Shading Effects on Output Power of Grid Connected Photovoltaic Generator Systems

Similar documents
Yield Reduction due to Shading:

Solar Cell Parameters and Equivalent Circuit

PHOTOVOLTAIC SYSTEMS. Alessandro Massi Pavan

Conception and realization of sun tracking system of photovoltaic array in the south west Algerian

Application Note - How to Design a SolarEdge System Using PVsyst

Solar Cell Bypass Diodes in Silicon Crystalline Photovoltaic Panels

Simulation of Photovoltaic generator Connected To a Grid

EFFICIENT EAST-WEST ORIENTATED PV SYSTEMS WITH ONE MPP TRACKER

Application Note: String sizing Conext CL Series

High Resolution Spatial Electroluminescence Imaging of Photovoltaic Modules

K.Vijaya Bhaskar,Asst. Professor Dept. of Electrical & Electronics Engineering

Maximum power point tracking techniques for solar water pumping systems

Maximum power point tracking using a fuzzy logic control scheme

PERFORMANCE OF MPPT CHARGE CONTROLLERS A STATE OF THE ART ANALYSIS

Stand Alone PV System Sizing Worksheet (example)

Designing PV Plants Optimised for Economic Efficiency

Design qualification and type approval of PV modules acc. to IEC 61215:2005 / IEC 61646:2008

APPLICATION NOTE TESTING PV MICRO INVERTERS USING A FOUR QUADRANT CAPABLE PROGRAMMABLE AC POWER SOURCE FOR GRID SIMULATION. Abstract.

INVERTER WITH MULTIPLE MPP TRACKERS: REQUIREMENTS AND STATE OF THE ART SOLUTIONS

Professional Simulation Programmes. Design and Optimization

SOLAR ChARge CONTROLLeRS

Gross/Active PV Surface Area: ,40 / ,29 m². Energy Produced by PV Array (AC):

O&M Service for Megasolar Power Plants and Precise Monitoring Techniques for PV Modules

Zero voltage drop synthetic rectifier


BJT AC Analysis. by Kenneth A. Kuhn Oct. 20, 2001, rev Aug. 31, 2008

Design qualification and type approval of PV modules

Design and realization of a photovoltaic system equipped with the analogical and digital MPPT command for better exploitation of solar energy

AN ULTRA-CHEAP GRID CONNECTED INVERTER FOR SMALL SCALE GRID CONNECTION

Application Note, V1.0, 2008 AN Thermal equivalent circuit models. replaces AN Industrial Power

Lab 7: Operational Amplifiers Part I

Training Systems for Renewable Energies. Acquiring Practical Skills and Project-oriented Expertise

JSI Series Single Phase String Inverter. Features. Typical Efficiency Curve JSI-1500TL JSI-2000TL JSI-2500TL

SolarMax P series The power package for residential solar plants

12 SOLAR PHOTOVOLTAIC POWER SUPPLY SYSTEMS by John Ware. PV modules are current-limiting

fuse.on Technical background information provided by SIBA: Know-how on Electrical Fuses

Virtual Laboratory for Study of Renewable Solar Energy

New Energy Lab. Experiment Guide. New Energy Lab - Experiment Guide 1

Solar Energy Conversion using MIAC. by Tharowat Mohamed Ali, May 2011

Improved incremental conductance method for maximum power point tracking using cuk converter

What are the basic electrical safety issues and remedies in solar photovoltaic installations?

ABB central inverters PVS to 1000 kw

Photovoltaic Solar Energy Unit EESFB

THE SUPERFLEX DESIGN OF THE FRONIUS SYMO INVERTER SERIES

Photovoltaic System Overcurrent Protection

Modeling of Photovoltaic Cell Using Free Software Application for Training and Design Circuit in Photovoltaic Solar Energy

Solar radiation and ambient temperature effects on the performances of a PV pumping system

Solar energy Solar technology in endurance testing

/ The personal storage solution for 24H Sun. / Dynamic Peak Manager. / Smart Grid Ready THREE-PHASE

Solar Matters III Teacher Page

Auburn University s Solar Photovoltaic Array Tilt Angle and Tracking Performance Experiment

T :: T :: T ::

400KHz 60V 4A Switching Current Boost / Buck-Boost / Inverting DC/DC Converter

SOLAR RADIATION AND YIELD. Alessandro Massi Pavan

A Stable DC Power Supply for Photovoltaic Systems

SOLAR PHOTOVOLTAIC ENERGY GENERATION AND CONVERSION FROM DEVICES TO GRID INTEGRATION HUIYING ZHENG SHUHUI LI, COMMITTEE CHAIR

MAKING MODERN LIVING POSSIBLE. UniLynx Indoor User Manual. ULX 1800i ULX 3000i ULX 3600i ULX 5400i SOLAR INVERTERS

Your Sharp system will be supplied with one of the following sets of panels:

Photovoltaic String Inverters and Shade-Tolerant Maximum Power Point Tracking: Toward Optimal Harvest Efficiency and Maximum ROI

KADUNA CLINICS SOLAR SYSTEMS PERFORMANCE TESTING

Design and implementation of a modified DC- DC converter suitable for renewable energy application

Modular I/O System Analog and Digital Interface Modules

Fronius IG Plus. The next generation grid-connected PV inverter

DC To DC Converter in Maximum Power Point Tracker

PSIM Tutorial. How to Use Solar Module Physical Model Powersim Inc.

Effect of Ambient Conditions on Thermal Properties of Photovoltaic Cells: Crystalline and Amorphous Silicon

SOLAR ELECTRIC MODULE ES-124 & ES-62T Owners Manual and Installation Guide

Solar Energy Systems. Matt Aldeman Senior Energy Analyst Center for Renewable Energy Illinois State University

Power Supplies. 1.0 Power Supply Basics. Module

Replacing Fuel With Solar Energy

White Paper SolarEdge Three Phase Inverter System Design and the National Electrical Code. June 2015 Revision 1.5

2.06. Version. Kinglong New Energy Technology Co.Ltd. Sunteams 1500 Sunteams Sunteams 4000 Sunteams 5000

IKS. Profi. Photovoltaic Trainingsystem for vocational and advanced training. Photovoltaik

Photovoltaic solar systems

DARK CURRENT-VOLTAGE MEASUREMENTS ON PHOTOVOLTAIC MODULES AS A DIAGNOSTIC OR MANUFACTURING TOOL

Application of photovoltaic s in the building and construction industry as a power generating facility

INSTRUCTION MANUAL. SIGNAL AMPLIFIER 4-20 ma

Photovoltaic (PV) Energy as Recharge Source for Portable Devices such as Mobile Phones

Performance of Single Crystal Silicon Photovoltaic Module in Bruneian Climate

SHARP SOLAR Frequently Asked Questions for PV Integrators Revised 05/04/2010

INVERTER SYSTEM PRODUCT BROCHURE

Everline Module Application Note: Round LED Module Thermal Management

Technical Information Battery Management of the Sunny Island Gentle charging control for lead-acid batteries based on current state of the battery

SUNNY TRIPOWER 5000TL 12000TL

PVWATTS DERATING FACTORS FOR SOLARBRIDGE PANTHEON MICROINVERTERS AND ACPV SYSTEMS

How To Make A Fronius Cl Power Inverter

A Photovoltaic Array Simulation Model for Matlab-Simulink GUI Environment

PV module safety qualification according to IEC 61730:2004 EN 61730:2007

Errors Due to Shared Leadwires in Parallel Strain Gage Circuits

Renewable Energy Test Station (RETS) TEST PROCEDURES FOR SOLAR TUKI

Design of Grid Connect PV systems. Palau Workshop 8 th -12 th April

YSmart Technology Co.,Ltd

Photovoltaic Systems II EE 446/646

Design, Analysis, and Implementation of Solar Power Optimizer for DC Distribution System

LONGTERM EXPERIENCE WITH PV POWER PLANTS IN GERMANY

Transcription:

Rev. Energ. Ren. : Power Engineering (2001) 93-99 Shading Effects on Output Power of Grid Connected Photovoltaic Generator Systems R. E. Hanitsch, Detlef Schulz and Udo Siegfried Technical University Berlin Institute of Electrical Power- and Automation Technology Sec. EM 4 Einsteinufer 11 D-10587 Berlin Germany Abstract the quality of power supply from photovoltaic generators is very sensitive to shading effects of single or multiple cells. The energy yield of a partly shaded photovoltaic system is much lower than we could assume from the mean solar irradiance. Therefore we have to optimise the module structure and to select the right type of maximum power point tracking system in combination with the solar inverter. Résumé la qualité d une puissance électrique produite par un générateur photovoltaïque reste très sensible a l effet d ombre produit par une ou plusieurs cellules. Ainsi, dans un système photovoltaïque, le rendement énergétique produit par ce phénomène d ombre est beaucoup plus faible par rapport a l irradiance solaire moyenne. C est pourquoi, nous devons optimiser la structure du modèle et choisir le système de poursuite et de mesure de la puissance maximale en combinaison avec le convertisseur solaire. Keywords: Power supply Photovoltaic generators Shading effects Solar irradiance. 1. INTRODUCTION From case studies it is known that PV systems with the same nominal power generate quite different energy yields due to different shading patterns. The typical problems are: - reduction of power output: As the insolation is reduced by shading we get a reduced photo current. Because of the series connection of all the cells the current for all the cells is reduced. - thermal stress on the module: Depending on the level of shading, the PV generator circuit and the load the voltage of shaded cells might reverse. In this case they operate in the blocking state as a resistive load. The losses in the individual cell can increase the cell temperature dramatically and overheating might occur. Inhomogenities of the cell might result in hot spots, local defects due to high temperatures. In order to overcome some of the problems related to shading, by-pass-diodes are connected parallel to a number of solar cells. Under normal operating conditions the diodes are blocked compared to the voltage generated by the cells. When shading occurs the reversal of the voltage can be observed in that specific section and now the by-pass diode in parallel will conduct the current. The results are: - The current of the unshaded section flows through the by-pass diode and the power/voltage characteristic shows a second local maximum - The shaded cell is only loaded with that fraction of power produced by the remaining unshaded cells of that section - When the number of cells which are bridged by the by-pass diode is not too high, the level of the breakthrough voltage will not be reached. But there are also some draw backs resulting from the by-pass diodes: - higher cost for the module production and assembly problems of the by-pass diodes. - losses in the by-pass diode in the case of shading - matching problems between the solar inverter and the photovoltaic generator because of the second local power maximum might not be included in the range of operation of the inverter. Two inverters were available for grid connected PV systems which were taylored to operate on different voltage levels. For the investigation we used two types of which the data are given in Table 1. 93

94 R.E.Hanitsch et al. Table 1: Inverter parameters Parameter Type A Type B input voltage in V input current in A U max in V nominal power in W 54-98 125-500 35 (max) 3-8 110 500 1740 1600 For the photovoltaic generator a number of 70 W modules were used and the circuit was designed to match with the inverter requirements [1]. The arrangement of the modules is shown in Fig. 1 and the details of the generators can be taken from Tables 2 and 3. Fig. 1: Circuits of PV generator Table 2: PV Generator data Inverter Strings Modules/String Number of modules Type A 5 4 20 Type B 1 20 20 Table 3: PV Generator details Inverter P n in W U MPP in V I MPP in A U o in V I SC in A U max in V Type A 1400 66.8 21 84.4 22.5 95.2 Type B 1400 334 4.2 422 4.5 476

UPEC : Shading Effects on Output Power of Grid Connected Photovoltaic Generator 95 2. MODELLING The classical one-diode model of the solar cell is not sufficient to handle problems of shade on cells. Therefore the model was extended, now including also the negative section of the diode characteristic. The well known equation is modified to: I = Iphoto IS U + I R m U U + I R S S exp 1 T b( U I RS ) RP n U + I RS + 1 (1) U Bt with U bt n m R S U break through voltage (- 10... - 50 V) exponent (1... 10) diode factor series resistor output voltage B I S U T R P I correction factor saturation current temperature voltage: U T = k T/e parallel resistor output current We measured the dark characteristic and realised that in the blocking state the voltage is often larger than 10 V. In combination with the resulting current the losses can be quite high. Fig. 2 shows the complete characteristic. 8 A cell current 4 2 0-18 -16-14 -12-10 -8-6 -4-2 0 V 2-2 -4-6 cell voltage Fig. 2: Complete characteristic The incomplete I-U-characteristic of 35 cells under full insolation and one cell shaded with only 50 % of the insolation is shown in Fig. 3. A characteristic of one cell (E=100%) module current characteristic of 35 cells (E=100%) short circuit current of cell (E=50%) part of characteristic of shaded cell (50%) module voltage V Fig. 3: Incomplete module characteris tic

96 R.E.Hanitsch et al. Taking into account the shaded area the final type of characteristic is given in Fig. 4. The power loss cannot be ignored. Fig. 4: Module characteristic with one cell shaded (50 %) What is the effect of by-pass diodes over 18 cells? Based on the by-pass diode characteristic we obtain a modified I-U-characteristic which is depicted in Fig. 5. Beside the simulation work also measurements were done for different levels of shade on cells of a module. From Fig. 5 it is already obvious that in this case we have a power versus voltage characteristic with two maximums. A characteristic without shade module current characteristic with shade (50%) and by-pass diode module voltage V Fig. 5: Module characteristic with one cell shaded (50%) and two by-pass diodes Fig. 6 and Fig. 7 give an example of measured characteristics showing that the first and second maximu m can be found over a wide voltage range. The power at maximum power point (MPP) for unshaded conditions is about 53 W. The power drops to 38 W in the case of 50 % shaded area just for one cell. In the case of two cells and the same conditions the first maximum is at 20 W while the second is close to 33 W. A small shaded area results in a dramatic loss of power [2]

UPEC : Shading Effects on Output Power of Grid Connected Photovoltaic Generator 97 Fig. 6: Measured module characteristic no shade module power W 1 cell under shade 2 cells under shade module voltage V Fig. 7: Measured power versus voltage 3. GRID COUPLED PV SYSTEMS Grid coupled PV systems are also characterised by the solar inverter, including the MPP tracker, between the grid and the module array. Before switching on the system the PV generator is in no-load mode. As soon as the inverter is feeding into the grid the voltage drops and approaches the MPP-voltage. Once the controller has reached that point only small oscillations around the MPP can be observed. In the case of poor insolation and therefore modest currents the controller will provide a fixed voltage level below MPP voltage. If the voltage drops further, e.g. due to high ambient temperature or less effective cooling, below a set-point the inverter will cut off the grid and the PV generator is in no-load conditions again. 4. PATTERN OF SHADE As a new parameter to describe the level of shading of a cell we used the following definition: ( c,shaded ) S = 1 E / E (2) c

98 R.E.Hanitsch et al. For an average insolation of 700 W/m² on the shaded cell, we get for 1000 W/m² on the unshaded cells a shade parameter of S c = 0.3. The effect of shade on the performance of a PV generator depends on influences such as: - reduction of insolation (as average value) - distribution of the shade on the PV generator (geometry of shade) - modules with or without by-pass diodes - circuit design of PV array (series connection, or strings in parallel). Experimental investigations and simulations were done for a variety of pattern of shade, e.g. simulations were done for S c = 0.3, 0.5 and 0.7. Fig. 8: Example of shade pattern We focused on shade pattern on 4, 8, 12, and 16 cells for: a) single string of modules for inverter type B b) two strings for inverter type A c) four strings for inverter type A An illustration example is given in Fig. 8. Shade pattern b) was realised by shading a single cell under each of the by-pass diodes for one module and this was repeated for a specific number of modules. For case c) all the four modules of a string had one cell shaded and this lay out was repeated for the other strings, as shown in Fig. 8. 5. POWER REDUCTION For the series connection of the modules and inverter type B and S c = 0.7 we measured a loss of power of about 10 % when four cells were shaded. The losses increased to 59 % for 12 and 16 cells under shade. For the five strings in parallel and inverter type A and again S c = 0.7, but only four strings shaded we found interesting results. The lower MPP can reach 27 % of power losses while the upper MPP may show a reduction of 46 %. This can be observed when 12 or even 16 cells are shaded.

UPEC : Shading Effects on Output Power of Grid Connected Photovoltaic Generator 99 In addition voltage drops occur up to 50 % and also a voltage increase above U MPP of about 20 % was found. The temperature influence was also analysed because beside the STC temperature of 25 C the voltage for - 10 C and + 60 C is of interest: U MPP, ϑ = U MPP, STC + ( 25 ϑ) RTCV (3) For inverter type A the U MPP will vary between 77.6 V (- 10 C) and 56.0 V (60 ) and for inverter type B we calculated 388 V (- 10 C) and 280 V (60 C). 6. CONCLUSIONS Beside insolation and temperature also the pattern of shade has a big influence on the position of maximum power point. Shade pattern may result in two MPP s and the voltage U MPP can increase above U MPP,STC or drop below. However, the voltage U MPP should always be within the range of operation of the inverter. The actual working point of the inverter is also a function of the shade distribution which will change with the position of the sun. If we switch on an already shaded PV system connected to an inverter the working point will be the upper MPP although this is not the real MPP. If the MPP-voltage operation range is selected too narrow the lower MPP might be outside the range for higher temperature and shaded cells. In this case the controller will operate always with the upper MPP resulting in reduced energy yield. REFERENCES [1] SOLON AG, Manual NEG 1600+ (1999) [2] V. Quaschning, Simulation der Abschattungsverluste bei solarelektrischen Systemen, Diss. TU Berlin, Verlag Dr. Köster (1996)