Product Information Dissolved gas analysis and supervision of oil condition in transformers and reactors

Similar documents
Dissolved Gas Analysis Guide for Transformers Filled with Beta Fluid

DGA - Method in the Past and for the Future

Electrical Maintenance Workshop

DISSOLVED GAS ANALYSIS OF MINERAL OIL INSULATING FLUIDS

ASSESSMENT OF OIL ANALYSIS DATA FOR MEDIUM VOLTAGE DISTRIBUTION TRANSFORMERS

UNDERSTANDING CORROSIVE SULFUR PROBLEMS IN ELECTRIC APPARATUS. Paul J. Griffin and Lance R. Lewand Doble Engineering Company

A GUIDE TO TRANSFORMER OIL ANALYSIS BY I.A.R. GRAY Transformer Chemistry Services

OXIDATION INHIBITORS FOR INSULATING OILS

FULLER S EARTH AS THE CAUSE OF OIL CORROSIVENESS AFTER THE OIL RECLAIMING PROCESS

CHEMICAL REACTIONS AND REACTING MASSES AND VOLUMES

GE Energy Transformer Monitoring: How Moving forward from Monitoring to Diagnostics can Positively Impact Indian Business and Industry

THE VALUE OF POWER FACTOR TESTING

ON-LINE DIAGNOSTIC CASE STUDY INVOLVING A GENERAL ELECTRIC TYPE U BUSHING

PRODUCTION OF CORROSIVE SULPHUR FREE TRANSFORMER FLUIDS vs. COMMON NAPHTHENIC MINERAL OILS

Investigation on Sampling, Measurement and Interpretation of Gas-in-Oil Analysis for Power Transformers

SIX REASONS TO DRY BIOGAS To A LOW DEWPOINT BEFORE COMBUSTION IN A CHP ENGINE STEVEN SCOTT MARKET DEVELOPMENT MANAGER ALTERNATIVE ENERGIES

The Empirical Formula of a Compound

Module 5: Combustion Technology. Lecture 33: Combustion air calculation

Honors Chemistry: Unit 6 Test Stoichiometry PRACTICE TEST ANSWER KEY Page 1. A chemical equation. (C-4.4)

General Chemistry I (FC, 09-10) Lab #3: The Empirical Formula of a Compound. Introduction

Lecture 35: Atmosphere in Furnaces

On-line Dissolved Gas Analysis

Formulae, stoichiometry and the mole concept

CONTENTS. ZVU Engineering a.s., Member of ZVU Group, WASTE HEAT BOILERS Page 2

Chemical Reactions in Water Ron Robertson

Chapter Three: STOICHIOMETRY

OPTIMIZE YOUR FLEET MANAGEMENT RESOURCES

Certain specific properties of compressed gases make them highly useful in various research activities.

COMBUSTION. In order to operate a heat engine we need a hot source together with a cold sink

OIL CONDITION MONITORING: AUTOMOTIVE ANALYSIS

This chapter is devided into two sections:

Energy Efficient Operations and Maintenance Strategies for Boilers

electrical services

Chapter 8 - Chemical Equations and Reactions

Hydro Plant Risk Assessment Guide

Enhance Power Equipment Reliability with Predictive Maintenance Technologies

Question Bank Electrolysis

Chemical Equations & Stoichiometry

Chapter 2. The Chemistry of Life Worksheets

Name Date Class STOICHIOMETRY. SECTION 12.1 THE ARITHMETIC OF EQUATIONS (pages )

Siemens TMDS transformer monitoring and diagnostic system. Solutions for transformer life-cycle management. Answers for energy.

THE OLTC AS AN "OIL ISOLATED SYSTEM" IN THE TRANSFORMER & OIL ANALYSIS IN OLTC. I Hr. Dr. Hurm, Hr. Dr. Schübel I I

Chapter 1 The Atomic Nature of Matter

IB Chemistry. DP Chemistry Review

Balancing chemical reaction equations (stoichiometry)

Session Five: Modern XLPE Materials for Extruded Energy Cable Systems

Getting the most from this book...4 About this book...5

Cambridge International Examinations Cambridge International General Certificate of Secondary Education

Halogen Free: What, Why and How. Presented by : Jim Cronin Environmental Monitoring and Technologies, Inc.

Chapter 2 Chemical and Physical Properties of Sulphur Dioxide and Sulphur Trioxide

IB Chemistry 1 Mole. One atom of C-12 has a mass of 12 amu. One mole of C-12 has a mass of 12 g. Grams we can use more easily.

KS3 Science: Chemistry Contents

CHAPTER 3: MATTER. Active Learning Questions: 1-6, 9, 13-14; End-of-Chapter Questions: 1-18, 20, 24-32, 38-42, 44, 49-52, 55-56, 61-64

Biogas as transportation fuel

Chapter 16: Tests for ions and gases

6 Reactions in Aqueous Solutions

Chapter 1: Moles and equations. Learning outcomes. you should be able to:

SUPPLEMENTARY TOPIC 3 ENERGY AND CHEMICAL REACTIONS

The photoionization detector (PID) utilizes ultraviolet

Chemistry 51 Chapter 8 TYPES OF SOLUTIONS. A solution is a homogeneous mixture of two substances: a solute and a solvent.

Mole Notes.notebook. October 29, 2014

About the course GENERAL CHEMISTRY. Recommended literature: Chemistry: science of the matter. Responsible for the course: Dr.

Comparison between Online and Laboratory Measurements of Fault Gases for Mineral Oil and Natural Ester

TMDS Smart Monitor. Solutions for transformer life-cycle management. Answers for energy.

Santa Monica College Chemistry 11

Unit 3 Notepack Chapter 7 Chemical Quantities Qualifier for Test

Inferred ph in Steam Plant Water Chemistry Monitoring

20.2 Chemical Equations

How Sensors Work. How Oxygen, Electrochemical Toxic, and Metal Oxide Semiconductor Sensors Work *

Properties and Classifications of Matter

MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING

VCE CHEMISTRY UNIT 2 Environmental Chemistry SAMPLE COURSE OUTLINE

Molar Mass of Butane

stoichiometry = the numerical relationships between chemical amounts in a reaction.

Chemical Building Blocks: Chapter 3: Elements and Periodic Table

Carbon Dioxide Membrane Separation for Carbon Capture using Direct FuelCell Systems

Metals and Non-metals. Comparison of physical properties of metals and non metals

Chapter 6 Notes Science 10 Name:

Chapter 7: Chemical Energy

Power transformers. Generator step-up and system intertie power transformers Securing high-quality AC transmission

Chemistry Post-Enrolment Worksheet

3/5/2015. Oil Analysis Tests. Lubricating Oils. Six Functions of Lubricating Oil

Review - After School Matter Name: Review - After School Matter Tuesday, April 29, 2008

Summer Holidays Questions

Norit Activated Carbon for Purification of Edible Oils

GCSE Chemistry Quiz Chemical Reactions

Pesticide Analysis by Mass Spectrometry

2. ATOMIC, MOLECULAR AND EQUIVALENT MASSES

Return to Lab Menu. Stoichiometry Exploring the Reaction between Baking Soda and Vinegar

83 to 87% carbon 11-15% hydrogen 0.1-7% sulphur % oxygen % nitrogen

ALS TRIBOLOGY Engine Coolant Reference Guide

DIN 2403 Identification of pipelines according to the fluid conveyed. Marking of pipes according to fluid transported

CHAPTER 7 THE DEHYDRATION AND SWEETENING OF NATURAL GAS

Chapter 2: The Chemical Context of Life

Application Requirement

1. Standard conditions are in. Hg (760 mm Hg, psia) and 68 F (20 C).

Formulas, Equations and Moles

Chapter 8: Chemical Equations and Reactions

Unit 9 Stoichiometry Notes (The Mole Continues)

F321 MOLES. Example If 1 atom has a mass of x g 1 mole of atoms will have a mass of x g x 6.02 x = 7.

Transcription:

Product Information Dissolved gas analysis and supervision of oil condition in transformers and reactors Transformers Diagnostic Services at ABB performs dissolved gas analysis and supervision of oil condition in power transformers, reactors, instrument transformers, circuit breakers and oilinsulated cables. This product information is divided into the following sections: 1. Dissolved gas analysis (DGA) 2. Supervision of oil condition 3. Sampling and frequency of analyses 4. Ordering of tests 1. DISSOLVED GAS ANALYSIS (IEC 60599) For many years the method of analysing gases dissolved in the oil has been used as a tool in transformer diagnostics in order to detect incipient faults, to supervise suspect transformers, to test a hypothesis or explanation for the probable reasons of failures or disturbances which have already occurred and to ensure that new transformers are healthy. Finally, DGA could be used to give scores in a strategic ranking of a transformer population used in condition assessments of transformers. In this respect the dissolved gas analysis is regarded as a fairly mature technique and it is employed by several ABB transformer companies around the world either in own plant or in cooperation with an affiliated or independent laboratory. The idea with dissolved gas analysis is based on the fact that during its lifetime the transformer generates decomposition gases, essentially from the organic insulation, under the influence of various stresses, both normal and abnormal. The gases that are of interest for the DGA analysis are the following: hydrogen C methane ethylene ethane acetylene C 3 propene C 3 H 8 propane CO carbon monoxide CO 2 carbon dioxide O 2 oxygen nitrogen N 2 Figure 1. Test vessels. TCG total combustible gas content (, C,,,, CO, C 3, C 3 H 8 ) All these gases except oxygen and nitrogen may be formed during the degradation of the insulation. The amount and the relative distribution of these gases depend on the type and severity of the degradation and stress. 1.1 Procedure The DGA procedure consists of essentially four steps: sampling of oil from the transformer extraction of the gases from the oil analysis of the extracted gas mixture in a gas chromatography, GC. interpretation of the analysis according to an evaluation scheme. The oil samples should preferably be taken in the moving oil so that the gas generated somewhere easily and rapidly is transported from the point of generation to the sampling point. Suitable locations are valves in the cooler/radiator circuit. To take samples from these locations is not always possible because of design limitations. Other places from which to draw samples are the cover, bottom valve, the conservator and from the Buchholz relay. In addition, it is very important that the sampling is made in such a way that the contamination of the sampling vessel is held at a minimum and that gas are not lost during sampling or transportation to the laboratory.

The removal of the gases from the oil can be accomplished by various methods: partial degassing (single-cycle vacuum extraction) total degassing (multi-cycle vacuum extraction) stripping by flushing the oil with another gas. by the headspace technique in which gases are equalized between a free gas volume and the oil volume. ABB Transformers Diagnostic Services in Ludvika uses the headspace method (figure 2). After extraction the extracted gas mixture is fed into adsorption columns in a GC where the different gases are adsorbed and separated to various degrees and consequently reaches the detector after different periods of time. In this way the gas mixture is separated into individual chemical compounds, identified and their concentrations in volume gas STP/volume oil is calculated and expressed in ppm. (STP=standard temperature and pressure). It should be emphasized that this extraction and analysis may involve analytical errors which mean that it may be difficult to directly compare the results from two different laboratories. One should not jump from one lab to another but try to stick to one well-reputed lab. 1.2 Interpretation There are several different approaches how to explain and interpret the analysed gas composition and to diagnose the condition of the transformer. Essentially the following methods are at hand: Identification of the key gas. The key gas identifies a particular problem, e.g. indicate partial discharges (PD). Determination of ratios between gases, normally between gas levels. Determination of the gas level, either determined in ppm or ml gas. Determination of rates of increase ( production rates ), in ppm/day or ml gas/day Around the world and during the years several different schemes have been proposed as evaluation schemes for the DGA. The most commonly known schemes are the one proposed by Rogers forming the basis for the ANSI method and the scheme laid down in IEC Publication 60599. Both these methods are using ratios between gas concentrations. In order to get a feeling for DGA interpretation the key-gas method is appropriate (figure 3). One looks for the most prominent gas - the one which differs most from a tacitly expected normal level (or change). For instance, at overheating of cellulose the main decomposition gases are CO and CO 2. At a partial discharge of corona is formed (PD in cellulose involves the formation of carbon oxides). At a more severe electric discharge such as arcing is formed (normally also is formed with smaller amounts of methane and ethane. If CO is present cellulose is involved). Finally, at overheated oil it is the hydrocarbons that are formed normally the saturated hydrocarbons such as at lower temperatures and unsaturated such as at higher temperatures. Acetylene indicates very high temperatures. This scheme can also be used to understand the evaluationschemes based on ratios. For instance, the IEC method uses three ratios: C C / is used to discriminate between a thermal fault and an electric fault. / indicates the presence of a strong discharge or very severe electric problem and / is an indication of the oil temperatures. 1. Overheating of cellulose CO, CO 2 2. Overheating of oil increasing temperature C C C 3. Partial discharges (PD) increasing intensity 4. Discharges, Figure 2. Headspace gas chromatography instrument for the analysis of gases in insulation oil. Figure 3. Characteristic key-gases, principal layout. 2 Dissolved gas analysis and supervision of oil condition in transformers and reactors

1.3 Application How often one should take oil samples depends on the importance of the transformer. When we suspect a fault (e.g. abnormal sounds). In case of signals from gas or pressure relay. Directly after, and within some weeks, after a short circuit. When a transformer essential to the network is taken into operation, followed by further tests after some months in operation. After an obvious overloading of the transformers The analysis results are documented in reports that are sent to the customer. All recent and historical results and recommendation are also available by a Web service (itrafo). 2. SUPERVISION OF OIL CONDITION Even though it is generally acknowledged that dissolved gas analysis is normally the most powerful tool for diagnostic purposes, and for the detection of incipient faults in a transformer, it is also very important to monitor the general status of the insulating oil. The oil may become contaminated with water, particles and other foreign substances. There is also a continuous ageing of the oil and the solid insulating with the formation of water, acids and sludge. Apart from impairing the insulating properties, these oxidation products also cause accelerated degradation of the cellulose insulation. There are a number of different tests devised for detecting changes in electrical properties and chemical composition of the oil. Some are made in order to obtain information about the status of the oil itself, while others are made mainly for the assessment of the status of the cellulose insulation. Only the most commonly used and important measurements are discussed here. 2.1 Electrical properties 2.1.1 Breakdown voltage (IEC 60156) The ability of the oil to withstand electrical stress is obviously an important parameter in itself. A lowering of the breakdown voltage is usually due to the presence of particles in the oil, in particular in combination with a large water content (figure 4). 2.1.2 Dielectric dissipation factor, tan δ (IEC 60247) This is a measure of the dielectric losses of the oil (figure 5). These losses are due mostly to conductivity of the oil. It is not as such a very important parameter for the operation of the transformer (unless the value is extremely high), but it is a good indication of the presence of dissolved metal ions and acids. Figure 4. Breakdown voltage measurement cell. Figure 5. Apparatus for measurement of dielectric dissipation factor (tan δ). Dissolved gas analysis and supervision of oil condition in transformers and reactors 3

2.2 Chemical properties 2.2.1 Water content (IEC 60814) Some buildup of water content is inevitable, due to the aging processes mentioned above. There may also occur leakage of water into the transformer by various mechanisms. Measurement of the water content of the oil also allows the estimation of the water content of the solid insulation, which is where most of the water is bound. A high water content of the oil may lower the breakdown voltage, while the main problem with a high water content of the solid insulation is the increased aging rate of the paper (figure 6). Note, however, that the water content of oil and of solid insulation are strongly linked, and as the temperature changes water is redistributed between the two. 2.2.2 Acidity (IEC 62021) Acids are a product of the oxidation of the oil. This is a process involving reactions very similar to those causing wine to turn into winegar, or butter or vegetable oil becoming rancid. The acidity, which is the amount of potassium hydroxide needed to neutralize the acids in the oil, is an indicator of the degree of aging. 2.2.3 Inhibitor content (IEC 60666) Inhibitors are added to the oil in order to slow down the oxidation of the oil. They act by reacting with certain intermediates in the oxidation process, thus preventing a chain reaction in which oxidation products promote further oxidation. Inhibited oils of good quality normally age very slowly as long as any inhibitor is still present. However, when the inhibitor is spent the oxidation will proceed relatively rapidly. For this reason it is important to monitor the inhibitor content, so that preventive maintenance actions can be taken before the onset of rapid oxidation (figure 7). 2.3.2 Interfacial tension ( IFT ) (ASTM D971-99) The interfacial tension between oil and water is a measure of the amount of polar contaminants and degradation products. It is a useful indicator of aging, and a good complement to the acidity, because, as opposed to the latter, it is also influenced by non-acidic oxidation products (figure 8). 2.3.3 Corrosive sulphur (IEC 62535) In recent years there have been a significant number of failures, in different types of equipment, due to the formation of copper sulphide in the cellulosic insulation. Also other problems due to the action of corrosive sulphur compounds in oil have been reported. It was realized that the tests for corrosive sulphur used in oil specifications, mostly ASTM D1275 Figure 7. Gas chromatography mass spectrometer (GC-MS) for analysis of inhibitor content in oil. 2.3 Physical properties 2.3.1 Colour (ASTM D1500) Colour is not itself a very important property of insulting oil. However, the colour is an indicator of degree of aging, and together with results from the chemical analyses it has some diagnostic value. Figure 6. Apparatus for determining the water content in oil using Karl- Fischer titration. Figure 8. Apparatus for measurement of interfacial tension (IFT). 4 Dissolved gas analysis and supervision of oil condition in transformers and reactors

(copper strip) or DIN 51353 (silver strip) were not adequate. Several oils passing these tests have caused copper sulphide formation in real life, in some cases with failure as a consequence. New tests have been developed, that have higher sensitivity or are more relevant for the failure mechanisms involved. A new more severe copper strip test has been introduced (ASTM D1275 method B), and a covered conductor deposition test ( CCD ) was developed to identify oils that may cause copper sulphide precipitation in cellulosic insulation. A simplified version of the latter test is described in IEC 62535. Although the phenomenon of copper sulphide formation has gotten most of the attention in the last few years, the risk of sulphide formation on silver coated selector contacts should also not be forgotten. The DIN 51353 silver strip test may be useful to detect this problem. 3. SAMPLING AND FREQUENCY OF ANALYSIS (IEC 60567, IEC 60475) It is recommended to perform the sampling of oil according to IEC 60567. In IEC 60475 the sampling procedure for the supervision of oil condition is described. ABB provides the appropriate test vessels and sampling instructions (figure 1). The frequency of sampling for DGA is recommended to be performed once every year or as recommended by the laboratory. The frequency of sampling for supervision of oil is recommended to be every fifth year for transformers up to 15 years age and then every third year or as recommended by the laboratory. 4. ORDERING OF TESTS Contact the laboratory at diagnostics@se.abb.com, or tel. +46 240 783307. We will provide the sampling containers required. Follow carefully the instructions in documents 1ZSE 209 001-4 and 1ZSE 209 001-6, which are provided together with the samplig vessels. It is very important that it is stated in the ordering if it is a normal routine test or if anything special has occurred in the transformer. Please give also the name of a contact person and the corresponding telephone number. Dissolved gas analysis and supervision of oil condition in transformers and reactors 5

Notes 6 Dissolved gas analysis and supervision of oil condition in transformers and reactors

For more information please contact: ABB AB Power Transformers, dept. AED Diagnostic Services SE-771 80 LUDVIKA, Sweden Phone: +46 240 78 20 00 This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. Contravention will be prosecuted. ABB AB 1171 1903-4E www.abb.com