IMAGINATION SOLAR LTD. Installation Guide B3. Vented & Unvented Cylinders

Similar documents
Range Tribune HE Solar Unvented Direct and Indirect Cylinders

Electric Flow Boiler

Installation and User Instructions Unvented Electric Storage Water Heater Models: S10UNV, S15UNV.

Plumbing and Electrical Installation Guide

Link-Up. Solid Fuel Association Guide to Central Heating.

Zenith Solar thermal 4.5m pump station Installation manual

INSTALLATION & TECHNICAL MANUAL

StainlessLite. Unvented mains pressure and vented water storage in Duplex stainless steel SUPPLIERS TO THE MERCHANT TRADE FOR OVER 40 YEARS

UNDERSTANDING CENTRAL HEATING SYSTEMS

Session 2: Hot Water Supply

High Output Boiler Systems

Operators manual Basic water heater

Thermo Siphon Solar Systems

UNDERSTANDING HOT WATER SYSTEMS IN THE HOME

INSTALLATION INSTRUCTIONS FOR ALBION ULTRASTEEL UNVENTED CYLINDERS: DIRECT, INDIRECT AND SOLAR MODELS.

Indirect-Fired Storage Water Heater Models WH-30 through WH-80 INSTALLATION AND OPERATING INSTRUCTIONS

FILLING AND PURGING THE SYSTEM

R e n e w a b l e s. Tribune HE Unvented Hot Water Cylinders Installation and Maintenance Instructions. Issue 14 May 2011 Part No.

ELECTRIC CENTRAL HEATING FLOW BOILER

Speedflow Undersink Unvented Water Heater. Models SF10K and SF15K. Instruction Manual

SF15K SF05KSS, SF10KSS

Visage. Digital. Digital diverter. Installation guide. Visage Digital diverter installation instructions Page 1

Please also see 10 golden rules for correct Saniflo installation on

WC flushing cistern single or dual flush to fill in 2 minutes WC trough cistern 0.15 per WC Wash basin tap size 1 2

Air Source Heat Pump Installation and Maintenance Manual

Elson 10/15L Unvented Water Heater

Commercial Semi-Instantaneous Water Heaters

Floor Heating Warehouse.co.uk

Solar Combisystems Changes on the market place since Task beginning

Solar Collector Series. Product List

I N S T A L L A T I O N I N S T R U C T I O N S F O R T H E H i l k o i l Energy S aving Hot Water Kit

Owners Guide and Installation Instructions.

Itho Products for Hot and Boiling water. product-

Morco House Riverview Road Beverley HU17 0LD

Unvented water heater

SOLAR HEATING SYSTEMS.

EcoSoft Water Softener. General Installation Guide

Guidance Notes For Provision Of Water Expansion For 10 & 15 Litre Unvented Hot Water Heaters

High Efficiency Boiler Range Technical Guide

Fully Pumped Systems

LK Electric Boiler - 4,5

Installation and User Instructions Aquaheat Unvented Water Heaters Models: AH7/2.2, AH10/2.2, AH15/2.2

your water pressure explained

VC Series Zone Valves BALANCED 2-WAY AND 3-WAY HYDRONIC VALVES

IMPORTANT: PLEASE READ AND UNDERSTAND THESE INSTRUCTIONS BEFORE COMMENCING INSTALLATION.

Qualification Guide. BPEC 601/2514/7 - Level 1 Diploma in Plumbing Foundation. BPEC 600/9432/1 - Level 2 Diploma in Plumbing Foundation

Unvented water heater

WALLACE MAXIPUMP 3000, 5000, 6000 and HYDROJET 30P, 30C AND HJ400 INSTALLATION AND MAINTENANCE INSTRUCTIONS

TANKLESS WATER HEATER INSTALLATION DIAGRAMS

Installation & Operation Manual Models: STU

building engineering services association specification for: Domestic Heating

HOT WATER SYSTEMS.

Coolflo Safe Touch Shower Mixing Valve ST20015CP

REGISTRATION EXAMINATION, JUNE 2009 PLUMBING QUESTION AND ANSWER BOOKLET. Time allowed THREE hours

Home Cover peace of mind made simple

User's Instructions. Alpha HE CB25/33 and HE SY25

PIPES AND TUBES FOR HVAC PIPING AND EQUIPMENT

SPARE PARTS EXPLODED VIEW GAS WALL BOILERS Model GENUS PREMIUM FS CUENOD. R EN - Edition 01-26/10/2009

XE70 SERIES VC SERIES BALANCED HYDRONIC VALVES 2-WAY AND 3-WAY

Home Made Solar Panel Installation For Under 900.

OWNER & INSTALLER MANUAL AND WARRANTY INFORMATION.

Modulex. Gas Fired Boiler Systems PIPING GUIDE GF-115-P. Modular, Condensing, Hot Water Boilers Models: 303, 454, 606, 757, 909, Instruction No.

Owner s Guide and Installation Instructions Electric Domestic Water Heater

Isotemp Basic, Slim/B & Slim Square

PRO-CLEAN. Technical Description. Specifications. Space-saving design with minimum heat loss (melamine resin insulation)

Hot water supply, distribution and use

Mikrofill Ethos Condensing combination boiler

Replacement parts. WM97+ gas-fired water boiler Boiler Manual. OBTAIN PARTS ONLY THROUGH WEIL-McLAIN THE BOILER CONTAINS CERAMIC FIBER MATERIALS

PLEASE LEAVE THIS MANUAL WITH THE OSO UNIT AFTER INSTALLATION. For capacities litres

Megalife Vented Cistern Fed Water Heater Installation manual

Installation and Servicing Instructions. Alpha 240/280. Range of Wall Mounted, Fan Assisted, Room Sealed, Gas Fired Combination Boilers

Installation and User Instructions Aquarius Undersink Vented Water Heaters Models: AU7/3, AU7/1, AU10/3, AU10/1.

Assembly and instructions

SunMor SM-V30 Solar Water Heater Installation Manual

CI/SfB. (53.3) x. August Unvented Water Heaters. PremierPlus. Unvented Hot Water Cylinders

SECTION Hot Water Heaters (Hot Water Recirculation Systems and Point-of-Use Water Heaters)

Installation and maintenance instructions

Owners Guide and Installation Instructions Electric Domestic Water Heater

1 DESCRIPTION OF THE APPLIANCE

ROTEX Solaris: Use the energy of the sun. ROTEX Solaris Solar energy for hot water and heating. The heating!

Megaflo eco. Unvented hot water cylinders

ecomax Instructions for use Wall hung room sealed fan assisted condensing boilers For the user

Laddomat Charging unit

Installation and Troubleshooting Instructions for Electric Tankless Residential Water Heaters.

THE BOILING WATER DISPENSER INSTALLATION & OPERATING INSTRUCTIONS

SHOWER WATER HEATER MODEL BS 35 / 45 / 60 BS 35 E / 45 E / 60 E OPERATION AND INSTALLATION INSTRUCTIONS

HEAVY DUTY STORAGE GAS

SPARE PARTS EXPLODED VIEW GAS WALL BOILERS Model. CELTIC RSc b CUENOD. R EN - Edition 02-21/04/2005

Solar SOLARMAX ELECTRIC BOOSTED SPECIFICATIONS ALL AUSSIE GAS & ELECTRIC BOOSTED SOLAR WATER HEATERS

Water Volume Calculation in Hydronic Heating & Cooling Systems

ECOCIAT. Domestic hot water heat recovery unit

Aquamax Australia Pty Ltd ABN

HEAT INTERFACE UNITS (Modular)

Elson Coral E. Open Vented Thermal Store providing mains pressure hot water heated by electricity. Installation, Servicing and User's Instructions

Solar Skies Stainless Tank Series Water Heater

Installation & User Instructions

THERM Tankless Water Heaters. Applications Manual

IMPORTANT: PLEASE READ AND UNDERSTAND THESE INSTRUCTIONS BEFORE COMMENCING INSTALLATION. PACK CONTENTS

Zip Hydroboil Plus Cuts energy consumption dramatically

REGISTRATION EXAMINATION, NOVEMBER 2013 CERTIFYING PLUMBER ANSWER SCHEDULE

Transcription:

Page 1 of 9 IMAGINATION SOLAR LTD Installation Guide B3 Vented & Unvented Cylinders Unit 4 Montpelier Central, Station Road Bristol BS6 5EE t: 0117 942 6668 f: 0117 942 8998 e: enquiries@imaginationsolar.com www.imaginationsolar.com Reg. in England No. 4226842

Page 2 of 9 B3.1 Connecting to a Standard ISL Hot Water Cylinder (microbore coil) In the Imagination low flow solar system microbore pipe is used for circulation and for construction of the solar coil in the lower part of the hot water cylinder. Pipework is usually 8mm (o.d.) for a single panel system and 10mm for a twin panel system. Only larger multi-panel systems will require conventional 15mm and 22mm pipework (see section B2.4 for pipe sizes). The first advantage of this arrangement is that with the correct match of flow rate and pipe size, the velocity of the water is such that all air is expelled from the system, regardless of whether there are any kinks or loops present. In fact the water flow can drive air downwards, without the air bubbling up and around the water flow, which could otherwise cause an airlock. This makes it possible to connect the hot flow pipe from the solar panel to the top of the solar 10mm coil and not the bottom, without risk of an airlock. We connect this way whenever possible to enhance the stratification effect in the cylinder. The second advantage is that when the Imagination solar system drains down it can use the unique thermosiphon drainback system to drain all water from the pipework in a single strand of water. Rather like a continuous rope over the top of a pulley the water is actually pulled upwards over the high point of the solar panel before dropping down into the drainback vessel. B3 Figure 1: Colour Coded Pipe Connections (standard microbore solar coil) The red pipe from the collector should go to the top connection of the solar coil on the hot water cylinder. The blue pipe from the collector should go to the blue John Guest push fit connection on the drainback unit. The black John Guest push fitting from the drainback unit should go to the bottom connection of the solar coil on the hot water cylinder N.B. A drain cock is fitted to the DBU as standard with an extension tube also supplied; use this to attach a pressure test pump to test joints to 2 bar whilst the pump is running. It may also be useful to add a draincock to the bottom of the solar coil, such that water can be drained from the coil should there be a need to disconnect the solar system or change the cylinder.

Page 3 of 9 B3.2 Connecting to a Large Diameter Solar Coil In certain cases large diameter solar coils are present, typically 22mm. This may be because the system is being installed into a solar ready house, where the client wants to provide their own cylinder or where we are obliged to use an off-the-shelf cylinder for example with an unvented cylinder, where the coil has been part of the approval procedure. There is no problem using this type of coil but certain modifications must be made to the design to prevent airlocks occurring which will prevent drainback: 1. The DBU should be placed above the highest point of the solar coil, which will mean that there is always water in the coil, ensuring hydraulic continuity, without any air pockets. This means the water never drains out of the coil, which also means a larger drainback vessel is not required to hold this additional water. It is essential that the 22mm return pipe is elbowed vertically before reducing to microbore in order to purge the air out of the coil. If the DBU is not placed above the solar coil, a larger capacity drain back vessel will be required. Pump above coil (>100mm) Pump Unit Right! Large Diameter Coil Pump below coil Not Ideal! Pump Unit Large Diameter Coil Pump below coil Wrong! Pump Unit Large Diameter Coil B3 Figure 2: Drainback unit positioning with a large diameter solar coil: DBU should be higher than solar coil. 2. The hot flow pipe from the solar panel must be connected to the bottom of the solar coil and not the top, allowing air to rise ahead of the water line as the system is filled for the first time. Air Lock Right! Wrong! B3 Figure 3: Flow direction to prevent air pocket developing in a 22mm helically wound coil.

Page 4 of 9 Air Lock 3. The top connection to the solar coil (flow out of coil) should have a 22mm elbow fitted facing upward, before being reduced to 8mm or 10mm microbore. This prevents small air pockets being formed in the top of the coil which will cause an airlock and prevent drainback. Wrong! B3 Figure 4: Elbow should be directed upwards to prevent air pocket developing. 4. In the case of certain, usually unvented, cylinders (e.g. Range Tribune) both connections may be at the same height, with the coil spiralling down and then up to the same point again. Hydraulically the coil is effectively a 22mm U tube so drainback will not occur and in this case the antifreeze provided must be added and serviced. This is because an air pocket will be formed which interrupts the continuity of the siphon, which is required for drainback. The system will work but will not drainback. Air Lock Wrong! B3 Figure 5: An air pocket will form with double helix U tube heat exchangers.

Page 5 of 9 B3.3 Installation of the Solar Hot Water Cylinder The hot water cylinder is installed as per any standard hot water cylinder with the boiler connected to the top coil where applicable. It should only be installed by a competent plumber with a full understanding of hot water supply. The solar circuit only contains a few litres of water so leaks are unlikely to be disastrous whilst poor installation of the hot water cylinder can result in major water damage. An unvented cylinder must be installed by a competent person as outlined in G3 of The Building Regulations. If installing an unvented cylinder see B3.8. B3.4 Connection of the Solar Coil Referring to section B 2.4 determine the correct size pipes to connect to the top and bottom of the coil. If you have an ISL standard vented cylinder the microbore solar coil connections are 10mm compression, so a reducer from that to the 8mm pipe will be needed for a single collector system. DHW flow/return and boiler coil connections are 22mm compression. For 22mm solar coils on un-vented cylinders, reducers from 22mm to the microbore pipe size, will be needed. B3.5 Installing the Cylinder Thermometer Imagination Solar do not supply a mechanical cylinder thermometer, unless specially ordered. The Deltasol BS controller has a temperature readout and a digital thermometer should be used with the ATON controller, with sensors placed into dry cylinder pockets. B3.6 Insulation to Building Regulations Standard All pipes of a solar primary system should be insulated throughout the circuit. All other pipes connected to hot water storage vessels, including the vent pipe, should be insulated for at least 1m from their points of connection to the cylinder (or they should be insulated up to the point where they become concealed). The 13mm wall Vidoflex insulation supplied exceeds the requirements of the Domestic Heating Compliance Guide for both 8mm and 10mm pipe. B3.7 Safety We recommend the installation of a thermostatic mixing valve on your hot water supply. On bright sunny days hot water could reach 80 C, which could cause scalding, if this is not fitted. The mixing valve may reduce dynamic pressure to the taps, which in some cases may not be acceptable (e.g. showers with a low head of water). If this is the case then the cold-water tank may need to be raised on a platform, a booster pump may be required or a pumped shower may be used to replace a simple mixer shower. A better option would be to fit an un-vented solar cylinder if this is likely to be a problem. Alternatively the cylinder maximum temperature can be set lower, e.g. 65 C, although this wastes some of the available solar energy. B3.8 Unvented cylinders Pre-installation surveys must include measurements of mains water supply pressure and flow rate, usually at the kitchen sink tap. Whilst an un-vented cylinder will work efficiently under any water flow and pressure conditions, the full potential of a mains pressure system is unlikely to be achieved unless the supply static pressure is at least 1.5 bar and a flow rate of at least 25 l/min can be reached. Mains water pipework to the cylinder should be a minimum of 22mm diameter. Each unvented cylinder is supplied with a safety controls listed below. Expansion vessel (size varies according to cylinder capacity) Inlet controls (pressure reducing valve, non return valve, pressure relief valve and tundish) 1 x Temperature and pressure relief valve 1 x 22mm 2 port valve 1 x Dual Aquastat (for boiler DHW primary circuit) 1 x Dual Aquastat for solar circuit

Page 6 of 9 The diagrams below shows the location of all the tappings and pockets that should be included with the unvented cylinder. B3 Figure 6: The location of all the tappings and pockets for the Ferroli unvented cylinder. Installers please note: Quantum Cylinders 200, 250 and 300 litre come with 1 1 / 2 tappings on hot water outlet and secondary return. Installers will need to carry either of the following: - 2 off 1 1 / 2 M to 22mm F reducers AND a 22mm M tapping blank OR - 1 off 1 1 / 2 M to 22mm F reducer AND a 1 1 / 2 M tapping blank

Page 7 of 9 B3 Figure 7: The location of all the tappings and pockets for the Telford unvented cylinder.

Page 8 of 9 Solar Collector Mixing Valve Hot Water to Taps Solar Aquastat Thermometer Boiler Aquastat Motorised Valve Boiler Controller Boiler Coil Expansion Vessel Pump & Drainback Unit Solar Coil Temperature and Pressure Relief Valves Tundish Non Return Valve Safety Group Pressure Reducing Valve Mains water in Stainless Steel Unvented Cylinder B3 Figure 8: A mains pressure (unvented) system. The system must be fitted with the safety devices. Note that the return from the panel is connected to bottom of solar coil so the direction of flow is upwards through a 22mm coil (see section B3.2 on connecting to a large diameter coil). B3.9 Aquastat Wiring In order to provide two levels of overheat protection the dual aquastat for the boiler DHW primary circuit should be wired to the two port valve as per the wiring diagram included with the cylinder. The power supply for the solar controller is wired via the solar dual aquastat to provide 2 levels of overheat protection: Solar controller maximum limit Aquastat maximum limit As an alternative to wiring the controller power supply via the solar aquastat some installers prefer to wire only the switched power supply to the pump via the aquastat. This has the advantage that the Resol display can be used to read out cylinder temperatures. On the other hand the lack of display would flag up that there is a problem. In either case the pump will stop and the system will drainback. Also if required the adjustable temperature aquastat probe may be wired in and used as an additional third means of limiting the cylinder temperature to a user defined maximum temperature. (Telford 90 C, Quantum 70 C) The dual aquastat for the solar circuit should be wired as the two circuit diagrams in figures 8 and 9 if the user adjustable maximum temperature is required.

Page 9 of 9 Control variable 70ºC Quantum 90 º C Telford B3 Figure 9: Schematic electrical diagram of dual aquastat. 1. From the power supply wire into a dual pole isolation switch to enable the system to be switched off. 2. A chocolate block type connector can be used within the isolation switch enclosure to run a two core wire to the solar dual aquastat as shown below. 3. Wire the rest of the wires as per the standard system. Power supply Dual pole isolation switch Connector block Wiring Diagram of Quantum & Telford Dual Aquastat. N.B. The wiring is the same for the Quantum Aquastat, but the jumper lead is not supplied so will need to be fitted as shown by the blue line below (only if temp adjustment is required) 2 core flex to Aquastat Controll er B3 Figure 10: Practical wiring diagram of dual aquastat. The photograph shows the jumper lead position inside the Quantum dual aquastat. Wire only the high limit stat on the left if you do not want the aquastat to control max solar temp.