Exposed Paper and Foil Faced Insulation FAQ

Similar documents
EcoTouch Insulation with PureFiber Technology

Underwriters Laboratories Testing Information

Insulating Basements: Part 3 Basement Wall Systems

Fiberglas, Exterior Wall Thermal Insulation

Requirements for Fire Protection of Light Weight Floor Systems **Act 1 Revisited**

Excerpts from the Canadian National Building Code (NBC)

Housing Fact Sheets. Insulation Check-Up

ICC-ES Evaluation Report. ESR-3493 Reissued September 2014 This report is subject to renewal September 2015.

Presented by: Jennifer Doyle, P.E., RRC, LEED AP

Article. Protecting the Building Envelope from Water Damage. MemBrain Smart Vapor Retarder & Air Barrier Film

Water Vapor Permeance of Wood Structural Panels and Wood Wall Construction

*Trademark of The Dow Chemical Company A business unit of The Dow Chemical Company and its subsidiaries Copyright 2003 The Dow Chemical Company.

Know the Code: Using Spray Foam Insulation In Attics and Crawl Spaces

Cost Estimation for Materials and Installation of Hot Water Piping Insulation

Foundation. Foundation

MAJOR 2015 MN RESIDENTIAL CODE CHANGES Effective Date: January 24 th, 2015

THE DOW CHEMICAL COMPANY Issued: August 1, LARKIN CENTER 1605 JOSEPH DRIVE MIDLAND MICHIGAN (989)

Chapter 2: Foundations

Lightweight Partition Design for Residential and Commercial Buildings

Renovating Your Basement

INCORPORATION BY REFERENCE OF INTERNATIONAL. (1) The Department of Labor and Industry adopts and incorporates by

Signs of insulation problems In the winter. In the summer. conditioning system

Field Performance of Different Interior Basement Insulation Systems

THERMAL BARRIERS FOR THE SPRAY POLYURETHANE FOAM INDUSTRY

This handout is a guide only and does not contain all of the requirements of the Minnesota State Building Code or city ordinances.

B. ASTM C 533 Calcium Silicate Block and Pipe Thermal Insulation. C. ASTM C 547 Mineral Fiber Preformed Insulation

City of Houston, Texas, Ordinance No

ROOFS, SNOW AND ICE DAMS

Preparation for 2015 Residential Code Changes Discussion with Local Builders and Designers

Continuous Insulation Using Polyiso Wall Sheathing

Preventing Ice Dams on Roofs

eading Performance Solutions

Fire Testing of Recycled Materials for Building Applications

COMMERCIAL BUILDING APPLICATIONS

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: CERTAINTEED CORPORATION

Tremco Fire Protection Systems Group Technical Bulletin

FOUNDATION INSULATING SYSTEM, INCLUDING WATERPROOFING AND DAMP PROOFING

How To Install A Carbon Monoxide Detector

RESIDENTIAL PLUMBING ALTERATIONS PERMIT REQUIREMENTS

SECTION PRE-ENGINEERED BUILDING BLANKET INSULATION

03/05/14 REVISOR RSI/JC RD3945

If you are a web registered user of ArlingontPermits.com you may also request an inspection at:

Meeting the Fire Code with Continuous Foam Plastic Insulation

ENERGY STAR Qualified New Homes Thermal Enclosure Checklist. Water Management Checklist. Eli Caudill

STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM

Contract for Weatherization Management Address City & State

Insulation Products For Residential Thermal Applications ROXUL. Better Best ROXUL. Solutions For Residential Thermal Applications.

FIRE AND SMOKE PROTECTION FEATURES

Basement Insulation Systems

5 Things. You Must Know. Before Buying. Radiant Barrier

Open-cell spray foam & what every contractor

Waterproofing and interior insulation for basements takes new twist in technology.

CONDENSATION IN REFRIDGERATED BUILDINGS

KITCHEN AND BATH REMODELING BUILDING PERMIT REQUIREMENTS

fire & soundproofing Insulation Roxul Safe n Sound Fire and Soundproofing Insulation for Interior Partition Walls and Floors

Category Measure Minimum Efficiency / Certification Requirements

LIFE SAFETY UPDATE. FULL SPRINKLERING OF ALL NURSING FACILITIES ADDITIONAL CLARIFICATIONS Prepared by Eric Rosenbaum, P.E. Hughes Associates, Inc.

2014 British Columbia Building Code Changes

High R-Value Does Not Always Mean High Performance

VILLAGE OF HUDSON FALLS 220 MAIN STREET HUDSON FALLS, NY (518) /

The Sky s the Limit. With Morton Buildings Aircraft Hangars AIRPLANE HANGARS. America s leader in post-frame construction

Residential Weatherization Plus Program

NCMA TEK CONCRETE MASONRY FOUNDATION WALL DETAILS. TEK 5-3A Details (2003)

Condensation Fact Sheet METAL BUILDING MANUFACTURERS ASSOCIATION

Common Errors in Truss Design

Best Practices for Crawl Space Insulation

Polyurethane Products

keep moisture in check by getting fairly hot and facilitating downward time the sun came out, Then, after installation roof no longer got very

Basement Insulation: Best Practices for Efficient, Durable, & Healthy Homes

Performance of 8 Passive House Envelopes in Cold Climates

Additions and Alterations

Fire & Soundproofing Insulation. Roxul SAFE N SOUND. Fire and Soundproofing Insulation for Interior Partition Walls and Floors.

CITY OF FAIRFAX CODE ADMINISTRATION / FAX

FOAMULAR LT40, 400 and 600 insulations with minimum compressive strengths of

Applications for building permits will not be reviewed until all of the required information has been submitted.

FIRE-RESISTANCE-RATED CONSTRUCTION

Energy Code Compliance With SIPs. Frank Baker, PFB Corporation Don Ferrier, Ferrier Custom Homes

Retrofit structural insulated panels (SIPs) increase sound transmission loss of existing single family houses impacted by highway noise

Moisture Control. System Solutions to Prevent Mold

FIRE-RESISTANCE-RATED CONSTRUCTION

Home inspectors are not mold inspectors, however they do inspect for defects that

ELIGIBLE REPAIR PROJECT PARAMETERS

GYPSUM AREA SEPARATION FIREWALLS GA

COMMONLY USED RESIDENTIAL BUILDING CODES

s ation lic app ntial Foamular sideor RE uide F Ily G am ation F sul In

Before You Start an Energy Efficiency Retrofit The Building Envelope

Avoiding Air Barrier Pitfalls

DUCT SYSTEMS CHAPTER 6

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: ICYNENE, INC.

Insulation R-Value Comparisons

Attic condensation during winter can

Guidelines for Earthquake Bracing Residential Water Heaters

The Closed Crawl Space: Making the Transition Climate Zones 3A & 4A

Gypsum Board Systems Manual

2009 IECC Update. Scope. Content. International Energy Conservation Code

Measure Guideline: Basement Insulation Basics

Transcription:

Exposed Paper and Foil Faced Insulation FAQ Prepared By Michael Thomas Paragon Property Services Inc. The most current version of this document can be found on-line at: http://paragoninspects.com/articles/pdfs/insulation/paper-facing-fire-hazards/insulation-exposed-face-reversed-vr.pdf Fig 1. This warning is printed on all paper and foil faced insulation manufactured in for sale in the United States, but is often ignored by installers. Q. What s the Cliff Notes version of this FAQ? A. If you can see paper or foil faced insulation at a property, the facing needs to be removed or covered with ½ inch drywall or replaced with a different type of insulation with a low flame-spread facing. In some situations is facing is wrong not only because it is a fire hazard but because it is in the wrong location it should be opposite the side of the insulation you can see. All these situations are discussed in more detail below.

Q. Why have you reported that exposed paper faced insulation is a fire hazard despite the fact that fiberglass batt insulation is commonly installed this way? A. Leaving the paper and/or foil facing of insulation exposed is prohibited by International Residential Code (IRC), which is the most common building code adopted and used in the United States for one and two family dwellings and townhouses. 1 All US manufacturers of paper and foil faced insulation prohibit such installation in their printed instructions and on the insulation s packaging materials 2, and the North American Insulation Manufactures Association (NAIMA) requires its manufacturer members to print the warning shown in the picture above on all conventional paper and foil faced fiberglass insulation products sold in the US. 3 Q. My contractor / builder / architect says that there are exceptions to this rule for concealed spaces such as attics and crawl spaces, and that the paper faced insulation at my property is allowed. A. While this is a widely held belief, it s an urban construction legend. 4 Q. Is exposed combustible facing really a serious hazard? A. While "insulation fires" account for around.5% (one-half of one percent) of residential fires, flame-spread across combustible facings can contribute to more rapid fire spread. This is a serious enough problem that current US building standards prohibit exposed paper facing, and that some countries (such as Canada) prohibit the sale or installation of paper faced fiberglass insulation entirely. 5 Q. What are my options to correct the problem? A. There are several options, depending on the requirements of your application. 1) If a vapor retarder is not required in your application, the exposed paper or foil facing can be removed, leaving unfaced fiberglass as the exposed surface. (If the facing was supporting the insulation, it will have to be re-secured in some other manner). 2a) If a vapor retarder is required in your application and 1) the facing is on the correct side of the wall to serve as a vapor retarder and 2) the paper or foil barrier is a sufficient vapor retarder, then the exposed paper or foil facing can be covered with ½ gypsum board ( drywall ) providing this is acceptable to your local building department or other authority having jurisdiction. In the case of locations where the drywall may be subject to mechinical damage (such as garages, basements, heavily traveled hallways, etc.) you may wish to consider abuse-resistant ( impact resistant ) panels. 6

2b) In our Chicago heating climate exposed facing is sometimes also incorrectly installed as reversed vapor retarder. This is a separate problem, but can effect how exposed paper facing is corrected. This problem occurs when 1) an optional or required paper or foil vapor retarder is exposed 2) and the insulation is also incorrectly installed with facing serving as a vapor retarder on the cool in winter side of a floor or wall with heated space on one side and unheated space on the other. In this case if a vapor regarded is required the insulation can sometimes be removed (if it can be removed intact) and reversed against the warm side of the floor or wall. As a result 1) the facing will now be in substantial contact with the gypsum board on the heated side of the wall (eliminating the fire hazard), 2) the exposed side of the insulation will be unfaced fiberglass (which is not a fire hazard) and 3) the required vapor retarder will now be on the correct (warm in winter) side of the floor or wall. 7 8 3) In cases where a vapor retarder is required and there are many small isolated sections of insulation or it is difficult to bring gypsum board panels to the insulation location (for example when the insulation behind a kneewall is around the corner from the access) it may be cost effective to install special Flame Spread 25 (FS25) insulation with a facing that meets the flame-spread and smoke-developed index requirements for exposed surfaces. 9 Again, check with your building department or other authority having jurisdiction to determine if this is acceptable. 1 The relevant section of the IRC is R316.1: R316.1 Insulation. Insulation materials, including facings, such as vapor retarders or vapor permeable membranes installed within floor-ceiling assemblies, roof-ceiling assemblies, wall assemblies, crawl spaces and attics shall have a flame-spread index not to exceed 25 with an accompanying smoke-developed index not to exceed 450 when tested in accordance with ASTM E 84. Since the standard paper and/or foil facing of insulation does not meet these standards, the insulation is not allowed to be installed with the facing left exposed. Additionally, the insulation is required to be installed in accordance with the installation instructions from the manufacturer, these instruction state (refer to the labeling on the insulation in the photo) "Warning: This facing will burn. Do not leave exposed. Cover with approved building material in contact with the facing." or similar wording, depending on the manufacturer of the insulation. 2 For example of a manufacturer s prohibition against exposed facings see page 1 of the Owings Corning Thermal Batt FIBERGALSS - Product Data Sheet http://paragoninspects.com/articles/pdfs/insulation/paper-facing-fire-hazards/oc-batt-data-sheet.pdf 3 Insulation Facts Publication #30, Insulation and Fire Safety, North American Insulation Manufacturers Association, http://paragoninspects.com/articles/pdfs/insulation/paper-facing-fire-hazards/naima30.pdf

4 The opinion that there are such exceptions probably results from misreading the one exception to R316.1 that applies to paper faced fiberglass insulation: - - Exceptions: - - 1. When such materials are installed in concealed spaces, the flame-spread and smoke-developed limitations do not apply to the facings, provided that the facing is installed in substantial contact with the unexposed surface of the ceiling, floor or wall finish (underline mine). To a casual reader this may seem to suggest that exposed paper facings are allowed in some concealed spaces, but it actually says exactly the opposite: that in such spaces the facings do not have to meet ASTM flame-spread and smoke-developed limitations, provided the facing is installed in substantial contact with the unexposed surface of the ceiling, floor or wall finish - that is, with the facing is installed on the inside of the wall or ceiling (the unexposed surface), with the un-faced, exposed fiberglass backside of the insulation exposed to view. 5 Straight Talk About Building Insulation and Fire, Applegate Insulation, http://www.applegateinsulation.com/product-info/technical-pages/249502.aspx 6 For example DensArmor Plus Abuse-Resistant Interior Panels http://www.gp.com/build/product.aspx?pid=6353 and Sheetrock Brand Abuse-Resistant Gypsum Panels www.ncs-stl.com/submittals/usg_ar_gypsum_panels.pdf 7 An common example of a reversed vapor barrier in a heating climate like Chicago s is at floor between a heated space on first floor of a house and an unheated crawlspace below the floor. In this configuration the bottom of the floor is colder in winter, so the facing of the insulation should be up against the bottom of the floor, and if the insulation is exposed at the ceiling of the crawl space it should be the unfaced back side of the insulation. Fig 2. If you can see the insulation facing on the underside of the ceiling when you are standing in a crawlspace such as this one, you are actually seeing two installation mistakes: 1) the exposed facing and 2) a vapor retarder on the cold side of a floor. (The vapor retarder is correct on the inside of the wall, which is the warm side.)

Other common locations for exposed facings which are also reversed vapor retarders are at walls between a second floor heated space and the attic of an unheated garage and on the floor of unheated attics above heated spaces below. 8 According to most authorities in a heating climate (4,000 heating degree days, base 65F, or more) like Chicago s, the vapor retarder should be placed on the warm in winter side of the wall. In cooling climates, vapor retarders are best placed near the warm in summer side of the wall. The recommendations for mixed climates are less consistent, with the most common recomendation being that the vapor retarder should be placed such that it controls the most serious condensation condition. For a general discussion of vapor retarders in wall assemblies see this extract from The Rehab Guide: Exterior Walls, U.S. Department of Housing and Urban Development (HUD) http://www.oldhouseweb.com/how-to-advice/best-practices-vapor-retarders-and-air-infiltration-barriers.shtml For a more detailed discussion see BSD-106: Understanding Vapor Barriers by Joseph Lstiburek, Building Science Corp. http://www.buildingscience.com/documents/digests/bsd-106-understanding-vapor-barriers 9 For example Guardian Building Products Reinforced FS25-Rated Fiberglass Blanket www.guardianbp.com/litlib/fs25_fiberglass%20blanket.pdf and Owens Corning Flame Spread 25 FIBERGLAS Insulation http://www.owenscorningcommercial.com/docs/datasheet/flame_spread_25.pdf