NERC s New BES Definition: How Many CHP Units Will It Impact?



Similar documents
121 FERC 61,143 UNITED STATES OF AMERICA FEDERAL ENERGY REGULATORY COMMISSION

Federal Energy Regulatory Commission. Small Entity Compliance Guide Mandatory Reliability Standards (Order No. 693)

NERC S DEFINITION OF THE BULK ELECTRIC SYSTEM

NERC Cyber Security Standards

Alberta Reliability Standard Cyber Security Configuration Change Management and Vulnerability Assessments CIP-010-AB-1

Alberta Reliability Standard Cyber Security Physical Security of BES Cyber Systems CIP-006-AB-5

4.1.1 Generator Owner Transmission Owner that owns synchronous condenser(s)

When this standard has received ballot approval, the text boxes will be moved to the Guidelines and Technical Basis section of the Standard.

Alberta Reliability Standard Cyber Security Security Management Controls CIP-003-AB-5

Summary of CIP Version 5 Standards

152 FERC 61,198 UNITED STATES OF AMERICA FEDERAL ENERGY REGULATORY COMMISSION. 18 CFR Part 40. [Docket No. RM ; Order No.

Alberta Reliability Standard Cyber Security System Security Management CIP-007-AB-5

CIP Cyber Security Security Management Controls

SCHEDULE 1. Scheduling, System Control and Dispatch Service

April 28, Dear Mr. Chairman:

Alberta Reliability Standard Cyber Security Personnel & Training CIP-004-AB-5.1

R8-67 RENEWABLE ENERGY AND ENERGY EFFICIENCY PORTFOLIO STANDARD (REPS) (a) Definitions. (1) The following terms shall be defined as provided in G.S.

UNITED STATES OF AMERICA 151 FERC 62,146 FEDERAL ENERGY REGULATORY COMMISSION ORDER AUTHORIZING DISPOSITION OF JURISDICTIONAL FACILITIES

149 FERC 61,140 UNITED STATES OF AMERICA FEDERAL ENERGY REGULATORY COMMISSION. 18 CFR Part 40. [Docket No. RM ; Order No.

Public Utilities and Their Reliability in Florida - History

BILLING CODE P DEPARTMENT OF ENERGY Federal Energy Regulatory Commission. [Docket No. IC ]

CIP Cyber Security Configuration Change Management and Vulnerability Assessments

Top 10 Compliance Issues for Implementing Security Programs

North American Electric Reliability Corporation. Compliance Monitoring and Enforcement Program. December 19, 2008

130 FERC 61,163 UNITED STATES OF AMERICA FEDERAL ENERGY REGULATORY COMMISSION ORDER APPROVING STIPULATION AND CONSENT AGREEMENT

142 FERC 62,199 UNITED STATES OF AMERICA FEDERAL ENERGY REGULATORY COMMISSION ORDER AUTHORIZING DISPOSITION OF JURISDICTIONAL FACILITIES

At the time of notification, the QF or OSGF shall provide the Company with the following information:

Nuclear Power Plant Electrical Power Supply System Requirements

sink asset load power pool ISO pool participant bids operating constraints ancillary service declarations

E-Commerce Security Perimeter (ESP) Identification and Access Control Process

Title 20 PUBLIC SERVICE COMMISSION. Subtitle 50 SERVICE SUPPLIED BY ELECTRIC COMPANIES. Chapter 02 Engineering

JEA Net Metering Policy Tiers 1-3

CIP Cyber Security Configuration Change Management and Vulnerability Assessments

PACIFIC GAS AND ELECTRIC COMPANY Transmission Owner Tariff (TO Tariff) FERC Electric Tariff Volume No. 5

Standard CIP Cyber Security Security Management Controls

152 FERC 61,208 UNITED STATES OF AMERICA FEDERAL ENERGY REGULATORY COMMISSION. 18 CFR Part 39. [Docket No. RM ]

CIP v5/v6 Implementation Plan CIP v5 Workshop. Tony Purgar October 2-3, 2014

Cyber Security Standards Update: Version 5

LSE Registration ERCOT Region. By Derrick Davis Texas RE Corporate Counsel

Residential Solar Service Agreement (RSSA) Customer Sited Solar Photovoltaic Systems

Doubts About State-Mandated Power Contracts

GRADUATE RELIABILITY TRAINING PROGRAM. Initiation Date: September 2012

Reliability and security of electricity supply: the Italian blackout

UNITED STATES OF AMERICA FEDERAL ENERGY REGULATORY COMMISSION

152 FERC 61,200 UNITED STATES OF AMERICA FEDERAL ENERGY REGULATORY COMMISSION. 18 CFR Part 40. [Docket No. RM ]

How PURPA is driving utility scale solar in North Carolina By QF Solutions April 7, 2015

ALCOA POWER GENERATING INC. Long Sault Division. Open Access Transmission Tariff

Investment In Electric Energy Infrastructure: Regulatory Issues

Scope of Restoration Plan

146 FERC 61,166 UNITED STATES OF AMERICA FEDERAL ENERGY REGULATORY COMMISSION

Applicability and Eligibility

Reactive Power and Importance to Bulk Power System OAK RIDGE NATIONAL LABORATORY ENGINEERING SCIENCE & TECHNOLOGY DIVISION

Chapter 7 System Operations and Physical Markets

Top Ten Compliance Issues for Implementing the NERC CIP Reliability Standard

The Policy and Market Environment for Renewable Energy Development

Reclamation Manual Directives and Standards

UNITED STATES OF AMERICA BEFORE THE FEDERAL ENERGY REGULATORY COMMISSION

122 FERC 61,040 UNITED STATES OF AMERICA FEDERAL ENERGY REGULATORY COMMISSION. 18 CFR Part 40. [Docket No. RM ; Order No.

Mr. Agustín F. Carbó Lugo, Esq., President, Puerto Rico Energy Commission World Plaza Building, 268 Muñoz Rivera Ave., Suite #702, Hato Rey, PR 00918

SERVICE CLASSIFICATION NO. 14-RA STANDBY SERVICE

PJM Overview of Markets. Georgian Delegation PUCO Office April 11, 2013

September 29, Docket No. ER Amendment to CAISO FERC Electric Tariff to Eliminate Annual External Operations Review

How To Build A Power Line From A Single Campus To A Power Plant

SOUTH CAROLINA. Standard for Interconnecting Small Generation 100 kw or Less with Electric Power Systems (EPS) (Interconnection Standard)

ORDINANCE NUMBER An ordinance to establish electric utility rates in the City of Beatrice, Nebraska, in

Power System review W I L L I A M V. T O R R E A P R I L 1 0,

Cincinnati Gas & Electric Corporation

Closing the Gap Between Wholesale and Retail

Alternative Options for the Availability Standard and Replacement Rule components of the Standard Capacity Product II Initiative March 18, 2010

The North American Electric Reliability Corporation ( NERC ) hereby submits

SERVICE CLASSIFICATION NO. 14-RA STANDBY SERVICE

Duke Energy Progress Standards of Conduct Transmission Function Employee Job Titles and Job Descriptions 9/1/13

-1- PSEG-LI Update of LIPA SGIP Full Docw-NYISO reqmts above 10 MW

Deep Dive on Microgrid Technologies

CIP Cyber Security Electronic Security Perimeter(s)

STATEMENT OF CHARGING METHODOLOGY FOR USE OF ELECTRICITY NORTH WEST LIMITED S ELECTRICITY DISTRIBUTION NETWORK

Administrative Services for the PJM Interconnection Operating Agreement

UNITED STATES OF AMERICA 151 FERC 62,147 FEDERAL ENERGY REGULATORY COMMISSION ORDER AUTHORIZING DISPOSITION OF JURISDICTIONAL FACILITIES

CIP Physical Security. Nate Roberts CIP Security Auditor I

MAINTAINING SYSTEM BLACKSTART IN COMPETITIVE BULK-POWER MARKETS

PG&E Web Tool for Reporting Information Related to. NERC Reliability Requirement Compliance

THE CONNECTICUT LIGHT AND POWER COMPANY, DBA EVERSOURCE ENERGY TERMS AND CONDITIONS FOR ELECTRIC SUPPLIERS PAGE 1 OF 20

Cyber Security Standards Update: Version 5 with Revisions

Presentation for The National Commission for Energy State Regulation of Ukraine

Schedule 19 POWER PURCHASES FROM COGENERATION AND SMALL POWER PRODUCTION QUALIFYING FACILITIES

University of Maryland College Park District Energy System. IDEA Campus Energy Conference February 9, 2012

WHITE PAPER THE NIAGARA FRAMEWORK A PLATFORM FOR DEMAND RESPONSE

UNITED STATES OF AMERICA FEDERAL ENERGY REGULATORY COMMISSION

References Appendices I. INTRODUCTION... 6 A. Background... 6 B. Standards... 6

Designing Compliant and Sustainable Security Programs 1 Introduction

TERMS AND CONDITIONS

High Natural Gas Prices and the Updated Market For CHP

Rules on Southern Companies Energy Auction Participation

Agenda do Mini-Curso. Sérgio Yoshio Fujii. Ethan Boardman.

Frequently Asked Questions PG&E s Power Purchase Agreement for Small Renewable Generation Feed-in Tariffs

Standard CIP 007 3a Cyber Security Systems Security Management

ONCOR ELECTRIC DELIVERY COMPANY LLC

GENe Software Suite. GENe-at-a-glance. GE Energy Digital Energy

Green Power Connection Net Energy Metering Engineering Review Process in Delaware and Speeding Up the Application Fee Process

Pivot Data Centres Inc.

Transcription:

NERC s New BES Definition: How Many CHP Units Will It Impact? A presentation by: Dr. John A. Anderson, President & CEO Electricity Consumers Resource Council (ELCON) Washington, D.C. At: US Combined Heat & Power Conference, Washington, DC December 10, 2013 1

What Is ELCON? The national association for large industrial users of electricity in the U.S. Founded in 1976 Members from a wide range of industries from traditional manufacturing to hightech Most members have CHP The views today are mine alone 2

At The Outset, Keep In Mind An Overarching FERC Mindset In 2007, FERC issued an order with the following statement: SUMMARY: The Federal Energy Regulatory Commission (Commission) is revising its regulations governing qualifying small power production and cogeneration facilities (QFs), to eliminate the exemption of QFs from the requirements of section 215 of the Federal Power Act. From a reliability perspective, there is not a meaningful distinction between QF and non-qf generators that warrants a generic exemption of QFs from reliability standards. FERC Order in Docket No. RM07-11-000 Applicability of FPA Section 215 to Qualifying Small Power Production and Cogeneration Facilities 3

As Well As An Overarching NERC Mindset The broader NERC community (NERC staff and utility volunteers) Assumes that ALL generators basically are stand-alone utilityowned or merchant units built and operated for the sole purpose to deliver to the bulk electric system (BES) power for resale to thirdparty, wholesale or retail customers. However, as we all know, CHP machines most often are built to serve an end-user thermal load with any residual electricity sold as a by-product to the grid under the terms of PURPA. The tight integration of CHP to the end user s steam/thermal requirements makes it inseparable from the load. 4

So What Is NERC? The North American Electric Reliability Corporation (NERC): Is the FERC-designated ERO Develops mandatory reliability standards with up to $1 million / day penalties Any entity that is on NERC s Compliance Registry must: Comply with all applicable standards Make required compliance filings Be subject to periodic audits Increasingly, previously unregistered entities are becoming Registered Entities And thus responsible for compliance with various reliability standards 5

So What Is NERC? NERC is comprised of the owners, operators and users of the bulk power system Created in 2007 under authority of the Energy Policy Act of 2005 NERC evolved from a voluntary organization created after the NY blackout in the 1960s NERC is charged with (among other things) drafting mandatory reliability standards that apply to the interconnected North American electricity grid including most of Canada and parts of Mexico NERC drafts and approves standards The standards must receive regulatory approval before they become mandatory By law, FERC cannot write standards as that would make FERC a standards writer for Canadian and Mexican entities However, FERC can deny approval of proposed standards and remand them to NERC with very specific guidance And keep in mind users can be anybody 6

In 2010, FERC Ordered a Redefinition of the BES FERC directed (Order 743 and 743-A) NERC to redefine the Bulk Electric System (BES) within one year: The bottom line: many more entities may be subject to the Compliance Registry based on the revised BES definition Once an entity is placed on Registry, it will REALLY care about NERC FERC s directive includes certain bright lines : Eliminate generally defined as to include: All facilities > 100 kv All generators > 20 MW and all generating plants > 75 MW Eliminate regional discretion 7

NERC s Process to Redefine the BES NERC established a Standards Drafting Team (BES DT) that: Was charged with crafting a new definition of the BES ELCON s VP of Technical Affairs John Hughes is on the SDT the only voting industrial SDT member The BES DT s initial product includes: A core definition all facilities operated or connected at >100 kv are included (as per the FERC directive) All Regional Entities must use the same definition (again, as per the FERC directive) But the BES DT approved 5 Inclusions and 4 Exclusions And an Exception Process with the burden of proof on the entity seeking change Radials are excluded Unless looped at any voltage And tie lines for BES generation are included Local networks are excluded (as per the FPA) but are undefined 8

Inclusions and Exclusions in the BES Definition Core Definition Inclusions Exclusions Unless modified by the lists shown [to the right], all Transmission Elements operated at 100 kv or higher and Real Power and Reactive Power resources connected at 100 kv or higher. This does not include facilities used in the local distribution of electric energy. I1: Transformers E1: Radial Systems I2: Generators E2: PURPA Qualifying Cogeneration I3: Blackstart Resources E3: Local Networks I4: Dispersed Power Producing Resources I5: Static or Dynamic Devices E4: Reactive Power Devices Serving End Use Customers 9

NERC s Process to Redefine the BES (Cont.) Originally the BES drafting team thought that generator inclusion should be much higher however, NERC s Planning Committee strongly opposed: There was no technical justification Would remove 34 GW (3.3%) of generation from the BES Remove about 6,000 generating units (over 50% of what is excluded today) Smaller units may be needed to satisfy local reserve margins The new definition was originally supposed to be in effect as of July 1, 2013 with a 2-year implementation plan ELCON led an opposition group including several industrial trade groups and the US CHP that resulted in a delay 10

The Second Effort to Redefine the BES (Cont.) After considerable concern was expressed, FERC postponed implementation until July 1, 2014 (still with a 2-year implementation) to allow additional revisions Key changes were made by the BES DT in both E1 and E2 E1 relates to radial systems E2 relates to PURPA Qualifying Cogeneration However, due to the FERC directive, the definition still is based on a bright line And, as we all know, nearly all bright line requirements bring unintended consequences We expect many in this case 11

Changes to E1: Exclusion for Radial Systems E1 Radial systems: A group of contiguous transmission Elements that emanates from a single point of connection of 100 kv or higher and: Only serves Load or, Only includes generation resources, not identified in Inclusions I2, I3, or I4, with an aggregate capacity less than or equal to 75 MVA (gross nameplate rating) or, Where the radial system serves Load and includes generation resources, not identified in Inclusions I2, I3 or I4, with an aggregate capacity of nonretail generation less than or equal to 75 MVA (gross nameplate rating). Note 1: A normally open switching device between radial systems, as depicted on prints or one line diagrams for example, does not affect this exclusion. Note 2: The presence of a contiguous loop, operated at a voltage level of 50 kv or less, between configurations being considered as radial systems, does not affect this exclusion. 12

Changes to E1: Exclusion for Radial Systems 13

Changes to E1: Exclusion for Radial Systems The drafting team proposed the threshold of 50 kv or less for loops between radial systems when considering the application of Exclusion E1. The SDT used a two step approach to determine the voltage level. As a first step, regional voltage levels that are monitored on major interfaces, paths, and monitored elements to ensure the reliable operation of the inter-connected transmission system were examined to determine the lowest monitored voltage level. Next, power system analyses determined the maximum amount of power that can be transferred through the low voltage systems, when looped, under a worst case scenario at various voltage levels. The technical justification was a formal white paper. Entities with facilities that loop at 69-kV or higher will have to seek an exception request. Whether the 50- kv threshold is a big or small victory is yet to be determined. 14

Changes to E2: QFs with Limited Power Exports E2 - A generating unit or multiple generating units on the customer s side of the retail meter that serve all or part of the retail Load with electric energy if: The net capacity provided to the BES does not exceed 75 MVA, and Standby, back-up, and maintenance power services are provided to the generating unit or multiple generating units or to the retail Load by a Balancing Authority, or provided pursuant to a binding obligation with a Generator Owner or Generator Operator, or under terms approved by the applicable regulatory authority. 15

Changes to E2: QFs with Limited Power Exports This exclusion was adopted from the Statement of Compliance Registry Criteria It eliminates the nameplate rating of a cogeneration unit from being used as the determinative factor for BES classification. The BES Drafting Team also adopted a single generation threshold (75 MVA) for manufacturing facilities with either a single or multiple cogeneration units on site. This exclusion continues to confuse the typical utility engineer that participates in standards drafting teams. This confusion is often accompanied by hostility or resentment because the exclusion is deemed unfair to the owners/operators of utility generators. 16

Examples of Other NERC Issues Impacting CHP: Generator requirements at the transmission interface (GOTO): Generator tie lines were deemed transmission assets by NERC The generator s owner was registered as a Transmission Owner (TO) and Transmission Operator (TOP) After several years of difficult interchange, FERC found that only 4 Standards (e.g., vegetation management) were appropriate While we won this battle, the war is far from over Generator verification reliability standards NERC proposed a Standard for verification and data reporting of generator real and reactive power capability and synchronous condenser reactive power capability (MOD-025-2) The Standard requires operating a generating unit in real time in order to determine the theoretical (i.e., nameplate) performance limits that are used to model the BES Loads with CHP cannot be modeled unless the underlying industrial/commercial process application is modeled and may force protracted shutdown and/or equipment damage 17

Examples of Other NERC Issues Impacting CHP: Long term reliability assessment (LTRA): The LTRA annually assess the adequacy of the BES over a 10 year period The assessment tends to lump all non-intermittent generation together into a single, homogenized conventional category even though CHP and conventional generation are quite different Generation availability data system (GADS): GADS will collect data from all generators > 20 MW (below is voluntary) If one behind the meter facility becomes a NERC registered entity ALL generation > 20 MW owned by that company is swept into GADS The GADS Data Reporting Instructions is 607 pages long Demand response availability data system (DADS): The goal of DADS is to measure the actual performance of demand response DR often is provided based on some form of backup generation The reporting burden presently is on Balancing Authorities (Bas) and TOPs There is growing pressure to shift the burden to the end-use provider 18

JA1 JA2 Conclusions We all want and need a reliable BES But industrials and CHP should only be required to conform to NERC standards if they have a material impact on BES reliability Unfortunately, the NERC requirements appear to go far beyond what is necessary and bring with them very large additional costs I urge each of you to get involved in or at least be quite aware of NERC There are many opportunities but be prepared to spend a lot of time At this time, ELCON is the only industrial group significantly involved in NERC and is a strong proponent of CHP Participation in ELCON is one way to be represented in NERC Thanks for the opportunity to be with you today 19

Slide 19 JA1 John Anderson, 12/3/2013 JA2 John Anderson, 12/3/2013

To Contact ELCON Phone: 202-682-1390 E-mail: janderson@elcon.org Web site: www.elcon.org Address: 1101 K Street N.W., Suite 700 Washington, DC 20005 20