1.3 12 0.6 Table 1: Deflection vs. Diameter We see from Table 1 above that doubling the outside diameter of our pier reduces the deflection angle by a factor 10/0.6 = 16.7. Diameter is our friend!

Note that we don t worry about wall thickness. In a steel pipe pier, the thinnest schedule wall thickness is the most cost effective specification. Let s look at another example: Which is better? Case i) Six foot high pier of 10-inch schedule 5s pipe with wall thickness 0.156 inch; weight 60 pounds; cost about $90 (scrap) Case ii) Six foot high pier of solid 6-inch diameter steel cylindrical stock; weight 384 pounds; cost $576 (scrap, if you can find it) The deflection for case i) is 0.6 arc seconds. The deflection for case ii) is 1.4 arc seconds. So we see the larger diameter, thinner wall, is both cheaper and stiffer. The foregoing example illustrates why filling a wobbly pier pipe with concrete or sand doesn t fix the problem. The difference in deflection between a solid rod and a hollow rod is surprisingly small. The way to reduce the deflection is by increasing the diameter. In the case of a concrete pier, the pier is of course solid. But again diameter is our friend. A concrete pier is generally cheaper for the same deflection specification as a steel pipe pier. I do not discuss aluminum because it is prohibitively expensive and offers no advantages whatsoever for a permanent pier. I do not know how to account for rebars in a concrete pier, so unfortunately I must omit concrete pier design from my paper. Perhaps a friendly Civil Engineer will someday contribute a section on concrete piers.

Table 2: Pipe Selection for Schedule 5s Steel Pipe Height inches Deflection arc seconds Deflection mils (1/1000 inch) OD inches ID Inches I inches^4 E PSI 12 6.625 6.407 0.2 0.0 12 3.0E+07 24 6.625 6.407 0.8 0.1 12 3.0E+07 36 6.625 6.407 1.9 0.2 12 3.0E+07 48 6.625 6.407 3.3 0.5 12 3.0E+07 60 6.625 6.407 5.2 1.0 12 3.0E+07 72 6.625 6.407 7.5 1.8 12 3.0E+07 12 8.625 8.407 0.1 0.0 26 3.0E+07 24 8.625 8.407 0.4 0.0 26 3.0E+07 36 8.625 8.407 0.8 0.1 26 3.0E+07 48 8.625 8.407 1.5 0.2 26 3.0E+07 60 8.625 8.407 2.3 0.5 26 3.0E+07 72 8.625 8.407 3.4 0.8 26 3.0E+07 12 10.75 10.482 0.0 0.0 63 3.0E+07 24 10.75 10.482 0.2 0.0 63 3.0E+07 36 10.75 10.482 0.4 0.0 63 3.0E+07 48 10.75 10.482 0.6 0.1 63 3.0E+07 60 10.75 10.482 1.0 0.2 63 3.0E+07 72 10.75 10.482 1.4 0.3 63 3.0E+07 12 12.75 12.438 0.0 0.0 1297 3.0E+07 24 12.75 12.438 0.0 0.0 1297 3.0E+07 36 12.75 12.438 0.0 0.0 1297 3.0E+07 48 12.75 12.438 0.0 0.0 1297 3.0E+07 60 12.75 12.438 0.0 0.0 1297 3.0E+07 72 12.75 12.438 0.1 0.0 1297 3.0E+07 84 12.75 12.438 0.1 0.0 1297 3.0E+07 Note: I show deflection values for 12.75 inch diameter pipe with pier heights ending at 84 inches because higher piers will require plug loading considerations that are beyond the scope of this paper. Two-story piers, in particular, require a more detailed engineering analysis. The Concrete Base or Plug The pier ideally is anchored to a plug that extends below ground. The purpose of the plug is to anchor the pier/plug assembly to mother Earth. My recommendations apply to Midwest soil conditions farmland with deep, soft soil. Pier builders in areas like Arizona with underlying rock will need to consult a contractor for advice.

Like the pier, the plug must not move very much. Some slight settling is normal, and can be compensated by the mount s polar alignment mechanism. The plug specification concerns both diameter and depth. I recommend a minimum 36 inch diameter plug. It can, of course, be 36 inches square, but most contractors have access to a 3-foot auger which reduces the hole digging operation to about a 15 minute job. The plug depth must be down to, or deeper than, the frost line, or three feet deep, which ever is greater. Failure to adhere to this requirement will result in not just minor settling, but listing of the pier by 10 degrees or more from frost heaving! The frost line in your area is well known to local contractors and is a firm requirement in building codes. Look it up and make your plug deeper. I am not knowledgeable in the areas of proper soil compaction, gravel base layers, and rebar usage. Please consult a DIY concrete book or other outside sources for information regarding these specifications. Concrete Plug Specification: The plug shall extend to or below the frost line, or three feet below ground level, whichever is greater. The plug shall be at least 36 inches in diameter if dug with an auger, or 36 inches on a side if square. Good concrete practices regarding gravel base, compaction and rebar installation shall be followed. Pier-to-Plug Encapsulation The steel pier is embedded into the concrete plug at the time the plug is poured. The pier should be embedded no less than two feet into the plug. The cheapest combination is a cast concrete pier, as opposed to an embedded pipe. It is also the most difficult for the hobbyist doing the job himself. I hired a contractor to do the work for my Igloo Observatory. I gave him plans, discussed the project, and followed his advice. He installed the rebar, braces and Sonotube so he could pour plug and pier at the same time. He poured the slab (isolated from the pier by a 3/16 inch gap) the second day. My concrete pier is 12 inches in diameter and two feet high. I have a 14 inch tall pier extension of 12-inch diameter schedule 5s steel pipe added to the pier so I can change the overall pier height in the future if I change scopes or mounts. Piers Bolted to Plug The DIY builder often chooses to bolt a steel pier to the plug at ground level. This makes for an easier (though more expensive) installation. The design specifications remain the same, but I offer a caution: The base of the bolt-on pier must have a large diameter, thick plate with generous gussets welded to pipe and pier. In almost all cases of home-made and commercially available piers, the major deflection occurs at the base plate. I do not know how to analyze this geometry and cannot offer any design specifications except to say that one must be very generous in the use of thick components in beefing up this end of the pier.

Appendix Reference: Machinery's Handbook 24th Edition p 220 Strength of Materials Reference: "Formulas for Stress and Strain", Raymond J. Roark, Table III. Shear, Moment and Deflection Formulas for Beams. Case 11: Beam with one end fixed, load at the other end Maximum deflection at end d = (Wl^3)/(3EI) deflection in inches W= load in pounds l= length in inches E= modulus of elasticity of material I= moment of inertia of the cross section of the beam (cylinder) I= [π(d^4 - d^4)]/64 E= 3.00E+07 PSI for carbon steel pipe E= 3.60E+04 PSI for concrete (w/o rebars) theta= (Wl^2)/(2EI) deflection angle in radians Revision History Rev 2 Oct. 10, 2005 Added cautionary note regarding clearance with piers with OD s exceeding 8 inches. Rev 3 Dec 10, 2005 Corrected errors in Table 2 with regard to 8.625 inch OD pier deflections.