Acoustic and RF Shielding for Magnetic Resonance Imaging

Similar documents
Acoustic Terms, Definitions and General Information

Lightweight Partition Design for Residential and Commercial Buildings

The Role of Acoustics in Curtain Wall Design:

Acoustic design with wall acoustic solutions

The Effects of Ultrasonic Sound Generated by Ultrasonic Cleaning Systems on Human Hearing and Physiology

Building Design for Advanced Technology Instruments Sensitive to Acoustical Noise

PAGE 2. Figure 1: Difference between PWL ins and SPL 1m

Relationship between Sound Pressure and Sound Power Levels

Controlling the Transmission of Impact Sound through Floors

General Thoughts on Generator Set - Acoustic Solutions & Noise Control

Fundamentals of Acoustics & Practical HVAC Design Considerations. Demir Doken Acoustic Engineer

Sound Attenuation INTRODUCTION

INTER-NOISE DECEMBER 2006 HONOLULU, HAWAII, USA

Acoustic performance of dwellings and specifics for lightweight constructions Professor Eddy Gerretsen

The Acoustical Properties of Wool Carpet

Acoustical Design Guidelines for HVAC Systems in Schools

Acoustical Doorway Solutions

Schindler 3300 / Schindler 5300 Information on noise and vibration.

Façade acoustic design strategy Proposed residential development Irvin Avenue, Saltburn

TOP 10 NOISE CONTROL TECHNIQUES

How To Reduce Noise From A Test Screen

VIPAC ENGINEERS & SCIENTISTS

Noise. CIH Review PDC March 2012

Office acoustics. How to effectively design the room acoustics of offices. AN INFORMATION BROCHURE OF

AMF Line; wall absorbers Wall mounted acoustic designs PERFORMANCE CEILINGS. M ore s c op e f or i n n ovat i on MADE IN GERMANY

Mass Loaded Vinyl A review of the performance and cost in acoustical applications

Acoustical Design for Concert Hall in the Science and Art Centre of Xiamen University

BNAM 2008 BERGEN BYBANE NOISE REDUCTION BY TRACK DESIGN. Reykjavik, august Arild Brekke, Brekke & Strand akustikk as, Norway

Leeds Metropolitan University - Design and Build of new Acoustic Laboratory Suite

Vibration Isolation in Data Centers

PART VIII: ABSORPTIVE SILENCER DESIGN

Airborne Sound Insulation

Avaya WLAN 9100 External Antennas for use with the WAO-9122 Access Point

Selecting Receiving Antennas for Radio Tracking

Acoustic Design Practices for Sustainable Buildings

SOUND INSULATION FOR EXTERIOR WALLS AND FACADE SYSTEMS

Optiffuser. High-performance, high bandwidth lightweight 1D diffuser.

INC Flexi-Sorb. Versatile Flexible Easy To Install Durable Good Noise Reduction Economical. Typical Applications

EMF shielding by building materials

MRI RF SHIELDING DESIGN

is the power reference: Specifically, power in db is represented by the following equation, where P0 P db = 10 log 10

Active noise control in practice: transformer station

An Experimental Study of the Sound Insulation Performance and Sound Defect Using Sound Intensity According to the Composition of Balcony Windows

Section 2.4. Built-up Metal Roofs. Rail and bracket system. Standing seam system. Bu02. Product: Earthwool FactoryClad range Bu01

Data Centres A complete solution to noise control and acoustic packages

EVERYTHING YOU WANTED TO KNOW ABOUT SOUND BUT WERE AFRAID TO HEAR.

Characterization of acoustics in open offices - four case studies

ACOUSTIC DESIGN - ROOMS FOR SPEECH

At the completion of this guide you should be comfortable with the following:

SOUND INSULATION FOR AIR CONDITIONERS AND OTHER EXTERNAL MECHANICAL PLANT. Installing and Maintaining Air Conditioning Units

Noise Control Solutions For Standby Power Generators

Squash Court Design general points

Cool air quietly and efficiently. A guide to buying and operating an air conditioner

Sound Pressure Measurement

Affordable Sports Halls

Interference to Hearing Aids by Digital Mobile Telephones Operating in the 1800 MHz Band.

Acoustic. Publication date June

CASE STUDY. Sarakasi Theatre Nairobi, Kenya Room Acoustical Measurements and Modelling. Africa Room Acoustics DIRAC and ODEON

Sound Power Measurement

ACOUSTICS TESTED WINDOWS & DOORS

MCS 020. MCS Planning Standards. For permitted development installations of wind turbines and air source heat pumps on domestic premises

ASTM E 90: Laboratory Measurement of Airborne Sound Transmission of Building Partitions and Elements

Rockwool Flexi Insulation Application Guide

Acoustical proprieties of light brick walls and its effects on flanking transmission

Sound absorption and acoustic surface impedance

How Noise is Generated by Wind Turbines The mechanisms of noise generation. Malcolm Hayes Hayes McKenzie Partnership Ltd Machynlleth & Salisbury

MERO Floor Systems - CleanRoom

Planning Information. Passenger and Freight Elevators.

Case Studies Illustrating Acoustic Design Guidelines for HVAC Systems in Schools

Generic - Hearing Loop - (AFILS) U.S. System Specification

Absorption mufflers in exhaust systems. Rolf Jebasinski. J. Eberspächer GmbH & Co. Abstract

SL30-ISO PROFILE SYSTEM

An Installers Guide to

Trans Bay Cable Project (400 MW) Preliminary Audible Noise Study

Dynamic sound source for simulating the Lombard effect in room acoustic modeling software

Direct and Reflected: Understanding the Truth with Y-S 3

HEALTHY LIVING WITH WOOD FIBRE INSULATING MATERIALS

Acoustics & Building Services An back to basics overview

VIII. Noise A. INTRODUCTION B. BACKGROUND

A COMPUTATIONAL METHOD FOR ANALYSIS AND DESIGN OF ACOUSTIC ABSORBERS AND LOW FREQUENCY TRANSMISSION LOSS

Fire 2This Technical Bulletin has been commissioned by the UK SIP Association in

KRUGER ENERGY CHATHAM WIND PROJECT ENVIRONMENTAL SCREENING REPORT / ENVIRONMENTAL IMPACT STATEMENT. Appendix E. Environmental Noise Impact Assessment

Security steel door dw 52-1 Teckentrup DF WK 2 optionally with glazing/ventilation grille

sound reduction systems for commercial, educational and industrial environments

Understanding Range for RF Devices

FUTURE SLAB. PENETRATIONS and. DEMOLITION of POST-TENSIONED FLOORS

Radio Frequency Interference (RFI) Shielding Principles

Acoustic design of schools: performance standards. From 2003 to 2014: a brief guide to the changes in BB 93. by Jack Harvie-Clark, 9th January 2015

The Regulation is established pursuant to 3 (4) and 6 (6) of the Occupational Health and Safety Act. Chapter 1 GENERAL PROVISIONS

4 SENSORS. Example. A force of 1 N is exerted on a PZT5A disc of diameter 10 mm and thickness 1 mm. The resulting mechanical stress is:

LEED Pilot Credit Library

Retrofit structural insulated panels (SIPs) increase sound transmission loss of existing single family houses impacted by highway noise

Basic Concepts of Sound. Contents: Definitions db Conversion Sound Fields db ± db

A simple method to compute aircraft noise inside dwellings

Acoustic Design Guide. NR and NC Curves CIBSE Noise Ratings Environmental Noise Control Maximum Air Velocities in Ducts Privacy in Cellular Offices

Installation, operation and maintenance manual TX 35A

Fire & Soundproofing Insulation. Roxul SAFE N SOUND. Fire and Soundproofing Insulation for Interior Partition Walls and Floors.

Noise Design Advice. Noise can be a major factor to consider in any new development.

In today s architectural environment, good acoustical design isn t a luxury

SMOKE DETECTOR INSTALLATION PROGRAM The Burlington Ordinance Perspective

Transcription:

SilentSHIELD Acoustic and RF Shielding for Magnetic Resonance Imaging 1

Contents 1. Why IMEDCO?...3 2. Foreword for our US customers...4 3. Why is soundproofing needed?...4 4. Airborne and structurally borne noise...5 5. How much soundproofing does a building need?...6 6. Designing soundproofing...7 6.1 Is an acoustic engineer necessary?...7 6.2 MRI equipment data...7 6.3 Utilisation of adjacent rooms...8 6.4 Construction of existing walls, ceiling and floor...8 6.5 What soundproofing is actually necessary?...9 7. Reduction of airborne noise...9 7.1 IMEDCO SilentSHIELD TM 1...10 7.2 IMEDCO SilentSHIELD TM 2...11 7.3 IMEDCO SilentSHIELD TM 3...12 8. Structural soundproofing...13 8.1 Single elastic supports...13 8.2 Double elastic support...14 9. Soundproofing components...15 9.1 IMEDCO SilentSHIELD TM RF doors...15 9.2 IMEDCO SilentSHIELD TM RF windows...16 10. Notes...17 11. Glossary of technical terms...18 11.1 How to convert the MRI sound into NC limitations...19 12. RF attenuatuion...20 13. IMEDCO, Switzerland...20 2

1. Why IMEDCO? Because IMEDCO is one of the leading suppliers of combined acoustic and RF shielding enclosures worldwide. The IMEDCO advantages in brief: The conformity of all acoustic and RF shielding components has been measured by the independent company Akustik Projekt Reichmuth (member of the Swiss Acoustical Society and the Deutsche Gesellschaft für Akustik ) according to ISO 140/717. The respective data sheets are available on request. The following US patents have been awarded: A radio frequency shielded and acoustically insulated door U.S. 6,519,899 Radio frequency shielded and acoustically insulated enclosure U.S. 6,626,264 Quality management system conforming to ISO 9001 since 1997. Monthly quality management meetings are held to ensure quality improvement. The company owners are also responsible for its day to day operations and success. Robert Schweizer CEO Urs Schläpfer Engineering and Development Walter Christen Sales and Project Management Peter Hürzeler Manufacturing and Installation More than 2 500 satisfied users worldwide (request our reference list). All shielding products and services from a single source: Magnetic shielding Magnetically shielded rooms (MSR) for bio-magnetic research Magnetic field and vibration measurements Acoustic insulation planning and engineering, acoustic expertises Active compensation system for low frequency magnetic field fluctuations Shielding for special purposes 3

2. Foreword to our US customers Soundproofing has been applied for a number of years in Germany and Switzerland. It is mandatory for dwellings and offices to be constructed such that they may be used for the purpose for which they are built without restriction. German DIN 4109 specifies permissible levels for residual noise in adjacent rooms. These levels are relatively low, but have been found to be correct in practice. Assuming that people around the world have roughly the same average perception of audible noise, we propose using the same permissible noise levels (see Page 6) for US projects as well. However, local regulations take precedence and only they count as binding. A list of units and symbols used in this brochure is given on pages 18 and 19. These units conform to DIN EN ISO. We are aware that these units are not binding in the US, nevertheless they are in common international use. Since in some cases other units are familiar in the USA, we have endeavored to indicate their international equivalents. 3. Why is soundproofing needed? Since their inception, magnetic resonance imaging (MRI) tomographs have become steadily more powerful. Whilst this improves image quality, it also means that the magnet assembly generates more audible noise. The propagation of this noise to neighbouring rooms has to be prevented. Examination of the noise situation on site is recommended for the following reasons: New buildings have to fulfil higher requirements with respect to noise reduction. Old buildings were not designed to accommodate magnet assemblies generating high levels of audible noise. Hospitals are now demanding lower levels of audible noise in neighbouring wards, operation theatres and consultation rooms. Where there are other tenants in the same building, their rights regarding audible noise and disturbance have to be respected. 4

4. Airborne and structurally borne noise IMEDCO, Illustration No. 9069 IMEDCO, Illustration No. 9070 Airborne noise: Airborne noise is the noise generated by the MRI equipment and transported via the air. It is conducted to neighbouring rooms either directly via ducts and penetrations in the building structure (a) or by impacting the building structure itself and causing it to vibrate (b). Structurally borne noise: Structurally borne noise is transmitted through the mounting of the MRI equipment to the floor (c). This energy causes the walls, floors and ceilings of neighbouring rooms to vibrate which then radiate airborne noise. 5

5. How much soundproofing does a building need? There are several German standards defining maximum noise levels in rooms where people work, so that neighbours are not disturbed and such that hospital patients can recover in a healthy environment. The unit of noise level in these standards, the time average sound pressure level (L AF,r ), is a mean value which takes into account the level when there is no noise disturbance and the level when there is (impulse and frequency content). Refer to DIN 45645 for the exact definition of assessment level. The MRI workplaces The maximum levels defined in the health and safety act (Arbeitsstättenverordnung) issued on May 20th, 1975 are: Operating, consultation and evaluation rooms L AF,r = 55 db(a) Normal office work mainly using machines L AF,r = 70 db(a) Other activities L AF,r = 80 db(a) Areas belonging to other departments in the hospital The health and safety act also applies to these areas, although its prime objective is to prevent damage to hearing and maintain working capacity and not to limit the subjectively disturbing transmission of acoustical noise. Thus the levels given in the health and safety act are inappropriate for satisfying today s workplace requirements. To ensure an undisturbed environment in other departmental areas they should be reduced by approximately 10 db and therefore the following maximum levels are recommended: Wards (daytime 6 am to 10 pm) L AF,r = 35 db(a) Doctors offices, consulting rooms, general offices L AF,r = 35 db(a) Quiet consulting rooms (e.g. psychiatric departments) L AF,r = 35 db(a) Noisy consulting rooms (e.g. with medical equipment) L AF,r = 45 db(a) Operating theatres L AF,r = 45 db(a) Intensive care L AF,r = 45 db(a) Waiting areas L AF,r = 45 db(a) Areas used by third parties (e.g. apartments or offices) Maximum levels according to DIN 4109 or the instructions concerning for noise suppression. Living rooms and bedrooms (night time 10 pm to 6 am) L AF,r = 25 db(a) Living rooms and bedrooms (daytime 6 am to 10 pm) L AF,r = 35 db(a) Training and working rooms L AF,r = 35 db(a) DIN 4109 specifies that these maximum levels may be exceeded only briefly by a maximum of 10 db. 6

6. Designing soundproofing Since they mutually influence each other, soundproofing and RF shielding should be designed together and wherever possible come from the same supplier. This is necessary, for example, to prevent penetrations through the RF shielding for air-conditioning, quench lines or filters from diminishing the efficiency of the soundproofing. All penetrations should be in the wall to the technical room and in cases where this is impossible, silencers or extra insulation layers have to be included. 6.1 Is an acoustic engineer necessary? Where a building structure has special characteristics or several rooms adjacent to the MRI room have to be protected, we can arrange for an expertise by an acoustic engineer. He then specifies how the RF shielding of the walls, floor and ceiling has to be executed to ensure that the maximum permissible audible noise level is not exceeded. New buildings: An acoustic engineer can calculate the transmission of noise to adjacent rooms to be expected on the basis of the plans and the material specifications for the new building. The sound reduction indices of the various kinds of materials are obtained from the respective data sheets or standards. Old buildings: Since the sound reduction indices of the building materials are seldom available, the best procedure is for an acoustic engineer to simulate the noise emitted by the MRI equipment to be installed and to measure the noise levels in the adjacent rooms. Where the sound reduction indices of the building materials are already known, we can offer a wide range of soundproofing solutions with values of D for floors, walls and ceilings from 35 db to 80 db. We guarantee the tested sound reduction indices of the RF enclosure components. The assessment of the overall sound transmission depends on the availability and accuracy of the data on which it was based. 6.2 MRI equipment data The sound pressure level (L p ) of the MRI equipment during operation is generally given in the supplier s engineering manuals. In order to determine the effective operating noise on site as accurately as possible, the following information is required: Make and Model of MRI equipment to be installed The operating sound pressure level L p measured at a distance of 1 m or the sound power level L w of the MRI equipment Level of the structural sound energy transmitted by the MRI equipment to the floor The proportion of operating noise peaks in relation to total operating time Any increase in sound level planned for the future 7

6.3 Utilisation of adjacent rooms The purposes for which the adjacent rooms are used bears a decisive influence on whether the operating noise of the MRI equipment actually disturbs or is barely audible in relation to the existing background noise. For what purpose is each of the adjacent rooms used? Which rooms require special soundproofing? Are there any rooms occupied by third parties close by and if so for what purpose are they used? Is a change in the utilisation of any of the adjacent rooms planned for the future? 6.4 Construction of existing walls, ceiling and floor The propagation of MRI operating noise depends on the construction of the building and different methods of insulation have to be adopted to confine noise and prevent it from being transmitted through the structure. The following data are required to calculate the overall characteristics necessary: How good is the existing soundproofing for airborne noise (D) between the MRI room and the adjacent rooms? How is the floor constructed, how thick are the various layers and what is the mass per unit area? Is the floor construction isolated from the rest of the building? Is the floor slab on grade? What are the longitudinal and lateral (R F ) sound transmission indices of the entire floor? Are there any unnecessary openings in the partition walls (ventilation)? Can noise be conducted via services ducts or pipes? Does the room below the MRI have a suspended ceiling? Does the soundproofing against airborne and structurally borne noise conform to building regulations? As is drawings are absolutely essential to clarify the conditions prevailing on site. However, should some of the data needed not be available, measurements by an acoustic engineer can provide them. 8

6.5 What soundproofing is actually necessary? The soundproofing to be integrated in the RF shielding is given approximately by the following: Noise emitted by the MRI equipment Tolerable noise in the adjacent room concerned = Required soundproofing step Example: MRI equipment 105 db Third-party conference/doctor s consulting room -35 db = Required soundproofing step 70 db 7. Reduction of airborne noise Noise either passes as air vibrations through openings (see Type a on Page 5) or causes walls, ceiling or floor to vibrate (Type b). Sound transmission can be limited by installing partition walls to create an inner shell. The IMEDCO RF shielding can be integrated in the overall design for this purpose. The aim is a room-in-room configuration with optimised spacing with respect to the building structure. To this end, the following criteria must be observed: The minimum gap specified between the RF enclosure and the structure of the building must be maintained. The inner shell must have a certain mass per unit area. Ridgid connections to the building structure must be avoided. Cavities should be filled to 2 / 3 with mineral wool. The inner shell must be uninterrupted at all transitions. To simplify project design, IMEDCO has grouped the many possibilities into a three-step soundproofing system. SilentSHIELD 1 SilentSHIELD 2 SilentSHIELD 3 65 db 70 db 80 db The noise suppression characteristic of the ideal uniform wall can be impaired by penetrations for windows, ventilation, wave-guides, filters, quench lines etc. Air-conditioning ducts and quench lines between NOISY and QUIET rooms are conductors of noise and must be correspondingly encapsulated. 9

7.1 IMEDCO SilentSHIELD 1 Building wall and ceiling KNAUF W112, w = 150 mm, and concrete ceiling w 200 mm R w = 54 db IMEDCO RF attenuation/soundproofing: Mineral fibre panels in ceiling and walls Total audible noise suppression 65 db (The supports for the MRI equipment feet depend on the make and may vary from the drawing.) Advantages: Optimum arrangement of layers to minimise thickness Soundproofing can be largely integrated during production and therefore extremely cost effective Low static load Alternative: KNAUF W143, w = 175 mm and concrete ceiling w 300 mm R w = 60 db RF attenuation/soundproofing: Mineral fibre panels in ceiling and walls Total audible noise suppression 70 db 10

7.2 IMEDCO SilentSHIELD 2 Building wall and ceiling KNAUF W112, w = 150 mm, and concrete ceiling w 200 mm R w = 54 db IMEDCO RF attenuation/soundproofing: Heavier ceiling and walls, elastic floor foundation Total audible noise suppression 70 db Increased performance in relation to the 65 db step: Self-supporting ceiling attached to joists. Additional mineral fibre soundproofing in RF ceiling. Extra layer makes soundproof ceiling heavier. Double inner shell forms heavy cavity wall. Elastically supported enclosure floor with chipboard reinforcement. Elastically supported floor with different densities. (The supports for the MRI equipment feet depend on make and may vary from the drawing.) Advantages: Highly cost effective Minimum width Elastically supported RF floor Alternative: KNAUF W143, w = 175 mm and concrete ceiling w 300 mm R w = 60 db RF attenuation/soundproofing: Heavier ceiling and walls, elastic floor foundation Total audible noise suppression 75 db 11

7.3 IMEDCO SilentSHIELD 3 Building wall and ceiling KNAUF W143, w = 175 mm, and concrete ceiling w 300 mm R w = 60 db IMEDCO RF attenuation/soundproofing: Much heavier ceiling and walls, thick elastic floor foundation Total audible noise suppression 80 db Increased performance in relation to the 70 db step: Ceiling cavity filled with 100 to 150 mm of mineral fibre panels. Soundproof ceiling with different degrees of weight increase. Wall cavity filled with mineral fibre panels Two inner shell panels of different thicknesses form heavy cavity wall. Two layers of Elastomer provide a super soft sprung floor. (The supports for the MRI equipment feet depend on make and may vary from the drawing.) Advantages: Extremely high sound level difference D Optimised construction makes best use of available space Elastically supported RF floor with 2 instead of 1 layer of Elastomer 12

8. Structural soundproofing The current in the gradient windings generates an oscillating magnetic field in the core of the MRI equipment which gives rise to audible vibrations. If the magnet is standing directly on the floor the vibrations are transferred to it (see Type c on Page 5). Depending on the material of the floor, they will be conducted over a greater or smaller distance. José can hear the train when it is still miles away. 8.1 Single elastic supports The mass per square metre m of a solid concrete floor for w 200 mm is approximately 460 kg. On this basis, the weighted apparent sound reduction index R w is already about 54 db (DIN 4109, Table 1). In this case, a single elastic support under each foot is generally sufficient to prevent the MRI vibrations from being transferred to the floor. They are usually supplied together with the MRI equipment, otherwise IMEDCO can supply them. D [db] IMEDCO, Illustration No. 9074 IMEDCO, Illustration No. 9075 100 f [Hz] Where the mass of the floor is particularly high, it can only be excited to a small degree by MRI vibration. Single elastic supports are usually all that are needed to optimally decouple the MRI equipment from the building structure and provide adequate soundproofing in the audible range (100 Hz to 20,000 Hz). There are different kinds of elastic supports. If they are necessary at all and if so which type depends on the make and model of MRI equipment. 13

8.2 Double elastic support Where the mass of the floor is low, the oscillations generated by the MRI equipment can be transferred to the building structure. By adding an additional elastically supported mass to create a double elastic foundation, the total elastically supported mass can be increased. This improves the soundproofing of the MRI equipment with respect to structurally conducted noise thus reducing its transmission to the building structure. D [db] IMEDCO, Illustration No. 9076 IMEDCO, Illustration No. 9077 100 f [Hz] What is used for the additional mass, its dimensions and the type of support depend on the building structure and the make and model of MRI equipment. An elastic system having two degrees of freedom achieves better noise reduction. IMEDCO offers either a stainless steel plate or a concrete slab. The additional heavy mass can either be integrated in the shielding floor to form a level surface or placed on the floor as a pedestal. Elastically supported stainless steel plate (height 30 to 50 mm) Slight additional thickness has to be accommodated Good load distribution Wherever possible, the heavy plate is transported into the building together with the MRI equipment U.S. Patent No.: 6,626,264 Elastically supported concrete pedestal (height 180 to 250 mm) An ideal solution for maintaining the minimum spacing when a magnetic shield is installed between the MRI equipment and the floor Cheaper than a stainless steel plate 14

9. Soundproofing components 9.1 IMEDCO SilentSHIELD RF doors US type door with handle/roller latch and dead bolt cylinder lock Standard size: 1200 mm x 2100 mm, other sizes on request U.S. Patent No.: 6,519,899 European type door with safety lock Standard RF door Double shell construction with contact fingers Extra soundproofed RF door R w = 40 db Double shell door with weighted and decoupled shells and integrated seal Super soundproofed RF door R w = 42 db As 40 db door but with perforated door frame 60 : R : Shifted reference curve acc. to ISO 717 60 : R : Shifted reference curve acc. to ISO 717 60 : R : Shifted reference curve acc. to ISO 717 db db db 50 50 50 40 40 40 30 30 30 Sound reduction index R 20 10 Sound reduction index R 20 10 Sound reduction index R 20 10 0 125 250 500 1000 2000 Hz Frequency f R w = 20 db Measurement Report No. 990604-B1 0 125 250 500 1000 2000 Hz Frequency f R w = 40 db, R f1600 = 44 db, Measurement Report No. 020401-B2 U.S. Patent Appl. Publication No. US 2003/0167697 A1 0 125 250 500 1000 2000 Hz Frequency f R w = 42 db, R f1600 = 46 db, Measurement Report No. 991101-B2 U.S. Patent No. 6,519,899 15

9.2 IMEDCO SilentSHIELD RF window Thin panes of glass suppress high frequency sound waves very well and thick ones suppress low frequencies. An effective soundproof window therefore includes thin and thick panes of glass. Further appreciable improvement is obtained by a third pane in the plain (a) (not normally part of our scope of supply). Connections to the building wall must be decoupled by elastic junctions. IMEDCO, Illustration No. 9055-I Soundproofed RF window R w = 36 db Two safety glass panes 60 db 50 : R : Shifted reference curve acc. to ISO 717 Highly soundproofed RF window R w = 43 db Two safety glass panes in different thicknesses 60 db 50 : R : Shifted reference curve acc. to ISO 717 Super soundproofed RF window combination R w = 55 db Three glass panes of different thicknesses, laminated glass and perforated intermediate frame 70 db 60 : R : Shifted reference curve acc. to ISO 717 40 40 50 30 30 40 Sound reduction index R 20 10 Sound reduction index R 20 10 Sound reduction index R 30 20 0 125 250 500 1000 2000 Hz Frequency f 0 125 250 500 1000 2000 Hz Frequency f 10 125 250 500 1000 2000 Hz Frequency f R w = 36 db, R f1600 = 46 db Measurement Report No. 990604-B3 R w = 43 db, R f1600 = 48 db Measurement Report No. 991101-B10 R w = 55 db, R f1600 = 63 db Measurement Report No. 031003-B4 16

10. Notes 17

11. Glossary of technical terms The following terms are frequently used in acoustics db db(a) A-weighted sound pressure level (SPL) Frequency f Resonance frequency f 0 Airborne sound Structure borne sound One-third sound pressure level octave band Sound reduction index (SRI) R (Sound transmission loss) Apparent sound reduction index R Weighted sound reduction index R w (almost identical to STC) Weighted apparent sound reduction index R w (Apparent sound transmission loss) Sound level difference D Weighted normalized sound level difference D n,w Sound power level L w (PWL) Sound pressure level L p (SPL) (Hz) (Hz) Symbol for decibel; unit for logarithmic physical quantities including sound pressure level Sound pressure level adjusted to take account of the variation in human perception of different frequencies. A tone of 100 Hz is subjectively perceived as being quieter than a tone of 1,000 Hz at the same sound level. (see graph on the next page). Cycles per second The natural frequency of an oscillatory system Sound propagated through the air Sound propagated through solid material Sound pressure level measured in each third of an octave Airborne noise suppression of components measured in the laboratory (excluding parallel paths) according to ISO 140/III. R is derived from the difference of noise levels D, the equivalent absorption area A in the receiving room and the test area S. As for sound reduction index R, but measured on site (including parallel paths) according to ISO 140/IV As for sound reduction index R, but reduced to a single number rating determined according to ISO 717/1 for classification of the frequency dependence As for apparent sound reduction index R, but reduced to a single number rating determined according to ISO 717/1 for classification of the frequency dependence Difference between the sound pressure level in the source room L 1 and the sound pressure level in the receiving room L 2. D = L 1 L 2 As for sound level difference but reduced to a single number rating according to ISO 717/1 for the classification of the frequency dependant normalized sound level difference Sound emitted by the MRI equipment as airborne sound excluding the influence of the MRI room. Assuming the acoustic properties of the future MRI room are known, the prospective sound pressure level L p can be calculated from the sound power level L w. The operating noise level e.g. of the MRI equipment in the MRI room 18

Maximum sound pressure level L AF,max Time-average sound pressure level L AF,r Day-night sound level (DNL) Absorption coefficient α RF shielding A weighted maximum sound pressure level determined with time weighting fast A weighted mean sound level determined during an assessment period (e.g. operating time of the MRI equipment) (DIN 45645). The purpose of this unit is similar to the day/night-sound level although the definition is slightly different Day/night sound level is a descriptor that takes account of the added impact of night time noise. It is a 24 hour L eq based on A weighting with 10 db(a) added between the hours of 10:00 p.m. to 7:00 a.m. DNL is an accepted descriptor of environmental noise where sleep disturbance is an issue. Community noise impact is commonly described by DNL contours Sound absorption coefficient Metal screening preventing the propagation of radio frequency electromagnetic waves, i.e. Faraday cage 11.1 How to convert the MRI sound into NC limitation 80 Sound pressure level L [db] 70 60 50 40 30 20 10 0 63 125 250 500 1000 2000 4000 Octave-band center frequency f [Hz] NC-45 Octave-band sound pressure level L [db] A -weighted octave-band sound pressure level L [db(a)] The octave band sound pressure level is the true NON-WEIGHTED energy sound pressure level of a typical MRI system measured in the control room (incl. RF door and RF window). The noise criteria (NC) are single numerical indices used primarily for air conditioning systems to define design goals for the maximum permissible noise in a given space. The NC criterion consists of a family of curves that define the maximum permissible octave band sound pressure level corresponding to a chosen NC design goal. To achieve the NC design goal the sound pressure level shall not exceed the given limit in each frequency band. Sound pressure level at 1000 Hz provides the single number value. The A weighted sound pressure level is adjusted to take account of the variation in human perception of different frequencies. A tone of 100 Hz is subjectively perceived as being quieter than a tone of 1000 Hz at the same sound level. The curve is given for comparison only. 19

12. RF Attenuation IMEDCO RF components and structures are available with the RF attenuations given on the right. These figures can, however, be adjusted according to the MRI equipment in use. Magnetic field: 15 MHz 100 db Electric field: 10 khz 100 db 30 MHz 100 db Plane waves: 30 MHz 100 db 100 MHz 100 db 130 MHz 100 db 13. IMEDCO, Switzerland Headquarters and manufacturing facility in Hägendorf, Switzerland (located 50 km south of Basle and 70 km west of Zurich at the motorway junction of the A1 and A2, motorway exit Egerkingen, Olten). Administration and Production Storage and Logistic IMEDCO AG, Hägendorf, Switzerland. Edition 10/2004 / Document No. 9055-BE 90 Employees Company owned premises Fully equipped with laboratory and test instruments for RF and magnetic shielding applications Own manufacturing facility 11 agents in Europe, Asia and America Quality management system according to ISO 9001 since 1997 More than 2 500 reference installations Reproduction in whole or in part is prohibited without prior written consent of the copyright holder. IMEDCO AG reserves the right to make changes in specifications or to discontinue any product at any time without notice or obligation and will not be liable for any consequences resulting from the use of this publication. email: imedco@imedco.ch Copyright by IMEDCO AG, Hägendorf, Switzerland. All internet: rights reserved. www.imedco-shielding.com 20 IMEDCO AG Industriestrasse West 14 CH-4614 Hägendorf Switzerland Phone +41 62 209 40 20 Fax +41 62 209 40 29