Tips to Address Temperature Measurement Reliability Challenges

Similar documents
Using Thermocouple Sensors Connecting Grounded and Floating Thermocouples

Uniformance Asset Sentinel. Advanced Solutions. A real-time sentinel for continuous process performance monitoring and equipment health surveillance

Troubleshooting accelerometer installations

White Paper: Electrical Ground Rules

CPA PC-Programmable Current/Voltage and RTD/Thermocouple Limit Alarm Trips

APPLICATION NOTES OF SIGNAL ISOLATORS

Frequently Asked Questions

THERMAL ANEMOMETRY ELECTRONICS, SOFTWARE AND ACCESSORIES

Isolated AC Sine Wave Input 3B42 / 3B43 / 3B44 FEATURES APPLICATIONS PRODUCT OVERVIEW FUNCTIONAL BLOCK DIAGRAM

Field operator with Honeywell Mobile Station

Linear Heat Series. Fiber Optic Linear Heat Detection System. Tunnels & Metros. Conveyer Belts. Parking Lots. Manufacturing Warehouse Facilities

Características. Starligh SA 9 de julio 1595 Córdoba Argentina /

HIGH RELIABILITY POWER SUPPLY TESTING

SMART SENSOR COLLECTION

Honeywell Corrosion Solutions

PRODUCT PROFILE FEATURES

Rosemount 333 HART Tri-Loop

ODOT ITB Section 4: Flashers, Timers, & Software Systems Item 4-1

Honeywell s OneWireless Network - The Building Blocks of Reliability Vibhor Tandon, Honeywell Process Solutions

Rosemount 333 HART Tri-Loop

Borregaard s Automation Migration: Strategic Tool for Business Improvement. Dag Skjeltorp, Chief Engineer, Borregaard, Ind. Ltd.

Practical Application of Industrial Fiber Optic Sensing Systems

TABLE OF CONTENT

MICROSENS. Central 48 V DC Power Supplies for PoE-Components. Description. Features

Verizon NEBS TM Compliance: Data Center Equipment NEBS Requirements Verizon Technical Purchasing Requirements VZ.TPR.9703 Issue 2, March 2012

CruzPro VAF110. AC Volts, Amps, Frequency, kw Monitor

LNG Monitoring. Fiber-Optic Leakage Detection System. Pipeline leakage detection. Regasification and liquefaction monitoring

Loop Calibration and Maintenance

THE WORLD'S FIRST WIRELESS GUIDED WAVE RADAR

W-14 FAQ MACHINERY MONITORING

Industrial Cyber Security Risk Manager. Proactively Monitor, Measure and Manage Industrial Cyber Security Risk

EC 350 Simplifies Billing Data Integration in PowerSpring Software

APPLICATION NOTE How to Deal with Electrical Noise and Interference in the Measuring Chain using a NEXUS

SC100 Series Seismic Vibration Sensors. The Best Way to Protect High-Risk Commercial Assets

MGL Avionics CAN bus interface for Trig Avionics TT21/TT22 transponders

Best Practices for Reducing Transmitter Life Cycle Costs

FIBER OPTIC APPLICATION IN A PROFIBUS NETWORK

Indoor / Outdoor Antenna

Boiler Control Solution. Boiler Control Solution. Instruments and Solution for Automatic Boiler Control LF3BUSS02-00EN.

Assurance 360 Performa. Ensuring a Secure, Reliable and High-Performing Control System

Industrial-Grade UPS System Heavy-duty power protection for harsh industrial environments

Fiber Optic Distributed Temperature Sensor (B-DTS)

3500/62 Process Variable Monitor

USB-500/600 Series Low-Cost Data Loggers and Accessories

Common Mode Choke Filtering Improves CMRR in Ethernet Transformer Applications. Application Note. June 2011

Process modules Digital input PMI for 24 V DC inputs for 120 V AC inputs

JNIOR. Overview. Get Connected. Get Results. JNIOR Model 310. JNIOR Model 312. JNIOR Model 314. JNIOR Model 410

PART 1 - INTRODUCTION...

Digital Controllers ACTUATOR COMPATABILITY

Model EC5111 Speed Controller Isochronous / Droop

Electronic Flow Switches

APC Matrix-UPS 5kVA 208V/240V In 120/208/240V Out

THYRISTORS T1-1PH from 850A to 2700A Specifications Universal 1 Phase Thyristor Unit , March 2012

Thermal Conductivity Detector

P R O D U C T S P E C I F I C A T I O N MSA Ultima X Series Sensor/Transmitter Specification

CONSTANT CURRENT REGULATOR INDUPERM TYPE CCR 951. Standarddescription of CONSTANT CURRENT REGULATOR TYPE CCR 951.

The Do s and Don ts of Pressure Transducers

Fiber Optic High Density ACC Sensor System Faser Optisches Beschleunigungs-Messsystem

Certified according to DIN EN ISO 9001 Technical Datasheet C-Flow Coriolis Mass Flow Meter

SM6 Series Circuit Breaker Monitors CONSOLIDATED. Electronics, Inc. MONITORING THE FUTURE

for Communication Systems Protection EMI CD-ROM INCLUDED

PPB Dissolved Oxygen Measurement - Calibration and Sampling Techniques

Product Data. Model 575 Series Submersible Level Transmitters ELECTRONIC PRESSURE MEASUREMENT PRODUCTS DESCRIPTION FEATURES APPLICATIONS

Report On Surge Protection & Voltage Fluctuation

Video Camera Installation Guide

SELECTION GUIDE INPUT CHARACTERISTICS. Voltage set point accuracy. Overall voltage error. Temperature coefficient of output voltage (slope)

OPERATING MANUAL. Table of contents. 2 Phase Stepping Motor Driver 2M542. Rev. A. Introduction page 2. Specifications page 2 Timing chart page 3

Contents. Document information

Type: EASY719 DC RC Article No.: Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC. Description

Advanced Solutions. Uniformance Suite. Real-time Digital Intelligence Through Unified Data, Analytics and Visualization

Table of Contents. TransformerIQ FAQs 1

TIG INVERTER INSTRUCTION MANUAL

Process Solutions. DynAMo Alarm & Operations Management. Solution Note

Benefits and Potential Dangers of Using USB for Test & Measurement Applications. Benefits of Using USB for Test and Measurement

Various Technics of Liquids and Solids Level Measurements. (Part 3)

Harmonics and Noise in Photovoltaic (PV) Inverter and the Mitigation Strategies

Fire detection equipment

MP-4000 Alarm List (Software version or later)

Differential Charge Amplifier

Measuring Temperature withthermistors a Tutorial David Potter

Temperature & Humidity SMS Alert Controller

Application of Honeywell MasterLogic-200 Controller in Highway Tunnel Monitoring Systems

Process Solutions. Uniformance Process History Database (PHD) Product Information Note

Application Requirement

Integrated Power Systems for Data Centers

Outages Happen 24/7 So Should Monitoring / SAFEGUARD YOUR HIGH VOLTAGE ASSETS WITH VAISALA ONLINE MONITORING

USB-500/600 Series Low-Cost Data Loggers and Accessories

Wireless Sensor Networks

Features. Picture. Specifications

Mobile Data Power Model: MDP-25

Delivering operations integrity through better plant safety, availability and compliance across your entire enterprise

Errors Related to Cable Resistance Imbalance in Three Wire RTDs

Microcor Wireless Transmitter (MWT)

Calibrating DC Shunts: Techniques and Uncertainties

LM1084 5A Low Dropout Positive Regulators

Alarm Systems. Peace of Mind. Agri-Alert alarms have been protecting swine operations across the world since automated production systems

ALARMLINE ANALOGUE Linear Heat Detection System

DET3 Contractor Series 3-Terminal Earth/Ground Resistance Testers

GE Consumer & Industrial Power Protection. Digital Energy LP Series UPS. Uninterruptible Power Supply 3-30 kva. GE imagination at work

Data Communications Competence Center

Transcription:

White Paper Tips to Address Temperature Measurement Reliability Challenges Executive Summary Temperature is one of the most common yet critical measurements in any process industrial plant. While the technology employed in measuring temperature has remained the same over the years, many methods have emerged to counter the challenges that impact measurement reliability.

Tips to Address Temperature Measurement Reliability Challenges 1 Table of Contents MEASUREMENT CHALLENGES 2 Variation in the measurement due to drift 2 Minimizing noise interference 2 Degradation of sensor performance 3 Ambient temperature variation 4 CONCLUSION 5

Tips to Address Temperature Measurement Reliability Challenges 2 Measurement Challenges Temperature is one of the most common yet critical measurements in any process industrial plant. While the technology employed in measuring temperature has remained the same over the years, many methods have emerged to counter the challenges that impact measurement reliability. These challenges include: Measurement variation due to drift in the device Noise interference Degradation of sensor performance Ambient temperature variation These challenges can be overcome by choosing a temperature transmitter with the right features and functions. Measurement variation due to drift in the device Drift of zero or span in temperature transmitters is a major source of measurement variation. It is impossible to trust the reliability of a device that is not stable. While calibration is a proven solution to eliminate drift, this cannot be done frequently enough considering there can be thousands of installed devices that are often located in remote and difficult to reach areas. This becomes even more critical when temperature measurements are used for fiscal metering in gas pipelines. Imagine a pipeline transferring hundreds of million dollars of energy. If there is a variation of 0.1 Deg C in a temperature measurement, this can create a variation of 0.02% in flow measurement resulting in losing several thousand dollars. In several instances like this, measurement stability is much more important than measurement accuracy. Noise interference Process and power plant environments inherently have electrically noisy environments. This noise comes from sources such as rotating high voltage equipment like motors and generators which cause electrical surges. Since temperature transmitters employ low voltage sensors like thermocouples and are often connected by compensating cables, the entire installation from sensing to the actual temperature device is susceptible to interference from electrical surges. This is compounded when grounded sensors are used. Grounded sensors create ground loops when subjected to electrical transients or lightning strikes. These transients can cause a difference in ground voltages which range from a few hundred volts up to a few thousand volts. Grounded Thermocouple Ungrounded Thermocouple

Tips to Address Temperature Measurement Reliability Challenges 3 The difference in ground potential between the sensor and the device leads to interference in the measurement loop. These issues are very prevalent in non-ferrous metal processing plants, like aluminum and zinc since the smelters in these industries operate at high voltage. In addition, coal-based power and cement plants have high voltage environments as a result of their material handling sections. Galvanic isolation in the temperature transmitter is a proven solution to eliminate noise and ground loops. Galvanic isolation separates signal currents from noise currents and will eliminate interference. Galvanic isolation is now available for up to 2000volts as opposed to few hundred volts. Another source of noise is caused by thermocouples when they are attached to a conductive material such as steel or are submerged in conductive liquids such as water. When they come into contact with any conductive material, thermocouples are susceptible to common-mode noise. Isolation can dramatically improve the rejection of common-mode noise. With conductive materials that have a large common-mode voltage, isolation is required. In the absence of isolation, amplifiers cannot measure signals with large commonmode voltages. In addition, all plants have electromagnetic interference (EMI) and radio frequency interference (RFI). They interfere with the low level signals generated by temperature sensors and carried through extension wires. It is very important that the temperature sensors are immune to these interferences. EMC compliance to IEC61326 is mandatory for use in noisy environments. Degradation of sensor performance Temperature measurement reliability is directly linked with temperature sensor health. Sensors start degrading the moment they are manufactured. They are made by combining dissimilar metals and are prone to corrosion and degradation. When sensors are installed in tough industrial process environments, sensor degradation accelerates. There are thousands of temperature sensors in difficult to reach locations in a process facility. This makes it critical to keep a continuous watch on their health. Operating the plant based on temperature readings with a poor sensor will result in faulty measurements leading to poor yield, and in extreme conditions, a plant shutdown. Current temperature transmitters have the intelligence to learn the resistance characteristics of all their thermocouple sensors. This intelligence can be customized based on the unique baseline determined for every installation. This gives the users a real-time view of sensor health instead of just sensor status information such as good or bad. The table below represents the resistance per unit length for various types of thermocouples. The resistance varies based on the type of thermocouple, thermocouple element size and the size of the cable. TC - Loop Resistance Chart - Ohms per Foot - 3/16" Probes (20 awg wire) Type J 0.367 Type K 0.589 Type T 0.304 Type E 0.709 Type N 0.783 1/4"Probes(18 Awg wire) Type J 0.234 Type K 0.376 Type T 0.194 Type E 0.453 Type N 0.5 An alert can be generated when the loop resistance crosses the trigger level. It can be made available locally in the device display as well as in the instrument asset management system to identify and implement necessary thermocouple maintenance or replacement.

Tips to Address Temperature Measurement Reliability Challenges 4 The sensor health trend can also be shown in the local display on a continuous basis, just like the process temperature display. This helps not only avoid bad PV measurements, but also optimizes sensor health to minimize the risk of a plant shutdown. Although several manufacturers provide sensor diagnostics, the level of visibility is limited to just a static status of the sensor health. In some cases, the user can only depend upon the instrument asset management system in the control room. This is due to the limitations of the transmitter display which are typically only preformatted or segment-type liquid crystal displays that can only show basic process variable information. Advanced display technology based on graphical displays, versus character based displays, do not have this limitation. Suppliers can also enhance measurement reliability by using two separate temperature sensors in a redundant mode or differential mode. In a redundant mode, in the event of a primary sensor failure, the temperature sensor can transfer the loop control mode to the second sensor and ensure uninterrupted measurement. There are situations where one sensor can degrade or drift faster than the other or one can show erroneous readings compared to the other. In these situations, it is possible to set up a drift alert limit detecting a variation between two sensors installed in the same location/application. If the reading exceeds the set limit, an alarm can be generated or the sensor can be switched to the second sensor. Ambient temperature variation Ambient temperature is one of the critical parameters impacting transmitter performance. Current transmitters employ an exclusive temperature sensor closer to the electronic module to monitor the ambient and Cold Junction temperature. This is used to adequately compensate for the variation in the process temperature measurement. In addition to this, the higher and lower limits are monitored to ensure the device is not subjected to abnormal limits. Alerts are set for the higher ambient or cold junction temperature so that a bad PV condition is eliminated. This alert helps the plant take timely action to avoid conditions that will degrade the life of the device.

Tips to Address Temperature Measurement Reliability Challenges 5 Conclusion Reliable temperature measurement requires temperature transmitters capable of delivering stable performance under noisy environments and addresses the challenges associated with sensor performance. To ensure reliable temperature measurement in harsh and noisy environment, users should evaluate the following transmitter features: Long-term stability performance Galvanic Isolation in thousands of volts to avoid ground loops and eliminate interference from electrical transients High common mode rejection capability to make measurements immune to common mode noise Sensor health diagnostics for thermocouples to avoid bad process temperature measurements Transmitter graphical display capable of showing a dynamic sensor health trend Hot back-up redundancy with dual sensors for improved availability Enhanced measurement reliability through sensor drift measurement and alert functionality with dual sensor inputs Built-in compensation for ambient temperature variation For example, Honeywell s SmartLine Temperature Transmitter offers industry-leading performance with: Stability of 0.05% of span per year Built-in galvanic isolation level of 2000VDC High noise immunity for common as well as series mode noise Superior sensor health diagnostics capabilities on a graphical display Dual sensor input capability for redundancy as well as sensor drift alert Superior ambient temperature compensation For More Information To learn more about Honeywell s SmartLine Temperature Transmitters, visit our website http://www.honeywellprocess.com/smartline or contact your Honeywell distributor. Honeywell Process Solutions Honeywell 1250 West Sam Houston Parkway South Houston, TX 77042 Honeywell Control Systems Ltd Honeywell House Skimped Hill Lane Bracknell RG12 1EB Shanghai City Centre, 100 Junyi Road Shanghai, China 20051 www.honeywellprocess.com WP-13-16-ENG October 2013 2013 Honeywell International Inc.