POLYMER CONDENSER BUSHING WITH COMPOSITE AIR END SILICONE INSULATOR

Similar documents
MiCAFIL. 1 RIP Technology. Bushings. Z. Zic 09/2003

1ZSC AAC en, Rev. 7. Resin impregnated paper bushing, oil to air, type GSB Technical guide

An Overview of Lapp Insulator High Voltage Bushing Design

Transformer Bushings for GIS

1ZSE en, Rev. 8. Transformer bushings, type GOE and GOE(2) Technical guide

25-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp and 1250 Amp

Transmission Silicone Insulators Line Post 69 kv to 161 kv

PPS-PPQ-BT-PIAS RESIN INSULATORS FOR OIL INSULATED ELECTRICAL MACHINES

Composite Insulators Suspensions Line Posts Brace Posts Station Posts

Vertical Break Parallel (VBP) / Vertical Break Slant (VBS)

High-Voltage Compact Switchgear 3AP1 DTC for 145 kv and 245 kv

CAUTION. 4. Cable Connections DANGER WARNING CAUTION. 3. Bushing Components

Design and testing of polymer-housed surge arresters with special emphasize on seismic stresses and selection of specific creepage in costal areas.

CABLE ACCESSORIES kv

SECTION 13. Multipliers. Outline of Multiplier Design Process:

New Distribution Class Arrester Ground Lead Disconnector Design Enhances Detonation Reliability and Improves Arrester Performance

No Heat. No Flames. No Shoving. No Special Tools. 3M Cold Shrink. 3M Cold Shrink. Medium Voltage Joints & Terminations. 3M Cold Shrink Joint

Pump Specifications 250 Series Submersible Sump / Effluent Pump 2 Solids handling

Electrical Maintenance Workshop

Pump Specifications 405 Series Commercial Drain Pump (High-Temp) 2 Solids handling

Veri*Lite Deadend & Suspension Insulators for 15-69kV Applications

3M Cold Shrink QT-III Silicone Rubber Skirted Termination Kits, 7620-S, 7680-S and 7690-S Series 5, 8, 15, 25/28 and 35 kv

TMC CableReady Connectors For Jacketed Metal Clad Cable TMC For Non-Hazardous Locations

This section applies to the design and installation of transformers.

ON-LINE DIAGNOSTIC CASE STUDY INVOLVING A GENERAL ELECTRIC TYPE U BUSHING

MEDIUM AND HIGH VOLTAGE CAPACITORS, CAPACITOR BANKS AND SYSTEMS

2. INDUCTIVE VOLTAGE TRANSFORMERS Oil-paper insulation Gas insulation

Modular Systems wind portfolio overview Power Collection and Grid Connection products

2013 RESIBLOC transformers Product presentation. ABB Group October 2, 2013 Slide 1

CRN A-F-G-E-HQQE 3x400D 50 HZ

SECTION DRY-TYPE TRANSFORMERS

Type K current limiting fuse canister Technical information and installation guide

SECTION SUBSTATION TRANSFORMERS

Aerial Fibre Optics. Complete One Stop Solution for Aerial Fibre Optics. OPGW Cable and Fittings for OPGW

Cable Accessories. for Extruded Dielectric Cable 69kV - 230kV Rated. Catalog Python13

Power transformers. Special transformers Railway

Analytical Report RF high voltage cable accessories market

produces and delivers products worldwide can provide the optimal are dedicated to supplying you with superior advice and global support.

Digital Energy ITI. Instrument Transformer Basic Technical Information and Application

Multi-tap Transformers

ACCESSORIES FOR HV CABLES WITH EXTRUDED INSULATION

Modular Systems, PPMV, 2014 UniPack-G Glass Fiber Reinforced Polyester Compact Secondary Substation

Power Voltage Transformers for Air Insulated Substations. THE PROVEN POWER.

Medium Voltage Terminations, 5 kv 46 kv

Transformer oil cooler ALFA A02

The following document contains information on Cypress products.

SF 6 Gas Insulated Switchgear Type SDF for 170 kv

Dry-type transformers. Dry-type transformers from ABB The ideal solution for the oil and gas industry

Capacitor Voltage Transformer. Answers for energy.

Lightning Arresters P KVA P KVA. Description & Installation

Packaged Terminal Air Conditioner Wall Sleeve Installation

INSTALLATION INSTRUCTIONS Fan Coil Replacement Coil Kit EBX & EBXX

How To Read A Pipe From A Sensor

Micalastic insulation for high voltage hydro generators

Solid-Cast Versus Resin-Encapsulated Transformers

V47 Series Temperature Actuated Modulating Water Valves

Outdoor Use Waterproof I/O Connectors (Optical / Modular / Electrical) FO-BH, FO-BC, NT5, JN2 / W Series

SnoTrace KSR Surface Snow and Ice Melting INSTALLATION PROCEDURES

IEC/CIGRE UHV Symposium Beijing KVDC: EXTERNAL INSULATION, INSULATION COORDINATION, TEST LEVELS

Gas insulated wall bushing, type GGFL

Explosion-Proof Electric Unit Heaters

Hi*Lite XL Transmission Insulators

2 WAY (2/2) AND 3 WAY (3/2) BRASS AND STAINLESS STEEL SOLENOID VALVES

TRANSFORMER DICTIONARY

A S Y N C H R O N O U S M O T O R S

Green Thread Product Data

Axial and Radial Leaded Multilayer Ceramic Capacitors for Automotive Applications Class 1 and Class 2, 50 V DC, 100 V DC and 200 V DC

TAN δ (DELTA) CABLE TESTING OVERVIEW AND ANSWERS TO FREQUENTLY ASKED QUESTIONS. What Is Tan δ, Or Tan Delta?

International Electrotechnical Commission Standards

Advantages of Fixed Circuit Breaker Switchgear

The very Best. ANSI Post Insulators 2016

Polymer Termination. Mechanical Cracking 2. The reason for polymer termination. What is Polymer Termination? 3

Givare NC-SRS 280 och 880

AIRMAR. The Latest Evolution in TRIDUCER Multisensor Technology. New THRU-HULL Depth Speed Temperature TECHNOLOGY CORPORATION. Specifications.

KOLMA and IHDA Indoor type Cable Current Transformers Catalogue ABB Power Distribution ABB Transmit 1 KKOLMA 1 GB

The oil condition sensor increases the function range of the thermal oil level sensor. The oil condition sensor measures the following variables:

Itemized RAI Responses

Horizontal Jet Pumps 1/3-1-1/2 HP

A99B Series Temperature Sensors

Types of Wound Film Capacitors

2004 TRANSMISSION SYSTEMS SEMINAR MEDIUM VOLTAGE, METAL-CLAD ARC RESISTANT SWITCHGEAR: ENHANCING WORKPLACE SAFETY

OLI. Oil level indicator

Masterclad Medium Voltage Passive Arc-Resistant Switchgear

ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013

Many Products...One Source

KNOW YOUR OPTIONS: 230 KV POWER CABLES

Pressure monitoring equipment for oil-sf 6. bushings, type GOEK

Installation Manual Gravity Solar Water Heater Evacuated Tube Integrated (Direct) System, unpressurized

Section 21. Telecommunication Hardware. BuyLog Catalog 21-1

AutoLink Three-Phase Sectionalizer Specifications. Scope. General. Applicable Standards. Operating principle

CRN5-5 A-FGJ-G-E-HQQE 3x230/400 50HZ

Understanding Insulation Resistance Testing

Medium Voltage Joints & Terminations

KALPANA INDUSTRIES LTD. TECHNICAL DATA SHEET

THE VALUE OF POWER FACTOR TESTING

INSTALLATION INSTRUCTIONS FOR VW MK5

Design Test Report Veri*Lite Suspension Insulators Catalog Numbers: , , ,

Replacement parts. WM97+ gas-fired water boiler Boiler Manual. OBTAIN PARTS ONLY THROUGH WEIL-McLAIN THE BOILER CONTAINS CERAMIC FIBER MATERIALS

Section kv Power Cables

3 WAY (3/2) POPPET VALVES FOR AIR AND VACUUM SERVICE SOLENOID OR AIR ACTUATED BROCHURE N-223

Transcription:

POLYMER CONDENSER BUSHING WITH COMPOSITE AIR END SILICONE INSULATOR Pritpal Singh ABB Inc. USA ABSTRACT The use of non-ceramic composite insulators with silicone rubber has been steadily increasing since they were introduced in the 60s. Silicone rubber offers unique properties that make it more suitable for contaminated environment. This material is now being used more and more on different types of insulators and apparatuses. This paper describes the construction, design, and testing of a proposed IEEE Style, oil free polymer condenser bushing with a non-ceramic composite insulator and silicone rubber weathersheds. INTRODUCTION Non-ceramic composite insulators with silicone rubber weathersheds were introduced in the 60s and their use for outdoor applications has been steadily increasing since their introduction. The use of silicone rubber for outdoor applications offers unique advantages that make it more suitable for contaminated environments such as coastal and industrial areas. Silicone rubber is now being used more and more on different types of insulators and apparatuses. This paper describes the design, construction, and testing of a proposed IEEE Style oil free, dry polymer condenser bushing with composite insulator and silicone weathersheds for outdoor applications. The bushing is of oil free type and can be used at any angle from vertical to horizontal. The design can be converted from a draw lead application to a bottom end connected split conductor application. A summary of the tests specified in the program is included. DESIGN AND CONSTRUCTION Type CORIP bushings have been designed for application on oil filled transformers and reactors and meet or exceed the applicable requirements of IEEE Standards C57.19.00 1991 and C57.19.01 2000. The design offers a capacitively graded, oil free, dry polymer condenser bushing with a composite air end insulator and silicone rubber weathersheds for outdoor applications. The condenser consists of an electrical grade paper wound over a central winding tube. The condenser deign is achieved by inserting aluminum foil layers at predetermined locations for distribution of stresses. The condenser core is then heat and vacuum dried and subsequently impregnated with an electrical grade epoxy. The cured resin paper condenser core has the electrical, mechanical, and thermal properties that make it suitable for application in oil filled transformer and reactors. The air end insulator consists of a filament-wound glass fiber reinforced composite insulating tube with silicone rubber weathersheds for outdoor application. The lower end of the composite insulating tube is attached to an aluminum-mounting flange. The upper end of the tube is attached to an aluminum cap that enables the assembly of the bushing. The insulator is assembled over the upper part of the condenser in such a way that it makes a seal with the condenser in the mounting flange area as well as at the upper end. The insulator assembly with the mounting flange provides the bushing with mechanical strength as well as means to mount the bushing on the apparatus. The double, oil resistant O-ring seals at the top and bottom ends along with the composite insulator make the bushing design virtually impervious to moisture from the outside. Both the mounting flange and the upper cap are made of corrosion resistant aluminum. The space between the condenser core and the composite insulator is filled with a specially formulated nontar polymer compound, which after curing results in a hard rubber like consistency. This filler maintains its rubberlike consistency at temperatures typically encountered in oil filled transformer and reactor applications. The lower end of the resin impregnated condenser core is exposed to transformer oil. Since there is no liquid filler, the bushing is dry in nature and therefore not susceptible to any leaks or fire hazards and can be applied at any angle from vertical to horizontal. See Figures 1 and 2 for constructional features. 1

DRAW LEAD SPLIT CONDUCTOR Constructional Features of Bushings 69 kv and Below FIGURE 1 DRAW LEAD SPLIT CONDUCTOR Constructional Features of Bushings Above 69 kv FIGURE 2 2

The composite silicone insulator is designed to meet or exceed the heavy contamination creep distance requirements of the IEEE Standards C57.19.01 2000 and C57.19.100 1995. The use of non-ceramic composite insulator with silicone rubber weathersheds offers unique features that make this design more suitable for areas with contamination and seismic activity. In the absence of porcelains, the bushing is lighter, easier to handle and install. It is less susceptible to damage from vandalism, shipping, and handling. Because of these unique features, it is virtually maintenance free and its use will result in a cost effective product on an overall basis. RATINGS Initially, the bushings will be offered in the 34.5 kv, 69, kv, 138 kv, and 230 kv voltage ratings. The current ratings will be as per the table below: TEST TAPS Test Tap Voltage Class 69 kv and Below Above 69 kv Draw Lead 400 A 800 A Split Conductor 1200 A 1200 A Bushings rated 69 kv and below are provided with a test tap. This tap is connected to the outermost foil/layer of the condenser. It is designed to withstand the 2 kv/60 HZ, 1-minute requirement as per the IEEE Standard C57.19.00 1991 and the proposed revision of this standard. Under normal operation, the tap is automatically grounded to the bushing-mounting flange with the help of a spring provided in the tap assembly. This tap can be used for checking the power factor and capacitance of the bushing. See Figure 3a for test tap details. Voltage Tap Bushings above 69 kv are provided with a Type A (Normally Grounded) voltage tap as per Figure 1 of the IEEE Standard C57.19.01 2000. This tap is connected to one of the inner foil/layers of the condenser. It is designed to withstand the 20 kv/60 HZ, 1-minute requirement as per the IEEE Standard C57.19.00 1991 and the proposed revision of this standard. Under normal operation, the tap is grounded to the flange with the help of the tap cover. This tap can be used for checking the power factor and capacitance of the bushing. Also, this tap can be used in conjunction with a potential device for drawing a small amount of power for relaying purposes. See Figure 3b for voltage tap details. Test Tap Details Figure 3a. Voltage Tap Details Figure 3b FIGURE 3 3

APPLICATION Type CORIP bushings are suitable for application in oil filled power transformers and reactors. They can be used in draw lead or bottom end connection split conductor application modes. The bushing can be converted from draw lead mode to a split conductor mode or vice versa by changing the necessary hardware. Both draw lead and the split conductor applications offer the advantage of removing or replacing the bushings without lowering the transformer oil. In the draw lead mode, the transformer current carrying cable is attached to the draw lead connector located near the top end of the bushing. In the split conductor mode, the transformer cable is attached to the lower terminal, which is an integral part of the split conductor. In the split conductor mode, the split conductor carries the current. Since the bushing is of oil free dry type, it can be applied at any angle from vertical to horizontal. The use of non-ceramic composite insulator with hydrophobic silicone rubber weathersheds allows the bushing to be applied in environment where contamination and seismic activity are an issue. TERMINAL CONNECTIONS Top End External Connection Bushings rated 400 and 1200 A, are designed with a standard top end termination of 1.5 12 thread class UNF 2A as per the IEEE Standard C57.19.01 2000. See Figures 1 & 2. Bottom End Internal Connection The internal connection to the bushing can be made using the following methods. Draw Lead Application In the draw lead mode, the transformer cable is brazed to a removable draw lead connector. The upper end of the draw lead connector also serves as the top terminal as shown in Figure 4. Split Conductor Application Draw Lead Connector With Removable Brazeable Adapter FIGURE 4 In this application, the bushing is supplied with a two-part split conductor. The two parts are connected together with bolted lap joint located in such a way that the upper part can be removed for transformer shipment without lowering the transformer oil. The top end of the upper split conductor also serves as the top terminal. The bottom end of the lower split conductor serves as the bottom terminal. Bushings, 69 kv and below and rated 1200 A are designed with a bottom end termination of 1.5 12 thread class UNF 2A as per the IEEE Standard C57.19.01 2000. Bushings above 69 kv and rated 1200 A, are designed with a bladed bottom end terminal with NEMA 4 - Hole pattern. This type of termination eliminates the need of an external bottom end terminal that is generally required to connect the bushing to the transformer leads. See Figure 5 for more details. Also, split conductor bushings above 69 kv are provided with a bottom terminal shield. 4

Above 69 kv 69 kv and Below TESTING Split Conductors FIGURE 5 The following tests have been specified for these bushings. Design Tests Design tests are done as per the requirements specified in the IEEE Standards C57.19.00 1991 and C57.19.01 2000. These tests include Dielectric, Mechanical, and Thermal. Special Tests In addition to the above, the bushings / insulators/samples were subjected to the following tests. Front of Wave Test as per the proposed revision of IEEE Standard C57.19.00-1991 and C57.12.00-2000 Tracking and Erosion Test as per IEC 61462 Water Immersion Test Mechanical tests on insulators as per IEC 61462 Tests on basic samples as per IEC 61462 which include dielectric, mechanical, and thermal tests ADVANTAGES OF POLYMER BUSHING WITH SILICONE RUBBER OUTDOOR WEATHERSHEDS The resin impregnated paper condenser core in combination with the non-ceramic non-brittle composite insulator with silicone rubber weathersheds provides the CORIP design with unique features. These features offer the following benefits to the users. Dry RIP condenser design with no liquid filler makes the bushing leak free and no risk of fire Silicone rubber has sustained hydophobicity, resulting in little or no washing, lower leakage current, reduced dry band arcing, and fewer chances of external flashovers in contaminated environment Silicone rubber is resistant to atmospheric degradation Non ceramic composite insulator with silicone rubber weathersheds is less susceptible to damage from vandalism, shipping, handling, and installation Proven performance in seismic and contaminated environment Absence of porcelains make the bushing lighter and safer to handle, transport, store, and install Absence of liquid filler enables the installation at any angle from vertical to horizontal Little or no wait time before energization due to absence of oil Split conductor/draw lead designs allow easy removal/installation without lowering of transformer oil Does not require lowering of oil prior to shipment of transformer Convertible between draw lead and split conductor application modes Fewer maintenance checks due to absence of oil and porcelain 5

Overall, more cost effective due to fewer maintenance checks, little or no washing, and resistance to vandalism, shipping, and handling damage Shorter lead times due to absence of porcelain SUMMARY Type CORIP polymer condenser bushing design, basically consists of an oil-free resin impregnated condenser core combined with a composite insulator with silicone rubber weathershed for outdoor applications. Being dry type, the bushing is leak free and has no risk of fire. The non ceramic composite insulator along with its end fittings, provide the bushing with the mechanical strength to withstand the design test and operating stresses and make it more suitable for areas with seismic activity. The silicone rubber insulator provides the bushing with features that make the bushing more suitable for areas with contamination. The bushing design can be applied either in a draw lead or a bottom end connected split conductor application mode. The design can be converted from a draw lead to a split conductor application mode or vice versa. The top end of draw lead and the split conductor also serve as the top terminal. The bottom end of the split conductor serves as the bottom terminal. The design offers unique features that make the bushing user friendly. In the absence of porcelain and oil, the bushing will require fewer maintenance checks and will be more cost effective on an overall basis. In the absence of porcelains, the design offers the advantage of a shorter lead-time. BIOGRAPHY Pritpal Singh is a Fellow Engineer with ABB Inc. in Alamo, TN and is engaged in business/product development activity. In the past 41 years, he has been involved in the design, development, and testing of transformers and bushings. He has held different technical and management positions in BHEL (India), General Electric (Pittsfield, MA), Westinghouse (Alamo, TN), and now with ABB Inc. (Alamo, TN). He has been an active member of the IEEE Transformer Committee for the past 20 years and was the Chair of the WG for the revision of IEEE Std. C57.19.01 2000. Presently, he is the Secretary of Bushing Subcommittee. He is a native of India and graduated in 1962 with a Bachelor of Science degree in Electrical Engineering from Aligarh University. REFERENCES 1. IEEE Standard C57.19.00 1991 2. IEEE Standard C57.19.01 2000 3. IEEE Standard C57.19.100-1995 4. IEEE Standard C57.12.00 2000 5. IEC Standard 61462 1998 6. Gorur R.S., Cherney E.A., Burnham J.T., Outdoor Insulators, Ravi S. Gorur, Inc., Phoenix, AZ 7. Gorur R.S., Cherney E.A., Burnham J.T., Outdoor Insulators, # 8208 Short Course Notes, March 1998, ASU, Tempe, AZ. 8. F. Schmuck, Technical Paper - Comparison Between HTV-Silicone Rubber and EPDM Used for Polymeric Outdoor Insulators, January 2000 Rev 0, SEFAG AG, Malters, Switzerland. 6